Inline Terminal With Two Analog Input Channels: Features
Inline Terminal With Two Analog Input Channels: Features
Inline Terminal With Two Analog Input Channels: Features
Edition 03
channels
1 Description
The terminal is designed for use within an Inline sta- This data sheet is only valid in associa-
tion. tion with the “Automation terminals of the
It is used to acquire analog voltage and current sig- Inline product range” application descrip-
nals. tion (DOK-CONTRL-ILSYSINS***-AW..-
EN-P, MNR R911317021).
Features
• 2 analog single-ended signal inputs for the con- Make sure you always use the latest doc-
nection of either voltage or current signals umentation.
• Connection of sensors in 2 and 3-wire technology It can be downloaded under
• Current ranges: 0 mA ... 20 mA, 4 mA ... 20 mA, www.boschrexroth.com/electrics.
±20 mA
• Voltage ranges: 0 V ... 10 V, ±10 V
• Channels are parameterized independently of
one another via the bus system
• Measured values can be represented in four dif-
ferent formats
• Resolution depends on the representation format
and the measuring range
• Process data update of both channels within a
max. of 1.5 ms
Datenblatt | R-IB IL AI 2/SF-PAC Bosch Rexroth AG 2/20
2 Table of contents
1 Description .............................................................................................................................. 1
2 Table of contents ..................................................................................................................... 2
3 Ordering data .......................................................................................................................... 3
4 Technical data ......................................................................................................................... 3
5 Additional technical data.......................................................................................................... 6
6 Tolerance data......................................................................................................................... 7
6.1 Tolerance and temperature response of the voltage inputs............................................................. 7
6.2 Tolerance and temperature response of the current inputs ............................................................. 7
6.3 Additional tolerances influenced by electromagnetic interference .................................................... 7
3 Ordering data
4 Technical data
136,8
119,8
71,5
Width 12.2 mm
Height 136.8 mm
Depth 71.5 mm
Note on dimensions Housing dimensions
General data
Color gray
Weight 69 g (with connector)
Operating mode Process data operation with 2 words
Ambient temperature (operation) -25 °C ... 55 °C
Ambient temperature (storage/transport) -25 °C ... 85 °C
Permissible humidity (operation) 10 % ... 95 % (non-condensing)
Permissible humidity (storage/transport) 10 % ... 95 % (non-condensing)
Air pressure (operation) 70 kPa ... 106 kPa (up to 3000 m above sea level)
Air pressure (storage/transport) 70 kPa ... 106 kPa (up to 3000 m above sea level)
Degree of protection IP20
Protection class III, IEC 61140, EN 61140, VDE 0140-1
Power consumption
Power consumption typ. 662 mW
max. 882 mW
Analog inputs
Number of inputs 2
Description of the input Single-ended inputs, voltage or current
Connection method Inline shield connector
Connection technology 2-wire, shielded
Current input signal 0 mA ... 20 mA, 4 mA ... 20 mA, -20 mA ... 20 mA
Voltage input signal 0 V ... 10 V, -10 V ... 10 V
Max. permissible current ± 100 mA (Current inputs)
A/D conversion time approx. 120 µs (per channel)
Measured value representation 16 bit two's complement
Data formats IB IL, IB ST, IB RT, standardized representation
Averaging Over 16 measured values (can be switched off)
Process data update < 1.5 ms (The time includes the internal firmware runtime and
the time for the analog-to-digital conversion. For system con-
siderations (e.g., for the step response determination of sen-
sors), please take into account additional times for latching and
bus transmission as well as the status of mean-value genera-
tion.)
Input resistance of voltage input > 220 kΩ
Input resistance current input 50 Ω (Shunt)
Limit frequency (3 dB) 40 Hz
Open circuit response Countering 0 V, 0 mA or 4 mA, an open circuit message is is-
sued in the process data from <3.2 mA in the measuring range
of 4 mA ... 20 mA
Permissible voltage max. ± 32 V (between analog voltage inputs and analog refer-
ence potential)
max. ± 5 V (between analog current inputs and analog refer-
ence potential, correspond to 100 mA through the shunts)
Datenblatt | R-IB IL AI 2/SF-PAC Bosch Rexroth AG 5/20
Analog inputs
Common mode voltage range 40 V (between current input and functional earth ground)
40 V (between voltage input and functional ground)
Common mode rejection (CMR) min. 90 dB (Current and voltage input)
typ. 110 dB (Current and voltage input signal, valid for ap-
proved DC common-mode voltage range)
Surge protection Suppressor diodes in the analog inputs
Approvals
For the latest approvals, please visit www.boschrexroth.com/electrics.
Datenblatt | R-IB IL AI 2/SF-PAC Bosch Rexroth AG 6/20
Mechanical tests
Shock in acc. with EN 60068-2-27/IEC 60068-2-27 15g load for 11 ms, half sinusoidal wave, three shocks per
space direction and orientation
25g load for 6 ms, half sinusoidal wave, three shocks per
space direction and orientation
6 Tolerance data
6.1 Tolerance and temperature response of the voltage inputs
The tolerance indications relate to the measuring range final value of 10 V.
Typical Maximum
Tolerance at 23°C
Tolerance through offset ±0.03% ±0.06%
Tolerance through gain ±0.05 % ±0.10%
Differential non-linearity ±0.10% ±0.20 %
Total tolerance ±0.15 % ±0.30%
Temperature and drift response (TA = -25°C ... +55°C)
Offset voltage drift TKVO ±6 ppm/K ±12 ppm/K
Gain drift TKG ±30 ppm/K ±50 ppm/K
Total voltage drift TKtot = TKVO + TKG ±36 ppm/K ±62 ppm/K
Total tolerance (tolerance through offset, gain, linearity, and drift) ±0.30% ±0.50 %
Typical Maximum
Tolerance at 23°C
Tolerance through offset ±0.03% ±0.06%
Tolerance through gain ±0.10% ±0.10%
Differential non-linearity ±0.10% ±0.30%
Total tolerance ±0.20 % ±0.40 %
Temperature and drift response (TA = -25°C ... +55°C)
Offset current drift TKIO ±6 ppm/K ±12 ppm/K
Gain drift TKG ±30 ppm/K ±50 ppm/K
Total current drift TKtot = TKIO + TKG ±36 ppm/K ±62 ppm/K
Total tolerance (tolerance through offset, gain, linearity, and drift) ±0.35 % ±0.60 %
Type of electromagnetic interference Typical deviation from the Typical deviation of the
measuring range final value measuring range final value
(voltage input) (current input)
Relative Absolute Relative Absolute
Electromagnetic fields EN 61000-4-3/ < ±2.0 % < ±200 mV < ±2.0 % < ±400 µA
IEC 61000-4-3
Fast transients (burst) EN 61000-4-4/ < ±1.0 % < ±100 mV < ±1.0 % < ±100 µA
IEC 61000-4-4
Conducted interference EN 61000-4-6/ < ±1.0 % < ±100 mV < ±1.0 % < ±100 µA
IEC 61000-4-6
Datenblatt | R-IB IL AI 2/SF-PAC Bosch Rexroth AG 8/20
5V I/O A
+5V 10 V interface
+10V B
µP 5V
10 V
Electrical isolation
REF between area
MUX
A and B
EEPROM
6
FE potential Analog
Inputs
Key:
Protocol chip
OPC
Optocoupler
Input amplifier
Coupling network
11 Connection notes
B
C
12 Connection examples
12.1 Connection of active sensors 12.3 Connecting a battery monitor
NOTE: Short-circuit
1.1 2.1 Both reference inputs (minus inputs) of
1.2 2.2
each terminal are connected to each oth-
er. If signal sources are connected in se-
1.3 2.3
ries, incorrect connections can lead to a
1.4 2.4
short circuit of individual signal sources.
• Observe the following connection ex-
ample for series connection.
+ - - +
2V 2V 2V 2V 2V 2V
12 V
IN
24 V
24 V
Function identification
Green
Datenblatt | R-IB IL AI 2/SF-PAC Bosch Rexroth AG 13/20
The terminal uses two words of IN process data and OUT00 OUT01
two words of OUT process data. Channel 1 Channel 2
Each channel is mapped to a word.
Assignment of the parameter words (OUT00 and
The analog values are transmitted via the input pro- OUT01)
cess data.
15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0
You can parameterize the terminal channel by chan-
nel via the OUT process data. Param- 0 0 0 0 0 Fil- 0 0 For- Measur-
eteriza- ter mat ing range
tion
14.1 OUT process data
You can parameterize each channel independently of
the other channels. Parameterize the first channel via Bit 15
the first output word (OUT0), and the second channel
via the second output word (OUT1). Code (bin) Parameterization
dec bin
The following parameterization options are available:
0 0 Default
• Selecting the measuring range according to the
1 1 Parameterization
input signal
• Switching off mean-value generation (filter) When bit 15 = 0, the preset (default) is active.
• Selecting the formats for representing measured In order to parameterize the terminal, set bit 15 to 1.
values
The parameterization is not saved. Transmit the pa- Bit 9 ... 8
rameterization in each bus cycle.
After applying voltage (power up) to the Inline station, Code Filter
the message "Measured value invalid" (error code dec bin
8004hex) appears in the process data input words. 0 00 16-sample mean-value (default)
After a maximum of one second, the preset parame- 1 01 No filter
terization is accepted and the first measured value is 2 10 Reserved
available. 3 11 Reserved
If you change the parameterization, the corresponding
channel is re-initialized. Bit 5 ... 4
The message "Measured value invalid" (error code
8004hex) appears in the process data output words for Code Format (data format)
maximum 100 ms.
dec bin
The following values are preset on the terminal: 0 00 IB IL (default) 15 bits + sign bit
Measuring range 0 V ... 10 V 1 01 IB ST 12 bits + sign bit
Mean-value generation 16-sample mean-value 2 10 IB RT 15 bits + sign bit
Format IB IL 3 11 Standardized 15 bits + sign bit
representation
You cannot switch the signal inputs via
See also Section "Measured value representation in
the OUT process data.
the different formats".
Select the current or voltage measure-
ment by applying the measuring signal at Bit 3 ... 0
the current or voltage input.
In addition, select the corresponding
Code Measuring range
measuring range via the OUT process
dec bin
data.
0 0000 0 V ... 10 V (default)
1 0001 -10 V ... +10 V
8 1000 0 mA ... 20 mA
9 1001 -20 mA ... +20 mA
10 1010 4 mA ... 20 mA
Other Reserved
Datenblatt | R-IB IL AI 2/SF-PAC Bosch Rexroth AG 14/20
15.1 IB IL format
The measured value is represented in bits 14 to 0.
An additional bit (bit 15) is available as a sign bit.
This format supports extended diagnostics. Values > 8000hex and < 8100hex indicate an error.
The error codes are specified in the section “Supported IB IL error codes and standardized representation”.
15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0
V Analog value
V Sign bit
15.2 IB ST format
The measured value is represented in bits 14 to 3.
An additional bit (bit 15) is available as a sign bit.
Bits 2 to 0 are measuring range and error bits.
IB ST format corresponds to the data format used on INTERBUS ST modules.
15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0
V Analog value 0/4 OC BÜ
V Sign bit
OC Open circuit
BÜ Overrange
0/4 4 mA ... 20 mA measuring range
15.3 IB RT format
The measured value is represented in bits 14 to 0.
An additional bit (bit 15) is available as a sign bit.
IB RT format corresponds to the data format used on INTERBUS RT modules.
Error codes and error bits are not defined in this data format. The positive final value 7FFFhex indicates an open
circuit.
15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0
V Analog value
V Sign bit
15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0
V Analog value
V Sign bit
15.5 Supported error codes for IB IL and standardized representation formats
In IB IL and standardized representation formats, a diagnostics code is mapped in the event of an error.
Code (hex) Cause
8001 Measuring range exceeded (overrange)
8002 Open circuit
8004 Measured value is invalid
8010 Configuration invalid
8020 Sensor and/or analog supply not present
8040 Device faulty
8080 Below measuring range (underrange)
15.6 Example
Measured value representation in different data for-
mats
Measuring range 0 mA ... 20 mA
Measured value 10 mA
Word x Channel
IN00 1
IN01 2
DOK-CONTRL-ILAI2/ Bosch Rexroth AG All rights reserved. No part of this document may be reproduced or stored,
SF***-KB03-EN-P Electric Drives and Controls processed, duplicated, or circulated using electronic systems, in any form or
Postfach 13 57 by any means, without the prior written authorization of Bosch Rexroth AG,
Electric Drives and Controls. Violations shall give rise to claims for damages.
97803 Lohr, Deutschland
The data specified above only serve to describe the product. They do not in-
Bgm.-Dr.-Nebel-Str. 2
dicate any specific condition or suitability for a certain application. It must be
97816 Lohr, Deutschland remembered that our products are subject to natural wear and ageing.
Tel. +49 9352 18 0
7545_en_02