Location via proxy:   [ UP ]  
[Report a bug]   [Manage cookies]                
0% found this document useful (0 votes)
132 views

Machine Foundation

This document summarizes the design calculations for the reinforcement of 4 concrete slabs. For each slab, it provides the load data, calculates the upward pressure, moments, and minimum steel requirements. It also checks that the punching shear stress is less than the allowable limit. All slabs are found to be safe based on the reinforcement provided.
Copyright
© © All Rights Reserved
Available Formats
Download as XLS, PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
132 views

Machine Foundation

This document summarizes the design calculations for the reinforcement of 4 concrete slabs. For each slab, it provides the load data, calculates the upward pressure, moments, and minimum steel requirements. It also checks that the punching shear stress is less than the allowable limit. All slabs are found to be safe based on the reinforcement provided.
Copyright
© © All Rights Reserved
Available Formats
Download as XLS, PDF, TXT or read online on Scribd
You are on page 1/ 4

Document No UH441_01853_MPE_A1

Revision No 00
Date 20-Apr-12
SI.no
1.0 Design Data
Static Load = 220 kN
Dynamic Load = 91.2 kN
Self Weight = 258.75 kN
Total Load(T.L) = 569.95 kN
Breadth = 4 m
Actual Depth = 0.45 m
Cover = 0.04 m
Effective depth(d) = 0.41 m
Area = 23 m2
2.0 Upward Pressure(U.P)
For Static Load(U.P) = S.L/Area
= 20.82 kN/m2
For Dynamic Load(U.P) = D.L/Area
15.22 kN/m2
For Total Load(U.P) = T.L/Area
24.79 kN/m2

3.0 Moment Calculation


Uniform Load(U.D.L) = U.PxWidth kN/m width=B/2
U.D.L = 49.58 kN/m
Effective Span(L) = 1.3 m
(+ve) Moment (wl2/8) = 10.48 kN.m
(-ve) Moment (wl2/10) = 8.38 kN.m
As per SP 16
Mu/bd2 for +ve moment = 0.07
2
Mu/bd for -ve moment = 0.05
From SP 16 Table 4
No value for 0.01, values from 0.3 so provide minimum Ast
Minimum Ast = 0.12%bD
= 540 mm2
= 565.20 mm2
Provided T12@200c/c & It is Found to be Safe
4.0 Check for Punching shear
Loading point
Breadth = 250 mm
Depth = 312 mm
Maximum force Vu = 569.95 kN

tv = 0.50 N/mm2
< 1.37 N/mm2
Hence Safe
Document No UH441_01853_MPE_A2
Revision No 00
Date 20-Apr-12
SI.no
1.0 Design Data
Static Load = 680 kN
Dynamic Load = 0 kN
Self Weight = 250 kN
Total Load(T.L) = 930 kN
Breadth = 3.65 m
Actual Depth = 0.445 m
Cover = 0.04 m
Effective depth(d) = 0.405 m
Area = 25 m2
2.0 Upward Pressure(U.P)
For Static Load(U.P) = S.L/Area
= 37.2 kN/m2
For Dynamic Load(U.P) = D.L/Area
0 kN/m2
For Total Load(U.P) = T.L/Area
37.2 kN/m2
< 300kN/m2

3.0 Moment Calculation


Uniform Load(U.D.L) = U.PxWidth kN/m width=B/2
U.D.L = 67.89 kN/m
Effective Span(L) = 3.35 m
(+ve) Moment (wl2/8) = 95.24 kN.m
(-ve) Moment (wl2/10) = 76.19 kN.m
As per SP 16
Mu/bd2 for +ve moment = 0.32
Mu/bd2 for -ve moment = 0.47
From SP 16 Table 4
pt = 0.082
pt = 100ast/bd
Ast =

Minimum Ast = 0.12%bD


= 534 mm2
= 678.24 mm2
Provided T12@200c/c & It is Found to be Safe
4.0 Check for Punching shear
Loading point
Breadth = 500 mm
Depth = 500 mm
Maximum force Vu = 930 kN

tv = 0.63 N/mm2
< 1.37 N/mm2
Hence Safe
Document No UH441_01853_MPE_A3
Revision No 00
Date 20-Apr-12
SI.no
1.0 Design Data
Static Load = 560 kN
Dynamic Load = 0 kN
Self Weight = 84 kN
Total Load(T.L) = 644 kN
Breadth = 1.4 m
Actual Depth = 0.286 m
Cover = 0.05 m
Effective depth(d) = 0.236 m
Area = 8.4 m2
2.0 Upward Pressure(U.P)
For Static Load(U.P) = S.L/Area
= 76.67 kN/m2
For Dynamic Load(U.P) = D.L/Area
0 kN/m2
For Total Load(U.P) = T.L/Area
76.67 kN/m2
< 300kN/m2
Hence Safe
3.0 Moment Calculation
Uniform Load(U.D.L) = U.PxWidth kN/m width=B/2
U.D.L = 107.34 kN/m
Effective Span(L) = 3.6 m
(+ve) Moment (wl2/8) = 173.9 kN.m
(-ve) Moment (wl2/10) = 139.12 kN.m
As per SP 16
Mu/fckbd2 for +ve moment = 2.24
2
Mu/fckbd for -ve moment = 1.79
From SP 16 Table 4
pt = 0.587
Ast = 1940 mm2
Provided T12@200c/c & T16@200c/c It is Found to be Safe
4.0 Check for Punching shear
Loading point
Breadth = 320 mm
Depth = 600 mm
Maximum force Vu = 644 kN

tv = 0.98 N/mm2
< 1.37 N/mm2
Hence Safe
Document No UH441_01853_MPE_A4
Revision No 00
Date 20-Apr-12
SI.no
1.0 Design Data
Static Load = 180 kN
Dynamic Load = 450 kN
Self Weight = 260 kN
Total Load(T.L) = 890 kN
Breadth = 4.9 m
Actual Depth = 1.01 m
Cover = 0.05 m
Effective depth(d) = 0.96 m
Area = 26 m2
2.0 Upward Pressure(U.P)
For Static Load(U.P) = S.L/Area
= 16.93 kN/m2
For Dynamic Load(U.P) = D.L/Area
27.31 kN/m2
For Total Load(U.P) = T.L/Area
34.24 kN/m2
< 300kN/m2
Hence Safe
3.0 Moment Calculation
Uniform Load(U.D.L) = U.PxWidth kN/m width=B/2
U.D.L = 83.89 kN/m
Effective Span(L) = 2.7 m
(+ve) Moment (wl2/8) = 76.45 kN.m
(-ve) Moment (wl2/10) = 61.16 kN.m
As per SP 16
Mu/bd2 for +ve moment = 0.04
Mu/fbd2 for -ve moment = 0.03
From SP 16 Table 4
No value for 0.01 values from 0.3 so provide minimum Ast
Minimum Ast = 0.12%bD
= 2969.4 mm2
Provided T12@100c/c & It is Found to be Safe
4.0 Check for Punching shear
Loading point
Breadth = 500 mm
Depth = 500 mm
Maximum force Vu = 890 kN

tv = 0.16 N/mm2
< 1.37 N/mm2
Hence Safe