Andover Continuum Cyberstation: Hvac Essentials Guide
Andover Continuum Cyberstation: Hvac Essentials Guide
Andover Continuum Cyberstation: Hvac Essentials Guide
Product Names are trademarks of TAC. All other trademarks are the property of their re-
spective owners.
Revision: A
The information in this document is furnished for informational purposes only, is subject
to change without notice, and should not be construed as a commitment by TAC. TAC as-
sumes no liability for any errors or inaccuracies that may appear in this document.
TAC, LLC
One High Street
North Andover, MA 01845
(978) 975-9600
Fax: (978) 975-9782
http://www.tac.com
Andover Continuum CyberStation
HVAC Essentials Guide
30-3001-1000
Revision A
September, 2008
Contents
6 TAC
About Alarm-Enrollment Objects ............................... 80
Create an Alarm-Enrollment Object .......................... 80
General Expressions for Security ............................... 82
About Attaching Alarms to Objects ............................ 84
Attach an Alarm-Enrollment to a Door ...................... 84
Attaching Alarms to a Point ....................................... 85
Using the Alarms / Advanced Alarms
Tab of an Object Editor ............................................... 86
More about Alarms ...................................................... 92
Task 12: Configure Video Layouts ............................................. 93
Create a VideoServer Object ....................................... 93
Create a VideoLayout Object ...................................... 94
Add a VideoLayout to an Object ................................. 95
More about Video ......................................................... 97
Task 13: Create Graphic Panels and Controls .......................... 98
About Graphic Controls for Access Control ................ 98
Create a Graphics Panel and a Door Control ............. 99
More about Graphics Panels and Controls ................ 102
Task 14: Configure Reports ........................................................ 103
About Report Objects ................................................... 103
Create a Report ............................................................ 103
More about Reports ..................................................... 107
8 TAC
About this Manual
Related Documentation
For additional or related information, refer to these documents.
10 TAC
About this Manual
Symbols Used
The Notes, Warnings and Cautions used in this manual are listed
below.
CAUTION or WARNING
Type of hazard
How to avoid hazard.
Failure to observe this precaution can result in injury or equipment
damage.
DANGER
ELECTRIC SHOCK HAZARD
How to avoid hazard.
Failure to observe these instructions will result in death or serious
injury.
12 TAC
Chapter 1: Getting Started
Chapter 1
Getting Started
14 TAC
Chapter 1: Getting Started
The following issues for this sample site determine the HVAC devices
that are needed and the configuration of the system.
z For the main warehouse how can the humidity be monitored and
regulated?
z How will the freezer temperature be monitored and maintained at a
constant below freezing temperature?
z How will the office be monitored and regulated separate from the
other two areas?
The following illustration shows the same floor plan, with HVAC
devices in place.
16 TAC
Chapter 1: Getting Started
18 TAC
Chapter 1: Getting Started
Single-User Configuration
20 TAC
Chapter 1: Getting Started
Multi-User Configuration
Network Controllers
z bCX1 Series
Infinet bCX1
BACnet bCX1
z NetController II series
z ACX (57xx)
All are Ethernet TCP/IP compatible. The first four contain at least one
Infinet port to allow communication with Infinet application
controllers.
The bCX1 series is a series of Infinet and native BACnet routers and
controller/routers. The bCX1 Infinet device functions as a Ethernet-to-
Infinet field bus router. The bCX1 BACnet devices function as BACnet/
IP-to-MS/TP field bus routers.
The NetController II and ACX (57xx) are powerful CPUs with flash
EPROM, providing the central network management functions for
Andover Continuum building automation system. These network
controllers can be connected to individual IOU modules via a different
proprietary RS-485 protocol called ACC-LON.
22 TAC
Chapter 1: Getting Started
Infinet Controllers
BACnet Controllers
Workstations
Networks
24 TAC
Chapter 1: Getting Started
Expansion
Type Function
Module
Universal xPUI4 4-Channel Universal Input
Module
xPBD4 * 4-Channel Universal Input and
4-Channel Digital Output Module
xPBA4 * 4-Channel Universal Input and
4-Channel Analog Output Module
Input xPDI8 8-Channel Digital Input Module
Output xPAO2 2-Channel Analog Output Module
xPAO4 4-Channel Analog Output Module
xPDO2 2-Channel Relay Output Module
xPD04 4-Channel Digital Relay Output
Module
Display xP Display Internal Mounted Keypad/
Display Module (920 only)
xP Remote Display Externally Mounted Keypad/
Display Module
Note: * These modules (xPBD4 and xPBA4) can only be used to expand
the I/O of bCX1 series controllers.
CyberStation Software
CyberStation
26 TAC
Chapter 1: Getting Started
Database
Objects
Attributes
28 TAC
Chapter 2: Configuring an HVAC System
Chapter 2
Configuring an HVAC
System
30 TAC
Chapter 2: Configuring an HVAC System
2. Select one of the three choices from the drop down menu.
32 TAC
Chapter 2: Configuring an HVAC System
Create a Network
When you configure an HVAC network, the first object you create is the
network itself.
1. In Continuum Explorer, right click Root, select New, and then
select Network.
2. Enter a name for the network for Object Name, and click the
Create button.
The UTC offset is the difference between your local time and
Greenwich Mean Time (GMT). Enter - if local time is behind GMT.
4. Click OK.
IP Address: 169.254.1.1
Subnet Mask: 255.255.0.0
Prior to changing these values, the PC being used to commission the
controllers must be configured to communicate with the controllers.
The setup values are:
IP Address: 169.254.1.(191-254)
Subnet Mask: 255.255.255.0
1. From Microsoft Internet Explorer, in the Address field, enter the
controller’s default IP address.
Username: acc
Password: acc
4. Select OK.
34 TAC
Chapter 2: Configuring an HVAC System
IO Configuration
Comm4 Port Line
8. Select Submit to Controller.
Note: Once you have finished commissioning your controller, your PC’s
IP address and Subnet Mask value can be returned to their
normal settings.
Create a Controller
Note: Before performing this procedure, you must first install the
controller, connect it to your Ethernet network, and then
commission the controller. Refer to “Web Configuration for
Controllers” on page 34.
1. In Continuum Explorer, right click the network object, select New,
and then select InfinityController.
2. Enter a controller name for Object Name, and click the Create
button.
7. Click Apply.
8. Select the General tab, and then click the Teach button.
36 TAC
Chapter 2: Configuring an HVAC System
Note: To confirm that the Comm Status is online, click the Refresh
button.
10. Click OK to close the InfinityController editor.
38 TAC
Chapter 2: Configuring an HVAC System
Use the General tab to enter basic information about the IOU module.
Description The description is optional, but a good description of
the IOUModule object helps others when they need
to test, modify or manipulate the network. To enter
a description, type up to 32 characters (including
spaces) in the text field.
For example, enter Fan Control for a DO4
IOUModule object.
IOU Number Enter the IOU number here. You must manually
assign a unique number (between 1 and 32) for each
IOU module on a network controller.
Physically label the IOU modules with the numbers
you assign. This number is not the same as the 12-
digit module ID # assigned to the individual module
at the factory.
You will use this number when you configure points
on this controller.
Model The model number identifies the type of the
Number IOUModule and is read from the module.
Comm This displays Online or Offline, depending on
Status whether the controller is in communication with the
module.
Module ID These TAC-assigned numbers appear after the
and Learn process. The only time you will need these
Program ID numbers is when speaking to a TAC Support
Representative. These numbers will help our staff to
answer your questions. You may manually enter the
Module ID number in this field, (if you know it),
rather than following the Learn process.
Learn Use the Learn button to commission the IOU
module on the network. See “Commissioning an
IOU Module” on page 42 later in this chapter.
40 TAC
Chapter 2: Configuring an HVAC System
See the following topic and its associated topics in the CyberStation
online help:
42 TAC
Chapter 2: Configuring an HVAC System
2. Comm Port objects appear in the list of objects in the viewing pane.
Double click the CommPort class folder under the controller.
5. Click OK.
See the following topic and it’s associated topics in the CyberStation
online help:
z “CommPort Editor”
In the General tab, enter basic information about the comm port.
Note: When Infinet or Wireless is selected in the Default Mode
field, another tab, Field Bus Controllers, appears. See “Field Bus
Controllers Tab – CommPort Editor” on page 51.
Description Type in a description for the comm port. You can use
up to 32 alphanumeric characters. This attribute is
optional, but providing a good description can aid
other users.
Comm Port The CommPort attribute displays the number of the
Number comm port(s) you are editing.
44 TAC
Chapter 2: Configuring an HVAC System
The following table briefly describes each comm port default mode.
NetController II 9680
The following table lists the default mode (and other modes available)
for the NetController II model 9680.
46 TAC
Chapter 2: Configuring an HVAC System
For a complete list of default modes for each comm port on each
controller, see the following CommPort associated topics in the
CyberStation online help:
In the General tab, click the XDriver Status button to view the
status of the device that is using the XDriver. The XDriver Status
button displays the following read-only information:
Status Displays the status of the device, or
XdrvNotInstalled when no XDriver file
has been selected.
Error Displays the last error to occur on the
device.
Error Time Displays the time and date that the last
error occurred on the device.
Error Count Displays the number of errors that have
occurred on the device since you last set it to
zero. Increments to 255 errors and remains
set at 255 until you reset it to zero by
clicking the Reset Count button.
48 TAC
Chapter 2: Configuring an HVAC System
The Settings tab is where you view or edit the communications speed
and ‘handshaking’ settings for the mode that you have chosen for the
port.
Depending on which Default Mode you select on the General tab, some
of the attributes on this tab may be disabled (appear gray).
Baud Rate The baud rate is the speed, measured in bits per
second, at which the controller sends
information to the device that you are
connecting to the comm port. Select the baud
rate required by the equipment connected to
this port.
Track CXD This option monitors a communications carrier
detect signal called CXD. When selected, it
enables the controller to detect when
communication with connected objects has been
lost.
Depending on your modem configuration, the
CXD (sometimes called DCD) signal (pin 8 on an
RS-232 connector) is asserted “high” when the
communications link is established between
modems. Once the carrier signal is lost, CXD
goes “low.” Track CXD looks for the high-to-low
transition and makes the controller reset this
comm port to its default mode. Track CXD
“cleans up” the comm port by logging off the last
user. Track CXD is selected by default, and it is
required for comm ports that are connected to
modems. If Track CXD is not selected, the
controller cannot respond to the loss of the CXD
signal.
Flow Control The flow control type determines how the comm
port handles the flow of data between the
controller and its attached device (usually a
printer, modem, or terminal). This process is
also known as “handshaking.”
Select one of the following options from the
dropdown menu:
z NoFlowControl: Select this flow control
type if you do not want to regulate the flow
of information between the controller and its
attached printer, modem, or terminal.
Without a flow control type, buffers that
hold data that is being transmitted or
received could overflow, and some data could
get lost.
z CtsRts: This flow control type uses
hardware signals to send “clear to send”
(Cts) and “request to send” (Rts) messages.
Both of these messages must be
acknowledged by the controller and its
attached device before information can be
transmitted.
z XonXoff: This control flow type uses
software signals in the form of characters
that are sent as part of the data being
transmitted. When the controller or its
attached device detects that it has been sent
an Xon character, it makes itself available
to receive data. It considers all data received
after the Xon character as valid. When it
detects an Xoff character at the end of the
data steam, the controller or attached device
knows the transmission is complete.
z XonXoff CtsRts: This flow control type uses
both the software (XonXoff) and hardware
(CtsRts) handshake methods for regulating
the flow of information between the
controller and its attached device.
50 TAC
Chapter 2: Configuring an HVAC System
For more information about the Field Bus Controllers Tab, see the
following CommPort associated topics in the CyberStation online help:
z “CommPort Editor”
52 TAC
Chapter 2: Configuring an HVAC System
Points enable you to monitor and control HVAC events. You use these
points with schedules, alarms, and other objects to establish routine
HVAC routines and to respond to out-of-range HVAC events.
Supervised points can have one of three values: On, Off, or Trouble.
You create a supervised input point for each input (for example, from a
contact sensor) from the devices wired to channels at each controller in
your network.
1. In Continuum Explorer, right click the controller where you want
to create the point, select New, and then select InfinityInput.
2. Enter a point name for Object name, and click the Create button.
Andover Continuum CyberStation HVAC Essentials Guide 53
Chapter 2: Configuring an HVAC System
Leave the Value field at 0. The system updates the value with the
input from the associated controller channel.
54 TAC
Chapter 2: Configuring an HVAC System
Note: For a NetController II, the IOU menu is available. In this menu,
you must select the IO module or IOU board on the LBus that is
sending the input.
9. Click OK.
10. To set conversion options for the HVAC configuration, see “Setting
the Conversions Tab” on page 56.
The Conversions tab allows you to set conversions for input sensor
readings into engineering units. These input signals are converted to
temperatures, relative humidity and atmospheric pressure. The
readings are helpful when monitoring and regulating an HVAC system
in an area.
56 TAC
Chapter 2: Configuring an HVAC System
In the Logs tab, you define logs and extended logs for a point.
In the Logs tab, you define and activate two types of logs for a point.
z Logs: Stores log entries on the local controller that owns the point.
See “Logs” on page 59.
z Extended logs: Stores log entries that would otherwise be deleted
once the maximum number of local-controller log entries are filled.
When you activate extended logs, the additional "extra" entries are
transferred (uploaded) to a workstation's Continuum database, to
capture them before they are deleted in the controller. The
extended log, which is an extension of a log, continues recording
values where the log leaves off. It records values depending on how
58 TAC
Chapter 2: Configuring an HVAC System
you set up the short-term log. These extended log entries can be
uploaded from both local-area network (LAN) controllers and
remote-access services (RAS) network controllers to the
workstation. Extended logs work according to the attribute settings
on this tab, in addition to the extended-log settings in the General
Preferences dialog and on the Preferences tab of the Device
editor for a workstation.
Logs
Under the Logs section, in the Number of Entries field, enter the
number of entries you want stored in the log table. The maximum
number of entries allowed is dependent on the memory available on
your PC.
In the Type field, use the dropdown menu to view and select a log type.
The log types include:
z Manual: This type is not set by CyberStation and can only be set
from the Command Line, a report, or a Plain English program.
z loginstataneous: CyberStation stores the current value of this
point at the beginning of every interval.
z LogAverage: CyberStation calculates the average point value over
every interval using a weighted average algorithm. Average values
are stored at the end of every interval.
z LogMinimum: CyberStation compares all values over an interval,
finds the minimum and stores it at the end of every interval.
z LogMaximum: CyberStation compares all values over an interval,
finds the maximum and stores it at the end of every interval.
If the Type is not Manual, under the Interval section, set the
interval. This setting determines how often CyberStation stores new
values in the log. The following intervals are available:
Tip: In order to have a log updated at the same time every hour (such
as every quarter hour or every half hour) the interval must be
evenly divisible into one hour (for example, 1 minute, 2 minutes,
3 minutes, etc.).
If you select any other Type other than Manual, in the Extended
Logs section, you can activate the extended logs option. This log is an
extension of the short-term log stored in the controller, and continues
recording values into the database. The values are recorded in the
extended log, depending on how you set the short-term log. These
extended log entries can be uploaded from both LAN controllers and
RAS controllers to the CyberStation workstation.
60 TAC
Chapter 2: Configuring an HVAC System
The Triggers tab is where you associate triggers with a point. Triggers
are Plain English programs whose status changes to active when the
point value changes by at least the amount of the Threshold attribute
setting. One point may have numerous triggers associated with it.
Conversely, one program can be triggered by many points.
To delete an Infinity program from the trigger list, click it, then click
the Remove button.
2. Enter a point name for Object name, and click the Create button.
For example, define the meaning of the On value: “On = A/C Unit
Runs.”
Leave the Value field at 0. The system updates the value with the
input from the associated controller channel.
5. From the Elec Type drop down menu, select the appropriate
electrical type for the input.
8. Click OK.
62 TAC
Chapter 2: Configuring an HVAC System
z AnalogValue
z BinaryValue
z MultistateValue
Note: For third-party BACnet devices that become part of the Andover
Continuum system, AnalogValue, BinaryValue, and
MultistateValue objects are already created as objects on those
third-party BACnet controllers.
2. Enter a point name for Object name, and click the Create button.
For example, define the meaning of the On value: “On = A/C Unit
Runs.”
Leave the Value field at 0. The system updates the value with the
input from the associated controller channel.
64 TAC
Chapter 2: Configuring an HVAC System
Note: For third-party BACnet devices that become part of the Andover
Continuum system, AnalogOutput objects were already created
as objects on those third-party BACnet controllers. Therefore,
Continuum Explorer already lists these objects as
AnalogOutputs within third-party devices.
66 TAC
Chapter 2: Configuring an HVAC System
You create schedules in the controller where the schedule will be used.
(Later, you can use the Schedule editor’s Mass Create feature to copy
the schedule to other controllers in your network, if needed.)
Note: Before creating a schedule, you must create the points called for
in the schedule. See “Task 5: Create CyberStation Points” on
page 53.
1. In Continuum Explorer, right click the controller, select New, and
then select Schedule.
6. Check the Automatic Download check box, and select the day of
the week and the time you want CyberStation to download the
schedule to the controller.
68 TAC
Chapter 2: Configuring an HVAC System
7. Click OK.
Each week, at the day and time you selected in the schedule, this
workstation downloads the next seven days of the schedule to the
controller.
70 TAC
Chapter 2: Configuring an HVAC System
You can also specify the notification actions that occur when the
conditions that triggered the alarm return to normal.
Create an Event-Notification Object
72 TAC
Chapter 2: Configuring an HVAC System
6. Under Colors and Fonts, right click to select the colors and fonts
used to display the alarm in the Active Alarm View window and the
Alarm Status bar.
9. Select the check box next to each action you want the system to
take in notifying users of the alarm and the return to normal.
74 TAC
Chapter 2: Configuring an HVAC System
14. Click the check box next to the actions the workstation should take
if it receives notification during the times you selected.
To perform the action only Select the check box under Backup
if a repeat of the alarm has for the action.
occurred
17. Select when to remove the alarm from the Active Alarm View
window.
76 TAC
Chapter 2: Configuring an HVAC System
z This e-mail distribution list must be stored in the first address book
shown in the list of available address books in the e-mail client
application. For example, if you create an EventNotification
distribution list in the Personal Address Book in Microsoft Outlook,
then the Personal Address Book must be the first one showing in
the address list dropdown menu when you open the Address Book.
3. Select the entry type Personal Distribution List and add this
entry in the Personal Address Book.
4. In the Name field, enter a name for the distribution list using the
following format:
List
Format of List Name Example
Type
Note: Use the EventNotification object Name not the Alias, for
example, Critical Temp, not CriticalTemp.
6. Set address book options so that the address book where your
personal distribution lists are stored is the first one to be searched
when sending e-mails or pages. For example, in Microsoft
Exchange, select Options from the Tools menu. Click the
Addressing tab. When sending mail, check names using these
address lists in the following order area, use the Add button, then
the up or down arrow buttons to add the correct address book to
this field and position it at the top of the list.
An AlarmEnrollment object:
z Defines the conditions that your HVAC system uses to determine
that a point is in the alarm state
z Defines the conditions that the system uses to determine that the
point has returned to its normal state
z Contains the text messages that are displayed in the Active Alarm
View window or the Alarm Status bar
z Has an attached EventNotification object that defines how the
system responds to the alarm and notifies the appropriate people
You attach an AlarmEnrollment object to points, doors, and other
objects that you want to alarm.
Create an Alarm-Enrollment Object
2. Enter a name for the alarm (e.g., doorisajar), and click the
Create button.
78 TAC
Chapter 2: Configuring an HVAC System
You define the expression used to define the alarm condition in the
Algorithms tab. Most access control alarms use the Expression
alarm type.
6. Under Send, select the Alarm check box. If you want to be notified
at the return to normal, select this check box as well.
10. Enter the messages that you want to be displayed in the Active
Alarm View or the Alarm Status bar.
80 TAC
Chapter 2: Configuring an HVAC System
Use the Alarms tab (or Advanced Alarms tab) to browse for up to
eight AlarmEnrollment objects to attach to the point.
To attach an alarm to an object:
1. Click the browse button in one of the empty alarm fields.
2. Search and find the alarm you want.
3. Click the Select button.
4. Check the Enabled checkbox.
To delete an attached alarm, select its name in the text field and press
the Delete key on your keyboard.
82 TAC
Chapter 2: Configuring an HVAC System
Additional information you can add from the Alarms tab include the
following attributes:
SHOWREPORT: “C:\PROGRAM
FILES\CONTINUUM\REPORTS\SYSTEMCH
K.HTM”
84 TAC
Chapter 2: Configuring an HVAC System
86 TAC
Chapter 2: Configuring an HVAC System
A control panel can have one or more controls, or not controls at all.
88 TAC
Chapter 2: Configuring an HVAC System
Pinpoint has several dynamic controls that are intended for HVAC:
Control
Examples
Type
Control
Examples
Type
90 TAC
Chapter 2: Configuring an HVAC System
Other Pinpoint controls and tools let you customize the appearance and
operation of graphics panels as needed. For example:
z Use an image file of a floor plan as the panel background, and
arrange HVAC devices (such as thermostats or temperature
sensors) and areas (such as a freezer) based on the physical location
of the objects they represent.
z Use text, switch, button, and other controls to display information
or perform specific actions, such as opening a Listview window.
In a Report object, you specify the characteristics of the report that you
want to generate:
z The data included
z The report format (text, bar chart, pie chart, etc.)
z The output format, including whether the report is viewed on
screen, printed, or saved to a file
z Whether the report is generated automatically or manually
z Whether the report is automatically e-mailed to a list of recipients
Create a Report
3. Right click the folder, select New, and then select Report.
92 TAC
Chapter 2: Configuring an HVAC System
6. From the Report Type drop down menu, select a report type.
94 TAC
Chapter 2: Configuring an HVAC System
12. Select the Log Filter radio button, and select a predefined filter for
the time interval of the report.
13. Select the Path browse button, and locate and select the controller
with the objects that you want to include in the report.
14. Click the Add button to locate and select the objects in this
controller that you want to include in the report.
16. Options in this tab allow you to define the output format.
19. Click the View Report button to generate the report and display
the content in the Report Viewer window.
20. Click the close button to close the Report Viewer window.
96 TAC
Chapter 2: Configuring an HVAC System
98 TAC
Chapter 3: Monitoring a Building Control System
Chapter 3
Monitoring a Building
Control System
Responding to Alarms
When you configure alarms, you typically specify that an alarm
message be displayed at one or more CyberStation workstations. At a
workstation, alarm messages appear either in the Alarm Status bar or
in the Active Alarm View window, depending on settings in the
EventNotification object associated with the alarm.
The Active Alarm View window notifies you of alarms and provides
information about current alarm conditions. The window displays
automatically when an alarm occurs if you selected the Display Alarm
View option in the EventNotification object associated with the alarm.
100 TAC
Chapter 3: Monitoring a Building Control System
This window updates in real time as alarms occur, are responded to, or
the affected objects return to their normal state.
Use buttons to the left of the entries in the list to respond to alarm
notifications:
Button Description
See the “Active Alarm View” topic in the CyberStation online help.
102 TAC
Chapter 3: Monitoring a Building Control System
Using Groups
A Group is an object used to view a collection of like objects. Each group
has a list of objects known as members. Members are objects of any
class that are related (for example, Relative Humidity, Space
Temperature and Temperature Average).
Three Group views exist: the Member list view, Graph view and the
History view.
z Member list view displays the name, class and value of every
member object in the Group.
z Graph view — displays logged values for the selected member list
objects.
z History view — displays a list of all selected member list objects,
as well as their logged values over a particular period.
Use the Group editor to create a Group, build and modify its member
list, and configure the group’s graph and history views.
104 TAC
Chapter 3: Monitoring a Building Control System
ListView objects are highly customizable. Settings that you can define
include:
z “ListView Editor”
z “CyberStation Main Screen”
106 TAC
Chapter 3: Monitoring a Building Control System
Using Logs
A log is a collection of point values for an object. The structure of the log
(array) looks like a two-column table. The first column contains an
index of entry numbers. The second column contains the recorded
values. A log is especially helpful when tracking recorded values, such
as humidity level or the average temperature for an area.
From the Logs tab of the InfinityInput Editor and various other point
editors, you can define the type of log (Log or Extended Log), the
number of entries, type of log, and the time intervals for recording the
log.
For more information, see the Log topics in the CyberStation online
help or the “Setting the Logs Tab” on page 58
The BACnet controller obtains the value of the input by polling the
current value of the input. Once the controller obtains the current
value, it uses the PID algorithm to monitor the input. Based on the
monitored input, The PID algorithm determines the output value that
is assigned to the output reference or an object whose values control
items such as sensors and dampers.
The difference between the input value and the setpoint value is used
by the PID algorithm to adjust the output value.
The Tuning tab allows you to set and adjust the input value, output
value and setpoint value to your particular preferences.
108 TAC
Chapter 3: Monitoring a Building Control System
The General tab allows you to view and/or alter the current state of
the loop object.
110 TAC
Chapter 3: Monitoring a Building Control System
For more information see the “Loop Editor” topic in the CyberStation
online help.
112 TAC
Chapter 4: Advanced Configuration for HVAC Control
Chapter 4
Advanced Configuration for
HVAC Control
Note: For more information on the Plain English language refer to the
Andover Continuum CyberStation Plain English Language
Reference, 30-3001-872.
The Plain English language (PE) allows you to customize your HVAC
building automation systems in accordance with specific site
requirements. PE, which is similar to BASIC, is based on keywords
that provide a simple, the basic programming language to develop
programming statements and requires minimal programming
experience.
114 TAC
Chapter 4: Advanced Configuration for HVAC Control
z User objects
z Security group objects
z Security level objects
The security group assignments of each user determine the objects and
data the user can view and edit, and well as other actions they can
perform, such as deleting objects.
You can further define each user’s interaction with the CyberStation
application by specifying the following in User objects:
You use the Security editor to specify the privileges of each security
group. CyberStation provides 1024 security groups in which you can
define access privileges. By default, the Security editor displays the
first 128 of these.
Each column corresponds to one security group. The lock and key icons
indicate whether the security group has the access privilege ( ) or is
denied the privilege ( ).
Each column
corresponds to
one security
group. Move the
cursor over a
column to
display a tooltip
showing the
name of the
security group.
116 TAC
Chapter 4: Advanced Configuration for HVAC Control
An object, such as a
door, can have only
one SecurityLevel
object attached to it.
z “User Editor”
z “Security Editor”
z “SecurityLevel Editor”
z “ControllerUser Editor”
118 TAC
Andover Continuum CyberStation
HVAC Essentials Guide
Document Number 30-3001-1000
Revision A