Remote Monitoring and Control Unit REC 501
1MRS750430-MBG
Issued: May 1999
Status: Updated
Version: B/06.11.2001
Data subject to change without notice
Features • Remote control and monitoring unit for the • Power supply unit including charger with
control of medium voltage disconnectors, integrated compensation for the battery
switches, ring-main units and other substa- temperature
tion secondary equipment
• Automatic heating control for low tempera-
• Extensive, bidirectional information tures and humid environments
exchange between the power system pro-
• Management via network control system,
cess and the network control centre
e.g. S.P.I.D.E.R. MicroSCADA
• Communication via radio telephone, radio
• Continuous self-supervision of hardware
link, fixed lines, leased lines, public tele-
and software
phone lines and mobile phones
(NMT/GSM) • Member of the ABB’s Substation Automa-
tion system
• Operation, communication and reporting
secured during power outages by means of
maintenance-free batteries
Application The remote monitoring and control unit modern technology applied in the unit
REC 501 is designed to be used for remote extends the flexibility of the total power sys-
and local control, condition monitoring, tem.
supervision and automation of secondary sub-
stations in medium voltage networks. It can The ABB Distribution Automation system
be used with various remote terminal units includes a complete range of protection
(RMUs), air-insulated and SF6-insulated dis- relays, feeder terminals, control units, annun-
connectors, switches and other remote-con- ciator units, Substation Monitoring Systems
trolled secondary substation equipment. The (SMS) and Substation Control Systems
(SCS).
3
Remote Monitoring and Control Unit REC 501
1MRS750430-MBG
Design The basic unit consists of the micro-processor Regular reinitialization is used for monitoring
and power supply charger board (PSC) and an the condition of the optional plug-in modem
optional plug-in modem. The PSC board and the external modem. The monitoring and
includes a processor, a switching mode power control unit reinitializes the modem even
supply unit with a temperature-compensated though there has not been any successful
battery charger, five binary inputs, four relay communication within a certain period of
outputs and an RS232 serial interface for time.
communication. All inputs and outputs are
galvanically isolated, and thus the I/Os have The number of operations of the disconnec-
wide operating voltage ranges, which allow tors, circuit breakers and other devices is
the unit to be used in a variety of remote con- recorded by two operation counters. The
trol applications. operation counters facilitate the condition
monitoring of the equipment and indicate the
The monitoring and control unit is used for need for maintenance.
remote control and remote measuring in the
application where it is used. Monitoring of the pressure of SF6 gas insu-
lated primary equipment can be obtained by
wiring the pressure sensor contact to one of
Control the binary inputs.
The unit includes binary inputs and relay out-
puts for the control of two disconnectors, The monitoring and control unit is pro-
switches or other objects. The objects can be
grammed using the setting emulator software,
controlled remotely over the network control SMS 010 tool, CAP 5xx configuration and
system or locally via push-buttons, which programming tool, terminal emulators with
normally are placed in a separate enclosure.
SPA parameters, and remotely via
Disconnector and switch status indication is MicroSCADA. The parameters can be set
obtained via the binary inputs. One of the out- off-line in the tool and downloaded via the
puts can be used for the control of an external communication system.
heater and one output can be used for internal
fault (IRF) indication.
Battery backup
The battery backup of the station can be
Voltage and temperature arranged by using two 12 V, 17 Ah or 24 Ah,
measurement sealed lead acid batteries in the monitoring
The unit measures the battery voltage and and control unit. The integrated temperature-
ambient temperature. The temperature mea- compensated switched-mode battery charger
surement is calibrated to measure the ambient charges the batteries under normal conditions
temperature of a unit mounted in an enclo- and supplies the power needed by the unit
sure. Further, the temperature information is during power outages. Thus the operation of
needed to control the charging voltage of the the unit and the communication between the
batteries and for switching the heating on and substation and the network control centre are
off in cold or humid environments. always secured.
4
Remote Monitoring and Control Unit REC 501
1MRS750430-MBG
5
Remote Monitoring and Control Unit REC 501
1MRS750430-MBG
6
Remote Monitoring and Control Unit REC 501
1MRS750430-MBG
Block diagram
7
Remote Monitoring and Control Unit REC 501
1MRS750430-MBG
Order numbers
Monitoring and control unit REC 501
110…240 V ac / 110…220 V dc, surface mounting 1MRS 090020-AA
110…240 V ac / 110…220 V dc, flush-mounting 1MRS 090021-AA
18…80 V dc, surface mounting 1MRS 090020-CA
18…80 V dc, flush-mounting 1MRS 090021-CA
Software
Protocol ANSI X3.28 1MRS 118006
Protocol RP570 1MRS 118007
Protocol IEC 870-5-101 1MRS 118008
Protocol MODBUS 1MRS 118009
Protocol DNP 3.0 1MRS 118010
Optional accessories
Programming cable 1MRS 120500
RS232 cable, 15 m 1MRS 120507
Plug-in modem, temperature range +5…+50°C 1MRS 119000-Axx *)
Plug-in modem, temperature range -20…+60°C 1MRS 119000-Bxx *)
Plug-in adapter module with RS 485 and plastic 1MRS 050248
fibre cable interfaces
Plug-in adapter module with RS 485 and glass fibre 1MRS 050249
cable interfaces