Transformer Design (Electrical) WO. No. Guaranteed Technical Particulars Bharat Bijlee Ltd. Transformer Division

Download as pdf or txt
Download as pdf or txt
Download as pdf or txt
You are on page 1/ 3

BHARAT BIJLEE LTD.

TRANSFORMER DIVISION
TRANSFORMER DESIGN (ELECTRICAL)
WO. No. Doc. No : GTP-T/10123358/4
Rev. No.: 0
GUARANTEED TECHNICAL PARTICULARS
10123358 Date : 16.05.2019
Page No.: 1 of 3
1 Name of the Manufacturer Bharat Bijlee Limited
2 Reference Standards IS 2026
3 Service Outdoor
4 Normal continuous Rating:
a) With ONAN cooling 12.5 MVA
b) With ONAF cooling 16 MVA
5 Rated Voltage
a) HV Winding 132 kV
b) LV Winding 3.54 kV
6 Rated Frequency 50 Hz
7 Number of Phases 3
8 Connections :
a) HV Winding STAR
b) LV Winding STAR
9 Connections Symbol:
HV - LV YNyn0
10 Tappings :
a) Range +9.375% to -20.625% @ of 1.875%
b) Number of Steps 16 Steps (17 position)
c) For high voltage variation / For intermediate Taps on HV for HV Variation
voltage variation / For low voltage variation
11 Reference ambient Temperatures :
0
a) Maximum ambient air temperature 50 C
0
b) Maximum daily average ambient air temperature 40 C
0
c) Maximum yearly weighted average ambient temperature 32 C
0
d) Minumum ambient air temperature -5 C
12 Type of cooling ONAN/ONAF
13 Temperature Rise
0
a) Top Oil by thermometer method 44 C
0
b) Windings by average resistance method 54 C
14 Total Loss at rated voltage at principal tapping and rated frequency 86 kW (Max) at 16MVA base
+ 1 KW (Max.) Auxilary loss
15 Component Losses
a) No Load Loss at rated voltage on principal tapping and 16 KW (Max)
at rated frequency
b) Load Loss at rated current at principal tapping at 750C 70 KW (Max) at 16 MVA base

16 Impedance voltage at rated current for NOR, MAX, MIN tapping :


a) HV - LV (Normal Tap) 12.6% ( Min.) at 16 MVA

17 Reactance at rated current and rated frequency :


a) HV - LV 12.59% (Approx) at 16 MVA
BHARAT BIJLEE LTD. TRANSFORMER DIVISION
TRANSFORMER DESIGN (ELECTRICAL)
WO. No. Doc. No : GTP-T/10123358/4
Rev. No.: 0
GUARANTEED TECHNICAL PARTICULARS
10123358 Date : 16.05.2019
Page No.: 2 of 3
18 No Load current at rated voltage and rated frequency 0.5% of full load current(Approx.)
19 Input to Cooling Plant 1 KW (Max)
20 Insulation Level
a) Separate source power frequency voltage withstand :
i) HV winding 275 kV rms
ii) LV winding 70 kV rms
b) Induced overvoltage withstand :
i) HV winding 275 kV rms
ii) LV winding Suitable to induce 275 kV rms in HV winding

c) Full wave lightning impulse withstand voltage :


i) HV winding 650 kV peak
ii) LV winding 170 kV peak
d) Switching impulse withstand voltage :
i) HV winding NA
ii) LV winding NA
0
21 Efficiencies at 75 C at unity/0.8 power factor : UPF 0.8 PF lag
a) At full load (100%) 99.47% 99.33%
b) At 3/4 full load (75%) 99.54% 99.43%
c) At 1/2 full load (50%) 99.58% 99.48%
d) At 1/4 full load (25%) 99.49% 99.37%
e) Maximum Efficiency 99.58% @ 47.809 % Load
0
22 Regulation at full load at 75 C : UPF / 0.8 PF 1.230% 8.387%
23 Equipment for ONAN or ONAN/ONAF Cooling :
a) State :
i) Radiators on main tank / separate cooler bank Yes, Tank mounted radiator
b) State ONAN rating in case of mixed cooling 16.0 MVA
24 Number of coolers or cooler banks per transformer 1X100%

25 Details of on load tap changer :


a) Make Easun MR

b) Type Intank Type

c) Rating :
i) Rated Voltage 72.5 kV
ii) Rated Current 350 A
iii) Step Voltage 1429.0 V
iv) Number of steps 16 Steps (17 position)
d) Control 110V, 50Hz, AC Supply
e) Auxiliary supply details 415V, 3Phase, 50Hz, AC Supply
BHARAT BIJLEE LTD. TRANSFORMER DIVISION
TRANSFORMER DESIGN (ELECTRICAL)
WO. No. Doc. No : GTP-T/10123358/4
Rev. No.: 0
GUARANTEED TECHNICAL PARTICULARS
10123358 Date : 16.05.2019
Page No.: 3 of 3

f) Voltage control Remote / Local /Auto


g) Parallel operation N.A.
h) Protective devices Oil Surge Relay, PRV
j) Approximate overall weight Included in overall weight
k) Approximate overall dimensions Included in overall dimensions
m) Approximate overall quantity of oil Included in overall oil Qty.

26 Terminal Arrangement :
a) High voltage 145 kV OIP condenser Bushing Bare Bushing
b) Low voltage 36kV, Oil communicating porcelain BT

c) HV Neutral 36 kV, Oil communicating porcelain Bare Bushing


d) LV Neutral 36 kV, Oil communicating porcelain Bare Bushing
27 Approximate masses :
a) Core and Windings (Untanking mass) 20000 kg (Approx)
b) Tank, Fittings and Accessories 14500 kg (Approx)
c) Oil 12000 kg (Approx)
d) Total Mass 46500 kg (Approx)
28 Approximate quantity of oil required for first filling 13955 liters (Approx)
29 Approximate Overall demensions :
a) Length 7000 mm (Approx)
b) Breadth 3850 mm (Approx)
c) Height 5250 mm (Approx)
30 Despatch details :
a) Approximate mass of heaviest package (Oil filled) 39000 (Approx)
b) Approximate dimensions of largest package :
i) Length 5600 mm (Approx)
ii) Breadth 2500 mm (Approx)
iii) Height 3400 mm (Approx)
31 Untanking Height 7500 mm (Approx)
32 Reference Standards IS 2026:2011

NOTES:

1 All clearances shall be as per CBIP

DATE 16.05.2019 PRD.: Ranjan RAMTEKE CHD.:Sanjay Nair APPD.: Sanjay Nair