Compressive Strength of AAC Block
Compressive Strength of AAC Block
Compressive Strength of AAC Block
11/103B
Determination of Compressive Strength of AAC Block
IS: 6441: 1972 (Part 5) RA 2017
SRAF NO 1129 Date 6/6/2020 Date of Testing From 7/6/2020 To 6-Apr
Rate of Loading during test shall be 0.5 to 2 kg/sq.cms (or 5.2 kN/sec)
Prior to testing the specimen shall be stored at room temperature until temperature equilibrium has been reached.
Five hours storage at room temperature is generally sufficient if the drying temperature applied has been 50 0C.
Observations
UP 155.10 150.04 152.80 23271.2 3555839.97 2388.3 2150.3 11.07 604.72 101.3 4.35
MID 155.26 150.14 152.90 23310.7 3564211.60 2386.1 2162.3 10.35 10.97 606.67 604.15 105.3 4.52 4.46
LOW 155.14 150.26 152.94 23311.3 3565235.79 2389.0 2142.9 11.48 601.05 104.9 4.50
UP 149.16 155.14 153.48 23140.7 3551631.93 2380.1 2144.6 10.98 603.84 99.8 4.31
MID 149.18 155.10 153.40 23137.8 3549341.28 2372.1 2152.8 10.19 10.41 606.54 606.60 99.6 4.30 4.31
LOW 149.10 155.14 153.08 23131.4 3540950.73 2375.0 2158.0 10.06 609.44 100.0 4.32
UP 155.18 150.20 153.42 23308.0 3575918.88 2315.8 2100.5 10.25 587.40 102.1 4.38
MID 155.16 150.16 154.20 23298.8 3592678.91 2318.5 2112.5 9.75 9.47 588.00 590.65 104.8 4.50 4.40
LOW 155.16 150.04 152.98 23280.2 3561405.98 2302.9 2124.5 8.40 596.53 100.6 4.32
Equipments
Vernier Caliper BIPL/ 05 CTM Loading Machine BIPL/34
Used :
Analyst By Checked By
(Asst. Manager/Technician) (Dy. Tech Manager)
FORMAT NO : BIPL/QSFM/7.11/103B
Determination of Compressive Strength of AAC Block
IS: 6441: 1972 (Part 5) RA 2017
SRAF NO 1129 Date 6/6/2020 Date of Testing From 7/6/2020 To 6-Apr
Rate of Loading during test shall be 0.5 to 2 kg/sq.cms (or 5.2 kN/sec)
Prior to testing the specimen shall be stored at room temperature until temperature equilibrium has been reached.
Five hours storage at room temperature is generally sufficient if the drying temperature applied has been 50 0C.
Observations
UP 155.10 150.04 152.80 23271.2 3555839.97 2388.3 2150.3 11.07 604.72 101.3 4.35
MID 155.26 150.14 152.90 23310.7 3564211.60 2386.1 2162.3 10.35 10.97 606.67 604.15 105.3 4.52 4.46
LOW 155.14 150.26 152.94 23311.3 3565235.79 2389.0 2142.9 11.48 601.05 104.9 4.50
UP 149.16 155.14 153.48 23140.7 3551631.93 2380.1 2144.6 10.98 603.84 99.8 4.31
MID 149.18 155.10 153.40 23137.8 3549341.28 2372.1 2152.8 10.19 10.41 606.54 606.60 99.6 4.30 4.31
LOW 149.10 155.14 153.08 23131.4 3540950.73 2375.0 2158.0 10.06 609.44 100.0 4.32
UP 155.18 150.20 153.42 23308.0 3575918.88 2315.8 2100.5 10.25 587.40 102.1 4.38
MID 155.16 150.16 154.20 23298.8 3592678.91 2318.5 2112.5 9.75 9.47 588.00 590.65 104.8 4.50 4.40
LOW 155.16 150.04 152.98 23280.2 3561405.98 2302.9 2124.5 8.40 596.53 100.6 4.32
Equipments
Vernier Caliper BIPL/ 05 CTM Loading Machine BIPL/34
Used :
Analyst By Checked By
(Asst. Manager/Technician) (Dy. Tech Manager)
FORMAT NO : BIPL/QSFM/7.11/103B
Determination of Compressive Strength of AAC Block
IS: 6441: 1972 (Part 5) RA 2017
SRAF NO 1129 Date 6/6/2020 Date of Testing From 7/6/2020 To 6-Apr
Rate of Loading during test shall be 0.5 to 2 kg/sq.cms (or 5.2 kN/sec)
Prior to testing the specimen shall be stored at room temperature until temperature equilibrium has been reached.
Five hours storage at room temperature is generally sufficient if the drying temperature applied has been 50 0C.
Observations
UP 151.28 150.20 153.28 22722.3 3482867.40 2382.5 2150.0 10.81 617.31 95.2 4.19
MID 155.02 150.16 153.24 23277.8 3567090.56 2371.0 2142.5 10.67 10.78 600.63 606.57 98.3 4.22 4.25
LOW 155.16 150.30 152.98 23320.5 3567577.43 2380.0 2146.9 10.86 601.78 100.8 4.32
UP 154.20 150.10 153.46 23145.4 3551896.15 2350.1 2108.0 11.48 593.49 96.9 4.19
MID 154.16 150.14 153.48 23145.6 3552383.99 2362.5 2115.1 11.70 11.17 595.40 597.81 97.8 4.23 4.27
LOW 152.10 150.16 153.90 22839.3 3514973.81 2344.1 2124.9 10.32 604.53 100.6 4.40
UP 150.16 154.16 151.98 23148.7 3518134.20 2318.9 2090.0 10.95 594.06 101.3 4.38
MID 150.26 154.24 152.46 23176.1 3533428.57 2324.1 2083.4 11.55 10.80 589.63 597.04 98.0 4.23 4.22
LOW 150.16 154.30 152.78 23169.7 3539864.93 2362.9 2150.2 9.89 607.42 94.3 4.07
Equipments
Vernier Caliper BIPL/ 05 CTM Loading Machine BIPL/34
Used :
Analyst By Checked By
(Asst. Manager/Technician) (Dy. Tech Manager)
FORMAT NO : BIPL/QSFM/7.11/103B
Determination of Compressive Strength of AAC Block
IS: 6441: 1972 (Part 5) RA 2017
SRAF NO 1129 Date 6/6/2020 Date of Testing From 7/6/2020 To 6-Apr
Rate of Loading during test shall be 0.5 to 2 kg/sq.cms (or 5.2 kN/sec)
Prior to testing the specimen shall be stored at room temperature until temperature equilibrium has been reached.
Five hours storage at room temperature is generally sufficient if the drying temperature applied has been 50 0C.
Observations
UP 152.30 152.64 152.64 23247.1 3548433.07 2345.0 2145.3 9.31 604.58 94.5 4.07
MID 152.34 150.32 152.64 22899.7 3495417.66 2348.5 2145.9 9.44 9.68 613.92 608.39 95.8 4.18 4.18
LOW 152.98 151.24 152.46 23136.7 3527420.55 2360.1 2140.0 10.29 606.68 99.4 4.30
UP 152.78 150.64 153.48 23014.8 3532308.31 2322.9 2125.4 9.29 601.70 96.4 4.19
MID 153.24 150.42 153.24 23050.4 3532237.29 2365.1 2134.7 10.79 9.97 604.35 603.64 95.7 4.15 4.22
LOW 153.90 150.84 152.82 23214.3 3547605.66 2356.6 2145.8 9.82 604.86 100.2 4.32
UP 152.40 150.46 153.42 22930.1 3517936.56 2388.0 2137.4 11.72 607.57 100.8 4.40
MID 152.40 150.40 153.64 22921.0 3521576.29 2392.1 2145.0 11.52 11.09 609.10 607.28 99.4 4.34 4.23
LOW 152.80 151.28 152.98 23115.6 3536222.04 2354.5 2140.0 10.02 605.17 91.5 3.96
Equipments
Vernier Caliper BIPL/ 05 CTM Loading Machine BIPL/34
Used :
Analyst By Checked By
(Asst. Manager/Technician) (Dy. Tech Manager)
FORMAT NO : BIPL/QSFM/7.11/103B
Determination of Compressive Strength of AAC Block
IS: 6441: 1972 (Part 5) RA 2017
SRAF NO 1129 Date 6/6/2020 Date of Testing From 7/6/2020 To 6-Apr
Rate of Loading during test shall be 0.5 to 2 kg/sq.cms (or 5.2 kN/sec)
Prior to testing the specimen shall be stored at room temperature until temperature equilibrium has been reached.
Five hours storage at room temperature is generally sufficient if the drying temperature applied has been 50 0C.
Observations
UP 150.12 154.20 153.42 23148.5 3551443.48 2368.4 2129.5 11.22 599.62 90.2 3.90
MID 150.28 151.28 153.62 22734.4 3492452.14 2358.7 2164.9 8.95 10.04 619.88 610.62 94.8 4.17 4.23
LOW 151.24 150.38 153.40 22743.5 3488848.48 2348.9 2136.5 9.94 612.38 105.4 4.63
UP 150.64 151.68 153.60 22849.1 3509617.95 2394.5 2134.7 12.17 608.24 100.8 4.41
MID 150.14 151.38 153.42 22728.2 3486959.40 2378.1 2139.0 11.18 11.19 613.43 613.43 95.6 4.21 4.26
LOW 150.24 151.64 152.48 22782.4 3473859.38 2368.4 2149.0 10.21 618.62 94.8 4.16
UP 151.34 150.90 152.50 22837.2 3482673.92 2352.8 2138.4 10.03 614.01 94.6 4.14
MID 150.38 152.46 152.52 22926.9 3496816.10 2364.0 2142.5 10.34 10.15 612.70 614.22 93.4 4.07 4.14
LOW 150.28 151.48 153.80 22764.4 3501166.93 2374.0 2156.5 10.09 615.94 95.5 4.20
Equipments
Vernier Caliper BIPL/ 05 CTM Loading Machine BIPL/34
Used :
Analyst By Checked By
(Asst. Manager/Technician) (Dy. Tech Manager)
FORMAT NO : BIPL/QSFM/7.11/103B
Determination of Compressive Strength of AAC Block
IS: 6441: 1972 (Part 5) RA 2017
SRAF NO 1129 Date 6/6/2020 Date of Testing From 7/6/2020 To 6-Apr
Rate of Loading during test shall be 0.5 to 2 kg/sq.cms (or 5.2 kN/sec)
Prior to testing the specimen shall be stored at room temperature until temperature equilibrium has been reached.
Five hours storage at room temperature is generally sufficient if the drying temperature applied has been 50 0C.
Observations
UP 155.26 150.14 152.64 23310.7 3558150.80 2380.1 2129.5 11.77 598.49 95.3 4.09
MID 155.16 150.18 152.64 23301.9 3556806.41 2348.5 2148.7 9.30 10.51 604.11 605.39 97.0 4.16 4.19
LOW 152.16 150.10 152.46 22839.2 3482066.87 2360.1 2136.5 10.47 613.57 98.9 4.33
UP 152.20 150.12 153.48 22848.3 3506751.56 2322.9 2120.0 9.57 604.55 96.8 4.24
MID 152.36 150.14 153.24 22875.3 3505415.63 2365.1 2139.0 10.57 9.93 610.20 608.84 98.3 4.30 4.26
LOW 153.14 150.10 152.82 22986.3 3512768.51 2356.6 2149.0 9.66 611.77 97.5 4.24
UP 152.28 150.18 153.42 22869.4 3508624.94 2388.0 2132.3 11.99 607.73 99.1 4.33
MID 152.24 150.16 153.64 22860.4 3512265.46 2392.1 2140.0 11.78 11.64 609.29 607.58 92.3 4.04 4.11
LOW 152.18 150.24 152.98 22863.5 3497661.78 2354.5 2118.6 11.13 605.72 90.8 3.97
Equipments
Vernier Caliper BIPL/ 05 CTM Loading Machine BIPL/34
Used :
Analyst By Checked By
(Asst. Manager/Technician) (Dy. Tech Manager)
FORMAT NO : BIPL/QSFM/7.11/103B
Determination of Compressive Strength of AAC Block
IS: 6441: 1972 (Part 5) RA 2017
SRAF NO 1129 Date 6/6/2020 Date of Testing From 7/6/2020 To 6-Apr
Rate of Loading during test shall be 0.5 to 2 kg/sq.cms (or 5.2 kN/sec)
Prior to testing the specimen shall be stored at room temperature until temperature equilibrium has been reached.
Five hours storage at room temperature is generally sufficient if the drying temperature applied has been 50 0C.
Observations
UP 152.34 150.08 152.78 22863.2 3493037.74 2384.5 2150.8 10.87 615.74 94.5 4.13
MID 152.42 150.30 152.34 22908.7 3489915.32 2358.0 2168.0 8.76 9.55 621.22 618.01 95.6 4.17 4.20
LOW 152.38 150.62 151.98 22951.5 3488165.26 2346.5 2152.4 9.02 617.06 98.4 4.29
UP 151.28 150.04 150.98 22698.1 3426951.77 2328.4 2108.0 10.46 615.12 95.7 4.22
MID 150.64 150.60 151.60 22686.4 3439255.81 2368.4 2139.5 10.70 10.69 622.08 615.50 96.4 4.25 4.28
LOW 150.78 150.36 151.34 22671.3 3431071.64 2318.9 2090.5 10.93 609.28 99.4 4.38
UP 151.46 151.28 150.96 22912.9 3458926.67 2358.2 2108.4 11.85 609.55 93.8 4.09
MID 151.34 150.64 150.64 22797.9 3434269.27 2360.4 2145.7 10.01 10.89 624.79 619.72 92.9 4.07 4.11
LOW 150.30 151.78 151.32 22812.5 3451992.64 2390.5 2156.9 10.83 624.83 94.7 4.15
Equipments
Vernier Caliper BIPL/ 05 CTM Loading Machine BIPL/34
Used :
Analyst By Checked By
(Asst. Manager/Technician) (Dy. Tech Manager)
FORMAT NO : BIPL/QSFM/7.11/103B
Determination of Compressive Strength of AAC Block
IS: 6441: 1972 (Part 5) RA 2017
SRAF NO 1129 Date 6/6/2020 Date of Testing From 7/6/2020 To 6-Apr
Rate of Loading during test shall be 0.5 to 2 kg/sq.cms (or 5.2 kN/sec)
Prior to testing the specimen shall be stored at room temperature until temperature equilibrium has been reached.
Five hours storage at room temperature is generally sufficient if the drying temperature applied has been 50 0C.
Observations
UP 150.24 150.08 152.78 22548.0 3444886.37 2384.5 2152.4 10.78 624.81 92.5 4.10
MID 150.32 150.30 152.34 22593.1 3441832.24 2358.0 2146.9 9.83 10.29 623.77 621.00 92.4 4.09 4.12
LOW 151.30 150.62 151.98 22788.8 3463442.74 2346.5 2128.0 10.27 614.42 95.2 4.18
UP 150.28 150.04 150.98 22548.0 3404298.73 2328.4 2146.8 8.46 630.61 96.4 4.28
MID 150.72 150.60 151.60 22698.4 3441082.29 2368.4 2129.6 11.21 10.06 618.88 620.39 96.8 4.26 4.28
LOW 150.76 150.36 151.34 22668.3 3430616.53 2318.9 2098.4 10.51 611.67 97.2 4.29
UP 150.46 151.28 150.96 22761.6 3436089.45 2358.2 2146.8 9.85 624.78 94.5 4.15
MID 151.28 150.64 150.64 22788.8 3432907.72 2360.4 2128.6 10.89 9.95 620.06 626.04 90.9 3.99 4.09
LOW 150.62 151.78 151.32 22861.1 3459342.20 2390.5 2190.7 9.12 633.27 94.2 4.12
Equipments
Vernier Caliper BIPL/ 05 CTM Loading Machine BIPL/34
Used :
Analyst By Checked By
(Asst. Manager/Technician) (Dy. Tech Manager)
FORMAT NO : BIPL/QSFM/7.11/103B
Determination of Compressive Strength of AAC Block
IS: 6441: 1972 (Part 5) RA 2017
SRAF NO 1129 Date 6/6/2020 Date of Testing From 7/6/2020 To 6-Apr
Rate of Loading during test shall be 0.5 to 2 kg/sq.cms (or 5.2 kN/sec)
Prior to testing the specimen shall be stored at room temperature until temperature equilibrium has been reached.
Five hours storage at room temperature is generally sufficient if the drying temperature applied has been 50 0C.
Observations
UP 152.42 150.24 152.86 22899.6 3500429.92 2384.5 2190.2 8.87 625.69 93.5 4.08
MID 152.04 150.28 152.42 22848.6 3482579.22 2345.6 2136.5 9.79 9.89 613.48 619.28 94.9 4.15 4.15
LOW 151.34 150.32 152.46 22749.4 3468377.91 2382.4 2145.8 11.03 618.68 95.8 4.21
UP 150.38 150.78 151.98 22674.3 3446039.57 2348.7 2150.0 9.24 623.90 94.8 4.18
MID 150.80 150.48 151.82 22692.4 3445157.74 2350.4 2148.4 9.40 9.99 623.60 623.29 95.2 4.20 4.16
LOW 150.28 150.34 151.34 22593.1 3419239.03 2368.7 2128.0 11.31 622.36 92.7 4.10
UP 150.24 150.92 151.42 22674.2 3433330.51 2346.8 2134.5 9.95 621.70 93.4 4.12
MID 150.34 150.38 151.56 22608.1 3426488.06 2375.4 2135.4 11.24 10.52 623.20 623.30 100.2 4.43 4.30
LOW 150.32 150.64 151.62 22644.2 3433314.33 2368.4 2145.8 10.37 624.99 98.7 4.36
Equipments
Vernier Caliper BIPL/ 05 CTM Loading Machine BIPL/34
Used :
Analyst By Checked By
(Asst. Manager/Technician) (Dy. Tech Manager)
FORMAT NO : BIPL/QSFM/7.11/103B
Determination of Compressive Strength of AAC Block
IS: 6441: 1972 (Part 5) RA 2017
SRAF NO 1129 Date 6/6/2020 Date of Testing From 7/6/2020 To 6-Apr
Rate of Loading during test shall be 0.5 to 2 kg/sq.cms (or 5.2 kN/sec)
Prior to testing the specimen shall be stored at room temperature until temperature equilibrium has been reached.
Five hours storage at room temperature is generally sufficient if the drying temperature applied has been 50 0C.
Observations
UP 152.42 150.34 152.86 22914.8 3502759.81 2348.0 2145.8 9.42 612.60 96.5 4.21
MID 152.04 150.46 152.42 22875.9 3486750.53 2345.6 2146.8 9.26 9.12 615.70 618.86 93.4 4.08 4.18
LOW 151.34 151.24 152.46 22888.7 3489605.35 2382.4 2192.4 8.67 628.27 97.2 4.25
UP 150.38 151.64 151.98 22803.6 3465694.65 2348.7 2168.7 8.30 625.76 94.3 4.13
MID 150.80 150.88 151.82 22752.7 3454315.52 2350.4 2158.7 8.88 8.87 624.93 626.45 94.7 4.16 4.23
LOW 150.28 151.40 151.34 22752.4 3443347.01 2368.7 2164.7 9.42 628.66 99.8 4.39
UP 150.24 150.88 151.42 22668.2 3432420.54 2346.8 2164.9 8.40 630.72 95.8 4.23
MID 150.34 151.46 151.56 22770.5 3451096.43 2375.4 2150.4 10.46 9.47 623.11 627.65 93.7 4.11 4.17
LOW 150.32 150.78 151.62 22665.2 3436505.14 2368.4 2162.0 9.55 629.13 94.6 4.17
Equipments
Vernier Caliper BIPL/ 05 CTM Loading Machine BIPL/34
Used :
Analyst By Checked By
(Asst. Manager/Technician) (Dy. Tech Manager)
FORMAT NO : BIPL/QSFM/7.11/103B
Determination of Compressive Strength of AAC Block
IS: 6441: 1972 (Part 5) RA 2017
SRAF NO 1129 Date 6/6/2020 Date of Testing From 7/6/2020 To 6-Apr
Rate of Loading during test shall be 0.5 to 2 kg/sq.cms (or 5.2 kN/sec)
Prior to testing the specimen shall be stored at room temperature until temperature equilibrium has been reached.
Five hours storage at room temperature is generally sufficient if the drying temperature applied has been 50 0C.
Observations
Analyst By Checked By
(Asst. Manager/Technician) (Dy. Tech Manager)