GHG 26 / EXKO 2.. Ex-Safety Switches
Rated current from 10 A - 630 A
Safety for your protection installation-friendly design Enclosed Switch-Disconnec- All products installed in ATEX/
The safety switches feature an tors to provide isolation dur- IECEx hazardous areas should
5 CEAG safety switches can be ing repair and maintenance.
protected against inadvertent installation-friendly design and be rated for Class 1. Class 1
switching on by our integrated easily accessible connection GHG 26 switches (10-160 A) requirements include minimum
locking facility for up to three terminals. and GHG 981 switches ratings for mechanical strength,
padlocks in the OFF position. (25 - 80 A) are now confirmed to IP protection, tamper resist-
Versions in impact-resistant
To prevent manipulations, the comply with the new standard ance, heat/vibration/corrosion
polyamide or glass-fibre-rein-
enclosure covers cannot be IEC 62626-1, requirements resistance, switching capacity,
forced polyester enclosures
opened in the locked position Class 1. and locking capability.
provide the high degree of
without destroying the enclo- protection IP66 for safety The new standard IEC 62626-1
sure itself. switches up 180 A. These can defines the requirements for
Full AC-3 switching capacity be optionally supplied with safety switches (switch-dis-
All CEAG safety switches fea- snap-on moulded plastic or connectors) that are used to
ture full AC-3 motor switching brass flanges. Safety switches provide isolation of equipment
capacities and isolating proper- for amperages up to 630 A are during repair and maintenance.
ties according to EN 60947-4-1 supplied in metal enclosures. These requirements go above
with compulsory opening of the These can be equipped with and beyond those of
main current contacts; optional screw-on flanges. IEC 60947-3, where no stand-
EMERGENCY STOP versions Explosion Group IIB ard previously existed.
according to EN 60204-1 are The described safety switches The standard divides products
also available. An additional at the sizes 210 - 630 A are also into two classifications:
lagging/leading auxiliary con- available for Explosion Group
tacts (option) guarantee double • Class 0 for general use and
IIB, which is sufficient for many
safety for extreme switching of the applications. • Class 1 for harsh and rough/
conditions. heavy duty conditions.
Features
• Full AC-3 switching capacity
• Double safety: additional auxiliary contact
• Cost-saving installation up to 180 A
• Snap-on mounting up to 40 A
• IP66 protection up to 180 A
Technical data
Ex-safety switches 10 A
5
Marking accd. to 2014/34/EU D II 2 G Ex eb db IIC T6 Gb / D II 2 D Ex tb IIIC T80°C Db
EC-Type Examination Certificate BVS 16 ATEX E 079
IECEx Certificate of Conformity IECEx BVS 16.0045
Marking accd. to IECEx Ex eb db IIC T6 Gb / Ex tb IIIC T80°C Db
Permissible ambient temperature –20 °C up to +40 °C1)
Rated voltage up to max. 500 V
Rated current max. 10 A
Frequency 50/60 Hz
Rated making-/ breaking capacity AC-3 Ue 230 V / Ie 10 A
accd. EN 60947-3 Ue 400 V / Ie 10 A
Ue 500 V / Ie 10 A
Switch-disconnector for maintenance Class 1
accd. to IEC 62262-1
Back-up fuse up to 400 V AC: 20 A gG
up to 500 V AC: 16 A gG
Connecting terminals main contact 2 x 1.5 - 2.5 mm2
auxiliary-/Signal contact 2 x 0.5 - 2.5 mm2 (option)
Degree of protection accd. to EN 60529 IP66
Protection class I
Cable glands/enclosure drilling M20 cable gland see ordering details
M25 cable gland see ordering details
Weight 0.55 kg
Enclosure material impact resistant polyamide
Enclosure colour black
Auxiliary contact (option) 1 x NO making - lagging; breaking - leading
Padlocking facility can be locked in OFF position with 3 commercially available padlocks (Ø max. 6 mm)
1)
Other ambient temperatures on request
Ordering details
Content Cable gland Auxiliary contact Order No.
5
Safety switch 10 A 3-pole
3-pole 2 x M25 / 1 x M20 1 NO GHG 261 0005 R0009
3-pole 2 x M25 none GHG 261 0007 R0001
3-pole 2 x M20 1 NO GHG 261 0005 R0005
3-pole EMERGENCY STOP 2 x M25 / 1 x M20 1 NO GHG 261 0005 R0010
3-pole EMERGENCY STOP 2 x M25 none GHG 261 0007 R0002
Safety switch 10 A 3-pole
4-pole 2 x M25 none GHG 261 0007 R0003
Customized version on request, auxiliary contacts in Ex ia available
Accessories
Type Application Fixing method Order No.
5.5
Please pay attention that only order units (OU) according to the ordering details can be delivered.
Ø 8.5
Dimension drawing
84 112
X68.5 80
X61.5
102
Ø 5.5
Ø 8.5
Technical data
Ex-safety switches 20 A
5
Marking accd. to 2014/34/EU D II 2 G Ex ed ia IIC T6 / D II 2 D Ex tD A21 IP66 T80 °C
EC-Type Examination Certificate PTB 99 ATEX 1161
IECEx Certificate of Conformity BKI 07.0012
Marking accd. to IECEx Ex ed ia IIC T6
Ex tD A21 IP66 T55 °C
Permissible ambient temperature –20 °C up to +40 °C1)
Rated voltage up to max. 690 V
Rated current max. 20 A
Frequency 50/60 Hz
Rated making-/rated breaking capacity AC-3 Ue 230 V / Ie 20 A
accd. EN 60947-3 Ue 400 V / Ie 20 A
Ue 500 V / Ie 16 A
Ue 690 V / Ie 10 A
Rated making-/ breaking capacity DC 1/DC 23 Ue 60 V / Ie 20 A (1 contact)
accd. EN 60947-3 Ue 120 V / Ie 20 A (2 contacts in series)
Rated making-/ breaking capacity DC-13 (L/R = 100 ms) Ue 60 V / Ie 6 A
accd. EN 60947-3
Switch-disconnector for maintenance Class 1
accd. to IEC 62262-1
Back-up fuse up to 400 V AC: 35 A gG
up to 500 V AC: 35 A gG
up to 690 V AC: 25 A gG
Connecting terminals main contact max. 2 x 4 mm2 (stranded wire or fine wire) / max. 6 mm² (pin cable lug)
auxiliary-/Signal contact 2 x 0.5 - 2.5 mm2 (option)
Protection class I
Degree of protection accd. to EN 60529 IP66
Cable glands/enclosure drilling M20 cable gland see ordering details
M25 cable gland see ordering details
M32 cable gland see ordering details
Option: metal flange with thread
Weight 3-pole approx. 1.48 kg
6-pole approx. 2.43 kg
Enclosure material glass-fibre reinforced polyester
Enclosure colour black
Auxiliary contact (option) 1 x NO making - lagging; breaking - leading
1 x NC (only 6-pole version) making - leading; breaking - lagging
Padlocking facility can be locked in OFF position with 3 commercially available padlocks (Ø max. 6 mm)
1)
Other ambient temperatures on request
Ordering details
Content Cable gland Auxiliary contact Order No.
5
Safety switch 20 A 3-pole
3-pole 2 x M32 / 1 x M25 1 NO GHG 262 2301 R0001
3-pole 2 x M32 none GHG 262 2304 R0001
3-pole EMERGENCY STOP 2 x M32 / 1 x M25 1 NO GHG 262 2301 R0002
3-pole EMERGENCY STOP 2 x M32 none GHG 262 2304 R0002
Safety switch 20 A 4-pole
4-pole 2 x M20 1 NO + 1 NC GHG 262 2301 R0007
4-pole 2 x M32 / 1 x M25 1 NO + 1 NC GHG 262 2301 R0009
4-pole 2 x M32 none GHG 262 2304 R0004
4-pole 2 x M20 none GHG 262 2304 R0003
4-pole EMERGENCY STOP 2 x M32 / 1 x M25 1 NO + 1 NC GHG 262 2301 R0010
Accessories
Type Application Fixing method Order No.
Canopies
Size 2 for mounting plate size 2 1 GHG 610 1955 R0102
Size 2A for mounting plate size 2A 1 GHG 610 1955 R0103
Size 3 for pipe mounting plate size 3 vertical 1 GHG 610 1955 R0104
Size 3A for mounting plates wall/trellis fixing 1 GHG 610 1955 R0105
size 3 vertical
Size 3B for mounting plates pipe fixing 1 GHG 610 1955 R0106
size 3 horizontal
Please pay attention that only order units (OU) according to the ordering details can be delivered.
110
X 96
Dimension drawing
5
110 129140
X 96 13
X 121-126
7
X150
170
X197
225
3/4-pole
13 129
7
140 156
X 121-126 8
7
X197
225
Dimensions in mm
Technical data
Ex-safety switches 40 A
5
Marking accd. to 2014/34/EU D II 2 G Ex ed ia IIC T6 / D II 2 D Ex tD A21 IP66 T80 °C
EC-Type Examination Certificate PTB 99 ATEX 1161
IECEx Certificate of Conformity BKI 07.0012
Marking accd. to IECEx Ex ed ia IIC T6
Ex tD A21 IP66 T53 °C
Permissible ambient temperature –20 °C up to +40 °C1)
Rated voltage up to max. 690 V
Rated current max. 40 A
Frequency 50/60 Hz
Rated making/breaking capacity AC-3 Ue 230 V / Ie 40 A
accd. EN 60947-3 Ue 400 V / Ie 40 A
Ue 500 V / Ie 40 A
Ue 690 V / Ie 32 A
Rated making-/ breaking capacity DC 1/DC 23 Ue 60 V / Ie 40 A (1 contact)
accd. EN 60947-3 Ue 120 V / Ie 40 A (2 contacts in series)
Switch-disconnector for maintenance Class 1
accd. to IEC 62262-1
Back-up fuse up to 400 V AC: 80 A gG
up to 500 V AC: 80 A gG
up to 690 V AC: 63 A gG
Connecting terminals main contact 2 x 16 mm2
auxiliary/signal contact 2 x 4 mm2 (option)
Protection class I
Degree of protection accd. to EN 60529 IP66
Cable glands/enclosure drilling M25 cable gland see ordering details
M40 cable gland see ordering details
Option: metal flange with thread
Weight 3-pole approx. 2.30 kg
4-pole approx. 2.75 kg
6-pole approx. 6.50 kg
Enclosure material glass-fibre reinforced polyester
Enclosure colour black
Auxiliary contact (option) 1 x NO making - lagging; breaking - leading
1 x NC (only 6-pole version) making - leading; breaking - lagging
Padlocking facility can be locked in OFF position with 3 commercially available padlocks (Ø max. 6 mm)
1)
Other ambient temperatures on request
Ordering details
Content Cable gland Auxiliary contact Order No.
5
Safety switch 40 A 3-pole
3-pole 2 x M40 / 1 x M25 1 NO GHG 263 2301 R0001
3-pole 2 x M40 none GHG 263 2303 R0001
3-pole EMERGENCY STOP 2 x M40 / 1 x M25 1 NO GHG 263 2301 R0002
3-pole EMERGENCY STOP 2 x M40 none GHG 263 2303 R0002
Safety switch 40 A 4-pole
4-pole 2 x M25 1 NO + 1 NC GHG 263 2301 R0007
4-pole 2 x M25 none GHG 263 2303 R0003
4-pole 2x M40 / 1 x M25 1 NO + 1 NC GHG 263 2301 R0009
4-pole 2x M40 none GHG 263 2303 R0004
Safety switch 40 A 6-pole
6-pole 4 x M40 / 1 x M25 1 NO + 1 NC GHG 263 0050 R0001
6-pole 4 x M25 1 NO + 1 NC GHG 263 0050 R0006
6-pole EMERGENCY STOP 4 x M40 / 1 x M25 1 NO + 1 NC GHG 263 0050 R0002
Customized version on request, auxiliary contacts in Ex ia available
Accessories
Type Application Fixing method Order No.
Canopies
Size 4 for mounting plate size 4 1 GHG 610 1955 R0107
Please pay attention that only order units (OU) according to the ordering details can be delivered.
140
X 121-126
X197
225
3-pole 3-pole EMERGENCY STOP 6-pole 6-pole EMERGENCY STOP
Dimension drawing
5
140 156
X 121-126 8
7
X197
225
3/4-pole
8 156
7 271 275
X 247 Ø12 211
11
Ø7
X 247
271
Dimensions in mm
Technical data
Ex-safety switches 80 A
5
Marking accd. to 2014/34/EU D II 2 G Ex db e [ia/ib] IIB/IIC T5/T6 Gb / DII 2 D Ex tb IIIC T80 °C Db
EC-Type Examination Certificate BVS 15 ATEX E 125 X
IECEx Certificate of Conformity IECEx BVS 15.0103X
Marking accd. to IECEx Ex db e [ia/ib] IIB/IIC T5/T6 Gb
Ex tb III C T80°C Db
Permissible ambient temperature –20 °C up to +40 °C1)
Rated voltage up to max. 690 V
Rated current max. 80 A
Frequency 50/60 Hz
Rated making/breaking capacity AC-3 Ue 230 V / Ie 80 A
accd. EN 60947-3 Ue 400 V / Ie 80 A
Ue 500 V / Ie 80 A
Ue 690 V / Ie 63 A
Rated making-/ breaking capacity DC 1/DC 23 Ue 60 V / Ie 80 A (1 contact)
accd. EN 60947-3 Ue 120 V / Ie 80 A (2 contacts in series)
Switch-disconnector for maintenance Class 1
accd. to IEC 62262-1
Back-up fuse up to 400 V AC: 160 A gG
up to 500 V AC: 160 A gG
up to 690 V AC: 125 A gG
Connecting terminals main contact 2 x 25 mm2
auxiliary/signal contact 2 x 4 mm2 (option)
Protection class I
Degree of protection accd. to EN 60529 IP66
Cable glands/enclosure drilling M25 cable gland see ordering details
M32 cable gland see ordering details
M50 cable gland see ordering details
Option: metal flange with thread
Weight 3/4-pole approx. 6.5 kg
6-pole approx. 9.0 kg
Enclosure material glass-fibre reinforced polyester
Enclosure colour black
Auxiliary contact (option) 1 x NO making - lagging; breaking - leading
1 x NC making - leading; breaking - lagging
Padlocking facility can be locked in OFF position with 3 commercially available padlocks (Ø max. 6 mm)
1)
Other ambient temperatures on request
Ordering details
Content Cable gland Auxiliary contact Order No.
5
Safety switch 80 A 3-pole
3-pole 2 x M50 / 1 x M25 1 NO + 1 NC GHG 264 0020 R0001
3-pole 2 x M50 none GHG 264 0025 R0001
3-pole EMERGENCY STOP 2 x M50 / 1 x M25 1 NO + 1 NC GHG 264 0020 R0002
3-pole EMERGENCY STOP 2 x M50 none GHG 264 0025 R0002
Safety switch 80 A 4-pole
4-pole 2 x M50 / 1 x M25 1 NO + 1 NC GHG 264 0020 R0012
4-pole 2 x M50 none GHG 264 0025 R0004
4-pole 2 x M32 1 NO + 1 NC GHG 264 0020 R0006
4-pole 2 x M32 none GHG 264 0025 R0003
Safety switch 80 A 6-pole
6-pole 4 x M50 / 1 x M25 1 NO + 1 NC GHG 264 0021 R0001
6-pole EMERGENCY STOP 4 x M50 / 1 x M25 1 NO + 1 NC GHG 264 0021 R0002
Customized version on request, auxiliary contacts in Ex ia available
Accessories
Type Application Fixing method Order No.
271
X 247
Dimension drawing
Ø7 Ø7
271
X 247
271
X 247