EENG492 Extended Assignment Spring 2019-2020 - v4
EENG492 Extended Assignment Spring 2019-2020 - v4
a- Calculate and Sketch the equivalent circuit of this transformer when referred to its low-
voltage side.
The transformer is now loaded: 12 KW load, 0.8 lagging PF, and a load voltage of 410 V.
1. Find the flux per pole to produce the rated voltage at no-load conditions
2. Calculate the current per path in the armature of this generator at the rated load. Assume no
losses in the machine.
3. Find the induced torque in this machine at the rated load.
4. How many commutator segments are in this machine?
5. How many brushes must this motor have? How wide must each brush be?
A six pole, Y-connected synchronous generator rated at 425 KVA, 2.4 KV, 0.9 PF lagging, and
60 Hz frequency. Its armature resistance is 0.3 Ω, and its synchronous reactance is 6 Ω.
If the generator is operating at its rated conditions with an efficiency of 86% ;
Problem 8
A 3-phase, 381 V, 50-Hz, 6-pole, Y-connected induction motor is driving a 30 HP load at
82% efficiency.
The total friction, windage, and core losses can be assumed to be constant at 2400 W,
independent of load. The motor is operating at rated voltage and frequency at a per-unit
slip of 0.08.
(a) Find the shaft speed of the motor in RPM and in rad/sec.
(b) Find the electrical input power Pin.
(c) What is the converted power from electrical to mechanical Pconv.
(d) Calculate the induced torque τind.
(e) Deduce the total Copper Losses.
Problem 9 (Chapter 9: Single Phase and Special Motors)