SIPROTEC 7UT86 Profile
SIPROTEC 7UT86 Profile
SIPROTEC 7UT86 Profile
www.siemens.com/siprotec
Description
The SIPROTEC 7UT86 transformer differential protection
has been designed specifically for the protection of three-
winding transformers (3 sides). It is the main protection
for the transformer and contains many other protection
and monitoring functions. The additional protection func-
tions can also be used as backup protection for subse-
quent protected objects (such as cables or lines). In this
process, you are also supported by the modular expanda-
bility of the hardware. The device supports all SIPROTEC 5
system characteristics. It enables upgradeable system
solutions with high investment security and low operating
costs. With its modular structure, flexibility and the power-
ful DIGSI 5 engineering tool, SIPROTEC 7UT86 offers fu-
ture-oriented system solutions with high investment secu- SIPROTEC 7UT86 Transformer Differential
rity and low operating costs. Protection (1/2 device = standard variant P1)
• Universal usability of the permissible measuring • Extensive cyber security functionality, such as role-
points based access control (RBAC), protocolling security-
related events or signed firmware
• Applicable from average up to extra-high voltage
• Simple, quick and secure access to device data via a
• Protection of standard power transformers, auto
standard Web browser – without additional software
transformers and motors
• Frequency tracked protection functions over a wide
• Typical properties of a transformer differential protec-
frequency range (10 Hz to 80 Hz) and the option to
tion such as flexible adaptation to the transformer
assign the protection functions in a single device to
vector group, control of inrush and overexcitation
different frequency tracking groups.
processes, safe behavior in case of current-
transformer saturation with different degrees of satu- • Phasor measurement unit (PMU) for synchrophasor
ration measured values and IEEE C37.118 protocol
• Adaptive adaptation of the operate curve to the trans- • Powerful fault recording (buffer for a max. record
former tap position time of 80 sec. at 8 kHz or 320 sec. at 2 kHz)
• Increased sensitivity with near-neutral-point ground • Auxiliary functions for simple tests and commission-
faults through a separate restricted ground-fault pro- ing
tection
• Flexibly adjustable I/O quantity structure within the
• Additional current and voltage inputs can be supple- scope of the SIPROTEC 5 modular system
ments for standard protection functions, such as
overcurrent, voltage frequency, etc. Benefits
• Graphical logic editor to create powerful automation • Safety due to powerful protection functions
functions in the device • Data security and transparency over the entire lifecy-
• Arc protection cle of the plant, saving time and money
• Voltage controller function ANSI 90V for two-winding • Increased reliability and quality of the engineering
transformers, three-winding transformers and grid process
coupling transformers with parallel control (mas- • Highest availability even under extreme environmen-
ter/follower, circulating reactive current minimization)
tal conditions by “conformal coating“ of electronic
• Up to 4 pluggable communication modules, usable for boards
different and redundant protocols (IEC 61850,
• Cyber security in accordance with NERC CIP and BDEW
IEC 60870-5-103, IEC 60870-5-104, Modbus TCP,
Whitepaper requirements
DNP3 serial and TCP, PROFINET IO)
• Full compatibility between IEC 61850 Editions 1 and 2
• Reliable data transmission via PRP and HSR redundan-
cy protocols