Option Slot A - Digital Input DI1A

Download as xls, pdf, or txt
Download as xls, pdf, or txt
You are on page 1of 17

Option Slot A - Digital Input DI1A

Option Slot A - Digital Input DI2A


EM6400 NG
Prohibited
Allowed for
When
Command Unprotected
Subsystem Command Name Command Tag Parameters User Notes Revenue
Number Command
Security
Interface
Active
REGISTER_ACCESS (0-999) Y
SYSTEM (1000-1999) Y
METERING (2000-2999)
Basic Meter Setup 2000 C_BASIC_METER_SETUP Y (1) Command Semaphore (13) Number VTs Y
(2) Number of Phases (14-15) VT Primary
(3) Number of Wires (16) VT Secondary
(4) Power System Configuration (17) Number CTs
(5) Nominal Frequency (18) CT Primary, Phase
(6-7) Nominal Voltage (19) CT Secondary, Phase
(8-9) Nominal Current (20) CT Primary, Neutral
(10-11) Nominal Power Factor (21) CT Secondary, Neutral
(12) Normal Phase Rotation (22) CT Location for 1 CT Metering
(23) VT Location for 1 VT Metering
(24) VT Connection Type

Advanced Meter Setup 2001 C_ADV_METER_SETUP (1) Command Semaphore Y


(2) Power Metering Mode

Demand System Setup 2002 C_DMD_SETUP Y (1) Command Semaphore Demand System ID Y
(2) Demand System ID 1 = Power
(3) Demand Method 2 = Current
(4) Demand Interval Duration 3 = Input Metering
(5) Demand Subinterval Duration

Energy Pulse Output Setup 2003 C_ENERGY_PULSE_OUTPUT_SETUP Y (1) Command Semaphore Digital Output ID Y
(2) Energy Channel 1 = Digital Output S01
(3) Digital Output ID 2 = Digital Output S02
(4-5) Pulse Weight 99 = Energy LED
(6) Energy Channel In PM2130, PM2230, DO1 and DO2 Available
(7) Digital Output ID when Optional DIO card is present
(8-9) Pulse Weight If DIO card is not present, write 0xFFFF along with
(10) Energy Channel all parameters listed.
(11) Digital Output ID
(12-13) Pulse Weight

Reset Cycle Count 2007 C_RESET_CYCLE_COUNT Y (1) Command Semaphore Y

Reset All Min/Max 2009 C_RESET_ALL_MIN_MAX Y (1) Command Semaphore Y

Reset Active Load Timer 2010 C_RESET_ACTIVE_LOAD_TIMER Y (1) Command Semaphore Y

Reset All Demands 2011 C_RESET_ALL_DMDS Y (1) Command Semaphore The Demand Reset Password is verified if See Y
(2-5) Demand Reset Password Revenue Security is active. User Note

Reset Current Demand 2012 C_RESET_CUR_DMD Y (1) Command Semaphore Y

Reset Power Demand 2013 C_RESET_POWER_DMD Y (1) Command Semaphore The Demand Reset Password is verified if See Y
(2-5) Demand Reset Password Revenue Security is active. User Note

Reset All Peak Demands 2015 C_RESET_ALL_PEAK_DMDS Y (1) Command Semaphore The Demand Reset Password is verified if See Y
(2-5) Demand Reset Password Revenue Security is active. User Note

Reset Current Peak Demands 2016 C_RESET_CUR_PEAK_DMDS Y (1) Command Semaphore Y

Reset Power Peak Demands 2017 C_RESET_POWER_PEAK_DMDS Y (1) Command Semaphore The Demand Reset Password is verified if See Y
(2-5) Demand Reset Password Revenue Security is active. User Note

Start New Demand Interval 2019 C_START_NEW_DMD_INTERVAL Y (1) Command Semaphore Y Y


(2) Bitmap of Demand Systems

Reset All Energies 2020 C_RESET_ALL_ENERGIES Y (1) Command Semaphore Y Y

Reset All Accumulated Energies 2021 C_RESET_ALL_ACC_ENG Y (1) Command Semaphore Y Y

Reset All Energy Pulse Output Channels 2024 C_RESET_ALL_ENG_PULSE_OUTPUT (1) Command Semaphore Y Y
Meter Initialization 2037 C_METER_INITIALIZATION Y (1) Command Semaphore Resets Y
Energy,
Demand,
Demand peaks,
Min/Max,
Alarm counters,
Alarm logs,
Alarm event queue,
IO Counters,
IO Timers,
Active Load Timer,
Comm diagnostics,
power fail counter,
cycle counter
Data logs (Scout only),
and Waveform capture Files (Scout only).

Energy / Alarm LED Enable 2039 C_ENERGY_LED_ENABLE Y (1) Command Semaphore


(2) 0 = Disable / 1 = Alarm / 2 = Energy

Active Load Timer Setup 2044 C_ACTIVE_LOAD_TIMER_SETUP Y (1) Command Semaphore


(2-3) Active Load Timer Setpoint

Set Time for Demand Synch 2063 C_DMD_SYNCH_TIME Y (1) Command Semaphore Time is 0000 to 2359 Y N
(2) Synch Time

COMMUNICATIONS (5000-5999)
Communications Setup 5000 C_COMMS_SETUP Y (1) Command Semaphore Communications Port ID Y
(2) Communications Port ID 1 = Standard RS-485
(3) RS-485 Comm Port (M/S) Protocol
(4) RS-485 Comm Port (M/S) Address
(5) RS-485 Comm Port (M/S) Baud Rate
(6) RS-485 Comm Port (M/S) Parity
(7) RS-485 Comm Port (M/S) Modbus ASCII Default Timeout

In PM2130, PM2230, Available when Optional DIO


IO (6000-6999) card is present
Digital Output Setup 6000 C_DO_SETUP (1) Command Semaphore Digital Output ID
(2) Digital Output ID 1 = Digital Output S01
(3-22) Label 2 = Digital Output S02
(23) Behavioral Mode
(24) On Time For Timed Mode

Digital Input Setup 6001 C_DI_SETUP (1) Command Semaphore Digital Input ID
(2) Digital Input ID 1 = Digital Input S01
(3-22) Label 2 = Digital Input S02
(23) Debounce Time 3 = Digital Input S03
4 = Digital Input S04
De-energize Digital Output 6002 C_DE_ENERGIZE_DO (1) Command Semaphore Digital Output ID Y
(2) Digital Output ID 1 = Digital Output S01
2 = Digital Output S02

Energize Digital Output 6003 C_ENERGIZE_DO (1) Command Semaphore Digital Output ID Y
(2) Digital Output ID 1 = Digital Output S01
2 = Digital Output S02

Release Digital Output From Coil Hold 6004 C_RELEASE_DO_FROM_COIL_HOLD (1) Command Semaphore Digital Output ID Y
(2) 1 or -1 (For All Digital Outputs) 1 = Digital Output S01
(3) Digital Output ID or -1 (For All Digital Outputs) 2 = Digital Output S02

Release Digital Output From Override Control 6005 C_RELEASE_DO_FROM_OVERRIDE (1) Command Semaphore Digital Output ID
(2) 1 or -1 (For All Digital Outputs) 1 = Digital Output S01
(3) Digital Output ID or -1 (For All Digital Outputs) 2 = Digital Output S02

Place Digital Output In Override Control 6006 C_PLACE_DO_IN_OVERRIDE (1) Command Semaphore Digital Output ID
(2) 1 or -1 (For All Digital Outputs) 1 = Digital Output S01
(3) Digital Output ID or -1 (For All Digital Outputs) 2 = Digital Output S02

Reset Operation Counter for Digital Output 6007 C_RESET_COUNT_FOR_DO (1) Command Semaphore Digital Output ID Y
(2) 1 or -1 (For All Digital Outputs) 1 = Digital Output S01
(3) Digital Output ID or -1 (For All Digital Outputs) 2 = Digital Output S02

Reset On-Time for Digital Output 6008 C_RESET_ON_TIME_FOR_DO (1) Command Semaphore Digital Output ID Y
(2) 1 or -1 (For All Digital Outputs) 1 = Digital Output S01
(3) Digital Output ID or -1 (For All Digital Outputs) 2 = Digital Output S02

Reset Operation Counter for Digital Input 6009 C_RESET_COUNT_FOR_DI (1) Command Semaphore Digital Input ID Y
(2) 1 or -1 (For All Digital Inputs) 1 = Digital Input S01
(3) Digital Input ID or -1 (For All Digital Inputs) 2 = Digital Input S02
3 = Digital Input S03
4 = Digital Input S04

Reset On-Time for Digital Input 6010 C_RESET_ON_TIME_FOR_DI (1) Command Semaphore Digital Input ID Y
(2) 1 or -1 (For All Digital Inputs) 1 = Digital Input S01
(3) Digital Input ID or -1 (For All Digital Inputs) 2 = Digital Input S02
3 = Digital Input S03
4 = Digital Input S04

De-energize Digital Output While in Override 6015 C_DE_ENERGIZE_DO_OVERRIDE (1) Command Semaphore Digital Output ID
(2) Digital Output ID 1 = Digital Output S01
2 = Digital Output S02

Energize Digital Output While in Override 6016 C_ENERGIZE_DO_OVERRIDE (1) Command Semaphore Digital Output ID
(2) Digital Output ID 1 = Digital Output S01
2 = Digital Output S02

Setup Digital Input to Reset Incremental Energy 6017 C_DI_SETUP_INC_ENERGY (1) Command Semaphore Y
(2) Digital Input ID assigned to reset Incremental Energy

Release DO control mode 6018 C_RELEASE_DO_CONTROL_MODE (1) Command Semaphore Digital Output ID Y
(2) Digital Output ID 1 = Digital Output S01
2 = Digital Output S02

Setup Analog Input ( PM2000 Option card ) 6500 C_AI_SETUP (1) Command Semaphore Analog input Id1=1 Analog input Id2=2 Y
(2) Analog Input Id
( 3-22 ) Label
( 23 ) Units Code
( 24 ) Scale Code
( 25 ) Range Select
( 26-27 ) Lower Limit Analog Value
( 28-29 ) Upper Limit Analog Value

Setup Analog Output( PM2000 Option card ) 6501 C_AO_SETUP ( 1 ) Commad Semaphore Analog Output Id1=1 Analog Output Id2=2 Y
( 2 ) Analog Output Id Reference Register Number Range 3000 to 3076
( 3-22 ) Label Adress
( 23 ) Range Select
( 24 ) Reference Register Number
( 25-26 ) Lower Limit Register Value
( 27-28 ) Upper Limit Register Value

Enable Analog Output( PM2000 Option card ) 6502 C_AO_ENABLE ( 1 ) Commad Semaphore Y
( 2 ) Analog Output Id
Disable Analog Output( PM2000 Option card ) 6503 C_AO_DISABLE ( 1 ) Commad Semaphore Y
( 2 ) Analog Output Id
ALARMS (7000-7999)
Over/Under Alarm Setup 7000 C_OVR_UND_ALM_SETUP (1) Command Semaphore Alarm ID
(2) Alarm ID 1 = Over Current, Phase
(3) Priority (0=None, 1=High, 2=Medium, 3=Low) 2 = Under Current, Phase
(4) Setpoints (0 = Fixed, 1 = Variable) 5 = Over Voltage, L-L
(5) Learning (0 = Not Learning, 1 = Learning) 6 = Under Voltage, L-L
(6) Enable (0 = Disabled, 1 = Enabled) 7 = Over Voltage, L-N
(7-8) Pickup Setpoint 8 = Under Voltage, L-N
(9-10) Pickup Time Delay 9 = Over Power, Active
(11-12) Dropout Setpoint 10 = Over Power, Reactive
(13-14) Dropout Time Delay 11 = Over Power, Apparent
(15) Digital Outputs to Associate - Standard 12 = Leading Power Factor, True
(16-19) Digital Outputs to Associate - Options (Scout Only) 13 = Lagging Power Factor, True
(20) Datalogs to Trigger (Scout Only) 25 = Over Frequency
(21) Waveform Capture to Trigger (Scout Only) 26 = Under Frequency
(Note: 11 to 16 write as 0 always for Scout model) 28 = Over Voltage Total Harmonic Distortion

Reset Alarm Counters 7002 C_RESET_ALM_COUNT (1) Command Semaphore Alarm ID


(2) 1 or -1 (For All Alarm Counters) 1-29 1-Second Standard
(3) Alarm Counter ID or -1 (For All Alarm Counters) 41-50 1-Second Custom
101-104 Unary
111-114 Digital

Acknowledge Alarms 7003 C_ACK_ALMS (1) Command Semaphore Y


(2) 1 or -1 (For All Alarms)
(3) Alarm ID or -1 (For All Alarms)

Disable Alarms 7004 C_DISABLE_ALMS (1) Command Semaphore


(2) 1 or -1 (For All Alarms)
(3) Alarm ID or -1 (For All Alarms)

Reset Aggregated Alarm History 7005 C_RESET_REG_BASED_ALM_LOG (1) Command Semaphore Y

Reset Event Queue 7006 C_RESET_EVENT_QUEUE (1) Command Semaphore Y

Digital Alarm Setup 7007 C_DIGITAL_ALARM_SETUP (1) Command Semaphore Alarm ID


(2) Alarm ID 111 = Digital Input S01
(3) Priority (0=None, 1=High, 2=Medium, 3=Low) 112 = Digital Input S02
(4) Enable (0 = Disabled, 1 = Enabled) 113 = Digital Input S03
(5) Subtype (0 = Off, 1 = On) 114 = Digital Input S04
(6-7) Pickup Time Delay
(8-9) Dropout Time Delay
(10) Digital Outputs to Associate - Standard
(11-14) Digital Outputs to Associate - Options (Scout Only)
(15) Datalogs to Trigger (Scout Only)
(16) Waveform Capture to Trigger (Scout Only)
(Note: 11 to 16 write as 0 always for Scout model)

Unary Alarm Setup 7008 C_UNARY_ALARM_SETUP (1) Command Semaphore Alarm ID


(2) Alarm ID 101 = Meter Power Up (Control Power Loss)
(3) Priority (0=None, 1=High, 2=Medium, 3=Low) 102 = Meter Reset
(4) Enable (0 = Disabled, 1 = Enabled) 103 = Meter Diagnostics
(5) Digital Outputs to Associate - Standard 104 = Phase Reversal
(6-9) Digital Outputs to Associate - Options (Scout Only)
(10) Datalogs to Trigger (Scout Only)
(11) Waveform Capture to Trigger (Scout Only)
(Note: 6 to 11 write as 0 always for Scout model)

FILES (8000-8999)
Enable Data Log 8001 C_ENABLE_DATA_LOG (1) Command Semaphore Y
(2) File ID
(3) Enable/Disable (0=Disable, 1=Enable)
Setup Data Log 8002 C_SETUP_DATA LOG (1) Command Semaphore Y
(2) File ID
(3) Record Management Method
(4) Topic List Reference
(5) Start time
(6) Stop time
(7) Interval Control minutes (1,5,10,15,30,60,1440)
(8) ID Item 1
(9) ID Item 2
(10) ID Item 3
(11) ID Item 4
(12) ID Item 5
(13) ID Item 6
(14) ID Item 7
(15) ID Item 8
(16) ID Item 9
(17) ID Item 10
(18) ID Item 11
(19) ID Item 12
(20) ID Item 13
(21) ID Item 14

Clear Data Log 8003 C_CLEAR_DATA_LOG (1) Command Semaphore Y


(2) File ID
Data Type Description Native Range N/A Value
UTF8 Alphanumeric 0-3 bytes 0x00
INT16 Signed Integer, 16 bits -32,768 - 32,767 0x8000
INT16U Unsigned Integer, 16 bits 0 - 65,535 0xFFFF
INT32 Signed Integer, 32 bits -2,147,483,648 – 2,147,483,647 0x80000000
INT32U Unsigned Integer, 32 bits 0 - 4,294,967,295 0xFFFFFFFF
INT64 Signed Integer, 64 bits 0x8000000000000000
FLOAT32 Floating Point, 32 bits +/- 1*10^38 0xFFC00000
FLOAT64 Floating Point, 64 bits +/-1.798*10^308 0xFFF8000000000000
BITMAP 0x8000

Example for a status


bitmap 1 register long.

DATETIME DateTime 1/1/2000 – 12/31/2127 0xFFFFFFFFFFFFFFFF

DATE Date 0xFFFFFFFF


TIME Time 0xFFFFFFFF

PORTAL A portal provides a means to access data of a size up to 125 registers by doing a Modbus block read of a single
without using a large number of registers. An example might be a data type of PORTAL100 located at register 1
would do a block read of 100 registers beginning at register 1000. The data at PORTAL100 could be stored in a
meter communications firmware as 100 16 bit quantities.
4Q FP PF Four Quadrant Floating -2 - 2 0xFFC00000
Point Power Factor
Notes

For status bitmaps that are multiple registers long, the most significant bit will
be set to indicate the entire bitmap is N/A.This does not apply to
configuration bitmaps. So, in setup commands that include a bitmap as a
parameter, the user must always include the desired value for these bitmaps.

DateTime coding format using 4 words as per IEC 870-5-4

Word 1
b0-b6: Year (0 - 127)
b7-b15: Reserved
Word 2
b0-b4: Day (1-31)
b5-b7: Weekday (1-7, 0 if not used)
b8-b11: Month (1-12)
b12-b15: Reserved
Word 3
b0-b5: Minutes (0-59)
b6: Reserved
b7: Time synchronization quality, 1 = non valid or non synchronization
b8-b12: Hour (0-23)
b13-b14: Reserved
b15: 0 = Standard time, 1 = Daylight Savings Time
Word 4
b0-b15: Millisecond (0 - 59999)

Word 1
b0-b7: Year (0 - 99)
b8-b15: Reserved
Word 2
b0-b4: Day (1-31)
b5-b7: Weekday (1-7, 0 if not used)
b8-b11: Month (1-12)
b12-b15: Reserved
Word 1
b0-b5: Minutes (0-59)
b6: Reserved
b7: Time synchronization quality, 1 = non valid or non synchronization
b8-b12: Hour (0-23)
b13-b14: Reserved
b15: 0 = Standard time, 1 = Daylight Savings Time
Word 2
b0-b15: Millisecond (0 - 59999)

ng a Modbus block read of a single register. This allows large data sets to be accessed
of PORTAL100 located at register 1000. In order to read the 100 registers, the user
at PORTAL100 could be stored in an internal format and presented to the user by the

Power factor values are specially encoded floating point values.

Angle of complex power = power factor register value


0° = 1
90° = 0
180° = -1
270° = 2
Q1: 0 < x < 1
Q2: -2 < x < -1
Q3: -1 < x < 0
Q4: 1 < x < 2

Pseudo code to decode PF Value


if (rigVal > 1)
{
PF_Val = 2 - regVal;
PF is leading
}
else if (regVal < -1)
{
PF_Val = -2-regVal
PF is leading
}
else if ( abs(regVal) equals 1 )
{
PF_Val = regVal
PF is at unity
}
else
{
PF_Val = regVal
PF is lagging
}
Alarm Attributes
type subtype parameter modifier phases level priority setpoints learning enable
Bits 28-31 Bits 23-27 Bits 17-22 Bits 11-16 Bits 07-10 Bits 05-06 Bits 03-04 Bit 02 Bit 01 Bit 00

0 NONE 0 NONE 0 NONE 0 NONE 0 NONE 0 LEVEL0 0 NONE 0 FIXED 0 NOT_LEARNING 0 DISABLED
1 STANDARD1S 1 OVER SIGNED 1 VOLTAGE 1 1 1 A 1 LEVEL1 1 HIGH 1 VARIABLE 1 LEARNING 1 ENABLED
2 CUSTOM1S 2 UNDER SIGNED 2 CURRENT 2 2 2 B 2 LEVEL2 2 MEDIUM
3 STANDARDHS 3 LEADING 3 ACTIVE_POWER 3 3 3 C 3 LEVEL3 3 LOW
4 CUSTOMHS 4 LAGGING 4 REACTIVE_POWER 4 4 4 AB
5 DISTURBANCE 5 PHASELOSS 5 APPARENT_POWER 5 5 5 BC
6 TRANSIENT 6 PHASEREV 6 FREQUENCY 6 6 6 CA
7 WAVESHAPE 7 REVPOWER 7 POWER_FACTOR 7 7 7 ABC
8 UNARY 8 POWERUP 8 STANDARD 8 8 8 N
9 DIGITAL 9 RESET 9 OPTION_SLOT_A 9 9 9 G
A BINARY A DIAGNOSTIC A OPTION_SLOT_B A 10 A NG
B TIME_OF_DAY B OFF2ON B OPTION_SLOT_C B 11 B 3PHASE_TOTAL
C LOGIC C ON2OFF C OPTION_SLOT_D C 12 C NOT_USED
D D SWELL D SELF_TEST D 13 D NOT_USED
E E SAG E HARMONIC E 14 E NOT_USED
F F AND F INTERHARMONIC F 15 F NOT_USED
10 NAND 10 K_FACTOR 10 16
11 OR 11 FLICKER 11 PHASE
12 NOR 12 ENERGY 12 NEUTRAL
13 XOR 13 DATETIME 13 GROUND
14 NOT 14 TEMPERATURE 14 LN
15 OVER ABSOLUTE 15 INPUT_METERING_1 15 LL
16 UNDER ABSOLUTE 16 INPUT_METERING_2 16 THD
17 17 INPUT_METERING_3 17 UNBALANCE
18 18 INPUT_METERING_4 18 1
19 19 INPUT_METERING_5 19 DISPLACEMENT
1A 1A INPUT_METERING_6 1A DEMAND_LAST
1B 1B INPUT_METERING_7 1B DEMAND_PREDICTED
1C 1C INPUT_METERING_8 1C DEMAND_PRESENT
1D 1D INPUT_METERING_9 1D RMS
1E 1E INPUT_METERING_10 1E FUNDAMENTAL
1F NOT_USED 1F 1F ANGLE
20 20 DEMAND_PEAK
21 21 CREST_FACTOR
22 22 DISTORTION
23 23 INSTANTANEOUS
24 24 SHORT_TERM
25 25 LONG_TERM
26 26 POSITIVE_SEQUENCE
27 27 NEGATIVE_SEQUENCE
28 28 ZERO_SEQUENCE
29 29 TREND
2A 2A 3_PHASE
2B 2B ACCUMULATED
2C 2C CONDITIONAL
2D 2D INCREMENTAL
2E 2E TOU_RATE_1
2F 2F TOU_RATE_2
30 30 TOU_RATE_3
31 31 TOU_RATE_4
32 32
33 33
34 34
35 35
36 36
37 37
38 38
39 39
3A 3A
3B 3B
3C 3C
3D USER_DEFINED1 3D USER_DEFINED1
3E USER_DEFINED2 3E USER_DEFINED2
3F USER_DEFINED3 3F USER_DEFINED3
Code Abbreviation Description
0 No Units
1 % Percentage
2 °C Degrees Celsius
3 °F Degrees Fahrenheit
4 Deg Degrees Angular
5 Hz Hertz
6 A amperes
7 kA Kilo Amperes
8 V Volts
9 kV Kilo Volts
10 MV Mega Volts
11 W Watts
12 kW Kilowatts
13 MW Megawatts
14 VAR Volt-Ampere Reactive
15 kVAR Kilo Volt-Ampere Reactive
16 MVAR Mega Volt-Ampere Reactive
17 VA Volt-Amperes
18 kVA Kilo Volt-Amperes
19 MVA Mega Volt-Amperes
20 WH Watt-Hour
21 kWH Kilowatt-Hour
22 MWH Megawatt-Hour
23 VARH Reactive Volt-Ampere Hour
24 kVARH Reactive Kilo Volt-Ampere Hour
25 MVARH Reactive Mega Volt-Ampere Hour
26 VAH Volt-Ampere Hours
27 kVAH Kilo Volt-Ampere Hours
28 MVAH Mega Volt-Ampere Hours
29 Seconds Seconds
30 Minutes Minutes
31 Hours Hours
32 Bytes (RAM) Bytes
33 kBytes (RAM) Kilobytes
34 $ Dollars
35 gal gallons
36 gal/hr gallons/hour
37 gal/min gallons/minute
38 cfm cubic feet/min
39 PSI PSI
40 BTU BTU
41 L liters
42 ton-hours ton-hours
43 l/hr liters/hour
44 l/min liters/min
45 € Euros
46 ms Milliseconds
47 m³ cubic-meters
48 m³/sec cubic-meters/sec
49 m³/min cubic-meters/min
50 m³/hr cubic-meters/hour
51 Pa pascals
52 Bars bar
53 RPM Revolutions/min
55 BTU/hr BTU/hour
56 PSIG Pounds/square inch gauge
57 SCFM Standard cubic feet/min
58 MCF Thousand cubic feet
59 Therm Therm
60 SCFH Standard cubic feet/hour
61 PSIA pounds/square inch absolute
62 lbs pounds
63 kg Kilogram
64 klbs Kilopounds
65 lb/hr pound/hour
66 ton/hr ton/hour
67 kg/hr Kilogram/hour
68 in. Hg inch of Mercury
69 kPa kiloPascals
70 %RH percentage of relative humidity
71 MPH miles per hour
72 m/sec meters/sec
73 mV/cal/(cm²/min) milliVolts/calorie/(square centimeters/min)
74 in inches
75 mm millimeter
76 GWH GigaWatt-Hour
77 GVARH Reactive Giga Volt-Ampere Hour
78 GVAH Giga Volt-Ampere Hours
79 AH Ampere-Hours
80 kAH Kiloamp-Hours
81 Therm/hr Therm/hour
References

Y
O
P

R
W
C

ASCII Characters

Abbreviations
Passwords shall be 4 alphanumeric characters long.
Passwords shall always be entered and setup left-to-right.
Characters shall be selected from the following subset of US ASCII printable characters:

Character  Decimal      Description


#          35           NUMBER SIGN
$          36           DOLLAR SIGN
%          37           PERCENT SIGN
&          38           AMPERSAND
*          42           ASTERISK
+          43           PLUS SIGN
-          45           MINUS SIGN
/          47           SLASH
0          48           DIGIT ZERO
1          49           DIGIT ONE
2          50           DIGIT TWO
3          51           DIGIT THREE
4          52           DIGIT FOUR
5          53           DIGIT FIVE
6          54           DIGIT SIX
7          55           DIGIT SEVEN
8          56           DIGIT EIGHT
9          57           DIGIT NINE
?          63           QUESTION MARK
@          64           COMMERCIAL AT SIGN
A          65           CAPITAL LETTER A
B          66           CAPITAL LETTER B
C          67           CAPITAL LETTER C
D          68           CAPITAL LETTER D
E          69           CAPITAL LETTER E
F          70           CAPITAL LETTER F
G          71           CAPITAL LETTER G
H          72           CAPITAL LETTER H
I          73           CAPITAL LETTER I
J          74           CAPITAL LETTER J
K          75           CAPITAL LETTER K
L          76           CAPITAL LETTER L
M          77           CAPITAL LETTER M
N          78           CAPITAL LETTER N
O          79           CAPITAL LETTER O
P          80           CAPITAL LETTER P
Q          81           CAPITAL LETTER Q
R          82           CAPITAL LETTER R
S          83           CAPITAL LETTER S
T          84           CAPITAL LETTER T
U          85           CAPITAL LETTER U
V          86           CAPITAL LETTER V
W          87           CAPITAL LETTER W
X          88           CAPITAL LETTER X
Y          89           CAPITAL LETTER Y
Z          90           CAPITAL LETTER Z
a          97           SMALL LETTER a
b          98           SMALL LETTER b
c          99           SMALL LETTER c
d          100          SMALL LETTER d
e          101          SMALL LETTER e
f          102          SMALL LETTER f
g          103          SMALL LETTER g
h          104          SMALL LETTER h
i          105          SMALL LETTER i
j          106          SMALL LETTER j
k          107          SMALL LETTER k
l          108          SMALL LETTER l
m          109          SMALL LETTER m
n          110          SMALL LETTER n
o          111          SMALL LETTER o
p          112          SMALL LETTER p
q          113          SMALL LETTER q
r          114          SMALL LETTER r
s          115          SMALL LETTER s
t          116          SMALL LETTER t
u          117          SMALL LETTER u
v          118          SMALL LETTER v
w          119          SMALL LETTER w
x          120          SMALL LETTER x
y          121          SMALL LETTER y
z          122          SMALL LETTER z
Yes, data item is supported as standard feature
Yes, item is supported as an option
Data item is supported but is private

An R in the Access column means the register may be read.


A W in the Access column means the register may be written.
A C in the Access column means the register may only be written via a setup command.

0 1 2 3 4 5 6 7 8 9 A B C D E F
0 NUL SOH STX ETX EOT ENQ ACK BEL BS HT LF VT FF CR SO SI
1 DLE DC1 DC2 DC3 DC4 NAK SYN ETB CAN EM SUB ESC FS GS RS US
2 SP ! " # $ % & ' ( ) * + , – . /
3 0 1 2 3 4 5 6 7 8 9 : ; < = > ?
4 @ A B C D E F G H I J K L M N O
5 P Q R S T U V W X Y Z [ \ ] ^ _
6 ` a b c d e f g h i j k l m n o
7 p q r s t u v w x y z { | } ~ DEL

PRODUCTION_HISTORY - PROD_HIST
APPLIED – APLY
READING – READ
SHIFT – SFT
PRESENT – PRES
PREVIOUS – PREV
DURATION – DUR
NOMINAL – NOM
PRIMARY – PRI
SECONDARY – SEC
WIRECORRECT – SWC
FIELD_CAL_CT_RATIO_PH_A - FLD_CAL_CT_A
FIELD_CAL_VT_RATIO_PH_A - FLD_CAL_VT_A
R_METER_SETUP_ENERGY_OUT_PW01 - R_METER_SETUP_ENERGY_ PW01
R_METER_SETUP_ENERGY_OUT_DIGOUT_01 - R_METER_SETUP_ENERGY_DO_01
RS485 – 485
DIAG – DIA
DIAGNOSTIC – DIA
BEHAVIORAL – BEH
REGISTER – REG
OVER – OVR
UNDER – UND
CURRENT – CUR
VOLTAGE – VOLT
LEVEL – LVL
TYPE – TYP
ENABLE_PRI – EP
VOLT_LL – VLL
VOLT_LN – VLN
DATALOG – DLG
LEADING_PF_TRUE – LEDPFT
LAGGING_PF_TRUE – LAGPGT
LEADING_PF_DISP – LEDPFD
LAGGING_PF_DISP – LAGPGD
DEMAND – DEM
1S_STD – 1ST
TYPE_LEVEL – TL
UNBALANCE – UNB
ENERGY_ACCUM – ENG_ACC
ENERGY – ENG
INTERVAL - INT

s shall be 4 alphanumeric characters long.


s shall always be entered and setup left-to-right.
s shall be selected from the following subset of US ASCII printable characters:

ter  Decimal      Description


   35           NUMBER SIGN
   36           DOLLAR SIGN
   37           PERCENT SIGN
   38           AMPERSAND
   42           ASTERISK
   43           PLUS SIGN
   45           MINUS SIGN
   47           SLASH
   48           DIGIT ZERO
   49           DIGIT ONE
   50           DIGIT TWO
   51           DIGIT THREE
   52           DIGIT FOUR
   53           DIGIT FIVE
   54           DIGIT SIX
   55           DIGIT SEVEN
   56           DIGIT EIGHT
   57           DIGIT NINE
   63           QUESTION MARK
   64           COMMERCIAL AT SIGN
   65           CAPITAL LETTER A
   66           CAPITAL LETTER B
   67           CAPITAL LETTER C
   68           CAPITAL LETTER D
   69           CAPITAL LETTER E
   70           CAPITAL LETTER F
   71           CAPITAL LETTER G
   72           CAPITAL LETTER H
   73           CAPITAL LETTER I
   74           CAPITAL LETTER J
   75           CAPITAL LETTER K
   76           CAPITAL LETTER L
   77           CAPITAL LETTER M
   78           CAPITAL LETTER N
   79           CAPITAL LETTER O
   80           CAPITAL LETTER P
   81           CAPITAL LETTER Q
   82           CAPITAL LETTER R
   83           CAPITAL LETTER S
   84           CAPITAL LETTER T
   85           CAPITAL LETTER U
   86           CAPITAL LETTER V
   87           CAPITAL LETTER W
   88           CAPITAL LETTER X
   89           CAPITAL LETTER Y
   90           CAPITAL LETTER Z
   97           SMALL LETTER a
   98           SMALL LETTER b
   99           SMALL LETTER c
   100          SMALL LETTER d
   101          SMALL LETTER e
   102          SMALL LETTER f
   103          SMALL LETTER g
   104          SMALL LETTER h
   105          SMALL LETTER i
   106          SMALL LETTER j
   107          SMALL LETTER k
   108          SMALL LETTER l
   109          SMALL LETTER m
   110          SMALL LETTER n
   111          SMALL LETTER o
   112          SMALL LETTER p
   113          SMALL LETTER q
   114          SMALL LETTER r
   115          SMALL LETTER s
   116          SMALL LETTER t
   117          SMALL LETTER u
   118          SMALL LETTER v
   119          SMALL LETTER w
   120          SMALL LETTER x
   121          SMALL LETTER y
   122          SMALL LETTER z

You might also like