Location via proxy:   [ UP ]  
[Report a bug]   [Manage cookies]                

Temperature Controller E5C2

Download as pdf or txt
Download as pdf or txt
You are on page 1of 6

Analogue Temperature Controller

E5C2
DIN-sized (48 x 48 mm) Temperature
Controller with Analog Setting
• Compact, low-cost Temperature Controller.
• Incorporates proportional control and reset adjustment function.
• Consecutive mounting possible using mounting adapter.
• Incorporates a plug-in socket, thus allows to DIN-track and flush
mounting.

Model Number Structure


■ Model Number Legend
E5C2- @ @ @ @
1 2 3 4 5
1. Model name 4. Input type
2. Control output K: K-type thermocouple
R: Relay L: J-type thermocouple
Q: Voltage P: Platinum resistance thermometer (PT100)
3. Control method G: Thermistor (THE)
20: ON-OFF control 5. Special type
40: P control Blank: Standard type
D, DIN: Special types

Temperature
Ordering Information

Controller
■ Temperature Controllers
Setting Indication Control mode Output Model
method method
Thermocouple Platinum resistance Thermistor
thermometer THE
K (CA) L (IC) Pt100
Chromel vs. Iron vs.
alumel constantan
Analog setting No indication ON/OFF Relay E5C2-R20K E5C2-R20L-D E5C2-R20P-D E5C2-R20G
P Relay E5C2-R40K E5C2-R40L-D E5C2-R40P-D ---

Note: When placing an order, specify the standard temperature range and supply voltage in addition to the model number.
(e.g., E5C2-R20K 0°C to 200°C 100/110 VAC)

■ Accessories (Order Separately)


Name Model
Front Connecting Socket P2CF-08
Back Connecting Socket (for flush mounting) P3G-08
Front Connecting Socket with Finger Protection P2CF-08-E
Protective Cover (for finger protection) Y92A-48G

Analogue Temperature Controller E5C2 I-7


Specifications
■ Ratings
Supply voltage 100/110/120 VAC (common), 200/220/240 VAC (common) (See note.)
50/60 Hz (common)
Operating voltage range 90% to 110% of rated supply voltage
Power consumption Approx. 2 VA
Input Thermocouple (with sensor burnout detection circuit), platinum resistance thermometer, or thermistor
Control mode ON/OFF or P control
Setting method Analog setting
Indication method No indication
Control output Relay output: SPDT, 3 A at 250 VAC, resistive load (switching capacity: 330 VA)

Note: Specify either 100/110/120 VAC or 200/220/240 VAC when ordering.

■ Input Ranges
Input Thermocouple Platinum resistance Thermistor (see note 2)
thermometer
K (CA) L (IC) Pt100 THE
Chromel vs. alumel Iron vs. constantan
Range °C 0 to 200 (5), 0 to 200 (5), –50 to 50 (2), –50 to 50 (2) (6 kΩ at 0°C),
0 to 300 (10), 0 to 300 (10), –20 to 80 (2), 0 to 100 (2) (6 kΩ at 0°C),
0 to 400 (10), 0 to 400 (10) 0 to 50 (1), 50 to 150 (2) (30 kΩ at 0°C)
0 to 600 (20), 0 to 100 (2),
0 to 800 (20), 0 to 200 (5),
0 to 1,000 (25), 0 to 300 (10),
0 to 1,200 (25) 0 to 400 (10)
°F 32 to 392 (10), 32 to 392 (10), 32 to 212 (5), ---
32 to 572 (20), 32 to 572 (20), 32 to 392 (10)
32 to 752 (20), 32 to 752 (20)
32 to 1,112 (40),
32 to 1,472 (50),
32 to 1,832 (50),
32 to 2,192 (50)

Note: 1. Values in ( ) are the minimum unit.


2. Values in ( ) are the thermistor resistive value.

■ Characteristics
Setting accuracy ±2% FS max.
Hysteresis Approx. 0.5% FS (fixed)
Proportional band 3% FS (fixed)
Control period Approx. 20 s
Reset range (see note 1) 5 ±1% FS min.
Insulation resistance 20 MΩ min. (at 500 VDC)
Dielectric strength 2,000 VAC, 50/60 Hz for 1 min between charged terminals and uncharged metallic parts
Vibration resistance Malfunction: 10 to 55 Hz, 0.15-mm single amplitude for 10 min each in X, Y, and Z directions
Destruction: 16.7 Hz, 2-mm double amplitude for 2 hrs each in X, Y, and Z directions
Shock resistance Malfunction: 147 m/s2, 3 times each in 6 directions
Destruction: 294 m/s2, 3 times each in 6 directions
Life expectancy Electrical: 100,000 operations min. (3 A at 110 VAC, resistive load)
Ambient temperature Operating: –10°C to 55°C (with no icing or condensation)
Ambient humidity Operating: 45% to 85%
Degree of protection Front panel: IEC standard IP40 (see note 2)
Terminals: IEC standard IP00
Weight Approx. 200 g (with flush-mounting adapter)

Note: 1. No reset function is incorporated by any E5C2 model with ON/OFF control.
2. The model number of the special watertight cover conforming to IP66, NEMA4 is Y92A-48B.

I-8 Analogue Temperature Controller E5C2


Nomenclature
Temperature setting knob

Operation indicator

RESET adjustment shaft


No reset function is incorporated by any
E5C2 model with ON/OFF control.

Operation Indicator
Indicator Output
Red Lit ON
Not lit OFF

Dimensions
Note: All units are in millimeters unless otherwise indicated.

Terminal Arrangement
48 x 48 (Bottom View)

44.8 x 44.8

Dimensions with Flush-mounting Adapter (Accessory),

Temperature
and Back Connecting Socket (Sold Separately)

Controller
Flush-mounting Panel
Y92F-30 Flush-mounting adapter
adapter
P3G-08 Back con-
necting socket

Tightening screw
(96) (see note)

Note: 109 mm for US08 Back Connecting Socket

Panel Cutout Side-by-side Mounting


of N Controllers

N 2 3 4 5 6
L 93+1
0 141+1
0 189+1
0 237+1
0 285+1
0

60 min.

Note: 1. Recommended panel thickness is 1 to 4 mm.


2. Close side-by-side mounting is possible (in a single direction).

Analogue Temperature Controller E5C2 I-9


Accessories (Order Separately)
P2CF-08 Front Connecting Socket
Terminal Arrangement/ Mounting Holes
Internal Connections
Eight, M3.5 x 7.5 sems (Top View)
Two, 4.5 dia. or Two, M4

70 max.
Two,
4.5-dia. Note: Can also be
holes mounted to a
DIN track.
50 max.
20 max.

Note: A finger-protection model (P2CF-08-E) is also available.

P3G-08 Back Connecting Socket (for Flush Mounting) Terminal Arrangement/


27 dia. Internal Connections
(Bottom View)

Note: A Protective Cover for finger protection (Y92A-48G) is also available.

Protective Cover Y92A-48


Appearance
The protective cover protects the front panel, particularly the setting
section, against dust, dirt, and water drip. It also prevents the set val-
ues from being altered due to accidental contact with the setting
keys.

Model Y92A-48B

Installation
■ Connections
Input Output
Connect a thermocouple, the E52-THE@ Thermistor or platinum If the load circuit is a heating control system, be sure to connect the
resistance thermometer to the E5C2 as shown in the following illus- load to terminals 4 and 5. If the load circuit is a cooling control sys-
tration. tem, be sure to connect the load to terminals 4 and 6. If the heating
control system is connected to terminals 4 and 6 or the cooling con-
trol system is connected to terminals 4 and 5, the temperature of the
heating control system or cooling control system will be abnormal
Platinum resistance Relay output and a serious accident may result.
thermometer input
If the E5C2 is in frequent operation, such as proportional operation,
add an appropriate external relay to the E5C2 by considering the
Thermocouple input
capacity of the load and the life of the relay.

Power Supply
Power supply
100/110, 200/220, If a single power supply is used for the E5C2 and the load, the supply
Thermistor input 110/120, 220/240 VAC voltage of the power supply may vary greatly when the load is open
50/60 Hz or closed if the capacity of the power supply is not large enough.
Make sure that the capacity of the power supply is large enough so
that the supply voltage range will be always from 90% to 110% of the
rated supply voltage.
The E5C2 operates at either 50 or 60 Hz.

I-10 Analogue Temperature Controller E5C2


Precautions
Mounting
Track Mounting (E5C2 with P2CF-08)
When mounting two or more E5C2 models with track-mounting sock-
ets, leave a space of approximately 20 mm on both sides of the sock-
ets where hooks are located.

Hook
Duct

P2CF-08
20
Panel

Flush Mounting
Insert E5C2 into the square hole of the panel and insert an adapter
from the back so that there will be no space between E5C2 and the
panel. Then, secure the E5C2 with a screw.

Tightening screw
The P3G-08 can be wired in the same way as the P2CF-08.

Temperature
Controller
Dismounting
If flush mounted, loosen the screw of the adapter and disengage the
hooks for dismounting.

Temperature Setting
Do not turn the temperature setting knob of the E5C2 with excessive
force, otherwise the stopper of the knob may break.

Others
Do not remove the housing of the E5C2, otherwise the housing may
break.
To clean the surface of the E5C2, use a soft cloth wet with neutral
detergent or alcohol. Do not use any organic solvent, such as paint
thinner or benzine, strong acid or strong alkali to clean the surface of
the E5C2, otherwise the surface of the E5C2 will become damaged.

Analogue Temperature Controller E5C2 I-11


ALL DIMENSIONS SHOWN ARE IN MILLIMETERS.
To convert millimeters into inches, multiply by 0.03937. To convert grams into ounces, multiply by 0.03527.

Cat. No. H081-E1-02 In the interest of product improvement, specifications are subject to change without notice.

I-12 Analogue Temperature Controller E5C2

You might also like