Location via proxy:   [ UP ]  
[Report a bug]   [Manage cookies]                

RPV311 TM en

Download as pdf or txt
Download as pdf or txt
You are on page 1of 151

GE

CONTENTS
Grid Solutions
Chapter 1: Introduction 15
Foreword 15
RPV311 1.1 Target Audience 15
1.2 Nomenclature 15
1.3 Acronyms and Abbreviations 16
Distributed Multifunction Fault Recorder Product Scope 17
Unpacking 17
External Indication 18
4.1 RPV311 Nameplate 18
4.2 RA331, RA332, and RA333 Nameplate 18
Key Features 19
Compliance 20
Cyber Security Disclaimer 21
Functional Overview 21
Programs Under the GPL 2 License 22
Ordering Options 22
10.1 RPV311 22
10.2 RA331 24
10.3 RA332 25
10.4 RA333 27
Chapter 2: Safety Information 29
Health and Safety 29
Symbols 29
Installation, Commissioning and Servicing 30
3.1 Lifting Hazards 30
3.2 Electrical Hazards 30
3.3 Fusing and Insulation Requirements 32
3.4 Equipment Connections 33
3.5 Pre-energisation Checklist 34
3.6 Peripheral Circuitry 35
Technical Manual 3.7 Upgrading/Servicing 35
Platform Hardware Version: C/D
Platform Software Version: 14
Decommissioning and Disposal 36
Publication Reference: RPV311-TM-EN-11.1 Standards Compliance 36
5.1 EMC Compliance: 36
5.2 Product Safety: 2006/95/EC 36
5.3 R&TTE Compliance 37
imagination at work Chapter 3: Hardware Design 39
Hardware Architecture 39
1.1 Processing Capability 40
Groups 90
Mechanical Implementation 40 Relays 91
2.1 RPV311 40 16.1 On time 91
2.2 RA331 42 16.2 Relays 2, 3, and 4 92
2.3 RA332 44
PMU 94
2.4 RA333 45
17.1 General 94
Chapter 4: Configuration 49 17.2 Data 94
17.3 Communication 94
Accessing the Equipment Configuration 49
1.1 Configuration History 50
MODBUS 96
Equipment 50 DNP3 97
2.1 Identification 50 19.1 Configuring the DNP3 function 97
2.2 Synchronization 51 19.2 DNP3 configuration example 97
2.3 Communications 52 Chapter 5: Operation 103
2.4 Acquisition with remote acquisition modules 55
Local Interface 103
2.5 Acquisition with Sampled Values 57
1.1 Status Indicators 103
2.6 Access Control 59
1.2 Menu Navigation 103
2.7 User 60
1.3 Local Interface Menus 104
2.8 Record Management 62
Monitoring Web Interface 117
2.9 Auto Upload 63
2.1 Accessing the Monitoring Web Interface 117
Voltage Circuit 65
2.2 Navigating 117
Current Circuits 66
2.3 Status 118
4.1 GIC Configuration (Geomagnetically Induced Current) 68
2.4 Log 120
Power Circuit 68 2.5 Manual Trigger 121
Digital Channels 69 2.6 Records 122
DC Channels 71 2.7 Monitoring 129
Thresholds 72 2.8 Configuration History 134
8.1 Adding New Voltage Thresholds 73 2.9 General Information 134
8.2 Adding New Current Thresholds 75 COMTRADE files download 137
8.3 Adding New Power Thresholds 77
Chapter 6: Records 138
8.4 Adding New Digital Thresholds 80
8.5 Adding New DC Thresholds 80 Continuous and Triggered Fault Records 138
Cross-Trigger 81 1.1 Recorded Values 138
Fault Recorder 81 1.2 Recording Times by Trigger 138
10.1 Trigger’d Recording 81 1.3 Sampling Rate 139
10.2 Continuous Recording 83 1.4 Re-trigger and Record Concatenation 139
Disturbance Recorder 84 1.5 Trigger Burst Limiter 140
11.1 Trigger'd Recording 84 Continuous and Trigger'd Disturbance Records 140
11.2 Continuous Recording 85 2.1 Recorded Values 141
Traveling Waves Recorder 86 2.2 Recording Times by Trigger 141
Recommended Sources of Trigger 87 2.3 Sampling Rate 142
2.4 Re-trigger and Record Concatenation 142
Steady-State 87
2.5 Trigger Burst Limiter 142
14.1 Average series 88
14.2 Harmonics 88
Traveling Wave Fault Records 142
3.1 Pre-conditions 142
14.3 Flicker 89
1.5 Configuration 164
3.2 Sampling Rate and Acquisition 143
Chapter 10: DNP3 167
3.3 Recording Times 143
Steady-State Records 143 Description 167
4.1 Average Series 143 Chapter 11: GOOSE Message Detection 169
4.2 Harmonics 144
4.3 Flicker 144 Description 169
SOE - Sequence of Events Records 144 1.1 GOOSE Timestamp Behavior 169
Record Format and Naming, and Mass Storage Capacity 145 Chapter 12: Software – RPV Tools 171
6.1 Record Format 145
RPV Tools Description 171
6.2 Record Naming 145
1.1 RPV Tools Installation 171
6.3 Mass Storage Capacity 147
1.2 Scanner 172
Record Management and Access 147 1.3 Configuration Tool 177
Chapter 7: TW Fault Locator 149 1.4 TW Fault Locator 181
1.5 GOOSE Configurator 186
TWFL Overview 149
TW Fault Location Information 150 Chapter 13: Software – DR Manager 193
2.1 TW Triggering System 150 Requirements 193
2.2 Switch-on to Fault 151 Software Description 193
2.3 Maximum Number of Lines Monitored by the TW Fault Locator 151 2.1 DR Manager Main Window 193
2.4 Underground and Overhead Cables 152 2.2 DR Manager Settings 195
Automatic Fault Location 152 2.3 Automatic TW Fault Location 205
How to Test the TW Fault Location in Lab 152 2.4 Polling and Refresh 208
Three Terminal Line Application 153
Chapter 14: Communications 211
5.1 Examples 154
TWFL in Mixed (Hybrid) Lines 156 Communication Interfaces 211
6.1 K Factor Calculation – Overhead Section 156 1.1 Electrical and Optical Ethernet 211
6.2 K Factor Calculation – Underground Section 157 1.2 Serial Port 213
Communication Ports and Protocols 214
Chapter 8: PMU 159
Communication Using the Electrical Ethernet Port 215
Synchrophasor Measurement and Broadcast 159 3.1 Checking the Connection 216
1.1 Reported Values 159 Communication Through Network Using the Serial Port 216
1.2 Accuracy Limits 160 Accessing the Equipment 217
1.3 Communication Ports, Transmission Rates 161 5.1 Computer Support Applications 217
1.4 Timestamp 161 5.2 Minimum Computer Requirements 217
1.5 Configuration 161 5.3 Communication Configuration 218
1.6 Standards Compliance 161 5.4 Auto Upload 218
WMU – Waveform Measurement Unit 162
Chapter 15: Installation 219
Chapter 9: MODBUS 163
Handling the Goods 219
Description 163 1.1 Receipt of the Goods 219
1.1 Register Types 163 1.2 Unpacking the Goods 219
1.2 Status 163 1.3 Storing the Goods 219
1.3 Analog Data 164 1.4 Dismantling the Goods 220
1.4 Digital Channels 164 Normal Use of the Equipment 220
5.2 READY indicator does not light up 259
Mounting the Device 220 5.3 PPS indicator does not light up (Only RA333) 259
3.1 RPV311 Mechanical Installation 220 5.4 Link with the processing module is not active 259
3.2 RA331, RA332 and RA333 Mechanical Installation 221 Equipment Return 259
Cables and Connectors 222 Instructions for Equipment Repair/Service for Service Personnel 260
Power Supply Connections 222
Chapter 17: Technical Specifications 261
RPV311 AC and DC Power Connection 223
RA331, RA332 and RA333 AC and DC Power Connection 224 RPV311 Specifications 261
Powering Up 224 1.1 Electrical Ethernet Port 261
Earth Connection 225 1.2 Optical Ethernet Port (optional) 262
1.3 Modem Serial Port 262
Connection Between RPV311 and RA331, RA332 or RA333 226
1.4 TTL IRIG Input 263
Analog Voltage Inputs (50/60 Hz) 229
1.5 Optical IRIG-Input (optional) 263
High-speed Analog Voltage Inputs (TW) 234
1.6 Dry-contact Relay Outputs 264
Analog Current Inputs 235 1.7 Fiber-optic Links 264
Analog DC Transducer Inputs ± 10 V 240 1.8 Power Supply 265
Analog DC Transducer Inputs ± 20 mA 242 1.9 Environmental Conditions 265
Current Clamps 244 1.10 Type Tests RPV311 266
Digital Inputs 245 1.11 Safety Tests 270
Time Synchronization Inputs 246 1.12 Environmental tests 270
Dry Contact Relays 248 1.13 Enclosure Protection IEC 60529 270
Case Dimensions 248 1.14 Dimensions 271
20.1 RPV311 and RA33X 248 RA331, RA332, and RA333 Specifications 273
RPV311 Accessories 250 2.1 Analog Acquisition (50/60 Hz) 273
RA33x Accessories 250 2.2 Analog Acquisition (High-speed – Only RA333 Module) 273
22.1 Panel Cutout 250 2.3 Voltage Inputs 274
2.4 Current Inputs 274
Panel for Installation of Two Remote Acquisition Modules (Q61) 251
2.5 Current clamps inputs specification 275
Chapter 16: Maintenance and Troubleshooting 253 2.6 DC Transducer Inputs 275
Maintenance 253 2.7 Binary Inputs 275
1.1 Maintenance Checks 253 2.8 Fiber-optic Links 276
1.2 Replacing the Unit 254 2.9 RA33x Power Supply 276
1.3 Cleaning 254 2.10 Environmental Conditions 277
1.4 Watchdog 255 2.11 Type Tests RA33x 277
1.5 Coin-battery replacement procedure 255 2.12 Safety Tests 281
RPV311 Troubleshooting 256 2.13 Environmental tests 281
2.1 Ready in processing module does not light up 256 2.14 Enclosure Protection IEC 60529 281
2.2 Alarm LED lights up 257 2.15 Dimensions 282
2.3 SYNC does not light up 257 2.16 Current Clamps 284
2.4 Date or time incorrect 257 Chapter 18: Wiring Diagrams 285
2.5 Time drift throughout operation week 257
Connection Diagrams of the Voltage Inputs 285
RPV311 Firmware Update 258
Connection Diagrams of the TW Inputs 287
Product Support Tools - PST 258
Connection Diagrams of the Current Inputs 287
RA331, RA332, and RA333 Troubleshooting 259
5.1 MAINS indicator does not light up 259 Appendix A 290
Equipment Log 290
Table of Figures
Figure 1: Functional design overview 22
Figure 2: RA332, RA333 and RPV311 39
Figure 3: Front View of the RPV311 41
Figure 4: Back view of the RPV311 42
Figure 5: Rear and front views of the RA331, respectively 43
Figure 6: Rear view of the RA332 44
Figure 7: Front and back views of the RA333 46
Figure 8: Equipment identification configuration section 51
Figure 9: Equipment Ethernet configuration section 53
Figure 10: Equipment serial port configuration section 54
Figure 11: Links between RPV and acquisition modules configuration section 55
Figure 12: Analog inputs configuration section 57
Figure 13: Sampled Values subscriptions links configuration section 58
Figure 14: Analog inputs configuration section for Sampled Values channels 59
Figure 15: Equipment access control configuration section 60
Figure 16: Adding new user section 61
Figure 17: Changing the administrator password section: Changing the administrator
password section 62
Figure 18: Record management configuration section 63
Figure 19: Auto upload configuration section 64
Figure 20: Email/Fax configuration 65
Figure 21: Adding and editing voltage circuits 66
Figure 22: Adding and editing current circuits 67
Figure 23: Adding and editing power circuits 69
Figure 24: Adding and editing digital channels 70
Figure 25: Adding and editing DC channels 72
Figure 26: Adding and editing a voltage threshold 75
Figure 27: Adding and editing a current threshold 77
Figure 28: Adding and editing a power threshold 78
Figure 29: Adding and editing a DC threshold 81
Figure 30: Fault recorder – triggered recording configuration section 82
Figure 31: Fault recorder – continuous recording configuration section 83
Figure 65: Monitoring the status of digital channels 133
Figure 32: Disturbance recorder – trigger’d recording configuration 84
Figure 66: Configuration History screen 134
Figure 33: Disturbance recorder – continuous recording configuration section 85
Figure 67: General Information screen 135
Figure 34: Traveling waves recorder – triggered recording configuration section 86
Figure 68: Setup screen 136
Figure 35: Steady-state recorder – average series configuration section 88
Figure 69: Concatenation event example 139
Figure 36: Steady-state recorder – harmonics configuration section 89
Figure 70: Example of an event without concatenation 140
Figure 37: Steady-state recorder – flicker configuration section 90
Figure 71 – TW Fault Locator architecture overview 149
Figure 38: Adding and editing a group 91
Figure 72 - Typical Circuit Three-Terminal Application 153
Figure 39: Relays on time configuration section 92
Figure 73 – Three terminal line application 154
Figure 40: Relay signaling events configuration section 93
Figure 74 – TW Fault Location example 1 155
Figure 41: MODBUS configuration section 96
Figure 75 - TW Fault Location example 2 156
Figure 42: Digital Channels Configured 98
Figure 76: Directory of the records received of the equipment 176
Figure 43: Analog channels selected 100
Figure 77: Configuration Tool main screen 177
Figure 44: Local interface of the RPV311 103
Figure 78: Fault Locator Interface 184
Figure 45: Status monitoring sequence 105
Figure 79: Graphical tool of Fault Locator interface 185
Figure 46: Monitoring sequence 107
Figure 80: Initial screen of the GOOSE Configurator 187
Figure 47: Records monitoring sequence: Fault disturbance, TW and average series 109
Figure 81: Screen to configuration on the SCL file 189
Figure 48: Records monitoring sequence: harmonics, flicker and SOE 110
Figure 82: Association of a GOOSE Control Block with a digital input 190
Figure 49: Equipment settings monitoring sequence 112
Figure 83: Filter parameters 191
Figure 50: Circuit and channel settings monitoring sequence 113
Figure 84 - DR Manager main window 193
Figure 51: Relays, PMU and MODBUS settings monitoring sequence 114
Figure 85 - Downloaded records 194
Figure 52: General information monitoring sequence 116
Figure 86: Alarms tab 194
Figure 53: Default screen for browsing on the Web Interface 117
Figure 87: Device window 197
Figure 54: Equipment status screen 119
Figure 88- Transmission Line configuration 198
Figure 55: Link status screen 120
Figure 89: Current Circuit name 199
Figure 56: Log screen 121
Figure 90: Terminal name configuration 199
Figure 57: Manual Trigger screen 122
Figure 91- Warning menu 199
Figure 58: Fault recorder screen 123
Figure 92 - Tools menu 200
Figure 59: Fault recorder screen 124
Figure 93: Percentage of records chart 203
Figure 60: Traveling Wave recorder screen 125
Figure 94: Polling configuration 204
Figure 61: Steady-state recorder screen 126
Figure 95: About window 205
Figure 62: SOE recorder screen 128
Figure 96: DR Manager TWFL methods 207
Figure 63: Monitoring with plots 131
Figure 97: Electrical and optical Ethernet inputs 212
Figure 64: Monitoring circuit quantities via Web interface 132
Figure 98: Serial communication port 213
Figure 132: Dry contact relays of the RPV311 248
Figure 99: Minimum distances for the equipment mounting 221
Figure 133: Dry contact relay connection diagram 248
Figure 100: Mounting panel to install two remote acquisition modules (RA331/332) in a 19-
Figure 134: Fiber-optic pair 250
inch rack 222
Figure 101: Pre-insulated tubular pin terminals 223 Figure 135: RA331, RA332 and RA333 panel cutout 251
Figure 136: Mounting panel to install two remote acquisition modules (RA331/332) in a 19-
Figure 102: Header connector assembly 223
inch rack 252
Figure 103: AC/DC power connection 223
Figure 137: RPV311 Dimensions 272
Figure 104: AC/DC power connection 224
Figure 138: RA331, RA332 and RA333 dimensions 283
Figure 105: RPV311 Grounding 225
Figure 139: AEMC / MN312 (PN 2468) current clamps 284
Figure 106: RA33X Grounding 226
Figure 107: RPV311 Fiber Optic Connectors 227
Figure 108: RA331, RA332 and RA333 fiber optic connectors 227
Figure 109: Connection between RPV311 and the RA331, RA332 or RA333 228
Figure 110: Screws of the Back Panel 229
Figure 111: Analog input terminals 230
Figure 112: Screws of the Back Panel 230
Figure 113: Internal Jumper 231
Figure 114: Analog Input Terminals to TW Measurement 234
Figure 115: Analog Input Terminals 236
Figure 116: Screws of the Back Panel 236
Figure 117: Internal Jumper 237
Figure 118: Analog Input Terminals 240
Figure 119: Screws of the Back Panel 241
Figure 120: Internal Jumper 241
Figure 121: Connection Diagram of DC Transducer Inputs ± 10 V 242
Figure 122: Analog Input Terminals 242
Figure 123: Screws of the back panel 243
Figure 124: Internal Jumper 244
Figure 125: Connection Diagram of DC Transducer Inputs ± 20 mA 244
Figure 126: Polarity of the Current Clamp Connection 245
Figure 127: Digital Input Terminals 245
Figure 128: Connection Diagram of Digital Inputs 246
Figure 129: Electrical and optical inputs for sync using IRIG-B 247
Figure 130: Connection diagram of electrical synchronism inputs 247
Figure 131: Connections diagram of optical synchronism inputs 247
RPV311 Chapter 1 – Introduction

Grid. The first instance of any acronym or term used in a particular chapter is explained.
RPV311 In addition, a separate glossary is available on the GE website, or from the GE contact
center.
We would like to highlight the following changes of nomenclature however:

Distributed Multifunction Fault Recorder x British English is used throughout this manual.

x The British term 'Earth' is used in favour of the American term 'Ground'.

Chapter 1: Introduction
This chapter provides some general information about the technical manual and an 1.3 Acronyms and Abbreviations
introduction to the device(s) described in this technical manual.

AC - Alternating Current;
Foreword CF - Constituição Federal (Federal Constitution);
This technical manual provides a functional and technical description of GE Reason COMNAME - IEEE C37.232 Recommended Practice for Naming Time Sequence Data
RPV311, as well as a comprehensive set of instructions for using the device. The level at Files;
which this manual is written assumes that you are already familiar with protection COMTRADE - IEEE C37.111 Common Format for Transient Data Exchange;
engineering and have experience in this discipline. The description of principles and DC - Direct Current;
theory is limited to that which is necessary to understand the product. DFR - DataFlex file extension;
We have attempted to make this manual as accurate, comprehensive and user-friendly EMC - Electromagnetic Compatibility;
as possible. However, we cannot guarantee that it is free from errors. Nor can we state FRQ - Frequency;
that it cannot be improved. We would therefore be very pleased to hear from you if you FUT - Firmware Upgrade Tool;
discover any errors, or have any suggestions for improvement. Our policy is to provide GOOSE - Generic Object Oriented Substation Events;
the information necessary to help you safely specify, engineer, install, commission, GPS - Global Positioning System;
maintain, and eventually dispose of this product. We consider that this manual provides HDD - Hard disk drive;
the necessary information, but if you consider that more details are needed, please HTML - HyperText Markup Language;
contact us. IMB - Imbalance;
All feedback should be sent to our contact center via the following URL: IEEE - Institute of Electric and Electronic Engineers;
http://www.gegridsolutions.com/alstomenergy/grid/grid/contactcentre IEC - International Electrotechnical Commission;
IED - Intelligent Electronic Devices;
IP - Internet Protocol;
IRIG-B -Inter Range Instrumentation Group (Rate Designation B);
1.1 Target Audience KML - Keyhole Markup Language;
This manual is aimed towards all professionals charged with installing, commissioning, MAC - Media Access Control;
maintaining, troubleshooting, or operating any of the products within the specified MODBUS - Modicon Bus;
product range. This includes installation and commissioning personnel as well as PC - Computer;
engineers who will be responsible for operating the product. PMU - Phasor Measurement Unit;
The level at which this manual is written assumes that installation and commissioning PST - Product Support Tools;
engineers have knowledge of handling electronic equipment. Also, system and Pst - Short-term flicker severity;
protection engineers have a thorough knowledge of protection systems and associated Plt - Long-term flicker severity;
equipment. RAM - Random-access Memory;
RFC, DEFLATE - RFC 1951, DEFLATE Compressed Data Format Specification;
RMS - Root Mean Square;
1.2 Nomenclature RPV - Multifunction Digital Fault Recorder;
SCADA - Supervisory Control and Data Acquisition;
Due to the technical nature of this manual, many special terms, abbreviations and SCD, CID - Input files extensions for the IED GOOSE messages;
acronyms are used throughout the manual. Some of these terms are well-known SCL - Edit Configuration File for the GOOSE Configurator;
industry-specific terms while others may be special product-specific terms used by GE SNTP - Simple Network Time Protocol;
15 RPV311-TM-EN-11 16 RPV311-TM-EN-11.1
Chapter 1 – Introduction RPV311 RPV311 Chapter 1 – Introduction

SOE - Sequency of Events;


SQL - Structured Query Language; Check the contents against the packing list. If any of the contents listed is missing,
SSD - Solid-state Drive; please contact GE immediately (see contact information at the beginning of this
TCP - Transmission Control Protocol; manual).
THD - Total harmonic distortion; Examine the equipment for any shipping damage. If the unit is damaged or fails to
TTL - Transistor-Transistor Logic; operate, notify the shipping company immediately. Only the consignee (the person or
TW - Travelling Wave; company receiving the unit) can file a claim against the carrier for occasional shipping
UDP - User Datagram Protocol; damages.
UTC - Coordinated Universal Time; We recommend that the user retain the original packing materials for use in case of
VLAN - Virtual Local Area Network; need to transport or ship the equipment at some future time.
XML - Extensible Markup Language.

External Indication
Product Scope
The processing unit RPV311 and the acquisition modules RA331, RA332, and RA333
offer a distributed solution for Multifunction Digital Recording. The solution is designed 4.1 RPV311 Nameplate
for the acquisition, monitoring and recording of electrical quantities normally
associated with electrical power generation, transmission or distribution equipment. It
is the solution for applications which require flexibility, allowing installation of RPV311 Information about the company, power supply and the serial number and part number
Processing Unit in existing panels and the Acquisition Modules RA331, RA332, and is shown on a small nameplate affixed to the rear of the equipment, as shown in Figure
RA333 near to the plant seeing monitored the applications installation. 1.
The RPV311Solution is a multifunction equipment with fan-less and no rotating part
design. It has an acquisition system with 16-bit A/D D converters that provide an
acquisition rate of 256 points-per-cycle synchronized by the IRIG-B signal.
It has a high processing capability, which allows the acquisition of up to 64 analog
channels and 256 digital channels divided in up to 8 acquisition modules connected by
fiber-optic links. Additionally, it is able to detect IEC 61850 GOOSE messages.
It allows communication through the electrical Ethernet ports and optionally has a
double internal converter for optical Ethernet interfaces.
Monitoring and configuration are performed through a web interface; also, it has a
human-machine interface on the front panel for displaying information. It has a
MODBUS and DNP3 interface for SCADA integration.
The RA331 module allows data acquisition of up to 8 analogue channels (voltage,
current, or DC transducers) and up to 32 digital channels. The RA332 module allows
data acquisition of up to 16 analogue channels (voltage, current, or DC transducers) and
up to 32 digital channels. Both modules use 16-bit A/D converters providing an Figure 1: Location of Serial Number, Part Number and specifications
acquisition rate of 256 points-per-cycle.
The RA333 module allows data acquisition of high-speed analog channels (voltage) for
one transmission line. This module allows the scheme to obtain traveling wave records
for fault locating. Additionally, the RA333 module allows data acquisition of up to 8
analog channels (voltage, current, or DC transducers) and up to 16 digital channels, 4.2 RA331, RA332, and RA333 Nameplate
using 16-bit A/D converters providing an acquisition rate of 256 points-per-cycle.

Information about the company, power supply, the serial number and part number and
specifications about the equipment are shown on a small nameplate affixed to the side
Unpacking of the equipment, as shown in Figure 2.
Unpack the equipment carefully and make sure that all accessories and cables are put
away so they will not be lost.
18 RPV311-TM-EN-11.1
RPV311-TM-EN-11.1 17
Chapter 1 – Introduction RPV311 RPV311 Chapter 1 – Introduction

ƒ Up to 8 fiber-optic links to connect to RA331, RA332 or RA333 remote


acquisition modules;
x Fan-less and no rotating part design
x Trigger waveform recorder at 256, 128, or 64 points-per-cycle;
x Continuous waveform recorder at 16 points-per-cycle;
x Continuous disturbance recorder and trigger recorder (optional);
x IRIGB-004 and SNTP/NTP version 2, 3 or 4 time synchronization
x Trigger using Boolean logic equations;
x TWFL - Traveling wave recorder for fault location (optional),
ƒ TWFL also for consecutive faults and switch-on to fault;
x MODBUS and DNP3 interface for SCADA integration (optional);
x Synchrophasor Class M measurement according to IEEE C37.118 (optional);
x Power quality records:
x Historical average at aggregation intervals of 1 or 10 minutes (optional);
x Measurement and recording of harmonics up to the 50th order according to IEC
61000-4-7 (optional);
x Measurement and recording of flicker according to IEC 61000-4-15:1997+A1:2003
(optional);
x Cross-trigger using standard network connection;
x One-end fault location based on Takagi algorithm;
x Flexible communication:
x Two 10/100BaseT electrical Ethernet interfaces;
x Two embedded optical Ethernet converters;
Figure 2: Location of Serial Number, Part Number and specifications
x RS232 serial port for modem connection;
x Support for IEC 61850:
Key Features x Up to 320 binary inputs related to IEC 61850-8-1 GOOSE messages – KEMA
Certified (optional);
x Two Ethernet ports for redundant connection (optional);
The RPV311 plus RA33x acquisition modules solution presents the following key
x One Ethernet port for Process Bus (IEC 61850-9-2LE Sampled Values) connection
features:
(optional).
x Acquisition system:
x Local interface on the front panel;
ƒ 16-bit opto-isolated analog-to-digital converters, independent for each
channel (50/60 Hz channels); x 4 dry-contact relays for remote signalling;
ƒ 256 points-per-cycle sampling rate (50/60 Hz channels); x Fax andȀor e-mail message after detection of a trigger. The fax can be sent to two
ƒ Frequency response of DC to 3.0 kHz; different destinations and the e-mail to four different destinations (optional).
ƒ 8-bit opto-isolated analog-to-digital converters, independent for each channel
(high-speed channels);
ƒ MHz sampling frequency (high-speed channels);
ƒ Internal time skew compensation;
Compliance
ƒ Sampling rate synchronized to external IRIG-B reference; The device has undergone a range of extensive testing and certification processes to
ensure and prove compatibility with all target markets. A detailed description of these
x Channel capacity: criteria can be found in the Technical Specifications chapter.
ƒ Up to 64 analog inputs (voltage, current, DC transducers);
ƒ Up to 12 high-speed analog inputs for Traveling Wave Fault Location;
ƒ Up to 256 digital inputs;
20 RPV311-TM-EN-11.1
RPV311-TM-EN-11.1 19
Chapter 1 – Introduction RPV311 RPV311 Chapter 1 – Introduction

Cyber Security Disclaimer


The Multifunctional Digital Fault Recorder RPV311 is designed to be installed and
operated in industrial and power sub-station environments and connected to private
networks.
GE strongly recommend users to protect their digital devices using a defense-in-depth
strategy to protect their products, their network, its systems and interfaces against
cyber security threats. This includes, but is not limited to, placing digital devices inside
the control system network security perimeter, deploy and maintain access controls,
monitoring of Intrusion Detection, security awareness training, security policies,
network segmentation and firewalls, password management, data encryption, antivirus
and other mitigating applicable technologies.
It is users’ sole responsibility to make sure that the devices are installed and operated
considering its cyber security capabilities and security context.
GE Grid Automation and its affiliates may not be liable for damages and/or losses
related to cyber security incidents.

Functional Overview

The processing unit RPV311 and the acquisition modules RA331, RA332, and RA333
offer a distributed solution for Multifunction Digital Recording. The solution is designed
for the acquisition, monitoring and recording of electrical quantities normally
associated with electrical power generation, transmission or distribution equipment. It
is the solution for applications which require flexibility, allowing installation of RPV311
Processing Unit in existing panels and the Acquisition Modules RA331, RA332, and
RA333 near to the plant seeing monitored the applications installation.

Figure 1: Functional design overview

Programs Under the GPL 2 License


The RPV311 uses GPL 2 licenses in its implementation.
In case the user wants get ahold of the source code, please contact out contact centre.

Ordering Options

10.1 RPV311
Variants Order Number
9- 1 13- 1
1-6 7 8 11 2 14 5
22 RPV311-TM-EN-11.1
RPV311-TM-EN-11.1 21
Chapter 1 – Introduction RPV311 RPV311 Chapter 1 – Introduction

Model Type 10.2 RA331


RPV311 Multifunction Recorder RPV311
Variants Order Number

Power Supply 1-5 6 7 8 9 10 11 12

24-48 Vdc 1 Model Type

100-250 Vdc / 110-240 Vac 3 RA331 Acquisition Module for RPV311 RA331

Network Interface Power Supply


Two RJ45 copper 100BASE-TX Ethernet 24-48 Vdc 1
interfaces E 100-250 Vdc / 110-240 Vac 3
Two RJ45 copper or duplex ST-type connector 100BASE-X Ethernet
interfaces O Analogue Inputs 1 to 4
Voltage inputs 115 V / Current inputs 1 A; full-scale 20 A (Ith = 40 A) (withdrawn) 1
Functions and Protocols Voltage inputs 115 V / Current inputs 1 A; full-scale 40 A (Ith = 100 A) 2
Fault Recorder *** Voltage inputs 115 V / Current inputs 5 A; full-scale 100 A (Ith = 200 A) 5
Sequence of Events Recorder *** Voltage inputs 115 V / Current inputs 5 A; full-scale 200 A (Ith = 200 A) 6
Disturbance Recorder *** Voltage inputs 115 V / Current inputs 5 A; full-scale 14 A (Ith = 32 A) (withdrawn) T
Continuous Fault and Disturbance Recorder *** Voltage inputs ±10 Vdc / Current inputs 0-20 mAdc D
Phasor Measurement Unit (PMU) *** Voltage inputs 115 V / Current inputs 100 mA; full-scale 100 mA (Ith = 2 A) P
GOOSE Message Subscription *** Not installed X
MODBUS/DNP3.0 Interface ***
Power Quality *** Analogue Inputs 5 to 8
IEC 61850-9-2LE Inputs *** Voltage inputs 115 V / Current inputs 1 A; full-scale 20 A (Ith = 40 A) (withdrawn) 1
Travelling Wave Fault Location *** Voltage inputs 115 V / Current inputs 1 A; full-scale 40 A (Ith = 100 A) 2
Waveform Measurement Unit (WMU) *** Voltage inputs 115 V / Current inputs 5 A; full-scale 100 A (Ith = 200 A) 5
Voltage inputs 115 V / Current inputs 5 A; full-scale 200 A (Ith = 200 A) 6
Customization / Regionalisation Voltage inputs 115 V / Current inputs 5 A; full-scale 14 A (Ith = 32 A) (withdrawn) T
GE branding C Voltage inputs ±10 Vdc / Current inputs 0-20 mAdc D
Voltage inputs 115 V / Current inputs 100 mA; full-scale 100 mA (Ith = 2 A) P
Firmware Version Not installed X
Firmware 14 14
Firmware 13 13 Digital Inputs 1 to 16
24 V / 48 V 1
Hardware Design Suffix 125 V 2
Third version (withdraw) C 250 V 3
Fourth version D Not installed X

Issue H Digital Inputs 17 to 32


24 V / 48 V 1
125 V 2
250 V 3
Not installed X

Customization / Regionalisation
GE branding C

Hardware Design Suffix


Third version C

24 RPV311-TM-EN-11.1
RPV311-TM-EN-11.1 23
Chapter 1 – Introduction RPV311 RPV311 Chapter 1 – Introduction

Voltage inputs 115 V / Current inputs 1 A; full-scale 20 A (Ith = 40 A) (withdrawn) 1

10.3 RA332 Voltage inputs 115 V / Current inputs 1 A; full-scale 40 A (Ith = 100 A) 2

Order Number Voltage inputs 115 V / Current inputs 5 A; full-scale 100 A (Ith = 200 A) 5
Variants
1-5 6 7 8 9 10 11 12 13 14 Voltage inputs 115 V / Current inputs 5 A; full-scale 200 A (Ith = 200 A) 6

Model Type Voltage inputs 115 V / Current inputs 5 A; full-scale 14 A (Ith = 32 A) (withdrawn) T

RA332 Acquisition Module for RPV311 RA332 Voltage inputs ±10 Vdc / Current inputs 0-20 mAdc D
Voltage inputs 115 V / Current inputs 100 mA; full-scale 100 mA (Ith = 2 A) P

Power Supply Not installed X

24-48 Vdc 1
100-250 Vdc / 110-240 Vac 3 Digital Inputs 1 to 16
24 V / 48 V 1

Analogue Inputs 1 to 4 125 V 2

Voltage inputs 115 V / Current inputs 1 A; full-scale 20 A (Ith = 40 A) (withdrawn) 1 250 V 3

Voltage inputs 115 V / Current inputs 1 A; full-scale 40 A (Ith = 100 A) 2 Not installed X

Voltage inputs 115 V / Current inputs 5 A; full-scale 100 A (Ith = 200 A) 5


Voltage inputs 115 V / Current inputs 5 A; full-scale 200 A (Ith = 200 A) 6 Digital Inputs 17 to 32

Voltage inputs 115 V / Current inputs 5 A; full-scale 14 A (Ith = 32 A) (withdrawn) T 24 V / 48 V 1

Voltage inputs ±10 Vdc / Current inputs 0-20 mAdc D 125 V 2

Voltage inputs 115 V / Current inputs 100 mA; full-scale 100 mA (Ith = 2 A) P 250 V 3

Not installed X Not installed X

Analogue Inputs 5 to 8 Customization / Regionalisation

Voltage inputs 115 V / Current inputs 1 A; full-scale 20 A (Ith = 40 A) (withdrawn) 1 GE branding C

Voltage inputs 115 V / Current inputs 1 A; full-scale 40 A (Ith = 100 A) 2


Voltage inputs 115 V / Current inputs 5 A; full-scale 100 A (Ith = 200 A) 5 Hardware Design Suffix

Voltage inputs 115 V / Current inputs 5 A; full-scale 200 A (Ith = 200 A) 6 Third version C

Voltage inputs 115 V / Current inputs 5 A; full-scale 14 A (Ith = 32 A) (withdrawn) T


Voltage inputs ±10 Vdc / Current inputs 0-20 mAdc D
Voltage inputs 115 V / Current inputs 100 mA; full-scale 100 mA (Ith = 2 A) P
Not installed X

Analogue Inputs 9 to 12
Voltage inputs 115 V / Current inputs 1 A; full-scale 20 A (Ith = 40 A) (withdrawn) 1
Voltage inputs 115 V / Current inputs 1 A; full-scale 40 A (Ith = 100 A) 2
Voltage inputs 115 V / Current inputs 5 A; full-scale 100 A (Ith = 200 A) 5
Voltage inputs 115 V / Current inputs 5 A; full-scale 200 A (Ith = 200 A) 6
Voltage inputs 115 V / Current inputs 5 A; full-scale 14 A (Ith = 32 A) (withdrawn) T
Voltage inputs ±10 Vdc / Current inputs 0-20 mAdc D
Voltage inputs 115 V / Current inputs 100 mA; full-scale 100 mA (Ith = 2 A) P
Not installed X

Analogue Inputs 13 to 16

26 RPV311-TM-EN-11.1
RPV311-TM-EN-11.1 25
Chapter 1 – Introduction RPV311 RPV311 Chapter 1 – Introduction

Fourth version D
10.4 RA333 Third version (withdrawn) C

Variants Order Number


1-5 6 7 8 9 10 11 12 13
Model Type
RA333 Travelling Wave and DFR Acquisition Module for RPV311 RA333

Power Supply
100-250 Vdc / 110-240 Vac 3
100-250 Vdc / 110-240 Vac 3

Analogue Inputs 1 to 4
Voltage inputs 115 V / Current inputs 1 A; full-scale 20 A (Ith = 40 A) (withdrawn) 1
Voltage inputs 115 V / Current inputs 1 A; full-scale 40 A (Ith = 100 A) 2
Voltage inputs 115 V / Current inputs 5 A; full-scale 100 A (Ith = 200 A) 5
Voltage inputs 115 V / Current inputs 5 A; full-scale 200 A (Ith = 200 A) 6
Voltage inputs 115 V / Current inputs 5 A; full-scale 14 A (Ith = 32 A) (withdrawn) T
Voltage inputs ±10 Vdc / Current inputs 0-20 mAdc D
Voltage inputs 115 V / Current inputs 100 mA; full-scale 100 mA (Ith = 2 A) P
Not installed X

Analogue Inputs 5 to 8
Voltage inputs 115 V / Current inputs 1 A; full-scale 20 A (Ith = 40 A) (withdrawn) 1
Voltage inputs 115 V / Current inputs 1 A; full-scale 40 A (Ith = 100 A) 2
Voltage inputs 115 V / Current inputs 5 A; full-scale 100 A (Ith = 200 A) 5
Voltage inputs 115 V / Current inputs 5 A; full-scale 200 A (Ith = 200 A) 6
Voltage inputs 115 V / Current inputs 5 A; full-scale 14 A (Ith = 32 A) (withdrawn) T
Voltage inputs ±10 Vdc / Current inputs 0-20 mAdc D
Voltage inputs 115 V / Current inputs 100 mA; full-scale 100 mA (Ith = 2 A) P
Not installed X

Digital Inputs 1 to 16
24 V / 48 V 1
125 V 2
250 V 3
Not installed X

Digital Inputs 17 to 32
24 V / 48 V 1
125 V 2
250 V 3
Not installed X

Travelling Wave Input


Three-phase bus or line voltage V

Customization / Regionalisation
GE branding C

Hardware Design Suffix


28 RPV311-TM-EN-11.1
RPV311-TM-EN-11.1 27
RPV311 Chapter 2 – Safety Information

RPV311 Caution: Refer to equipment documentation. Failure to do so


could result in damage to the equipment

Distributed Multifunction Fault Recorder


Risk of electric shock
Chapter 2: Safety Information
Ground terminal. Note: This symbol may also be used for a
protective conductor (ground) terminal if that terminal is
This chapter provides information about the safe handling of the equipment. The part of a terminal block or sub-assembly.
equipment must be properly installed and handled in order to maintain it in a safe
condition and to keep personnel safe at all times. You must be familiar with information
contained in this chapter before unpacking, installing, commissioning, or servicing the Protective conductor (ground) terminal
equipment.

Both direct and alternating current


Health and Safety
Personnel associated with the equipment must be familiar with the contents of this
Safety Information. Instructions on disposal requirements
When electrical equipment is in operation, dangerous voltages are present in certain
parts of the equipment. Improper use of the equipment and failure to observe warning
notices will endanger personnel.
Only qualified personnel may work on or operate the equipment. Qualified personnel
The term 'Ground' used in this manual is the direct equivalent of the European term
are individuals who are: 'Earth'.

x familiar with the installation, commissioning, and operation of the equipment


and the system to which it is being connected.
x familiar with accepted safety engineering practises and are authorised to
energise and de-energise equipment in the correct manner.
Installation, Commissioning and Servicing
x trained in the care and use of safety apparatus in accordance with safety
engineering practises
x trained in emergency procedures (first aid).
3.1 Lifting Hazards
Many injuries are caused by:
The documentation provides instructions for installing, commissioning and operating x Lifting heavy objects
the equipment. It cannot, however cover all conceivable circumstances. In the event of x Lifting things incorrectly
questions or problems, do not take any action without proper authorisation. Please
x Pushing or pulling heavy objects
contact your local sales office and request the necessary information.
x Using the same muscles repetitively
Plan carefully, identify any possible hazards and determine how best to move the
Each product is subjected to routine production testing for Dielectric Strength and Protective product. Look at other ways of moving the load to avoid manual handling. Use the
Bonding Continuity
correct lifting techniques and Personal Protective Equipment (PPE) to reduce the risk of
injury.

3.2 Electrical Hazards


Symbols
Throughout this manual you will come across the following symbols. You will also see
these symbols on parts of the equipment.
30 RPV311-TM-EN-11.1
Chapter 2 – Safety Information RPV311 RPV311 Chapter 2 – Safety Information

Integration of the equipment into systems shall not interfere with


All personnel involved in installing, commissioning, or servicing
its normal functioning.
this equipment must be familiar with the correct working
procedures.
The functioning of the device has been certified under the
Consult the equipment documentation before installing, circumstances described by the standards mentioned in
commissioning, or servicing the equipment. Chapter 17: Technical Specifications (item Type Tests). Usage of
the equipment in different conditions from the specified in this
Always use the equipment as specified. Failure to do so will manual might affect negatively its normal integrity.
jeopardise the protection provided by the equipment.
The equipment shall have all their rear connectors attached even
if they are not being used, in order to keep their levels of ingress
Removal of equipment panels or covers may protection as high as possible
expose hazardous live parts. Do not touch until the
electrical power is removed. Take care when there
is unlocked access to the rear of the equipment. Never manipulate liquid containers near the equipment even
when it is powered off.

Avoid modification to the wiring of panel when the system is


Isolate the equipment before working on the running.
terminal strips.

VT circuits must never be left short circuited.

Use a suitable protective barrier for areas with


restricted space, where there is a risk of electric
shock due to exposed terminals.
3.3 Fusing and Insulation Requirements
Disconnect power before disassembling. Disassembly of the
equipment may expose sensitive electronic circuitry. Take
suitable precautions against electrostatic voltage discharge (ESD) A high rupture capacity (HRC) fuse type with a maximum current
to avoid damage to the equipment. rating of 10 Amps and a minimum dc rating of 250 V dc may be
used for the auxiliary supply (for example Red Spot type NIT or
NEVER look into optical fibres or optical output connections. TIA). Alternatively a miniature circuit breaker (MCB) of type C,
Always use optical power meters to determine operation or signal 10A rating, compliant with IEC 60947-1 and IEC 60947-3 may be
level. used.

Testing may leave capacitors charged to dangerous voltage levels. Digital input circuits should be protected by a high rupture
Discharge capacitors by reducing test voltages to zero before capacity NIT or TIA fuse with maximum rating of 10 A, or
disconnecting test leads. equivalent MCB as above. For safety reasons, current transformer
circuits must never be fused. Other circuits should be
If the equipment is used in a manner not specified by the
appropriately fused to protect the wire used.
manufacturer, the protection provided by the equipment may be
impaired.
Reason devices contain an internal fuse for the power supply
Operate the equipment within the specified electrical and which is only accessed by opening the product. This does not
environmental limits. remove the requirement for external fusing or use of an MCB as
previously mentioned. The ratings of the internal fuses are:
Before cleaning the equipment, ensure that no connections are RPV unit: 5 Amp, type T, 250V rating
energised. Use a lint free cloth dampened with clean water.
RA units: 2 Amp, type T, 250V rating

32 RPV311-TM-EN-11.1
RPV311-TM-EN-11.1 31
Chapter 2 – Safety Information RPV311 RPV311 Chapter 2 – Safety Information

The PCT is sometimes used to terminate cable screens. Always


CTs must NOT be fused since open circuiting them may produce
check the PCT’s integrity after adding or removing such earth
lethal hazardous voltages.
connections.

Models with a low DC power source must be supplied with a DC


supply source to the equipment that is derived from a secondary
The user is responsible for ensuring the integrity of any
circuit which is isolated from the AC/DC Mains by Double or protective conductor connections before carrying out any
Reinforced Insulation (e.g.: UL Certified ITE power supply which other actions.
provides Double or Reinforced Insulation).
The PCT connection must have low-inductance and be as short
as possible. For best EMC performance, ground the unit using
a 10 mm (0.4 inch) wide braided grounding strap.
3.4 Equipment Connections
All connections to the equipment must have a defined
potential. Connections that are pre-wired, but not used,
should be earthed, or connected to a common grouped
Terminals exposed during installation, commissioning and potential.
maintenance may present a hazardous voltage unless the
equipment is electrically isolated.
Pay extra attention to diagrams before wiring the equipment.
Always be sure that the connections are correct before
energizing the circuits.
Tighten M3 clamping screws of heavy duty terminal block
connectors to a nominal torque of 1.0 Nm.
Tighten captive screws of header-type (Euro) terminal blocks to The connections: Console1, Console2, MODEM and Process
0.5 Nm minimum and 0.6 Nm maximum. bus are non-isolated and for local connection only.

Always use insulated crimp terminations for voltage and current


connections.
3.5 Pre-energisation Checklist
Always use the correct crimp terminal and tool according to the
wire size.
Check voltage rating/polarity (rating label/equipment
documentation).
In order to maintain the equipment’s requirements for
protection against electric shock, other devices connected to the
Check CT circuit rating (rating label) and integrity of
RPV311 and RA33x shall have protective class equal or superior
connections.
to Class I.

Check protective fuse or miniature circuit breaker (MCB)


rating.
Watchdog (self-monitoring) contacts are provided to indicate
the health of the device on some products. We strongly
recommend that you hard wire these contacts into the Check integrity of the PCT connection.
substation's automation system, for alarm purposes.

Check voltage and current rating of external wiring,


Earth the equipment with the supplied PCT (Protective ensuring it is appropriate for the application.
Conductor Terminal).

Do not remove the PCT.

34 RPV311-TM-EN-11.1
RPV311-TM-EN-11.1 33
Chapter 2 – Safety Information RPV311 RPV311 Chapter 2 – Safety Information

3.6 Peripheral Circuitry Do not insert or withdraw modules, PCBs or expansion


boards from the equipment while energized, as this
may result in damage to the equipment. Hazardous
live voltages would also be exposed, endangering
Do not open the secondary circuit of a live CT personnel.
since the high voltage produced may be lethal to
personnel and could damage insulation. Short
the secondary of the line CT before opening any
connections to it. Internal modules and assemblies can be heavy and may
have sharp edges. Take care when inserting or removing
modules into or out of the IED.

Reason devices DO NOT feature any automatic CT shorting feature. Therefore


external shorting of the CTs is mandatory. Check the equipment documentation
and wiring diagrams carefully. Decommissioning and Disposal
Before decommissioning, completely isolate the
Where external components such as resistors or voltage equipment power supplies (both poles of any dc supply).
dependent resistors (VDRs) are used, these may present a The auxiliary supply input may have capacitors in
risk of electric shock or burns if touched. parallel, which may still be charged. To avoid electric
shock, discharge the capacitors using the external
terminals before decommissioning.
Operation of computers and equipment connected to
RPV311 and RA33x under environmental conditions such as
temperature and humidity that exceed the conditions Avoid incineration or disposal to water courses. Dispose
specified in their respective manuals can cause of the equipment in a safe, responsible and
malfunctioning or even irreversible damage to them or the environmentally friendly manner, and if applicable, in
nearby installation. accordance with country-specific regulations.

There might be situations in which the RPV311 and RA33x


are operating within its environmental operational range,
but the computers, equipment connected to them or nearby
equipment are operating outside their operational range. Standards Compliance
That situation can cause malfunctioning and/or irreversible
damage to those devices. In that occasion the Compliance with the European Commission Directive on EMC and LVD is demonstrated
communication to the Reason equipment might be using a Technical File.
compromised but its recording, operational and safety
capacities will not be affected.

Take extreme care when using external test blocks and 5.1 EMC Compliance:
test plugs such as the MMLG, MMLB and P990, as
hazardous voltages may be exposed. Ensure that CT Compliance with IEC 60255-26:2013 was used to establish conformity.
shorting links are in place before removing test plugs, to
avoid potentially lethal voltages.
5.2 Product Safety: 2006/95/EC
Compliance with IEC 61010-1:2010 was used to establish conformity.

3.7 Upgrading/Servicing Protective Class


Protective Class 1. This equipment requires a protective conductor (earth) to ensure
user safety.
36 RPV311-TM-EN-11.1
RPV311-TM-EN-11.1 35
Chapter 2 – Safety Information RPV311

Installation category
IEC61010-1:2010 Overvoltage Category II.

Environment
IEC 60068-2-1, IEC 60068-2-2, IEC 60068-2-30, IEC 60068-2-14, IEC 60255-21-1, IEC
60255-21-2. The equipment shall always be installed in a specific cabinet or housing
which will enable it to meet the requirements of IEC 60529 with the classification of
degree of protection IP54 or above.

5.3 R&TTE Compliance


Radio and Telecommunications Terminal Equipment (R&TTE) directive 99/5/EC.
Conformity is demonstrated by compliance to both the EMC directive and the Low
Voltage directive, to zero volts.

RPV311-TM-EN-11.1 37
RPV311 Chapter 3 – Hardware Design

RPV311 1.1 Processing Capability


The RPV311 has 8 link connections to communicate with RA33x acquisition units. As
each acquisition unit has different number of channels and functions, they require
different levels of demand from the RPV311. In order to respect the RPV311 processing
Distributed Multifunction Fault Recorder capability the number of RA33x that can be connected to the RPV311 obey the
following rule:
The RPV311 can process 12 logical slots and each RA demands the following number of
Chapter 3: Hardware Design slots.

This chapter provides information about the hardware design of the products.

Device Logic Demand (slots)

Hardware Architecture RA331 1


The RPV311 is a multifunction processing unit and has an acquisition system with 16-bit
A/D D converters that provide an acquisition rate of 256 points-per-cycle synchronized RA332 2
by the IRIG-B signal.
It has a high processing capability, which allows the acquisition of up to 64 analog RA333 DFR 1
channels and 256 digital channels divided in up to 8 acquisition modules connected by
RA333 TW 2
fiber-optic links. Additionally, it is able to detect IEC 61850 GOOSE messages.
All the registers are stored in a SSD hard disk.
It allows communication through the electrical Ethernet ports and optionally has a The user can combine the RA units as long as the logical sum of the slots value of each
double internal converter for optical Ethernet interfaces. RA do not exceed the maximum number of 12.
Monitoring and configuration are performed through a web interface; also, it has a
human-machine interface on the front panel for displaying information. It has a
MODBUS and DNP3 interface for SCADA integration. Note:
The RA331 module allows data acquisition of up to 8 analog channels (voltage, current, Differently from the RA331/332 the RA333 has two link: One for the DFR
functionality and another for the TW functionality.
or DC transducers) and up to 32 digital channels. The RA332 module allows data
acquisition of up to 16 analog channels (voltage, current, or DC transducers) and up to
32 digital channels. Both modules use 16-bit A/D converters providing an acquisition
rate of 256 points-per-cycle.
The RA333 module allows data acquisition of high-speed analog channels (voltage) for
one transmission line. This module allows the scheme to obtain traveling wave records
for fault locating. Additionally, the RA333 module allows data acquisition of up to 8
Mechanical Implementation
analog channels (voltage, current, or DC transducers) and up to 32 digital channels,
using 16-bit A/D converters providing an acquisition rate of 256 points-per-cycle
2.1 RPV311

2.1.1 Main features


x Fan-less and no rotating part design
x Trigger waveform recorder at 256, 128, or 64 points-per-cycle;
x Continuous waveform recorder at 16 points-per-cycle;
x Continuous disturbance recorder and trigger recorder (optional);
x Trigger using Boolean logic equations;
x Traveling wave recorder for fault location (optional);
x MODBUS and DNP3 interface for SCADA integration (optional);

Figure 2: RA332, RA333 and RPV311 40 RPV311-TM-EN-11.1


Chapter 3 – Hardware Design RPV311 RPV311 Chapter 3 – Hardware Design

Alarm: Lights up when the equipment requires attention of the operator.


x Synchrophasor measurement according to IEEE C37.118 (optional);
Trigger: Flashes when a threshold has been triggered;
x Power quality records: Sync: Lights up when the internal clock and the acquisition system are synchronized
ƒ Historical average at aggregation intervals of 1 or 10 minutes (optional); through the IRIG-B signal, whether the GPS Clock that provides the IRIG-B signal is
ƒ Measurement and recording of harmonics up to the 50th order according to locked or not;
IEC 61000-4-7 (optional); Ready: Lights up after the equipment has passed through the self-test routines and is
ƒ Measurement and recording of flicker according to IEC 61000-4- then in normal operation.
15:1997+A1:2003 (optional);
B Local interface for human-machine interaction.
x Cross-trigger using standard network connection;
C Buttons for navigation on the local interface.
x One-end fault location based on Takagi algorithm;
x Flexible communication: Back view of the RPV311, showing all the main components on the back panel.
ƒ Two 10/100BaseT electrical Ethernet interfaces;
ƒ Two embedded optical Ethernet converters;
ƒ RS232 serial port for modem connection;
x Support for IEC 61850:
ƒ Up to 320 binary inputs related to GOOSE messages (optional);
ƒ Two Ethernet ports for redundant connection (optional);
ƒ One Ethernet port for Process Bus (Sampled Values) connection (optional).
x Local interface on the front panel;
x dry-contact relays for remote signalling;
x Fax andȀor e-mail message after detection of a trigger. The fax can be sent to two
different destinations and the e-mail to four different destinations (optional).

2.1.2 Components
Figure 4: Back view of the RPV311

Front view of the RPV311, showing all the main components on the front panel.
D Up to 8 pairs of connectors for fiber-optic links. For each link there is an Act indicator
that lights up when the link is receiving data of the acquisition module.

E AC or DC power input.

F 4 dry contact relays.

G Electrical and Optical (optional) IRIG-B input for the external synchronization of the
equipment.
A H 2 electrical Ethernet interfaces for the communication between the equipment.

B I 1 electrical Ethernet interface for the Process Bus communication.


C
J Double internal converter for optical Ethernet interface.

K Serial port RS232 for modem connection.


Figure 3: Front View of the RPV311
L Maintenance ports for exclusive use by GE's technical support personnel.
A Indicators of the state of the equipment:

2.2 RA331

42 RPV311-TM-EN-11.1
RPV311-TM-EN-11.1 41
Chapter 3 – Hardware Design RPV311 RPV311 Chapter 3 – Hardware Design

F Front Panel Indicators: Mains lights up when the module is powered-up. Ready
2.2.1 Main Features indicator lights up after the module self-test is completed. The Link1 indicator lights up
when active.
x Up to 8 analog inputs (voltage, current, DC transducers, probes);
x Up to 32 digital inputs;
x 16-bit analog-to-digital converters, 256 points-per-cycle sampling rate; 2.3 RA332
x Frequency response of DC to 3.0 kHz;
x Fiber-optic interface to connect to the processing module;
2.3.1 Key Features
x Up to 2 km fiber-optic links;
x Up to 16 analog inputs (voltage, current, DC transducers, probes);
x Front panel mounting or internal panel mounting.
x Up to 32 digital inputs;
x 16-bit analog-to-digital converters, 256 points-per-cycle sampling rate;
2.2.2 Components
x Frequency response of DC to 3.0 kHz;
x Fiber-optic interface to connect to the processing module;
Figure 5 shows all the components of the RA331 module. x Up to 2 km fiber-optic links;
x Front panel mounting or internal panel mounting.

2.3.2 Components
Figure 6 shows all the components of the RA332 module.

Figure 5: Rear and front views of the RA331, respectively


A AC or DC power input.

B Mains and Ready back panel indicators: The Mains is lit when the module is powered.
Ready indicator lights up after the module self-test is completed.

C Up to 8 analog inputs for voltage, current, or DC transducers, identified as 101 to 108. Figure 6: Rear view of the RA332
A AC or DC power input.
D Up to 32 digital inputs identified as 201 to 232.
B Mains and Ready back panel indicators: Mains is lit when the module is powered-up.
E One connector for fiber optic links. The connector has an Act indicator that lights up
Ready indicator lights up after the module self-test is completed.
when its link is active (i.e., it is receiving requests of the processing module).
C Up to 16 analog inputs for voltage, current, or DC transducers, identified as 101 to 116.
44 RPV311-TM-EN-11.1
RPV311-TM-EN-11.1 43
Chapter 3 – Hardware Design RPV311 RPV311 Chapter 3 – Hardware Design

D Up to 32 digital inputs identified as 201 to 232.

E One connector for fiber optic links. The connector has an Act indicator that lights up
when its link is active (i.e., it is receiving requests of the processing module).

Front Panel Indicators: Mains lights up when the module is powered-up. Ready indicator
lights up after the module self-test is completed. The Link1 indicator lights up when
active. The front panels indicator of the RA332 are the same as the RA331, see Figure 5.

2.4 RA333

2.4.1 Key Features


x 3 high-speed analog inputs with 5 MHz;
x Up to 8 analog inputs with 50/60 Hz (voltage, current, DC transducers);
x Up to 32 digital inputs;
x 16-bit analog-to-digital converters, 256 points-per-cycle sampling rate for 50/60 Hz
acquisition; Figure 7: Front and back views of the RA333
x 8-bit analog-to-digital converters, 5 MHz sampling frequency for high-speed
acquisition;
x Frequency response of DC to 3.0 kHz; A AC or DC power input.

x 2 fiber-optic interface to connect to the processing module, one for 50/60 Hz and B Rear TW and DFR indicators, that means:
other for high-speed acquisition;
The Ready indicator lights up after the module's self-test is completed;
x Up to 2 km fiber-optic links;
The Mains indicator lights up when the module is powered;
x Front panel mounting or internal panel mounting. The PPS indicator flashes signaling that the timing signal of the processing module is
detected;
2.4.2 Components The Busy indicator lights up when a traveling wave signal is detected and the RA333 is
transmitting the data for processing module.

Figure 7 shows all the components of the RA333 module. C Connector for fiber optic link between RA333 and processing module of the TW
acquisition. The connector has an Act indicator that lights up when its link is active (i.e.,
it is receiving requests of the processing module).

D Connector for fiber optic link between RA333 and processing module of the analog
acquisition. The connector has an Act indicator that lights up when its link is active (i.e.,
it is receiving requests of the processing module).

E 3 high-speed analog inputs with 5 MHz identified as 301 to 303.

F Up to 8 analog inputs for voltage, current, or DC transducers, identified as 101 to 108.

G Up to 32 digital inputs identified as 201 to 232.

The front panel of the RA333 has the following indicative LEDs:

46 RPV311-TM-EN-11.1
RPV311-TM-EN-11.1 45
Chapter 3 – Hardware Design RPV311

The DFR Link indicators are lit when their links are active.
The DFR Ready indicators light up after the module self-test is completed.
The TW Busy indicator lights up when a traveling wave signal is detected and the RA333
is transmitting the data for processing module.
The TW PPS blinks once per second indicating that the unit is synchronized.
The TW LINK indicates that the TW module in the RA333 is communicating with the
RPV311 processing unit.
The TW READY indicates that the TW module in the RA333 is healthy.
MAINS lights up when the RA333 is powered on.

RPV311-TM-EN-11.1 47
Chapter 4 – Configuration RPV311

If the configuration is not transmitted to the equipment, the changes are not applied.
RPV311
Opening more than one configuration section at a time is not allowed. If a second session
is required, the following message will show:
Distributed Multifunction Fault Recorder The server is temporarily unable to service your request due to maintenance downtime
or capacity problems. Please try again later.

Chapter 4: Configuration By using the Configuration Tool, which is part of the DR Manager software, it is possible
to receive, manage, save, edit and transmit the configuration between equipment and a
computer.
This chapter includes concise instructions of how to configure all available features in
the device. For information about the Configuration Tool, see Chapter 13: Software – DR Manager.

Accessing the Equipment Configuration 1.1 Configuration History


The history of changes in the equipment configuration can be shown in the Web
Interface. The information shown is:
Access to the equipment's configuration is provided by the Web Interface. When the
equipment is accessed, a copy of the current configuration is maintained on the Revision Indicates the number of each configuration;
equipment until a new configuration is sent. Time stamp Indicates the date and time the configuration was changed;
To enter the configuration interface, click on the <CONFIGURE> button of the initial Web
User Indicates who changed the configuration;
Interface. A new window is open. The username and password are required. The default
Description Describes the change.
username and password are:
To obtain a report about the configuration, select the revision of the configuration and
click on the <REPORT> button. A new window will open displaying all the information
Default username and password to enter the configuration interface
about the configuration selected.

Username admin The configuration of the RPV311 can be done in 4 languages: English, Spanish, Russian,
Polish and Portuguese.
Password 1234

Equipment
The available information on the initial configuration screen is described below:

A Menu configuration items. It is recommended that the configuration of the equipment


be performed item by item in top-to-bottom order. The menu items in the configuration
2.1 Identification
can be configured one by one and by clicking on the <OK> button, the changes are saved On this screen, shown below, it is possible to configure the equipment identifier,
in the interface but will not be sent to the equipment. By clicking on the <CANCEL> button, location and owner.
the changes are discarded. These three fields make up the equipment file name pursuant to the COMNAME rule.
The equipment identification will appear in the name of the records; therefore, it is very
B The <LOGOUT> button allows user to logout the configuration section. important that it be properly identified. The name format of the records is:

C To send the changes to the equipment, click on the <UPLOAD> button. Before sending
the configuration to the equipment, the user must define the changes to be included in
date,hour,location,identifier,owner...
the configuration history. By clicking the <OK> button, the configuration is send and the
equipment will be temporarily unavailable.

D Arrows to pass by the menu items.

50 RPV311-TM-EN-11.1
RPV311 Chapter 4 – Configuration Chapter 4 – Configuration RPV311

B The TIMEZONE defines if time zone information is supplied by the IEEE1344 extensions
of the IRIG-B signal, or if it is manually set. This option will allow the RPV311 to identify
the UTC time using information from the signal or from the manual configuration of the
user:

ƒ When Auto (IRIGB with extensions) is selected the RPV311 shall use the
information of time zone sent within the IRIGB signal to recover the UTC time.

ƒ When Manual is selected the RPV will not consider eventual time zones within
the IRIGB signal, and rather it will use the UTC time zone configured in the
Manual parameter to retrieve the UTC time. This option is used specially when
the IRIGB does not inform the time zone, so the RPV311 cannot retrieve the UTC
time unless we inform the time zone manually.

The time setting that the RPV will use for time stamping is configured on the screen
Internal Clock.

It is possible to configure 30 min time zones.

C The NTP FALLBACK SERVER defines the IP address of the SNTP time server to be used to
provide time synchronism when the IRIG-B is not connected.

Figure 8: Equipment identification configuration section 2.2.2 Internal Clock


On the screen the internal clock for time stamping the registers and logs is configured,
as well as day light saving configurations.The configurable settings are:
A The IDENTIFIER text field allows user to enter an equipment code (maximum 12
A The TIMEZONE defines if time zone information is supplied by the IEEE1344 extensions
characters).
of the IRIG-B signal, or if it is manually set.
B The LOCATION text field allows user to enter a substation code (maximum 12
ƒ When Auto is selected the RPV311 will use the same local time sent within the
alphanumeric characters, ̴ , െ , 0 , 0-9 , a-z , A-Z)
IRIGB signal.
C The OWNER text field allows user to enter the name of the company which purchased
ƒ When Manual is selected the RPV311 will use the UTC time (retrieved using
the equipment (maximum 12 characters).
information from the Time Source screen) and calculate the local time using the
UTC time zone configured on the Internal Clock screen.

2.2 Synchronization B The DAYLIGHT SAVING TIME defines if time information is supplied by IEEE1344 extensions
of the IRIG-B signal, or if it is either manually set or disabled. If it is manually set, it is
If the IRIG-B signal has the CF extensions (IEEE1344), timing information as date, hour,
possible to choose the date and time of the start and the end of the DST period.
year, time zone and daylight saving time can be provided by the signal. Time zone and
daylight saving time information can also be manually set via the Web Interface, It is possible to configure 30 min time zones.
overriding the information of the IRIG-B signal.

2.2.1 Time Source 2.3 Communications


On the screen TIME SOURCE it is possible to configure how the RPV311 will interpret the
time zone of the IRIGB signal and also the IP address of the NTPv2, 3 or 4 server.
The configurable settings are: The RPV311 communication may be via Ethernet and serial ports. The equipment may
also operate as a gateway over a local subnet.
A Synch Source: Allows to user to choose between the IRIG-B signal or No Source.
Optionally the user can choose between two types of Ethernet, optical and electrical.

52 RPV311-TM-EN-11.1
RPV311-TM-EN-11.1 51
RPV311 Chapter 4 – Configuration Chapter 4 – Configuration RPV311

Gateway setup will enable the RPV311 to communicate with other equipment
connected over a local subnetwork. The Gateway can be configured by accessing the
equipment gateway configuration section, shown in Figure 9.

Figure 10: Equipment serial port configuration section

A The BITS, PARITY scroll box allows user to select the data bits (7 or 8), parity (none,
Figure 9: Equipment Ethernet configuration section
even or odd) and stop bit (1 or 2).

B The SPEED scroll box allows user to select the speed: 4800, 9600, 19200, 57600 or
A The IP text field allows user to enter the equipment's IP address.
115200 bps.
B The NETWORK MASK text field allows user to enter the subnetwork mask to which the
C The USE THIS PORT FOR ROUTING check box enables the use of the equipment as a
equipment is connected.
router for another network.
C The BROADCAST text field allows user to enter the sub network broadcast address to
D The MODEM check box allows permanent communication between an RPV311 and
which the equipment is connected.
a server through a telephone line.
D The IP text field allows user to enter the equipment's IP address.
E The DIAL OUT NUMBER text field allows user to enter a number to be dialed via
E The PORT scroll box allows user to select the communication port of the equipment used modem. This can be left blank if a direct serial communication link is used.
as gateway.
F The MODEM INIT STRING text field allows user to enter a string of characters which will
Ethernet 1 and Ethernet 2 can be configured.
be sent to the modem before any communication is attempted. This can be left
The Ethernet port enables the RPV to connect to the TCP / IP / UDP / IP networks. blank.

The RPV311 allows point-to-point communication with a conventional modem, cellular


phone, GPRS and radio links. The Serial Port can be configured by accessing the section
shown in Figure 10.

54 RPV311-TM-EN-11.1
RPV311-TM-EN-11.1 53
RPV311 Chapter 4 – Configuration Chapter 4 – Configuration RPV311

2.4 Acquisition with remote acquisition modules


A The Position represents the position where the acquisition module is physically
connected to the RPV311. Positions A to L.
The RPV311 data acquisition can be performed by the RA331, RA332 and RA333 remote
acquisition modules. B The Module scroll box allows user to select the acquisition module used in the link
The RA333 module consists of two different acquisition systems. One, called DFR, is
and its characteristics based on the Part Number of the module. The modules can
used for analog data acquisition of 50/60 Hz of voltage, current, or DC. The other, called
be:
TW, is used for high-speed acquisition of traveling waves. The RA333 (TW) and RA333
(DFR) are physically installed in the same module, but are logically independent, i.e., the RA331: Acquisition module with up to 8 analog (voltage, current, or DC) and 32
RPV311 will be treated as two logical modules. digital channels;
The RA331, RA332 and RA333 (DFR) modules are independent and use 16-bit opto- RA332: Acquisition module with up to 16 analog (voltage, current, or DC) and 32
isolated A/D converters with simultaneous acquisition of all channels provided by the digital channels;
IRIG-B signal, thus ensuring that the frequency acquisition is kept constant. RA333 (TW): High frequency acquisition module with 3 high-speed analog channels
The analog channels for current measurement use internal shunts to minimize the for acquisition of the traveling waves;
effects of phase variation caused by transformers.
RA333 (DFR): Acquisition module with up to 8 analog (voltage, current, or DC) and
There is a delay in the data transmission of the acquisition module for the processing 16 digital channels.
module proportional to the length of the fiber-optic cable. This delay is compensated by
the RPV311 considering the information of the fiber length specified in the
configuration of the equipment. Note 1:
The last two fields related to the binary inputs are configure according to the physical
The links should be installed of positions A to L. Intermediate empty positions are
order of the inputs in the back of the RA33x, as in Figure 6: Rear view of the RA332. The
considered as "using" 8 analog channels. last field corresponds to the inputs 201 to 216 and the next to the last to 217 to 232. In
Each link must be configured considering the module type and its inputs. the Part Number the binary fields are inverted in comparison with the physical order.
To configure the links, access the LINKS section, shown in Figure 11. Note 2:
The board options 2 and 6 are only available from RPV311 firmware version 14
onwards

C The Fiber length text field allows user to enter the fiber length, in meters, to
compensate the delay in the data transmission between the acquisition and
processing modules.

All analog channels have two configuration options. Circuits and channels will be
configured based on the option selected.
In the Inputs section, shown in Figure 12, it is possible to configure the analog inputs of
the acquisition module connected with the RPV311 configured in the previous section.
It is important to configure the analog inputs for voltage or current, according to the
physical configuration of the module, shown in Chapter 15: Installation. The RA333's
high-speed acquisition channels do not require configuration, since they are dedicated
for voltage measurement.
To improve the accuracy of the measurement, a correction factor can be manually
provided. Inputs without the correction factor have accuracy better than 1%.
The digital channels do not have type selection.

Figure 11: Links between RPV and acquisition modules configuration section

56 RPV311-TM-EN-11.1
RPV311-TM-EN-11.1 55
RPV311 Chapter 4 – Configuration Chapter 4 – Configuration RPV311

Figure 13: Sampled Values subscriptions links configuration section

Figure 12: Analog inputs configuration section


A The ENABLED check box allows user to enable the Subscription link feature.

B The SAMPLED VALUE IDENTIFIER text field allow user to insert the monitored Sampled Values
A The POSITION indicates the position of each analog input on the back panel of the
identification.
module.
C The MAC ADDRESS text field allow user to insert the monitored Merging Unit MAC
B The INPUT scroll box allows user to select the type of the signal to be measured (AC
Address.
voltage 115 V, AC current 1 A, AC current 5 A, DC current 0-20 mA or DC voltage ±10 V).
D The APP ID text field allow user to insert the monitored Sampled Values APP ID.
C The ADJUSTMENT text field allows user to enter a correction factor to adjust the accuracy
of the measurement. E The VLAN ID text field allow user to insert the VLAN ID of the monitored Sampled
Values.

F The VLAN PRIORITY scroll box allow user to select the priority of the Sampled Values data
2.5 Acquisition with Sampled Values at the configured VLAN.
The RPV311 data acquisition can be performed by Sampled Values data, incoming of
G The SAMPLE RATE scroll box allow user to select the Sampled Values sample rate. 80
Merging Units. The acquisition is done by connecting the Process Bus Ethernet port to
points-per-cycle is used for protection purposes and 256 points-per-cycles is used for
the Sampled Values generator.
If the acquisition is done by Sampled Values, there is no physical link to configure. The measurement purposes.
configuration is performed by Subscription links. Each subscription link contains data of H The PACKET LOSS TOLERANCE allow user to insert a package-loss rule.
4 current (Phases A, B, C and Neutral) and 4 voltage (Phases A, B, C and Neutral) circuits.
Once a subscription link is created, the RPV311 automatically configures the first
channels as current and the last as voltage, as shown in Figure 86. This is done because
In the Inputs section, shown in Figure 14, it is possible to configure the analog inputs of
the Merging Units send the Sampled Values package according to the IEC 61850-9-2LE.
the Sampled Values configured in the previous section. It is important to configure the
The RPV311 processing module can be configured with up to 8 Subscription links.
analog inputs for voltage or current, according to the Sampled Values messages
To configure the links, access the SAMPLED VALUES SUBSCRIPTIONS section, shown in Figure
received of the monitored Merging Unit.
13.

58 RPV311-TM-EN-11.1
RPV311-TM-EN-11.1 57
RPV311 Chapter 4 – Configuration Chapter 4 – Configuration RPV311

Figure 14: Analog inputs configuration section for Sampled Values channels Figure 15: Equipment access control configuration section

A The POSITION indicates the position of each analog input according to the Sampled Value A The USE PASSWORD FOR ALL ACCESS LEVELS check box enables use of password to access
message. equipment operation and configuration via Web Interface.

B The INPUT scroll box allows user to select the type of the signal to be received as Sampled B The FIRMWARE UPDATE PASSWORD text field allows user to enter an independent password
Values. to update the firmware for the equipment. The factory-set default password is 12345.
This field cannot be disabled.
C The ADJUSTMENT text field allows user to enter a correction factor to adjust the accuracy
of the measurement. C The DOWNLOAD PASSWORD text field allows user to enter an independent password to
access the automatic file records scanning. The factory-set default password is 12345.
This field cannot be disabled.

D The GOOSE CONFIGURATION PASSWORD text field allows user to enter an independent
2.6 Access Control password to configure the GOOSE application. The factory-set default password is 12345.
This field cannot be disabled.
The equipment has independent access control to:
x Check the equipment status, monitor the measured values, access the records The password can have up to 8 characters and following ones are allowed: Alphabetic,
and the equipment's configuration; numeric, upper and lower case, dash (-) and underscore (_).
x Firmware Upgrade;
x Maintenance;
x Modem connection.
2.7 User
In the section shown in Figure 15, it is possible to determine whether the password will
be required for every access and it also allows user to exchange the update firmware
password and the download password. It is possible to either add a new user or configure the administrator user.
In the Add a new user section, shown in Figure 16, it is possible to add users with
different access levels.

60 RPV311-TM-EN-11.1
RPV311-TM-EN-11.1 59
RPV311 Chapter 4 – Configuration Chapter 4 – Configuration RPV311

Figure 16: Adding new user section

Figure 17: Changing the administrator password section: Changing the administrator password section

A The USER text field allows entering a user identification (maximum 8 characters).
No editing is allowed. A The OLD PASSWORD text field allows user to enter an old password.
B The NEW PASSWORD text field allows user to enter a new password to access the B The NEW PASSWORD text field allows user to enter a new password to access the Web
Web Interface (maximum 8 characters). Interface (maximum 8 characters).

C The CONFIRM text field allows user to confirm password entered in the field above. C The CONFIRM text field allows user to confirm password entered in the field above.

D The ALLOW user to configure equipment check box allows user to set the equipment The user administrator is always able to configure the equipment and cannot be
and also to access the Web Interface. deleted.

To delete a user, select the user in the configuration interface menu and click on the 2.8 Record Management
<REMOVE> button. User can be deleted only if there is more than one user entered and
may be performed by any user who is authorized to access equipment setup. In this section, shown in Figure 18, it is possible to configure the permanent deletion of
In the User - admin section, shown in Figure 17, it is possible to change the equipment records, when memory capacity exceeds 90%.
administrator password.
The following characters are allowed in the passwords: Alphabetic, numeric, upper and
lower case, dash (-) and underscore (_).

62 RPV311-TM-EN-11.1
RPV311-TM-EN-11.1 61
RPV311 Chapter 4 – Configuration Chapter 4 – Configuration RPV311

Figure 18: Record management configuration section Figure 19: Auto upload configuration section

A Selecting the AUTO ERASE check box, erases older record automatically if memory A The DESTINATION check box allows user to select a record destination IP address
capacity exceeds 90%. previously entered.

B The ERASE ALL scroll box allows user to choose a type of record (fault, disturbance, B Selecting the FAULT, DISTURBANCE, STEADY-STATE, TRAVELING WAVE OR SOE check boxes, these
steady-state and SOE) to be removed. records will be automatically uploaded to a preset destination.

C The <EXECUTE> button allows user to erase all the records on the list.

For details about the memory capacity of each record type, see Chapter 6: Records.
2.9.2 E-mail/Fax

The RPV311 is capable of sending email up to 4 different addresses and fax up to 2


2.9 Auto Upload different numbers.
Upon creating a new COMTRADE file the RPV send a warning email/fax with the name
2.9.1 Records of the register that has been created. The file name contains the time stamp of the
fault.
It is possible to send a record to two different servers. In the configuration interface it is
possible to configure the IP address of each destination server and the type of record
which will be sent. When a new record is generated and the record type is enabled for
auto upload, it is automatically transmitted to the servers.
If at the upload time the server is not available or the network is unreadable, the record
is not retransmitted. In this case, the record will be transmitted only through the
automatic scanning by the server.
The automatic upload of records is a process in which the records are transferred to the
server in advance. To ensure that all the records are stored in the server, it is necessary
that the server perform the scanning process periodically. The records that have already
been transmitted to the server are not retransmitted.
In the section shown in Figure 19, it is possible to automatically upload records to a
preset destination.

64 RPV311-TM-EN-11.1
RPV311-TM-EN-11.1 63
RPV311 Chapter 4 – Configuration Chapter 4 – Configuration RPV311

The RATIO text fields allows user to enter ratio of power transformers for each input.

Once the circuit is created, it appears in the configuration interface menu. When
selecting the circuit, a screen shows the characteristics of the circuit selected, as shown
in Figure 21. It is possible to edit some parameters, such as nominal value and
transformation ratio.
The frequency is calculated individually for each circuit as long as the magnitude of the
voltage is over 10% of the nominal magnitude configured in the Voltage Circuit window.
The frequency track occurs within the range of Nominal Frequency ±5Hz.

Figure 20: Email/Fax configuration

Voltage Circuit

Considering the input type configurations, it is possible to create voltage circuits with 1,
2, 3, or 4 elements. Figure 21: Adding and editing voltage circuits
The circuit sequences supported by the equipment are ABC, BCA, CAB, CBA, BAC, and
CBA and may be customized by the user in the equipment setup. The default sequence
is ABC.
To add a new voltage circuit select the VOLTAGE CIRCUITS section and fill in the following: Current Circuits
The IDENTIFIER text field allows user to enter a single code for the circuit being defined
(maximum 15 characters). No editing allowed;
Considering the input type configurations, it is possible to create current circuits with 1,
The WIRING scroll box allows user to select a number of elements used for measuring (1,
2, 3, or 4 elements.
2, 3, or 4). No editing allowed;
The phase sequences of the circuits supported by the equipment are ABC, BCA, CAB,
Selecting the 3-PHASE CIRCUIT SYNTHESIS check box, the 3-phase circuit synthesis is enabled.
CBA, BAC, and CBA and may be customized by the user in the Equipment Setup, shown
It is only possible to select 3-phase circuit synthesis in a 1 element circuit (phase A, B, or
in Section 2.9. The default sequence is ABC.
C);
To add a new current circuit, select the CURRENT CIRCUITS section and fill in the following:
The INPUTS scroll box allows user to select the inputs to which each measuring element
is connected. No editing allowed;
The NOMINAL VALUE text field allows user to enter a circuit rated voltage;
66 RPV311-TM-EN-11.1
RPV311-TM-EN-11.1 65
RPV311 Chapter 4 – Configuration Chapter 4 – Configuration RPV311

The IDENTIFIER text field allows user to enter a single code for the circuit being defined
(maximum 15 characters). No editing allowed;
The WIRING scroll box allows selecting a number of elements used for measuring (1, 2, 3
4.1 GIC Configuration (Geomagnetically Induced Current)
or 4). No editing allowed; GICs are quasi-DC currents that cannot be measured with conventional CTs. In
Selecting the 3-PHASE CIRCUIT SYNTHESIS check box, the 3-phase circuit synthesis is enabled. conjunction with optical CT and IEC 61850-9-2LE Merging Units, the RPV311 can be
It is only possible to select 3-phase circuit synthesis in a 1 element circuit (phase A, B, or applied to monitored GIC currents in the power system
C);
The INPUTS scroll box allows user to select the inputs to which each measuring element To create a circuit to monitor GIC, check the GIC check box in the current circuit wiring
is connected. No editing allowed; screen, as below:
The NOMINAL VALUE text field allows user to enter a circuit rated current;
The FREQUENCY REFERENCE scroll box allows user to select a reference voltage circuit;
The RATIO text fields allows user to enter ratio of power transformers for each input
.
Once the circuit is created, it appears in the configuration interface menu. When
selecting the circuit, a screen shows the characteristics of the circuit selected, as shown This check box configuration will disable the autozero filter that all the RPV311 channels
in Figure 22. It is possible to edit some parameters, such as nominal value, frequency have (autozero is slow filter that removes the DC components from the measurement)
reference, and transformation ratio. and apply a low-pass first order filter to the current measurement. This channel will
The frequency is calculated individually for each circuit as long as the magnitude of the only monitor and show DC measurement then, instead of RMS.
current is over 10% of the nominal magnitude configured in the Current window of the The first order filter has a configurable time constant ranging from 0,1 to 1000 seconds
chosen Voltage Circuit. The frequency track occurs within the range of Nominal that can be chosen in the last screen of the current circuit configuration, as below.
Frequency ±5Hz.

Note:
In a GIC circuit, the RMS measurement is replaced by the DC measurement. When
creating a threshold in a GIC circuit, the ABC threshold is related to the DC
measurement.

Figure 22: Adding and editing current circuits

A The <RENAME> button allows user to rename the circuit.

B The <REMOVE> button allows user to delete the circuit. Power Circuit
68 RPV311-TM-EN-11.1
RPV311-TM-EN-11.1 67
RPV311 Chapter 4 – Configuration Chapter 4 – Configuration RPV311

The acquisition is simultaneous and synchronized with a time resolution of 65.104 ߤs at


Power circuits can be created of circuit voltage and current. 60 Hz or 78.125 ߤs at 50 Hz. The polarity is user-programmable (active high, active low).
To add a new power circuit select the POWER CIRCUITS section and fill in the following: Digital channels can be associated with physical electrical digital inputs or associated
with the detection of IEC61850 GOOSE messages. For details about the GOOSE
The IDENTIFIER text field allows user to enter a single code for the circuit being defined messages, see Chapter 11: GOOSE Message Detection. The level of the state transitions
(maximum 15 characters). No editing allowed; for physical inputs can be seen in Chapter 17: Technical Specifications
The VOLTAGE CIRCUIT scroll box allows user to select a code of the voltage circuit to be It is possible to adjust denouncing of the digital input to eliminate the effect of
used; switching of the relay contacts. The debounce time has a 0 to 20ms with 1ms steps.
The CURRENT CIRCUIT scroll box allows user to select a code of the current circuit to be All transitions of the digital channels are stored in the sequence of events (SOE) record.
used. To add a new digital channel, select the Digital Channels section and fill in the following:
The IDENTIFIER text field allows user to enter a single code for the channel being defined
Once the circuit is created, it shows in the configuration interface menu. When selecting (maximum 15 characters). No editing allowed;
the circuit, a screen shows the characteristics of the circuit selected, as shown in Figure The INPUT scroll box allows user to define the input to which each digital channel is
23. It is possible to edit the voltage or current circuit. connected. No editing allowed;
The frequency is calculated individually for each circuit as long as the magnitude of the The POLARITY scroll box allows user to select the input logic level (normal or inverted);
voltage is over 10% of the nominal magnitude configured in the Voltage Circuit window. DEBOUNCING TIME: the RPV311 will only start a record once the binary activation time has
The frequency track occurs within the range of Nominal Frequency ±5Hz. exceeded the debouncing time parameter.
Once the digital channel is created, it shows in the configuration interface menu. When
selecting the digital channel, a screen shows the characteristics of the digital channel
selected, as shown in Figure 24. It is possible to edit the polarity and the debounce
time.

Figure 23: Adding and editing power circuits

The <RENAME> button allows user to rename the circuit.


The <REMOVE> button allows user to delete the circuit. Figure 24: Adding and editing digital channels

The <RENAME> button allows user to rename the digital channel.


Digital Channels The <REMOVE> button allows user to delete the digital channel.

70 RPV311-TM-EN-11.1
RPV311-TM-EN-11.1 69
RPV311 Chapter 4 – Configuration Chapter 4 – Configuration RPV311

DC Channels

The signal of the transducer (±10 V or 0-20 mA) is converted in to the desired physical
measurement using a first order transfer function with the parameters of gain (‫ )ܣ‬and
offset (‫ )ܤ‬defined by the user:

‫ ݕ‬ൌ ‫ܣ‬ሺ‫ ݔ‬൅ ‫ܤ‬ሻ

where ‫ ݕ‬is the converted value and ‫ ݔ‬is the value read by the DC channel in Volts or
Amps.
The RMS value of the DC channels (transducers) is calculated every cycle.
To add a new DC channel, select the DC CHANNELS section and fill in the following:
The IDENTIFIER text field allows user to enter a single code for the channel being defined
(maximum 15 characters). No editing allowed;
The INPUT scroll box allows user to define the input to which each DC channel is
connected. No editing allowed;
The FREQUENCY REFERENCE scroll box allows user to select a reference voltage circuit;
The GAIN and the OFFSET text field allows user to define the transfer connected
transducer function;
The UNIT text field allows user to define the connected transducer unit (maximum 6 Figure 25: Adding and editing DC channels
characters, letters only).

Once the DC channel is created, it shows in the configuration interface menu. When The <RENAME> button allows user to rename the DC channel.
selecting the DC channel, a screen shows the characteristics of the DC channel selected, The <REMOVE> button allows user to delete the DC channel.
as shown in Figure 25. It is possible to edit the frequency reference, gain, offset and
unit.

Thresholds

Measured values are continuously monitored and may be tested once every cycle of the
nominal frequency of the system, against lower and upper thresholds and range rates
involving:
x Magnitude;
x Frequency;
x Active, Reactive, and Apparent Powers;
x Positive and Negative Sequences;
x Imbalance;
x Digital Signals.
x Variation (d/dt)¹
x GOOSE Signals

¹ The variation thresholds are calculated using a 1-cycle time window.


72 RPV311-TM-EN-11.1
RPV311-TM-EN-11.1 71
RPV311 Chapter 4 – Configuration Chapter 4 – Configuration RPV311

The results of all thresholds are processed using user-definable Boolean equations and
can be used to trigger the recording of fault, traveling waves, and disturbance data.
The thresholds can be associated with power, voltage and current circuits, digital
To add a voltage threshold fill in the following:
channels or DC channels, as follows:
The SOURCE scroll box allows user to define a code of a voltage circuit used. No editing
Voltage and Current: upper and lower limits, and rate of change: allowed;
The QUANTITY scroll box allows user to select the associated magnitude to be monitored.
o  - RMS value; For voltage circuits:
o  - neutral RMS value;
x  and  - magnitude or effective value;
o ͳ - RMS value of fundamental component;
x  and ͳ - phasors;
o ͳ - RMS value of neutral fundamental component;
x ܵା - positive sequence;
o ‫ܨ‬ - frequency;
o ܵା - positive sequence; x ܵି - negative sequence;
o ି - negative sequence; x   - imbalance;
o ܷ - imbalance; x   - frequency;
o   - total harmonic distortion. x   - total harmonic distortion;
o  - voltage oscillation; x  - voltage oscillation;
o  - frequency oscillation (measured from voltage);
x  - frequency oscillation;
x † and dN: - magnitude or effective value variation;
Power: upper and lower limits, and rate of change:
x †ͳ and dN1 - phasor variation;
o  - combined apparent power; x ݀ܵ ା - positive sequence variation;
o ଵ - fundamental apparent power; x ݀ܵ ି - negative sequence variation;
o ଵ - fundamental active power;
x †  - unbalance variation;
o ଵ - fundamental reactive power.
x †  - frequency variation;
x †  - THD variation.
Power: upper limits:

o ܱܵ‫ܥ‬ - power swing.


The OPERATOR scroll box allows user to select greater than or less than for analog
DC Transducers: upper and lower limits; magnitude;
The VALUE text field allows user to enter the magnitude value associated with greater
Digital channels: "L" to "H" transition, "H" to "L" transition, "H" and "L" level.;
than or less than operator;
Following parameters can be set for every defined threshold: The HOLD TIME text field allows user to enter the time in milliseconds, where the
threshold needs to be exceeded to be considered valid. Due to internal processing time
the trigger might start up to 2 cycles after the hold time;
The HYSTERESIS text field allows user to enter a percentage of the VALUE , the quantity
Parameters set for every defined threshold
monitored needs to exceed that percentage in order to end the event and to reset the
threshold detector.
Hysteresis 0 … 100 % 0.1 %
Once the threshold is created, it appears in the configuration interface menu. When
Hold time 0 … 0.5 s 0.01 s
selecting the threshold, a screen shows the characteristics of the threshold selected, as
shown in Figure 26. It is possible to edit the value, hold time, and hysteresis.

To add new thresholds, select the ADD NEW THRESHOLDS section and choose the type of
threshold (voltage, current, power, digital, or DC). Each threshold is related to a circuit
or channel previously created.

8.1 Adding New Voltage Thresholds


74 RPV311-TM-EN-11.1
RPV311-TM-EN-11.1 73
RPV311 Chapter 4 – Configuration Chapter 4 – Configuration RPV311

x † and dN: - magnitude or effective value variation;


x †ͳ and dN1 - phasor variation;
x ݀ܵ ା - positive sequence variation;
x ݀ܵ ି - negative sequence variation;
x †  - unbalance variation;
x †  - frequency variation;
x †   - THD variation.

The OPERATOR scroll box allows user to select greater than or less than for analog
magnitude;
The VALUE text field allows user to enter the magnitude value associated with greater
than or less than operator;
The HOLD TIME text field allows user to enter the time in milliseconds, where the
threshold needs to be exceeded to be considered valid. Due to internal processing time
the trigger might start up to 2 cycles after the hold time;
The HYSTERESIS text field allows user to enter a quantity in Ψ, whose the value needs to
be smaller in relation to the threshold to determine the end of the event and to reset
the threshold detector.

Figure 26: Adding and editing a voltage threshold


Once the threshold is created, it appears in the configuration interface menu. When
selecting the threshold, a screen shows the characteristics of the threshold selected, as
shown in the figure below. It is possible to edit the value, hold time, and hysteresis.
A The <APPLY ALL> button allows user to apply the hold time or the hysteresis for all
thresholds.

B The <REMOVE> button allows user to delete the threshold.

8.2 Adding New Current Thresholds

To add a current threshold, fill in the following:


The SOURCE scroll box allows user to define a code of a current circuit used. No editing
allowed;
The QUANTITY scroll box allows user to select the associated magnitude to be monitored.
For current circuits:
x  and  - magnitude or effective value (DC measurement for GIC
circuits);
x ͳ and ͳ - phasors;
x ܵା - positive sequence;
x ܵି - negative sequence;
x  - imbalance;
x  - frequency;
x   - total harmonic distortion;
76 RPV311-TM-EN-11.1
RPV311-TM-EN-11.1 75
RPV311 Chapter 4 – Configuration Chapter 4 – Configuration RPV311

x The OPERATOR scroll box allows user to select greater than or less than for analog
magnitude.
x The VALUE text field allows user to enter the magnitude value associated with
greater than or less than operator.
x The HOLD TIME text field allows user to enter the time in seconds, where the
threshold needs to be exceeded to be considered valid. For the SOSC power
threshold, this field is called OSCILLATION TIME. Due to internal processing time the
trigger might start up to 2 cycles after the configured time;
x The HYSTERESIS text field allows user to enter a quantity in Ψ, whose value needs to
be smaller in relation to the threshold to determine the end of the event and to
reset the threshold detector.

Once the threshold is created, it shows in configuration interface menu. When selecting
the threshold, a screen shows the characteristics of the threshold selected, as shown in
Figure 28. It is possible to edit the value, hold time, and hysteresis.

Figure 27: Adding and editing a current threshold

A The <APPLY ALL> button allows user to apply the hold time or the hysteresis for all
thresholds.

B The <REMOVE> button allows user to delete the threshold.

8.3 Adding New Power Thresholds

To add a power threshold, fill in the following:


x The SOURCE scroll box allows user to define a code of a power circuit used. No
editing allowed.
x The QUANTITY scroll box allows user to select the associated magnitude to be
monitored. For power circuits:
ƒ  - total apparent power;
ƒ ͳ - apparent power; Figure 28: Adding and editing a power threshold
ƒ ͳ - active power;
ƒ ͳ - reactive power;
ƒ † - total apparent power variation; A The <APPLY ALL> button allows user to apply the hold time or the hysteresis for all
ƒ †ͳ - apparent power variation; thresholds.
ƒ †ͳ - active power variation;
ƒ †ͳ - reactive power variation; B The <REMOVE> button allows user to delete the threshold.
ƒ  - power swing;
78 RPV311-TM-EN-11.1
RPV311-TM-EN-11.1 77
RPV311 Chapter 4 – Configuration Chapter 4 – Configuration RPV311

8.4 Adding New Digital Thresholds

x Power Swing, Voltage Oscillation and Frequency Oscillation: To add a digital threshold, fill in the following:
The parameters that are configurable in Power Swing, Voltage Oscillation and
Frequency Oscillation threshold are: Oscillation magnitude (in MVA, PU and Hz), x The SOURCE scroll box allows user to define a code of a digital channel used. No
Oscillation time (in seconds) and Hysteresis (in percentage). The Operator scroll box can editing allowed;
only be set to Greater Than. To trigger, the RPV311 uses a fixed band-pass filter
x The CONDITION scroll box allows user to select the threshold condition:
adjusted at 0.1 Hz to 5 Hz.

ƒ (blank) - High level;


ƒ (!) - Low level;
ƒ (‫)ר‬ - Rising edge;
ƒ (‫)ש‬ - Falling edge.
Once the threshold is created, it shows in the configuration interface menu. When
selecting the threshold, a screen shows its operator and identifier.
The <REMOVE> button allows user to delete the threshold.

8.5 Adding New DC Thresholds

To add a DC threshold, fill in the following:


x The Source scroll box allows user to define a code of a DC channel used. No
editing allowed;
x The Operator scroll box allows user to select greater than or less than for
analog magnitude;
x The Value text field allows user to enter the magnitude value associated with
greater than or less than operator;
x The Hold time text field allows user to enter the time in milliseconds, where
the threshold needs to be exceeded to be considered valid. Due to internal
processing time the trigger might start up to 2 cycles after the hold time;
x The Hysteresis text field allows user to enter a quantity in Ψ, whose value
needs to be smaller in relation to the threshold to determine the event end
and reset the threshold detector.

Once the threshold is created, it appears in configuration interface menu. When


selecting the threshold, a screen shows the characteristics of the threshold selected, as
shown in Figure 29. It is possible to edit the value, hold time and hysteresis.

80 RPV311-TM-EN-11.1
RPV311-TM-EN-11.1 79
RPV311 Chapter 4 – Configuration Chapter 4 – Configuration RPV311

Figure 29: Adding and editing a DC threshold


Figure 30: Fault recorder – triggered recording configuration section

A The <APPLY ALL> button allows user to apply the hold time or the hysteresis for all
threshold. A The ENABLED check box allows user to enable the fault recorder feature.
B The <REMOVE> button allows user to delete the threshold. B The PRE TIME text field allows user to enter the recording time before the event in
seconds. The POST TIME text field allows user to enter the recording time after the event
in seconds. The TIME OUT text field allows user to enter the maximum time (in seconds)
Cross-Trigger that the event will be recorded while the trigger is active. The DISABLED FOR – MINUTES IF
The cross-trigger is performed through an Ethernet broadcast UDP message sent MORE THAN – TRIGGERS IN THE LAST – SECONDS allows user to disable recorder if the event
whenever the device triggers, then all the RPV311 within the network with the cross- repeats within a programmed time period.
trigger enabled will receive the message and trigger as well.
C The TRIGGER LOGIC field contains all the thresholds created. The logic equation uses AND
and OR logic operators over previously defined thresholds. Initially, all preset thresholds

Fault Recorder are displayed as implicit OR operators, one per line.

The RPV311 allows user to register triggered and continuous fault recorder. To enable thresholds individually, click on the threshold and select ENABLE;
To disable discarded thresholds individually, click on the threshold and select DISABLE;
To break or remove complex thresholds, click on the threshold and select CUT LAST;
10.1 Trigger’d Recording To create equations with AND operators, follow the procedures below:
ƒ Click on the threshold and select Cut last;
ƒ Click on the threshold to which is desired to add the previously selected
threshold and then select the threshold to be added.
In this section, shown in Figure 30, it is possible to configure the equipment's fault
triggered recorder. D Selecting the RECEIVE ETHERNET CROSS-TRIGGER or SEND ETHERNET CROSS-TRIGGER check
box enables these features. It allows the start of the recording of an exceeded
threshold by Ethernet cross-trigger.

82 RPV311-TM-EN-11.1
RPV311-TM-EN-11.1 81
RPV311 Chapter 4 – Configuration Chapter 4 – Configuration RPV311

E The RATE scroll box allows user to select the rate on the fault recorder (64, 128, or
256).
Disturbance Recorder

10.2 Continuous Recording The RPV311 allows user to configure triggered and continuous disturbance recording.

In this section, shown in the figure below, is possible to configure the equipment's 11.1 Trigger'd Recording
continuous recorder.

In this section, shown in Figure 32, it is possible to configure the equipment disturbance
triggered recorder.

Figure 31: Fault recorder – continuous recording configuration section

A The ENABLED check box allows user to enable the continuous fault recording
feature.
Figure 32: Disturbance recorder – trigger’d recording configuration
B The QUANTITY scroll box allows user to select the derived quantity of continuous
disturbance records.
A The ENABLED check box allows user to enable the disturbance triggered recorder feature.
C The <DESELECT ALL> button allows user to deselect magnitudes selected.
B The PRE TIME text field allows user to enter the recording time before the event in
seconds. The POST TIME text field allows user to enter the recording time after the event

It is possible only to enable the fault continuous recorder if the disturbance continuous in seconds. The TIME OUT text field allows user to enter the maximum time (in seconds)
recorder is disabled. It is not possible to use both recorders simultaneously. that the event will be recorded while the trigger is active. The DISABLED FOR – MINUTES IF
MORE THAN – TRIGGERS IN THE LAST – SECONDS allows user to disable recorder if the event
repeats within a programmed time period.

84 RPV311-TM-EN-11.1
RPV311-TM-EN-11.1 83
RPV311 Chapter 4 – Configuration Chapter 4 – Configuration RPV311

C The TRIGGER LOGIC field contains all the thresholds created. The logic equation uses AND
and OR logic operators over previously defined thresholds. Initially, all preset thresholds A The ENABLED check box allows user to enable the continuous disturbance reordering
are displayed as implicit OR operators, one per line. feature.

To enable thresholds individually, click on the threshold and select ENABLE; B The DERIVED QUANTITY scroll box allows user to select the derived quantity of continuous
To disable discarded thresholds individually, click on the threshold and select DISABLE; disturbance records.
To break or remove complex thresholds, click on the threshold and select CUT LAST;
C The <DESELECT ALL> button allows user to deselect magnitudes selected.
To create equations with AND operators, follow the procedures below:
ƒ Click on the threshold and select CUT LAST;
ƒ Click on the threshold to which is desired to add the previously selected
threshold and then select the threshold to be added. It is possible only to enable the disturbance continuous recorder if the fault continuous
recorder is disabled. It is not possible to use both recorders simultaneously.
D Selecting the RECEIVE ETHERNET CROSS-TRIGGER or SEND ETHERNET CROSS-TRIGGER check
box enables these features. It allows the start of the recording of an exceeded
threshold by Ethernet cross-trigger.

E The <SELECT QUANTITY> button allows user to select the derived quantity of triggered Traveling Waves Recorder
disturbance records. If the quantities are not manually selected, the record will
consist of all the quantities available for measurement.
The RPV311 allows user to configure a traveling wave recorder for fault location, by
trigger. To start the configuration, it is necessary add a new recorder in accordance with
the position of selected links in equipment.
Once created, the traveling wave recorder can be configured as per the section shown
11.2 Continuous Recording in Figure 34.
In this section, shown in Figure 33, it is possible to configure the equipment's
continuous recorder.

Figure 34: Traveling waves recorder – triggered recording configuration section


Figure 33: Disturbance recorder – continuous recording configuration section

A The ENABLED check box allows user to enable the fault recorder feature.
86 RPV311-TM-EN-11.1
RPV311-TM-EN-11.1 85
RPV311 Chapter 4 – Configuration Chapter 4 – Configuration RPV311

B The TERMINAL text field allows user to enter the terminal of this recorder.
RPV311 allows user to register average series, harmonics, and flicker in the steady-state
C The TRIGGER LOGIC field contains all the thresholds created. The logic equation uses AND recorder.
and OR logic operators over previously defined thresholds. Initially, all preset thresholds
are displayed as implicit OR operators, one per line.

To enable thresholds individually, click on the threshold and select Enable; 14.1 Average series
To disable discarded thresholds individually, click on the threshold and select Disable;
To break or remove complex thresholds, click on the threshold and select Cut last; In this section, shown in Figure 35, it is possible to configure the equipment's
To create equations with AND operators, follow the procedures below: average series recorder.
ƒ Click on the threshold and select Cut last; The average series the following voltage and current circuits quantities:
ƒ Click on the threshold to which is desired to add the previously selected magnitude or effective value, neutral magnitude or effective value, frequency,
threshold and then select the threshold to be added. unbalance and total harmonic distortion.

D Selecting the RECEIVE ETHERNET CROSS-TRIGGER or SEND ETHERNET CROSS-TRIGGER check box
enables these features. It allows the start of the recording of an exceeded threshold by
Ethernet cross-trigger.

Note:
The maximum number of RA333 that can be connected to the RPV311 is 4.

The RA333 module has to be connected to the RPV311 processing module before its
initialization. Otherwise a log message will tell the user to reboot the device.

Recommended Sources of Trigger


In order to register the beginning of the fault’s traveling wave it is important to use
instantaneous protections trips (or starts) as digital input for trigger, for example: 50,
21Z1, 67I, 87 etc. In addition, we recommend the following thresholds:

Threshold Limit

Phase Overcurrent 1,2 pu

Neutral Overcurrent 0,2 pu

Current Negative Sequence 0,15 pu

Phase Undervoltage 0,85 pu Figure 35: Steady-state recorder – average series configuration section

Neutral Overvoltage 0,10 pu


A The PERIOD scroll box allows user to select the recording average series every 1 or 10
The limits values can be adjusted depending on the needs of each installation using real minutes.
events as basis

14.2 Harmonics
In this section, shown in Figure 36, it is possible to configure the equipment's harmonics
recorder.

Steady-State
88 RPV311-TM-EN-11.1
RPV311-TM-EN-11.1 87
RPV311 Chapter 4 – Configuration Chapter 4 – Configuration RPV311

Figure 36: Steady-state recorder – harmonics configuration section


Figure 37: Steady-state recorder – flicker configuration section

A The IDENTIFIER field shows all the circuits previously configured.

B The TYPE field shows the circuit type. A The IDENTIFIER field shows all the voltage circuits previously configured.

C The check box allows the selection of preset circuits for the steady-state record B The TYPE field shows the circuit type.
formation. C The check box allows the selection of circuits to be included in the steady-state record.

In the flicker recorder, up to 6 circuits can be selected at the same time.


In the harmonics recorder, only 2 circuits can be selected at the same time.

Groups
14.3 Flicker Group setup allows the user to monitor voltage and current circuit information via local
interface or the Monitoring screen at the web interface operation.
It is not possible to monitor circuits that are not included in either group.
Figure 37 shows the configuration screen of the Flicker feature. To add new groups fill in the following:
ƒ The IDENTIFIER text field allows user to enter a single code for the group being
defined (maximum 15 characters). No editing allowed;
ƒ The IDENTIFIER field shows all the circuits and channels previously configured;
ƒ The TYPE field shows the circuits type;
ƒ The check box allows user to include the preset circuits for the group
formation;
ƒ The <DESELECT ALL> button allows user to deselect all circuits marked;
ƒ The <SELECT ALL> button allows user to select all circuits;
ƒ The LENGTH, R0, X0, R1 and X1 text fields allow user to enter the transmission
line characteristics (length and impedance), for the fault location.
The RPV311 uses one-end impedance fault location based on the Takagi algorithm
90 RPV311-TM-EN-11.1
RPV311-TM-EN-11.1 89
RPV311 Chapter 4 – Configuration Chapter 4 – Configuration RPV311

Once the group is created, it shows in the configuration interface menu. When selecting
the group, a screen shows its characteristics, as shown in the figure below. It is possible
to edit all the fields.

Figure 39: Relays on time configuration section

A The TIME scroll box allows user to select the relays on time for logging signaling events
Figure 38: Adding and editing a group
(1 to 10 seconds).
A The <REMOVE> button allows user to delete the group.

Relays
16.2 Relays 2, 3, and 4
Below is shown the configuration screen of the signaling relays.
Relays indicate events or state transitions and set off the alarm on the equipment.
RPV311 provides four relays: three relays set by the user and one factory default relay,
which signals internal equipment failure.

16.1 On time

In this section, shown in Figure 39, it is possible to configure the relays on time for
logging signaling events.

92 RPV311-TM-EN-11.1
RPV311-TM-EN-11.1 91
RPV311 Chapter 4 – Configuration Chapter 4 – Configuration RPV311

PMU
Synchrophasors are measured and broadcast according to the specifications contained
in IEEE C37.118, Standard for Synchrophasors for Power Systems.
For further information about the PMU, see Chapter 8: PMU.
The RPV311 is able to send up to 4 PMU in the frame of data and the configuration is
divided into three sub menus: General, Data and Communication described below.

17.1 General
This window is responsible for configuring the following settings:

<Enable> Turns the PMU streaming on and off.


The <ID> text field allows user to enter a single ID for the entire PMU streaming; the
range is of 1 to 65534.
The <Rate> scroll box allows user to select a frame transmission rate; at 60Hz the
Figure 40: Relay signaling events configuration section parameters are10, 12, 15, 20, 30, and 60 fps; at 50Hz they are 10, 25 and 50Hz.

A The LOG events text field allows user to enter a code used for signaling events. Refer to 17.2 Data
Appendix Afor log references. The relays will stay closed during the time set in the On
The data selection is related to the groups configuration (refer to Chapter 4:
time configuration (previous section). In order to combine several LOG events to trigger
Configuration, Section 15 - Groups). Each group can configure a PMU with its specific
the alarm, use “comma” to separate the LOG numbers, for instance: 709, 710. data and frequency.
B The WARNINGS check box allows user to select the following events for signaling: The parameters present on the screen are:
<GROUP> this setting displays all the values related to the selected group that can be
ƒ Equipment not ready; transmitted. Each group has a particular setting for the frequency and rate of change of
ƒ Primary power failure; frequency related to it.
ƒ Equipment unsync; The <ENABLE> check box allows user to enable data packet transmission.
ƒ Fault recorder lack of memory; The <ID> text field allows user to enter a single PMU transmitter ID; the range is of 1 to
ƒ Disturbance recorder lack of memory; 65534.
ƒ Steady-state recorder lack of memory; <FREQUENCY> selects the reference frequency of PMU. It is possible to choose which
ƒ SOE recorder lack of memory; signal is used to calculate the frequency, namely: Voltage from phases A, B or C, voltage
ƒ Link communication failure; positive sequence, current from phases A, B or C.
ƒ Internal failure. The <PHASORS>, Analog data and Digital data fields contain all the inputs configured on
ƒ Class C chain OK¹ the equipment. The check box allows user to select the input to evaluate magnitudes.
The <DESELECT ALL> button allows user to deselect all the magnitudes selected.
¹ - Class C chain OK: output relay is closed when two conditions happen simultaneously:
Equipment healthy (code 50) and Synchronization OK (code 102). When “No Source” is
selected as Synch source on the synchronization page, then the “Class C chain OK” relay 17.3 Communication
closes when Equipment healthy (code 50) condition is met.
The RPV311 has two types of operation modes: Commanded; and Spontaneous.
In addition to closing the output relays, the warning events will cause the Alarm LED in When using the Commanded mode the RPV only transmits data when the client
the front panel of the RPV311 to light up. The Both the outputs and the LED will stay requests. This mode allows up to 4 destinations of the PMU frame through the UDP
active as long as the warning event in active. ports.
The ports the RPV311 uses to send synchrophasors are:

94 RPV311-TM-EN-11.1
RPV311-TM-EN-11.1 93
RPV311 Chapter 4 – Configuration Chapter 4 – Configuration RPV311

MODBUS
Status, analog and digital data are available in MODBUS registers.
Stream of data Port number Access to SCADA integration is provided over the Ethernet interface. Up to 8
simultaneous connections are allowed a maximum rate of 60 accesses per second.
1 4713 For further information about MODBUS, see Chapter 9: MODBUS.
Each register reports 16-bit data. Registers are divided into 3 groups:
2 4714

3 4715 Registers groups

0 Status
4 4716

100 to 199 Analog data


In Spontaneous mode the RPV sends the PMU data automatically up to 4 different
socket addresses (IP + port number). All 4 destination configuration can be set as 200 to 223 Digital channels
unicast or multicast transmission.
The parameters of the Communication screen are listed below:
<COMMANDED> Sets the respective streams of data to Commanded mode. When set to
In the MODBUS section shown in Figure 41, it is possible to configure MODBUS.
Commanded mode. The RPV311 can send the HDR, CFG2 and CFG3 frames according to
the client’s IED request.
<SPONTANEOUS> Sets the respective streams of data to Spontaneous mode. When in
Spontaneous mode it is also possible to select which CFG frame the PMU will use. The
options are CFG2 and CFG3, at least one of them must be set. Additionally, it is possible
to choose if the HDR frame will be sent.
<UNICAST> Sets the addressing of the respective streams of data to Unicast mode. This
kind of transmission connects to a single IP address and the routing of the messages
though the available Ethernet ports are managed by the RPV system. It is important
that the destination IP and the RPV311 share the same subnetwork address.
<MULTICAST> Sets the addressing of the respective streams of data to Multicast mode.
This mode required the user to choose which Ethernet interface the RPV shall use to
convey the data.

Note 1:
When the PMU is configured in spontaneous mode, the RPV311 will transmit the
PMU data through the Ethernet port whose IP address is within the same subnet as
the destination IP address of the PMU stream. In case different streams are
configured, they will be transmitted simultaneously through both Ethernet ports 1
and 2, in case, the subnets of the destination IP addresses match the configured IP
of the RPV311 Ethernet ports.
When the PMU is configured in commanded mode, the RPV311 will transmit the
PMU data through the same Ethernet port as the PMU requisition was made. Figure 41: MODBUS configuration section
Note 2:
When the primary values being read are less then 1A or 1 V, the PMU TVE will not
work properly, i.e. in performance test scenarios do not use transformer ratios
A The ENABLE check box allows user to enable recording.
equal to 1.
B The ANALOG DATA field allows user to select a derived quantity and insert a decimal
correction factor of an analog input.

96 RPV311-TM-EN-11.1
RPV311-TM-EN-11.1 95
RPV311 Chapter 4 – Configuration Chapter 4 – Configuration RPV311

C The DIGITAL DATA field allows user to select a block of a digital input.

D The <DESELECT ALL> button allows user to deselect all the magnitudes selected.

Note: Whenever MODBUS/DNP3 feature is enabled, the RPV will send both types of
messages. It is not possible to enable just one protocol.

DNP3

The DNP3 functionality is fully associated with the MODBUS functionality in the RPV311.
To use the DNP3 protocol, it is necessary to insert a configuration key at the equipment
to unlock the MODBUS and DNP3 functionalities. However, it is necessary to check the
HABILITATED option at the web interface and insert analog channels block or digital
channel blocks at MODBUS/DNP3 menu.

Figure 42: Digital Channels Configured

19.1 Configuring the DNP3 function

To add binary data to the DNP3 slave database (RPV311), it’s just necessary to add a
digital channel in the equipment’s configuration, as shown at section 6. At the RPV311
restarting proccess, the DNP3 library reads the configuration archive and adds digital
channels sequentially, associating to an integer number plus an increment, starting at
zero, for each digital channel. GOOSE digital channels are not added to the DNP3
database.

19.2 DNP3 configuration example

19.2.1 Adding digital channels


First step for digital channel DNP3 database association is to create a digital channel.
Figure 42 shows the digital channels configured and table below shows associated
number at the DNP3 database for each digital channel of the example.

98 RPV311-TM-EN-11.1
RPV311-TM-EN-11.1 97
RPV311 Chapter 4 – Configuration Chapter 4 – Configuration RPV311

Channel name RA33x input Channel type DNP3 Database associated number

D1 A201 Physical 00

D2 A217 Physical 01

D4 C201 Physical 02

D_Linha2 B201 Physical 03

D_Linha3 B202 Physical 04

G1 GOOSE

G2 GOOSE

D10 A210 Physical 05

D11 A211 Physical 06

D12 A212 Physical 07

19.2.2 Adding analog channels


Figure 43: Analog channels selected
The analog data possibilites for the DNP3 communication procol are the same as for
MODBUS. The MODBUS analog data are shown in section 1.3.
To configure the analog data, access the MODBUS/DNP3 menu via web interface. Analog A The field is only used for analog quantities with DNP3;
data are added in a sequential way, like the digital channels, but the starting number for
B Used to configure the digital inputs that will be sent.
the analog channels is 5. Numbers 0, 1, 2, 3 and 4 are reserved for equipment
information.

Note:
For analog channels, the first number associated at the DNP3
database is 5. Numbers 1, 2, 3 and 4 are reserved for equipment
information.

Figure 43 shows the analog channels selected at the MODBUS/DNP3 menu and the table
below it shows the associated number at the DNP3 database for each example analog
channel.

100 RPV311-TM-EN-11.1
RPV311-TM-EN-11.1 99
RPV311 Chapter 4 – Configuration Chapter 4 – Configuration RPV311

Data name MODBUS DNP3 Database Data type


register number associated
number
Note: The phase angles are sent in degrees for the MODBUS and radian for DNP3
0 00 Alarms:
bit 0: Equipment NOK
bit 1: Primary power failure
bit 2: Not used
bit 3: Not used
bit 4: Equipment not synchronized
bit 5: Fault recorder low memory
bit 6: Disturbance recorder low memory
bit 7: Steady-state recorder low memory
bit 8: SOE recorder lack of memory
bit 9: Internal failure

1 01 Not used

2 02 Not used

3 03 Not used

4 04 Time quality

VA CV1 100 05 CV1 voltage circuit, phase A RMS value

VB CV1 101 06 CV1 voltage circuit, phase B RMS value

VC CV1 102 07 CV1 voltage circuit, phase C RMS value

VN CV1 103 08 CV1 voltage circuit, neutral RMS value

VC1 CV1 mag 106 09 CV1 voltage circuit, phase C phasor magnitude

VN1 CV1 mag 107 10 CV1 voltage circuit, neutral phasor magnitude

VA1 CV1 phi 110 11 CV1 voltage circuit, phase A phasor angle

VS+ CV1 mag 112 12 CV1 voltage circuit, positive sequence magnitude

VS- CV1 mag 113 13 CV1 voltage circuit, negative sequence magnitude

Note:
The 104, 105, 108, 109 and 111 registers (without configuration, as
shown in figure 114) have no influence DNP3 Database analogue
object number’s increment

Note: Whenever MODBUS/DNP3 feature is enabled, the RPV will send both types
of messages. It is not possible to enable just one protocol.

102 RPV311-TM-EN-11.1
RPV311-TM-EN-11.1 101
Chapter 5 – Operation RPV311

RPV311
ƒ The Back button returns to the previous menu level;
ƒ The Enter button selects an item of the list;
Distributed Multifunction Fault Recorder ƒ The arrows allow the user to scroll through the list of items displayed.

Chapter 5: Operation 1.3 Local Interface Menus


This chapter provides information on possible ways to access and operate the device. .
1.3.1 Status

Local Interface The information below is displayed in the local menu:


The RPV311 has a local interface for human-machine interaction, composed of a ƒ Date and time;
display, navigation buttons, and status indicators, as shown in the figure below. ƒ If the equipment is in normal operation;
ƒ If the RPV311 is being synchronized by IRIGB or NTP;
ƒ Date and time since last power up;
ƒ Percentage of mass memory used;

To access the items, use the sequence shown in Figure 45.

Figure 44: Local interface of the RPV311

1.1 Status Indicators


The local interface has 4 status indicators:
ƒ ALARM: Lights up when the equipment requires attention of the operator;
ƒ TRIGGER: Flashes when a threshold has been triggered;
ƒ SYNC: Lights up when the internal clock and the acquisition system are
synchronized through the IRIG-B signal;
ƒ READY: Lights up when the equipment has passed through the self-test routines
and is in normal operation.

Note: If during the RPV311 initialization (boot) the Alarm LED is active due to an
opened link of the RA333 TW link (log code 297 – Traveling wave not identified).
The user must reboot the RPV311 after normalizing the link connection, otherwise
the RPV311 will not create the TW COMTRADE recordings.

1.2 Menu Navigation


The navigation buttons are used as follows:

103 RPV311-TM-EN-10 104 RPV311-TM-EN-11.1


RPV311 Chapter 5 – Operation Chapter 5 – Operation RPV311

1.3.2 Monitoring

It is possible to locally monitor the analog quantities measured by the RPV311.


Quantities are separated by the name of the circuit and the data is updated once per
second.
To view the values related to quantities associated with a circuit, select the circuit
group, choose the circuit type (voltage, current, or power) and then select the name of
the circuit to be monitored.
To access the Monitoring items, use the sequence shown in Figure 46.

Figure 45: Status monitoring sequence

106 RPV311-TM-EN-11.1
RPV311-TM-EN-11.1 105
RPV311 Chapter 5 – Operation Chapter 5 – Operation RPV311

1.3.3 Records

This menu shows the list of records provided by the equipment in decreasing
chronological order (of the latest to the oldest).
To view a record, select the type of the record (Waveform, Synchrophasors, Steady-
state, TW or SOE), and then select the date and the time of the record to be viewed. For
each record the following data will be shown:
ƒ Time stamp of the record;
ƒ Record duration;
ƒ Thresholds exceeded (triggered records only);
ƒ Time quality;
ƒ The fault location (waveform records only).

To access the Record, use the sequence shown in Figures 49 and 50.

Figure 46: Monitoring sequence

108 RPV311-TM-EN-11.1
RPV311-TM-EN-11.1 107
RPV311 Chapter 5 – Operation Chapter 5 – Operation RPV311

Figure 47: Records monitoring sequence: Fault disturbance, TW and average series
Figure 48: Records monitoring sequence: harmonics, flicker and SOE
110 RPV311-TM-EN-11.1
RPV311-TM-EN-11.1 109
RPV311 Chapter 5 – Operation Chapter 5 – Operation RPV311

1.3.4 Settings

Shows the RPV311 configuration, related to:


ƒ Equipment identification;
ƒ Synchronization information;
ƒ Communication settings (gateway, serial port and Ethernet);
ƒ Information about voltage, current and power circuits and digital channels;
ƒ Relay configuration.

To access the Setting items, use the sequence shown in Figures 51 to 53.

Figure 49: Equipment settings monitoring sequence

112 RPV311-TM-EN-11.1
RPV311-TM-EN-11.1 111
RPV311 Chapter 5 – Operation Chapter 5 – Operation RPV311

Figure 50: Circuit and channel settings monitoring sequence


Figure 51: Relays, PMU and MODBUS settings monitoring sequence
114 RPV311-TM-EN-11.1
RPV311-TM-EN-11.1 113
RPV311 Chapter 5 – Operation Chapter 5 – Operation RPV311

1.3.5 General Information

Shows general information about the equipment, such as:

ƒ Equipment model;
ƒ Processor;
ƒ Module identification;
ƒ Frequency;
ƒ Type of sequence;
ƒ Key (to enable the equipment functions);
ƒ Features (features enabled).

To access the items of General Information, use the sequence shown in Figure 52.

Figure 52: General information monitoring sequence


116 RPV311-TM-EN-11.1
RPV311-TM-EN-11.1 115
RPV311 Chapter 5 – Operation Chapter 5 – Operation RPV311

Monitoring Web Interface B Menu and scroll bar.

C Buttons to close a section or start a new configuration.

2.1 Accessing the Monitoring Web Interface D Desktop.


The equipment’s monitoring interface allows access to the equipment and link status,
event log, manual trigger, records, monitoring of magnitudes, configuration history, and
general information about the equipment. Web Interface navigation follows the rules below:
Refer to Chapter 14: Communications in order to verify the support applications and ƒ The menu items near the arrows are expandable. To expand or compress a
the minimum requirements needed to access all the RPV311 web interface menu item, click on the arrow or click on the item.
features. ƒ To expand or compress all menu items, click on the folder at the bottom of the
To access the monitoring interface, enter the equipment's Ethernet IP in a web browser. screen beside the scroll bar.
If the Flash Player 9.0 (or higher) plug-in is not already installed on the computer, it will ƒ To select a menu sub-item, click on the item.
be automatically installed by the operating system. The Ethernet interface default ƒ To move through the menu using the scroll bar, click on the arrow related to
settings are shown in Chapter 14: Communications. the direction desired. Click on the single arrow to move one step or on the
. double arrow to move 10 steps.
If the equipment is not fond with the default IP settings, refer to Chapter 5: Operation
in order to be able to verify the current IP address. To finish the session, click on the <LOGOUT> button. A confirmation box will appear. Click
Yes to confirm or No to keep logged in. If the screen is closed before pressing the logout
button, the user will remain connected until a time delay expires (1 minute).
2.2 Navigating
2.3 Status
The default screen of the Web Interface is shown in Figure 53. In the Status screen the statuses of the equipment and of the links are shown.
If any information of the Status screen indicates a parameter different of the normal
operation of equipment, such indication will be shown in red.

2.3.1 Equipment Status

The Equipment screen, shown in Figure 54, displays a summary of the status of the
equipment.

Figure 53: Default screen for browsing on the Web Interface

A Equipment identification.

118 RPV311-TM-EN-11.1
RPV311-TM-EN-11.1 117
RPV311 Chapter 5 – Operation Chapter 5 – Operation RPV311

Figure 54: Equipment status screen

Figure 55: Link status screen


A Equipment status, with the following information:

A Indicates the date the equipment status was last updated in the yyyy-mm-dd hh:mm:ss
x Date: indicates the date the equipment status was last updated in the yyyy-mm-dd
+ 0000 format where o is UTC time offset.
hh:mm:ss + 0000 format where o is UTC time offset;
x Equipment: indicates whether the equipment is operational or not; B Link status, with the following information:

x Synchronization: indicates locked if receiving a valid IRIG-B signal and the acquisition
x Position: indicates the link position of A to L;
system is synchronized with the IRIG-B signal, even if the time quality is different of
locked; x Module: indicates the module type related to the link position;

x Time quality: indicates the received IRIG-B signal quality; x Status: indicates the status of the link. Active if it is sending and receiving data and
inactive if it is not.
x Memory usage: indicates the memory usage related to the fault, disturbance, TW,
steady-state and SOE records and log;
C The <REFRESH> button allows user to refresh the screen information.
x Last power-up: indicates the date and time since the last power up.
D The <CLOSE> button allows user to close the section.
B The <REFRESH> button allows user to refresh the screen information.

C The <CLOSE> button allows user to close the section.


2.4 Log
2.3.2 Links Status
The Log screen, shown in Figure 56, displays a history of equipment event logs.

The Links screen, shown in Figure 55, displays the equipment links status.

120 RPV311-TM-EN-11.1
RPV311-TM-EN-11.1 119
RPV311 Chapter 5 – Operation Chapter 5 – Operation RPV311

Figure 56: Log screen


Figure 57: Manual Trigger screen

A The Search box allows user to choose the period of time of the oldest to the latest to
display. A By selecting this box, a fault recording is triggered.
B The Codes box allows user to search for specific logs or time intervals. For example, to B By selecting this box, a disturbance recording is triggered.
search a log between 300 and 399, fill 3?? and to search a list, fill 2??, 507, 700. Codes
shall be entered with 3 digits. C The <TRIGGER> button allows user to trigger the selected record.

C The <LIST> button allows user to show the list of records according to the filtering D The <CLOSE> button allows user to close the section.

parameters.

D Logs listed, with the following information:

x Time stamp: indicates the date and time of event log (yyyymm-dd hh:mm:ss[.uuuuuu] േ
2.6 Records
0000 (UTC time offset);
x Code: indicates the log code;
This section describes how to access different types of records on the RPV311. For
x Description: describes the log. details about the records, see Chapter 6: Records.

E The <CLOSE> button allows user to close the section. The Fault recorder screen, shown in Figure 58, displays a history of equipment fault
records.

2.5 Manual Trigger

The Manual Trigger screen, shown in Figure 57, allows the user to trigger the
equipment manually even if no threshold was exceeded.
122 RPV311-TM-EN-11.1
RPV311-TM-EN-11.1 121
RPV311 Chapter 5 – Operation Chapter 5 – Operation RPV311

2.6.1 Disturbance recorder

The Disturbance recorder screen, shown in Figure 59, displays a history of equipment
disturbance records.

Figure 58: Fault recorder screen

A The Search box allows user to choose the period of time of the oldest to the latest to
display.

B The Manual Filter box allows user to filter the records manually, according to their
selection.

C The Trigger and the Continuous boxes allow user to select either or both types of record Figure 59: Fault recorder screen
present on the list.

D The <LIST> button allows user to show the list of records according to the filtering A The Search box allows user to choose the period of time of the oldest to the latest, in
parameters. If clicking <LIST> finds no record available, a window will be opened with a order to display it in the interface.
message: "No records available´´. So click <OK> and return to the previous section.
B The Manual Filter box allows user to filter the records manually, according to their
E Fault records listed, with the following information: selection.

C The Trigger and the Continuous boxes allow user to select either or both types of record
x Time stamp: indicates the date and time of event log (yyyymm-dd hh:mm:ss[.uuuuuu] േ
to be present on the list.
0000 (UTC time offset);
x Cause: indicates threshold exceeded; D The <LIST> button allows user to show the list of records according to the filtering
parameters. If clicking <LIST> finds no record available, a window will be opened with a
x Duration: record length in seconds.
message: "No records available´´. So click <OK> and return to the previous section.

F The <DETAILS> button allows user to view information about the record. This information E Disturbance records listed, with the following information:
is also included in the .HDR file.

G The <COMTRADE> button allows download of record, line per line, and saving it in the x Time stamp: indicates the date and time of event log (yyyymm-dd hh:mm:ss[.uuuuuu] േ
Comtrade format, and compression as .zic file. 0000 (UTC time offset);
x Cause: indicates threshold exceeded;
H The <CLOSE> button allows user to close the section.
x Duration: records length in seconds.

124 RPV311-TM-EN-11.1
RPV311-TM-EN-11.1 123
RPV311 Chapter 5 – Operation Chapter 5 – Operation RPV311

F The <DETAILS> button allows user to view information about the record. This information
is also included in the .HDR file. x Time stamp: indicates the date and time of event log (yyyymm-dd
hh:mm:ss[.uuuuuu] േ 0000 (UTC time offset);
G The <COMTRADE> button allows download of record, line per line, and saving it in the
COMTRADE format, and compression as .zic file. x Cause: indicates threshold exceeded;
x Terminal: terminal where the traveling wave was detected.
H The <CLOSE> button allows user to close the section.

E The <DETAILS> button allows user to view information about the record. This information
is also included in the .HDR file.

2.6.2 Traveling Wave Recorder F The <COMTRADE> button allows download of record, line per line, and saving it in the
COMTRADE format, and compression as .zic file.

G The <CLOSE> button allows user to close the section.


The Traveling wave recorder screen, shown in Figure 60, displays a history of equipment
traveling wave records.

2.6.3 Steady-state

The Steady-state recorder screen, shown in Figure 61, displays a history of equipment
steady-state records.

Figure 60: Traveling Wave recorder screen

A The Search box allows user to choose the period of time of the oldest to the latest to
display.

B The Manual Filter box allows user to filter the records manually, according to the their
selection.

C The <LIST> button allows user to show the list of records according to the filtering
Figure 61: Steady-state recorder screen
parameters. If clicking <LIST> finds no record available, a window will be opened with a
message: "No records available´´. So click <OK> and return to the previous section.
A The Search box allows user to choose the period of time of the oldest to the latest to
D Fault records listed, with the following information:
display.

126 RPV311-TM-EN-11.1
RPV311-TM-EN-11.1 125
RPV311 Chapter 5 – Operation Chapter 5 – Operation RPV311

B The Manual Filter box allows user to filter the records manually, according to their
selection.

C The Average series, Harmonics, Flicker PST, and Flicker PLT boxes allow user to select
only this type of record on the list.

D The <LIST> button allows user to show the list of records according to the filtering
parameters. If clicking <LIST> finds no record available, a window will be opened with a
message: "No records available´´. So click <OK> and return to the previous section.

E Steady-state records listed, with the following information:

x Time stamp: indicates the date and time of event log (yyyymm-dd hh:mm:ss[.uuuuuu] േ
0000 (UTC time offset);
x Cause: indicates threshold exceeded;
x Duration: record length in seconds.

F The <COMTRADE> button allows download of record, line per line, and saving it in the
Comtrade format, and compression as .zic file.

G The <CLOSE> button allows user to close the section.


Figure 62: SOE recorder screen

2.6.4 SOE A The Search box allows user to choose the period of time of the oldest to the latest to
display.

B The Manual Filter box allows user to filter the records manually, according to their
The SOE recorder screen, shown in Figure 62, displays a history of equipment SOE
records. selection.

C The <LIST> button allows user to show the list of records according to the filtering
parameters. If clicking <LIST> finds no record available, a window will be opened with a
message: "No records available´´. So click <OK> and return to the previous section.

D SOE records listed, with the following information:

x Time stamp: indicates the date and time of event log (yyyymm-dd hh:mm:ss[.uuuuuu] േ
0000 (UTC time offset);
x Cause: indicates threshold exceeded;
x Duration: record length in seconds.

E The <COMTRADE> button allows download of record, line per line, and saving it in the
Comtrade format, and compression as .zic file.

F The <CLOSE> button allows user to close the section.

128 RPV311-TM-EN-11.1
RPV311-TM-EN-11.1 127
RPV311 Chapter 5 – Operation Chapter 5 – Operation RPV311

2.7 Monitoring
 Combined apparent power

With the Web Interface it is possible to monitor the values related to circuits and ଵ Fundamental apparent power
channels in three different ways: through Plots, Current and Voltage Circuits, and
Digital Channels.
ଵ Phasors ¹

2.7.1 Measurements ଵ Phasors (neutral) ¹

x Voltage and Current Measurement: Reactive power has a positive sign for circuits with inductive characteristics and a
The values listed below are computed at the nominal system frequency (50 or 60 Hz): negative sign for circuits with capacitive characteristics.

Voltage and current measurement


x DC Transducers Measurement:
 RMS value ²
The RMS value of the DC channels (transducers) is calculated once per cycle.
 RMS value (neutral) ²
x High-speed Voltage Measurement:
ͳ Phasors ¹ There is an 8-bit opto-isolated analog-to-digital converter, independent for each
channel. The acquisition is performed with 5 MHz sampling frequency (high-speed
ͳ Phasors (neutral) ¹ channels), that means one acquisition each 200 ns.

ା Positive sequence ¹ ²
2.7.2 Plots
ି
 Negative sequence ¹ ²

 Imbalance ¹ ² To graphically monitor the values related to circuits and DC channel quantities, access
the Web Interface:
Fundamental frequency ²
Monitoring > Plots
  Total harmonic distortion ²
In this screen it is possible to monitor up to 6 different voltage, current, or DC channel
quantities, as shown in Figure 63.

¹ Is not calculated for circuits of 1 element without 3-phase synthesis.


² Is not calculated for neutral circuits.

The fundamental frequency of the input signal must be within a range of ± 6 Hz of the
nominal frequency of the electrical system.

x Power Measurement:
Power measurement is computed based on the values of a voltage circuit and a current
circuit. The following values are computed once per cycle:

Voltage and current measurement

130 RPV311-TM-EN-11.1
RPV311-TM-EN-11.1 129
RPV311 Chapter 5 – Operation Chapter 5 – Operation RPV311

In this interface, up to 4 channels of voltage or current can be simultaneously


monitored, as shown in Figure 64.

Figure 63: Monitoring with plots

A The Fault Recorder or Disturbance Recorder check boxes allows user to select which
type of recording to trigger.

B The <TRIGGER> button allows user to trigger the selected record.


Figure 64: Monitoring circuit quantities via Web interface
C Quantities selected to be monitored.

D <RE-SCALE> button.
A Phasor angle for each phase of the selected circuit.
E Plots with time evolution for the values related to the selected quantity.
B Selected circuit to be monitored.

C Quantities related to the circuits being monitored.


The graphics show the time evolution of the selected quantity with the update
frequency of 2 points per second. The time selected is related to the pre-fault time of
the synchrophasor recorder.
Phasor angles measured and displayed are absolute angles referenced to the PPS signal
The plotted points are automatically scaled based on the previous points displayed. The
provided by the synchronization. When no sync signal is connected, the measured
range between the minimum and maximum current values is adjusted by using the <RE-
angles are referenced to Phase A of the reference circuit.
SCALE> button.
Values are updated at the rate of 2 points per second, however, when two or more
It is possible to create a waveform or synchrophasor records using the buttons at the
circuits are simultaneously displayed, their time stamps may not be related to each
top right corner of the screen.
other.

Note: The RPV311 has an autozero automatic feature, which is a slow filter that
2.7.3 V & I Circuits takes about 15 minutes to filter the DC components of the reading signal and then
subtracts it from the readings in order to locate the correct position of the signal
reference on the graph. The response of the filter is stored in the solid memory with
the purpose of turning this process faster for subsequent reboots on the device.
The user will be able to monitor the values of voltage and current circuits, via Web This filter will not interfere with the registering of the DC components generated by
Interface: faults.
MONITORING > V & I CIRCUITS

132 RPV311-TM-EN-11.1
RPV311-TM-EN-11.1 131
RPV311 Chapter 5 – Operation Chapter 5 – Operation RPV311

2.7.4 Digital Channels

The status of each digital channel can be monitored via Web Interface, as shown
2.8 Configuration History
inFigure 65.
Access:
MONITORING > DIGITAL CHANNELS
It is possible to monitor the status of up to 64 digital channels per page and up to six The Configuration History screen, shown in Figure 66, displays the history of changes
pages. made in the equipment configuration and its corresponding revision number.
The data is updated every 2 seconds.
The channels status is represented according to the following:

Voltage and current measurement

Active channel

Non-active channel

Figure 66: Configuration History screen

A Configuration history, with the following information:

x Revision: indicates the number of each change in configuration;


x Time stamp: indicates the date and time of change in configuration;
x User: indicates the user who changed the configuration;
x Description: describes the change.

B The <REPORT> button allows user to print an equipment configuration report.


Figure 65: Monitoring the status of digital channels
C The <CLOSE> button allows user to close the section.

A Status of the digital channel.


2.9 General Information
B Changes pages being monitored.

C Shows the number of the page being monitored.


134 RPV311-TM-EN-11.1
RPV311-TM-EN-11.1 133
RPV311 Chapter 5 – Operation Chapter 5 – Operation RPV311

The General Information screen, shown in Figure 67, displays general information about
the equipment, such as:

Figure 68: Setup screen

Figure 67: General Information screen


A Information about the equipment, such as:

A General information about the equipment, such as: x Equipment model: model of RPV;
x Processor: processor type.
x Equipment model: model of RPV;
x Processor: processor type; B The Language box allows choice of the language of the Web Interface - English, Spanish,
Russian, Polish and Portuguese
x Module identification: unique identification code of the module;
x Frequency: nominal frequency reference; C The Frequency box allows choice of the nominal frequency reference - 50 Hz or 60 Hz.

x Type of sequence: phase sequence reference (ABC, ACB, BAC, BCA, CAB, CBA); D The Type of sequence box allows choice of the phase sequence reference.
x Firmware version: the current firmware version for the equipment. E The Key box allows user to enable the equipment features.

B The key related to the features enabled on the equipment. F The <LOGOUT> button allows user to logout of the section.

C The equipment features enabled or disabled. G The <TRANSMIT> button allows user to send the changes to the equipment.

D The <SETUP> button allows user to set some features of the equipment. When contacting our support personnel, it is necessary to inform the equipment serial
number and part number.
E The <CLOSE> button allows user to close the section. GE's support personnel will send an email with the new key.
In order to enable the new key, please follow the instructions below:

Clicking on the <Setup> button will open a screen, shown in Figure 68, which displays 1. Click on the <SETUP> button to enter the new key. A new window will open, enter the
the equipment model, processor type used, and enables the user to change the username and password (username and password for Web Interface configuration).
following parameters:
136 RPV311-TM-EN-11.1
RPV311-TM-EN-11.1 135
RPV311 Chapter 5 – Operation

2. Another window will open indicating that all open Web Interface windows should be RPV311
closed (except the key window). Close the windows and click on the <OK> button.
3. Copy the code key sent by e-mail and enter it in the <KEY> box to replace the old one.
Then click on the <TRANSMIT> button. Distributed Multifunction Fault Recorder
COMTRADE files download Chapter 6: Records
There are four different ways to get the COMTRADE files from the RPV311 to a This chapter details all types of registers created by the RPV311.
computer, one manual way and three automatic way.
The manual method uses the web interface and is described in the item Chapter 5:
Operation, 1.3.3 Records Continuous and Triggered Fault Records
The three ways automatic ways listed below:
ƒ Scanner software ( Chapter 12: Software – RPV Tools): Simple platform that
download specific types of files (fault, disturbance, SOE, TW...) from specific IP
Fault records can be created in the following ways:
address with preset time intervals.
ƒ DR Manager (Chapter 13: Software – DR Manager): Elaborate software that x Continuously:
downloads the records from several separate RPVs, performs TW fault Measurements are continuously recorded. A new record is available every 10 minutes.
location and shows the equipment alarms. The record size depends on the number of derived measurements selected by the user.
ƒ Auto-upload which is a feature of the RPV where the user specifies an IP Up to 16 measurements can be selected. The continuous fault records does not contain
address and prepare a computer to be the server. Upon creating a record the the digital inputs status.
RPV will automatically send it to the destination IP. If for some reason, it is not x By trigger:
able to send the record at that time it will not send again later. The fault recorder can be triggered by a Boolean equation, by a cross-trigger signal of
All those means save the record to a folder named based on the DFR’s information another recorder or by a manual trigger using the Web Interface.
LOCATION,IDENTIFIER within another folder located in C:\RPV\records\. Continuous and triggered fault records share the same mass storage area.

1.1 Recorded Values


The following values are recorded by the fault recorder:
x Voltage waveform of all voltage circuits (A, B, C, and N);
x Current waveform of all current circuits (A, B, C, and N);
x Transducer waveform of all transducer channels;
x Digital channels (state of digital inputs and binary GOOSE messages – digital
inputs are recorded only in the triggered fault records).

1.2 Recording Times by Trigger


Once triggered, the following parameters are considered by the fault recorder:

Parameter Allowed values Increment

Pre-fault time (‫ݐ‬୮୰ୣ ) 0…5s 0.1 s

Post-fault time (‫ݐ‬୮୭ୱ ) 0 … 60 s 0.1 s

Timeout 1 … 60 s 0.1 s

138 RPV311-TM-EN-10
RPV311-TM-EN-11.1 137
RPV311 Chapter 6 – Records Chapter 6 – Records RPV311

In the figure below, if T ≥ pre-fault time + post-fault time, then the RPV311 creates two
The Timeout configures the maximum duration that the actual fault (threshold separate COMTRADE files.
exceeded/trigger ON) can reach within a record. The maximum timeout of the fault
record is 60 seconds.
The maximum time of the recorded will be composed of the pre-fault time plus fault
duration plus post-fault time.

1.3 Sampling Rate


The trigger recorder sampling rate is user-selectable from 256, 128, or 64 points-per-
cycle of the nominal frequency of the input signal. The size of the records is
proportionally affected.
The continuous recorder sampling rate is 16 points-per-cycle of the nominal frequency
of the input signal.
Both analog and digital inputs are recorded at the same sampling rate depending on the
type of recorder, i.e. Triggered fault records: 256, 128, or 64ppc and Continuous fault
record: 16ppc.

1.4 Re-trigger and Record Concatenation


When two or more consecutive triggers happen, case the post-fault time of the first Figure 70: Example of an event without concatenation
trigger and the pre-fault time of the second trigger cross each other, then the RPV311
concatenates both records and stores it in a single COMTRADE file.
In the figure below, if the time T≤ pre-fault time + post-fault time, then the records are 1.5 Trigger Burst Limiter
concatenated:

There is an user-configurable trigger burst limiter for the fault recorder.


The burst limiter is based on the number of triggers time interval (both parameters are
user-configurable). When the limit is exceeded, recording will be disabled for a period
of time defined by the user.

Parameter Allowed values Increment

Number of 0 … 12 1
triggers

Time interval 0 … 60 s 1s

Disabling time 1 … 60 min 1 min

Figure 69: Concatenation event example


Continuous and Trigger'd Disturbance Records
If the pre-fault time of the second register does not overlap the post-fault time of the
first records, then the RPV311 creates two separate COMTRADE files. Disturbance records can be created in the following ways:

140 RPV311-TM-EN-11.1
RPV311-TM-EN-11.1 139
RPV311 Chapter 6 – Records Chapter 6 – Records RPV311

x Continuously:
Derived measurements are continuously recorded. A new record is created at each hour
rollover. The record size depends on the number of derived measurements selected by The Timeout configures the maximum duration that the actual fault (threshold
the user (limited to 64). exceeded/trigger ON) can reach within a record. The maximum timeout of the
x By trigger: disturbance record is 20 minutes.
The disturbance recorder can be triggered by a Boolean equation, by a cross-trigger
signal of another recorder, by a manual trigger using the Web Interface, or by the
triggering of the fault recorder. It is possible to select the derived quantity of triggered 2.3 Sampling Rate
disturbance records. If the quantities are not manually selected, the record will consist
The trigger and continuous recorder sampling rate is one-per-cycle.
of all the quantities available for measurement. The record size depends of the number
Both analog and digital inputs are recorded at the same sampling rate depending on the
of derived measurements selected by the user.
type of recorder.
Continuous and triggered disturbance records share the same mass storage area.

2.1 Recorded Values 2.4 Re-trigger and Record Concatenation


Two records will be concatenated if the disturbance recorder is re-triggered and there is
an overlap between the post-fault time of the first record and the pre-fault time of the
second record.
The following values are recorded by the continuous and triggered disturbance
recorders:
x RMS value of voltage and current circuits;
2.5 Trigger Burst Limiter
x Voltage and current phasors;
There is an user-configurable trigger burst limiter for the disturbance recorder which is
x Frequency of voltage circuits;
identical to the fault recorder limiter.
x Positive sequence of voltage and current circuits;
x Negative sequence of voltage and current circuits;
x Imbalance of voltage and current circuits; Traveling Wave Fault Records
x Total harmonic distortion of voltage and current circuits; Faults in a transmission line cause transients traveling along the line as waves
x Apparent combined power of power circuits; composed of by a frequencies ranging of a few kilohertz to several megahertz.
x Apparent fundamental power of power circuits; These traveling waves have a wave front with a very fast rise time and a down time
which is relatively slow. The waves move at speeds near that of light, away of the fault
x Active fundamental power of power circuits;
point toward the end points of the line.
x Reactive fundamental power of power circuits; The waves are not limited to the transmission line where the fault occurred, spreading
x Digital channels (state of digital inputs and binary GOOSE messages). through the adjacent electrical system with decreasing amplitude, the result of the
combined effects of the impedance of the line and successive reflections.
Fault location by traveling waves is based on accurate determination of the moment
2.2 Recording Times by Trigger that the wave fronts pass the two terminals of the line. The traveling wave recorder can
be triggered by a Boolean equation.

Once triggered, the following parameters are considered by the disturbance recorder:
3.1 Pre-conditions
Parameter Allowed values Increment
The traveling wave fault location requires that a second equipment with the same
functionality is installed at the other end of the monitored power line.
Pre-fault time (‫ݐ‬୮୰ୣ ) 0 … 2 min 0.1 min
Both units must be synchronized by an IRIG-B signal with less than 100 ns jitter.
Specific traveling wave fault location software must be installed in the user´s computer.
Post-fault time (‫ݐ‬୮୭ୱ ) 0 … 20 min 0.1 min
This software, using the traveling wave records of both terminal lines and the power
line parameters, executes the fault location algorithm and shows the fault location
Timeout 1 … 20 min 0.1 min
estimation. For details about the Traveling Waves Fault Locator software, please refer
to Chapter 12: Software – RPV Tools and Chapter 13: Software – DR Manager.
142 RPV311-TM-EN-11.1
RPV311-TM-EN-11.1 141
RPV311 Chapter 6 – Records Chapter 6 – Records RPV311

3.2 Sampling Rate and Acquisition


Voltage total harmonic Quadratic average
The acquisition module RA333 has 3 independent channels (one circuit A, B, C), with an distortion
8-bit A/D converter. The sampling frequency acquisition is 5 MHz, synchronized by a
PPS signal, which means one acquisition each 200 ns. Current total harmonic Quadratic average
The acquisition module conditions the line voltage signal. With an efficient band-pass distortion
filter, the passing frequency is limited between 1 kHz and 1 MHz.
The module constantly acquires signals and storing the measured values locally in a 64 Fundamental active Simple average
MB RAM (approximately 4 seconds). The data is written into a circular buffer where the Power
oldest data will be overwritten by the latest until a threshold violation occurs.
On detecting violation of the threshold, the memory writing is interrupted. The Fundamental reactive Simple average
Power
memorized data is sent to the processing module at this moment. The complete
transfer of data takes about 2 minutes, and in this time the BUSY indicators are lit.
DC transducers Simple average
While data is being transferred to the processing module (2 minutes), new TW records
will not be registered. During this time, the other acquisition and processing modules
continue functioning normally.
The aggregation time interval is user-selectable between 1 minute or 10 minutes,
synchronized to UTC minute rollover. The timestamp refers to the end of the averaging
3.3 Recording Times window.
.
The recording parameters are fixed and the record has 3 electrical cycles (50 or 60 Hz)
before the violation of the limit and one cycle after, approximately 67 ms at 60Hz and
80 ms at 50 Hz. The duration of recording may vary slightly but this does not cause in
implications for fault location. 4.2 Harmonics
Harmonics are computed for phases A, B and C and for the neutral of up to two voltage
or current circuits. The algorithm used conforms to IEC 61000-4-7:1991.
Steady-State Records The signal is band-limited by Hanning-windows with width ܶ௪ = 200 ms, overlapped
்ೢ
every = 100 ms.
Steady-state records are composed of the following records and measurements: ଶ
A Fourier transform is used to obtain all frequency components of the input signal up to
x Average Series;
the 50௧௛ order.
x Harmonics;
The values obtained at every measuring window are aggregated over ܶ୴ୱ = 3 s.
x Flicker. Values resulting of the ܶ୴ୱ = 3 s aggregation are aggregated a second time over ܶୱ୦ = 10
min using classifiers. The result is the cumulative probability for each harmonic
One separate record for each measurement above are created once per day and component of the input signal.
recorded at 1 ppc. For each harmonic component of the input signal, the value that does not exceed the ‫݌‬
= 1, 10, 50, 90, 95, and 99 % percentiles in the ܶୱ୦ time interval is recorded.

4.1 Average Series


The equipment continuously records averaged values of
4.3 Flicker
Values of average series recorder Flicker is computed for phases A, B, and C for up to six voltage circuits. The algorithm
used conforms to IEC 61000-4-15:1997+A1:2003.
RMS (voltage) Simple average The aggregation time interval is 10 minutes in the Pst Flicker or Plt Flicker 2 hours,
synchronized to UTC minute rollover. The timestamp refers to the end of the averaging
RMS (current) Simple average window.

Voltage imbalance Simple average


SOE - Sequence of Events Records
Frequency Simple average
144 RPV311-TM-EN-11.1
RPV311-TM-EN-11.1 143
RPV311 Chapter 6 – Records Chapter 6 – Records RPV311

All variations of the equipment inputs occurred are recorded on this record.
The events in the SOE are recorded with accuracy better than 100μs.
Parameter Format Description
One SOE file is created per day.

STARTDATE yymmdd Record’s start date

Record Format and Naming, and Mass Storage Capacity (year, mounth, day)

STARTTIME hhmmssuuuuuu Record’s start time


(hour, minutes, seconds,
microsseconds)
6.1 Record Format
TIMECODE soohmm Indication of timezone offset
Records comply with the COMTRADE standard IEEE C37.111-1999, IEEE Standard (the last three characters are
Common Format for Transient Data Exchange for Power Systems. The ".dat", ".hdr", included only when fractional hours
".cfg", ".inf" and ".tri" files are zipped together in a ".zic" (zipped comtrade) file for are in use)
faster transmission.
The ".zic" files are created following the RFC 1951, DEFLATE Compressed Data Format STATIONID Location of the equipment,
Specification. configurable in:
The ".hdr" files have the information about the Reason for the trigger and the location
EQUIPMENT > IDENTIFICATION > LOCATION
of the fault, the md5sum of the ".dat" and ".cfg" files, and the status of the equipment
when the record was created. (up to 12 characters)
The ".inf" files have the groups and the power lines parameters. The data are formatted
according to the requirements of GE's Analise software. DEVICEID Equipment identifier, configurable
The ".tri" files have the sequence of digital events. The data was formatted according to in:
the requirements of GE's Analise software. EQUIPMENT > IDENTIFICATION > IDENTIFIER
The following information about the register and the RPV311 can be found within the
.zic file: (up to 12 characters)
x Trigger cause
COMPANY Equipment owner description,
x Date configurable in:
x Equipment health and sync status
EQUIPMENT > IDENTIFICATION > OWNER
x Memory usage
(up to 12 characters)
x Last power up
x Firmware version DURATION sssssuuuuuu Duration of the record
x Identifier
(seconds, microsseconds)
x Location
x Owner TYPE Record type:
Fault (fault record)

6.2 Record Naming Disturbance (disturbance record)


Avgs (historical averages)
Records are named using the COMNAME methodology, according to IEEE C37.232, SOE (sequence-of-events)
Recommended Practice for Naming Time Sequence Data Files.
Oharm (odd harmonics)
Fault, Disturbance, Steady-state, and Sequence of Events records are named as follows:
STARTDATE,STARTTIME,TIMECODE,STATIONID,DEVICEID,COMPANY,DURATION,TYPE.ZIC
Eharm (even harmonics)
Traveling wave records are named as follows:
STARTDATE,STARTTIME,TIMECODE,STATIONID,DEVICEID,COMPANY,DURATION,TW,TERMINAL.ZIC

146 RPV311-TM-EN-11.1
RPV311-TM-EN-11.1 145
RPV311 Chapter 6 – Records

TERMINAL Terminal identification of the


Power Line where the wave front
has been recorded.

6.3 Mass Storage Capacity

Memory Capacity Typical use

3300 records (triggered) or 14 days (continuous with 16


Fault 22 GB measurements selected) - 12 circuits, 2 seconds and 256 points-
per-cycle

1350 records (triggered) or 9 days (continuous with 64


Disturbance 9 GB
measurements selected) - 12 circuits, 2 minutes

1 year - 12 circuits@ 1 minute, 2 samples of harmonics @ 10


Steady state 1 GB
minutes

SOE 500 MB 36 days - 256 channels @ 10 events per minute

TW 1 GB 410 records (2.4 MB each)

The equipment can be configured to automatically remove the oldest records as the
soon as mass storage occupation exceeds 90%.
All RPV311 files including configuration and records are stored in the SSD non-volatile
memory.

Record Management and Access

Records can be accessed in three ways:


x Through the Web Interface, see further information in Chapter 5: Operation;
x Through the Scanner which is part of the RPVTools package, see further
information in Chapter 12: Software – RPV Tools;
x Through auto upload, see further information in Chapter 4: Configuration.
Management of records is done using the DR Manager. For details about the DR
Manager, see Chapter 13: Software – DR Manager.

RPV311-TM-EN-11.1 147
Chapter 9 – TW Fault Locator RPV311

RPV311
The RPV from one terminal does not need to communicate with the other terminal’s
RPV in order to create the TW COMTRADE file.
A communication link is only needed between the control centers and the RPVs (or local
Distributed Multifunction Fault Recorder data concentrators) the user wants to implement remote access to the equipment.
The communication setup that the user would deploy to download the TW record and
perform the fault location is exactly the same as the one used to download the fault
Chapter 7: TW Fault Locator records.
The fault distance is calculated based on the time that each wavefront arrived at the
line terminal. According to the following equation.
This chapter provides information regarding the architecture and the proper use of the
Reason Traveling Wave Fault Location.

݈ ൅ ‫ܿܭ‬ሺ‫ݐ‬௔ െ ‫ݐ‬௕ ሻ
݀ ൌ
TWFL Overview ʹ
The figure below shows an overview of the Traveling Wave Fault Location architecture.
Where:
d: fault distance from terminal A;
l: length of the line;
k: constant of the line attenuation of the speed of the wave;
c: speed of light
ta: time which the traveling wave gets to terminal A
tb: time which the traveling wave gets to terminal B

The means to get the COMTRADE files from the RPV311 to the computer where the
fault location will be performed are described in Chapter 5: Operation, COMTRADE files
download.

TW Fault Location Information

2.1 TW Triggering System


The TW record is a COMTRADE file with 3 cycles prior to the trigger plus 1 cycle after
the trigger, that means approximately 67 ms @ 60 Hz and 80 ms @ 50 Hz. The RPV311
takes about 30 seconds to create a record and it can create up to 4 records at the same
Figure 71 – TW Fault Locator architecture overview time. When 4 records are being created at the same time new triggers will not create a
Each terminal of the line must have a set of RPV311 processing unit+RA333 acquisition record and the “BUSY” LED in the RA333 will turn on. After the record from the first
unit; and each RPV311 has to be synchronized with a GPS Clock as accurate as possible. trigger is finished, then the RA333 will be able to capture the next trigger.
The signal used to extract the traveling waves if the voltage signal from the secondary Trigger events that happen within a time window of 1 electric cycle will create a single
circuitry of the VT. TW COMTRADE file. If another trigger happens after 1 cycle from the first trigger of the
During a fault the RPV311 in each terminal will register the waveform of the traveling event, then another TW COMTRADE file will be created.
wave in a COMTRADE file, after being triggered by any of the thresholds described in
Chapter 4 - Thresholds.
The DR Manager software will download the COMTRADE files with the TW capture
automatically and periodically from all the RPV311 within the ethernet network and will
2.1.1 Consecutive Faults
calculate the distance to fault automatically. More information on the DR Manager is
found in Chapter 13: Software – DR Manager or in the DR Manager user manual.

150 RPV311-TM-EN-11.1
RPV311 Chapter 9 – TW Fault Locator Chapter 9 – TW Fault Locator RPV311

The RPV311 can have up to 4 TW COMTRADE files being created at the same time, it
means that it can record and locate faults in at least 4 consecutive events in a 2-minute
time frame, such as evolving faults and switch-on to fault operations
2.4 Underground and Overhead Cables
There are no restraints regarding the fact that the cable is underground. In the
calculation of the fault location, there is a parameter k (as presented in the fault
location formula aforementioned) that depends on the physical characteristics of the
Note:
wire. When the TW fault locator method is used on combination of cable. The user can
For regular 3-phase circuits, the triggers are also 3-phase, i.e. in an event where a
fault evolve to another phase, the trigger will already be sensitized by the previous configure the TW fault location in two manners: using the mixed lines configuration,
fault. Since the TW recorder do not have a retrigger system it is necessary that a where the user will configure a different k parameters for each section of the line. This
new trigger activates for the TW recorder to capture the consecutive event. To do method does not lose accuracy; or use a single average k for the entire line. , note that
so, it is necessary to have binary triggers monitoring the different protection trips the average k will not represent the actual k of the line at the faults location. It is an
that will detected the consecutive events, by doing so only the phase involved in approximation, therefore it will present less accuracy.
each fault will trigger at a time, allowing the multiple recordings.

Note:
The maximum number of RA333 that can be connected to the RPV311 is 4.
2.2 Switch-on to Fault
The RA333 module has to be connected to the RPV311 processing module before
its initialization. Otherwise a log message will tell the user to reboot the device.
When a short circuit occurs right after the circuit breaker closes, the behavior of the
traveling waves become different from regular faults, mainly because the circuit
breaker itself can create traveling waves that can be misinterpreted as traveling wave
from the fault and it may turn the fault location calculation more difficult. To avoid that,
the DR Manager analyses both the waveform/fault and the TW COMTRADE records to Automatic Fault Location
first identify that a switch-on event occurred and then to apply a special fault location The DR Manager software is a tool design for management of COMTRADE files,
algorithm. Additionally, special conditions need to be met for the switch-on to fault configuration and fault location. One of its features is the automatic TW fault location.
(SOTF) events to be located automatically: The DR Manager download the COMTRADE files from both terminals of the line,
performs the fault location calculations, displays the fault location results in its interface
ƒ The fault shall be at least 6 km away from both line terminals. and sends the location via MODBUS to the supervisory system.
ƒ The transmission line maximum length shall be 2000 km. Details on the configuration procedure, please refer to Chapter Software – DR Manager.
ƒ The fault location for switch-on events will not work for mixed (hybrid) lines.
ƒ There needs to be a corresponding waveform recording for each event
(Chapter 4: Configuration. 10. Fault Recorder). How to Test the TW Fault Location in Lab
Even meeting all the conditions above, SOTF events are rare and difficult to interpret
The most complete test would be using two sets of RPV311+RA333:
automatically, thus, the DR Manager will indicate on its interface whenever an event is
1. Make sure that both RPV311 are properly time synced. For conditions that are
characterized as a switch-on so the user can be cautious and double check the
more realistic, the sync sources could be independent;
recordings.
2. Configure a line arbitrarily long on the DR Manager or TW Fault Locator
software connecting the two sets of equipment;
3. Configure the TW register to be triggered by an undervoltage threshold in
both RPV311;
2.3 Maximum Number of Lines Monitored by the TW Fault Locator 4. Connect three phase voltage to the TW analogic inputs in both RPV311 though
If the voltage is sourced from a bus VT you only need one RA333 to capture TWs from a circuit-breaker or test switch;
all the lines connected to that bus. Moreover, it is possible to connect up to 4 modules 5. Switch off the circuit-breaker (or test switch), both RA333 should indicate the
RA333 to one processing unit RPV311. BUSY state, showing that the TW is being processed. register is being
processed;
6. Download both files to a computer with the TW Fault Locator tool installed.
7. Run the TW Fault Locator tool to find the fault location (Procedure described
RPV311 manual, in topic 14.5). The fault location should be 50% of the line.

152 RPV311-TM-EN-11.1
RPV311-TM-EN-11.1 151
RPV311 Chapter 9 – TW Fault Locator Chapter 9 – TW Fault Locator RPV311

Alternatively, it is possible to useone RPV311 and two RA333 connected to the same
RPV311. Taking care when creating the powerline file, in which only the “line” + L1’’ (Figure 73), and the second powerline file configuration regarding the section C ->
parameter will be different, for example: B with length and k1 equal L1’’ + L2 (Figure 73).
In order to locate the fault is necessary to combine the fault location of both situations
<terminal_a>LOCATION,IDENTIFIER,LINE_A</terminal_a> describe above.
<terminal_b>LOCATION,IDENTIFIER,LINE_B</terminal_b>

Another possibility that also tests the acquisition system of the RA333 module, is to use
only one RPV311+RA333 and configure the powerline file with the same parameters for
both terminals, for example:

<terminal_a>LOCATION,IDENTIFIER,LINE_A</terminal_a>
<terminal_b>LOCATION,IDENTIFIER,LINE_A</terminal_b>

In this case, the TW fault locator tool will use the same file for both ends locating the
fault.
For all the previous mentioned tests, the algorithm shall point the fault location at 50%
of the line length, as we are using with very short cable lengths or using the same TW
register for both ends.

Three Terminal Line Application

The figure below shows a line of three-terminal. The Terminal A, B and C (sources X, Y
and Z respectively).

Figure 73 – Three terminal line application

5.1 Examples

Consider the TAP point located at 50% of line A-B and 50% of line C-B. Consider the
Figure 72 - Typical Circuit Three-Terminal Application names and topology of Figure 73.
Example 1:
If the result of the fault location of the line A-B returns more than 50% of the length of
To use TWFL in the case above 3 sets of equipment are necessary: 3(RPV311 + RA333). the line and the result of the fault location of line C-B also returns more the 50% of the
One set for each terminal (Figure 73). length, then we know the fault is in the L1’’ section, as in Figure 73 Figure 74.
In this application, it is necessary to configure two transmission lines in the TW Fault Example 2
Locator tool, which means to create two powerline configuration files. The first Now consider the result of fault location on line A-B being at more than 50% of the
powerline configuration file is regarding line A -> B with length and k1 equal to L1 = L1’ length and the result of the fault location on line C-B at less than 50%, then we know

154 RPV311-TM-EN-11.1
RPV311-TM-EN-11.1 153
RPV311 Chapter 9 – TW Fault Locator Chapter 9 – TW Fault Locator RPV311

the fault is in the L2 section, as in Figure 74 and Figure 75 show the location of the
faults in example 1 and 2, respectively.

Figure 75 - TW Fault Location example 2

Figure 74 – TW Fault Location example 1 TWFL in Mixed (Hybrid) Lines

A hybrid transmission line is comprised of two or more different line types. That matters
for the TWFL because the velocity of the fault wave is different in each section of the
line and that shall be taken into account during the fault distance calculations.
The wave velocity is related to the relative permittivity of the main insulation and
different thicknesses of the semi-conducting layers. Assuming one constant wave
velocity for such a line will result in errors.

6.1 K Factor Calculation – Overhead Section


In the case of K factor relating to overhead line, without insulating material, it is
considered that the dielectric material insulating the cable is only the air. In this case,
the constant of permeability and permittivity is very close to 1.0.
ߤ௥ೌ೔ೝ ؆ ͳ ߳௥ೌ೔ೝ ؆ ͳ

156 RPV311-TM-EN-11.1
RPV311-TM-EN-11.1 155
RPV311 Chapter 9 – TW Fault Locator

‫ܥܭ‬
ܸ௪௔௩௘೚ೡ೐ೝ೓೐ೌ೏ ൌ ؆ ͳǤͲ‫ܥ‬
ඥߤ௥ೌ೔ೝ ߳௥ೌ೔ೝ

In overhead lines, the velocity of the fault wave is very close the speed of light, between
98% and 99.5%, it means that the factor K ranges from 0.985 to 0.995. Calculating the K
precisely is a very complex task, because it depends on unknown constants of
permeability and permittivity of the overhead cable dielectric, which in this case is the
air. That means that these constants may vary with humidity, atmospheric pressure and
distance between the conductors of the transmission line in question.
Therefore, during commissioning, the K is usually set to 0.99 and improved later based
on the data from subsequent fault location distances.

6.2 K Factor Calculation – Underground Section


In this type of table the insulation material have permeability and permittivity well
defined for the entire cable, which makes it easier to calculate the k factor more
accurately.
A common material used in the insulation of these cables is the XLPE. The example
below shows the calculation of the K parameter using XLPE cable and its permeability
and permittivity constants, where the result is K = 0.66.

ߤ௥ೣ೗೛೐ ؆ ͳ ߳௥ೣ೗೛೐ ؆ ʹǤ͵

‫ܥܭ‬
ܸ௪௔௩௘೚ೡ೐ೝ೓೐ೌ೏ ൌ ؆ ͲǤ͸͸‫ܥ‬
ඥߤ௥ೌ೔ೝ ߳௥ೌ೔ೝ

RPV311-TM-EN-11.1 157
Chapter 8 – PMU RPV311

RPV311
3-phase Apparent Power from phasor (S1) and
from RMS (S)
Distributed Multifunction Fault Recorder
3-phase Real Power from phasor (P1)
3-phase Reactive Power from phasor (Q1)
Chapter 8: PMU
Digitals Any digital channel
This chapter provides detailed information about the PMU feature.

Synchrophasor Measurement and Broadcast


1.2 Accuracy Limits
Synchrophasors UDP/IP Class M are measured and broadcast according to the
specifications contained in IEEE C37.118, Standard for Synchrophasors for Power
The Total Vector Error defined through
Systems.

1.1 Reported Values ሺܺ௥ ሺ݊ሻ െ ܺ௥ ሻଶ ൅ ሺܺ௜ ሺ݊ሻ െ ܺ௜ ሻʹ


 ൌ ඨ
ܺ௥ଶ ൅ ܺ௜ଶ
The reported values are user-selectable of the list below.

Reported values user-selectable

Represents the magnitude of the error vector, obtained by subtracting the measured
Phasors Voltage synchrophasors (any phase)
synchrophasor of the theoretical value. It is represented as a fraction of the magnitude
of the theoretical value.
Current synchrophasors (any phase)
In the equation above, ܺ௥ ሺ݊ሻ and ܺ௜ ሺ݊ሻ are the measured values, while ܺ௥ and ܺ௜ are
the theoretical values of the input signal at the instant of measurement.
Positive and Negative sequence for voltage
circuits All 1A and 5A analog inputs/boards in RA33x modules have the proper accuracy
necessary for the RPV311 PMU solution to be rated as level 1 compliant according to
Positive and Negative sequence for current IEEE C37.118 under the condition below.
circuits
Influence quantity Range TVE max
Frequency Frequency and frequency variation of the
respective frequency chosen frequency Signal frequency ± 5 Hz of Fnom 1%

Any DC channel Signal magnitude 10 % … 120 % 1%


rated
Voltage (RMS) value (any phase)
Phase angle ± 180° 1%
Current (RMS) value (any phase)
Harmonic distortion 10 % ¹ 1%
Scalars Voltage circuit imbalance
Out-of-band interfering signal ³ 10 % ² 1%
Current circuit imbalance ‫ܨ‬௦
ȁ݂௜ െ ݂ே ȁ ൐
ʹ
Total voltage harmonic distortion (any phase)
¹ Any harmonic up to 50௧௛ order
² Of input signal magnitude
Total current harmonic distortion (any phase)
160 RPV311-TM-EN-11.1
RPV311 Chapter 8 – PMU Chapter 8 – PMU RPV311

³ ݂௜ frequency of interfering signal, ݂ே nominal frequency and ‫ܨ‬௦ synchrophasors


broadcast frequency
WMU – Waveform Measurement Unit

1.3 Communication Ports, Transmission Rates The WMU transmits Ethernet messages that are analogue signals calculated and sent
within a PMU frame with a transmission rate equal to 4 times the system nominal
Each stream of data is transmitted through a particular UDP/IP port listed in the table
below: frequency.
The analog signal sent is a representation of a three-phase signal that is used to
evaluate wide-area subcyclic oscillations. The WMU uses the analogue field (No 10) of
the frame below to send its data.
Stream of data Port number The WMU uses the commanded logic through the port number 4723.
The table below exemplifies a frame of PMU described as per IEEE C37.118.2-2011.
1 4713 N Size
Field Comment
o (bytes)
2 4714 1 SYNC 2 Sync byte followed by frame type and version number
FRAMESIZ
2 2 Number of bytes in frame
3 4715 E
3 IDCODE 2 Stream source ID number, 16-bit integer
4 4716
4 SOC 4 SOC timestamp, for all measurements in frame.
The transmission rate options at 60Hz are: 10, 12, 15, 20, 30, or 60 frames per second
At 50Hz the rates are: 10, 25, or 50 frames per second.
5 FRACSEC 4 Fraction of Second and Time Quality, for all measurements in frame.

6 STAT 2 Bit mapped flags.

Phasor estimates. May be single phase or 3-phase positive,


1.4 Timestamp 4x
negative, or zero sequence. 4 or 8 bytes each depending on
PHNMR
the fixed 16-bit or floating point format used, as indicated
7 PHASORS or
by the FORMAT field in configuration the frame. The
The reported timestamp is synchronized to the UTC second rollover and refers to the 8x
number of values is determined by the PHNMR field in
middle of the sampling window. PHNMR
configuration 1, 2, and 3 frames.

8 FREQ 2/4 Frequency (fixed or floating point).


1.5 Configuration 9 DFREQ 2/4 Rate of change of frequency (fixed or floating point).

2x Analog data, 2 or 4 bytes per value depending on fixed or


The PMU configuration is carried out through the Web Interface. For details about the ANNMR floating point format used, as indicated by the FORMAT
ANALOGU
PMU configuration, see Chapter 4: Configuration. 10 or field in configuration 1,2, and 3 frames. The number of
E
4x values is determined by the ANNMR field in configuration 1,
ANNMR 2, and 3 frames.

1.6 Standards Compliance 2x Digital data, usually representing 16 digital status points
11 DIGITAL DGNM (channels). The number of values is determined by the
R DGNMR field in configuration 1, 2, and 3 frames
The RPV311 PMU Class M complies with the following standards: Repeat 6 – 4x Fields 6 - 11 are repeated for as many PMUs as in NUM_PMU field in
11 ANNMR configuration frame.
IEEE C37.118-2005 12
CHK 2 CRC-CCITT
+
IEEE C37.118.1-2011
IEEE C37.118.2-2011
IEEE C37.118.1a-2014 .

162 RPV311-TM-EN-11.1
RPV311-TM-EN-11.1 161
Chapter 9 – MODBUS RPV311

Bit 4: IRIG-B synchronization failure


RPV311 Bit 5: Fault recording low memory
Bit 6: Disturbance recording low memory
Bit 7: Steady-state recording low memory
Distributed Multifunction Fault Recorder Bit 8: Sequence-of-events recording low memory
Bit 9: Internal failure
Chapter 9: MODBUS
This chapter provides detailed information about the MODBUS feature.

Description 1.3 Analog Data

Status, analog and digital data are available in MODBUS registers. Access to SCADA The user must manually associate analog data to a register number. The following
integration is provided over Ethernet interface. Up to 8 simultaneous connections are analog data can be selected:
allowed at a maximum rate of 60 accesses per second. x RMS value of voltage and current circuits (any phase);
x Voltage and current synchrophasors (any phase, angles are sent in degrees
units);
x Frequency of voltage and current circuits;
1.1 Register Types
x Positive sequence of voltage and current circuits;
Each register reports 16-bit data. Registers are divided into 3 groups:
x Negative sequence of voltage and current circuits;
Register Type x Imbalance of voltage and current circuits;
x Total harmonic distortion of voltage and current circuits;
0 Status
x Apparent combined power of power circuits;
100 to 199 Analog data x Apparent fundamental power of power circuits;
x Active fundamental power of power circuits;
200 to 223 Digital channels
x Reactive fundamental power of power circuits;
x RMS value of transducer channels.

1.2 Status 1.4 Digital Channels


The equipment status is reported by the following registers:

Register Type All digital channels are reported in groups of 8 channels. A register data is composed of
16-bit data where the least significant bit represents the state of the first digital channel
0 General State of the group. The user must manually associate a digital group with a register number.

Bit 0: General failure


Bit 1: Low primary power voltage 1.5 Configuration
Bit 2: Not used
Bit 3: Not used
164 RPV311-TM-EN-11.1
RPV311 Chapter 9 – MODBUS

The MODBUS configuration is carried out through the Web Interface. For details about
the MODBUS configuration see Chapter 4: Configuration.

RPV311-TM-EN-11.1 165
RPV311
Distributed Multifunction Fault Recorder
Chapter 10: DNP3
This chapter provides detailed information about the DNP3 feature.

Description

Status, analog and digital data are available in DNP3 registers. Access to SCADA
integration is provided via Ethernet interface. The DNP3 functionality is fully dependent
on the MODBUS functionality. To use DNP3, it is necessary for a configuration key to
unlock the MODBUS functionality.
Each register reports 16-bit data. Registers are divided into 3 groups, status, analog and
digital channels.
For each digital channel added to the DNP3 library database, a number is associated.
These numbers are integers and start at zero. The number associated follows the order
that the digital channels are created at equipment configuration.
For each analog channel added to the DNP3 library database, a number is associated.
These numbers are integers and, for analog channels, start at number five. The number
associated follows the order that the analog channels are configured at the
MODBUS/DNP3 configuration.

Associated number at DNP3 database

0a4 Status

5 a 199 Analog data

0 to 23 Digital data.

Note:
The phase angles are sent in radians units.
Chapter 12 – RPV Tools RPV311

RPV311
clock is larger than 1 electric cycle, then the RPV311 will disregard the timestamp within
the message and use the internal clock as time reference to record the message.
Distributed Multifunction Fault Recorder
Chapter 11: GOOSE Message Detection
This chapter provides detailed information about the GOOSE message detection
functionality.

Description
Digital channels can be associated with physical electrical digital inputs or associated to
the detection of IEC61850, GOOSE messages.
GOOSE messages are captured and filtered by one of the Ethernet interfaces installed at
the communications module. The state of the binary variables in the GOOSE message
associated with digital channels and can be included in trigger equations, and can be
stored in the fault record, disturbance record, and in the sequence of event (SOE)
record.
The equipment can detect up to 320 binary inputs. The dataset types supported are:
x Boolean data type (1 bit);
x Bitstring data type (group of 64 bits);
x Enumeration data type (compare with some value to create a Boolean state).
GOOSE messages can be filtered by VLAN, MAC addresses and by the application
identifier.
The association between the GOOSE messages and digital channels is made using the
GOOSE Configurator, which is part of the RPVTools package. For details about the
GOOSE Configurator configuration see Chapter 12: Software – RPV Tools.
The RPV311 GOOSE subscription is tested and attested for conformance according to
IEC 61850 by DNV GL (KEMA).

Note:
All the three rear Ethernet ports are capable of reading the GOOSE messages, but
the same GOOSE messages shall not be sent to more than one port at the same
time because they will be processed again by the device as it was the same
message causing wrong readings.

1.1 GOOSE Timestamp Behavior


Depending on the following conditions, the RPV311 will chose whether to use the
timestamp within the GOOSE message or the RPV311 own internal clock to position the
message in time in the records.
The RPV311 considers two different time quality bits of the GOOSE message (IEC61850-
8-1) when deciding the point in time the message should be positioned. Whenever
either the “ClockFailure” or the “Clock not synchronized” are asserted in the message
coming in; or the difference between the GOOSE timestamp and the RPV311 internal
170 RPV311-TM-EN-11.1
RPV311 Chapter 12 – RPV Tools Chapter 12 – RPV Tools RPV311

RPV311 Mozilla Firefox version 17.0 or higher;


Adobe Flash Player version 12 or higher.

Distributed Multifunction Fault Recorder Minimum requirements

Processor 1 GHz or higher;


Chapter 12: Software – RPV Tools Minimum 512 MB RAM memory;
Minimum 500 MB free space on disk.

This chapter provides detailed information about the features, configuration and usage
Only the administrator of the system can install the RPV Tools. To check if the user is
of the DR Manager software.
the administrator click START ൐ SETTINGS ൐ CONTROL PANEL ൐ USER ACCOUNTS. The computer
administrator information will show below the login. If the user is not the computer
administrator contact the manager of your system.
RPV Tools Description To install the software, follow the procedures below:
1. Insert the CD-ROM in the CD-ROM unit of the PC;
2. Access the CD-ROM unit, double click on the rpv-software. install-en-swvrr.msi
The RPV Tools are a suite of applications to be installed on the PC and allow the file (for example: rpv-software.install-en- 04A00.msi);
communication and the transfer of records between several pieces of equipment and a 3. The screen RPV Tools Setup will appear. Accept the terms in the License
PC. It also allows user to receive, manage, edit, and transmit configurations of different Agreement and click <INSTALL>. Wait for the complete installation of the
pieces of equipment. software;
The suite consists of: Scanner, Configuration Tool, Fault Locator and GOOSE 4. After installation is finished, click <FINISH> and then click <YES> to restart the
Configurator. system.
The Scanner is a tool that makes a sequential scanning of the records. It searches,
transfers and saves the records on the PC according to the user configuration. Four icons for quick access to the applications will be created on the Desktop and an
The Configuration Tool allows user to receive, manage, save, and transmit the RPV directory will be created in the root directory where Windows is installed. For
configuration between the equipment and a PC. example: C:̳RPV̳conftool\conf. The same applications also can be accessed by clicking
The Fault Locator application allows user to define where an event has happened, Start ൐ Programs ൐ RPV.
based on traveling wave records (two ends of the transmission line). It is necessary to restart the PC to complete the removal process.
The GOOSE Configurator allows the user to configure the RPV in order for it to receive The RPV Tools installation is in the same disk where Windows is installed.
and filter GOOSE messages Ethernet. The installation process takes up to 5 minutes.

1.1.2 Uninstalling
1.1 RPV Tools Installation
To uninstall the software, click START ൐ SETTINGS ൐ CONTROL PANEL ൐ ADD OR REMOVE
1.1.1 Installing PROGRAMS. And then select RPV TOOLS on the list and click <REMOVE> then click <YES> on
the ADD OR REMOVE PROGRAMS window.
The removal process takes about 4 minutes.
The installation of the RPV Tools applications on the PC is performed with a special tool
The directory containing the files will not be removed.
called Installer, which is part of the software.
The minimum hardware requirements for the installation and execution of the RPV
Tools are:
Supported operational systems
1.2 Scanner
Windows XP operational system Service Pack 2.
1.2.1 Description
Windows 7.

Applications
172 RPV311-TM-EN-11.1
RPV311-TM-EN-11.1 171
RPV311 Chapter 12 – RPV Tools Chapter 12 – RPV Tools RPV311

The Scanner is a tool that searches for the records in several pieces of equipment; it
transfers and saves them in an organized manner on the user's PC. The Scanner does a
<modem enabled=”xx”> Enter Yes if communication with the RPV is
recurrent scanning of the equipment's records, meaning that it scans all the pieces of only by modem or enter No if the modem is
equipment and, after some programmable period of time, it starts the scanning again. not necessary for, communication with the
RPV

1.2.2 Access <phonenumber>xxxxx</phonenumber> Telephone number to connect the modem


automatically

Scanner is accessed through an xml configuration file, where it is possible to configure a


The configuration file can be changed during the scanning process. The update
list of pieces of equipment to be scanned in each cycle, the configuration file can be
will occur in the next scanning cycle, after the waiting time.
saved either in a standard file
Once the file is configured, scanning will be performed following the configuration
(C:̳RPV̳scanner̳conf̳conf.xml) or in an alternative file, which in turn can be indicated of the file whenever the Scanner is started.
by command line. Example of a configuration file with RPV:
The Scanner can also be started directly of the desktop icon on the desktop created Below is the configuration of the xml file with an interval of 300 seconds between
when the user install the RPV Tools. the cycles.
First RPV: activated scanning, RPV 192.168.0.195, waiting time for connection of 60
seconds, scanning fault, disturbance, steady state and SOE records, no baud rate limit,
1.2.3 Editing Configuration File automatic deletion of records, activated modem, telephone number for connection to
the modem 21080 300;
Second RPV: activated scanning, RPV 192.168.0.199, waiting time for connection of 60
Using Notepad or any other editor, open the xml configuration file located in
seconds, scanning fault records, no baud rate limit, automatic deletion of records, no
C:̳RPV̳scanner̳conf̳conf.xml.
modem.
The configuration file must be saved; otherwise, the configuration will be lost.
To configure each RPV311, it is necessary to fill in the file fields as shown below: ൏?xml version="1.0" encoding="UTF-8"?൐

Configuration file fields ൏scanner൐

<interval>xxx</interval> Time interval between the beginning of a ൏interval൐300൏Ȁinterval൐


cycle and the beginning of another,
൏list൐
expressed in seconds
൏equipment enabled="yes ൐
<equipment enabled=”xxx”> Indicates whether the configured RPV will be
scanned or not (yes or no) ൏address൐192.168.0.195൏Ȁaddress൐

൏timeout൐60൏Ȁtimeout൐
<address>xxx.xxx.xxx.xxx</address> IP address of the RPV to be scanned
൏records൐
<timeout>xx</timeout> Waiting time for communication with the RPV
expressed in seconds ൏record൐fault൏/record൐

<record>xxxxx</record> Indicates the type of the record that will be ൏record൐disturbance൏Ȁrecord൐


transferred or saved on the PC. The records
൏record൐steadystate൏Ȁrecord൐
can be fault, disturbance, steady-state, SOE
and TW. ൏record൐soe൏Ȁrecord൐

<bandwidth>x</bandwidth> Limits or raises the baud rate of the records, ൏Ȁrecords൐


where zero means no baud limits, expressed
in KB ൏bandwidth൐0൏Ȁbandwidth൐

൏delete൐yes൏Ȁdelete൐
<delete>xxx</delete> Determine whether automatic removal,
programmed on the RPV, will be ignored or ൏modem enabled="yes"൐
not (yes or no)
൏phonenumberȀ൐21080300൏Ȁphonenumber൐
174 RPV311-TM-EN-11.1
RPV311-TM-EN-11.1 173
RPV311 Chapter 12 – RPV Tools Chapter 12 – RPV Tools RPV311

൏Ȁmodem൐

൏Ȁequipment൐ 1.2.6 Records


൏equipment enabled="yes"൐

൏address൐192.168.0.199൏Ȁaddress൐ The records received are saved in C:̳RPV̳records,as shown in Figure 76.
[location, RPV identifier]̳[record type]̳.
൏timeout൐60൏Ȁtimeout൐

൏records൐

൏record൐fault൏Ȁrecord൐

൏Ȁrecords൐

൏bandwidth൐0൏Ȁbandwidth൐

൏delete൐yes൏Ȁdelete൐

൏modem enabled="no"൐

൏Ȁmodem൐

൏Ȁequipment൐

൏Ȁlist൐

൏Ȁscanner൐ Figure 76: Directory of the records received of the equipment

1.2.4 Starting Scanner


1.2.7 Logging
There are 2 possible ways to start the Scanner:

The Scanner generates a log file with all the information about the ongoing process.
1. Double click on the Scanner icon on the Desktop;
The log messages are available in the directory C:̳RPV̳scanner̳log̳scanner.log
2. Click on Start ൐ Programs ൐ RPV ൐ Scanner.

The Windows security alert window may appear during the first cycle of the Scanning. 1.2.8 Troubleshooting
Click on the <UNBLOCKED> button to start the second cycle.

Example: Problem Solution

C:̳RPV̳scanner̳resources൐scanner Scanner 02A00 Starting cycle ͓1 The connection with the RPV311 was Check if the modem or the network is working
not possible
͓1: Scanning records of the RPV 192.168.0.195: "fault disturbance steadystate soe"
͓1: Records transferred of 192.168.0.195. Waiting 300.0 seconds for the next cycle...

1.2.5 Terminating the Scanner

To stop using the Scanner, either press <CTLR> + <C> or close the command Prompt.

176 RPV311-TM-EN-11.1
RPV311-TM-EN-11.1 175
RPV311 Chapter 12 – RPV Tools Chapter 12 – RPV Tools RPV311

A Shows the identification and the version of the RPV Tools.


1.3 Configuration Tool
B List of equipment configurations stored locally:

1.3.1 Description
Equipment configurations
The Configuration Tool allows creation of offline equipment configuration and sending
of it to several RPV's. With this tool it is possible to make a safety backup of all the Name Configuration name defined by the user
equipment configurations and either export them to a file server or keep them locally
on the user's PC. Location Shows location of the equipment.
The user interface is based on the Web Interface used to access the equipment. A Web The location of the equipment is defined in the
browser is required to run this tool. RPV configuration. This information is read of
An Ethernet or a modem interface makes access for sending or receiving configuration the EQUIPMENT > CONFIGURATION FILE
to from the equipment. Once it is received, the equipment configuration is stored
locally and may be edited or renamed without requiring any other access to such Identification Shows the identification of the equipment.
equipment. The identification of the equipment is defined in
To send a configuration it is mandatory that the connection to equipment be available. the RPV configuration. This information is read
The same configuration may be sent to different pieces of equipment. of the EQUIPMENT > IDENTIFICATION
The user must beware that all configuration parameters are immediately effective once
the configuration has been transmitted. Wrong configuration parameters may set the Equipment Shows the equipment model and firmware
equipment to Not Ready or cause loss of communication. version to which the configuration refers
By clicking the Configuration Tool icon, the PC's default Web browser will open the tool.
The main screen is shown in Figure 77.
C Buttons to send or receive a configuration to or of a piece of equipment, to import or
export a configuration to or of a file, to edit or remove an equipment configuration which
is locally stored, and to convert an older version configuration for a newer version (the
Convert button is applicable only for the model RPV-310).

Before using the Configuration Tool it may be necessary to install a plug-in file related
to the firmware version installed on the equipment.

1.3.2 Plug-in

Every equipment model and firmware upgrade has a new plug-in file to incorporate the
changes to the Configuration Tool.
The plug-in file is available with the firmware release.
Installation of the plug-in file is mandatory for any equipment model and firmware
version that is to use this tool.
To install the plug-in, do the following:
1. Double click on the plug-in file (example: rpv310-software.plugin. install-en-21A00).
2. Select the checkbox with the text to Accept the agreement license terms and click on
the ൏Install൐button. Wait for installation to be completed and then click on the
൏Finish൐ button.

See C:̳RPV̳conftool̳resourses̳plugins to check which plug-ins are installed.


Figure 77: Configuration Tool main screen
178 RPV311-TM-EN-11.1
RPV311-TM-EN-11.1 177
RPV311 Chapter 12 – RPV Tools Chapter 12 – RPV Tools RPV311

To remove a plug-in, go to Start ൐ Control Panel ൐ Add or remove programs.


Select the plug-in file to be removed and click on the ൏Remove൐ button.
The uninstall process takes about 1 minute.
1.3.6 Importing Equipment Configuration

1.3.3 How to Use It It is possible to import a configuration previous saved on the computer. To import a
configuration, the exported configuration XML file has to be first stored in the folder
To open the Configuration Tool, double click on the Conftool icon and wait while C:\RPV\conftool\conf and then proceed as follows:
default Web browser is opening. Double click Conftool icon. The Configuration Tool interface will open in the default
To close the Configuration Tool, close the Web browser window. Web browser;
Click on the ൏IMPORT൐ button. A new window will open;
Click on the Browse button to choose the configuration file previously saved on the
1.3.4 Web Browser Configuration
computer;
Enter a name for the configuration;
Click on the ൏OK൐ button. An RPV configuration interface will open. It is possible to
The Configuration Tool runs on a Web browser (Internet Explorer or Mozilla Firefox).
check the configuration parameters as if user were on-line with the equipment;
Before using it for the first time, it is necessary to configure some security parameters
Click on the ൏SAVE൐ button once again to save the new configuration on the PC;
of the Web browser and the Flash Player. To perform the configuration, follow these
Click on the ൏FINISH൐ button to go back to the main screen of the Configuration Tool.
steps:
The configuration will be on the list of locally stored configurations.
In the configuration tool window, right click and select Global Settings. The Adobe Flash
The configuration window will appear in the Configuration Tool. The user can choose to
Player Settings will open;
edit the configuration again, store it or transmit it to the RPV.
Click on Trusted locations settings. The window will open;
It is possible to save the configuration with the same name as an existing one. However,
Click on Add and then click on Browse for folder, find the RPV folder, then click it and
the existing configuration will be overwritten.
after that click on the ൏OK൐ button.
Close the Flash Player Help window.
1.3.7 Editing a Stored Configuration
1.3.5 Receiving Equipment Configuration
To edit a stored configuration follow these steps.
Select the name of the stored configuration to be edited and click on the ൏EDIT൐
To be able to receive an equipment configuration, the user must be connected to the
button;
equipment by Ethernet or modem interface.
Change the configuration parameters and click on the ൏SAVE൐ button;
Double click Conftool icon. The Configuration Tool interface will open in the default
A new window will open requiring the name of the configuration (maximum of 22
Web browser;
characters including ̴, -, 0-9, a-z and A-Z);
Click on the <RECEIVED> button. A new window will open;
Click on the ൏SAVE൐ button once again to save it on the PC;
Type IP address of the equipment and click on the <OK> button. An RPV-like
Click on the ൏FINISH൐ button to go back to the main screen of the Configuration Tool.
configuration interface will open. It is possible to check the configuration parameters as
if user were on-line with the equipment;
Change the configuration if necessary;
Click on the <SAVE> button. A new window will open and require a name for this
configuration. Type the configuration name (maximum of 22 characters including ̴, -, 0-
1.3.8 Deleting a Locally Stored Configuration
9, a-z and A-Z); To remove a configuration that is locally stored, follow these steps:
Click on the <SAVE> button once again to save the new configuration on the PC; Select the name of the stored configuration to be deleted and click on the ൏REMOVE൐
Click on the <FINISH> button to go back to the main screen of the Configuration Tool. button;
The configuration will be on the list of locally stored configurations. The message Remove this item will be shown. Click on the ൏YES൐ button to remove the
The configuration window will appear in the Configuration Tool. The user can choose to configuration.
edit the configuration again, store it or transmit it to the RPV.
It is possible to save the configuration with the same name as an existing one. However,
the existing configuration will be overwritten.
1.3.9 Creating a Configuration Report
To create the configuration report, follow these steps:

180 RPV311-TM-EN-11.1
RPV311-TM-EN-11.1 179
RPV311 Chapter 12 – RPV Tools Chapter 12 – RPV Tools RPV311

Select the name of the stored configuration to be deleted and click on the ൏REPORT൐
button; towers between the ends of the line are defined, the results are georeferenced and a
An HTML Web page will open with a list of all configuration parameters. KML file is created for viewing through Google Earth.
The report consists of a header with the following information: owner, identifier, and
location of the equipment, revision number, date and time of the last configuration
1.4.2 The Power Line Configuration
change.
To print this report, click on the ൏PRINT൐ button.

Before running the fault locator algorithm, it is necessary to establish the power line
1.3.10 Transmitting a Configuration configuration. The basic information related to the power line must be described in an
To be able to transmit an equipment configuration, the user must be connected to the XML file with the following fields:
equipment by an Ethernet or Modem interface.
Select the name of the stored configuration to be sent and click on the ൏TRANSMIT൐
button;
Power line file configuration
Type the IP address of the equipment that will receive the configuration;
Type the description of the configuration changes and click on the ൏OK൐ button;
<length>nnn</length> Nominal length of the line as the owner of the
Type the user name and the password to configure the equipment; line claims (in kilometers)
Click on the ൏OK൐ button to transmit the configuration and to go back to the main
screen of the Configuration Tool. <k1>nnn<k1> Is the coefficient related to the length of the
line, represents the actual length of the cable
of the line.
This value can be adjusted using data of faults
1.3.11 Exporting a Configuration subsequent to the commissioning
It is possible to export a configuration to the computer. To export a configuration, do
the following: <k2>nnn<k2> Is the coefficient related to the light speed
Select the name of the stored configuration to be exported and click on the ൏EXPORT൐ factor
button;
Type the name of the configuration file (.txt extension) and choose the storage location, <terminal_a>Location,Identifier,Line</termi STATIONID,DEVICEID and the terminal
nal_a> identifier
then click on the ൏SAVE൐ button.
The configuration file will be saved in the chosen location and can be imported into the
<terminal_b>Location,Identifier,Line</termi STATIONID,DEVICEID and the terminal
RPV Tools.
nal_b> identifier

<tower id=”X” name=”NAME”> Is the identification of the towers and their


1.4 TW Fault Locator geographic coordinates. This information must
<latitude>nnn</latitude> be provided by the user

1.4.1 Description <longitude>nnn</longitude>

<distance>nnn</distance>
The TW Fault Locator is a tool that uses the records of the traveling wave front signals
at two ends of a transmission line to locate a fault in this line. </tower>
To record traveling waves in RPV it is necessary to install the appropriate acquisition
module, RA333. The records of traveling waves at both ends of the line should be
The geographic coordinates are optional and must be provided by the user.
transferred of RPV's to the specific area of records in the user's computer that will run
The technical note "Traveling Wave Fault Locator (NT0802)" shows how the coefficients
the Fault Locator software.
K1 and K2 are calculated.
By using a graphic interface, based on the distance between terminals A and B and on
A model of the power line configuration file is created in the directory
the time stamp of the wave front, and by running the algorithm, the fault can be
C:̳RPV̳faultlocator̳conf of Windows after the RPV Tools installation. The power line
located. If unable to locate the fault automatically by the software, it is necessary to use
configuration model is shown below.
a graphical tool to identify the times of the wave front of each terminal manually. Of the
time identified it is possible run the fault locator graphically. If the locations of the
182 RPV311-TM-EN-11.1
RPV311-TM-EN-11.1 181
RPV311 Chapter 12 – RPV Tools Chapter 12 – RPV Tools RPV311

൏?xml version="1.0" encoding="UTF-8"?൐


൏line൐
൏length൐100൏/length൐
൏k1൐100൏Ȁk1൐
൏k2൐1൏Ȁk2൐
൏terminal ̴ a൐LOCATION,IDENTIFIER,LINE൏Ȁterminal ̴ a൐
൏terminal ̴ b൐LOCATION,IDENTIFIER,LINE൏Ȁterminal ̴ b൐
൏Ȁline൐
Make a copy of the file and edit it with the parameters related to the power line to be
monitored.
Below is an example of the power line configuration:

൏?xml version"1.0" encoding="UTF-8"?൐


൏line൐
൏length൐248.5993൏Ȁlength൐
൏k1൐248.28൏Ȁk1൐
൏k2൐0.98658൏Ȁk2൐
൏terminal ̴ a൐substation1,RPV311-TW,term ̴ a൏Ȁterminal ̴ a൐
൏terminal ̴ b൐substation2,RPV311-TW,term ̴ b൏Ȁterminal ̴ b൐
൏towers൐
൏tower id"0" name="Pórtico substation1"൐
൏latitude൐-13.82689൏Ȁlatitude൐ Figure 78: Fault Locator Interface
൏longitude൐-48.29898൏Ȁlongitude൐
൏distance൐0൏Ȁdistance൐
൏/tower൐ A Selection of the power line to be checked. The lines available are these with XML files
൏tower id"1" name="T1"൐ already configured by the user. To appear in the list, the files must be stored the directory
൏latitude൐-13.82665൏Ȁlatitude൐ C:\RPV\faultlocator\conf.
൏longitude൐-48.29866൏Ȁlongitude൐
൏distance൐43.7൏Ȁdistance൐ B Terminal identification of each end of the line and the list of the traveling wave records
൏/tower൐ of each terminal. Each record on this list is named with a time stamp. User must select
... one time stamp of each terminal that matches the same event. When selecting the record
൏tower id="581" name="Pórtico substation2"൐ one terminal, it automatically selects a record with the same timestamp at the other
൏latitude൐-15.923331൏Ȁlatitude൐ terminal.
൏longitude൐-48.175103൏Ȁlongitude൐
൏distance൐248593.3൏Ȁdistance൐ The TW Fault Locator Software considers the time zone information in the COMTRADE
൏Ȁtower൐ file’s name, in order to set the register of both sides of the transmission line at UTC Time
൏Ȁtowers൐ for calculations. Therefore, lines that go beyond two diferent time zones will not canse
൏Ȁline൐ the algorithm to miscalculate the fault location.

C Selector of sensitivity for the fault location.

D Buttons for fault location, where:


1.4.3 The Traveling Wave Fault Location
The ൏LOCATE൐ button allows user to run the fault location algorithm;
The ൏VIEWER൐ button allows user to open the manual graphical tool to locate the time
The graphical interface must be open, double click the Fault Locator icon on the of the wave fronts in each terminal;
desktop. The ൏LOCATE BY CHART൐ button allows user to use the wave front times located in the
The Fault Locator interface is shown in Figure 78. graphical tool, to run the algorithm of fault location;
The ൏KML൐ button allows user to create a KML file, only if the tower’s geographic
coordinates have been provided.
184 RPV311-TM-EN-11.1
RPV311-TM-EN-11.1 183
RPV311 Chapter 12 – RPV Tools Chapter 12 – RPV Tools RPV311

E Location of the fault of terminals A and B.


൏SHIFT൐ ൅ ൏LEFT/RIGHT ARROW൐ position the cursor each 50 μs;
൏CRTL൐ ൅ ൏LEFT/RIGHT ARROW൐ position the cursor each 100 μs;
൏HOME൐ position the cursor at the record beginning;
In order to locate a fault, select a power line configuration and then, select one record
൏END൐ position the cursor at the record end;
of terminal A and the related record of terminal B is automatically selected. The user
can manually exchange the terminal B record.
To manipulate the graphic windows, use the following buttons of the software:
Click on the ൏LOCATE൐ button to run the fault location algorithm. If it is possible to
locate the fault automatically, the result is the distance between both terminals A and B
and the estimated fault location, and a "Success fault location" message is declared.
TW Fault Locator software’s buttons
If some problem occurs in the fault location, a "Fault not be locate" message will
appear. Possibly the selected records are not about the same event or the wavefront is
The <HOME> button displays the graphic in the format of the initial display
less than the threshold set. In this case change the threshold levels of the location and
click the ൏LOCATE൐ button again.
The <BACK> and <FORWARD> allow the zoom graph to navigate the front
If the fault is still not located, use the graphical tool to identify the times of the wave and rear positions
fronts in the two terminals manually.
To use the graphical tool, click on the ൏VIEWER൐ button. Each terminal of the The <PAN> button allows manual dressing of the graphic
transmission line has a record of traveling waves, which are simultaneously displayed in
the graphics window. In each record it is necessary to position the cursor at the exact The <ZOOM> button allows selection of the area of the graph to enlarge
moment of the beginning of the wave front, as shown in Figure 79.
The <SAVE> button allow saving in an image file

The information presented for each of the records is:


Date and time stamp of the record beginning;
Terminal identification;
Voltage values of the phases A, B and C at the moment when the cursor is positioned;
Time stamp when the cursor is positioned.

It is possible to only one open window graphics for viewing. If the viewer is open and
runs a new location for another set of records it is necessary to close the preview
window and open it again.
After manually setting the times of the wave fronts, it is possible to use the ൏LOCATE BY
CHART൐ button to find the fault, of the time stamps marked on the graph.
While the fault location algorithm is running, no other time stamps can be selected.
The graphical tool can also be used to confirm the results of automatic fault location.
If the user provides the tower’s geographic coordinates in the .tw file, the program
enables the ൏KML൐ button. Click on this button and a KML file is created to be viewed
on Google Earth. In addition, the geographic coordinates of the fault are shown on the
graphic interface.

1.5 GOOSE Configurator


Figure 79: Graphical tool of Fault Locator interface
1.5.1 Description
To move the cursor with the keyboard, first click on the corresponding graph with the
The GOOSE Configurator is an application that combines elements of a configuration
left mouse button and navigate the graph, as follows:
GOOSE message file of the IED with the digital channels of the RPV.
Right mouse button position the cursor on the local clicked;
The software allows the user to receive, edit, and transmit a configuration of the RPV.
൏LEFT/RIGHT ARROW൐ position the cursor each 1 us;
186 RPV311-TM-EN-11.1
RPV311-TM-EN-11.1 185
RPV311 Chapter 12 – RPV Tools Chapter 12 – RPV Tools RPV311

1.5.2 Interface Starting a Configuration


To perform a configuration, it is possible to either edit a pre-existing configuration
on the equipment, create a new configuration,or open a file containing a pre-
When installing the RPV Tools, it creates a desktop icon for quick access. The existing configuration.
configuration interface can be accessed directly via this icon.
To access the configuration interface, do the following: x Receiving an equipment configuration
1. Click Start ൐ Programs ൐ Accessories ൐ Command Prompt; To receive a configuration file of the RPV, access COMMUNICATION ൐ RECEIVE. A window
2. At Prompt, access C:\RPV\goosemon̴config\resources; will open and then the user must enter the RPV IP address and click on the ൏OK൐
3. Run the Goosemon̴Config.exe file and the application will open. button to confirm. This prompts a login password that can be obtained of the Web
The initial screen of the GOOSE Configurator application is shown in Figure 80 and has Interface of the RPV in the configuration of the access control. This password can be
the following characteristics: changed through a new configuration in the Web Interface of the RPV.
When receiving the configuration of RPV, a temp.cfg temp file is saved in the directory
A The GOOSE's list the configuration files loaded. These files are divided into GOOSE
config files. It is recommended that the user save that file with a different name
CONTROL BLOCK, which are composed of datasets with binary elements that can be
because every time a new file is received, the previous file will be overwritten.
associated with the digital channels of the RPV.

B The Digital channel of the RPV has the 320 binary magnitudes of the RPV, which can be x Creating a new configuration
associated to GOOSE messages. These inputs shall be identified in the RPV.
To create a new configuration access: FILE ൐ NEW CONFIGURATION. This will create a
C The buttons allow association or disassociation of a GOOSE CONTROL BLOCK to a digital template configuration file, called TEMP.CFG. This file will be saved in the directory
input of the RPV. CONFIG_FILES, and can be opened and/or modified.
When saving changes to file TEMP.CFG, it is recommended that the user save it with a
D The STATUS indicates the status of each operation.
different name because every time a new file is received, the previous file will be
overwritten.

x Open a configuration

To open a configuration file that has been previously made, access File ൐ Open
Configuration. Select the location where the file is stored and click on the file to open it.

x Remove links of the configuration file

To remove links of the configuration file, access Tools ൐ Remove All Configuration Files.
All links will be removed.

Edit Configuration

x SCL File Input


To select the SCL input file access File ൐ Select SCL. A screen will open to perform
configuration of the SCL file, which is shown in Figure 81.
The input files can be SCD or CID and contain the IED GOOSE message configurations,
according to IEC61850.

Figure 80: Initial screen of the GOOSE Configurator

1.5.3 Configuration

188 RPV311-TM-EN-11.1
RPV311-TM-EN-11.1 187
RPV311 Chapter 12 – RPV Tools Chapter 12 – RPV Tools RPV311

Figure 81: Screen to configuration on the SCL file

The ൏OK൐ button is to confirm the changes in the files list. The ൏CANCEL൐ button is to
cancel the changes. The ൏ADD FILES൐ and ൏REMOVE FILES൐ buttons are used to add or
remove a file of the list of IED configurations, loaded onto the initial screen.
When a file is removed, it is necessary to know that the configuration files are not
modified. It is not possible to view the GOOSE CONTROL BLOCK, associated with an input if
the file is removed, however the configuration of the digital input of the RPV remains
active. Figure 82: Association of a GOOSE Control Block with a digital input

x Association between GOOSE messages RPV digital inputs


To associate a GOOSE Control Block to a digital input, do the following: x Filter parameters
Initially select an element GOOSE binary of the GOOSE Control Block list, obtained of To edit the filter parameters, access TOOLS ൐ FILTER PARAMETERS. A screen will open and
the SCL files generated by IED; show the parameters that can be changed, shown in Figure 83.
Select one of the 320 RPV digital inputs according to GOOSE; The parameters that can be changed in the configuration files are:
Click on the button to make association between the GOOSE message and the
previously selected RPV digital input; Ethernet: indicates the Ethernet interfaces used for capture;
The message indicating the operation will show in the status area; VLAN: enables the VLAN filtering;
To remove the association click on the disassociation button.; MAC Address filtering: enables MAC address filtering;
The user can only associate a GOOSE CONTROL BLOCK with a digital input if the data is Filtering by identifying the application: enables the filtering by identifying the
compatible with the permitted limits on GOOSE. An example of a combination of application.
GOOSE CONTROL BLOCK with a digital input.

It is possible to associate a GOOSE CONTROL BLOCK with a digital input only if the data is
compatible with the permitted GOOSE message data. An example of association of a
GOOSE CONTROL BLOCK with a digital input is shown in Figure 82.

190 RPV311-TM-EN-11.1
RPV311-TM-EN-11.1 189
RPV311 Chapter 12 – RPV Tools Chapter 12 – RPV Tools RPV311

View the Configuration Files


To view the contents of the configuration file to be sent to the equipment, access
TOOLS ൐ VIEW THE CONFIGURATION FILES. A new window will open only for reading
of data, it cannot be modified.

Figure 83: Filter parameters

Transmission of the Configuration

x Transmitting the configuration


To transmit the configuration to the RPV access COMMUNICATION ൐ TRANSMIT. A window
will open for user to enter the RPV IP address, and then click on the ൏OK൐ button to
confirm.

x Saving changes in the configuration file


To save changes in the configuration file, access FILE ൐ SAVE THE CONFIGURATION.
The user is recommended to save files received of the RPV with name different of that
of the temp.cfg that is saved when creating a new configuration.

1.5.4 Additional Tools

Setting the Colors


To set the colors used on the GOOSE Configurator, access TOOLS ൐ SETTING
THE COLORS. The colors may indicate:

x Currently selected item;


x Existence of link between SCL and the setting;
x Bit set to an unknown SCL file;
x Item that must be selected or not;
x Line that contains the original SCL filename
192 RPV311-TM-EN-11.1
RPV311-TM-EN-11.1 191
RPV311 Chapter 13 – DR Manager

RPV311
By right-clicking on the equipment, the user can update the State of the equipment,
through the option "Refresh", or access the equipment web configuration page,
through the option "Access Web Configuration".
Distributed Multifunction Fault Recorder The records highlighted yellow are stored only in equipment memory which can be seen
each time Refresh occurs.
Green highlight represents the records that have already been downloaded and then
Chapter 13: Software – DR Manager saved in the database in the respective directory including data of the equipment within
the COMTRADE directory.
The DR Manager is a tool that allows data management of the equipment. If communication is lost with the equipment, only records in green will be displayed.
Download of records can be done automatically or manually. In the manual case either
a few selected records or all records can be downloaded.
Requirements
The DR Manager Installer works on Microsoft Windows and needs .NET 4 (client profile)
to run. It also depends on a database engine, PostgreSQL 9.3. The user must have
administrative rights to install the software.
The software is supported on Windows 7 and 10.
This manual refers to DR Manager version 09A00.
Figure 85 - Downloaded records

Software Description 2.1.2 Alarms


Alarms tab shows all registered equipment alarms, including information of "Time
2.1 DR Manager Main Window Quality" and "firmware version".

2.1.1 System Monitor

Figure 86: Alarms tab


Figure 84 - DR Manager main window
There are four background colours:
The software main tab is called System Monitor. All the substation and RPV311 White: Communication not yet established with the equipment.
configured in the software are listed in a tree menu on the left corner of the window. Yellow: Alarm(s) active
The top level of the tree shows the user created facilities and the equipment installation Green: No alarms
on the second level. Orange: Communication lost with the equipment.
After clicking on the device with the left mouse button, the equipment records will be
loaded and displayed in tabs depending on the type of record selected (Fault,
Disturbance, Traveling Wave, Steady-State or Sequence of Events). This information is The user can check details on the alarms and their states by clicking the equipment’s
updated after a Refresh. name.

194 RPV311-TM-EN-11.1
Chapter 13 – DR Manager RPV311 RPV311 Chapter 13 – DR Manager

2.1.3 Auto Polling ƒ Compares the local configuration file with the respective RPV311 configuration
file.

With the Auto Polling tab the user can check the number of files that have been
downloaded and the number of files waiting to be downloaded. x Close the software with the "Exit" option.
When active, the software will check which records have not yet been saved and will
download them. Records will only be downloaded automatically from equipment with
Auto Polling enabled. 2.2.2 Settings Menu
A background colour indicates that the equipment is being checked. In the Settings menu, the user can:
During the download, the data is updated on the screen as the records are transferred.
x Create, edit and remove Installations;
x Create and remove Devices;
x Transmission line configuration for TW fault location;
2.1.4 Download Modes
x Create, edit and remove contacts for e-mail and fax sending;

x Automatic download: x Create, edit and remove Warnings to be sent.


Signing up RPVs to the DR Manager:
The DR Manager sorts the devices in the follow manner:
The procedure to activate the Auto Polling can be seen in the Settings Menu 2.2.2. First, it is necessary to create what is called Installation, that can ben, for example, the
substation where de RPV is installed. Then the user has to register the RPV and assign
x Manual Download: each of them to an installation by creating what is called Device.
Below mentioned is the procedure to create Installations and Devices.
Selected records:
Select the records required, and click the button “Get Selected”; 1.1.1.1 CREATING INSTALLATIONS
The process to create a new Installation is:
All records: 1. Click <SETTINGS> menu and then click <INSTALLATIONS>;
Click "Get All". 2. Click <NEW> to create. Type the Installation's name and description and then
press <OK>.
Double click on the downloaded record to open (it is necessary to have a software to The user can view the list of registered substations and add, edit, or remove a
open .zic files already installed). substation. Substations can only be removed without any equipment being associated.
To close this window use the close button in the top right, or use File >Exit.
A confirmation message will be shown after closing.
1.1.1.2 CREATING DEVICES

2.2 DR Manager Settings The user can view the list of registered equipment, add, edit, or remove some
equipment. Equipment can only be removed when there is no transmission line
DR Manager presents some settings that user can access through the menu bar. These associated and if the Auto Polling is disabled. bellow
settings are shown below.
The process to create a new device is:
2.2.1 File Menu x Click <SETTINGS> menu and then click <DEVICES>;
In the File menu, the user can: x Click <NEW> to create.
x Open COMTRADE folder; x At <HOST>, type equipment's IP address;
The Open containing folder option will open the default register's downloaded folder. x Choose device installation in the Installation list;
By default, the folder is C:\RPV\Records.
x Click at <Get Info> and then press <Ok>.
Generally, User name and Password are not required to download DFR registers. If
x , Refresh All Devices. required for the application, then type Users name and password for administrator user
of the equipment (GE’s default, user name is admin and password is 1234). The figure
ƒ Refresh the list with COMTRADE files (but does not download them); below shows the Device configuration window.
ƒ Refresh Alarms tab;
ƒ Check alarms to send email/fax when new ones are exist;
196 RPV311-TM-EN-11.1
RPV311-TM-EN-11.1 195
Chapter 13 – DR Manager RPV311 RPV311 Chapter 13 – DR Manager

Figure 87: Device window


There are two parameters to be configured by the user:

Enable Auto COMTRADE Download: When enabled, the unit will be part of the Auto
Polling process, where records not yet saved are automatically downloaded.
Enable Auto Refreshing: When enabled, the unit will be part of the process of Auto Figure 88- Transmission Line configuration
Refresh, where the equipment state will be updated automatically during the process. In order to add and edit a transmission line, the user must:
The user can change the equipment host address, and enable or disable the "Enable 1. Select the installation A at one terminal of the line;
Auto COMTRADE Download" and "Enable Auto Refreshing". At the end of the editing, 2. Select the device A that is monitoring the line in installation A;
the software automatically communicates with the equipment in order to upgrade the 3. Select the installation B at the other terminal of the line;
name and location information. 4. Select the device B that is monitoring the line in installation B;
If the equipment is associated with any transmission, a message will be shown to the 5. The field Section is used to select how many sections the line has, i.e. how
user at the beginning of the Edit. many different propagation constants K (used when the line has overhead an
After the closing the ‘Device’ window, the equipment updates are registered. underground sections)
6. Enter the line lengths and K for each section of the line. Refer to Chapter 7,
section 6 TWFL in Mixed (Hybrid) Lines for further information on the constant
1.1.1.3 TRANSMISSION LINES (AUTOMATIC FAULT LOCATION)
K.
The transmission line window configures the parameters necessary to execute the 7. Enter the Threshold used in the TWFL Basic method. Refer to 2.3 Automatic
Traveling Wave Fault Location algorithm on the TW high acquisition frequency records. TW Fault Location for further information.
8. Enter the names of the Current Circuits A and B. As it is configured in the
On this menu the user can view the list of the registered lines, add, edit, or remove any RPV311, Figure 89 . These circuit names are used to identify the correct Fault
transmission line. chart used in the Advanced TWFL Method. Refer to TW Fault Location
Methods 2.3.3 for more information.

198 RPV311-TM-EN-11.1
RPV311-TM-EN-11.1 197
Chapter 13 – DR Manager RPV311 RPV311 Chapter 13 – DR Manager

2.2.3 Polling Menu


In the Polling menu, the user can:
x Select software polling to be manual;
x Select software polling to be automatic;
Figure 89: Current Circuit name
In the manual mode, both the Refresh of the COMTRADE list and the download of
1. Enter the names for the terminals A and B. As configured on the TW screen in register has to be commanded by the user.
the RPV311, see below. In the automatic mode, the software will download the registers and refresh the
COMTRADE list automatically according the parameters set on the
Configuration>Polling menu. Also, each device has to have those option enabled on the
Settings>Device menu.

2.2.4 Tools Menu


Figure 90: Terminal name configuration
1. Finally, enter the name of the transmission line. In the Tools menu, the user can:
The field ID shows the ID of the MODBUS transmission of the fault location. Further
information in 2.3 Automatic TW Fault Location.

1.1.1.4 CONTACTS
This menu configures the contacts to which the RPV can send emails notifications.
On this window the user can view the list of registered contacts, add, edit, or remove
any contact. During the removal of any contact, if any association with any warning, a
confirmation message will be displayed to the user.

1.1.1.5 WARNINGS
On this screen the user can view the list of warnings, add, edit or remove any warning.
By setting the warning the user can select which contact will receive the alarms.
It is possible to configure which events will make the DR Manager send warning email,
according to the following settings: Figure 92 - Tools menu

x View software alarms and alarms history;


x Calculate Traveling Wave fault location;
x Execute the GOOSE configuration tool Chapter 12, Section 1.5 GOOSE
Configurator;
x Execute the RPV311 Configuration tool and manage the software plugins
x View records history;
x Search for records (with date filter);
x View records report.

1.1.1.6 SOFTWARE ALARMS AND HISTORY


Figure 91- Warning menu
The Alarm window shows active alarms and the alarm history.
Send email when the RPV311 being monitored have active alarms, when a fault is found The Active Alarms tab displays the alarms still on. Examples of these alarms are:
in the COMTRADE files. In case a fault has been identified it is possible to attach the Equipment not Ready, Slot or Enlace Problem, Equipment not sync, primary power not
COMTRADE file of that fault to the email.
200 RPV311-TM-EN-11.1
RPV311-TM-EN-11.1 199
Chapter 13 – DR Manager RPV311 RPV311 Chapter 13 – DR Manager

found and communication error. The History tab displays alarms that came back to off
The maximum number of records displayed is configured in the option Display
state.
Downloaded
The list is updated by the Refresh command.
COMTRADES Limit on the Polling configuration window.

1.1.1.12 SEARCH FOR RECORDS


1.1.1.7 TRAVELING WAVES FAULT LOCATION

To locate the fault in the transmission line using the Traveling Wave method, the user In this option user can use filters to search for specific downloaded records of a selected
must: DFR.
1. Select the transmission line, enabling the other fields for editing; The search can be made taking into account:
2. Select the COMTRADE TW files of both terminals of the line. Note that when ƒ Selection of one or more equipment;
you select the Transmission Line, the directory selection window will open ƒ Period start and/or end of the occurrence of the registry;
directly the register folder in C:\RPV\records. ƒ Reason of occurrence;
3. Click Locate to run the algorithm and locate the fault. ƒ Record type:
ƒ All (This will get all types of records);
ƒ Fault recorder: records of short duration, with two advanced search options:
Triggered and Continuous.
1.1.1.8 GOOSE CONFIGURATOR ƒ Disturbance recorder: records, with two advanced search options: Triggered
and Continuous.
This option opens the GOOSE configuration software described in Chapter 12, Section ƒ Travelling Wave recorder: records of travelling wave
1.5 GOOSE Configurator. The GOOSE configuration software is responsible for the ƒ Steady-state: measuring records continues with four advanced search options:
association of the SCL file of the sending IED with the RPV311 GOOSE inputs. Average series, Harmonics, Flicker PST and PLT.
ƒ SOE: records of sequence of events.

1.1.1.9 CONFIGURATION TOOL


1.1.1.13 RECORDS REPORT
This option open the Configuration Tool described in Chapter 12, section 1.3
Configuration Tool. This software is responsible for the management of the several
RPV311 configurations and offline configuration. This option displays, for the selected equipment, month and year, the number of
downloaded registers. They are separated by register type and displayed as a Pie chart
in the records report window. Number of records percentage are displayed by default,
Note: The Configuration Tool access through the DR Manager works only with
and if the user passes the mouse over the register type displayed at the bottom of the
firmware versions from 13A02 onwards. To deal with firmware version before that,
the RPV Tools (Chapter 12 Software – RPV Tools) should be used. window, the number of records are displayed in the record's type region on the pie
chart.

1.1.1.14 RECORDS REPORT


1.1.1.10 PLUGINS MANAGEMENT
This menu displays a chart with the percentage number of each kind of register
This menu is used to install the plugins that the Configuration Tool mentions above uses downloaded.
to work with offline configurations. Each firmware version requires a separate plugin to To view the chart you must select a period of time, select a device and click the button
work offline. "Report". That will display the graph showing the percentages of each type of record.
Hover the mouse cursor over the graph to see the number of records saved, as shown
in the figure below:
1.1.1.11 VIEW RECORDS HISTORY

In this option the user can view the records download history, sort by download date,
by registry and by duration time.

202 RPV311-TM-EN-11.1
RPV311-TM-EN-11.1 201
Chapter 13 – DR Manager RPV311 RPV311 Chapter 13 – DR Manager

Figure 93: Percentage of records chart

It is possible for certain periods to have no downloaded files available so no graph will
be loaded on the interface. Figure 94: Polling configuration
Polling Configuration fields description:
COMTRADE Directory: directory path where the new records are downloaded and
2.2.5 Configuration Menu where the fault locator calculation searches.
In the Configuration menu, the user can: Display Downloaded COMTRADES Limit: maximum COMTRADE records already
downloaded that will be displayed on the screen
x Configure software polling;
Display Available COMTRADE Age (day): limit, in days, of downloaded records that will
x Configure the coefficients used in TW calculation be fetched and displayed on the screen.
x Configure e-mail. COMTRADE DAT File: format in which the COMTRADE file will be saved.
x Choose which Browser will be used to open the Configuration Tool Start Auto Polling on Init: starts Auto Polling automatically by the application.
Automatic Fault Location: performs the fault location calculation after the COMTRADE
file refresh.
1.1.1.15 POLLING Auto Refresh Interval (min): interval, in minutes, that anautomatic update of the data
of the device will run when the Auto Polling is active.
On the Polling Configuration menu, the user can configure the COMTRADE polling,
Auto COMTRADE Polling Interval (min): interval, in minutes, that will be held the
refresh and storage of files. The Figure below shows the Polling configuration window.
automatic download of COMTRADE files.
Auto Polling COMTRADE Age (day): maximum age, in days, of records that will be
downloaded automatically in Auto Polling. For example, if a register was made 5 days
ago and the DR Manager is started today and the Auto Polling COMTRADE Age (day) is
set to 4 (or 1, 2 or 3) the register will not be downloaded during the auto polling.
Equipment Request Limit: limit of records that will be requested from the equipment in
each query.
Retrieve Fault: When selected, automatically downloads the short duration records,
both triggered and continuous.
Retrieve Disturbance: When selected, performs the automatic download of the slower
disturbance records, both triggered and continuous.
Retrieve Travelling Wave (TW): When selected, performs the automatic download of
the travelling wave records.
Retrieve Steady State (SS): When selected, performs the automatic download of the
204 RPV311-TM-EN-11.1
RPV311-TM-EN-11.1 203
Chapter 13 – DR Manager RPV311 RPV311 Chapter 13 – DR Manager

continuous measurement records.


Retrieve Sequence of Events (SOE): When selected, performs the automatic download 2.3.1 Description
of After the fault location calculations are performed, the distance to fault is displayed on
the sequence of events records. the software interface and it is made available via MODBUS communication according
to the MODBUS IDs configured on the Transmission Line configuration menu and the IP
If modification on this windows is made, a message will be displayed asking the user to address configured in the windows Ethernet properties of the DR Manager computer.
restart the program.
MODBUS Fault Location Transmission
1.1.1.16 COEFFICIENTS Whenever a TW fault location is performed the DR Manager will provide three separate
The TW fault location algorithm uses a few coefficients during the fault location 16-bit MODBUS registers. The registers are described below:
process. The DR Manager default coefficients shall not be altered unless advised by GE
Grid Solutions. Description MODBUS Observation
MODBUS identifier configured on the Transmission Line
1.1.1.17 EMAIL Register_1 30001 menu used to identify which transmission line the current
fault location refers to.
Allows the configuration of the email accout that the DR Manager will use to send
As the fault location is split into 2x16-bit register. This
emails. Register_2 30002 register carries the LSBs (least significant bits) of the 32-bit
register.
1.1.1.18 BROWSER Second part of the fault location. This register carries the
Register_3 30003
MSBs (most significant bits) of the 32-bit register.
This option allows the user to choose which Browser will be used to open the
Configuration Tool. The MS Internet Explorer and the Mozilla Firefox are supported.
In order to achieve the actual fault location, it is necessary to combine the 2 fault
location registers (30002 and 30003) into a single 32-bit value. The register 30003 is a
2.2.6 Help Menu decimal representation of the 16 most significant bits of the complete 32-bit register
which contains the fault location and the register 30002 is a decimal representation of
x About the 16 least significant bits of the 32-bit register. The combination of them will result in
The About screen shows information on the software such as: software version, the actual fault location in meters.
copyright ans memory usage. Below is the necessary operation to combine both fault location registers:

Actual fault location in meters = ((Register_2 & 0XFFFF) | (Register_3 << 16))

When consecutives fault locations are found for the same line, the DR Manager will
display all the fault locations as list. And these locations are going to be sent via
MODBUS with a 1-minute time interval between them.

2.3.2 Switch-on to Fault


When a short circuit occurs right after the circuit breaker closes, the behavior of the
Figure 95: About window
traveling waves become different from regular faults, mainly because the circuit
breaker itself can create traveling waves that can be misinterpreted as traveling wave
from the fault and it may turn the fault location calculation more difficult. To avoid that,
the DR Manager analyses both the waveform/fault and the TW COMTRADE records to
2.3 Automatic TW Fault Location first identify that a switch-on event occurred and then to apply a special fault location
DR Manager features an automatic TW fault location capability, where the DR Manager algorithm. Additionally, special conditions need to be met for the switch-on to fault
automatically downloads the COMTRADE registers from both line ends, calculates the (SOTF) events to be located automatically:
fault location, displays it on the software interface and make it available via Ethernet
MODBUS. ƒ The fault shall be at least 6 km away from both line terminals.
ƒ The transmission line maximum length shall be 2000 km.
ƒ The fault location for switch-on events will not work for mixed (hybrid) lines.
206 RPV311-TM-EN-11.1
RPV311-TM-EN-11.1 205
Chapter 13 – DR Manager RPV311 RPV311 Chapter 13 – DR Manager

ƒ There needs to be a corresponding waveform recording for each event


(Chapter 4: Configuration. 10. Fault Recorder). 2.4 Polling and Refresh
Even meeting all the conditions above, SOTF events are rare and difficult to interpret
automatically, thus, the DR Manager will indicate on its interface whenever an event is 2.4.1 Refresh
characterized as a switch-on so the user can be cautious and double check the
recordings. The equipment refresh option performs the following actions:
x Update of the list of records on the home screen;
x Updating the status of the equipment;
2.3.3 TW Fault Location Methods x Update of Alarms (Alarms tab);
x Verification of alarms for sending e-mail/fax;
The DR Manager uses two calculation methods for TW fault location. They are called x Check the settings (local and remote).
“Basic” and “Advanced”. The method used for each calculation is identified on the DR
Manager interface, as shown in Figure 96. The two methods are described below: This refresh may occur in the following situations
x Basic Method x "Refresh" option from the equipment menu, access by right clicking on the
substations equipment tree in the System Monitor. This option will update
Uses a threshold configured on the Transmission Line menu, which is a percentage x the data of the selected equipment;
value of the full scale of the register, to identify the beginning of the traveling wave
x "Refresh All Devices", access through the File menu. This option will update all
created by the fault and, consequently, to find its timestamp in order to use in TWFL
registered equipment;
calculations. This method uses only the high frequency COMTRADE files acquired by the
RA333 units locate the fault. x "Auto Refresh". This option will update only the information of configured
equipment.

x Advanced Method To configure the Auto Refresh:


1. For each device the the box Enable Auto Refresh on the Settings>Device
This method uses both the fault register (waveform at 50/60Hz) and the TW register menu;
(high frequency register) to identify the fault location. The fault register is analyzed 2. To set the update interval change the field "Auto Refresh Interval " on the
using a high-pass filter in order to find the time window that contains the fault begging, Configuration>Polling menu;
then that time window is used in the TW register to enhance the location of the correct 3. To activate or deactivate the Auto Refresh, access the Polling menu and
time stamp for the fault. As the time window to track the fault waveform in narrow choose between Manual or Auto options;
down using this method, various system noises are eliminated from the calculations 4. To ensure that the software starts with the Auto Refresh option active, check
increasing significantly the chances to automatically find the fault. the box "Auto Polling on Init" on the Configuration>Polling menu;
The refresh action also happens during the:

x Start of application execution;


x Change in list of substations;
x Change in the equipment list.

After communication with the equipment, the software checks if any information was
changed and updates the information as follows:
x Interface: System Monitor equipment tree tab and equipment lists in the
other tabs;
x Database;
x Information of the Transmission Line configurations for each device;
Figure 96: DR Manager TWFL methods
x Name of the directory where the new records will be downloaded.

208 RPV311-TM-EN-11.1
RPV311-TM-EN-11.1 207
Chapter 13 – DR Manager RPV311

2.4.2 Polling
The polling routine is responsible for performing the automatic download of records
from each equipment.
Configure the Auto Polling as follows:
1. For each equipment if you want to have Auto Polling functionality, "Enable
Auto COMTRADE Download " should be enabled.
2. To set the update interval, the field "Auto Polling Interval" must be changed in
the Polling configuration screen.
3. To activate or deactivate the Auto Polling, access the menu Polling Auto, to
activate, and Polling > Manual, to disable.
4. To ensure that the software starts with the Auto option active Polling, select
the field "Auto Polling on Init" on the Polling configuration screen
5. COMTRADES records will only be downloaded that are younger than the
period entered in the field “Polling COMTRADE Acts ", in Polling configuration
screen,
6. Only the types of COMTRADE records configured through the fields "Retrieve
..." in the Polling configuration screen of will be downloaded.
7. To run the fault location algorithm automatically after downloading a
COMTRADE record, select the field "Automatic Fault Location", in Polling
configuration screen.
8. Once everything is configured, the records will be downloaded to the directory
"COMTRADE Directory "/Records.

When the Auto Polling is set to on it will run during the following occasion:
1. At system start up;
2. When closing the Device window.

Enable Automatic Polling by clicking the menu Polling>Auto;


If the Auto Polling is active, each time interval is set in "Auto Polling COMTRADE Interval
".
If the execution time of the Polling process exceeds the polling interval configured, the
next polling procees will be ignored until the pending execution ends.

RPV311-TM-EN-11.1 209
RPV311 Chapter 14 – Communications

RPV311
Distributed Multifunction Fault Recorder
Chapter 14: Communications
This chapter provides detailed information about the communication options and how
to configure them

Figure 97: Electrical and optical Ethernet inputs


Communication Interfaces
The RPV311 has the following communication interfaces:
To minimize EMC effects, the use of fiber-optic cables is recommended for
Two 10/100BaseT Ethernet interfaces using RJ45 connectors (ETH 1 and ETH 2);
communication over distances greater than 3 m.
One 100 Mbps Ethernet interface using RJ45 connectors (Process Bus)
Two optical Ethernet interfaces (100BaseFX), using ST connectors for use with
multimode fiber-optic, of an internal electric-optical Ethernet converter (optional);
Ethernet Port Default Settings
A serial interface in RS232C level, using DB-9 female connector, DTE standard (Modem).
This interface can be used only to communicate by Modem.

The Ethernet interface default settings are:

Ethernet 1 default setting


1.1 Electrical and Optical Ethernet IP 192.168.0.199
The RPV311 has 2 electrical 10 / 100 Mbps Ethernet interfaces for configuration, Address
monitoring and GOOSE reading and one electrical 100 Mbps Ethernet interface for
Process Bus (IEC 61850-9-2LE Sampled Values and GOOSE) Netmask 255.255.255.0
Optionally it is possible to use the double internal converter for optical Ethernet
interface, making the connection between the RJ45 connector of the electrical Ethernet Broadcast 192.168.0.255
interface and the RJ45 connector of the internal optical Ethernet converter by using a
jumper cable, and connecting the fiber-optic pair with the appropriate ST connectors.
Figure 97 shows the electrical and optical Ethernet interfaces. On the left are the
interfaces for configuration, monitoring and GOOSE. On the right is the interface for Ethernet 2 default setting
Sampled Values and GOOSE reading.
IP 192.168.1.199
Address

Netmask 255.255.255.0

Broadcast 192.168.1.255

Gateway default setting

212 RPV311-TM-EN-11.1
Chapter 14 – Communications RPV311 RPV311 Chapter 14 – Communications

In order to convert the RPV311 pinout to standard RS232 pinout, the user shall use a
Gateway 192.168.0.1
cable or adapter with the following pinout specification:

1.2 Serial Port

The RPV311 has a serial communication port, shown in Figure 98, for connection
through modem, which can be used to transfer records. The port can be configured by
the user through the Web Interface.

DB9 Male DB9 Male

1 5

2 4

3 3

4 2
Figure 98: Serial communication port

5 1
Although the serial port is compatible with the RS232, the pinout is not according to the
6 9
standard and rather it follows the specification below:

DB9- 7 8
Signal
Female
8 7
5 DCD
9 6
4 RX

3 TX

2 DTR
Communication Ports and Protocols
1 GND To guarantee the full permission for communication equipment via Ethernet, it is
necessary that the following ports and protocols are freed:
9 DSR

8 RTS Port Protocol Use

7 CTS 22 TCP / IP Remote record download, automatic record upload,


firmware upgrade, remote diagnostics and
6 Not used maintenance.

214 RPV311-TM-EN-11.1
RPV311-TM-EN-11.1 213
Chapter 14 – Communications RPV311 RPV311 Chapter 14 – Communications

80 TCP / IP Interface Web remote access. Broadcast 192.168.0.255

123 UDP Time-of-day synchronism over SNTP

4041 TCP / IP Real-time monitoring using Web interface. If the equipment is not with the default IP settings, see Chapter 5: Operation to see how
to check the current IP address.
UDP Cross-trigger After connecting the equipment with the computer, see Chapter 4: Configuration for
details about equipment access.
4042 TCP / IP Manual Trigger
Note:
4713 UDP/IP Synchrophasors data streams
4714 Process Bus Ethernet port is used only to receive data of
4715 merging units (Sampled Values measured on monitored
4716 Power System). It is not possible to communicate to this
RPV311 using that Ethernet port for s their purposes.
502 TCP MODBUS interface

20000 TCP / IP DNP3 interface

UDP DNP3 interface 3.1 Checking the Connection


In order to verify whether the equipment connection is correctly set up, connect a
crossover network cable between the computer and the equipment and, using a
command line terminal, run a ping command to the IP address of the equipment.

Communication Using the Electrical Ethernet Port


To connect to the RPV311 locally or through Ethernet switches, it is necessary that the Communication Through Network Using the Serial Port
device and the computer be on the same network. To achieve this, configure the
network connection of the computer according to the IP address, Broadcast and
Netmask of the equipment, as shown below: Communication via modem is a Dial-in access method, but in cases of automatic
Given the following IP address, broadcast and netmask of the RPV311: connection via modem, the connection is permanent and is automatically started by the
equipment.
For communication through network using the serial port, it is first necessary to make a
pre-configuration of the computer, as following:
IP address, broadcast and netmask of the RPV311
1. Access the Control Panel of the computer;
2. On the Control Panel, access the Network Connection icon, and then access
IP Address 192.168.0.199
File ൐ New Connection ൐ Connect to Internet;
3. Select the Set up my connection manually check box and then, click on the
Netmask 255.255.255.0
൏Next൐ button;
4. Select the Connect using a dial-up modem check box and then, click on the
Broadcast 192.168.0.255
൏Next൐ button;
Set the local connection as follows: 5. Insert a connection name and click on the ൏Next൐ button;
6. Insert a phone number to dial and click on the ൏Next൐ button;
7. Enter a username and password. The default username and password to
connect via modem, that cannot be changed by the user, are:
IP address, broadcast and netmask of the local connection
8.

IP Address 192.168.0.190 Default username and password to connect via modem

Netmask 255.255.255.0 Username PQFW

216 RPV311-TM-EN-11.1
RPV311-TM-EN-11.1 215
Chapter 14 – Communications RPV311 RPV311 Chapter 14 – Communications

Password PQFW 5.3 Communication Configuration


It is possible to configure the communication ports (Ethernet, Gateway and Modem) of
1. Then, click on the ൏Finish൐ button to end the configuration. the RPV311 in the Web Interface. For communication configuration details, refer to
Chapter 4: Configuration.

To access the Web Interface of the RPV-311, verify the Server IP Address of the
connection properties and then, enter this IP address in the web browser. 5.4 Auto Upload
Application to Access the Equipment
When any new record is generated, it can be transmitted to up to two different servers
The equipment can be accessed through the Web Interface using a web browser. Please automatically. When using the configuration interface, each destination IP address
note that some applications may need to be installed and the minimum computer should be entered, along with the designated record type.
requirements should be met. If at the upload time the server is not available or the network is unreadable, the record
will not be transmitted. Within such case, it is always advisable to use the application
Scanner or the DR Manager to
For further Scanner application information see Chapter 12: Software – RPV Tools.
Accessing the Equipment
For further DR Manager application information seeChapter 13: Software – DR
Manager.
For auto upload configuration details, see Chapter 4: Configuration.
Enter the equipment IP via a web browser. If the Flash Player 9.0 plug in or higher is not
previously installed on the computer, it will be automatically installed by the operating
system.
For details about the Web Interface, refer to Chapter 5: Operation.

5.1 Computer Support Applications

Internet Explorer version 7 or higher, or Mozilla Firefox version 3.0 or higher;


Adobe Flash Player 9.0 or higher.

The support applications can be obtained on the Internet.

5.2 Minimum Computer Requirements

1GHz processor or higher;


512 MBytes RAM;
500 MBytes free disk space;
Super VGA 1024 x 768 video card.

218 RPV311-TM-EN-11.1
RPV311-TM-EN-11.1 217
RPV311 Chapter 15 – Installation

flat racks and spaced to allow circulation around them. The time taken for regeneration
RPV311 will depend on the size of the bag. If a ventilating, circulating oven is not available,
when using an ordinary oven, open the door on a regular basis to let out the steam
given off by the regenerating silica gel.
Distributed Multifunction Fault Recorder On subsequent unpacking, make sure that any dust on the carton does not fall inside.
Avoid storing in locations of high humidity. In locations of high humidity the packaging
may become impregnated with moisture and the de-humidifier crystals will lose their
efficiency.
Chapter 15: Installation The device can be stored between –25º to +70ºC for unlimited periods or between -
40°C to + 85°C for up to 96 hours (see technical specifications).
This chapter provides information about the product installation.

1.4 Dismantling the Goods


Handling the Goods If you need to dismantle the device, always observe standard ESD (Electrostatic
Our products are of robust construction but require careful treatment before Discharge) precautions. The minimum precautions to be followed are as follows:
installation on site. This section discusses the requirements for receiving and unpacking Use an antistatic wrist band earthed to a suitable earthing point.
the goods, as well as associated considerations regarding product care and personal Avoid touching the electronic components and PCBs.
safety.

Before lifting or moving the equipment you should be familiar


with the Safety Information chapter of this manual.

Normal Use of the Equipment


In order to maintain the equipment integrity, levels of protection and assure user
safety, the RPV311 and RA33x shall be installed in an enclosed panel with
1.1 Receipt of the Goods recommended ingress protection rating of IP42 or above. The Reason range of
On receipt, ensure the correct product has been delivered. Unpack the product equipment shall be kept in an environment where their rear connection and sides are
immediately to ensure there has been no external damage in transit. If the product has protected against impact and water. The enclosing panel shall ensure that the
been damaged, make a claim to the transport contractor and notify us promptly. equipment rear connections are not exposed, meanwhile maintaining adequate
For products not intended for immediate installation, repack them in their original temperature and humidity condition for the devices. Furthermore, the equipment shall
delivery packaging. have all their rear connectors attached, even if not being used, in order to keep their
levels of ingress protection as high as possible.
The RPV311 and RA33x modules are IEC 61010-1 rated at Installation/Overvoltage
Category II and Pollution Degree 3. These ratings allow mounting of the equipment
1.2 Unpacking the Goods indoors or in an outdoor (extended) enclosure where the equipment is protected
When unpacking and installing the product, take care not to damage any of the parts against exposure to direct sunlight, precipitation, and full wind pressure.
and make sure that additional components are not accidentally left in the packing or During the normal use of the device only its the frontal panel shall be accessible.
lost. Do not discard any CDROMs or technical documentation. These should accompany
the unit to its destination substation and put in a dedicated place.
The site should be well lit to aid inspection, clean, dry and reasonably free from dust
and excessive vibration. This particularly applies where installation is being carried out
Mounting the Device
at the same time as construction work.

3.1 RPV311 Mechanical Installation


1.3 Storing the Goods The RPV311 must be installed in a 19-inch rack.
If the unit is not installed immediately, store it in a place free from dust and moisture in The RPV311 must be installed at least 10 cm away from any other equipment to avoid
its original packaging. Keep any de-humidifier bags included in the packing. The de- obstruction of air circulation impairing the cooling efficiency.
humidifier crystals lose their efficiency if the bag is exposed to ambient conditions.
Restore the crystals before replacing it in the carton. Ideally regeneration should be
carried out in a ventilating, circulating oven at about 115°C. Bags should be placed on 220 RPV311-TM-EN-11.1
Chapter 15 – Installation RPV311 RPV311 Chapter 15 – Installation

Figure 99: Minimum distances for the equipment mounting

Figure 100: Mounting panel to install two remote acquisition modules (RA331/332) in a 19-inch rack
The screws for fixing the equipment are of the M6 type.
The curvature of fiber-optic connected to the back of the equipment must have a
minimum radius of 30 mm.
The fixing screws are not included in the product order.
Cables and Connectors
This section describes the type of wiring and connections that should be used when
installing the device. For pin-out details please refer to the Hardware Design chapter or
the wiring diagrams.
3.2 RA331, RA332 and RA333 Mechanical Installation
To install the module in the panel, make a cut with the drilling and dimensions Before carrying out any work on the equipment you should be
described in Section 22.1. The screws used for fixation are of the M6 type. familiar with the Safety Section and the ratings on the equipment’s
It is possible to order an optional panel for installation of one or two modules adapted rating label.
to a 19-inch rack.
To install either a single or two modules of RA331, RA332 or RA333 it is available for The connections: Console1, Console2, MODEM and Process bus are
ordering the optional panels presented below. The screws used for fixing are of the M6 non-isolated and for local connection only.
type.

3.2.1 Panel for Installation of Two Remote Acquisition Modules (Q61) Power Supply Connections

The Mounting panel to install two remote acquisition modules (RA331/332) in a 19-inch The RPV311, RA331, RA332 and RA333 can be powered-up by DC or AC power source
rack is shown in Figure 100. within the limits specified in Chapter 17: Technical Specifications.
The power connections shall use insulated flexible conductors anti-flame (BWF type)
with 1.5 mm² section, thermal class 70 °C and isolation voltage of 750 V.
To reduce risk of electrical shock, pre-insulated pin terminals, as shown in Figure 101,
should be used on the ends of the power connections.

222 RPV311-TM-EN-11.1
RPV311-TM-EN-11.1 221
Chapter 15 – Installation RPV311 RPV311 Chapter 15 – Installation

For compliance with IEC 61010, install a suitable external switch or circuit breaker in
each current-carrying conductor of RPV311 power supply; this device should interrupt
both the hot (+/L) and neutral (-/N) power leads. An external 10 A, category C, bipolar
circuit-breaker is recommended. The circuit breaker should have an interruption
capacity of at least 25 kA and comply with IEC 60947-1 and IEC 60947-3. The switch or
circuit-breaker must be suitably located and easily reachable, also it shall not interrupt
Figure 101: Pre-insulated tubular pin terminals the protective earth conductor.
Information about nominal voltage range, maximum voltage range, frequency and
power consumption, refer to Specifications Chapter 17: Technical Specifications.
The pin terminals should be completely inserted into the header connector supplied
with the unit so that no metallic parts are exposed, as shown in Figure 102.

RA331, RA332 and RA333 AC and DC Power Connection

Figure 104 show the wiring diagram for the AC and DC of the RA331, RA332 and RA333
respectively.

Figure 102: Header connector assembly

A safety ground lead shall be connected to the terminal marked with the functional
earth symbol.
For better electromagnetic compatibility, ground the unit using a 10 mm (0.4 in) wide
grounding strap to connect the back panel of the unit to a good grounding point on the
mounting rack.

Models with a low DC power supply must be supplied with a DC supply source to the Figure 104: AC/DC power connection
equipment that is derived from a secondary circuit which is isolated from the AC/DC
Mains by Double or Reinforced Insulation (e.g.: UL Certified ITE power supply which
provides Double or Reinforced Insulation). For compliance with IEC 61010, install a suitable external switch or circuit breaker in
each current-carrying conductor of RA33x power supply; this device should interrupt
both the hot (+/L) and neutral (-/N) power leads. An external 10 A, category C, bipolar
circuit-breaker is recommended. The circuit breaker should have an interruption
RPV311 AC and DC Power Connection capacity of at least 25 kA and comply with IEC 60947-1 and IEC 60947-3. The switch or
circuit-breaker must be suitably located and easily reachable, also it shall not interrupt
the protective earth conductor.
Figure 103 show the wiring diagram for the AC and DC of the RPV311 respectively. For information about nominal voltage range, maximum voltage range, frequency and
power consumption, see Section 2.9 of the Specifications Chapter.

Powering Up

8.1.1 RPV311
Do not operate the unit without the safety ground connection in place;
Figure 103: AC/DC power connection Connect power cable (including safety grounding) to the unit;

224 RPV311-TM-EN-11.1
RPV311-TM-EN-11.1 223
Chapter 15 – Installation RPV311 RPV311 Chapter 15 – Installation

A self-test will be executed and at the end, if no configuration has been sent, the READY
indicator on the front panel will light up; 9.1.1 RA33x Earthing
If any pair of optical fibers has already been connected to the acquisition module, the
ACT indicator will light up, indicating that there is communication between the modules; To ensure proper operation of the equipment under adverse conditions of
If the module does not work as described, carefully check all power and signal electromagnetic compatibility, connect the equipment protective earth terminal to the
connections. Refer to Chapter 16: Maintenance and Troubleshooting for panel using a copper strap of at least 10 mm wide with M6 ring lug. As shown in the
troubleshooting guide; Figure 106.
To turn off the module, switch off the external switch or circuit breaker. All indicators
will be off.

8.1.2 RA331, RA332 and RA333

Do not operate the module without the safety ground connection in place;
Connect power cable (including safety grounding) to the module. The Mains indicator
on the front and back panel will light immediately;
A self-test will be executed and the Ready indicators on the front and back panels will
light up when the process has ended;
If a pair of fiber-optics have already been connected to the processing unit, the Link
indicator will light up, indicating that there is a communication between the modules;
If the module does not work as described, carefully check all power and signal
connections. Refer to Chapter 16: Maintenance and Troubleshooting for
troubleshooting guide; Figure 106: RA33X Grounding
To turn off the module, switch off the external switch or circuit breaker. All indicators
on the front and the back panels will be off.

Connection Between RPV311 and RA331, RA332 or RA333


Earth Connection The RPV311 can process a maximum number of 64 analogue channels that can be
To ensure proper operation of the equipment under adverse conditions of achieved using 8 acquisition modules.
electromagnetic compatibility, connect the equipment protective earth terminal to the The RPV311 processing unit allows connection with up to 8 RA331 acquisition modules,
panel using a copper strap of at least 10 mm wide with M6 ring lug. As shown in the up to 4 RA332 acquisition modules or up to 4 RA333 acquisition modules respecting the
Figure 105. maximum quantity of 64 analog channels. That is: when it is using only RA332, it is
possible to install a maximum of 4 modules with 16 analog inputs each, and when it is
using only RA331, it is possible to install up to 8 modules with 8 analog inputs each.
When it is using only RA333, it is possible to install a maximum of 4 modules with 8
analog and 3 TW inputs each one (each TW board counts as 8 analogue channels). The
RA331, RA332, and RA333 can be connected to the same RPV311 processing module.
Each link on the RPV311, composed of a pair of fiber-optic connectors, is named from A
to H. For each link, an optical fibers pair is used to make transmission and reception of
data between the processing module and the acquisition modules. Connections with
acquisition modules must be made according to the sequence of RPV311 identification:
the first connection should be made with link A, the second, with link B, and so forth.
On the RPV311, each link has an ACT indicator, as shown in Figure 107, which lights up
when the link is receiving data of the acquisition module.
Figure 105: RPV311 Grounding

226 RPV311-TM-EN-11.1
RPV311-TM-EN-11.1 225
Chapter 15 – Installation RPV311 RPV311 Chapter 15 – Installation

Figure 107: RPV311 Fiber Optic Connectors

The RA331 and RA332 modules each occupy one physical link of the processing module.
The RA333 occupies two physical links of the processing module, one for data
transmission of analog channels (DFR) and the other for data transmission of TW
channels (TW).
On the RA331, RA332 and RA333 (TW and DFR) modules, each link has an indicator
showing the state of the connection with the processing module, as shown in Figure
108. These indicators, LINK and ACT, on the front panel and back panel, respectively, light
up when the link is active (i.e. it is receiving requests of the processing module).
Figure 109: Connection between RPV311 and the RA331, RA332 or RA333

The length of the fiber-optic cables shall not exceed 2 km.


Make sure to use the appropriate optical fiber, considering its curvature radius.
For information about optical fiber types and link specifications, see Chapter 17:
Technical Specifications.
When more than one RA333 module is required, an internal module jumper must be
configured, according to the TW link position. The position of links does not have to be
consecutive, but module installation related to A to H position must match the jumper
identification. For example, ID 0 must be the first RA333 (TW) link, ID 1 must be the
second RA333 (TW) link, and so on.
Figure 108: RA331, RA332 and RA333 fiber optic connectors In order to configure these jumpers, remove all connectors and cables which are
connected to the module and remove the back panel of the RA333 removing the 12
screws of the panel and the screw of the protective grounding, as shown in Figure 110.
The connectors are identified as RX for receiving data and TX for transmitting data. The
corresponding fibers must be linked to the acquisition module so that the TX of RPV311
is connected to the RX of the RA331, RA332, or RA333 and RX of RPV311 is connected to
the TX of the RA331, RA332, or RA333, according to Figure 109.

228 RPV311-TM-EN-11.1
RPV311-TM-EN-11.1 227
Chapter 15 – Installation RPV311 RPV311 Chapter 15 – Installation

define if the driver will measure voltage, it is necessary to select an internal jumper in
the module. The binary and analog inputs are galvanically isolated.

Figure 111: Analog input terminals

In order to configure the analog input to measure voltage signals, remove all connectors
and cables which are connected to the module and remove the back panel of the
Figure 110: Screws of the Back Panel RA331, RA332, or RA333 removing the 12 screws of the panel and the screw of the
protective grounding, as shown in Figure 112.

Remove the QTW board, which corresponds to the traveling waves acquisition board.
Configure jumper identification as shown at table 4.1, according to the RA333 TW link
positions.

JP4 JP3 ID

Open Open 0

Closed Open 1

Open Closed 2

Closed Closed 3

Re-fit the board in the case until perfectly connected.


Secure the case by screwing the back panel and connecting the terminal cables.

Figure 112: Screws of the Back Panel


Analog Voltage Inputs (50/60 Hz)
Remove the board corresponding to the channel to be configured. In order to configure
The RA331, RA332, and RA333 modules have up to 8, 16 or 8 analog inputs, a channel for voltage, connect the jumper between positions 1 and 2 as shown in Figure
respectively, which can be configured for measurement of voltage. All channels are 113.
identified of 101 to 108 for the RA331 and RA333, and 101 to 116 for the RA332.
Each analog input has three terminals: positive voltage, positive current and negative
terminal, which are used for the current and for the voltage, as shown in Figure 111To
230 RPV311-TM-EN-11.1
RPV311-TM-EN-11.1 229
Chapter 15 – Installation RPV311 RPV311 Chapter 15 – Installation

3-element (Phases A, B and C)


connection: in this case, the
fourth element is derived of the
values measured by the other
elements. The three elements
are equivalent to the values
applied to the equipment

3-element (Phases A, B and


neutral) connection: in this case,
the fourth element is
Figure 113: Internal Jumper synthesized of the values
measured by the other
elements. The three elements
Place the board back in the case. are equivalent to the values
Secure the case by screwing the back panel and connecting the terminal cables. applied to the equipment.
Connections shall use insulated flexible wires of 1.5 mm² cross section, 8 mm ring
terminals, and M3 holes.
Before making the electrical connection, make sure the signal is applied in accordance
with the technical specifications of the equipment. For information about analog
3-element (Phases A, C and
voltage inputs specifications, see Chapter 17: Technical Specifications.
neutral) connection: in this case,
the fourth element is derived of
11.1.1 Connection diagram of the voltage inputs the values measured by the
other elements. The three
elements are equivalent to the
The RPV311 provides the capability for making some different voltage signal values applied to the equipment.
connections for a 3-phase circuit:

Connection diagram of the voltage inputs

3-element (Phases B, C and


neutral) connection: in this case,
the fourth element is derived of
4-element connection: in this the values measured by the
case, the values shown are other elements. The three
equivalent to the voltages of elements are equivalent to the
phases A, B and C, and to the values applied to the equipment.
neutral voltage applied to the
equipment.

232 RPV311-TM-EN-11.1
RPV311-TM-EN-11.1 231
Chapter 15 – Installation RPV311 RPV311 Chapter 15 – Installation

2-element connection: in this


case, the neutral voltage is zero, Connection diagram for 1 voltage element connection
and the three phase-to-ground
voltage are computed based on
the two line-to-line voltages 1-element connection:
applied to the equipment. Connection diagram of 1
element (phase A, B or C).

In circuits of one element, the measurements can be in two different ways:


An isolated phase or neutral measurement: If the element is a phase, only the voltage 1-element connection:
related to this channel is measured considering the off-set compensation. If the Connection diagram of 1
element is a neutral, the voltage related to this channel is measured without the off-set element (neutral).
compensation.
A 3-Phase synthesis: The magnitude for the 3-phases is considered with the same value
as that of the channel measured and balanced (i.e., angles with 120º between each
other).
In all cases, the equipment will compute the phase-to-ground voltage and the neutral
voltage.

High-speed Analog Voltage Inputs (TW)


The RA333 module has 3 high-speed analog inputs for measurement of TW
voltage, with a sampling frequency of 5 MHz. All channels are identified from 301
to 303.
Each analog input has two terminals: positive voltage, and negative, which are
used for one phase voltage, as shown in Figure 114. The binary and analog inputs
are galvanically isolated.

Figure 114: Analog Input Terminals to TW Measurement

Connections shall use insulated flexible wires of 1.5 mm² cross section, 8 mm ring
terminals, and M3 holes.

234 RPV311-TM-EN-11.1
RPV311-TM-EN-11.1 233
Chapter 15 – Installation RPV311 RPV311 Chapter 15 – Installation

Before making the electrical connection, make sure the signal is applied in accordance
with the technical specifications of the equipment. For information about analog
voltage inputs specifications, refer to Chapter 17: Technical Specifications.

12.1.1 Connection diagram of the TW inputs

The RPV311 provides the capability for connecting one 3-phase circuit (phases A, B, and
C):
Figure 115: Analog Input Terminals

Connection diagram for TW inputs


In order to configure the analog input to measure current signals, remove all connectors
and cables which are connected to the module and remove the back panel of the
RA331, RA332 or RA333, removing the 12 screws of the panel and the screw of the
protective grounding, as shown in Figure 116
3-element (Phases A, B
and C) connection: in this
case, the three elements are
equivalent to the values of
TW voltage.

Analog Current Inputs

The RA331, RA332, and RA333 modules have up to 8, 16 or 8 analog inputs,


respectively, which can be configured for measurement of current. All channels are
identified of 101 to 108 for the RA331 and RA333, and 101 to 116 for the RA332.
Each analog input has three terminals: positive voltage, positive current and negative
terminal, which are used for the current and for the voltage, as shown in Figure 115. To
define if the driver will measure current, it is necessary to select an internal jumper in
the module. The binary and analog inputs are galvanically isolated.
Figure 116: Screws of the Back Panel

Remove the board corresponding to the channel to be configured. For each channel to
be configured for current, connect the jumper between positions 2 and 3 as shown in
Figure 117.

236 RPV311-TM-EN-11.1
RPV311-TM-EN-11.1 235
Chapter 15 – Installation RPV311 RPV311 Chapter 15 – Installation

3-element (Phases A, B and C)


connection: in this case, the fourth
element is derived of the values
measured by the other elements.
The three elements are equivalent
to the values applied to the
equipment

3-element (Phases A, B and


neutral) connection: in this case,
the fourth element is derived of the
values measured by the other
Figure 117: Internal Jumper elements. The three elements are
equivalent to the values applied to
the equipment.
Place the board back in the case.
Secure the case by screwing the back panel and connecting the terminals cables.
Connections shall use insulated flexible wires of 1.5 mm² cross section, 8 mm ring
terminal, and M3 holes.
Before making the electrical connection, make sure the signal is applied in accordance 3-element (Phases A, C and
with the technical specifications of the equipment. For information about analog neutral) connection: in this case,
current inputs specifications, see Chapter 17: Technical Specifications. the fourth element is derived of the
values measured by the other
elements. The three elements are
13.1.1 Connection diagram of the current inputs equivalent to the values applied to
the equipment.

The RPV311 provides the capability for connecting some different current signal
connections for a 3-phase circuit:

3-element (Phases B, C and


Connection diagram of the current inputs
neutral) connection: in this case,
the fourth element is derived of the
values measured by the other
elements. The three elements are
4-element connection: in this case, equivalent to the values applied to
the values shown are equivalent to the equipment.
the voltages of phases A, B and C,
and to the neutral voltage applied
to the equipment.

238 RPV311-TM-EN-11.1
RPV311-TM-EN-11.1 237
Chapter 15 – Installation RPV311 RPV311 Chapter 15 – Installation

2-element connection: in this case,


the neutral voltage is zero, and the Connection diagram for 1 current element connection
three phase-to-ground voltage are
computed based on the two line-
to-line voltages applied to the
1-element connection:
equipment
Connection diagram of 1
element (phase A, B or C).

In circuits of 1 element, the measurements can be in two different ways:


An isolated phase or neutral measurement: If the element is a phase, only the current
1-element connection:
related to this channel is measured considering the off-set compensation. If the
Connection diagram of 1
element is a neutral, the current related to this channel is measured without the off-set
element (neutral).
compensation.
A 3-Phase synthesis: The magnitude for the 3-phases is considered with the same value
as that of the channel measured and balanced (i.e., angles with 120º between each
other).
In all cases, the equipment will compute the line current and the neutral current.

Analog DC Transducer Inputs ± 10 V

The RA331, RA332 and RA333 modules have up to 8, 16 or 8 analog inputs, respectively,
which can be configured for measurement of voltages of DC transducers of -10 V to +10
V. All channels are identified of 101 to 108 for the RA331 and RA333, and 101 to 116 for
the RA332.
Each analog input has three terminals: positive voltage, positive current and negative
terminal which are used for the current and for the voltage, as shown in Figure 118. To
define if the driver will measure voltage of a DC transducer it is necessary to select an
internal jumper in the module. The binary and analog inputs are galvanically isolated.

Figure 118: Analog Input Terminals

240 RPV311-TM-EN-11.1
RPV311-TM-EN-11.1 239
Chapter 15 – Installation RPV311 RPV311 Chapter 15 – Installation

In order to configure the analog input to measure voltage signals of DC transducers,


remove all connectors and cables which are connected to the module and remove the
Place the board back in the case.
back panel of the RA331, RA332 or RA333, removing the 12 screws of the panel and the
Secure the case by screwing the back panel and connecting the terminals cables.
screw of the protective grounding, as shown in Figure 119.
Connections shall use insulated flexible wires of 1.5 mm² cross section, 8 mm ring
The fixing screws are not included in the product order.
terminals, and M3 holes.
Before making the electrical connection, make sure the signal is applied in accordance
with the technical specifications of the equipment. For information about DC transducer
inputs specifications, see Chapter 17: Technical Specifications.

14.1.1 Connection diagram of the DC transducer inputs of ± 10 V

Figure 121: Connection Diagram of DC Transducer Inputs ± 10 V

Figure 119: Screws of the Back Panel Analog DC Transducer Inputs ± 20 mA

Remove the board corresponding to the channel to be configured. For each channel to The RA331, RA332, and RA333 modules have up to 8, 16, or 8 analog inputs,
be configured to DC transducers of േ 10 V, connect the jumper between positions 1 and respectively, which can be configured for measurement of currents of DC transducers of
2 as shown in Figure 120. -20 mA to 20 mA. All channels are identified of 101 to 108 for the RA331 and RA333,
and 101 to 116 for the RA332.
Each analog input has three terminals: positive voltage, positive current and negative
terminal which are used for the current and for the voltage, as shown in Figure 122.
To define if the driver will measure current of a DC transducer it is necessary to select
an internal jumper in the module. The binary and analog inputs are galvanically isolated.

Figure 120: Internal Jumper Figure 122: Analog Input Terminals


242 RPV311-TM-EN-11.1
RPV311-TM-EN-11.1 241
Chapter 15 – Installation RPV311 RPV311 Chapter 15 – Installation

In order to configure the analog input to measure currents signals of DC transducers,


remove all connectors and cables which are connected to the module and remove the
back panel of the RA331, RA332 or RA333, removing the 12 screws of the panel and the
screw of the protective grounding, as shown in Figure 123.
The fixing screws are not included in the product order.

Figure 124: Internal Jumper

Place the board back in the case.


Secure the case by screwing the back panel and connecting the terminals cables.
Connections shall use insulated flexible wires of 1.5 mm² cross section, 8 mm ring
terminals, and M3 holes.
Before making the electrical connection, make sure the signal is applied in accordance
with the technical specifications of the equipment. For information about DC transducer
input specifications, see Chapter 17: Technical Specifications.

15.1.1 Connection diagram of the DC transducer inputs ± 20 mA

Figure 123: Screws of the back panel

Remove the board corresponding to the channel to be configured. For each channel to
be configured to DC transducers of ±20 mA, connect the jumper between positions 2
and 3 as shown in Figure 124.

Figure 125: Connection Diagram of DC Transducer Inputs ± 20 mA

Current Clamps

In order to operate the equipment with the current clamps connection, it is necessary
that the RA33x have the proper analog input board (CORTEC description: Analog Input
100 mA / 115 V).

244 RPV311-TM-EN-11.1
RPV311-TM-EN-11.1 243
Chapter 15 – Installation RPV311 RPV311 Chapter 15 – Installation

As the measuring principle is based on current, the RA’s internal jumper needs to be set Each block of 8 inputs uses an appropriate connector which can be disconnected of the
to current mode. To do so, follow the procedure described on the topic 13 Analog module. When plugging it, make sure that it is perfectly fitted.
Current Inputs. Connections shall use insulated flexible wires of 1.5 mm² cross section and 5.08 mm
After setting the internal jumper and reassembling the device, connect the outputs of pitch plug terminals.
the current clamp to the correct inputs terminals of the RA respecting the polarity of For information about digital input specifications, see Chapter 17: Technical
the outputs and the inputs, as shown in the figure below. Specifications.

17.1.1 Connection diagram of the digital inputs

Figure 128: Connection Diagram of Digital Inputs

Figure 126: Polarity of the Current Clamp Connection

Time Synchronization Inputs


Digital Inputs
Timing synchronism is provided by the IRIG-B000/001/002/003/004/005/006/007
signal. The IRIG-B signal is used to keep the RPV311 data acquisition frequency constant
The RA331 and RA332 modules have up to 32 insulated digital inputs, and the RA333 and to provide the time stamp for the equipment.
module has up to 16, as shown in Figure 127.The digital inputs of RA331 and RA332 The equipment indicates sync when the data acquisition frequency is according to the
modules are identified of 201 to 232. The digital inputs of RA333 module are identified equipment's nominal acquisition frequency and the equipment's internal clock is
of 201 to 216. Make sure that the appropriate terminal pair are selected to the voltage updated.
applied. The RPV311 internal clock is updated with every hour rollover or when the equipment
turns to sync mode.
If the IRIG-B signal is not valid or not connected, the device indicates no sync. If the
IRIG-B signal is connected and valid, the time quality of the time reference reported in
the IRIG-B frame is shown by the RPV311, but the time quality is not considered by the
synchronization.
In the absence of the IRIG-B signal, the equipment can be synchronized by an SNTP time
server, however, the acquisition frequency does not have the same stability afforded by
the IRIG-B signal (accuracy less than 12 ppm), and the equipment does not indicate
sync.
The IRIG-B signal is preferred over the SNTP time server.
If no IRIG-B signal is available and the SNTP server is unreachable, the unit obtains the
time of an internal CMOS clock. Drift is better than 0.1 second in 24 hours.
Figure 127: Digital Input Terminals
The RPV311 has an electrical and an optical IRIG-B input, as shown in Figure 129.

246 RPV311-TM-EN-11.1
RPV311-TM-EN-11.1 245
Chapter 15 – Installation RPV311 RPV311 Chapter 15 – Installation

Dry Contact Relays

The RPV311 has 4 electromechanical signaling relays. Each relay has one dry contact, as
shown in Figure 132.
The first relay contact is normally closed and it opens when the unit goes into operation
Figure 129: Electrical and optical inputs for sync using IRIG-B and it is not configurable by the user.
The other three contacts are normally open and can be individually configured using the
Web Interface. For information about relays output configuration, Chapter 17: Technical
To synchronize the equipment using fiber-optic input, use the appropriate fiber-optic Specifications.
type, considering its minimum curvature radius.
The use of a twisted pair cable is recommended for the electrical input.
For distances greater than 3 m, to minimize EMC effects, the use of fiber-optic cable is
recommended.

18.1.1 Connection diagram of the synchronism inputs

Figure 132: Dry contact relays of the RPV311

19.1.1 Dry contact relay connection diagram

Figure 130: Connection diagram of electrical synchronism inputs

For information about electrical synchronism input specifications, Chapter 17: Technical
Specifications.

Figure 133: Dry contact relay connection diagram

For information about relay outputs specification, see Chapter 17: Technical
Specifications.

Figure 131: Connections diagram of optical synchronism inputs


Case Dimensions
Information about optical synchronism inputs specifications, see Chapter 17: Technical
Specifications. 20.1 RPV311 and RA33X
Refer to the technical specification section to check the RPV311 and RA33X dimensions
and weight.

248 RPV311-TM-EN-11.1
RPV311-TM-EN-11.1 247
Chapter 15 – Installation RPV311 RPV311 Chapter 15 – Installation

RPV311 Accessories

Fiber-optic pair, ST connector (Q026):

Fiber type Multimode 62.5 / 125 μm

Curvature ratio (min) 30 mm

Connector ST

Figure 134: Fiber-optic pair

RA33x Accessories

RA33x accessories

Q061 Mounting panel to install two remote acquisition modules (RA331 / RA332 / RA333) in a
19-inch rack + blank plate to cover one cutout in case only one RA33x is being used.

22.1 Panel Cutout

The RA331, RA332 and RA333 panel cutout is shown in Figure 135.

250 RPV311-TM-EN-11.1
RPV311-TM-EN-11.1 249
Chapter 15 – Installation RPV311 RPV311 Chapter 15 – Installation

Figure 136: Mounting panel to install two remote acquisition modules (RA331/332) in a 19-inch rack

Figure 135: RA331, RA332 and RA333 panel cutout

Panel for Installation of Two Remote


Acquisition Modules (Q61)
The Mounting panel to install two remote acquisition modules (RA331/332) in a 19-inch
rack is shown in Figure 136.

252 RPV311-TM-EN-11.1
RPV311-TM-EN-11.1 251
RPV311 Chapter 16 – Maintenance and Troubleshooting

RPV311
1.1.1 Alarms
First check the alarm status LED to see if any alarm conditions exist. If so, press the
Distributed Multifunction Fault Recorder Read key repeatedly to step through the alarms.
After dealing with any problems, clear the alarms. This will clear the relevant LEDs.

Chapter 16: Maintenance and Troubleshooting 1.1.2 Measurement Accuracy


If the power system is energised, the measured values can be compared with known
This chapter provides information about proper equipment maintenance and system values to check that they are in the expected range. If they are within a set
troubleshooting. range, this indicates that the A/D conversion and the calculations are being performed
The troubleshooting part of the chapter allows an error condition on the IED to be correctly.
identified so that appropriate corrective action can be taken. Alternatively, the measured values can be checked against known values injected into
the device using the test block, (if fitted) or injected directly into the device's terminals..

Maintenance
1.2 Replacing the Unit
If your product should develop a fault while in service, depending on the nature of the
1.1 Maintenance Checks fault, the watchdog contacts will change state and an alarm condition will be flagged. In
the case of a fault, you should normally replace the cradle which slides easily out of the
In view of the critical nature of the application, GE Grid products should be checked at
case. This can be done without disturbing the scheme wiring.
regular intervals to confirm they are operating correctly. GE Grid products are designed
In the unlikely event that the problem lies with the wiring and/or terminals, then you
for a life in excess of 20 years.
must replace the complete device, rewire and re-commission the device.
The devices are self-supervising and so require less maintenance than earlier designs of
protection devices. Most problems will result in an alarm, indicating that remedial If the repair is not performed by an approved service centre,
action should be taken. However, some periodic tests should be carried out to ensure the warranty will be invalidated.
that they are functioning correctly and that the external wiring is intact. It is the
responsibility of the customer to define the interval between maintenance periods. If
Before carrying out any work on the equipment, you should
your organisation has a Preventative Maintenance Policy, the recommended product be familiar with the contents of the Safety Information section
checks should be included in the regular program. Maintenance periods depend on of this guide or the Safety Guide SFTY/4LM, as well as the
many factors, such as: ratings on the equipment’s rating label. This should ensure
that no damage is caused by incorrect handling of the
x The operating environment electronic components.
x The accessibility of the site
x The amount of available manpower
x The importance of the installation in the power system Before working at the rear of the unit, isolate
all voltage and current supplying it.
x The consequences of failure

Although some functionality checks can be performed from a remote location, these are
predominantly restricted to checking that the unit is measuring the applied currents
and voltages accurately and checking the circuit breaker maintenance counters. For 1.3 Cleaning
this reason, maintenance checks should also be performed locally at the substation.

Before carrying out any work on the equipment you should


be familiar with the contents of the Safety Section and the Before cleaning the device, ensure that all AC
ratings on the equipment’s rating label. and DC supplies and transformer connections
are isolated, to prevent any chance of an
electric shock while cleaning.
The RPV311 has a small coin-battery to power the internal
clock. In order to replace it, please follow the battery
replacement procedures presented in this chapter.

253 RPV311-TM-EN-10 254 RPV311-TM-EN-11.1


Chapter 16 – Maintenance and Troubleshooting RPV311 RPV311 Chapter 16 – Maintenance and Troubleshooting

Only clean the equipment with a lint-free cloth dampened with clean water. Do not use 4. Position the device in place where there is free space to work and make sure
detergents, solvents or abrasive cleaners as they may damage the product's surfaces to install proper working and safety warnings at the location, also keep
and leave a conductive residue. available all tools and aids that is going to be used;
5. Wait a few minutes so the capacitors may discharge;
6. Disassemble the device by unscrewing the case screws and pulling up the top
side of the case; after that. Keep in mind that disassembling the equipment
1.4 Watchdog may expose sensitive electronic circuitry. Take suitable precautions against
electrostatic voltage discharge (ESD) to avoid damage to the equipment.
The RPV311 presents an internal watchdog algorithm. This algorithm verifies, every
7. Locate the CR2032 battery. It has 20mm of diameter and looks like the picture
second, if the device’s system is responding correctly. Case the system does not
below:
respond the device performs a hardware reboot while the output relay 1 signals that
the RPV311 is off.

1.5 Coin-battery replacement procedure


.
8. Use your fingers to grab on the edge of the battery and pull it up and out of
the socket holding it in place.
Before carrying out any work on the equipment, you 9. Insert the new battery.
should be familiar with the contents of the Safety
Information section of this manual, as well as the ratings After the replacement, follow the procedure below in order to verify the safe state of
on the equipment’s rating label. This should ensure that the equipment and to put it back into operation.
no damage is caused by incorrect handling of the
electronic components.
1. Reconnect all internal cable that have been removed for the repair;
2. Perform a visual inspection on the device to make sure there are no
remainders of the repair service inside the casing or any other noncompliance;
Before working at the rear of the unit, isolate
3. Place back the top side of the case and fasten it using the proper screws;
all voltage and current supplying it.
4. Connect the grounding strap and then the power supply to the equipment;
5. Wait for the equipment to initialize, it will run self-diagnostic routines and if
The RPV311 coin-battery (3V CR2032 ) supplies energy for the internal clock and everything is right the “Ready” LED on its front panel will light up indicating
mother-board BIOS. Its average life span is 3 years, after which it is advisable to replace the equipment is safe and operational;
the battery.
The user can either ship the device to a GE technical support center or replace it
following carefully the procedure described in this section.
The battery is only accessed using specific tools to open the equipment cabinet and
expose the battery.
RPV311 Troubleshooting
The battery connector is design to fit only battery with right
size and with correct polarity position. In case, the battery 2.1 Ready in processing module does not light up
does not fit, do not force the fitting. Stop and reassess
whether the right battery and right polarity is being The unit continuously executes an internal auto-diagnosis routine. The result of this
applied. diagnosis is reflected by the Ready led on the front panel of the unit, on the status page
of the Web Interface and by the failure relay (normally closed contact) on the back
panel of the unit.
To replace the battery, follow the procedure below:
If the local interface does not operate, the Ready indicator does not light up. In this
1. Disconnect the power supply;
case, the processing module must be sent for technical assistance.
2. Disconnect all other connections leaving the grounding strap to be removed at
the end;
3. Perform a visual inspection to make sure the equipment is isolated;

256 RPV311-TM-EN-11.1
RPV311-TM-EN-11.1 255
Chapter 16 – Maintenance and Troubleshooting RPV311 RPV311 Chapter 16 – Maintenance and Troubleshooting

2.2 Alarm LED lights up


The equipment must be operating without an external reference.
Make sure that an IRIG-B signal is present at the optical or electrical input, and connect
If the indicator is lit up, the equipment may have some of the problems described
signal if is not;
below. To identify the problem that generated the alarm, access the status of
Verify the NTP/SNTP server and guarantee this alternative source of timing.
equipment and links in the Web Interface, as shown in Chapter 5: Operation.

RPV311 Firmware Update


Problem Solution

Transmission of Normal behavior, no action should When installing the application software package accompanying the equipment (refer
configuration be taken
to Software Installation), the Firmware Upgrade Tool (FUT) is installed and associated
having an files with extension .fw allowing an RPV firmware update to be easily carried
Internal failure Equipment is not operating, replace
out by user.
the processing module
The steps to be followed for updating the equipment firmware are:

Opened link Check the links between RPV and


1. Request GE for the firmware file.
acquisition modules.
2. Copy the file to the PC on which the RPV application software is installed (see
*If during the RPV311 initialization Software Installation). The file shall have a .fw extension.
(boot) the Alarm LED is active due to 3. Double click file.
an opened link of the RA333 TW link 4. A screen opens and if it is the first-time connection between the local PC and
(log code 297 – Traveling wave not
the equipment is made an acknowledgement message will appear in the
identified). The user must reboot the
interface. Answer ൏Y൐ and press ൏ENTER൐;
RPV311 after normalizing the link
connection, otherwise the RPV311 5. Provide the RPV IP address and press ൏ENTER൐;
will not create the TW COMTRADE 6. Enter the password for firmware updating and press ൏ENTER൐;
recordings. Default firmware upgrade password: 12345
7. The entire updating process is performed automatically and can be followed
on the PC screen;
8. The process requires resetting of the equipment. Therefore, answer ൏Y൐.
Equipment will take a few minutes to return to normal operation;
9. After performing the update operation, press ൏ENTER൐ to end.
2.3 SYNC does not light up
The updating operation log can be checked locally in the fut.log file which is in the
folder where the RPV software has been installed.
Make sure that on IRIG-B signal is present at the optical or electrical input, and connect
signal if is not;
Verify the quality of the IRIG-B signal, in Web or Local Interface. If the signal is low
quality, try to use the optical input.
Product Support Tools - PST

The PST is a tool used to obtain internal information about the equipment.
2.4 Date or time incorrect Before using the PST it is necessary to install the dotNet program. To use the PST tool,
install it on the computer by using the installation file.
Set IP and click on the ൏CONNECT൐ button. Once connected, use the following tabs:

Make sure that time zone and daylight-saving time have been properly configured and
Logs: Equipment information can be downloaded. The default location is on the user´s
set correctly if is not.
Desktop. Deselect ONLY CURRENT LOG to obtain all the log files. Click on GET LOGS to start
the process. The OPEN DIR link opens the directory. The UPLOAD FILE link opens the Web
browser for uploading the file to GE´s technical support personnel;
2.5 Time drift throughout operation week
258 RPV311-TM-EN-11.1
RPV311-TM-EN-11.1 257
Chapter 16 – Maintenance and Troubleshooting RPV311 RPV311 Chapter 16 – Maintenance and Troubleshooting

Online: Equipment information is shown. Click on the command in the tree and the All parts and components comprising Reason devices shall be repaired exclusively by
result will show on the right; GE. In case of equipment malfunction the customer shall get in contact with GE’s
Prompt: Type the command and then ൏ENTER൐ to execute (the password will be Contact Centre and never attempt to repair the device by his own.
prompted in the first command). If no interaction is requested, the command will not To request equipment repair service, call GE to check out shipment options and receive
return (use another tool in such a case); the technical assistance order code.
Contact: Shows the contacts for assistance and support by GE. The equipment shall be packed in its original package or a suitable package to protect
against impacts and moisture.

RA331, RA332, and RA333 Troubleshooting


Instructions for Equipment Repair/Service for Service Personnel
The instructions presented in this topic shall only be followed by GE service Personnel.
5.1 MAINS indicator does not light up In case any repair needs to be done, follow the procedure below to ensure the safety of
the operation.
Make sure the terminal is connected; 10. Disconnect power supply;
Make sure there is power supply. 11. Disconnect all other connections leaving the grounding strap to be removed at
the end;
12. Perform a visual inspection to make sure the equipment is isolated;
13. Position the device in place where there is free space to work and make sure
5.2 READY indicator does not light up to install proper working and safety warnings at the location, also keep
If the Ready indicator does not light up, the module has failed the self-test. In such case, available all tools and aids that is going to be used;
contact the technical support personnel. 14. Wait a few minutes so the capacitors may discharge;
15. Disassemble the device by unscrewing the case screws and pulling up the top
side of the case; after that, carry on with the proper repairs. Keep in mind that
5.3 PPS indicator does not light up (Only RA333) disassembling the equipment may expose sensitive electronic circuitry. Take
suitable precautions against electrostatic voltage discharge (ESD) to avoid
damage to the equipment.
Make sure the synchronism signal is present on the processing module;
Make sure the link with the processing module is active.
After the repairs are done, follow the procedure below in order to verify the safe state
of the equipment and to put it back into operation.

5.4 Link with the processing module is not active 6. Reconnect all internal cable that have been removed for the repair;
Make sure that Link and Act indicators are lit; 7. Perform a visual inspection on the device to make sure there are no
Verify that the fiber-optic cables are properly connected in the RA332 and in the remainders of the repair service inside the casing or any other noncompliance;
processing module; 8. Place back the top side of the case and fasten it using the proper screws;
Verify that the processing module is on; 9. Connect the grounding strap and then the power supply to the equipment;
Make sure the connectors for receiving and transmitting data are not mixed; 10. Wait for the equipment to initialize, it will run self-diagnostic routines and if
Verify that the fiber optic cables are in good condition; everything is right the “Ready” LED on its front panel will light up indicating
If possible, do the test using another fiber-optic cable; the equipment is safe and operational;
Make sure that the distance between the processing module and the RA332 does not 11. Follow the procedures in the Chapter 2: Safety Information.
exceed 2 km;
Verify that the type of fiber is in accordance with the specifications.
If the problem persists, contact technical support.
http://www.gegridsolutions.com/alstomenergy/grid/grid/contactcentre

Equipment Return

260 RPV311-TM-EN-11.1
RPV311-TM-EN-11.1 259
RPV311 Chapter 17 – Technical Specifications

1.2 Optical Ethernet Port (optional)


RPV311 Optical Ethernet port

Interface 10BASE-T / 100BASE-TX


Distributed Multifunction Fault Recorder
Bit Rate 10 / 100 Mbps

Chapter 17: Technical Specifications Connector ST

Wavelength 1300nm
This chapter describes the technical specifications of the product.
Fiber Type Multimode 62.5 / 125 μm

RPV311 Specifications Emission Power - 20 dBm

Receiver sensitivity - 32 dBm

1.1 Electrical Ethernet Port Maximum Applicable - 14 dBm


Power
Electrical Ethernet - Ports 1 and 2

Use Configuration, monitoring and GOOSE


1.3 Modem Serial Port
Interface 10BASE-T / 100BASE-TX

Bit Rate 10 / 100 Mbps


Modem Serial Port
Connector RJ 45
Signal level RS232
Isolation Level 1.44 KVdc
Bitrate 1200, 2400, 4800, 9600, 19200, 38400 bps

Databits 7 or 8

Electrical Ethernet - Process Bus Port (Sampled Values) Stopbits 1 or 2

Use IEC 61850-9-2LE Sampled Values and Parity None, even, odd
GOOSE
Connector DB9 (female), standard DTE
Interface 10BASE-T / 100BASE-TX
Isolation Level 1.44 KVdc
Bit Rate 100 Mbps

Connector RJ 45

Isolation Level 1.44 KVdc

261 RPV311-TM-EN-10 262 RPV311-TM-EN-11.1


Chapter 17 – Technical Specifications RPV311 RPV311 Chapter 17 – Technical Specifications

1.4 TTL IRIG Input 1.6 Dry-contact Relay Outputs

TTL IRIG Dry-contact Relay Outputs

Signal IRIG-B004 Max Voltage 250 Vdc

Minimum voltage input 4.20 V Max Current 1A

Maximum input voltage 9.80 V Load Resistive

Impedance 200 Ω 1 normally closed


Contact Numbers
Connector PCB pluggable 3 normally open

Isolation Level 1.44 KVdc Isolation Level 3.3 KVdc

1.5 Optical IRIG-Input (optional)


1.7 Fiber-optic Links
Optical IRIG Fiber-optic Links

Signal IRIG-B004 Wavelength 1300 nm

Wavelength 820 nm Fiber Type Multimode 62.5 / 125 μm

Fiber type Multimode 62.5 / 125 μm Connector ST

Connector ST Emission Power - 20 dBm

Sensitivity - 24 dBm Receiver sensitivity - 32 dBm

Maximum Applicable - 14 dBm


Power

264 RPV311-TM-EN-11.1
RPV311-TM-EN-11.1 263
Chapter 17 – Technical Specifications RPV311 RPV311 Chapter 17 – Technical Specifications

1.8 Power Supply 1.10 Type Tests RPV311


Power Supply EMC tests were performed according to IEC 60255-26 referring to the following
standards
Nominal voltage range 125-250 V dc, 110-240 V ac Type Tests RPV311

Maximum voltage range 102-300 V dc, 88-264 V ac Test Standard Level

Frequency 50 / 60 Hz, ± 3 Hz Electrostatic IEC 61000-4- 8kV contact / 15KV air (level 4)
discharge 2:2008
MAX 60 VA
Power consumption IEC 61000-4- 10 V/m (level 3)
Typically 50W RF immunity
3:2010

Isolation Level 3.3 KVdc Fast IEC 61000-4- 2 KV @ 5KHz (level 3)


transient 4:2012
disturbance

Power supply specifications 24/48 Vdc IEC 61000-4- Differential mode: 1 kV


Surge 5:2005
immunity Common mode: 2 kV
Operating nominal voltage 24/48 Vdc
(level 3)

Operating voltage range 20 – 75 Vdc


Conducted IEC 61000-4- 10V
RF immunity 6:2008
Power Consumption MAX 50W
Power IEC 61000-4- 30A/m continuous - 300A/m @ 1s.
Isolation Level 3.3 KVdc magnetic 8:2009
immunity

AC and DC voltage dips


Test level: 0% residual voltage
1.9 Environmental Conditions Duration time
a.c.: 1 cycle
d.c.: 16.6ms

Environmental Conditions Test level: 40% residual voltage


Voltage dip,
Duration time
short IEC 61000-4-
Operating temperature range - 40… +50 °C (or –13°F to +122°F) a.c.: 12 cycle
interruptions 11:2004 d.c.: 200ms
and voltage
Maximum operating altitude 2000 m (6560 ft) variation IEC 61000-4-
immunity 29:2000 Test level: 70% residual voltage
Relative humidity 5 … 95 %, noncondensing tests Duration time
a.c.: 30 cycle
d.c.: 500ms
As tested per 60068-2-1 -40°C
AC and DC voltage interruptions
As tested per 60068-2-2 +55°C Test level: 0% residual voltage
Duration time
a.c.: 300 cycles

266 RPV311-TM-EN-11.1
RPV311-TM-EN-11.1 265
Chapter 17 – Technical Specifications RPV311 RPV311 Chapter 17 – Technical Specifications

d.c.: 5s 30 to 230MHz - 50dB(μV/m) quasi peak


at 3m
Test frequency: Test frequency: 16,7 Hz,
230 to 1000MHz - 57dB(μV/m) quasi
50 Hz and 60 Hz
peak at 3m
Test Voltage: 100V (differential mode)
with 1 sec dwell time ƒ Radiated emission
Limits:
-Coupling resistor 100 Ω

-Coupling capacitor 0,047μF 1 to 3GHz - 56dB(μV/m) average;


Conducted
IEC 61000-4- 76dB(μV/m) peak at 3m
RF immunity,
16:1998+A2:2009 300V (common mode) with 1 sec dwell
0 to 150 kHz 3 to 6GHz - 60dB(μV/m) average;
time
80dB(μV/m) peak at 3m
-Coupling resistor 200 Ω
The test frequency is defined based on
-Coupling capacitor 0,47μF Radio the maximum internal frequency of
CISPR22:2008
disturbance
Number of repetition: 3 equipment.

(Level 4) ƒ Conducted emission


Limits:

0.15 to 0.50MHZ - 79dB(μV) quasi


peak; 66dB(μV) average

0.5 to 30MHz - 73dB(μV) quasi peak;


60dB(μV) average

Class 2
Test level: 15 % of rated d.c. value
Horizontal Axes:
Voltage IEC 61000-4- Test frequency: 120Hz, sinusoidal Frequency Range: 1Hz – 35Hz
ripple 17:1999 waveform. Cross-over Frequency: 8.14Hz
(Level 4) Severity: 7.5mm zero-peak
displacement below 8.14Hz
Damped Voltage oscillation frequency: 1MHz 2g zero-peak acceleration above 8.14Hz
oscillatory Differential mode: 1kV peak voltage;
IEC 61000-4- Sweep Rate: 1 Octave/minute
wave
18:2006 Common mode 2,5kV peak voltage IEC 60255-21-3: Number of Sweep Cycles: 1
immunity
test (Level 3) Seismic 1995 Configuration: Operational throughout
Vertical Axis:
Shut-down ramp: 60s Frequency Range: 1Hz – 35Hz
--- Gradual Startup Power off: 5m Cross-over Frequency: 8.42Hz
Severity: 3.5mm zero-peak
Start-up ramp: 60s
displacement below 8.14Hz
1g zero-peak acceleration above 8.14Hz
Radio- Radiated emission
frequency CISPR11:2009 Sweep Rate: 1 Octave/minute
disturbance Limits: Number of Sweep Cycles: 1
Configuration: Operational throughout

268 RPV311-TM-EN-11.1
RPV311-TM-EN-11.1 267
Chapter 17 – Technical Specifications RPV311 RPV311 Chapter 17 – Technical Specifications

1.11 Safety Tests


Safety tests

Safety IEC 61010-1

IEC 60255-5 Inpulse - 5KV

Dielectric withstand - 3,3KVDC for 60 seconds

Insulation > 100M Ω

1.12 Environmental tests


Environmental tests

Cold IEC 60068-2-1 -40°C, 16 hours (Cold)

Dry heat IEC 60068-2-2 +55°C, 16 hours (Dry heat)

Damp heat IEC 60068-2-30 95% no condensation, 55°C (Damp


heat)

Change of IEC 60068-2-14 -40°C to 55ºC / 9 hours / 2 cycles


temperature (Change of temperature)

Vibration IEC 60255-21-1 Class 2 (Vibration)

Shock IEC 60255-21-2 Class 1 (Shock)

1.13 Enclosure Protection IEC 60529

Enclosure Protection IEC 60529

Front flush mounted with panel IP40

Rear and sides IP20

270 RPV311-TM-EN-11.1
RPV311-TM-EN-11.1 269
Chapter 17 – Technical Specifications RPV311 RPV311 Chapter 17 – Technical Specifications

1.14 Dimensions

RPV311 dimensions

Height (front panel) 133.55 mm (3 U)

Height (rear) 86 mm

Width (front panel) 482.6 mm (19’’)

Width (rear) 427 mm

Depth 260 mm

Weight < 4.0 kg

The RPV311 dimensions are shown in Figure 137.


Dimension in accordance to IEC 60297-3.

Figure 137: RPV311 Dimensions

272 RPV311-TM-EN-11.1
RPV311-TM-EN-11.1 271
Chapter 17 – Technical Specifications RPV311 RPV311 Chapter 17 – Technical Specifications

RA331, RA332, and RA333 Specifications 2.3 Voltage Inputs


Voltage inputs specifications (50/60 Hz)
2.1 Analog Acquisition (50/60 Hz)
Nominal Voltage (ܸ௡ ) 115 V

Voltage range 0.02-230 V


Analog acquisition specifications (50/60Hz)
Analog Input Accuracy ± 0.1 % of FS magnitude range
Resolution 16 bits
Impedance > 200 kΩ
Acquisition Rate 256 ppc
Burden Vn < 0.1 VA
Bandwidth DC to 3.0 kHz
Continuous Overload 230 V (2 x ܸ௡ )
Attenuation @ 3000 Hz < 0.1 dB
Maximum Overload (1 s) 460 V (4 x ܸ௡ )
Attenuation @ 6400 Hz > 30 dB

Time skew 0 μs

Frequency Tracking Range Nominal Frequency ±5Hz 2.4 Current Inputs

Current inputs specifications (50/60Hz)


2.2 Analog Acquisition (High-speed – Only RA333 Module)
CORTEC option 1 2 5 6 T

5A
Analog acquisition RA333 Nominal Current (‫ܫ‬௡ ) 1A 5A (Measurement
CT)
Resolution 8 bits
0.01… 20 0.01…40 A 0.05… 100 A 0.05…200 A
Current range 0.01… 14 A
Sampling frequency 5 MHz A (20In) (240In) (20In) (40In)

Time skew 0 μs Analog Input Accuracy ± 0.1 % FS

Resistance 15 mΩ 5 mΩ 3 mΩ 1 mΩ 15 mΩ

Burden In < 0.02 VA

Continuous overload
10 A (10 x ‫ܫ‬௡ ) 20 A (4 x ‫ܫ‬௡ ) 10 A (2 x ‫ܫ‬௡ )
(rms)

AC current thermal
40 A (40 x 100 A (100 x
withstand (Ith rms for 1 200 A (40 x ‫ܫ‬௡ ) 40 A (8 x ‫ܫ‬௡ )
‫ܫ‬௡ ) ‫ܫ‬௡ )
sec)

274 RPV311-TM-EN-11.1
RPV311-TM-EN-11.1 273
Chapter 17 – Technical Specifications RPV311 RPV311 Chapter 17 – Technical Specifications

2.5 Current clamps inputs specification Impedance 82 kΩ 180 kΩ 15 kΩ

Burden < 0.25 W < 0.5 W < 0.2 W


Current clamp inputs
Continuous 240 V 340 V 100 V
Nominal Current ( ୬ ) 100 mA (Clamps) Overload ¹

Current range 0.005 … 0.1 A ଵ The digital inputs are protected against continuous reverse polarity for the nominal
voltage
Analog Input Accuracy ± 1 % FS

Impedance 1Ω
2.8 Fiber-optic Links
Burden < 0.01 VA

Continuous Overload 0.5 A


Fiber-optic links specifications
Maximum Overload (1 s) 2A
Wavelength 1300 nm

2.6 DC Transducer Inputs Fiber Type Multimode 62.5 / 125 μm

Connector ST

DC Transducer inputs specifications Emission Power - 20 dBm

Full Scale ± 10 V ± 20 mA Receiver sensitivity - 32 dBm

Input range - 13,7 to + 13,7 V - 32 to 32 mA Maximum Applicable Power - 14 dBm

Analog Input ± 0.1 % of FS magnitude ± 1 % of FS magnitude range


Accuracy range
2.9 RA33x Power Supply
Impedance > 5 kΩ 10 Ω
RA33x Power supply specifications

Nominal voltage range 100-250 V dc, 110-240 V ac


2.7 Binary Inputs
Maximum voltage range 80-300 V dc, 88-264 V ac

Frequency 50 / 60 Hz, ± 3 Hz
Binary Inputs specifications
RA331 and RA332 Power MAX 20 VA
Nominal Voltage 125 Vdc 250 Vdc 24 / 48 Vdc Consumption

Level Low 40 V 110 V 08 V RA333 Power Consumption MAX 30 VA

Level High 85 V 170 V 17 V

276 RPV311-TM-EN-11.1
RPV311-TM-EN-11.1 275
Chapter 17 – Technical Specifications RPV311 RPV311 Chapter 17 – Technical Specifications

Power supply specifications 24/48 Vdc Differential mode: 1KV


Surge
Operating nominal voltage 24/48 Vdc IEC 61000-4-5:2005 Common mode: 2KV
immunity
(level 3)
Operating voltage range 18 – 75 Vdc
Conducted 10V
IEC 61000-4-6:2008
Power Consumption MAX 30W RF immunity

Power 30A/m continuos – 300A/m @ 1s.


magnetic IEC 61000-4-8:2009
immunity

A.C. and d.c. voltage dips


2.10 Environmental Conditions
Test level: 0% residual voltage
RA33x Environmental Conditions
Duration time
Operating temperature range -40 … +55 °C
a.c.: 1 cycle

Maximum operating altitude 2000 m (6560 ft) d.c.: 16,6ms

Relative humidity 5 … 95 % noncondensing


Test level: 40% residual voltage
Tested as per 60068-2-1 -40°C
Duration time
Tested as per 60068-2-2 +85°C
a.c.: 12 cycles
Voltage dip,
short d.c.: 200ms
interruptions IEC 61000-4-11:2004
2.11 Type Tests RA33x and voltage
variation IEC 61000-4-29:2000
immunity Test level: 70% residual voltage
EMC tests were performed according to IEC 60255-26 referring to the following tests
standards Duration time

a.c.: 30 cycles

Type Tests RA33x d.c.:500ms

Test Standard Level


A.C. and d.c. voltage interruptions
Electrostatic 8kV contact / 15KV air (level 4)
IEC 61000-4-2:2008
discharge Test level: 0% residual voltage

RF immunity IEC 61000-4-3:2006 10 V/m (level 3) Duration time

a.c.: 300 cycles


Fast 2 KV @ 5KHz (level 3)
transient IEC 61000-4-4:2012 d.c.: 5s
disturbance

278 RPV311-TM-EN-11.1
RPV311-TM-EN-11.1 277
Chapter 17 – Technical Specifications RPV311 RPV311 Chapter 17 – Technical Specifications

Test frequency: 16,7 Hz, 50 Hz and 60 frequency of the equipment. On


Hz RA33x, the maximum internal
frequency is 100 MHz. For this case,
Test Voltage: 100V (differential
the levels of CISPR 11 satisfy the
mode) with 1 sec dwell time
normative IEC 60255-26.
-Coupling resistor 100 Ω
Conducted emission

Conducted -Coupling capacitor 0,047μF


IEC 61000-4- Limits:
RF immunity,
16:1998+A2:2009 300V (common mode) with 1 sec
0 to 150 kHz 0.15 to 0.50MHZ – 79dB(μV) quasi
dwell time
peak; 66dB(μV) average
-Coupling resistor 200 Ω
0.5 to 30MHz – 73dB(μV) quasi peak;
-Coupling capacitor 0,47μF 60dB(μV) average

Number of repetition: 3 Class 2


Horizontal Axes:
(Level 4)
Frequency Range: 1Hz – 35Hz
Cross-over Frequency: 8.14Hz
Test level: 15 % of rated d.c. value
Severity: 7.5mm zero-peak
Voltage Test frequency: 120Hz, sinusoidal displacement below 8.14Hz
IEC 61000-4-17:1999
ripple waveform. 2g zero-peak acceleration above
(Level 4) 8.14Hz
Sweep Rate: 1 Octave/minute
Damped Voltage oscillation frequency: 1MHz Number of Sweep Cycles: 1
oscillatory
wave IEC 61000-4-18:2006 Differential mode: 1kV peak voltage; IEC 60255-21-3: Configuration:Operational
immunity Seismic 1995 throughout
test Common mode 2,5kV peak voltage
Vertical Axis:
Frequency Range: 1Hz – 35Hz
Gradual Startup Shut-down ramp: 60s
Cross-over Frequency: 8.42Hz
--- Power off: 5m Severity: 3.5mm zero-peak
displacement below 8.14Hz
Start-up ramp: 60s
1g zero-peak acceleration above
8.14Hz
Radiated emission
Sweep Rate: 1 Octave/minute
Limits: Number of Sweep Cycles: 1
Radio- Configuration: Operational
30 to 230MHz – 50dB(μV/m) quasi
frequency CISPR11:2009
peak at 3m throughout
disturbance
230 to 1000MHz – 57dB(μV/m) quasi
peak at 3m

Radiated emission
Radio
CISPR22:2008
disturbance The definition of the limit frequency
is based on the maximum internal
280 RPV311-TM-EN-11.1
RPV311-TM-EN-11.1 279
Chapter 17 – Technical Specifications RPV311 RPV311 Chapter 17 – Technical Specifications

2.12 Safety Tests 2.15 Dimensions

Safety tests
RA33x dimensions
Safety IEC 61010-1
Height (front panel) 222 mm (5 U)
IEC 60255-5 Inpulse – 5KV
Height (rear) 200 mm
Dielectric withstand – 3,3KVDC for 60

seconds Width (front panel) 222 mm ( 19’’)

Insulation > 100M Ω


Width (rear) 214 mm

Depth 100 mm

2.13 Environmental tests Weight < 3.0 kg

Environmental tests The RA331, RA332, and RA333 dimensions are shown in Figure 138.

IEC 60068-2-1 -40°C, 16 hours (Cold)

IEC 60068-2-2 +85°C, 16 hours (Dry heat)

IEC 60068-2-30 95% no condensation, 55°C (Damp heat)

IEC 60068-2-14 -40°C to 85ºC / 9 hours / 2 cycles (Change of


temperature)

IEC 60255-21-1 Class 2 (Vibration)

IEC 60255-21-2 Class 1 (Shock)

2.14 Enclosure Protection IEC 60529


Enclosure Protection IEC 60529

Front flush mounted with IP54


panel

Sides IP20

Rear IP10

282 RPV311-TM-EN-11.1
RPV311-TM-EN-11.1 281
Chapter 17 – Technical Specifications RPV311 RPV311 Chapter 17 – Technical Specifications

2.16 Current Clamps

Current clam specification

Manufacturer / Model AEMC / MN312

Dynamic range 0.1 A … 100 A

Output 1mA/A

Frequency response 40 Hz … 10 kHz

2 % ± 0.02 mA (0.1 to 1 A)

Accuracy 1 % ± 0.02 mA (1 to 80 A)

2 % ± 0.02 mA (80 to 100 A)

Jaw opening 21 mm

Maximum conductor size 20 mm

Figure 138: RA331, RA332 and RA333 dimensions Weight 180 g

Operating temperature - 10 … 55 °C

Figure 139: AEMC / MN312 (PN 2468) current clamps

284 RPV311-TM-EN-11.1
RPV311-TM-EN-11.1 283
Chapter 18 – Wiring Diagrams RPV311

RPV311
3-element (Phases A, B and
neutral) connection: in this case,
Distributed Multifunction Fault Recorder the fourth element is synthesized
of the values measured by the
other elements. The three
elements are equivalent to the
Chapter 18: Wiring Diagrams values applied to the equipment.

This chapter contains the all the possible wiring diagrams for the analogue inputs. For
further details on the inputs, refer to Chapter 15: Installation.

3-element (Phases A, C and


Connection Diagrams of the Voltage Inputs neutral) connection: in this case,
the fourth element is derived of
The RPV311 provides the capability for making some different voltage signal the values measured by the other
connections for a 3-phase circuit: elements. The three elements are
equivalent to the values applied to
the equipment.

Connection diagram of the voltage inputs

3-element (Phases B, C and


neutral) connection: in this case,
the fourth element is derived of
4-element connection: in this
the values measured by the other
case, the values shown are
elements. The three elements are
equivalent to the voltages of
equivalent to the values applied to
phases A, B and C, and to the
the equipment.
neutral voltage applied to the
equipment.

2-element connection: in this


case, the neutral voltage is zero,
and the three phase-to-ground
voltage are computed based on
3-element (Phases A, B and C) the two line-to-line voltages
connection: in this case, the applied to the equipment.
fourth element is derived of the
values measured by the other
elements. The three elements are
equivalent to the values applied to
the equipment In circuits of 1 element, the measurements can be in two different ways:
An isolated phase or neutral measurement: If the element is a phase, only the voltage
related to this channel is measured considering the off-set compensation. If the
element is a neutral, the voltage related to this channel is measured without the off-set
compensation.

RPV311-TM-EN-11.1 286
Appendix A – Equipment Log RPV311 Chapter 18 – Wiring Diagrams RPV311

A 3-Phase synthesis: The magnitude for the 3-phases is considered with the same value The RPV311 provides the capability for connecting some different current signal
as that of the channel measured and balanced (i.e., angles with 120º between each connections for a 3-phase circuit:
other).

Connection diagram of the current inputs


Connection diagram for 1 voltage element connection

4-element connection: in this


1-element connection: case, the values shown are
Connection diagram of 1 equivalent to the voltages of
element (phase A, B or C). phases A, B and C, and to the
neutral voltage applied to the
equipment.

1-element connection:
Connection diagram of 1
element (neutral).
3-element (Phases A, B and C)
connection: in this case, the
fourth element is derived of the
values measured by the other
elements. The three elements
In all cases, the equipment will compute the phase-to-ground voltage and the neutral are equivalent to the values
voltage. applied to the equipment

Connection Diagrams of the TW Inputs


3-element (Phases A, B and
The RPV311 provides the capability for connecting one 3-phase circuit (phases A, B, and neutral) connection: in this case,
C): the fourth element is derived of
the values measured by the
other elements. The three
elements are equivalent to the
Connection diagram for TW inputs values applied to the equipment.

3-element (Phases A, B and C)


connection: in this case, the 3-element (Phases A, C and
three elements are equivalent to neutral) connection: in this case,
the values of TW voltage. the fourth element is derived of
the values measured by the
other elements. The three
elements are equivalent to the
values applied to the equipment.

Connection Diagrams of the Current Inputs

RPV311-TM-EN-11.1 288
RPV311-TM-EN-11.1 287
Appendix A – Equipment Log RPV311
Appendix A – Equipment Log RPV311

RPV311
3-element (Phases B, C and
neutral) connection: in this case,
the fourth element is derived of
Distributed Multifunction Fault Recorder
the values measured by the
other elements. The three
elements are equivalent to the Appendix A
values applied to the equipment.

Equipment Log
The equipment log contains information about:
2-element connection: in this
x Threshold violations, fault and disturbance triggers and data recording;
case, the neutral voltage is zero,
and the three phase-to-ground x Data record transfer (including the IP address to which data has been
voltage are computed based on transferred);
the two line-to-line voltages x Access to the unit's configuration pages (including IP address of which the
applied to the equipment access was performed);
x Alarms and the results of auto-diagnosis routines;
x Power-up and shutdown.

In circuits of 1 element, the measurements can be in two different ways:


The equipment log cannot be erased by the user. Its capacity is enough for
An isolated phase or neutral measurement: If the element is a phase, only the current
approximately 5 years of typical use, with past events being erased if memory space is
related to this channel is measured considering the off-set compensation. If the
needed.
element is a neutral, the current related to this channel is measured without the off-set
compensation.
A 3-Phase synthesis: The magnitude for the 3-phases is considered with the same value
as that of the channel measured and balanced (i.e., angles with 120º between each Log Event Cause
other).
000 Internal failure Hardware or processing failure
Connection diagram for 1 current element connection

001 Invalid key The key applied to the


equipment is not valid
1-element connection:
Connection diagram of 1 003 Insufficient processing High volume of processing data
element (phase A, B or C). time and events in a short period of
time

004 Data Acquisition Failure Failure on data acquisition


1-element connection:
Connection diagram of 1 010 Power up Equipment power-up
element (neutral).
011 Power off Equipment power-off

012 Auto power-off (primary Battery operated power time


In all cases, the equipment will compute the line current and the neutral current. power failure) run-out

RPV311-TM-EN-11.1 290
RPV311-TM-EN-11.1 289
Appendix A – Equipment Log RPV311 Appendix A – Equipment Log RPV311

013 Emergency power-off Battery charge below expected, 120 DST started [at: ] Equipment started operating at
(low battery) equipment shut off the daylight saving time
automatically
121 DST ended [at: ] Equipment stopped operating
020 Primary power OK Primary power supply voltage at the daylight saving time
equipment
129 Leap second added [at: ] Add 1 second to the UTC time
021 Primary power NOK Battery backup equipment
190 Internal clock updated by Equipment synchronization by
029 Battery status [value: ] Battery voltage indication fallback SNTP server SNTP time server

030 Temperature normal Temperature return to normal 191 Internal clock updated by Equipment time reference
[value: ] values IRIG-B provided by IRIG-B signal

031 Temperature high [value: Internal temperature high 192 Internal clock running The internal clock is running
] without external without external reference
reference
039 Temperature status Equipment temperature
[value: ] indication 200 Configuration changed Equipment set up changed
[revision:]
050 Equipment ready Equipment normal operation
202 Default configuration The default configuration was
051 Equipment not ready Equipment is not operational reestablished reestablished

100 IRIG-B signal Equipment is connected to


IRIG-B signal

101 No IRIG-B signal Equipment is not connected to


IRIG-B signal

102 Equipment sync Equipment synchronization of


IRIG-B external timing
reference signal

103 Equipment unsync Loss of synchronization with


IRIG-B external timing
reference

104 Out-of-sync IRIG-B frame Equipment received out of sync


received [at: ] IRIG-B signal data

105 Missing IRIG-B frame [at: Equipment did not receive IRIG-
] B signal data

106 Time quality changed The time quality was changed


[Time quality: ]

109 IRIG-B [type: 00x] Indication of IRIG-B type


connected

RPV311-TM-EN-11.1 292
RPV311-TM-EN-11.1 291
Appendix A – Equipment Log RPV311 Appendix A – Equipment Log RPV311

203 Default configuration Default settings reset via the 295 Invalid acquisition module Exist an invalid acquisition
reestablished by local local interface [slot: ] module
interface
296 Invalid conditioning module Exist an invalid conditioning
210 Default access reestablished Factory set access password [slot: ] module
by local interface reset at local interface
300 Invalid Ethernet cross- Ethernet cross-trigger
211 Default access reestablished The default parameters to trigger communication was not
access the equipment was validated by equipment
reestablished
350 Operation user access via Start of operation user access
250 Firmware upgrade [revision: Firmware upgrade indication web [user: ; source: ]
]
351 Operation user access End of operation user access
270 Sequential sampled values Indicates loss of Sampled logout via web [user: ;
loss in [sv stream] Values (SV) packets source: ]

271 Sampled values loss in [sv Indicates loss of Sampled


stream] Values (SV) connections

273 Stream [sv stream] up Indicates that the RPV311 is


reading Sampled Values (SV)

280 Link down The link connection was down

281 Link up The link connection was up

282 Thresholds related to inputs The thresholds related to


of link disabled inputs of the link was disabled

283 Thresholds related to inputs The thresholds related to


of link enabled inputs of the link was enabled

284 All links up All the links was up

290 Acquisition module Date of the acquisition module


calibration date [slot:%p; calibration
date:%p]

291 Unused acquisition module Exist an unused acquisition


[slot: ] module

292 Unused conditioning Exist an unused conditioning


module [slot: ] module

293 Missing acquisition module An acquisition module was


[slot: ] missing

294 Missing conditioning An conditioning module was


module [slot: ] missing

RPV311-TM-EN-11.1 294
RPV311-TM-EN-11.1 293
Appendix A – Equipment Log RPV311 Appendix A – Equipment Log RPV311

352 Operation user access Invalid password or user 418 Disturbance record auto Disturbance record auto
failure via web [user: ; indication upload [name: ; user: ; upload indication
source: ] destination: ]

355 Configuration user access Start of configuration user 419 Auto upload failure [name: Invalid password or user
via web [user: ; source: ] access ; user: ; destination: ] indication

356 Configuration user access End of configuration user 504 Traveling wave record Traveling wave record erased
logout via web [user: ; access removed [name: ]
source: ]
505 Steady-state record Steady-state record erased
357 Configuration user access Invalid password or user removed [name: ]
failure via web [user: ; indication
source: ] 506 SOE record removed SOE record erased
[name: ]
405 Steady-state record Steady-state record
download [name: ; user: ; downloaded by user 507 Fault record removed Fault record removed
source: ] [name: ]

406 SOE record download SOE record downloaded by 508 Disturbance record Disturbance record removed
[name: ; user: ; source: ] user removed [name: ]

407 Fault record download Fault record downloaded by Record memory usage limit Recorder memory capacity
[name: ; user: ; source: ] user 510
exceeded exceeded 90 % capacity

408 Disturbance record Disturbance record Traveling wave recorder Traveling wave recorder
download [name: ; user: ; downloaded by user 514 memory usage limit memory capacity exceeded
source: ] exceeded 90 % capacity

409 Traveling wave record Traveling wave record Steady-state recorder Steady-state recorder
download [name: ; user: ; downloaded by user 515 memory usage limit memory capacity exceeded
source: ] exceeded 90 % capacity

414 Traveling wave record auto Traveling wave record auto SOE recorder memory SOE recorder memory
upload [name:; user: ; uploaded 516 usage limit exceeded capacity exceeded 90 %
destination: ] capacity

415 Steady-state record auto Steady-state record auto Fault recorder memory Fault recorder memory
upload [name: ; user: ; upload indication 517 usage limit exceeded capacity exceeded 90 %
destination: ] capacity

416 SOE record auto upload SOE record auto upload Disturbance recorder Disturbance recorder
[name: ; user: ; destination: indication 518 memory usage limit memory capacity exceeded
] exceeded 90% capacity

417 Fault record auto upload Fault record auto upload Record memory usage limit Return of memory capacity
[name: ; user: ; destination: indication 520 no longer exceeded below 90 % with deletion of
] older records

RPV311-TM-EN-11.1 296
RPV311-TM-EN-11.1 295
Appendix A – Equipment Log RPV311 Appendix A – Equipment Log RPV311

Traveling wave recorder Return of memory capacity All disturbance records Request for removal of all
524 memory usage limit no below 90 % with deletion of 580 scheduled manually for disturbance records by user
longer exceeded older records removal

Steady-state recorder Return of memory capacity Oldest disturbance records Request for removal of oldest
525 memory usage limit no below 90 % with deletion of 581 scheduled automatically for disturbance records
longer exceeded older steadystate records removal automatically

SOE recorder memory Return of memory capacity Steady-state record Steady-state record creation
526 usage limit no longer below 90 % with deletion of 590 available [name: ; time
exceeded older SOE records stamp: ; duration: ]

Fault recorder memory Return of memory capacity SOE record available SOE record creation
527 usage limit no longer below 90 % with deletion of 591 [name: ; time stamp: ;
exceeded older fault records duration: ]

All traveling wave records Request for removal of all Continuous record available Continuous record creation
540 scheduled manually for Traveling wave records by 592 [name: ; trigger: ; cause: ;
removal user duration: s; md5sum: ]

Oldest traveling wave Request for removal of oldest Continuous record updated Continuous record update
541 records scheduled traveling wave records 593 [name: ; trigger: ; cause: ;
automatically for removal automatically duration: ; md5sum: ]

Disturbance recorder Return of memory capacity Traveling wave recorder Traveling wave recorder
528 memory usage limit no below 90 % with deletion of 600 threshold exceeded [at: ; preset threshold exceeded
longer exceeded older disturbance records threshold: ]

All steady-state records Request for removal of all Traveling wave recorder Return to normal level for the
550 scheduled manually for steady-state records by user 601 threshold no longer traveling wave recorder
removal exceeded [at: ; threshold: ]

Oldest steady-state records Request for removal of oldest Maximum traveling wave Indicates the maximum
551 scheduled automatically for steady-state records 602 recorder threshold time traveling wave recorder
removal automatically exceeded [at: ; threshold: ] threshold time was exceeded

All SOE records scheduled Request for removal of all Traveling wave trigger Indicates the detection of a
560
manually for removal SOE records by user 609 detected [at: ] traveling wave recorder
trigger
Oldest SOE records Request for removal of oldest
561 scheduled automatically for SOE records automatically Traveling wave recording Start of traveling wave
610
removal started [at: ] recording threshold exceeded

All fault records scheduled Request for removal of all


570
manually for removal fault records by user
Traveling wave recording End of traveling wave
614 finished [at: ] recording threshold
Oldest fault records Request for removal of oldest exceeded
571 scheduled automatically for fault records automatically
removal

RPV311-TM-EN-11.1 298
RPV311-TM-EN-11.1 297
Appendix A – Equipment Log RPV311 Appendix A – Equipment Log RPV311

Traveling wave recording Trigger rejected due to Fault recording started [at: Start of fault recording
710
refused (equipment excess consecutive ] threshold exceeded
619
unsync) [at: ] triggering protection
enabled Fault recording extended Fault recording extended
712
[at: ] due to threshold exceeded
Traveling wave recorder Start of traveling wave
Ethernet cross-trigger recorder Ethernet cross- Fault recording finished End of fault recording
630 714
started [at: ; identifier: ; trigger detection [at: ] threshold exceeded
location: ; owner: ]
Fault recording timed-out Threshold exceeded the
Traveling wave recorder End of traveling wave 716 [at: ] maximum preset recording
Ethernet cross-trigger recorder Ethernet cross- time
631
finished [at: ; identifier: ; trigger detection
location: ; owner: ]
Fault recording refused Trigger rejected due to
[at: ] excess consecutive
Traveling wave recorder Traveling wave recorder 720
triggering protection
Ethernet cross-trigger Ethernet crosstrigger enabled
632
timed-out [at: ; identifier: ; exceeded the maximum
location: ; owner: ] preset recording time
Fault recording disabled Recording disabled due to
721 [at: ; timeout: s] fault recorder repeat in
Start of traveling wave Traveling wave recorder preset time period
recorder Ethernet cross- Ethernet crosstrigger
633 trigger ignored [at: ; ignored due to another
Fault recording enabled Recorder enable due to
identifier: ; location: ; cross-trigger being 722
[at: ] threshold exceeded
owner: ] recorded by equipment

Fault recorder Ethernet Start of fault recorder


End of traveling wave Ignored traveling wave
crosstrigger started [at: ; Ethernet cross-trigger
recorder Ethernet cross- recorder Ethernet cross- 730
identifier: ; location: ; detection
634 trigger ignored [at: ; trigger finished
owner: ]
identifier: ; location: ;
owner: ]
Fault recorder Ethernet End of fault recorder
crosstrigger finished [at: ; Ethernet cross-trigger
Traveling wave record Indicates the traveling 731
identifier: ; location: ; detection
650 available [name: ; trigger: ; wave record creation
owner: ]
cause ; duration: ]

Fault recorder Ethernet Fault recorder Ethernet


Fault recorder threshold Fault recorder preset
700 crosstrigger timed-out [at: crosstrigger exceeded the
exceeded [at: ; threshold: ] threshold exceeded 732
; identifier: ; location: ; maximum preset recording
owner: ] time
Fault recorder threshold Return to normal level for
701 no longer exceeded [at: ; the fault recorder
Start of fault recorder Fault recorder Ethernet
threshold: ]
Ethernet cross-trigger crosstrigger ignored due to
733
ignored [at: ; identifier: ; another cross-trigger being
Maximum fault recorder Indicates the maximum location: ; owner: ] recorded by equipment
702 threshold time exceeded fault recorder threshold
[at: ; threshold] time was exceeded
End of fault recorder Ignored fault recorder
Ethernet cross-trigger Ethernet cross-trigger
Fault recorder trigger Indicates the detection of a 734
709 ignored [at: ; identifier: ; finished
detected [at: ] fault recorder trigger location: ; owner: ]

RPV311-TM-EN-11.1 300
RPV311-TM-EN-11.1 299
Appendix A – Equipment Log RPV311 Appendix A – Equipment Log RPV311

Fault recorder manual Indicates a manual fault Disturbance recording Recording disabled due to
740 trigger detected [at: ] recorder trigger activated disabled [at: ; timeout: s] disturbance recorder
821
by user repeat in preset time
period
Fault recorder manual Manual fault recorder
741 trigger ignored [at: ] trigger activated by user Disturbance recording Recorder enable due to
822
was ignored enabled [at: ] threshold exceeded

Fault record available Indicates the fault record Disturbance recorder Start of disturbance
750 [name: ;trigger: ;cause: creation Ethernet cross-trigger recorder Ethernet cross-
830
;duration: ] started [at: ; identifier: ; trigger detection
location: ; owner: ]
Disturbance recorder Fault recorder preset
800 threshold exceeded [at: ; threshold exceeded Disturbance recorder End of disturbance
threshold: ] Ethernet cross-trigger recorder Ethernet cross-
831
finished [at: ; identifier: ; trigger detection
Disturbance recorder Return to normal level for location: ; owner: ]
801 threshold no longer the disturbance recorder
exceeded [at: ; threshold: ] Disturbance recorder Disturbance recorder
Ethernet cross-trigger Ethernet cross-trigger
832
Maximum disturbance Indicates the maximum timed-out [at: ; identifier: ; exceeded the maximum
recorderthreshold time disturbance recorder location: ; owner: ] preset recording time
802
exceeded [at: ; threshold: ] threshold time was
exceeded Start of disturbance Disturbance recorder
recorder Ethernet cross- Ethernet cross-trigger
Disturbance recorder Indicates the detection of a 833 trigger ignored [at: ; ignored due to another
809 trigger detected [at: ] disturbance recorder identifier: ; location: ; cross-trigger being
trigger owner: ] recorded by equipment

Disturbance recording Start of disturbance End of disturbance Ignored disturbance


810 started [at: ] recording threshold recorder Ethernet cross- recorder Ethernet cross-
exceeded 834 trigger ignored [at: ; trigger finished
identifier: ; location: ;
owner: ]
Disturbance recording Disturbance recording
812 extended [at: ] extended due to threshold
exceeded Disturbance recorder Indicates a manual
840 manual trigger detected disturbance recorder
[at: ] trigger activated by user
Disturbance recording End of disturbance
814 finished [at: ] recording threshold
exceeded Disturbance recorder Manual disturbance
841 manual trigger ignored [at: recordertrigger activated
] by user was ignored
Disturbance recording Threshold exceeded the
816 time-out [at: ] maximum preset recording
time Disturbance record Indicates the disturbance
850 available [name: ; trigger: ; record creation
cause: ; duration: ]
Disturbance recording Trigger rejected due to
refused [at: ] excess consecutive
820
triggering protection
enabled

RPV311-TM-EN-11.1 302
RPV311-TM-EN-11.1 301

You might also like