BUSBAR
Technology and Solutions
Protection and Substation Automation
PROTECTION
APPLICATION
BASICS 2
BBP_basics_2 / 2002-03-15 / RW
© ABB Switzerland Ltd. - 1
ABB
Topic Objectives
Objectives
r CB close command
ABB
Busbar Zones & Protection Zones
BBP_basics_2 / 2002-03-15 / RW
© ABB Switzerland Ltd. - 3
BB1 BB2
BBP_basics_2 / 2002-03-15 / RW
© ABB Switzerland Ltd. - 4
BB1 BB2
BBP_basics_2 / 2002-03-15 / RW
© ABB Switzerland Ltd. - 5
BB1 BB2
Þ NO TRIP !
BBP_basics_2 / 2002-03-15 / RW
© ABB Switzerland Ltd. - 6
BB1
Þ TRIP
BB 2
BBP_basics_2 / 2002-03-15 / RW
© ABB Switzerland Ltd. - 7
BB1
BBP_basics_2 / 2002-03-15 / RW
© ABB Switzerland Ltd. - 8
ABB
Single Busbar with Section Coupler (2 coupler CTs)
5000A 4400A
Fault condition II BB2
BB1
Þ TRIP
BB 1
&
BB 2
BBP_basics_2 / 2002-03-15 / RW
© ABB Switzerland Ltd. - 9
0A 0A 0A 0A 0A 0A
ABB
Single Busbar with Section Coupler (1 coupler CT)
BB1 BB2
© ABB Switzerland Ltd. - 11
BBP_basics_2 / 2002-03-15 / RW
ABB
Single Busbar with Section Coupler (1 coupler CT)
+200A to Zone 1 positive
Load conditions - 200A to Zone 2 negative
BB1 BB2
the coupler current is
added to both systems,
Þ NO TRIP !
© ABB Switzerland Ltd. - 12
BBP_basics_2 / 2002-03-15 / RW
BB1
Þ TRIP
BB 2
© ABB Switzerland Ltd. - 13
BBP_basics_2 / 2002-03-15 / RW
BB1
© ABB Switzerland Ltd. - 14
BBP_basics_2 / 2002-03-15 / RW
ABB
Single Busbar with Section Coupler (1 coupler CT)
5000A
Fault condition II BB2
BB1
Þ TRIP
BB 2
© ABB Switzerland Ltd. - 15
BBP_basics_2 / 2002-03-15 / RW
BB1
© ABB Switzerland Ltd. - 16
BBP_basics_2 / 2002-03-15 / RW
???
BBP_basics_2 / 2002-03-15 / RW
ABB
Coupler functions I
Þ by deactivating of the
current measurement in the
coupler in case of internal
BBP tripping signal
(= coupler blocking)
© ABB Switzerland Ltd. - 18
BBP_basics_2 / 2002-03-15 / RW
ABB
Coupler functions I
trip from
BBP ³1
³1 t
&
Current signal to
~120 ms measurement
system
Input
Current
signal
© ABB Switzerland Ltd. - 19
BBP_basics_2 / 2002-03-15 / RW
ABB
Coupler functions I
5000A start CB
Fault condition II reclaim time BB2
BB1
Þ TRIP
BB 2
© ABB Switzerland Ltd. - 20
BBP_basics_2 / 2002-03-15 / RW
BB1
Þ TRIP
BB 1
the coupler current is switched off
after the CB reclaim time
© ABB Switzerland Ltd. - 21
BBP_basics_2 / 2002-03-15 / RW
0A 0A 0A 0A 0A 0A
ABB
Coupler functions II
5000A 4400A
Fault condition II BB2
BB1
Þ TRIP
BB 1
&
BB 2
© ABB Switzerland Ltd. - 23
BBP_basics_2 / 2002-03-15 / RW
???
ABB
Coupler functions II
Þ by deactivating of the
current measurement in the
coupler in case of an open
CB
(= coupler blocking)
© ABB Switzerland Ltd. - 25
BBP_basics_2 / 2002-03-15 / RW
ABB
Coupler functions II
trip from
BBP ³1
³1 t
CB open
&
Current signal to
~120 ms measurement
system
Input
Current
signal
© ABB Switzerland Ltd. - 26
BBP_basics_2 / 2002-03-15 / RW
ABB
Coupler functions II
5000A
Fault condition III BB2
BB1
Þ TRIP
BB 1
the coupler current
is switched off
since the coupler
CB was opened !
© ABB Switzerland Ltd. - 27
BBP_basics_2 / 2002-03-15 / RW
ABB
Coupler functions II
What advantage and what
disadvantage will result for the
system by connecting the CB
auxiliary contacts
???
(concerning the main requirements on
protection systems: DEPENDABILITY;
© ABB Switzerland Ltd. - 29
BBP_basics_2 / 2002-03-15 / RW
SECURITY;SPEED; SENSITIVITY;
SELECTIVITY)
ABB
Coupler functions II
Þ the selectivity in
case the CB is
already open and
selectivity
the fault occurs
speed
will be increased
dependability
Þ the tripping speed in case of a fault between
coupler CB and CT will be increased (in case of a
coupler with only one CT)
© ABB Switzerland Ltd. - 30
BBP_basics_2 / 2002-03-15 / RW
ABB
Supervision of Circuit Breaker (& Isolator) Position
Isolator) Position
BBP_basics_2 / 2002-03-15 / RW
ABB
Supervision of Circuit Breaker (& Isolator) Position
Supervision
CB closed
=1
isolator alarm
CB open
³1 t
switching
=1 prohibited
© ABB Switzerland Ltd. - 33
BBP_basics_2 / 2002-03-15 / RW
ABB
Supervision of Circuit Breaker (& Isolator) Position
circuit ???
BBP_basics_2 / 2002-03-15 / RW
ABB
Supervision of Circuit Breaker (& Isolator) Position
ABB
Supervision of Circuit Breaker (& Isolator) Position
Memory of the position in case of missing aux. supply
S
internal:
CB closed
CB closed
& R
CB open
R
internal:
CB open
S
© ABB Switzerland Ltd. - 36
BBP_basics_2 / 2002-03-15 / RW
ABB
Supervision of Circuit Breaker (& Isolator) Position
A undefined CB / isolator
position will generate 2
alarms: isolator alarm &
switching prohibited! Why
switching prohibited
???
© ABB Switzerland Ltd. - 37
BBP_basics_2 / 2002-03-15 / RW
ABB
Supervision of Circuit Breaker (& Isolator) Position
ABB
Supervision of Circuit Breaker (& Isolator) Position
How is it possible to
de- block the system
???
© ABB Switzerland Ltd. - 39
BBP_basics_2 / 2002-03-15 / RW
ABB
Supervision of Circuit Breaker (& Isolator) Position
ABB
Supervision of Circuit Breaker (& Isolator) Position
“Accept isolator alarm”
CB closed
=1
isolator alarm
CB open
³1 t switching
prohibited
=1 blocking
& (optional)
accept
S
“isolator alarm”
© ABB Switzerland Ltd. - 41
BBP_basics_2 / 2002-03-15 / RW
isolator alarm
R
ABB
Supervision of Circuit Breaker (& Isolator) Position
ABB
Supervision of Circuit Breaker (& Isolator) Position
ABB
Supervision of Circuit Breaker (& Isolator) Position
ABB
Supervision of Circuit Breaker (& Isolator) Position
ABB
CB / isolator auxiliary circuits
ABB
Supervision of Circuit Breaker (& Isolator) Position
ABB
CB / isolator auxiliary circuits
Phase Phase
+ +
NO aux.
R
contacts
R S T
S
CB closed
T protection
system
CB open
NC aux.
contacts
© ABB Switzerland Ltd. - 48
BBP_basics_2 / 2002-03-15 / RW
ABB
CB auxiliary circuits
ABB
CB auxiliary circuits
Þ BBP “sees” an internal fault because
one current is not yet measured
CB open !!!
current not
ABB
measured !!!
Supervision of Circuit Breaker (& Isolator) Position
ABB
© ABB Switzerland Ltd. - 52
BBP_basics_2 / 2002-03-15 / RW
CB auxiliary circuits
???
How can this be avoided
ABB
CB auxiliary circuits
ABB
CB auxiliary circuits
Phase Phase
+ +
CB closing NC aux.
R
coil contacts
R S T
S
CB closed
T protection
system
CB open
NC aux.
contacts
CB (manual)
© ABB Switzerland Ltd. - 54
BBP_basics_2 / 2002-03-15 / RW
close command
CB close
order
+
ABB
Supervision of Circuit Breaker (& Isolator) Position
Memory of the position in case of missing aux. supply
CB closing
command
S
internal:
CB closed ³1
CB closed
& R
CB open
R
internal:
CB open
S
© ABB Switzerland Ltd. - 55