The Sizing Boiler Feed Pumps Calculation
The Sizing Boiler Feed Pumps Calculation
The Sizing Boiler Feed Pumps Calculation
This will eliminate one of the biggest causes of pump problems and poor deaerator performance. If you use on-off pump
control to control the boiler water level the boiler is subjected to feedwater surges which are two to three times the peak
boiler capacity. On-off pump control results in:
We know that we need a pump which will produce at least 94 gpm. To compensate for minimum flow requirements we will
probably look for a pump with a capacity that is 10 to 20 gallons higher than the Net Pump Capacity. We must also consider
the minimum flow requirement of the pump if modulating feedwater control is used.
Minimum Flow – Minimum flow is the lowest flow rate at which there is sufficient flow thru the pump to allow it to operate
without damage caused by overheating. There are two minimum flow rates which are commonly referred to.
Instantaneous Minimum Flow – applies when it is impossible for the pump to operate with the feedwater control valve
closed.
1. Published by pump vendors
2. Requires the pumps be turned off when the boiler cycles off, (interlock to stop pump if burner stops)
Continuous Minimum Flow – applies when the pump may be required to operate “on the by-pass” when flow to the boiler
stops. Calculate Continuous Minimum Flow :
1. Determine Flow at peak pump efficiency
2. The continuous minimum flow is equal to 20% of the Flow at peak pump efficiency.
“ The total pump capacity must satisfy the boiler evaporation rate, the capacity required to catch up and the minimum
flow requirements of the boiler feed pumps
5. Provide for minimum flow protection for the boiler feed pumps.
Gross Pump Capacity = Net Pump Capacity + Minimum Flow Pump Protection: If the boilers use modulating feedwater control,
protection for the pumps is provided by recirculation of the minimum flow amount back to the deaerator to insure the pump
always has sufficient flow to prevent overheating during periods of low flow. Let’s assume this system will never operate with
the burner off or the feed water valve closed. As a result, we will use the instantaneous minimum flow for these pumps.
The conditions for the pump using the two previous examples are 94 gpm @ 462’ TDH. A review of the Industrial Steam pump
curves shows that the VC90 can make the 94 gpm capacity, but the NPSH is excessive, so we will review the next larger
pump. The VC100 will easily satisfy the flow requirement at a reasonable NPSH. The instantaneous minimum flow for the
VC100 is 13.5 gpm.