PORTABLE LIGHTING FIXTURES Explosion Proof Electrical Equipment

FOR INCANDESCENT LAMPS


Ex Lighting

EVP-100
Installation: hazardous areas - Zone 1 / 2 (Gases) - Zone 21 /22 (Dusts)
Classification: Group II - Category 2G 2D EVP-100

LIGHTING FIXTURE
ATEX 94/9/EC GOST-R (RTR / RTN) GOST-K
II 2 G Ex d IIC T4/T2 1Ex d IIC T4 (T5…T2) X 1Ex d IIC T4 (T5…T2) X
EXECUTION
II 2 D Ex tD A21 T130°C DIP A21 TA (130)°C DIP A21 TA (130)°C
installation ZONE 1 / 2 - ZONE 21 / 22 ZONE 1 / 2 - ZONE 21 / 22 ZONE 1 / 2 - ZONE 21 / 22

PROTECTION DEGREE IP66 IP66 IP66

CERTIFICATE REF. INERIS 01 ATEX 0054X POCC IT. ГБ05.B02536 No. 07/43-269

ГОСТ Р 51330.9-99 (МЭК 60079-0-98);


EN 60079-0; EN 60079-1; ГОСТ Р 51330.0 / 1 / 8 / 14-99
RULES OF COMPLIANCE ГОСТ Р 51330.1-99 (МЭК 60079-1-98);
EN 61241-1 ГОСТ Р МЭК 61241-1-1-2002
ГОСТ Р 51330,8-99; ГОСТ Р МЭК 61241-1-1-99

Mechanical characteristics
Body marine grade copper free aluminium (control gear & lamp body)
Globe high-temperature resistant borosylicate glass
Painting external epoxy powders grey ral-9006 colour
Screws external stainless steel
Gaskets silicon rubber
Cable entry Nickel plated brass cable gland 1/2” npt (armoured cable)

Electrical characteristics
Power supply 12 ÷ 230V AC/DC
lampholders e27 porcelain

On Request Accessories:
• External painting colour on request

Since 1961

Feam Catalogue 02 - 1
YOUR PARTNER FOR SAFETY
Ex Lighting

EVP-100 Technical data


EVP-100

TEMPERATURE CLASS TEMPERATURE CLASS LAMPHOLDER CABLE


CODE LAMP DETAIL
(GAS) (DUSTS) SIZE ENTRY SIZE

LIGHTING FIXTURE FOR INCANDESCENT LAMP - POWER SUPPLY 230V-50Hz


EVP-100 100 W T4 T 130°C E-27 CABLE GLAND 1/2” NPT A

EVP-100 Technical features


CODE A [mm] B [mm] C [mm] Ø D [mm] weight [Kg] CABLE ENTRY DETAIL
EVP-100 395 257 287 150 4,00 CABLE GLAND 1/2” NPT A

Reference details
A
A

ØD

REMARK:
Due to the development of the national and international specifications and of the technology, the above technical characteristics
showed on this bulletin can be considered as binding on our confirmation only.