Manual Load Calculation
Manual Load Calculation
U= Q/ (A x ∆T)
Collect basic data:
Find out area & volume to be air conditioned
Find out type of building, wall and glass
Find out exposed wall and glass to sun rays
Location and orientation of area to be air-conditioned
Find out DBT,WBT, RH and grain/lb. for inside and outside of area
Type of equipment used in air-conditioned space
Find occupancy and type of lighting used for AC area from client
Ventilation (Fresh Air Quantity):
Method-1
Find out amount of air quantity per person depending upon type of application.
Mostly 7.5 CFM per person is taken
For warehouse 10 CFM/Person
For areas like entrance lobby, auditorium, Photo studio, Offices is taken as 5 CFM/ Person
For areas like mall, retail stores, Barber shop is taken as 7.5 CFM/ Person
For Beauty and nail salons is taken as 20 CFM/ person
Method -2
Heat gain = Area (ft2) x U value for glass x Equivalent temperature difference
Q= UA (∆T)
Calculate heat gain through each exposed glass as per orientation
U= Depends upon type of glass
Double pane glass: 0.38
Single pane glass: 0.56
A= Area of glass ft2
∆T= Outside and inside temperature difference of glass
Calculate heat gain through each partition glass (Not exposed to sun & and air-conditioning area)
U value for partition wall is 1.13
Find out weather slab of air conditioning area is directly exposed to sun or not
1) For Roof
Heat gain = Area (ft2) x U value of roof x Equivalent temperature difference
Q= UA (∆T)
U= for underdeck insulation-0.12
Without insulation- 0.54
A= Area of roof in ft2
∆T= Outside and inside temperature difference of floor
OR
For ceiling
Heat gain = Area (ft2) x U value of ceiling x Equivalent temperature difference
Q= UA (∆T)
U= 0.4 (If above floor is not AC)
0 (If above is A/C)
A= Area of ceiling in ft2
∆T= Outside and inside temperature difference of ceiling
2) For Floor
Heat gain = Area (ft2) x U value of floor x Equivalent temperature difference
Q= UA (∆T)
U= 0.4 (If above floor is not AC)
0 (If above is A/C)
A= Area of floor in ft2
∆T= Outside and inside temperature difference of floor
1. Fresh Air :
Heat Gain = Fresh Air Quantity (CFM) x Bypass factor x Sensible air constant x Equivalent
temperature difference
Q= CFM x BF x K x ∆T
B.F= Bypass factor
0.1 to 0.15 for office (4 Row coil)
0.15 to 0.25 for Retail (3 Row coil)
0.05 to 0.1 for Auditorium (6 Row coil)
K= Sensible air constant -1.08
∆T- Outside and design inside temperature difference
2. Equipment
Heat Gain = Equipment Load x No of Equipment x 3.41
Q= EL x N x 3.41
Electrical Load from ASHRAE Handbook
1. Fresh Air:
Heat gain = Fresh Air Quantity (CFM) x Bypass factor x Latent Heat Constant x
Equivalent Specific humidity difference
Q= F.A x B.F x K x ∆w
F.A= Fresh Air (CFM)
B.F = Bypass factor
0.1 to 0.15 for office (4 Row coil)
0.15 to 0.25 for Retail (3 Row coil)
0.05 to 0.1 for Auditorium (6 Row coil)
K= Latent air constant -0.67
∆w- Outside and design inside specific humidity difference
R.T.S.H = Wall Heat Gain + Glass Heat Gain +Ceiling Heat Gain + Floor Heat Gain +
Fresh Air Heat Gain + Occupancy Heat Gain + Equipment Heat Gain+ Light Heat
Gain
R.T.L.H = Fresh Air Latent Heat Gain + Occupancy latent Heat gain
E.R.T . H. L
Ton of Refrigeration (TR) =
12000
E. R.S. H .L
E.R.S.H.F = E . R . T . H . L
Calculate ADP based on inside and outside condition using Psychometric Chart
Infiltration
Method-1