Datasheet Spsa-V01

Download as pdf or txt
Download as pdf or txt
You are on page 1of 11

981-991-SPSA 2012.9.

7 5:6 PM 페이지981 한국원색인쇄사

Pressure Switch

● Digital Pressure Sensor


Series SPSA 983
● Micro Vacuum Sensor
Series SPSB 992
● Auto Switch 994
● Compatible Pressure Switch
Series SPS 1002

※ Specifications in this catalogue may be changed for product performance upgrade without notice.
Inquiries can be made to the manufacturer when purchasing the product.

981
www.TPCpage.com
www.TPCpneumatics.com
981-991-SPSA 2012.9.7 5:6 PM 페이지982 한국원색인쇄사

Digital Pressure Switch

Series SPSA
Various output modes(6Type) :
Hysteresis mode
Automatic Sensitivity Setting mode
Change of Analog ▶ Individual 2 output mode
Output Scale ▶ ▶ Window Comparative output mode


High Accuracy Semi

High Brightness Red LED


Conductor Pressure Sensor
(LED Digit : 9.5mm)

Selectable Response Time


Convertible Pressure Unit (Chattering Prevention
kPa, Mpa, ㎏f/㎠, bar, psi, Function of Output)
㎜Hg, inHg, ㎜H2O 2.5ms, 5ms, 100ms, 500ms

Precision measurement of Pneumatic Pressure in Piping and Pneumatic products is necessary and

in being used in Industrial Progress, Inspection Progress, Control & Analysis Equipments.

Digital Sensors of TPC can effectively protect equipments by extraordinary pressure control

from various unstable factors such as supply pressure, flow, ambient temperature change etc.

Digital Sensors of TPC furnish the most stable conditions with high accuracy and precision control.

982
981-991-SPSA 2012.9.7 5:6 PM 페이지983 한국원색인쇄사

Series SPSA SPSA


Digital Pressure Sensor SPSB

Auto
Swtch
HIGH ACCURACY SEMI CONDUCTOR SPS
PRESSURE SENSOR
HIGH BRIGHTNESS RED LED.(DIGIT:9.5MM)
CONVERTIBLE PRESSURE UNIT
VARIOUS OUTPUT MODES
CHATTERING PREVENTION FUNCTION
OF OUTPUT
ANALOG OUTPUT(1-5VDC)
CURRENT PROTECTION CIRCUIT, REVERSE
POWER POLARITY PROTECTING CIRCUIT

How to order
Model Output
SPS A V 01 P SPS : Pressure Sensor
Body Type
Blank : NPN Open Collector Output
P : PNP Open Collector Output

1 2 3 4 5 6 A : Square(30mm×30mm) Port Size


Pressure Blank : Rc(PT)1/8
Type Range of Rating Pressure
U : NPT1/8
01 0~100kPa(14.5psi) Option
1 0~1000kPa(145psi) Blank : With Bracket(Bracket A, B)
V01 -101.3~0kPa(-14.7~0psi) C : Panel Mounting Bracket(PSO-01)
C01 -100.0~100kPa(-14.5~14.5psi)
D : Panel Mounting Bracket
※ Blank : Standard pressure
V : Negative pressure(Vacuum) +Front Protection Cover(PSO-01+ PSO-02)
C : Vacuum, Low pressure

Pressure and Max. pressure display range


Pressure type kPa kgf/Cm2 bar psi mmHg inHg mmH2O
Negative 0~-101.3 0~-1.034 0~-1.034 0~-14.70 0~-760 0~-29.9 0~-103.4
pressure (5.0~-101.3) (0.051~-1.034) (0.05~-1.034) (0.72~-14.70) (38~-760) (1.5~29.9) (5.1~103.4)
0~100.0 0~1.020 0~1.020 0~14.50 - - -
Standard (-5.0~110.0) (-0.051~1.122) (-0.050~1.100) (-0.72~15.90)
pressure 0~1000 0~10.20 0~10.20 0~145.0 - - -
(-50~1013) (-0.51~11.22) (-0.50~11.00) (-7.2~159.0)
※( ) is Max. pressure display range.
※mmH2O Unit : Displayed pressure numberX100

Input conversion chart

from to Pa kPa MPa kgf/Cm2 mmHg mmH2O psi bar inHg


1kPa 1000.000 1 0.001000 0.010197 7.500616 101.9689 0.145038 0.010000 0.2953
1kgf/Cm2 98069.10 98.06910 0.098069 1 735.5787 10000.20 14.22334 0.980691 28.95979
1mmHg 133.3220 0.133322 0.000133 0.001359 1 13.5954 0.019336 0.001333 0.039370
1mmH2O 9.80665 0.00980 - 0.000099 0.0735578 1 0.00142 0.000098 0.002895
1psi 6894.939 6.89493 0.00689 0.070307 51.71630 703.07 1 0.068947 2.036074
1pa 100000.0 100.0000 0.100000 1.019689 750.062 10196.89 14.50339 1 29.52998
1inHg 3386.388 3.386388 0.003386 0.034530 25.40000 345.3240 0.491141 0.033863 1
Ex) Calculate 760mmHg as Pa unit.
: According to above chart, 1mmHg is 0.133322kPa, therefore 760mmHg will be 760x0.133322kPa=101.32472kPa.

Please read“Caution for your safety”in operation manual before using.

983
www.TPCpage.com
www.TPCpneumatics.com
981-991-SPSA 2012.9.7 5:7 PM 페이지984 한국원색인쇄사

Series SPSA
Specifications

Gauge pressure
Pressure type
Nagative pressure type Standard pressure type Vacuum, Low Pressure Type
NPN SPSA-V01 SPSA-01 SPSA-1 SPSA-C01
Model
PNP SPSA-V01P SPSA-01P SPSA-1P SPSA-C01P
Rated pressure range 0.0~-101.3kPa(0.0~-14.7psi) 0.0~100.0kPa(0.0~14.5psi) 0.0~1,000kPa(0.0~145psi) -100.0~100kPa(-14.5~14.5psi)
5.0~-101.3kPa -5.0~110.0kPa -5.0~1,100kPa -101.3~110kPa
Display pressure range
(0.72~-14.7psi) (-0.72~15.9psi) (-7.25~159.5psi) (-14.7~15.9psi)
Max. oressyre rabge 2 times of rating pressure 1.5 times of rating pressure 2 times of rating pressure
Fluid Air, Non-corrosive gas
Power supply 12~24VDC±10%(Ripple P-P : Max. 10%)
Current consumption Max. 50mA
Control output ・NPN open collector output ☞Load current : Max. 100mA, Load voltage : Max. 30VDC, Residual voltage : Max. 1V
・PNP open collector output ☞Max. sink current : Max. 100mA, Residual voltage : Max. 2V
Hysteresis 1digit(2digit/psi) fixed 2digit/psi fixed
Repeat error ±0.2% F・S ±1digit ±0.2% F・S ±2digit
Response time Selectable 2.5ms, 5ms, 100ms, 500ms
Short circuit protection Built-in
・Output voltage:1V-5VDC±2% F.S. ・Resolution:Approx. 1/200 ・Span:Within 4VDC ±2% F.S.
Analog output
・Zero point:Within 1VDC±2% F.S. ・Linear:Within ±2% F.S. ・Output impedance:1kΩ
Display method 3 1/2 digit LED 7Segment
Min. display interval 1 digit(2digit/psi) 2digits
Display kPa, kgf/Cm2, bar, psi kPa, kgf/Cm 2
, bar, psi
kPa, kgf/Cm2, bar, psi
Pressure unit mmHg, mmH2O, inHg mmHg, mmH2O, inHg
Characteristic of control
Max. ±1% F.S. Max. ±2% F.S.
output and displayed temp
Analog output temper-
Max. ±2% F.S. (25℃(77℉) standard)
ature characteristic
Ambient temperature -10℃ to ±50℃(14~±122℉)(at non-dew status)
Environment

Storage temperature -20℃ to ±60℃(-4~±140℉)(at non-freezing status)


Ambient humidity 35 to 85% RH
Storage humidity 35 to 85% RH
Vibration 1.5mm ampltude at frequency of 10 to 55Hz in each of X, Y, Z directions for 2 hours
Meterial Front case : PC, Rear case : PC(Insert glas), Presure port : die-cast(Zn)
Protection structure IP40(IEC standard)
Cable 5P, Ø4, Length : 2m(0.2mm2)
Acquirement standard
Weight Approx. 120g(4.23ozs)
※Weight : Without box
※F.S. : Full Span
※(*1) Output operating, hysteresis is adjustable in F-1 mode
※(*2) ±1% F.S. or less (25℃)

Analog output voltage-Pressure characteristic Analog output voltage linear

Output Output
voltage voltage
(V) (V)
Full Scale

Pressure(kPa) Pressure(kPa)

984
981-991-SPSA 2012.9.7 5:7 PM 페이지985 한국원색인쇄사

Series SPSA
Dimensions SPSA

Product (Unit : mm) SPSB

Auto
Swtch

SPS

Atmospheric pressure inflow hole Pressure port : 2-M3


PT 1/8×7L hexagon wrench bolt

PT 1/8×7L

Fixed Bracket Dimensions


●Bracket A ●Bracket B

Panel Mounting Bracket Dimensions


●Accessory(Option) ●Accessory:front protection
Cover(Option)

Mounting
PSO-03 PSO-02
Bracket
PSO-03 ●Panel cut-out

Front
Protection
Cover
PSO-02
(Panel thickness
0.8mm to 3.5mm)
When putting on front Cover
●Bracket-A ●Bracket-B

※ Bracket- A / B : SPSA only.

985
www.TPCpage.com
www.TPCpneumatics.com
981-991-SPSA 2012.9.7 5:7 PM 페이지986 한국원색인쇄사

Series SPSA
Input/Output circuit and connection diagram

NPN open collector output type PNP open collector output type

※There is no over current protection circuit in analog voltage output type. Do not connect this unit to power source or capacitive load directly.
※Please observe input impedance of connected equipment when using analog voltage output and be sure with voltage drop by resistance of extended wire.

Front panel identification and function

2 output indicator(Red) : Output 2 is ON, LED will be ON


Mode key : Parameter setting mode or preset setting mode, save setting value
Up key : Set the setting value to upper step in preset setting or pressure unit, output
mode, response time, analog output scale, key lock, peak hold value, bottom hold
value display in parameter setting.
Down key : Set setting value to lower step in preset setting or pressure unit, output
mode. response time, analog output scale, key lock, peak hold, bottom hold display
in parameter setting.
3 1/2 LED display(Red) : Display detected pressure, every setting value and display error Range of rating pressure : It is possible to change the pressure unit in Pressure
1 output indicator(Red) : Output 1 is ON, LED will be ON sensor. Please use different unit as labeled for your application.

Setting

Zero point adjustment

1. In state of atmospheric pressure during RUN mode, press Key and Key at the same If excute Zero point when external pressure has been
time for over 1 sec. applied, will be flashing. Please execute Zero
2. When the zero point adjustment is completed, it will display zero(0.0, 0.00, 0.000) and return to point again in state of atmospheric pressure.
RUN mode automatically. ※Please execute Zero point adjustment regularly.

986
981-991-SPSA 2012.9.7 5:7 PM 페이지987 한국원색인쇄사

Series SPSA
Setting parameter SPSA

SPSB

Auto
Swtch

and previous unit will flicker by turning on.(0.5sec.) Select the unit with SPS
key.(Pressing key momentarily, the unit will be saved, than move
to the next mode)
●Negative pressure type :

●Standard pressure type :

and previous output operation mode will flicker by turning on.(0.5sec.)


Select the output operation mode with key.
(Pressing Key momentarily, the output operation mode will be saved, then move to the next mode.)

and the previous response time will flicker by turning on.(0.5sec.)


Select the response time with key.
(Pressing Key momentarily, the response time will be saved, then move to the next mode.)

and the previous pressure will flicker by turning on.(0.5sec.)


Set the pressure which will output 1VDC with key.
Allowable Setting range : Min. value of rating pressure ≤ ≤90% of rating pressure

and the previous pressure will flicker by turning on.(0.5sec.)


Set the pressure which will output 5VDC by key.
Allowable Setting range : +10% of rating pressure ≤ ≤Max. value of rating pressure

and the previous key lock will flicker by turning on(0.5sec.)


Select key lock with key.

※Key protections
: Unable to change preset value and Parameter value(Enable Key protection)
: Able to change Preset value, Unable to change Parameter value
: Able to change Preset value and Parameter value(Key protection off)
※When entering into Parameter setting mode and preset setting mode, it displays“Setting item”and“Previous setting value”
by 0.5sec. turn.
This display will stop by pressing or Key(Display setting value), if no key touched for over 1 sec., it will display old value by 0.5sec. turn again.
※If no key touched for 60sec. during setting, it will display previous setting value not current setting.
※Please check preset value again when changing the output mode.
※If changing pressure display unit, preset setting value will be changed automatically.
※There is memory retention by EEPROM, but life cycle of EEPROM is 100,000 times.

987
www.TPCpage.com
www.TPCpneumatics.com
981-991-SPSA 2012.9.7 5:7 PM 페이지988 한국원색인쇄사

Series SPSA
Preset value setting

Hysteresis mode(F-1) and 1 independent(F-3,F-4,F-5) output mode

press one time press one time press one time


RUN mode

Press Display alternates by 0.5sec. Display alternates by 0.5sec.


Key in Run mode. Set the pressure Select the pressure detection level
detection level 1 by 2 by key.
key. Allowable setting range:
Allowable setting range: ・Hysteresis mode:Min. value of
Min. Value of setting setting pressure ≤ St2 < St1
pressure < St1≤ ・2 independent output mode:
Max. value of setting Min. value of setting presssure
pressure < St2 ≤ Max. value of
setting pressure.
Automatic sensitivity setting mode(F-2)

press one press one press one


time press one time
time time
RUN mode

Press Display alternates by 0.5sec. Display alternates by 0.5sec. Display alternates by 0.5sec.
Key in Run mode.
After applying After applying SET value will be
St1 in to St2 in to calculated automatically
Pressure port, Pressure port, and fine adjustment is
then press then press available between St1
Key. Key. and St2 by key.
(Able to Set Allowable Setting Range : SET = St1+St2
repeatedly by key) St1+1% of Setting Pressure≤St2 2
≤Max.Value of Setting Pressure Adjustable Range of Set Value :
between St1 and St2
Window (F-6)

press one time press one time press one time


RUN mode

Press Display alternates by 0.5sec. Display alternates by 0.5sec.


Key in Run mode.
Set Low setting value by Set High setting value by
key. key.
Allowable setting range: Allowable setting range:
Min. setting pressure ≤ Lo < Lo < Hi ≤
Max. value of setting pressure Max. value of setting pressure
•Please check the preset value again when changing output operation mode.
•When changing the display unit, preset value will be calculated according to the dissplay unit.
•If no key is touched for 60sec., it will return to RUN mode. [automatic sensitivity setting mode(F-2) is exception]
•Whenever a key is touched one time, 2digits increased(decreased) but it will be continuously increasing(decreasing) by pressing key constantly.

Peak hold and Bottom hold


1. Press for more than 3sec. in RUN mode.
2. and memorized max. pressure(Negative type is for max. vacuum pressure) will flicker by turning on(0.5sec.)
3. and memorized min. pressure(Negative type is for min. vacuum pressure) will flicker by turning on(0.5sec.)
then display Bottom hold value.
4. If press Key one time shortly, memorized Peak hold and Bottom hold value will be removed then return to RUN mode.
※ When the Peak hold and Bottom hold value is over the max. display pressure value, it displays , On the opposite, it displays .

988
981-991-SPSA 2012.9.7 5:7 PM 페이지989 한국원색인쇄사

Series SPSA
Output operation mode SPSA

1. Hysteresis mode(F-1) SPSB


Pressure Auto
※It can be set for pressure detection level(St1) and detection difference(St2) Swtch
※St1 setting range : Min.value of specified prssure ≤ St1 ≤
Max.value of specified pressure SPS
St2 setting range : Min.value of specified pressure ≤ St2 < St1
Time •OUT 1 : When applying pressure larger than St1, it will be ON.
•OUT 2 : When applying pressure lower than St2, it will be ON.

※This function is to set pressure detection level to the proper


2. Automatic sensitivity setting mode(F-2)
position automatically, it is set by received pressure from two
Pressure position(St1, St2)
※SET value will be calculated as below.
(St1 + St2)
SET value =
2
•OUT 1 : When applying pressure larger than SET value, it will be ON.
•OUT 2 : When applying pressure between St1 and St2, it will be ON.
Time Note1) If there is not enough difference between St1
and St2, will be displayed.
Please set again after applying enough pressure.
Note2) For fine adjustment for detection level, adjust detection
level(SET) by Key.
3. Independent 2 output mode(F-3, F-4, F-5)
(Adjustment range : Between St1 and St2)
Pressure ※St1 and St2 can be set independently within specified pressure
range.
※One is for control, the other is for alarm or optional control.
※St1 setting range : Min.value of specified pressure ≤ St1 ≤
Max. value of specified pressure
St2 setting range : Min.value of specified pressure ≤ St2 ≤
Time Max. value of specified pressure

●2 Independent output mode(F-3)


Mode
•OUT 1 : It will be ON, when it is beyond St1.
•OUT 2 : It will be ON, when it is beyond St2.
●2 Independent opposite mode(F-4)
Mode •OUT 1 : It will be OFF, when it is beyond St1.
•OUT 2 : It will be OFF, when it is beyond St2.
●2 Independent cross mode(F-5)
•OUT 1 : It will be OFF, when it is under St1.
Mode
•OUT 2 : It will be ON, when it is under St2.

4. Window mode(F-6)
Pressure ※Set Lo/Hi-limit value of pressure detection level in this mode.
※Lo setting range : Min.value of specified presssure ≤ Lo ≤
Max.value of specified pressure
Hi setting range : Lo< Hi ≤ Max.value of specified pressure

•OUT 1 : It will be ON between High limit value(Hi) and Low limit value (Lo)
Time
•OUT 2 : It will be ON when it is beyond High limit value(Hi) and Low limit
value (Lo)

989
www.TPCpage.com
www.TPCpneumatics.com
981-991-SPSA 2012.9.7 5:7 PM 페이지990 한국원색인쇄사

Series SPSA
Function

1. Change of display unit 8. Error

SPSA-V01(P) and SPSA-C01(P) has 7 kinds of pressure


Error display Problem Remedy
units. SPSA-01(P) and SPSA-1(P) has 4 kinds of pressure
units. Please select the proper unit for application. If external pressure applied, Piease try again after
•SPSA-V01(P), SPSA-C01(P) : kPa, kgf/㎠, bar, psi, mmHg, when adjusting Zero point external pressure removing
inHg, mmH2O When overloaded on
Remove overload
•SPSA-01(P), SPSA-1(P) : kPa, kgf/㎠, bar, psi control output
When the setting value is not Set proper setting value after
matched with setting condition checking setting condition
2. Change of output mode
When the applied pressure exceeds
There are 6 kinds of control output mode in order to the upper display pressure range up Apply pressure within
realize the various pressure detection. Select a mode for
When the applied pressure exceeds display pressure range
your proper application.
the lower display pressure range down
•Hysteresis mode(F-1) : Change hysteresis for detecting
pressure.
•Automatic sensitivity setting mode(F-2) : Set cletection Installation
sensitivity automatically at proper position.
1. When installing the pressure port
•Indepentent 2 output mode(F-3, F-4, F-5) : Detect
it is able to bring pressure from
pressure from two positions with one product.
3 directions by changing the
•Window comparative output mode(F-6:) : Detect pressure
mounting direction of the
in certain areas.
pressure port.
2. Pressure port is PT1/8 and it is able
3. Change of response time(Chattering prevention)
to use general one touch fittings.
It can prevent chattering of the control output by changing response
3. Please use seal tabe at port plug
time. It is able to set 4 kinds of response times(2.5ms, 5ms, 100ms,
in order to prevent pressure leak.
500ms) and if the response time is getting longer, the detection will be
more stable by increasing the number of the digital filter. 4. Please block another two pressure
Spring washer
ports not used with port plugs. Hexagon
Port plug wrench bolt
4. Change of Analog output scale 5. Please connect it by using
spanner(13mm) at the metal part in
Change properly for user a application. It setting A1 position for 1VDC output and order not to overload the body
A5 position for 5VDC output, the pressure range of A1 to A5 is to 5VDC analog when connecting one touch fittings. 13mm spanner

output. Therefore analog output will be 1-5VDC between A1 and A5.

5. Key lock function The tightening torque of one touch


This unit has 2 kinds of key lock functions in order to prevent wrong operation. fitting should be Max 10N・m.
•Loc : All keys are locked. It is impossible to change any
parameter setting preset, Zero point adjustment, Peak hold 6. SPSA series has 2kinds of Spring washer

and Bottom hold.(Able to change the status of lock) brackets so it is able to install
•PA.L : This is partial locked status, it is impossible to change parameter two different ways.
setting(Able to change the status of lock) only, the rest of the functions
7. At first, please unscrew hexagon
can be changed.
wrench bolt and assemble the Hexagon
•UnL : All of the setting are available, all keys are unlocked. wrench bolt
bracket on this unit by fixing the
hexagon wrench bolt.
6. Zero point adjustment function In this case, tightening torque of
Set the display value pressure as Zero point forcibly. hexagon wrench should be max. 3N・ Panel bracker
m. (PSO-01)

Body
7. Peak hold and Bottom hold function 8. Bracket(PSO-01) and front
(SPSA)
Protection
cover
Diagnosis malfunction of the system caused by parasitic protection cover(PSO-02) are (PSO-02)
pressure or check through memorizing the max. /min, optional to sell. Please see the
Bracker panel
pressure occurring from the system. pictures for installation.

990
981-991-SPSA 2012.9.7 5:7 PM 페이지991 한국원색인쇄사

Series SPSA
Accessories SPSA

SPSB
•Pressure unit label
Auto
Swtch

SPS

•Port Plug •Bracket A •Bracket B

Caution for using

1. Do not insert any sharp or pointed object into pressure port.


It may cause mechanical trouble due to sensor damage.
2. This unit must avoid direct contact with water, oil, thinner etc.
3. Be sure to avoid transient time(within 3sec.) after initial power on. Switching

4. When a switching moving regulator is used for the power regulator

supply, the frame ground(F.G) terminal of the power supply


Ground
must be grounded.
5. When moving this unit from a warm place to a cold place,
please remove the humidity on the cover.
6. Do not press the setting button with sharp or pointed object.
7. Do not put over 30N tensile strength on connection part or load.
8. When using mmH2O unit, please multiply display value by 100.

※ Malfunctions may occur if the above instructions are not


followed.

991
www.TPCpage.com
www.TPCpneumatics.com