TRANSFORMER DIVISION
TRANSFORMER DESIGN (ELECTRICAL)
WO. No. Doc. No : GTP-T/10123358/4
Rev. No.: 0
GUARANTEED TECHNICAL PARTICULARS
10123358 Date : 16.05.2019
Page No.: 1 of 3
1 Name of the Manufacturer Bharat Bijlee Limited
2 Reference Standards IS 2026
3 Service Outdoor
4 Normal continuous Rating:
a) With ONAN cooling 12.5 MVA
b) With ONAF cooling 16 MVA
5 Rated Voltage
a) HV Winding 132 kV
b) LV Winding 3.54 kV
6 Rated Frequency 50 Hz
7 Number of Phases 3
8 Connections :
a) HV Winding STAR
b) LV Winding STAR
9 Connections Symbol:
HV - LV YNyn0
10 Tappings :
a) Range +9.375% to -20.625% @ of 1.875%
b) Number of Steps 16 Steps (17 position)
c) For high voltage variation / For intermediate Taps on HV for HV Variation
voltage variation / For low voltage variation
11 Reference ambient Temperatures :
0
a) Maximum ambient air temperature 50 C
0
b) Maximum daily average ambient air temperature 40 C
0
c) Maximum yearly weighted average ambient temperature 32 C
0
d) Minumum ambient air temperature -5 C
12 Type of cooling ONAN/ONAF
13 Temperature Rise
0
a) Top Oil by thermometer method 44 C
0
b) Windings by average resistance method 54 C
14 Total Loss at rated voltage at principal tapping and rated frequency 86 kW (Max) at 16MVA base
+ 1 KW (Max.) Auxilary loss
15 Component Losses
a) No Load Loss at rated voltage on principal tapping and 16 KW (Max)
at rated frequency
b) Load Loss at rated current at principal tapping at 750C 70 KW (Max) at 16 MVA base
c) Rating :
i) Rated Voltage 72.5 kV
ii) Rated Current 350 A
iii) Step Voltage 1429.0 V
iv) Number of steps 16 Steps (17 position)
d) Control 110V, 50Hz, AC Supply
e) Auxiliary supply details 415V, 3Phase, 50Hz, AC Supply
BHARAT BIJLEE LTD. TRANSFORMER DIVISION
TRANSFORMER DESIGN (ELECTRICAL)
WO. No. Doc. No : GTP-T/10123358/4
Rev. No.: 0
GUARANTEED TECHNICAL PARTICULARS
10123358 Date : 16.05.2019
Page No.: 3 of 3
26 Terminal Arrangement :
a) High voltage 145 kV OIP condenser Bushing Bare Bushing
b) Low voltage 36kV, Oil communicating porcelain BT
NOTES:
DATE 16.05.2019 PRD.: Ranjan RAMTEKE CHD.:Sanjay Nair APPD.: Sanjay Nair