Location via proxy:   [ UP ]  
[Report a bug]   [Manage cookies]                

Array Sizing: Information About System

Download as docx, pdf, or txt
Download as docx, pdf, or txt
You are on page 1of 8

Array sizing

1. Information about system

Total load demand (KW) 700


h (hour) 12
System DC Voltage (V) 120
PSH OF Gardiz city(KWh/m2/day) 5.48

2. Considered factor in sizing

Overall inverter efficiency 0.97


Oversupply co-efficient 1.3
Coulombic efficiency of Battery 90%
Loss in charge regulator and cables 5%
Loss due to temperature 5%
soling loss 5%

3. Module

Module type Polycrystalline


Tolerance 0/+3
Pmax(W) 300
Dimension 1956*992*40
Cell type 156*156/6*12
Weight(Kg) 25
Imp(A) 8.26
Vmp(V) 36.3
Isc(A) 8.679
Voc(V) 44.8
AC daily load demand (Wh )∗¿ supply co−efficinet
DC Daily load demand ∈Ah=
Ac−system efficiency∗systemnominal volatge

AC daily load demand=12∗700=8400 KWh=8400000Wh


inverter
Ac system efficiency= efficiency∗battery coulombi efficiency∗Trans efficiency
all
AC system efficiency=0.9∗0.9∗0.95=0.7695=77 %

8400000∗1.3
DC Daily load demand∈Ah= =118181.8 Ah
0.77∗120

Module derating factor=Temperature derating∗manufacture r ' s tolerence∗derat f soiing


Module derating factor=0.95∗1∗0.95=0.9025
Module output ∈ Ah=5.48 ( PSH )∗8.26 ( Imp )∗0.9025=40.85 A /day
118181.8
No∥module= =2893.06 round up 2893
40.85
120
No∥series= =3.333round up 4
36
Total No of module=4∗2893=11572−300℘ PV panal

Therefore we need 11572 Polycrystalline module (300 WP, 36V)


Battery sizing
1. Information Total load demand (KW) 700 about system
h (hour) 12
System DC Voltage (V) 120
Highest temperature ( C ) 30
Lowest temperature ( C ) -10
Days of autonomy 3 or1
2. Battery

Battery type Exide 6RP830


DOD (at -10 C) 70%
Derating Factor (at -10 C) 0.85
1. Battery back-up for 1 day
1 days∗24 hour /day
Average Rate of discharge = =34.29 hour rate
0.7
Capacity at slow average PV rate 910
Rate factor= = =1.8
Capacity at manufactur e sstandard 501
'

1∗8400000
Battery cpacity ( Ah ) = =65359.5 Ah
120∗0.7∗0.85∗1.8
65359.5
NO of batt ∈¿= =71.82 round up 72
910
120
NO of batt inseries= =20
6
Total NO of batt=72∗20=1440

Therefore we need 1440 Exide 6Rp830 Batteries (910A, 6V)

2. Battery back-up for 3 days

3 days∗24 hour / day


Average Rate of discharge = =102.85 hour rate
0.7
Capacity at slow average PV rate 910
Rate factor= = =1.8
Capacity at manufactur e sstandard 501
'

3∗8400000
Battery cpacity ( Ah ) = =196078.43 Ah
120∗0.7∗0.85∗1.8
196078.43
NO of batt ∈¿= =215.47 round up 216
910
120
NO of batt inseries= =20
6
Total NO of batt=216∗20=4320

Therefore we need 4320 Exide 6Rp830 Batteries (910A, 6V)

Inverter sizing
Inverter rating =𝐿𝑜𝑎𝑑×1.25(𝑠𝑎𝑓𝑒𝑡𝑦 𝑓𝑎𝑐𝑡𝑜𝑟)

Inverter rating=700 KW ∗1.25=87


Total energy that will be generated yearly by PV system

¿ ≫11572 ( Total module )∗300 ( Module ℘ )∗300 ( suny days )∗5.48 ( PSH )
¿ ≫5707310400 Wh=5707310.4 KWhTotal energy generation energy by PV system
1 KWh energy price by Diesel generator=45 Afg/KWh
So 5707310.4*45=256828968 Afg will be saved yearly by this system
And 1 KWh generated by diesel generator produce 1.5 Kg CO2
So 1.5 *5707310.4=8560965.6 Kg CO2 emission prevent by this system