O P E R AT I O N A L CO N T I N U I T Y

ABB H+Line safety and reliability


Switchboards and devices for
medical locations

switchboards and devices for medical locations


ABB H+Line safety and reliability,

2 A B B H + L I N E S A F E T Y A N D R E L I A B I L I T Y S W I TC H B O A R D S A N D D E V I C E S F O R M E D I C A L LO C AT I O N S


ABB technology and safety
in hospital segment
Over ten years’ experience, state-of the- art solutions offered to the
most important Italian hospitals, a complete and performing range of
products: this is H+Line, an ABB products range specific for group 2
medical locations, where operational continuity and reliability are key
requirements for patients’ and medical staff’s safety and protection.

Helpful for designers The document has been developed in a tight collaboration
What Standards say is explained by everybody. ABB tells with ABB customers. The aim is to add practical solutions,
what Standards don’t say. The “Practical guide for group 2 ideas and plant design suggestions coming from the field to
medical locations” can be a useful daily tool to be consulted fundamental standards.
for supporting designers and installers in each step of the
design and installation process of group 2 medical locations Thus the “Practical guide to group 2 medical locations” turns
electrical plants into a real help, full of examples, and a useful tool even for
the ones designing hospital plants for the first time ever. In
the practical guide, ABB customers will find at their com-
plete disposal all the expertise of a leading company which
has always been promoting and sustaining safety.
A B B T E C H N O LO G Y A N D S A F E T Y 3
4 A B B H + L I N E S A F E T Y A N D R E L I A B I L I T Y S W I TC H B O A R D S A N D D E V I C E S F O R M E D I C A L LO C AT I O N S


Range overview
A wide range of reliable products assuring patients’ and medical
staff’s safety in intensive care units, operating theatres, first aid and
day hospital premises, ambulatories, nursing homes, dentist’s and vet’s.

— — —
01 ISOLTESTER-DIG 02 SELVTESTER-24 03 QSD-DIG 230/24
Insulation monitoring device Insulation monitoring device Remote signalling panel with luminous
for 230 V AC IT-M circuits for 24 V AC/DC SELV circuits and acoustic fault indicators
supplying scialytic lamps

— —
04 TI 05 QSO
Medical insulating transformers Wall-mounted and floor standing
supplying IT-M networks operating heatres switchboards to
supply and protect medical locations
ART
R A NIG
CLE EOOR
V E RCH
VIE
APWT ER T I TL E 5
6 A B B H + L I N E S A F E T Y A N D R E L I A B I L I T Y S W I TC H B O A R D S A N D D E V I C E S F O R M E D I C A L LO C AT I O N S


QSO Switchboards - S series
Details which make a difference
In order to satisfy the needs of group 2 medical locations, ABB supplies
preassembled wall-mounted and floor standing QSO electrical
switchboards, complete with TI insulating transformer and
ISOLTESTER-DIG-RZ insulation monitoring device to detect and signal
promptly the first fault to earth.
Q S O S W I TC H B O A R D S - S S E R I E S 7

Transparent cover panel Reduced depth


A split opening in the cover panel enables to operate on the The narrow depth of the enclosure makes the installation
modular devices without opening the compartment beneath easier even inside cupboards, compartments or recesses,
where the transformer and the terminal block are placed. thanks to the ArTu M series single-piece structure.

S750 DR-K miniature circuit-breakers Terminal block


The S750 DR main circuit-breaker placed in the upstream IT All terminal blocks have been studied in such a way as to
section of the insulation transformer ensures total selectiv- guarantee correct connections between all switchboard
ity up to 10 kA with all downstream circuit-breakers. They equipment, ensuring mechanical separation between the
can be equipped with a signalling contact in order to re- circuits.
motely control the status of the lever.

Transparent S750 DR-K


cover panel miniature
circuit-breakers

Reduced
depth

Terminal
block
8 A B B H + L I N E S A F E T Y A N D R E L I A B I L I T Y S W I TC H B O A R D S A N D D E V I C E S F O R M E D I C A L LO C AT I O N S


QSO Switchboards -
M and L series
Details which make a difference

S750 DR-K Lifting


miniature eyebolts
circuit-breakers

S200 residual
miniature
circuit-breakers

OVR surge
protection
device

DS200
residual current
breaker with
overcurrent
protection

M1175-FL
schuko socket
outlet

Cable
container

TI
insulating
transformer
Q S O S W I TC H B O A R D S - M A N D L S E R I E S 9

Safety lock

ArTu
Structure

Free
modules

ISOLTESTER
DIG-RZ
insulation
monitoring
device

SELVTESTER-24
insulation
monitoring
device

Alarms
monitoring
10 A B B H + L I N E S A F E T Y A N D R E L I A B I L I T Y S W I TC H B O A R D S A N D D E V I C E S F O R M E D I C A L LO C AT I O N S


QSO Switchboards -
M and L series
Details which make a difference

S200 miniature circuit-breakers M1175-FL schuko socket outlet


These protect the downstream circuits of the IT-M section QSO switchboards are equipped with a socket outlet which
against overloads and short-circuits, assuring reliability and is useful to supply measurement devices and tools used
safety during the operations. during maintenance. This socket is protected by an inte-
grated fuse and is equipped with an indicator lamp that al-
OVR surge protection device lows detecting whenever the auxiliary circuit has been sup-
It has been designed in order to safeguard the electrical sys- plied, even in the darkness.
tems and equipment from any transient and impulsive
over-voltages. Cable container
OVR surge protective devices, installed in both the emer- ArTu K series floor standing switchboards are equipped with
gency and safety sections, are coordinated with suitable a cable container that makes installation and wiring easier,
back up protection in order to avoid circuit overloads during both for the electrical systems distributed along the false
the devices useful life. All surge protective devices are cieling, as under the floor.
equipped with removable cartridges and signalling contacts It is possible to reach any terminal block in a comfortable
in order to optimize maintenance operations, and opera- way. Finally, there is a copper equipotential bonding busbar
tional continuity. which may lodge up to 20 additional connections, providing
grounding connections to all the external masses which are
S750 DR-K miniature circuit-breakers present in the medical premises, and avoiding the creation
The S750 DR main circuit-breaker placed in the upstream of further cascade sub-nodes that are not allowed.
IT-M section of the insulation transformer ensures total se-
lectivity up to 10 kA with all downstream circuit-breakers.
Furthermore it protects the insulating transformers from
overloads.
They can be equipped with a signalling contact in order to
remotely control the status of the lever (see page 51 for the
S750 DR selectivity table).
Q S O S W I TC H B O A R D S - M A N D L S E R I E S 11

TI insulating transformer SELVTESTER-24 insulation monitoring device


Specifically designed and assembled for medical use ac- QSO “Premium” are equipped with 24 V SELV line supplying
cording to the EN 61558-2-15, it ensures protection against the scialytic lamp.
indirect contacts without the need to interrupt the circuit SELVTESTER-24 monitors extremely low voltage circuits. IEC
automatically upon the first grounding fault. 60364-7-710 reference standard does not impose monitor-
Thanks to its two PT100 temperature probes, on primary ing of such circuits, but, it is possible that during regular
and secondary winding, it is possible to monitor the trans- handling of the lamp some conductors, detaching them-
former over temperature produced by any eventual overload, selves from the terminals, may enter into contact with the
and therefore anticipating any breakdown. The transformer metal housing. Therefore SELVTESTER-24 detects the dam-
is mounted on the base of the switchboard in order to ease age as soon as it happens, and consequently improve opera-
handling and installation operations. tional continuity.

DS200 residual current breaker with overcurrent Alarms monitoring


protection High end configurations are equipped with I/O modules for
They protect emergency section TN-S terminal circuits from alarms management. In particular it is possible to control
any direct and indirect contacts. These lines feed the light- the status of the main circuit-breaker and signalling con-
ing system, the radiological and the general purpose socket tacts of the OVR and ISOLTESTER-DIG, by means of the KNX
outlets, mounted outside the patients’ environment. bus.

Lifting eyebolts ArTu Structure


They allow immediate and safe wall fastening. Floor standing QSO switchboards are composed of modular
ArTu K series enclosures. The switchboards are equipped
ISOLTESTER-DIG-RZ insulation monitoring device with venting grooves that guarantee proper natural convec-
This is an insulation monitoring device for group 2 medical tion, useful to dissipate the heat produced by the trans-
locations fully compliant with the IEC 60364-7-710 reference former during its normal functioning.
standard. It integrates all the performances established by
the reference standard, such as overload and overcurrent Free modules
monitoring, together with traditional IT system earthing in- Switchboard flexibility is ensured by the possibility of in-
sulation measurement. serting further equipment that may be necessary to com-
plete the system or for possible future expansions.
Safety lock
This is a door with a key lock system in order to avoid unde- E210 indicator lamp
sired interventions by non authorized personnel. Thanks to the green LED indicator lamp it is possible to see
in a blink whether the switchboard is supplyed or not.
12 A B B H + L I N E S A F E T Y A N D R E L I A B I L I T Y S W I TC H B O A R D S A N D D E V I C E S F O R M E D I C A L LO C AT I O N S


QSO Switchboards and devices
for medical locations
Protection by electrical separation as laid down by IEC 60364 reference
standard (user electrical plants with a rated voltage of no more than 1000
V in alternating current and 1500 V in direct current) prevents the
generation of hazardous currents due to contacts with earths under
voltage because of a fault in the main insulation of the circuit.

By using insulating transformers, the protection against QSO switchboards represent the ideal solution for all
indirect contacts can be guaranteed without having to medical locations classified by the IEC 60364-7-710
automatically break the circuit at the first fault to earth. reference standard, as group 2 medical locations
Insulating transformers are therefore suitable for use in (anaesthesia, surgery, preoperative preparation, surgical
plants where the sudden and automatic breaking of the plaster applications, postoperative wakening, heart
service may have serious implications: examples of these catheterizations, intensive care, angiography and blood flow
applications are plants for medical and surgery rooms (in tests, premature births) where the use of an IT-M (Medical
accordance with IEC 60364-7-710 reference standard where IT) system is mandatory. In addition, they are suitable for
specific electromedical devices perform patients’ installation in any further medical locations and any other
monitoring and attending functions. To meet the special room where the automatic breaking of the service at the
needs of these fields of application, ABB supplies first fault to earth is dangerous or inconvenient: industrial
preassembled wall-mounted and floor-standing QSO laboratories, craft workshops (jewellery’ and the like), test
switchboards, complete with an insulation transformer and laboratories, school laboratories, research institutes and
an ISOLTESTER-DIG device to detect and signal the first any other room with similar problems.
fault to earth.

IT-M system

Supply
IT-M for group 2
medical locations

TEST pushbutton

Medical Insulation
insulating monitoring device
transformer
MUTE pushbutton

TEST pushbutton

Remote signalling
panel

MUTE pushbutton

Equipotential
bonding
P R OT E C T I O N , C O N T R O L A N D O P E R AT I O N A L C O N T I N U I T Y 13


Protection, control and
operational continuity
The new QSO operating theatre switchboards are the ideal solution to
supply operating theatres and group 2 medical locations according to
the IEC 60364-7-710 reference standard.

All the switchboards are wired by ABB, and are equipped Compactness, total protection selectivity and maximum
with the declaration of conformity which is necessary for the ergonomics and simplicity during maintenance operations
system initial start up, guaranteeing the installer full make QSO range the most suitable product to guarantee
conformity for plant performance. service continuity at medical locations.
14 A B B H + L I N E S A F E T Y A N D R E L I A B I L I T Y S W I TC H B O A R D S A N D D E V I C E S F O R M E D I C A L LO C AT I O N S


QSO S
01 Wall-mounted switchboards of 3 kVA and 5 kVA for applications such as
surgery ambulatories, recovery rooms, test laboratories, dentist’s and vet’s

FROM GENERAL
SWITCHBOARD FROM UPS

1 2 3

10
6

11

4
QSO S 15

1 Lighting circuit 7 Anaesthetist’s up-mount 2


2 General purpose sockets 8 Medical sockets group
3 Radiological sockets 9 Bed-head
4 Surgical up-mount 1 10 Negatoscope screen
5 Surgical up-mount 2 11 Scialytic lamp
6 Anaesthetist’s up-mount 1

4 5 6 7 8 9 10 11

7
16 A B B H + L I N E S A F E T Y A N D R E L I A B I L I T Y S W I TC H B O A R D S A N D D E V I C E S F O R M E D I C A L LO C AT I O N S


QSO M
Floor standing switchboards of 3 kVA, 5 kVA and 7,5 kVA, for day hospital
premises, medium-size operating theatres, intensive care units.

FROM GENERAL
SWITCHBOARD FROM UPS

1 2 3 4 5 6

13

15 2

12 6

16
8

18

10

14 7

4
11
QSO M 17

1 Lighting circuit 7 Anaesthetist’s up-mount 2 13 Stopwatch


2 General purpose sockets 8 Medical plugs group 1 14 Electric bed
3 Radiological sockets 9 Medical plugs group 2 15 Reserve
4 Surgical up-mount 1 10 Medical plugs group 3 16 Bed-head
5 Surgical up-mount 2 11 Medical plugs group 4 17 Various
6 Anaesthetist’s up-mount 1 12 Negatoscope screen 18 Scialytic lamp

7 8 9 10 11 12 13 14 15 16 17

18

17

5
18 A B B H + L I N E S A F E T Y A N D R E L I A B I L I T Y S W I TC H B O A R D S A N D D E V I C E S F O R M E D I C A L LO C AT I O N S


QSO L
Floor standing switchboards of 7,5 kVA and 10 kVA for operating theatres,
intensive care units, cardiac surgeries, long-term hospitalizations.

FROM GENERAL
SWITCHBOARD FROM UPS

1 2 3 4 5 6 7

13

9
20
19

24 16 3 10

6
8 12

2 23

22

15 21

4
QSO L 19

1 Lighting circuit 7 Anaesthetist’s up-mount 2 13 Stopwatch 19 TV and radio plugs


2 General purpose sockets 8 Medical plugs group 1 14 Motorized door 20 Reserve
3 Radiological sockets 9 Medical plugs group 2 15 Surgical up-mount motor 21 Infusion pump
4 Surgical up-mount 1 10 Medical plugs group 3 16 Anaesthetist’s up-mount motor 22 Scialytic lamp 1
5 Surgical up-mount 2 11 Medical plugs group 4 17 Bed plug 23 Scialytic lamp 2
6 Anaesthetist’s up-mount 1 12 Negatoscope screen 18 Various 24 Local section
switchboard supply

8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23

24

11

14

15

17

5
18
20 A B B H + L I N E S A F E T Y A N D R E L I A B I L I T Y S W I TC H B O A R D S A N D D E V I C E S F O R M E D I C A L LO C AT I O N S

• Safety and service continuity: thanks to certified • Reliability: the quality of ABB technology in every
insulation transformer,QSO portfolio is a complete and component
high performing solution to assure safety and operation • Compact size: limited overall dimensions
continuity in group 2 medical locations where patient’s life • Completeness: 24 V line control, PT100 probes embedded
is the most important thing • Effectiveness: complete electrical network monitoring
• Flexibility: available in different versions (S, M and L sizes;
Classic and Premium series), customizable to meet any
customer need
QSO L 21
22 A B B H + L I N E S A F E T Y A N D R E L I A B I L I T Y S W I TC H B O A R D S A N D D E V I C E S F O R M E D I C A L LO C AT I O N S


ISOLTESTER-DIG
Medical insulation monitoring
devices
ISOLTESTER-DIG is the insulation monitoring device specifically
designed by ABB for group 2 medical locations. ISOLTESTER-DIG
measures the insulation to earth in IT-M network and the thermal and
electrical overload of the insulation transformer, in accordance with the
international standards: EN 61557-1, EN 61557-8 and IEC 60364-7-710.

Functioning principle For better integration and improved monitoring


Insulation resistance is measured by applying a direct cur- Thanks to the RS485 serial port, the ISOLTESTER-DIG-RS is
rent signal between insulated line and earth and determin- able to communicate with the supervision system via
ing the dispersion current generated. Effective ModbusRTU in order to collect all the required information
measurement is granted thanks to a digital filter integrated of the monitored IT-M system in a centralized place. It also
in the device even if interferences and harmonic compo- improves the monitoring activity with the possibility of log­
nents occur. ging mesaurements (max. and min. values). Logs can then
be sent to the centralized control system via the
Programming communica­tion protocol.
Through its LCD display and four selection keys, the device
offers easy programming possibilities by setting interven- For higher safety
tion thresholds without making any for the complete moni- Thanks to a codified signal, the new ISOLTESTER-DIG-PLUS
toring of all electrical parameters. ISOLTESTER-DIG tests IT networks insulation monitoring device grants absolute re-
the thermal and electrical overload of the medical insulation liability of measurement in any operational condition, even if
transformer, managing two temperature thresholds coming high network interferences occur. Furthermore it is fitted
from both PT100 and PTC probes. By controlling tempera- with a RS485 serial port through which it can be perfectly in-
ture, the overload of the transformer can be monitored and tegrated with communication systems such as PLC/PC by
the automatic circuit-breaker downstream of the secondary using ModbusRTU protocol. The measurement of network
can be avoided. All faulty conditions are remotely controlled maximum and minimum values enables a wider monitoring
thanks to QSD-DIG 230/24 remote signalling panels, grant- and an easier plant checking in case of any fault. Finally, the
ing a proper prompt technical supervision. programmable output relay allows to manage any warning
condition signalled in a dedicated way.
Self-testing system
Error-Link Fail system checks device proper functioning and • Quality: the recognized standard in hospital insulation
controls wiring presence and properness at the end of the control
terminal blocks: it prevents the possibility to operate in • Flexibility: adjustable intervention thresholds according
group 2 medical locations when the insulation monitoring to all the parameters monitored
device is disconnected. • Completeness: all electrical and thermal parameters
controlled by a single device
• Integration: alarms sent up to 4 medical locations
attended by medical and healthy staff, thanks to remote
signalling panels. Only for RS and PLUS versions, ablility to
interact with supervising systems through ModbusRTU
protocol via RS485 serial port
I S O LT E S T E R - D I G 23


ISOLTESTER-DIG
Frontal operators functioning

Green LED, SET: Yellow LED, Alarm:


Tool programming Parameter out
status of threshold

3 digit display Red LED, Output Relay:


Auxiliary relay status

Red LED, R:
Insulation Red LED, Error/Link Fail:
resistance (kΩ) Internal fault alarm,
faulty wiring to the line to
be controlled, PT100
temperature probe open
or under short-circuit
Red LED, Z:
Insulation impedance
and line capacity
(only for ISOLTESTER-
DIG-PLUS) TEST | ENTER:
Device and remote
signalling panels testing
and SETUP settings
Red LED, T1: confirmation
Primary winding
temperature control

RESET | SET:
Device programming
Red LED, T2: access, alarm disconnection
Secondary winding and memorized values
temperature control cancellation

Red LED, I:
Line current +/-:
Selection of the parameter
to be displayed, settings
adjustment and memorized
maximum and minimum
Easy programming values display (only for
by four pushbuttons ISOLTESTER-DIG-PLUS/RS)
24 A B B H + L I N E S A F E T Y A N D R E L I A B I L I T Y S W I TC H B O A R D S A N D D E V I C E S F O R M E D I C A L LO C AT I O N S


ISOLTESTER-DIG-PLUS
The solution to unwanted alarms
Wherever it is necessary to guarantee safety and operational continuity
and prevent power supply interruptions, such as in hospitals and in
other medical locations, insulation transformers and devices detecting
and signalling any first fault to earth have to be used.

Operating theaters equipment A traditional monitoring device


can generate interference can generate an unwanted
within the network alarm in operating theaters

Risks arising from the use of a traditional insulation monitor:

Imposibility to distinguish between


interference and real fault

Carelessness of the medical staff

Unjustified intervention of
specialized technical stuff
IASROTLT
I CE
LES TOERR -CDHI G
AP- PTLU
E RST I T L E 25

ISOLTESTER-DIG-PLUS is the device for insulation monitoring in IT-M


networks. It ensures absolute reliability of measurement by means
of a codified signal able to detect interferences generated by common
equipment in operating theatres and avoid unwanted alarms signalling.

Despite network interferences... ISOLTESTER-DIG-PLUS avoids


unwanted alarms.

Advantages of ISOLTESTER-DIG-PLUS:

Monitoring reliability

Integration with supervision


systems

Proper fault analysis

Complete control of network


parameters
26 A B B H + L I N E S A F E T Y A N D R E L I A B I L I T Y S W I TC H B O A R D S A N D D E V I C E S F O R M E D I C A L LO C AT I O N S


SELVTESTER-24
Medical insulation monitoring
device for scialytic lamps
SELVTESTER-24 tests the insulation to earth of 24 V AC/DC SELV circuits
dedicated to scialytic lamps supply. Scialytic lamps insulation has to be
monitored in order to prevent detaching from conductors when being
moved. The conductors, by contact with the metal structure of the
lamp, may transfer a potential of over 250 V, resulting in damage to
equipment and people.

SELVTESTER-24 measures the variation in potential of the • Flexibility: programmable alarm threshold
two network polarities with reference to earth in order to • Intelligence: recognition of faulty pole in direct current
signal when insulation drops below a set value, through the • Compact size: fits into just 3 modules
frontal microbreakers, identifying the faulty pole in direct • Practicality: extremely easy to install and use
current. The output signal can be connected to QSD-DIG • Integration: ideal complement for ISOLTESTER-DIG
230/24 remote signalling panel. The frontal panel of the de-
vice carries out test pushbutton, status indicator and two
LEDs for low insulation signalling.

Frontal operators functioning

Microbreakers Green LED ON


The front microbreakers allow the Indication that the instrument
threshold to be set in the range 10 is working properly
to 50 kΩ, as shown in the picture below.

10 kΩ 40 kΩ
Yellow LED ALARM
Low insulation alarm signal;
in the case of a line to be monitored,
with alternating current the two
LEDs light up, whereas with direct
20 kΩ 50 kΩ current only the LED of the polarity
below the activation threshold
lights up.

30 kΩ
TEST pushbutton
Instrument correct functioning test
Q S D - D I G 2 3 0/ 2 4 27


QSD-DIG 230/24
Remote signalling panel
QSD-DIG 230/24 remote signalling panel enables to send alarm signals
from the insulation monitoring devices to all the medical locations
attended by medical staff, as laid down by reference standards.

QSD-DIG 230/24 panel provides an acoustic and luminous • Compact size: limited dimensions
signaling in case of low insulation or thermal and electrical • Easy to install: installation in a universal 3-module flush-
overload. Moreover, it is provided with a TEST pushbutton to mounted box type E503, in horizontal or vertical position
periodically check its operating status and a pushbutton for • Reliability: prompt fault recognition
disconnecting the acoustic signal. It is assembled in univer- • Comfort: simultaneous disconnection of more signalling
sal 3-module flush-mounted boxes. panels
• Operational efficiency: both visual nd acoustic signalling

Frontal operators functioning

TEST Green LED


Pushbutton device is working
properly

Red LED
overload alarm

MUTE Yellow LED


Pushbutton fault alarm
28 A B B H + L I N E S A F E T Y A N D R E L I A B I L I T Y S W I TC H B O A R D S A N D D E V I C E S F O R M E D I C A L LO C AT I O N S


TI
Insulating transformers
Medical single-phase insulating transformers provide galvanic
separation between the distribution network and the user load in
accordance with the EN 61558-1 and EN 61558-2-15 reference standards
concerning power supply in group 2 medical locations.

ABB medical insulating transformers combine conformity • Specialization: especially designed for
with reference standards to maximum performance and lim- medical use
ited dimensions thanks to which it is thus possible to reduce • Compact size: the overall dimensions of the insulation
switchboards costs. The range is made up of transformers transformers installed in ABB QSO switchboards are the
with 3, 5, 7, 5 and 10 kVA power, available with two PT100 most compact on the market
temperature probes, on the primary and the secondary • Quality: the insulation of the windings, realized with the
winding, thus enabling continuous and precise temperature exclusive vacuum pressure technology, guarantees
monitoring. ABB transformers are provided with a particular maximum heat dissipation
impregnation system which allows maximum heat dissipa- • Accessories: versions available with PT100 probes
tion thanks to the exclusive vacuum pressure technology.
Finally, the insulating transformer has a metallic shield be-
tween the two windings allowing to reduce network inter-
ferences and harmonic components coming from the sup-
ply. Upon communication of the item serial number, ABB will
provide the testing certificates of each medical insulation
transformer.

1
2 1 Primary winding
0-230: Primary
3 SCH: Metallic shield
4
2 PE
5
3 Secondary winding
0-230: Secondary
SCH: Central socket

4 Probe 1
1: to ISOLTESTER-DIG 28 terminal block
2: to ISOLTESTER-DIG 28 terminal block
3: to ISOLTESTER-DIG 30 terminal block

5 Probe 2
4: to ISOLTESTER-DIG 25 terminal block
5: to ISOLTESTER-DIG 25 terminal block
6: to ISOLTESTER-DIG 27 terminal block

Serial number
printed on the label attached at the
metallic base, to be provided when
requesting testing certificate
Q S O S W I TC H B O A R D S 29


QSO Switchboards
Technical features

Type Power [kVA] Installation TN-S section feeder lines IT-M section feeder lines Net weight [kg]
QSO 3S Classic 3 wall mounted 2x10A+5x16A+1x25A 73
QSO 5S Classic 5 wall mounted 2x10A+5x16A+1x25A 88
QSO 3S Premium 3 wall mounted 1X10A+2x16A 2x10A+5x16A+1x25A 75
QSO 5S Premium 5 wall mounted 1X10A+2x16A 2x10A+5x16A+1x25A 90
QSO 3M Classic 3 floor standing 1x10A 3x10A+7x16A 126
QSO 5M Classic 5 floor standing 1x10A 3x10A+7x16A 141
QSO 7.5M Classic 7.5 floor standing 1x10A 3x10A+7x16A 147.5
QSO 3M Premium 3 floor standing 1X10A+2x16A 6x10A+8x16A+1x25A 127
QSO 5M Premium 5 floor standing 1X10A+2x16A 6x10A+8x16A+1x25A 142
QSO 7.5M Premium 7.5 floor standing 1X10A+2x16A 6x10A+8x16A+1x25A 147.5
QSO 10L Classic 10 floor standing 1X10A+2x16A 6x10A+9x16A 190
QSO 7.5L Premium 7.5 floor standing 1X10A+2x16A 6x10A+11x16A+3x25A+1x32A 168
QSO 10L Premium 10 floor standing 1X10A+2x16A 6x10A+11x16A+3x25A+1x32A 193.5

Wall-mounted QSO Wall-mounted QSO Floor standing QSO


Operating rated voltage (Ue ) 230 V ~ ± 15%
Network rated frequency 50 - 60 Hz
Number of phases 1 + N ~⁄ PE
Rated voltage of service auxiliary circuits 24 - 230 V ~
Insulation rated voltage (Ul) 300 V - *2500 V
Grounding power system TT / TN-S
Expected maximum short circuit current for input terminals (Icc) 10 kA RMS Sym **
Maximum height 2000 m a. s. l.
Pollution level 1 ***
Impact resistance level (code IK) EN 50102 IK 09 (5kg - 200mm)
Humidity level related with temperature expressed in ° C Internal mounting 50% with maximum temperature of +40°C
Operating room air temperature -5°C - +55°C
Transport and storage room air temperature -25°C - +40°C
Protection level of the front IP EN 60529 QSO 3S Classic IP 40 QSO 3M Classic IP 54
QSO 5S Classic IP 40 QSO 5M Classic IP 54
QSO 3S Premium IP 40 QSO 5M Premium IP 54
QSO 5S Premium IP 40 QSO 7.5M Premium IP 54
QSO 10L Classic IP 54
QSO 7.5L Premium IP 54
QSO 10L Premium IP 54
* Dielectric strength testing voltage.
** Value subject to upstream coordination with fuse NH 00 100A gL-gG
*** It corresponds to absence of pollution or only to dry pollution and non conducting pollution.
30 A B B H + L I N E S A F E T Y A N D R E L I A B I L I T Y S W I TC H B O A R D S A N D D E V I C E S F O R M E D I C A L LO C AT I O N S


QSO Switchboards
Overall dimensions

QSO S QSO M

924 250

700 200

1796
1100

QSO L

948 362
2031
Q S O S W I TC H B O A R D S 31


QSO Switchboards
Wiring diagrams
QSO S diagram

SD202/63 SD202/40

E 91hN/32

E 219-D
S752 DR-K25

E 91hN/32
PT100
TI 5-S

ISOLTESTER-DIG-RZ QSD-DIG 230/24

E 219-D Id Id Id

SD202/40
DS202C DS202C DS202C E 91hN/32
C10 A30 C16 A30 C16 A30
CT PRO XT40


Devices within dashed areas are provided S202 S202 S202 S202 S202 S202 S202 S202
only with “Premium” version. C16 C16 C16 C16 C16 C10 C10 C25

Description QSO 3S QSO 5S QSO 3S QSO 5S


Classic Classic Premium Premium
2P 40 A SD202/40 disconnector 2 2 2 2
2P 63 A SD202/63 disconnector 1 1
E 91hN/32 fuse-holder 2 2 3 3
E219-D green light indicator power supply presence 1 1 2 2
ISOLTESTER-DIG-RZ insulation monitoring device 1 1 1 1
6 kA 2P C10 S202 miniature circuit-breaker 2 2 2 2
6 kA 2P C16 S202 miniature circuit-breaker 5 5 5 5
6 kA 2P C25 S202 miniature circuit-breaker 1 1 1 1
25 kA 2P S752 DR-K25 miniature circuit-breaker 1 1 1 1
1N 10 A 0,03 A DS202 C C10 A30 residual current breaker with overcurrent protection 1 1
1N 16 A 0,03 A DS202 C C16 A30 residual current breaker with overcurrent protection 2 2
AMM damper set 4 4 4 4
CT PRO XT40 current transformer 1 1 1 1
Medical insulation transformer with 3000 VA 230/230 V TI 3-S probes 1 1
Medical insulation transformer with 5000 VA 230/230 V TI 5-S probes 1
10 x 38 gG 2A E 9F10 GG2 fuse 4 4 6 6
32 A B B H + L I N E S A F E T Y A N D R E L I A B I L I T Y S W I TC H B O A R D S A N D D E V I C E S F O R M E D I C A L LO C AT I O N S

QSO M diagram
SD202/63
SD202/63

E 91hN/32
S202 C10

E 91hN/32 S202 C10


S752 DR-K
E219-D
OVR T2-T3 1N
20-275 P QS
TI 3-S PT100
Id Id Id
TI 5-S
E 219-D M1175-FL TI 7,5-S
ISOLTESTER-DIG-RZ QSD-DIG 230/24
DS202C DS202C DS202C OVR T2-T3 1N
C10 A30 C16 A30 C16 A30 20-275 P QS

SD202/40

E 91hN/32
CT PRO XT40

TM-S 1000/12-24 P

E 91hN/32

S202 S202 S202 S202 S202 S202 S202 S202 S202 S202 S202 S202
SELVTESTER-24
C16 C16 C16 C16 C16 C16 C16 C10 C16 C10 C10 C10

S202
Devices within dashed areas are provided C25
only with “Premium” version.

Description QSO 3M QSO 5M QSO 7,5M QSO 3M QSO 5M QSO 7,5M


Classic Classic Classic Premium Premium Premium
2P 63 A SD202/63 disconnector 3 3 3 3 3 3
E 91hN/32 fuse-holder 3 3 3 4 4 4
E219-D green light indicator power supply presence 2 2 2 2 2 2
ISOLTESTER-DIG-RZ insulation monitoring device 1 1 1 1 1 1
24 V SELVTESTER-24 insulation monitoring device 1 1 1
OVR T2-T3 1N 20-275 P QS surge protective device 2 2 2
6 kA 2P C10 S202 miniature circuit-breaker 3 3 3 8 8 8
6 kA 2P C16 S202 miniature circuit-breaker 7 7 7 8 8 8
6 kA 2P C25 S202 miniature circuit-breaker 1 1 1
M1175-FL 2P+T 16 A schucko socket with indicator lamp and fuse 1 1 1 1 1 1
25 kA 2P S752 DR-K25 miniature circuit-breaker 1 1 1 1
25 kA 2P S752 DR-K40 miniature circuit-breaker 1 1
1N 10 A 0,03 A DS202 C C10 A30
residual current breaker with overcurrent protection 1 1 1 1 1 1
1N 16 A 0,03 A DS202 C C16 A30
residual current breaker with overcurrent protection 2 2 2
AMM damper set 4 4 4 8 8 8
CT PRO XT40 current transformer 1 1 1 1 1 1
TM-S 1000/12-24 P. 230-400V S. 24V control and safety transformer 1 1 1
Medical insulating transformer with 3000 VA 230/230 V TI 3-S probes 1 1
Medical insulating transformer with 5000 VA 230/230 V TI 5-S probes 1 1
Medical insulating transformer with 7500 VA 230/230 V TI 7,5-S probes 1 1
10 x 38 gG 2A E 9F10 GG2 fuse 6 6 6 8 8 8
A RSTOI CSLWEI TC
Q O RHCBH
OAAPRTDESR T I T L E 33

QSO L diagram
SD202/63
SD202/63

E 91hN/32

E 91hN/32 S202 C10


S202 C10
S752 DR-K
E 219-D
BE/S SA/S
Id Id Id PT100 4.20.2.1 4.10.1
OVR T2-T3 1N TI 7,5-S
20-275 P QS TI 10-S
E 219-D M1175-FL

DS202C DS202C DS202C


C10 A30 C16 A30 C16 A30 E 91hN/32

E 202/40g
OVR T2-T3 1N
20-275 P QS
CT PRO XT50 ISOLTESTER-DIG-RZ QSD-DIG 230/24

TM-S 1000/12-24 P

E 91hN/32

— S202 S202 S202 S202 S202 S202 S202 S202 S202 S202 S202 S202 S202 S202 S202 S202 S202 S202 S202 S202
SELVTESTER-24
C16 C16 C16 C16 C16 C16 C16 C16 C16 C10 C10 C10 C10 C10 C10 C16 C16 C25 C25 C32
Devices within dashed
areas are provided only S202
C25
with “Premium” version.

Description QSO 10L QSO 7.5 L QSO 10 L


Classic Premium Premium
2P 63 A SD202/63 disconnector 3 3 3
E 91hN/32 fuse-holder 3 4 4
E219-D green light indicator power supply presence 2 2 2
BE/S 4.20.2.1 4 channel binary input terminal 1
ISOLTESTER-DIG-RZ insulation monitoring device 1 1 1
24 V SELVTESTER-24 insulation monitoring device 1 1
10 A SA/S 4.10.1 4 channel output terminal 1
OVR T2-T3 1N 20-275 P QS surge protective device 2 2
S2-CS/H6R auxiliary contact 1 exchange 1
6 kA 2P C10 S202 miniature circuit-breaker 6 8 8
6 kA 2P C16 S202 miniature circuit-breaker 9 11 11
6 kA 2P C25 S202 miniature circuit-breaker 3 3
6 kA 2P C32 S202 miniature circuit-breaker 1 1
M1175-FL 2P+T 16 A schucko socket with indicator lamp and fuse 1 1 1
25 kA S752 DR-K40 miniature circuit-breaker 1
25 kA S752 DR-K50 miniature circuit-breaker 1
25 kA S 752 DR-K50+S750DR-AUX miniature circuit-breaker 1
1N 10A 0,03A DS202 C C10 A30 residual current breaker with overcurrent protection 1 1 1
1N 16A 0,03A DS202 C C16 A30 residual current breaker with overcurrent protection 2 2 2
AMM damper set 4 8 8
CT PRO XT50 current transformer 1 1 1
TM-S 1000/12-24 P. 230-400 V S.24 V control and safety transformer 1 1
Medical insulating transformer with 7500 VA 230/230 V TI 7,5-S probes 1
Medical insulating transformer with 10000 VA 230/230 V TI 10-S probes 1 1
10 x 38 gG 2A E 9F10 GG2 fuse 6 8 6
34 A B B H + L I N E S A F E T Y A N D R E L I A B I L I T Y S W I TC H B O A R D S A N D D E V I C E S F O R M E D I C A L LO C AT I O N S


ISOLTESTER-DIG
Technical features

Technical features ISOLTESTER-DIG-RZ ISOLTESTER-DIG-PLUS/RS


Supply voltage/frequency 110 - 230 V/50-60 Hz
Network voltage to be controlled 24 ÷ 230 V AC
Maximum voltage measurement 24 V
Maximum current measurement 1 mA
Maximum internal resistance 100 kΩ
Insulation voltage 2,5 kV/60 seconds
Control signal type Continuous component with digital filter Codified composite signal (only PLUS)
Sensed measures Insulation measurement range 0÷999 kΩ/HIGH – resolution 1 kΩ
Temperature measurement by Rd PT100 or 2/3-wire thermal-probe – 0÷200°C, accuracy 2%
Current measurement by external CT with secondary 5 A, accuracy 5%
(selectable CT ratio 1÷40)
Impedance measurement 0÷999 kΩ/HIGH - Impedance measurement 0÷999 kΩ/HIGH -
resolution 1 kΩ (test signal 2500 Hz) resolution 1 kΩ (variable composite signal)
Intervention threshold Low insulation 50÷500 kΩ, accuracy 5%, hysteresis 10%, settable delay
Overtemperature 30 ÷ 200°C, accuracy 2%
Current overload 1 ÷ 99.9 A, accuracy 2%
Low impedance (deactivable)
Device not connected to the line (Error/Link-Fail)
Available outputs Up to maximum 4 QSD panels for remote signalling
Programmable auxiliary relay output NA-C-NC, Programmable auxiliary relay output NA-
5A, 250 V AC C-NC, 5A, 250 V AC,
RS 485 serial output, standard ModbusRTU
protocol
Displays Insulation resistance value signalling over full scale and fault to earth
Measured temperature value 0 ÷ 200°C for channel 1
Measured temperature value 0 ÷ 200°C for channel 2
Measured current value 0 ÷ 99.9 A
Insulation impedance value (only PLUS)
Setting parameters
Device failing connection to the line (Error/Link-Fail)
Relay output status
Line-to-earth capacity value
Minimum insulation and maximum
temperature
and current values
Connections Maximum linkable section 2,5 mm2
Operating temperature -10...60 °C
Storage temperature -25...70 °C, humidity < 90%
Overall dimensions 6 DIN MODULES
Weight 0,4 kg 0,5 kg
Casing Self-extinguishing plastic case to be assembled on 35 mm DIN rail,
with transparent lead-sealable protective front cover
Degree of protection IP20
Self-consumption 5 VA
Reference standards IEC 60364-7-710; EN 61557-1; IEC EN 61557-8
IASROTLT
I CE
LES TOERR -CDHI G
APTER TITLE 35


ISOLTESTER-DIG
Technical features

Wiring diagrams

19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36

RS485 2 1 T.A. .../5 A RS485 2 1 T.A. .../5 A


(only PLUS/RS PT100 PT100 Out (only PLUS/RS PT100 PT100 Out
version) version)
ISOLTESTER-DIG-RZ ISOLTESTER-DIG-RZ
Checking ISOLTESTER-DIG-PLUS Checking ISOLTESTER-DIG-PLUS
faulty QSD-DIG 230/24
V aux.* V aux.*
faulty ISOLTESTER-DIG-RS QSD-DIG 230/24 V aux.* ISOLTESTER-DIG-RS
connection Insulation connection Insulation
115 V 115 V 115 V 115 V to the line monitoring QSD-DIG 230/24 115 V 115 V to the line monitoring QSD-DIG 230/24

1 2 3 4 5 6 7 8 9 10 11 1 2 13 14 15 16 17 18 1 2 3 4 5 6 7 8 9 10 11
1 2 3 4 1 2 3 4 5 6 7 8 9 10 11 1 2 13 14 15 16 17 18 1 2 3 4 5 6 7 8 9 10 11

V aux. 230 V AC

To other QSD-DIG
To other QSD-DIG
V aux. 115 V AC V aux. 230 V AC

PE
PE

S S
S S
C.T.
C.T.
L
L
PC IT-M Loads
IT-M Loads
N
N

Insulation transformer
Insulation transformer without central socket

— —
Transformer with central socket Transformer without central socket

19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36

RS485 2 1 T.A. .../5 A


(only PLUS/RS PT100 PT100 Out.
version)
ISOLTESTER-DIG-RZ
Checking ISOLTESTER-DIG-PLUS
faulty ISOLTESTER-DIG-RS QSD-DIG 230/24
V aux.*
connection Insulation
115 V 115 V to the line monitoring QSD-DIG 230/24

1 2 3 4 5 6 7 8 9 10 11 1 2 13 14 15 16 17 18 1 2 3 4 5 6 7 8 9 10 11
To other QSD-DIG

V aux. 230 V AC

PE

S S

N
L3 IT-M Loads
L2
L1
Insulation transformer


3-phase transformer

* Optional wiring of temperature probes and current transformers

Overall dimensions

61
90

90

45

44
105
56
6 modules
36 A B B H + L I N E S A F E T Y A N D R E L I A B I L I T Y S W I TC H B O A R D S A N D D E V I C E S F O R M E D I C A L LO C AT I O N S


SELVTESTER-24
Technical features

Technical features SELVTESTER-24


Network voltage and auxiliary supply 24 V AC/DC
Frequency 50-60 Hz
Maximum self-consumption 3 VA
Maximum measurement current 0,5 mA
Internal impedance 50 kΩ
Intervention threshold 10 ÷ 50 kΩ 4 levels
Intervention delay 1s
Signals LED ON, LED ALARM +, LED ALARM -
Output maximum 24 V 1 A
Remote signalling panels maximum 2 QSD-DIG 230/24
Operating temperature -10 ÷ 60 °C
Storage temperature -20 ÷ 70 °C
Relative humidity ≤ 95%
Insulation test 2,5 kV 60 s / 4 kV imp. 1,2/50 μs
Terminal blocks section 4 mm2
Degree of protection front IP40 with cover / IP20 case
Modules 3
Weight 200 g
Reference standards IEC 60364-7-710; EN 61557-1; EN 61557-8

Wiring diagrams

SELVTESTER-24 QSD-DIG 230/24

1 2 3 4 5 6 7 8 9 10 11 1 2 3 C1 C2 C3 C4 X Y Z
To other QSD-DIG 230/24

PE

S S

L(+)
IT-M Loads
N(-)

Insulation transformer

Overall dimensions
85,5

85,5
45

44
52,5
58
3 modules
A RSTDI-CDLIEG O
Q 2R3 0/
CH24
APTER TITLE 37


QSD-DIG 230/24
Technical features

Technical features QSD-DIG 230/24


Signals Green LED NETWORK; Red LED overload ALARM; Yellow LED FAULT ALARM; Low insulation; Acoustic
signaller; Emission 2400 Hz; Intermittence 2 Hz dB
Pushbuttons Testing (TEST), acoustic disconnection (MUTE)
Terminal blocks section 2,5 mm2
Degree of protection IP30
Installation E503universal 3-module flush-mounted box
Weight 2 200 g
Operating temperature -10 ÷ 60 °C, maximum humidity 95%
Storage temperature -25 ÷ +80 °C
Insulation 2.500 V rms 50 Hz for 60 s
Connection UTP cable (recommended)
Cable minimum section 0,35 mm² (maximum 300 m)
Reference standards IEC 60364-7-710, EN 61557-1, EN 61557-8

Wiring diagrams

SEL VTESTER-24 QSD-DIG 230/24


19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36

RS485 2 1 T.A. .../5 A


(only PLUS/RS PT100 PT100 Out 1 2 3 4 5 6 7 8 9 10 11 1 2 3 4 5 6 7 8 9 10 11
version) V+ V- OUT- OUT- OUT- P COM- F- PV- ACUS ACK OVER FAULT COMP TEST- TEST- TEST+
ISOLTESTER-DIG-RZ NO C NC E S S - S
Checking ISOLTESTER-DIG-PLUS
V aux.* V aux.*
faulty ISOLTESTER-DIG-RS QSD-DIG 230/24
connection Insulation
115 V 115 V 115 V 115 V to the line monitoring QSD-DIG 230/24

1 2 3 4 1 2 3 4 5 6 7 8 9 10 11 1 2 13 14 15 16 17 18 1 2 3 4 5 6 7 8 9 10 11
To other QSD-DIG

V aux. 115 V AC V aux. 230 V AC


PE

PE
To other
S S QSD-DIG 230/24

S S

C.T. L(+)
L
PC IT-M Loads
IT-M Loads
N(-)
N

Insulation transformer Insulation transformer

— —
ISOLTESTER-DIG SELVTESTER-24

Overall dimensions

55 55
78

121

121 17

17
78

— —
QSD-DIG 230/24 QSD-DIG 230/24 V
38 A B B H + L I N E S A F E T Y A N D R E L I A B I L I T Y S W I TC H B O A R D S A N D D E V I C E S F O R M E D I C A L LO C AT I O N S


TI
Technical features

Insulating transformer technical features

Power 3 kVA 5 kVA 7.5 kVA 10 kVA


Electrical protection class
Thermal insulation class [°C] B 130 B 130 F 155 F 155
Maximum ambient temperature [°C] 40 40 40 40
Primary voltage [V] 230 230 230 230
Secondary voltage [V] 230 230 230 230
Secondary current [A] 13 21.7 32.6 43.5
Maximum inrush current [A] 221 369 553 738
External secondary slow-blow fuse current [A] T 12,5 T 20 T 32 T 40
Maximum power dissipation [W] 120 150 260 320
Frequency [Hz] 50-60 50-60 50-60 50-60
Dispersion current to earth of the secondary winding [mA] < 0,5 < 0,5 < 0,5 < 0,5
Dispersion current to earth of the case [mA] < 0,5 < 0,5 < 0,5 < 0,5
Voltage drop in short-circuit < 3% < 3% < 3% < 3%
Primary no load current [In] < 3% < 3% < 3% < 3%
Dispersion current between primary and secondary winding [mA] < 3,5 < 3,5 < 3,5 < 3,5
Dimensions (BxHxP) [mm] 205 x 340 x 150 240 x 380 x 150 240 x 380 x 160 277 x 380 x 260
Weight [kg] 29,5 44 50,5 73
Reference standards EN 615588; EN 61558-2-15

Overall dimensions

3 KVA 5 KVA 7,5 KVA 10 KVA


b [mm] 205 240 240 277
c [mm] 170 170 170 176
f [mm] 115 115 115 173
h [mm] 340 380 380 380
p [mm] 150 150 160 203
h

f c

p b
S 7 5 0 D R V S S 2 0 0 S E L E C T I V I T Y TA B L E 39


S750 DR vs S200 Selectivity table

Power Upstream circuit-breaker S750 DR


Caractheristic E/K
Downstream Icu [kA] 25
circuit-breaker
In [A] 16 20 25 35 40 50 63
S 200 ≤2 > 15 > 15 > 15 > 15 > 15 > 15 > 15
C 3 T T T T T T T
4 T T T T T T T
B, C 6 T T T T T T T
C 8 T T T T T T T
10 T T T T T T T
13 T T T T T T T
16 T T T T T T
20 T T T T T
B, C
25 T T T T
32 T T T
40 T T
50/63
40 A B B H + L I N E S A F E T Y A N D R E L I A B I L I T Y S W I TC H B O A R D S A N D D E V I C E S F O R M E D I C A L LO C AT I O N S


Order codes


QSO switchboards order codes

Type Power BbN 8012542 ABB code


(kVA) EAN
Operating theatre electrical switchboards, series S
QSO 3S Classic 3 611226 2CSM261122R1551
QSO 5S Classic 5 736929 2CSM273692R1551
QSO 3S Premium 3 736028 2CSM273602R1551
QSO 5S Premium 5 736820 2CSM273682R1551
Operating theatre electrical switchboards, series M
QSO 3M Classic 3 735922 2CSM273592R1551
QSO 5M Classic 5 736721 2CSM273672R1551
QSO 7,5M Classic 7.5 735823 2CSM273582R1551
QSO 3M Premium 3 736622 2CSM273662R1551
QSO 5M Premium 5 735724 2CSM273572R1551
QSO 7,5M Premium 7.5 736523 2CSM273652R1551
Operating theatre electrical switchboards, series L
QSO 10L Classic 10 735625 2CSM273562R1551
QSO 7,5L Premium 7.5 736424 2CSM273642R1551
QSO 10L Premium 10 735526 2CSM273552R1551


ISOLTESTER-DIG order codes

Type BbN 8012542 ABB code


EAN
ISOLTESTER-DIG-RZ 884507 2CSM244000R1501
ISOLTESTER-DIG-RS 568339 2CSM256833R1521
ISOLTESTER-DIG-PLUS 884606 2CSM341000R1501


SELVTESTER-24 order codes

Controlled network Type BbN 8012542 ABB code


EAN
IT-M SELV 24 V AC/DC SELVTESTER-24 884705 2CSM211000R1511
ORDER CODES 41


QSD-DIG 230/24 order codes

Installation Type BbN 8012542 ABB code


EAN
Horizontal QSD-DIG 230/24 730637 2CSM273063R1521
Vertical QSD-DIG 230/24 V 570936 2CSM257093R1521


Medical insulating transformers order codes

Description Type PT100 BbN 8012542 ABB code


Probes EAN
Insulating transformer 3 kVA TI 3 2896005 2CSM110000R1541
Insulating transformer 5 kVA TI 5 2896104 2CSM120000R1541
Insulating transformer 7,5 kVA TI 7.5 2896203 2CSM130000R1541
Insulating transformer 10 kVA TI 10 2521204 2CSM140000R1541
Insulating transformer 3 kVA TI 3-S • 2521402 2CSM210000R1541
Insulating transformer 5 kVA TI 5-S • 2521501 2CSM220000R1541
Insulating transformer 7,5 kVA TI 7.5-S • 2521600 2CSM230000R1541
Insulating transformer 10 kVA TI 10-S • 2521709 2CSM240000R1541
Anti-jamming dampers for transformers AMM 2CSM900000R1541
42 A B B H + L I N E S A F E T Y A N D R E L I A B I L I T Y S W I TC H B O A R D S A N D D E V I C E S F O R M E D I C A L LO C AT I O N S


Questions and answers

What does HI_ which can be displayed on ISOLTESTER- The IEC 60364-7-710 reference standard does not allow this
DIG-RZ insulation monitoring device mean? application. Any medical facility must be supplied by a
It means high insulation. ISOLTESTER-DIG-RZ displays, dedicated medical insulating transformer. “For any group of
thanks to its three digit display, the real time insulation functionally connected facilities at least an IT-M system is
measurement up to 99 kΩ. HI appears whenever the necessary” (article 710.512)
detected insulation is higher than this value.
Has the QSO switchboard got an integrated change-over
What does LF_ which can be displayed on ISOLTESTER-DIG- device?
RZ insulation monitoring device mean? The QSO switchboards does not perform switching
It means “Link Fail”. ISOLTESTER-DIG-RZ display is capable functions to safety power supply.
of carrying out an internal self diagnosis to verify whether This functionality is required by the installation standard IEC
the measurement of the insulation is correctly performed. If 60364-7-710 (or by the relevant national rules) while the QSO
the indication LF appears, it may mean that: distribution boards must comply with the IEC 61439 series
of standards.
• The device has not been wired correctly. In this case it is As the presence of the changeover in the group 2
necessary to verify the wiring according to the installation switchboards is not yet necessary, though it could be one of
electrical scheme. the possible measures that can be used, the installer
• There are electrical devices that discharge some direct responsible for compliance with the IEC 60364-7-710
current interference on the PE safety conductor which standard must do otherwise to guarantee this function.
affects ISOLTESTER-DIG-RZ measuring signal.
Shall I avoid the protection related with the insulation
In this case it is necessary to verify the dispersion by means monitoring device by means of a fuse, in order to avoid the
of a tester. ABB has specifically developed ISOLTESTER-DIG- risk of the monitor being disconnected?
PLUS in order to operate also in a strongly interfered The protection of the insulation monitoring device is
context. necessary to protect the device from short circuits, in
particular at the end of the equipment useful life. Without a
Which insulation value shall I set on ISOLTESTER-DIG as suitable protection, a fire could be produced which should
insulation threshold? damage seriously the switchboard. For these reasons, in
There are not normative prescription. It all depends on the accordance with the IEC 60364 reference standard, the
level of protection you want for the system. The higher the switchboard manufacturer cannot ignore the duty of
threshold, the higher the protection. On the other hand, the protection.
higher the threshold, the higher the possibility to be warned. It is also true that the insulation monitoring device cannot
A useful recomendation may be of setting the threshold be accidentally disconnected for several reasons:
around 20% below the insulation measured in standard
operating conditions. • QSO Switchboards are equipped with a locked door. Only
qualified and authorized personnel are expected to open it.
How do I enter ISOLTESTER-DIG setup menu? • The E 91hN/32 fuse holder that protects the insulation
Press “MINUS” and “SET/RESET” pushbutton monitoring device has no disconnecting performance
simultaneously. under load, and therefore, in order to open the handle it is
necessary to operate on the circuit upstream, disconnect-
How do I access the ISOLTESTER-DIG regulation menu? ing this way the operating theatre from the supply.
Press “SET/RESET” pushbutton. • The E 91hN/32 fuse holder is sealed, and it may only be
opened intentionally.
How many signalling panels can I connect to each
insulation monitor?
You can connect up to 4 remote parallel signalling panels,
without adding any auxiliary supply.

Is it possible to use the same QSO switchboards to feed


two (or more) group 2 medical facilities?
QUESTIONS AND ANSWERS 43

How is it possible to connect 99 ISOLTESTER-DIG-PLUS to Can I use any kind of insulating transformer in medical
a single PLC with only few input channels? premises?
The connection between ISOLTESTER-DIG-PLUS and the PLC General purpose insulating transformers are to be used in
is via bus. This mean that no point to point connection is accordance with the EN 61558-2-4 reference standard
needed and only one PLC input is used. “Particular requirements for general insulating
transformers”. The range of IT medical insulating
Does ABB release the QSO declaration of conformity? transformers is in accordance with the EN 61558-2-15
Certainly. reference standard “Particular requirements for insulating
transformers for the supply of medical locations”.
Is it possible to receive the test report related to the This regulation prescribes additional requirements in order
medical insulating transformer according to the to safeguard the safety of the medical facilities. It is
IEC 60364-7-710 reference standard? therefore not possible to use general purpose insulating
Certainly. It is enough to communicate the serial number transformers.
printed on the label at the metallic base of the transformer,
since the test reports on each produced unit are performed Shall the insulating transformer be protected?
at the factory. The serial number is the seven digit number, All transformers shall be protected from short circuits and
as shown in the picture of the label below. overloads according to the IEC 60364-1 reference standard.
The protection shall be assigned by the manufacturer in
order to guarantee suitable coordination.

Can the upstream protection of insulation transformer be


performed with an overcurrent protection device?
In compliance with the instructions provided by the
manufacturer, an overcurrent protection device can be
therefore used to protect the upstream side of the
insulation transformer. The 710.531 is satisfied if the rated
current of the circuit breaker upstream is higher than the
rated current of the transformer.

TI [KVA] 3 5 7,5 10
How shall the PT100 temperature probes of the medical Circuit breaker [A] 25 25 40 50
insulating transformer be connected?
The temperature probes shall be connected to ISOLTESTER-
DIG insulation monitoring device, as follows: - Connection of IEC 60364-7-710 reference standard requires that the
the primary winding temperature probe: medical transformer inrush current shall not be higher
than 12 times the rated current. Why does the transformer
Terminal block Description ISOLTESTER technical specifications table shows a ratio of about 17
terminal block times (inrush current divided by rated current)?
A-B Sensor 1 28 The rated current is not a RMS value, and therefore it is
C Sensor 1 30 necessary to extract the peak value multiplying it by a factor
D-E Sensor 2 25 root of two. Dividing the inrush current by the rated current
F Sensor 2 27 RMS, the result shall be a ratio equal to 12.
SCH
230

230

W
R
R

R
R

A B CD E F
44 A B B H + L I N E S A F E T Y A N D R E L I A B I L I T Y S W I TC H B O A R D S A N D D E V I C E S F O R M E D I C A L LO C AT I O N S

Additional information
We reserve the right to make technical
changes or modify the contents of this
document without prior notice. With
regard to purchase orders, the agreed
particulars shall prevail. ABB AG does
not accept any responsibility whatso-
ever for potential errors or possible lack
of information in this document.