Summary

1. Introduction.....................................................................................................................5
2. List of Models and Technical Specifications.........................................................................5
3. Installation and Connection...............................................................................................9
3.1 Mechanical Installation...............................................................................................9
3.1.1 Installation Environment.....................................................................................9
3.1.2 Positioning and Mounting..................................................................................9
3.1.3 Access to the Control and Power Terminal Strips and Front Cover Mounting..........10
3.2 Electrical Installation - Grounding Terminals................................................................11
4. Accessories for the CFW-11 IP54 Protection Degree Models...............................................11
5. Mechanical Data.............................................................................................................12
6. Others............................................................................................................................15

Índice

1. Introducción....................................................................................................................16
2. Relación de Modelos y Especificaciones Técnicas...............................................................16
3. Instalación y Conexión.....................................................................................................20
3.1 Instalación Mecánica.................................................................................................20
3.1.1 Condiciones Ambientales.................................................................................20
3.1.2 Posicionamiento y Fijación................................................................................20
3.1.3 Acceso a los Bornes de Control y de Potencia y Montaje de la Tapa Frontal..........21
3.2 Instalación Eléctrica - Puntos de Puesta a la Tierra.......................................................22
4. Accesorios para los Modelos CFW-11 con Grado de Protección IP54.................................22
5. Datos Mecánicos.............................................................................................................23
6. Otros.............................................................................................................................26

Índice

1. Introdução......................................................................................................................27
2. Relação de Modelos e Especificações Técnicas..................................................................27
3. Instalação e Conexão......................................................................................................31
3.1 Instalação Mecânica.................................................................................................31
3.1.1 Condições Ambientais......................................................................................31
3.1.2 Posicionamento e Fixação.................................................................................31
3.1.3 Acesso aos Bornes de Controle e Potência e Montagem da Tampa Frontal...........32
3.2 Instalação Elétrica - Pontos de Aterramento.................................................................33
4. Acessórios para os Modelos CFW-11 com Grau de Proteção IP54......................................33
5. Dados Mecânicos............................................................................................................34
6. Outros...........................................................................................................................37
Availability of option kits
that can be incorporated into the
product
(Refer to the smart code in the
user’s guide chapter 2) (8)

Model
Frame
phases
RFI filter

nominal
1. INTRODUCTION

Inverter supply
Weight [kg (lb)]

Surrounding air

current [Arms] -
current [Arms] -
Dynamic braking

voltage range [V]

Number of power
filter

refer to the table 2


refer to the table 3
temperature [°C (°F)]

HD (1) nominal output

ND (1) nominal output


Safety stop
power supply

RFI suppressor
Dynamic braking
is also valid for these models.

Equivalent IP20 inverter frame size


24 Vdc external control
CFW11 0010 S 2 O 54 ... 1φ 10 10 Yes
CFW11 0006 B 2 O 54 ... 1φ / 3φ 6.0 5.0
Yes (*)
CFW11 0007 B 2 O 54 ... 1φ / 3φ 7.0 7.0
10
CFW11 0007 T 2 O 54 ... A 3φ 7.0 5.5
(22)
CFW11 0010 T 2 O 54 ... 3φ 10 8.0
1
CFW11 0013 T 2 O 54 ... 3φ 13 11

Notes: 1ϕ = single-phase power supply, 3ϕ = three-phase power supply.


CFW11 0016 T 2 O 54 ... 3φ 16 13
CFW11 0024 T 2 O 54 ... 3φ 24 20 Built-in

(*) Inverter model with RFI filter option has only single-phase power supply input.
15
CFW11 0028 T 2 O 54 ... B 3φ 28 24

200...240 V
(33) Yes Yes Yes
CFW11 0033 T 2 O 54 ... 3φ 33.5 28
2. LIST OF MODELS AND TECHNICAL SPECIFICATIONS

CFW11 0045 T 2 O 54 ... 3φ 45 36


36
CFW11 0054 T 2 O 54 ... C 3φ 54 45

-10...40 °C (14 ... 104 °F)


(79)
CFW11 0070 T 2 O 54 ... 2 3φ 70 56
No (braking IGBT available in the standard product)

Optional (the standard product does not have RFI filter)


Addendum to the CFW-11 User’s Manual

CFW11 0086 T 2 O 54 ... 3φ 86 70 41


D
CFW11 0105 T 2 O 54 ... 3φ 105 86 (90)

Optional
(the standard No (filter available
80
CFW11 0142 T 2 O 54 ... 3 E 3φ 142 115 product does Built-in in the standard Yes
(176)
not have product)

220...230 V
braking)
Table 1 a) - CFW-11 IP54 list of models and technical specifications - 200-240 V/220-230 V supply models
IP20 protection degree) are presented. The other information presented in the user’s guide
This addendum brings information on the CFW11 XXXX X X O 54 ... (CFW-11 models
with IP54 protection degree). Only the differences compared to the standard product (with

5
ENGLISH
6
ENGLISH

Availability of option kits


that can be incorporated into the
product
(Refer to the smart code in the user’s
guide chapter 2) (8)

Model
Frame
phases
RFI filter

nominal
Inverter supply
Weight [kg (lb)]

Surrounding air

current [Arms] -
current [Arms] -
Dynamic braking

voltage range [V]

Number of power
filter

refer to the table 2


refer to the table 3
temperature [°C (°F)]

HD (1) nominal output

ND (1) nominal output


Safety stop
power supply

RFI suppressor
Dynamic braking

Equivalent IP20 inverter frame size


24 Vdc external control

CFW11 0003 T 4 O 54 ... 3φ 3.6 3.6


CFW11 0005 T 4 O 54 ... 3φ 5.0 5.0
10
CFW11 0007 T 4 O 54 ... A 3φ 7.0 5.5
(22)
CFW11 0010 T 4 O 54 ... 3φ 10 10
1
CFW11 0013 T 4 O 54 ... 3φ 13.5 11
CFW11 0017 T 4 O 54 ... 3φ 17 13.5
15
CFW11 0024 T 4 O 54 ... B 3φ 24 19 Built-in Yes Yes Yes
(33)
380-480 V supply models

CFW11 0031 T 4 O 54 ... 3φ 31 25


CFW11 0038 T 4 O 54 ... 3φ 38 33
36

380...480 V
CFW11 0045 T 4 O 54 ... C 3φ 45 38
(79)
CFW11 0058 T 4 O 54 ... 2 3φ 58.5 47
-10...40 °C (14 ...104 °F)

CFW11 0070 T 4 O 54 ... 3φ 70.5 61 41


No (braking IGBT available in the standard product)

D
Optional (the standard product does not have RFI filter)

CFW11 0088 T 4 O 54 ... 3φ 88 73 (90)

Optional
No (filter
Table 1 b) - CFW-11 IP54 list of models and technical specifications -

CFW11 0105 T 4 O 54 ... 3φ 105 88 (the standard


80 available in
3 E product does Built-in Yes Yes Yes
(176) the standard
CFW11 0142 T 4 O 54 ... 3φ 142 115 not have
product)
braking)
Overload
Rated current (2) Rated carrier Maximum Rated input Dissipated
output [Arms]
Model frequency (3) motor (4) current power
current (1)

Frame
[kHz] [HP/kW] [Arms] [W]

frame size

Equivalent
[Arms]

IP20 inverter
1 min 3s

CFW11 0010 S 2 O 54 ... 10 11.0 15.0 5 3/2.2 20.5 180


CFW11 0006 B 2 O 54 ... 6.0 6.60 9.00 5 1.5/1.1 12.3/6.0 (5) 130
CFW11 0007 B 2 O 54 ... 7.0 7.70 10.5 5 2/1.5 14.4/7.0 (5) 140
CFW11 0007 T 2 O 54 ... A 7.0 7.70 10.5 5 2/1.5 7.0 140
CFW11 0010 T 2 O 54 ... 10 11.0 15.0 5 3/2.2 10.0 170
1
CFW11 0013 T 2 O 54 ... 13 14.3 19.5 5 4/3.0 13.0 200
CFW11 0016 T 2 O 54 ... 16 17.6 24.0 5 5/3.7 16.0 230
CFW11 0024 T 2 O 54 ... 24 26.4 36.0 5 7.5/5.5 24.0 310
CFW11 0028 T 2 O 54 ... B 28 30.8 42.0 5 10/7.5 28.0 370
CFW11 0033 T 2 O 54 ... 33.5 36.9 50.3 5 12.5/9.2 33.5 430
CFW11 0045 T 2 O 54 ... 45 49.5 67.5 5 15/11 45.0 590
CFW11 0054 T 2 O 54 ... C 54 59.4 81.0 5 20/15 54.0 680
CFW11 0070 T 2 O 54 ... 2 70 77.0 105 5 25/18.5 70.0 900
CFW11 0086 T 2 O 54 ... 86 94.6 129 5 30/22 86.0 970
D
CFW11 0105 T 2 O 54 ... 105 116 158 5 40/30 105 1200
CFW11 0142 T 2 O 54 ... 3 E 142 156 213 2.5 50/37 142 1490
CFW11 0003 T 4 O 54 ... 3.6 3.96 5.40 5 2/1.5 3.6 130
CFW11 0005 T 4 O 54 ... 5.0 5.50 7.50 5 3/2.2 5.0 140
CFW11 0007 T 4 O 54 ... A 7.0 7.7 10.5 5 4/3 7.0 180
CFW11 0010 T 4 O 54 ... 10 11.0 15.0 5 6/4.5 10.0 220
1
CFW11 0013 T 4 O 54 ... 13.5 14.9 20.3 5 7.5/5.5 13.5 280
CFW11 0017 T 4 O 54 ... 17 18.7 25.5 5 10/7.5 17.0 360
CFW11 0024 T 4 O 54 ... B 24 26.4 36.0 5 15/11 24.0 490
Normal duty cycle (ND) application

CFW11 0031 T 4 O 54 ... 31 34.1 46.5 5 20/15 31.0 560


CFW11 0038 T 4 O 54 ... 38 41.8 57.0 5 25/18.5 38.0 710
CFW11 0045 T 4 O 54 ... C 45 49.5 67.5 5 30/22 45.0 810
CFW11 0058 T 4 O 54 ... 2 58.5 64.4 87.8 5 40/30 58.5 1050
CFW11 0070 T 4 O 54 ... 70.5 77.6 106 5 50/37 70.5 1280
D
CFW11 0088 T 4 O 54 ... 88 96.8 132 5 60/45 88.0 1480
CFW11 0105 T 4 O 54 ... 105 116 158 2.5 75/55 105 1270
3 E
CFW11 0142 T 4 O 54 ... 142 156 213 2.5 100/75 142 1680
Table 2 - CFW-11 IP54 protection degree models electrical specification -

7
ENGLISH
8
ENGLISH

Overload
Rated current (2) Rated carrier Maximum Rated input Dissipated
output [Arms]
Model frequency (3) motor (4) current power
current (1)

Frame
[kHz] [HP/kW] [Arms] [W]

frame size

Equivalent
[Arms]

IP20 inverter
1 min 3s

CFW11 0010 S 2 O 54 ... 10 15.0 20.0 5 3/2.2 20.5 140


CFW11 0006 B 2 O 54 ... 5.0 7.50 10.0 5 1.5/1.1 10.3/5.0 (5) 120
CFW11 0007 B 2 O 54 ... 7.0 10.5 14.0 5 2/1.5 14.4/7.0 (5) 140
CFW11 0007 T 2 O 54 ... A 5.5 8.25 11.0 5 1.5/1.1 5.5 120
CFW11 0010 T 2 O 54 ... 8.0 12.0 16.0 5 2/1.5 8.0 170
1
CFW11 0013 T 2 O 54 ... 11 16.5 22.0 5 3/2.2 11.0 170
CFW11 0016 T 2 O 54 ... 13 19.5 26.0 5 4/3.0 13.0 190
CFW11 0024 T 2 O 54 ... 20 30.0 40.0 5 6/4.5 20.0 250
CFW11 0028 T 2 O 54 ... B 24 36.0 48.0 5 7.5/5.5 24.0 290
CFW11 0033 T 2 O 54 ... 28 42.0 56.0 5 10/7.5 28.0 350
CFW11 0045 T 2 O 54 ... 36 54.0 72.0 5 12.5/9.2 36.0 450
CFW11 0054 T 2 O 54 ... C 45 67.5 90.0 5 15/11 45.0 540
CFW11 0070 T 2 O 54 ... 2 56 84.0 112 5 20/15 56.0 680
CFW11 0086 T 2 O 54 ... 70 105 140 5 25/18.5 70.0 740
D
CFW11 0105 T 2 O 54 ... 86 129 172 5 30/22 86.0 920
CFW11 0142 T 2 O 54 ... 3 E 115 172.5 230 5 (3) 40/30 115 1280
CFW11 0003 T 4 O 54 ... 3.6 5.40 7.20 5 2/1.5 3.6 110
CFW11 0005 T 4 O 54 ... 5.0 7.50 10.0 5 3/2.2 5.0 140
CFW11 0007 T 4 O 54 ... A 5.5 8.25 11.0 5 3/2.2 5.5 140
CFW11 0010 T 4 O 54 ... 10 15.0 20.0 5 6/4.5 10.0 200
1
CFW11 0013 T 4 O 54 ... 11 16.5 22.0 5 6/4.5 11.0 220
CFW11 0017 T 4 O 54 ... 13.5 20.3 27.0 5 7.5/5.5 13.5 270
Heavy duty cycle (HD) application

CFW11 0024 T 4 O 54 ... B 19 28.5 38.0 5 10/7.5 19.0 360


CFW11 0031 T 4 O 54 ... 25 37.5 50.0 5 15/11 25.0 430
CFW11 0038 T 4 O 54 ... 33 49.5 66.0 5 20/15 33.0 590
CFW11 0045 T 4 O 54 ... C 38 57.0 76.0 5 25/18.5 38.0 650
CFW11 0058 T 4 O 54 ... 2 47 70.5 94.0 5 30/22 47.0 800
CFW11 0070 T 4 O 54 ... 61 91.5 122 5 40/30 61.0 1050
D
CFW11 0088 T 4 O 54 ... 73 110 146 5 50/37 73.0 1170
CFW11 0105 T 4 O 54 ... 88 132 176 2.5 60/45 88.0 1020
3 E
Table 3 - CFW-11 IP54 protection degree models electrical specification -

CFW11 0142 T 4 O 54 ... 115 173 230 2.5 75/55 115 1290
NOTES!
- The notes (1) to (8) mentioned in the tables 1, 2 and 3 are those from the section 8.1 of
the user’s guide. Observe that the environment temperature specification (surrounding the
inverter) for CFW11 XXXX X X O 54 ... inverters is from -10 °C (14 °F) to 40 °C (104 °F). It is
possible to operate this inverter in environments with temperatures surrounding the inverter
up to 50 °C (122 °F) if a derating of 2 % for each °C (1.1 % for each °F) is applied to the
output current. This output current derating is valid for all the switching frequencies.
- The tables 1, 2 and 3 replace the table 8.1 of the user’s guide.

3. INSTALLATION AND CONNECTION

3.1 Mechanical Installation

3.1.1 Installation Environment

ENGLISH
Environment conditions for the operation of the inverter:
- Temperature: -10 ºC to 40 ºC (14 °F to 104 °F) - standard conditions (surrounding the inverter).
- From 40 ºC to 50 ºC (104 °F to 122 °F) - current derating of 2 % each °C (or 1.11 % each °F)
above 40 ºC (104 °F).
- Relative Humidity: from 5 % to 90 % non-condensing.
- Altitude: up to 1000 m - standard conditions.
- From 1000 m to 4000 m - current derating of 1 % each 100 m (or 0.3 % each 100 ft) above
1000 m (3,300 ft) altitude.

3.1.2 Positioning and Mounting

(a) External dimensions


Figure 1 (a) - Mechanical installation details

9
a2 a2 a2

b2

b2
∅ c2
∅ c2

Air flow

(b) Surface mounting (c) Frame sizes 1 and 2 (d) Frame size 3 mounting
mounting

A1 B1 C1 D1 a2 b2 c2
Model mm mm mm mm mm mm
M
(in) (in) (in) (in) (in) (in)
ENGLISH

255 410 235 450 200 425


Frame 1 M6
(10.04) (16.14) (9.23) (17.72) (7.87) (16.73)
350 625 298 675 250 650
Frame 2 M8
(13.78) (24.61) (11.71) (26.57) (9.84) (25.59)
400 825 389 875 150 850
Frame 3 M8
(15.75) (32.48) (15.31) (34.45) (5.91) (33.46)
Dimension tolerance: ±1.0 mm (±0.039 in).

Figure 1 (b) to (d) (cont.) - Mechanical installation details

3.1.3 Access to the Control and Power Terminal Strips and Front Cover Mounting

1 2 3

3 4

5 2

1 6

Note: The tightening sequence for mounting the front cover is: 1-2-3-4-5-6. Torque: 2.5 Nm.

Figure 2 - Removal of keypad and front cover

10
3.2 Electrical Installation - Grounding Terminals

The figure 3 shows the grounding points located inside the product.

ENGLISH
Grounding

Figure 3 - Product grounding

4. ACCESSORIES FOR THE CFW-11 IP54 PROTECTION DEGREE MODELS

Table 4 - List of available accessories for the CFW-11 with protection degree IP54

WEG Part
Name Description
Number
10960847 CCS-01 Kit for control cables shielding (included in the standard product).
Shielding kit for power cables for IP54 frame size 1 models (standard for
11112774 PCS1-01
option FA).
Shielding kit for power cables for CFW110045T2O54...,
CFW110054T2O54..., CFW110070T2O54..., CFW110038T4O54...,
11112776 PCSC-02
CFW110045T4O54... and CFW110058T4O54... models (standard for
option FA).

Shielding kit for power cables for frame size D (IP20) inverters and
11119781 PCSD-01 CFW110086T2O54..., CFW110105T2O54..., CFW110070T4O54...
and CFW110088T4O54... models - included in the standard product.

Shielding kit for power cables for frame size E (IP20) and frame size 3
10960844 PCSE-01
(IP54) inverters - included in the standard product.

11
ENGLISH

12
Frame 1

Dimensions in mm [in]
5. MECHANICAL DATA

Figure 4 - Inverter dimensions - frame 1


* Models of the frame size 1 up to CFW11 0016T2O54 ... and CFW11 0013T4O54 ...
** Models of the frame size 1 beginning from the CFW11 0024T2O54 ... and CFW11 0017T4O54 ...
Frame 2

Dimensions in mm [in]
Figure 5 - Inverter dimensions - frame 2
* Models of the frame size 2 up to CFW11 0070T2O54 ... and CFW11 0058T4O54 ...
** Models of the frame size 2 beginning from the CFW11 0086T2O54 ... and CFW11 0070T4O54 ...
ENGLISH

13
Frame 3
ENGLISH

Dimensions in mm [in]
Figure 6 - Inverter dimensions - frame 3
14
6. OTHERS

ATTENTION!
The parameter P0352 (Fan Configuration) must be set at 1 or 4 for the CFW11 XXXX X X
O 54 ... inverters.

NOTES!
- The CFW11 XXXX X X O 54 ... models are supplied with the parameter P0352 adjusted in
4, i.e., the heatsink fan is controlled based in the IGBT/rectifier temperature and the internal
fan is always activated.
- If the factory settings are loaded (via P0204) and the inverter software version is equal
or prior to V1.6x, the parameter P0352 is adjusted automatically in 2. In this case, for the
CFW11 XXXX X X O 54 ... inverters, adjust this parameter again in 1 or 4.

ENGLISH
ATTENTION!
The following items from the user’s guide do not apply to the CFW11 XXXX X X O 54 ...
inverters:
- Flange mounting described in the section 3.1.3;
- Figure 3.5 (section 3.1.4) of the CFW-11 inverters frame sizes A…D user’s guide;
- Sections 3.1.4 to 3.1.7 of the CFW-11 inverters frame size E user’s guide;
- Frame sizes 1 and 2 inverters: values for surrounding air temperature = 50 °C (122 °F)
of the table 8.2;
- Frame size 3 inverters: values presented in the tables 8.2 and 8.4;
- Protection degree specification of the section 8.2.

NOTE!
The CFW11 XXXX X X O 54 ... models are not UL listed.