Location via proxy:   [ UP ]  
[Report a bug]   [Manage cookies]                

VF-3000 Traction User Manual PDF

Download as pdf or txt
Download as pdf or txt
You are on page 1of 138

MVFAC-3000 User Manual

Virginia Controls, Inc.


2513 Mechanicsville Turnpike
Richmond, Virginia 23223

Tel: (804) 225-5530


Fax: (804) 225-0116

email: eng@vacontrols.com
website: www.vacontrols.com

Revision 2.11
Revision 3.02
VIRGINIA CONTROLS, INC. MVFAC-3000 User Manual, Rev. 2.11 Page 1
Table of Contents

1. TABLE OF FIGURES .....................................................................................................7

2. PRE-INSTALLATION INSTRUCTIONS AND NOTES ........................................................8


2.1 General Notes .................................................................................................................................8

2.2 Important Precautions and Notes ....................................................................................................8

3. CONTROLLER INSTALLATION AND WIRING ..............................................................10


3.1 Controller Installation ....................................................................................................................10
3.1.1 Controller Location Selection and Environment ................................................................................... 10
3.1.2 Controller Grounding .......................................................................................................................... 11

3.2 Car and Hoistway Wiring................................................................................................................11


3.2.1 Floor Switches ..................................................................................................................................... 11
3.2.2 Car Top Selector .................................................................................................................................. 12
3.2.3 Leveling Switches ................................................................................................................................ 12
3.2.4 Terminal Landing Normal Slowdown Switches .................................................................................... 12
3.2.5 Terminal Landing Normal Limit Switches ............................................................................................. 12
3.2.6 Terminal Landing Final Limit Switches ................................................................................................. 13
3.2.7 Emergency Terminal Landing Limit Switch........................................................................................... 13
3.2.8 Hoistway Access Zone Switches........................................................................................................... 13
3.2.9 Door Open and Close Limit Switches ................................................................................................... 13

3.3 Machine Room Wiring ...................................................................................................................14


3.3.1 Incoming Power .................................................................................................................................. 14
3.3.2 Grounding ........................................................................................................................................... 14
3.3.3 Motor Wiring ...................................................................................................................................... 15

4. START-UP INSTRUCTIONS ........................................................................................16


4.1 Before Applying Power ..................................................................................................................16
4.1.1 Power and Grounding ......................................................................................................................... 16
4.1.2 Input/Output Wiring ........................................................................................................................... 16

4.2 Applying Power .............................................................................................................................17

4.3 Temporary Run Connections ..........................................................................................................17

5. FINAL ADJUSTMENTS ...............................................................................................18

VIRGINIA CONTROLS, INC. MVFAC-3000 User Manual, Rev. 2.11 Page 2


5.1 Inspection Operation .....................................................................................................................18

5.2 Floor Position and Slowdown .........................................................................................................19

5.3 Position Indicators .........................................................................................................................19

5.4 Independent Service ......................................................................................................................19

5.5 Car and Hall Calls ...........................................................................................................................20

5.6 Door Operation..............................................................................................................................20

5.7 Fire Service ....................................................................................................................................21

5.8 Failure Timers ................................................................................................................................21


5.8.1 Stuck Button Timer.............................................................................................................................. 21
5.8.2 Running Timers ................................................................................................................................... 21
5.8.3 Door Fault Timers................................................................................................................................ 22
5.8.4 Door Check Circuitry ........................................................................................................................... 22

5.9 Field Adjustable Features...............................................................................................................22

5.10 Zoned Duplex Operation.............................................................................................................23


5.10.1 Common Circuits................................................................................................................................. 23
5.10.2 Next Car .............................................................................................................................................. 23
5.10.3 Car Start .............................................................................................................................................. 23
5.10.4 Homing ............................................................................................................................................... 24
5.10.5 Communication .................................................................................................................................. 24

5.11 ETSD Monitoring System Setup ..................................................................................................25


5.11.1 Setup of the UCM (Unintended Car Movement) System ...................................................................... 26
5.11.2 Setup of the O-S (Over Speed) System ................................................................................................. 28
5.11.3 Setup of the ETSD (Emergency Terminal Stopping Device) System ....................................................... 34

5.12 A-B Micro PLC Setup ...................................................................................................................37


5.12.1 SPECIAL ADJUSTMENTS with ETSD/UCM BOARD, HSC ......................................................................... 37
5.12.2 SPECIAL FAULTS for ETSD/UCM BOARD, HIGH SPEED COUNTER .......................................................... 38
5.12.3 ADJUST MODE..................................................................................................................................... 38
5.12.4 ALLEN-BRADLEY MICRO830 HSC SETUP. .............................................................................................. 39
5.12.5 CALIBRATE THE HIGH SPEED COUNTER. .............................................................................................. 39
5.12.6 TROUBLESHOOTING ............................................................................................................................ 40
5.12.7 ALLEN-BRADLEY PLC OUTPUTS and INPUTS ......................................................................................... 40
5.12.8 SPEED CODES ...................................................................................................................................... 40

6. CONTROLLER HARDWARE DESCRIPTION .................................................................41


6.1 Transformers .................................................................................................................................41
VIRGINIA CONTROLS, INC. MVFAC-3000 User Manual, Rev. 2.11 Page 3
6.2 Fuses .............................................................................................................................................42

6.3 12VDC Power Supply .....................................................................................................................42

6.4 Safety Interface .............................................................................................................................43


6.4.1 Bypass Switches .................................................................................................................................. 43
6.4.2 Inspection Switches............................................................................................................................. 43
6.4.3 Phase Monitor .................................................................................................................................... 43
6.4.4 Digiset Timer....................................................................................................................................... 44

6.5 Microprocessor..............................................................................................................................45
6.5.1 CPU ..................................................................................................................................................... 45
6.5.2 Input/Output Boards ........................................................................................................................... 53
6.5.3 I/O Board Connectors.......................................................................................................................... 56

6.6 ETSD Monitoring System ...............................................................................................................59


6.6.1 Unintended Car Movement (UCM) System.......................................................................................... 60
6.6.2 Over-Speed System (O-S) System ........................................................................................................ 63
6.6.3 Emergency Terminal Slowdown Device (ETSD) System ........................................................................ 66
6.6.4 ETSD Monitoring System Routine Maintenance ................................................................................... 69
6.6.5 ETSD Board Specifications ................................................................................................................... 73
6.6.6 Speed (Photo) Sensor & Cable Specifications ....................................................................................... 75

7. MH-3000 SCREENS AND DIAGNOSTICS ....................................................................76


7.1 Run Mode ......................................................................................................................................76
7.1.1 Run Mode Screens .............................................................................................................................. 76
7.1.2 Show I/O Status .................................................................................................................................. 78
7.1.3 Show Fault Log .................................................................................................................................... 78
7.1.4 Show Internal Memory ....................................................................................................................... 93
7.1.5 Show Car Status .................................................................................................................................. 95
7.1.6 Go To Set-Up Mode ............................................................................................................................. 99
7.1.7 Effect of Diagnostic Modes on Scan Time ............................................................................................ 99

7.2 Set-Up Mode ............................................................................................................................... 100


7.2.1 How to Enter Set-Up Mode ............................................................................................................... 100
7.2.2 How to Exit Set-Up Mode .................................................................................................................. 100
7.2.3 Set-Up Mode Screens ........................................................................................................................ 100
7.2.4 Reset Settings ................................................................................................................................... 101
7.2.5 Change Settings ................................................................................................................................ 102
7.2.6 Change Features ............................................................................................................................... 114
7.2.7 Show Fault Log .................................................................................................................................. 116
7.2.8 Show Internal Memory ..................................................................................................................... 116
7.2.9 Set the Time ...................................................................................................................................... 116
7.2.10 Enter Password ................................................................................................................................. 117
7.2.11 Test I/O Boards ................................................................................................................................. 118

VIRGINIA CONTROLS, INC. MVFAC-3000 User Manual, Rev. 2.11 Page 4


8. CONTROLLER NOMENCLATURE ............................................................................. 120

9. PARTS LIST.............................................................................................................. 121

10. TROUBLESHOOTING SUGGESTIONS ....................................................................... 123


10.1 Locating Faults ......................................................................................................................... 123
10.1.1 Troubleshooting I/O Board Communication Problems....................................................................... 124

10.2 I/O Board Replacement ............................................................................................................ 125

10.3 Factory Assistance .................................................................................................................... 125

10.4 Changes for Program Revisions ................................................................................................ 126


10.4.1 Program Revision 3B ......................................................................................................................... 126
10.4.2 Program Revision 3C ......................................................................................................................... 126

11. CONTROLLER MAINTENANCE................................................................................. 127


11.1 Periodic Maintenance............................................................................................................... 127

11.2 Parts Replacement ................................................................................................................... 127


11.2.1 CPU Exchange ................................................................................................................................... 127
11.2.2 EPROM Memory Chip Exchange ........................................................................................................ 128
11.2.3 Input/Output Board Exchange ........................................................................................................... 129

12. FREQUENTLY ASKED QUESTIONS ........................................................................... 130


12.1 Questions on Field Devices ....................................................................................................... 130

12.2 Questions on Field Devices ....................................................................................................... 130

12.3 Questions on the Controller ..................................................................................................... 131

13. DRIVE SPECIAL INSTRUCTIONS ............................................................................... 133


13.1 Over Speed Test ....................................................................................................................... 133

14. ETSD MONITORING SYSTEM TESTING .................................................................... 133


14.1 UCM System Testing ................................................................................................................ 133
14.1.1 When equipped for Rope Brake Operation ........................................................................................ 133
14.1.2 When equipped for Emergency Brake Operation............................................................................... 134

VIRGINIA CONTROLS, INC. MVFAC-3000 User Manual, Rev. 2.11 Page 5


14.2 O-S System Testing ................................................................................................................... 134

14.3 ETSD System Testing ................................................................................................................ 135

15. INDEX ..................................................................................................................... 136

VIRGINIA CONTROLS, INC. MVFAC-3000 User Manual, Rev. 2.11 Page 6


1. Table of Figures
Figure 1 - ETSD Monitoring System Hardware ........................................................................................ 25
Figure 2 - UCM SELECT Jumper .............................................................................................................. 26
Figure 3 - ETSDFT & SHTDFT Input Indicators ......................................................................................... 26
Figure 4 - EX1, EX2, ET1, ET2, RBP1 & RBP2 Output Indicators ................................................................ 27
Figure 5 - ETSD Tape .............................................................................................................................. 28
Figure 6 - Speed Sensor & Mounting Bracket ......................................................................................... 28
Figure 7 – “PHOTO” Connector on ETSD Board....................................................................................... 29
Figure 8 – Installed ETSD Tape & Sensor ................................................................................................ 29
Figure 9 - Sensor Green POWER LED Indicator ....................................................................................... 30
Figure 10 - Sensor Yellow SENS. LED Indicator........................................................................................ 30
Figure 11 - PHOTO-1 Indicator ............................................................................................................... 30
Figure 12 - PHOTO-0 Indicator ............................................................................................................... 31
Figure 13 - Sensor L/D Switch ................................................................................................................ 31
Figure 14 - Output Indicators ................................................................................................................. 32
Figure 15 - O-S TUNED Indicator ............................................................................................................ 32
Figure 16 - State LEDs and DIP Switches ................................................................................................. 33
Figure 17 - Output Indicators ................................................................................................................. 35
Figure 18 - ETSD TUNED Indicator .......................................................................................................... 35
Figure 19 - State LEDs and DIP Switches ................................................................................................. 36
Figure 20 - ETSD Monitoring System ...................................................................................................... 59
Figure 21 - UCM TRIP Indicator .............................................................................................................. 61
Figure 22 - O-S TRIP Indicator ................................................................................................................ 64
Figure 23 - O-S RESET Push Button ......................................................................................................... 64
Figure 24 - ETSD TRIP Indicator .............................................................................................................. 68
Figure 25 - ETSD RESET Push Button....................................................................................................... 68
Figure 26 - ETSD Tape ............................................................................................................................ 69
Figure 27 - Speed Sensor ....................................................................................................................... 70
Figure 28 - +24V and +3.3V Indicators& Test Points ............................................................................... 71
Figure 29 - Sensor POWER LED Indicator ................................................................................................ 71
Figure 30 - Sensor SENS. LED Indicator ................................................................................................... 72
VIRGINIA CONTROLS, INC. MVFAC-3000 User Manual, Rev. 2.11 Page 7
Figure 31 - PHOTO-1 Indicator ............................................................................................................... 72
Figure 32 - ETSD Board .......................................................................................................................... 74
Figure 33 - Speed (Photo) Sensor & Cable .............................................................................................. 75

2. Pre-Installation Instructions and Notes


2.1 General Notes
It is strongly recommend that you read this manual carefully before proceeding with the installation.
Important information is highlighted by the headings WARNING, CAUTION, or NOTE. These words are
defined as follows:

WARNING - Warnings are used to indicate instructions which, if not followed


correctly, will probably result in personal injury or substantial damage to equipment.

CAUTION - Cautions are used to indicate instructions or information which, if not


observed, may result in some damage to equipment if care is not taken.

NOTE - Notes are used to indicate instructions or information which is especially


helpful in understanding and operating the equipment, and which will usually speed
up the installation process.

2.2 Important Precautions and Notes


The following general rules and safety precautions must be observed for safe and reliable operation of
your system.

WARNING: If you need to change the EPROM program chip on the CPU board, make
sure you read the instructions and know exactly how to install the new chip. Plugging
the EPROM chip in upside-down may damage the chip. Static electricity can damage
the EPROM, so avoid touching the pins on the chip, and ground yourself (by touching
the controller cabinet) before touching the chip or the controller. Do not expose the
EPROM program chip to bright light, and do not remove the label over the EPROM
program chip window.

WARNING: The elevator controller must be installed by experienced field installation


personnel. The field installation personnel must know and follow all the rules and
regulations pertaining to the safe installation and running of elevators. Additional
information for specific devices (such as the valves, door operator, etc.) is the
responsibility of the manufacturers of those devices.

WARNING: This equipment is designed and built to comply with ANSI A17.1, ASME
A17.5 and CAN/CSA B44.1 and must be installed by a qualified contractor. It is the
VIRGINIA CONTROLS, INC. MVFAC-3000 User Manual, Rev. 2.11 Page 8
responsibility of the contractor to make sure that the final installation complies with
all applicable local, state and national codes, and is installed safely.

WARNING: The 3 phase AC power supply to this equipment must come from a fused
disconnect switch or circuit breaker which is sized in accordance with all applicable
national, state and local electrical codes, in order to provide the necessary overload
protection for the controller and motor. Incorrect motor branch circuit protection
may create a hazardous condition.

WARNING: Proper grounding is vital for the safe operation of your system. Bring the
ground wire to the ground stud that is labeled "GND" or "G". You must choose the
proper conductor size. See national electrical code article 250-95, or the related local
applicable code.

Pay special attention to points highlighted in this manner. They are of


special consideration and are frequently overlooked.

VIRGINIA CONTROLS, INC. MVFAC-3000 User Manual, Rev. 2.11 Page 9


3. Controller Installation and Wiring
3.1 Controller Installation

3.1.1 Controller Location Selection and Environment


Mount the controller in a location that provides:
• adequate support for the weight of the controller,
• adequate lighting for installation and maintenance,
• convenient access for the routing of required conduits and cables,
• convenient access to other devices in the machine room,
• a minimum of vibration (supply additional bracing or reinforcement if required).

For improved controller reliability:


• Keep the machine room clean.
• Do not install the controller in a dusty area.
• Do not install the controller in a carpeted area, or area where static electricity is a problem.
• Keep room temperature between 0°C to 40°C (0°F to 104°F), and 95% non-condensing relative
humidity. Extended high temperatures will shorten the life of electronic components. Provide
adequate ventilation or air-conditioning as required if necessary.
• Avoid condensation on the equipment. Keep the controller away from sources of condensation and
water (such as open windows) as these can create a hazardous condition and can damage the
equipment.
• Do not install the controller in a hazardous location and where excessive amounts of vapors or
chemical fumes may be present. A NEMA 4 or NEMA 12 rated enclosure can be provided if
necessary.
• Make sure power line fluctuations are within the drive ratings.
• High levels of radio frequency emissions may cause interference with the controller and drive micro-
processors, and produce unexpected and even dangerous results. This could be caused by hand-
held communications devices used near the controller.
• Long term operation of the controller without the door or cover in place is not recommended.

VIRGINIA CONTROLS, INC. MVFAC-3000 User Manual, Rev. 2.11 Page 10


3.1.2 Controller Grounding
3.1.2.1 Grounding of the controller must conform to all applicable codes. Proper
grounding is essential to the safe operation of the equipment. It will also reduce the
likelihood of noise-induced problems, which could include CPU crashes, or I/O
communication errors.
• The grounding wire should be sized per the applicable codes.
• Connect the ground to a good building ground, such as the structural steel of the building, or
a cold water pipe.

3.2 Car and Hoistway Wiring


Review the schematics and field wiring diagrams before attempting to hook up the controller.

3.2.1 Floor Switches


The Floor Switches, if used, are normally open contacts that should close under each of the following
conditions:
1. the car is at the slowdown point above the floor, OR
2. the car is at the slowdown point below the floor, OR
3. the car is at the floor (optional), OR
4. the car is between the up and down slowdown points of that landing (optional).
Conditions (1) and (2) are required to change the floor relays and initiate slowdown. Condition (3) is
required at the terminal landings, but is optional at the intermediate landings. Condition (4) is optional.
There are many acceptable methods of providing the floor switch signals, such as by having a single
Floor Switch at floor level, and an adjustable length cam on the car, or by having two Floor Switches per
floor, and a fixed length cam on the car. The Floor Switches may be mounted on the car if they are in
separate rows. It is recommended that the method used allow for separate adjustment of the up and
down slowdown distances.

NOTE: Recommended slowdown distance is about 6" for every 25fpm of car speed,
for speeds of up to 200fpm. Minimum recommended target length for the floor
switches is 1".
If there are short floors, refer to the schematic for special instructions, if required.

NOTE: The terminal landing Floor Switches must be maintained while the car is within
door zone of the terminal landing.

VIRGINIA CONTROLS, INC. MVFAC-3000 User Manual, Rev. 2.11 Page 11


3.2.2 Car Top Selector
The pulsing-type Car Top Selector provides Floor Change/Slowdown signals and Leveling signals, as
shown on the car top selector sheet in the schematic. The signals should be a normally open contact
that closes as described below.
1. UP SLOWDOWN closes at the Slowdown distance below the floor.
2. DOWN SLOWDOWN closes at the Slowdown distance above the floor.
3. UP and DOWN LEVEL, and DOOR ZONE/LOW LEVEL. (See "Leveling Sws")

NOTE: Recommended slowdown distance is about 6" for every 25fpm of car speed,
for speeds of up to 200fpm. Minimum recommended target length for the floor
switches is 1".

An extra reset target is required at each terminal landing, as shown on the


schematic, so that the Up Slowdown Switch is closed when the car is in the leveling
zone at the top landing, and the Down Slowdown Switch is closed when the car is in
the leveling zone at the bottom landing. These targets are used to reset the floor
position at the terminal landings.

3.2.3 Leveling Switches


The Up Level Switch is a normally open contact that closes when the car is in the leveling zone below the
floor, and the Down Level Switch is a normally open contact that closes when the car is in the leveling
zone above the floor. Adjust the distance between the Up Level Switch and the Down Level Switch to be
equal to the length of the leveling vane/target plus the desired Dead Zone distance (usually 1/4" to
1/2"). The actual length of the leveling target is not critical (except in some short floor situations) and is
usually 6-10". Position the leveling vane/target so that when the car is floor level the Up and Down
Leveling Switches are centered around the vane/target, and both switches are open.
The Door Zone Switch is a switch (or switches) activated by the leveling vane/target when the car is
within 3" of floor level. If the leveling vane/target is 6" long, then only one switch is required, mounted
between the Up and Down Leveling Switches, otherwise two switches wired in series should be
provided.

3.2.4 Terminal Landing Normal Slowdown Switches


The Terminal Landing Normal Slowdown Limit Switch is a normally closed contact that opens when the
car is closer to a terminal landing than the minimum slowdown distance. It will prevent the car from
running into the terminal landing at full speed. It should be adjusted to open approximately one inch
beyond the point where the normal slowdown (from the floor switches or the car top selector) is
initiated.

3.2.5 Terminal Landing Normal Limit Switches


The Terminal Landing Normal Limit Switch (sometimes called a Directional Limit Switch) is a
normally closed contact that opens when the car has traveled 1" past floor level at a terminal
landing. The car should not be on the Terminal Landing Normal Limit Switch when the car is
VIRGINIA CONTROLS, INC. MVFAC-3000 User Manual, Rev. 2.11 Page 12
floor level at the terminal landing. The Limit Switch will prevent the car from traveling further away
from the normal area of car travel, but allows the car to run back towards the normal area of car travel.

3.2.6 Terminal Landing Final Limit Switches


The Terminal Landing Final Limit Switch, where required by code, is a normally closed contact that opens
when the car has gone a considerable distance beyond floor level at a terminal landing. It will prevent
any further movement of the car in either direction. Consult the applicable codes for the proper setting
of this switch.

3.2.7 Emergency Terminal Landing Limit Switch


The Emergency Terminal Landing Slowdown Switch should be installed as required by the applicable
codes. It is a normally closed contact that opens after the car has gone beyond the Terminal Landing
Normal Limit Switch.

3.2.8 Hoistway Access Zone Switches


The Hoistway Access Limit Switches limit the motion of the car on Hoistway Access, by disabling the car
if it moves away from the access floor. Install the zone switches to stop the car from running down if the
top of the car goes below floor level at the top access floor, and to stop the car from running up if the car
goes above the second floor while on Hoistway Access at the bottom floor.

3.2.9 Door Open and Close Limit Switches


The Door Open Limit Switch is open when the doors are fully open, and closed at all other times. It will
de-energize the door open relays in the door operator when the doors have opened fully.
The Door Close limit Switch is open when the doors are fully closed, and closed at all other times. It will
de-energize the door close relays in the door operator when the doors have closed fully.

NOTE: Many problems in operation can be attributed to failures in the Door Open or
Close Limit Switches (including long door times, improper door operation on Fire
Service, inability to go on to or to clear Fire Service, etc.) Always check the Door Open
and Close Limit Switches if unusual operation of the elevator is observed.

NOTE: It is recommended that the Door Close Limit Switch be adjusted so that, as the
doors are closing, the Car Door Contact closes before the Door Close Limit opens.
Consult the Door Operator Manufacturer's installation instructions for further details
on the adjustment of the doors.

NOTE: 2000 (or later) code compliant controllers will not run without the Door Close
Limit operation properly.

NOTE: If a solid state door operator unit is being used, check the appropriate
schematics to see if any changes are required on the actual operator. These may
include changing resistors in the operator, and adding a diode for proper open and
close torque.

VIRGINIA CONTROLS, INC. MVFAC-3000 User Manual, Rev. 2.11 Page 13


3.3 Machine Room Wiring
Mount the controller firmly and install all required conduits before wiring the controller. Note where
duct has been provided in the controller for customer access, before deciding where to locate conduit
openings.

WARNING: Do not allow any metal shavings to get into relays or contactors, or in or
behind the electronic components, as these could cause serious damage to personnel
or the equipment.

3.3.1 Incoming Power


WARNING: THE 3 PHASE AC POWER SUPPLY TO THIS EQUIPMENT MUST COME FROM
A FUSED DISCONNECT SWITCH OR CIRCUIT BREAKER WHICH IS SIZED IN ACCORDANCE
WITH ALL APPLICABLE NATIONAL, STATE AND LOCAL ELECTRICAL CODES, IN ORDER TO
PROVIDE THE NECESSARY OVERLOAD PROTECTION FOR THE CONTROLLER AND
MOTOR. INCORRECT MOTOR BRANCH CIRCUIT PROTECTION MAY CREATE A
HAZARDOUS CONDITION.
Incoming AC power wiring should be done by a qualified and licensed electrician, using the appropriate
size wires for the installation. Consider the motor size and type of starter, and also the length of wire
required from the main power distribution center in determining the proper wire size.
Proper branch circuit protection and disconnect device(s) must be provided, as required by applicable
local, state and national codes.

3.3.2 Grounding
WARNING: PROPER GROUNDING IS VITAL FOR THE SAFE OPERATION OF YOUR
SYSTEM. BRING THE GROUND WIRE TO THE GROUND STUD THAT IS LABELED "GND"
OR "G1". YOU MUST CHOOSE THE PROPER CONDUCTOR SIZE AND MINIMIZE THE
RESISTANCE TO GROUND BY USING SHORTEST POSSIBLE ROUTING. SEE NATIONAL
ELECTRICAL CODE ARTICLE 250-95, OR THE RELATED LOCAL APPLICABLE CODE.

Proper grounding is vital for the safe operation of your system, and will also reduce the
likelihood of noise-induced problems, which could include CPU crashes, or I/O communication
errors.

• The grounding wire should be sized per the applicable codes.


• Connect the ground to a good building ground, such as the structural steel of the building, or a cold
water pipe.
• Connect the ground on the controller to the stud labeled "GND" or the terminal "G1", as shown on
the controller schematic.

VIRGINIA CONTROLS, INC. MVFAC-3000 User Manual, Rev. 2.11 Page 14


3.3.3 Motor Wiring
Connect the motor as shown on the schematic. Consult the applicable codes for proper wire sizing and
circuit protection for the motor being used.
Refer to the schematic for the location of the motor connections to the Drive.
Connect the encoder as shown on the schematic, if required.

VIRGINIA CONTROLS, INC. MVFAC-3000 User Manual, Rev. 2.11 Page 15


4. Start-Up Instructions
If it is desired to run the car temporarily, during construction, the microprocessor must still be used to
move the car. All normal inputs and safety devices will be required for the microprocessor to run the
car. If a safety device is not installed yet, all necessary safety precautions should be made before
jumping out the device. It remains the responsibility of the installing technicians to make sure that the
elevator is run in a safe mode, and that all operators are aware of any safety devices that may have been
disabled.

4.1 Before Applying Power


The system has been programmed and tested for the specific elevator system, so no further changes
should be made without consulting with Virginia Controls.

4.1.1 Power and Grounding


WARNING: Confirm that the voltage of the incoming power matches the controller
before applying power to the controller.
Check the system for improper grounds before applying power to the controller.
With the power off, remove the fuses from the secondary of the main control circuit transformer
("CCXF"). Check the safety circuit (terminals 1 through 6, and 14, 16, 18, 19) for grounds. Using a Volt-
Ohm meter connect one lead to terminal 35 (ground) and touch the other lead to each terminal to be
tested. The resistance should be considerably greater than 100 ohms.

NOTE: If the fuses are not removed, the meter will read a short through the windings
of the main control circuit transformer.
With the fuses still removed, apply power to the controller, and verify that the voltage at the secondary
of the main control circuit transformer ("CCXF") is 110-125VAC.

4.1.2 Input/Output Wiring


NOTE: The input/output boards are equipped with quick disconnect terminal blocks.
During the initial installation, you may want to remove the terminal blocks, hook up
your field wires to the terminal blocks, test the field wiring for no shorts to ground or
hot (terminal 1) before plugging these terminals back into the I/O boards.
With the power off, and the fuses removed, check each input point for grounds, as described in the
previous section, "Power and Grounding". If a ground is observed, check the schematic to determine if
this is correct (it usually is NOT!).
With the power off check each output for grounds, also check for shorts to the hot side (terminal 1).
Note that some field devices, such as buzzers, will have very low resistance.

WARNING: Each output point should be isolated from ground and the hot side.
VIRGINIA CONTROLS, INC. MVFAC-3000 User Manual, Rev. 2.11 Page 16
4.2 Applying Power
Remove all fuses before applying power. Reinsert the fuses, one circuit at a time, checking each circuit
before adding the next.
It is recommended that you start up the controller in Inspection mode, which can be done by opening
the Inspection Switch, or removing the field wire(s) from terminal 23.

WARNING: The field wire in terminal 23 is HOT. If it is removed, make sure it is


insulated and labeled. Reconnect it when the car is to be taken off Inspection
Operation.

4.3 Temporary Run Connections


The controller should be connected as shown on the schematic, with all safety devices installed. If the
installing company needs to run the car before all safety devices are installed, they will assume the
responsibility for the safe operation of the elevator.
Make sure that any special operation inputs (such as Fire Service, Emergency Power, etc) are in the
proper state to allow the car to run. If necessary, and if it is safe to do so, jump these out during
construction.
Refer to the appropriate section for the type of Drive supplied for instructions on starting up the Drive.
Also refer to the schematic for connections, and parameters that may require adjustment.

VIRGINIA CONTROLS, INC. MVFAC-3000 User Manual, Rev. 2.11 Page 17


5. Final Adjustments
When the controller is ready to be run in automatic, it is recommended that EITHER a factory reset be
performed OR the values of the settings and features be verified. If the program is custom (the job
number will be in the bottom line of the banner) then a factory reset is recommended. If the job is not
custom, then if a factory reset is done, all the values and settings for the job must be re-entered. Refer
to the section Controller Diagnostics/Set-up Mode/Reset Settings, or in Controller
Maintenance/Frequently Asked Questions/How Do I Reset All Settings and Features Back to the Original
Values.
A factory reset can be done by:
1. Turning off the power;
2. Put the car on inspection;
3. Jump terminals 1 to 21 and 1 to 22;
4. Turn on the power for 15 seconds;
5. Turn off the power, and remove the jumpers, and continue as normal.
Alternatively, the keypad can be used. Press Nxt until the menu item "Go to Setup Menu" is displayed,
then press Ent 3 times. (The screen will show a warning, then go to the Setup Menu, where the first
item is Reset (factory) Settings). The password “911” should be entered when requested. Press Esc to
return the elevator to service.
As the wiring is completed, the following modes of operation can be checked and used.

5.1 Inspection Operation


To run the car on Inspection Operation, the safety string (including the door contacts, terminal landing
normal slowdowns, normals and finals) should be operational.
The Doors Closed and Gate Closed inputs on the I/O board should be on.
The Inspection Input should be de-energized.
Pressing the Up Run and Run Buttons will energize the Up Inspection Input, which will cause the Up
Direction and Door Close outputs to come on. (The Inspection Run Inputs may be connected to the Car
Call Inputs. See the schematic for the actual connections for each particular job)
When the Doors Closed input comes on, the up run outputs for the motor and the valves will energize,
and the car will run up.
(Down direction is similar)

NOTE: If Hoistway Access is used to get on top of the car, then the doors will be open
when Top of Car Inspection is initiated. In this case, the doors will close when the Up
(or Down) Run and Run (or Enable) buttons are pressed. If it is required that the doors
should only operate manually on Inspection, then the Bit Feature to “Disable Door

VIRGINIA CONTROLS, INC. MVFAC-3000 User Manual, Rev. 2.11 Page 18


Close on Inspection” should be enabled. In this case the doors must be closed
manually or by means of the Door Close button on the Door Operator (if provided).

NOTE: If 2000 (or later) Code is provided, then the controller is expecting terminal 3 to
go low when the Inspection Run Buttons are not being pressed. If a temporary run
station is being used that is not wired as shown on the schematics, then the controller
will show a fault if terminal 3 does not go low when the car stops. The redundancy
fault can be temporarily defeated by turning Switch 3 on the CPU Slide Switch S2 to
the ON position. This will also turn on the Fire Audible Visible output, as a reminder to
turn off the defeat when the car is ready for full operation.

5.2 Floor Position and Slowdown


The program is in EPROM (Electrically Programmable Read Only Memory). The floor relays and fire
service relays are maintained in the micro-processor RAM memory and are held through power loss by a
battery on the CPU board. The floor relays may need to be reset when the controller is initially installed.
This will be accomplished when the elevator hits any floor switch. With a pulsing type selector, the floor
position is reset at either terminal landing when a slowdown switch and the Door Zone switch are
energized at the same time.

NOTE: If floor switches are used, they should be maintained at the terminal landings,
so that they are energized whenever the car is in the slowdown zone at that landing.
Make your final adjustments for the slowdown targets. All slowdown distances should be equal.
If a pulsing selector arrangement is used, remember to install the reset targets at the terminal landings.

5.3 Position Indicators


Verify that the floor position changes properly as the car goes past each landing. Floor change should
take place at the slowdown point before each landing.
If the Position Indicator does not match the actual car position, run the car to a terminal landing reset
target (with pulsing selector only).

5.4 Independent Service


Independent Service is useful for final tune-up of the car. Initiate Independent Service by turning on the
Independent Service Switch in the car, or by jumping the Independent Service Switch input.
On Independent Service, the hall calls will be canceled. The car will run from car calls only, and will park
with the doors open. To close the doors, jump terminal 1 to terminal 28 ("Door Close Button" input).
This jumper may be left on, if desired, so that the car may be run by jumping the desired car call input.

NOTE: To run the car from the machine room, without the doors opening, turn off the
DOL Cutout Switch. This will de-energize the Door Open Limit Sw Input, and prevent
the doors from opening.
VIRGINIA CONTROLS, INC. MVFAC-3000 User Manual, Rev. 2.11 Page 19
NOTE: If the car does not run, verify that no door protective device (Door Open
Button, Safety Edge, Electric Eye, Infra-red Curtain) is holding the doors open. Verify
that the car is not stuck in leveling. Verify that the Door Contacts input is energized
and the Door Close Limit input is de-energized.

5.5 Car and Hall Calls


To observe the operation of the car and hall calls, the system must be in automatic operation (LED D1 on
the CPU board should be on.) Verify that all car and hall calls work.

NOTE: On DUPLEX systems the doors must be allowed to operate for the calls to be
canceled properly.
Each call will be canceled when the car initiates slowdown for the call, or when the doors start to re-
open for the call if the car is already at the floor.
If both hall calls are entered at an intermediate landing, and no other calls are in the system, the doors
will close after answering one of the calls, then re-open in response to the other call.

5.6 Door Operation


Verify that any required changes to the door operator, as shown on the door operator drawings, have
been made correctly.
Check the Door Open and Close Limits for proper operation.
If the doors attempt to open for too long, the open cycle will be stopped. The car will then respond to
other calls, and try to open the doors again.
If the doors fail to close properly within a preset time, the doors will re-open, and try to close again. If
the doors closed, but the car does not run in response to a call, the doors will re-cycle, and the car will
try again.
For very slow doors, the Door Stuck Timer, which initiates the Door Open and Door Close Fail, as
described above, may need to be increased. It is normally set at 15 seconds.
If Nudging Operation is activated, the Electric Eye will be disabled when the Nudging Timer has tripped
AND the doors are fully open. If the nudging timer trips while the doors are closing, the Nudging Buzzer
will turn on, and the Electric Eye will remain active. If the doors do reopen fully, then the Electric Eye
will be cut out. The Safety Edge Input remains active on nudging.

VIRGINIA CONTROLS, INC. MVFAC-3000 User Manual, Rev. 2.11 Page 20


5.7 Fire Service
Fire Service Phase 1 may be initiated by turning off a Smoke Sensor input, or by energizing the Hall Fire
Switch "On" input.
Confirm that the car returns to the correct Main and Alternate landings.
Confirm that the car operates as required on Car Fire Service (Phase 2) operation.

NOTE: To reset Hall Fire Service (Phase 1), most codes require the Bypass input be
energized. To disable Hall Fire Service, jump the Hall Bypass input on. On 2000 (or
later) Fire Code, Fire Service (Phase 1) is reset when the Hall Fire Switch is turned from
Bypass to Off.

NOTE: If Car Fire Service (Phase 2) appears to be operating incorrectly, check the Door
Open and Close Limits for proper operation. Most codes require that the doors be
fully open before allowing a change in the mode of operation on Car Fire Service.
Most codes require that Hall Fire Service (Phase 1) be in effect for the car to return
automatically to the main fire landing when the Car Fire Switch is turned to the off
position.

5.8 Failure Timers

5.8.1 Stuck Button Timer


If a car or hall call button remains on for an adjustable time, and other calls are registered, the stuck
button call will be ignored, and the car will answer the other call(s). The car will return to the stuck
button call as it answers other calls, and the stuck button timer sequence will be repeated.

5.8.2 Running Timers


If the car runs for an adjustable time, without changing floors, then running shutdown operation will be
initiated. The Shutdown LED on the CPU will come on. The Shutdown could be caused by a problem
with the motor starter circuit(s); or a problem with the drive system; or a problem with the selector. The
car will stop immediately. It will then be shut down, with only the Door Open Button and door
protective devices being operational. The fault can be reset by cycling the Main Line Disconnect Switch,
or by putting the car on "Inspection" then back to "Automatic".

NOTE: If a Reverse Phase Relay or Emergency Power circuitry is supplied, these will
also initiate a shutdown signal if the inputs are not energized.
A sequence fault timer monitors key inputs from the drive system, such as Drive Enabled, Brake Micro
Switch, and contacts of the key drive contactors. If these fail to change state properly as the car starts or
stops, then the car will be shut down. The fault can be reset by cycling the Main Line Disconnect Switch,
or by putting the car on "Inspection" then back to "Automatic".

VIRGINIA CONTROLS, INC. MVFAC-3000 User Manual, Rev. 2.11 Page 21


A leveling timer is provided that will cut out leveling if the car has been leveling for over 15 seconds.
This prevents the car from stalling in leveling. The car will not be shut down, but will not be allowed to
relevel until the car has run to another floor.
If the car stops between floors, it will run down until it energizes the Door Zone Input, or a Leveling
Switch Input. This prevents the car from parking between floors. If the car runs down for over 1 minute
while looking for a floor, it will stop, and return to normal operation.

5.8.3 Door Fault Timers


If the doors fail to open fully after an adjustable time, the open cycle will be canceled. The door time
will expire as normal, the doors will close, and the car will continue to answer calls.
If the doors fail to close after an adjustable time, the doors will reopen, and attempt to close again. The
doors will be held open an adjustable time (factory set at 15 seconds) which allows the door motor to
remain cool. The close cycle will be repeated until the doors close.

5.8.4 Door Check Circuitry


Door Check circuitry is an optional feature that is provided as required by the appropriate codes. The
circuit checks to make sure the Door Contacts in the safety string are not jumped out. A Door Contact
fault condition is recognized if ALL the following conditions exist:
1. The "DC" or "DG" relay Input is energized (the car or hall doors are closed), AND
2. The Door Close Limit Input is energized (the car door is not fully closed), AND
3. The Up Level and Down Level Inputs are both off (the car is not leveling).
4. The doors are not opening or closing.
If the above fault condition exists then the fault will be initiated after 0.1 seconds. When a Door Fault is
initiated, the Door Fault Output will energize and the doors will be held open. The fault is cleared when
the door contacts relay input(s) go off.
When the doors are fully open, and the car is not leveling, the DOLX output will energize. This will
change the connections of the car door and hall doors, so that the microprocessor can monitor the car
and hall doors independently.

5.9 Field Adjustable Features


Refer to the section on changing Settings and Features to see the features that are adjustable.
The controller is already set up for the specific job when it is shipped from Virginia Controls. It is
recommended that the "Reset Settings" sequence be performed, or the settings and features be
checked, when the controller is first powered up. This sequence is described in the section Controller
Diagnostics/Set-up Mode/Reset Settings, or in Controller Maintenance/Frequently Asked
Questions/How Do I Reset All Settings and Features Back to the Original Values.
The settings or features that most often need adjustment are the door times, and fire service return
floors.

VIRGINIA CONTROLS, INC. MVFAC-3000 User Manual, Rev. 2.11 Page 22


5.10 Zoned Duplex Operation
The Duplex System will keep one car at the Main Dispatch Landing, as the Lobby Car, and allow the other
car, or the Free Car, to stop at it's last call. The Lobby Car will answer calls in the Lobby Zone, and the
Free Car will answer all other calls. The Lobby Car may leave the lobby to assist the Free Car under
various load conditions as described below under Start Control. The "Lobby Zone" is an adjustable group
of landings but the factory preset value is normally the Lobby/Main landing and any landings below the
Lobby/Main landing. All other landings are in the "Upper Zone". If a car is "Next" in a zone, then it will
answer calls in that zone, otherwise it will answer calls in the other zone. If both cars are in service, a car
will always be homed to the Main Lobby level.

5.10.1 Common Circuits


Several circuits need to be energized when either car is on. These include the Hall Calls, Fire Service,
and some other circuits that may be required for a particular job (such as Emergency Power, Hospital
Service, etc.). These circuits get their power from either car by means of the VR (Voltage) relay. (See the
schematic.)
Install each car separately. The Hall Calls and Hall Fire signals may be wired to either car, then cross-
connected to the other car.

WARNING: Be careful not to mix the power supplies from one car with the other car.
Signals that are common to both controllers must be connected to a common supply,
as shown on the schematic.

5.10.2 Next Car


A "Next Car" is selected for the Lobby Zone and the Upper Zone. This car will be assigned hall calls in the
respective zone. The other car may answer calls in a zone where it is not "Next", but it will not normally
be sent to calls outside its zone. The "Next Car" assignments can be seen in the communication signals
(see below).

5.10.3 Car Start


The Car START feature controls when the car will respond to registered Hall Calls by controlling the
internal direction circuits. When the START circuit is energized the car will immediately begin to
respond to Hall Calls. There is a separate start circuit for the Lobby Zone and the Upper Zone. A car will
always respond to Car Calls immediately.
The START circuit is energized if ANY of the following conditions are true:
1. The car is Next in that zone.
2. The car is in the other zone, and is NOT next in that zone. (This means that both cars are in the other
zone, so the car that is not next in the other zone will be pulled into this zone.)
3. The call(s) in this zone have been registered for a preset time. (This allows the other car to help in
heavy traffic situations.)
4. The car is not in normal group operation.

VIRGINIA CONTROLS, INC. MVFAC-3000 User Manual, Rev. 2.11 Page 23


5. The other car is not in normal group operation.
6. The other car has a call behind it.
7. Emergency Power is activated, and this car is assigned to run.

5.10.4 Homing
If there are no cars at the Main Dispatch landing, the "Next" car in the Lobby Zone will home, or return,
to the Main Dispatch Landing. If there is no "Next Car" in the Lobby Zone, then the first available car will
home to the Lobby. If desired, the "Free" car can be set up to home to a specific (adjustable) landing in
the upper zone, or to home to the Main landing. (See the separate description on Feature Adjustments.)
A car will home if the following conditions have been met for 10 seconds:
1. The car is in group operation (not on Inspection, Independent Service, Fire Service, Load Weighing
etc.).
2. The Stop Switch is not thrown.
3. The car is not stuck.
4. The doors are closed.
5. The car is not at the Main Dispatch Landing.
6. The car is not running.
7. The other car is in group operation.
8. The other car is not next in the Lobby Zone.
9. The other car is not running down.
10. The other car is not homing.

5.10.5 Communication
Confirm that the termination jumpers have been installed to connect the termination resistors. These
are two small jumpers just below the Duplex Communication Connector block in the upper left corner of
the CPU. (Refer to the diagram of the CPU below)
Connect the communication cable from the Duplex Communication Connector block of one car to the
other car. The negative terminal on one car only should be connected to ground.
When both cars are in operation, the LED L4 should flash repeatedly. This indicates the two CPUs are
communicating properly.
If LED L4 is not flashing, check the communication cable, the termination jumpers, and the grounding. If
these look OK, but the CPUs are not communicating, do a factory reset on both cars. Memory location
0508 shows the number of successful communications (it should be constantly changing when both cars
are operating) and memory location 0509 shows the number of bad communication attempts (this
should be 0). (Note: These memory locations are subject to change.)

VIRGINIA CONTROLS, INC. MVFAC-3000 User Manual, Rev. 2.11 Page 24


5.11 ETSD Monitoring System Setup
The ETSD board by Virginia Controls is a hardware system for traction elevator controllers that provides
a level of redundancy for a specific set of control functions required by the A17.1 Safety Code for
Elevators and Escalators.
See Chapter 5 for additional details.

Figure 1 - ETSD Monitoring System Hardware

VIRGINIA CONTROLS, INC. MVFAC-3000 User Manual, Rev. 2.11 Page 25


5.11.1 Setup of the UCM (Unintended Car Movement) System
1. With power off, verify that UCM Select Jumper is set to “RB” for use with a Rope Brake device, or set
to “EB” for use with a Hoist machine Emergency Brake.

Figure 2 - UCM SELECT Jumper

NOTE: Follow the prints for setting the UCM Select Jumper. If a label was applied to
the board for setting this jumper, then follow it, but it should agree with the prints.

2. To begin construction, defeat the UCM System (and O-S & ETSD Systems) by placing a jumper from
controller TB-1 to Inputs SHTDFT and ETSDFT.
3. Power up the controller and verify that Input LED’s: “EII, ETSDFT & SHTDFT” are lit.

Figure 3 - ETSDFT & SHTDFT Input Indicators

VIRGINIA CONTROLS, INC. MVFAC-3000 User Manual, Rev. 2.11 Page 26


4. Other Input LED’s may be lit as well, but also verify that Relay Output LED’s: “EX1, EX2, ET1, ET2,
RBP1 & RBP2” are lit to permit movement of the elevator.

Figure 4 - EX1, EX2, ET1, ET2, RBP1 & RBP2 Output Indicators

5. Construction of the elevator may now proceed until it is decided that the O-S System should be
tuned.
6. Once the O-S System is tuned per the next “Setup of the O-S System” Section, the jumper from
controller TB-1 to Input SHTDFT will be removed.
7. The jumper from controller TB-1 to Input ETSDFT will be removed when the ETSD System is tuned
per the final “Setup of the ETSD System” Section. (Required if car speed is greater than 200FPM.)

VIRGINIA CONTROLS, INC. MVFAC-3000 User Manual, Rev. 2.11 Page 27


5.11.2 Setup of the O-S (Over Speed) System
The un-tuned O-S System was previously defeated in the “Setup of the UCM System”
Section by a jumper from controller TB-1 to Input SHTDFT.
During construction, once the elevator is running in a controlled and consistent
manner, the O-S System can be tuned while on Inspection, therefore start here!
NOTE: An un-tuned O-S System powers up with “O-S TRIP” & “O-S TUNED” LED’s off.
1. Apply the ETSD Speed Sensor Tape around a machined surface of a sheave (either machine driver or
deflector sheave) that is and will remain free of oil and grease. Note, ETSD Tape runs at rope speed.

Figure 5 - ETSD Tape


NOTE: The ETSD Tape is ⅝” wide by 10 feet long and should be trimmed to length and
can be shaved in width once installed.
2. Insure that the ETSD Tape will not come in contact with the brake pad surfaces of the main or
emergency brakes, nor lap over into a rope groove.
3. If not already assembled, mount the Speed Sensor in its steel, 90 ⁰ angle mounting bracket with
about half (or ≈1”) of the threaded barrel extending through the bracket, and with the controls &
LED’s of the sensor facing outward for viewing. Note the arrangement/order of the grommet &
washers.

Figure 6 - Speed Sensor & Mounting Bracket


VIRGINIA CONTROLS, INC. MVFAC-3000 User Manual, Rev. 2.11 Page 28
IMPORTANT NOTE: The rubber grommet & washers are provided to isolate the speed
sensor electrically from the mounting bracket & motor, otherwise damage may occur.

4. Use the mounting bracket to position the Speed Sensor approximately 5” (±1/4”) away from the
ETSD Tape at an angle that is nearly, but slightly off (approx. 10⁰) perpendicular to the tape.
5. With power off, route the 30ft Speed Sensor Cable through a metal conduit to the ETSD Board.
NOTE: Be sure the metal conduit is grounded at the motor end, and if possible, also
ground the other metal conduit containing the motor leads in the same manner.
6. Wire the cable per markings the 4-Pole “PHOTO” connector on the ETSD board. Shorten the cable at
the ETSD Board once its route through conduit is determined. Do not coil cable within the
controller.

Figure 7 – “PHOTO” Connector on ETSD Board


7. Connect the braided Drain wire of the Speed Sensor Cable to un-used ring lug at lower-right of ETSD
Board. Remove the #8 nut of the ETSD Board mounting stud to crimp and secure drain wire of cable.
8. Align and plug in the connector (whether straight or right-angle) of the Speed Sensor Cable to the
connector of the end of the Speed Sensor, then finger tighten this connection.

Figure 8 – Installed ETSD Tape & Sensor

VIRGINIA CONTROLS, INC. MVFAC-3000 User Manual, Rev. 2.11 Page 29


9. Power up controller, and verify that the Green “POWER” LED is lit on Speed Sensor.

Figure 9 - Sensor Green POWER LED Indicator

10. Verify that the Yellow “SENS.” LED of the Speed Sensor and the “PHOTO -1” LED on the ETSD Board
are lit only when the red light beam of the Speed Sensor is pointed at a white segment of the ETSD
Tape.

Figure 10 - Sensor Yellow SENS. LED Indicator

Figure 11 - PHOTO-1 Indicator


VIRGINIA CONTROLS, INC. MVFAC-3000 User Manual, Rev. 2.11 Page 30
11. Verify that the “PHOTO-0” LED on the ETSD Board lights only when the red light beam is pointed at a
black segment of the ETSD Tape.

Figure 12 - PHOTO-0 Indicator

12. Important Step: Perform the following checks to insure that “PHOTO-1” LED on the ETSD Board
lights only when the sensor is pointed at a white segment of the ETSD Tape, and to prevent “PHOTO-
0 & PHOTO-1” LED’s from oscillating while the sheave is still, and perhaps pointed at a black
segment:
• “L/D” (Light/Dark) Switch of Speed Sensor is set to “L” or Light position. (Check carefully!)
• “SENS.” Potentiometer of Speed Sensor (2-turn w/clutch) is set on turn - middle.
• Speed Sensor is about 5” (±1/4”) away from the ETSD Tape.
• Speed Sensor is aligned slightly off (approx. 10°) perpendicular from tape.

Figure 13 - Sensor L/D Switch


• Important: Increasing the angle of the sensor off perpendicular with the tape, or adjusting the
"SENS.” Potentiometer per the P+F Adjustment Instructions included with the Sensor, may be
required to eliminate these issues.
NOTE: The goal of these steps is a focused (<1mm Dia.) red light beam on the ETSD
Tape having maximum sensitivity to white segments while rejecting black segments.
NOTE: “PHOTO-1 & PHOTO-0” LED’s should never oscillate when the red light beam is
resting on a seam or edge between white & black segments of the ETSD Tape.
VIRGINIA CONTROLS, INC. MVFAC-3000 User Manual, Rev. 2.11 Page 31
13. Power down controller, and move the jumper from Input SHTDFT to Input OSC.
14. Power up controller, and verify that Input LED’s: “EII, OSC & ETSDFT” are lit.
15. Other Input LED’s may be lit as well, but also verify that Relay Output LED’s: “EX1, EX2, ET1, ET2,
RBP1 & RBP2” are lit to permit movement of the elevator.

Figure 14 - Output Indicators


16. Set the drive for an Inspection speed of 150FPM and run the car for 5 seconds.

NOTE: Car speed should be checked with hand tachometer, or repeat when available.
17. If elevator contract speed is 150FPM or lower, then set the drive (in previous step…) to 80%-90% of
contract speed.
18. When the elevator comes to a stop, remove jumper at Input OSC with power on. The “O-S TUNED”
LED will light indicating a valid calibration of O-S System.

Figure 15 - O-S TUNED Indicator


19. Power down the controller to complete the removal of Input OSC jumper from controller TB-1.

VIRGINIA CONTROLS, INC. MVFAC-3000 User Manual, Rev. 2.11 Page 32


20. Power up controller, and verify Input LED’s: “EII & ETSDFT” are lit, and that Relay Output LED’s: “EX1
& EX2” are also lit. Other I/O LED’s may be lit as well.
21. Return the drive to its former Inspection Speed setting (40-50FPM).
22. If contract speed is 150fpm or lower, limit the Inspection Speed setting on the drive to not more
than 50%-60% of contract speed – well below O-S Calibration.
23. The UCM & O-S Systems are now operational.
NOTE: The ETSD System alone remains defeated until final adjustments are made on
Normal operation.

24. Important: If the O-S System should fault intermittently, it is most likely caused by “noise” that is
picked up by the Speed Sensor Cable due to its proximity to the motor leads of the Drive, or by a
poorly aligned or adjusted Speed Sensor. See Step 12 (above) and Steps 25 & 26 (below).
25. Important: Car speed can be monitored on LED’s “S0-S7” by turning on DIP SW-4, “AUX”, only.
These LED’s show car speed as a binary count that should ramp up & down with Accel & Decel and
appear stable at constant speed, with dithering (or flashing…) on the lowest one or two bits only.
LED’s “SO-S7” represent an 8 Bit count (1, 2, 4, etc…) where each bit accounts for 5FPM (or, one ¼”
of tape travel sampled over 250mS). Example: LED’s “S1 + S2 + S3 + S4” = ( 2 + 4 + 8 + 16 ) x 5 =
150FPM.
Leave the SW-4, “AUX” in the ON/Up position.

Figure 16 - State LEDs and DIP Switches

26. Important: While running, if LED’s “S0-S7” flash off and on randomly, without a pattern: check that
the Speed Sensor Cable is ran separate and away from line & motor leads; check conduit grounding;

VIRGINIA CONTROLS, INC. MVFAC-3000 User Manual, Rev. 2.11 Page 33


and check the alignment and adjustment of the Speed Sensor per Step 12. Then, recalibrate O-S
System.

5.11.3 Setup of the ETSD (Emergency Terminal Stopping


Device) System

The un-tuned ETSD System was previously defeated in the “Setup of the O-S System”
Section by jumping from controller TB-1 to Input ETSDFT.
If the elevator contract speed is 200FPM or less, then the ETSD System is not tuned,
and the jumper from controller TB-1 to Input ETSDFT remains in place. Stop here!
If contract speed is greater than 200fpm, proceed with ETSD tuning.
The ETSD System can be tuned only after the O-S System has been tuned.
An un-tuned ETSD System powers up with “ETSD TRIP” & “ETSD TUNED” LED’s off.
NOTE: Minimum ETS Switch Cam lengths are 6ft for +200-500FPM to provide
approximately 0.5 Sec of dwell time. The ETS Switches may also be maintained to the
Final Limit Switch as most cam lengths are the height of the car.
Once the elevator has been fully adjusted for Normal operation (Contract Speed set
along with Accel/Decel & Jerk Rates), and the ETS Switches and Cam are installed,
then ETSD System can be tuned.

Table 1 - Recommended ETS Switch Placement (one N.C. switch per terminal & direction)
Car Speed
Switch Placement
(FPM)
225 2’-3”
250 2’-6”
300 3’-6”
350 4’-3”
400 5’-3”
450 6’-6”
500 7’-6”

1. Power down controller, and move the jumper from Input ETSDFT to Input ETSC.
2. Power up controller, and verify that Input LED’s: “EII, ETSC & AUTO” are lit.

VIRGINIA CONTROLS, INC. MVFAC-3000 User Manual, Rev. 2.11 Page 34


3. Other Input LED’s may be lit as well, but also verify that Relay Output LED’s: “EX1, EX2, ET1, ET2,
RBP1 & RBP2” are lit to permit movement of the elevator.

Figure 17 - Output Indicators

4. Set the drive for a High Speed setting of 90% of contract speed, and send the elevator on a multi-
floor run on Normal operation. Verify that the elevator obtains this speed.
5. When elevator comes to a stop, remove jumper at Input ETSC with power on. The “ETSD TUNED”
LED will light indicating a valid calibration of the ETSD System.

Figure 18 - ETSD TUNED Indicator

6. Return the drive to its former High (Contract) Speed setting.


7. Power down to complete the removal of Input ETSC jumper from controller TB-1.
8. Power up controller and verify Input LED “EII” is lit, and that Relay Output LED’s: “EX1 & EX2” are
also lit. Other Input & Output LED’s may be lit as well.
9. If on Normal Operation and the car is not on an ETS Switch, Relay Output LED’s: “ET1 & ET2” should
be lit. If lit, remove a wire from Input ETU or Input ETD of the ETSD Board, and verify that Relay
Output LED’s: “ET1 & ET2” turn off. Replace wire.

VIRGINIA CONTROLS, INC. MVFAC-3000 User Manual, Rev. 2.11 Page 35


10. The UCM, O-S & ETSD Systems are now operational. Run the elevator into the terminal landings.
If the ETSD System should fault intermittently, then move the ETS Switch(es) toward the terminal
landing(s) by 6” to 1’ (depending on car speed) to eliminate nuisance ETSD faults.
11. Important: If the ETSD System persists with nuisance faults, it is most likely caused by “noise” that is
picked up by the Speed Sensor Cable due to its proximity to the motor leads of the Drive; or by a
poorly aligned or adjusted Speed Sensor. See Step 12 of Section 4.11.2, and Steps 12 & 13 (below).
12. Important: Car speed can be monitored on LED’s “S0-S7” by turning on DIP SW-4, “AUX”, only.
These LED’s show car speed as a binary count that should ramp up & down with Accel & Decel and
appear stable at constant speed, with dithering (or flashing…) on the lowest one or two bits only.
LED’s “SO-S7” represent an 8 Bit count (1, 2, 4, etc…) where each bit accounts for 5FPM (or, one ¼”
of tape travel sampled over 250mS). Example: LED’s “S1 + S2 + S6” = ( 2 + 4 + 64 ) x 5 = 350FPM.
Leave the SW-4, “AUX”, in the ON/Up position.

Figure 19 - State LEDs and DIP Switches

13. Important: While running, if LED’s “S0-S7” flash off and on randomly without a pattern: check that
the Speed Sensor Cable is ran separate and away from line & motor leads; check conduit grounding;
check the alignment and adjustment of the Speed Sensor per Step 12 of Section 4.11.2.
Then, recalibrate both O-S & ETSD Systems.

VIRGINIA CONTROLS, INC. MVFAC-3000 User Manual, Rev. 2.11 Page 36


5.12 A-B Micro PLC Setup
Where speed checking is required, a separate Allen-Bradley Micro PLC may be provided. This is
connected to the encoder to monitor the speed of the car, and generate a fault if an overspeed condition
is detected.

5.12.1 SPECIAL ADJUSTMENTS with ETSD/UCM BOARD, HSC


This section shows the standard definitions of any Custom Times and Features used for ETSD/UCM
Board. Refer to the Installation and Adjustment Manual for all other adjustments and for instructions on
changing the values of the features shown below.

NAME and DESCRIPTION


HSC FAULT DELAY. (Value is in tenths of a second) This sets the delay before a High Speed Counter fault
is initiated. The car will shut down, and the cause of the fault will be logged.
HSC START DELAY. (Value is in tenths of a second) This sets the delay after the start of a run before the
speed is checked for movement, and for proper direction.
ETS FAULT DELAY. (Value is in tenths of a second) This sets the delay before an Emergency Terminal
Speed fault is initiated. The car will shut down, and the cause of the fault will be logged.
UCM FAULT DELAY. (Value is in tenths of a second) This sets the delay before an ETSD/UCM Monitoring
Fault is logged. It should be set long enough to prevent nuisance faults.
1FR HOLD DELAY. (Value is in tenths of a second) This sets the delay to hold the 1FR output when the
car is running full speed and slows down. It allows the car to pass the leveling zone of the previous floor,
so that it stops at the correct floor.
ENABLE ETSD/UCM BOARD. Enable this bit feature when the ETSD/UCM Board is used. It enables the
Rope Brake check and Redundancy Faults used with the ETSD/UCM Board.
DISABLE UCM BOARD REDUNDANCY FAULTS. Enable this bit feature to disable Redundancy Faults from
the UCM Board.
ENABLE HIGH SPEED COUNTER. Enable this bit feature when using an external PLC with a High Speed
Counter. This can be turned off temporarily during setup to disable HSC faults.
ENABLE EMERGENCY TERMINAL SLOWDOWNS (ETS). Enable this bit feature when using an ETS system
with the ETSD/UCM Board.
ENABLE ONE AND TWO FLOOR RUN SPEEDS. Enable this bit feature when a separate speed is provided
for One Floor Runs.
ENABLE LONG FLOOR FROM ? to ?. Enable one of these bit features when there is a long floor at the
specified floors. The car will then run full speed between those two floors.

VIRGINIA CONTROLS, INC. MVFAC-3000 User Manual, Rev. 2.11 Page 37


5.12.2 SPECIAL FAULTS for ETSD/UCM BOARD, HIGH SPEED
COUNTER
When an ETSD/UCM Board or a High Speed Counter Processor is used, additional checks are used that
check for proper operation. The message “REDUCM” on the main status screen indicates a problem with
the ETSD/UCM board. “HSC-ETS” indicates a speed related problem. Go to the Fault Log and check the
status line to determine the cause. Refer to the Fault Log to get the detailed fault information. See the
section for Fault Log later in this manual for a description of the Fault Status bits for these faults.

5.12.3 ADJUST MODE


Adjust Mode allows various parameters to be set using the 10 inputs on the top of the A-B Micro 830
PLC.
WARNING: The inputs to the Allen-Bradley Micro830 PLC are 115VAC. DO NOT MIX THE VOLTAGES. See
the prints and PLC documentation for details of the PLC wiring.
1. Make sure the car cannot not run.
2. Jump Input I-09 on. Leave the jumper on until step 5. Light 9 on the front of the PLC will come on. If
it does not, verify the input common is connected and that you are jumping to the correct terminal.
3. After I-09 has been on for at least 1 second, jump I-08 on.
4. Output 4 will go off, and output 5 will come on, indicating the Adjust Mode has been initiated.
5. Remove the jumper to I-09 then remove the jumper to I-08. Output 0 will come on.
6. Jump In0 to I-07 to select the value to be changed, see the table below. Leave the jumpers on until
step 9.
I-00 I-01 I-02 I-03 FUNCTION
ON OFF OFF OFF Car Speed, in FPM
OFF ON OFF OFF Speed to trip 10fpm Speed Indication
ON ON OFF OFF Speed to trip Doors Open Speed Indication
OFF OFF ON OFF Speed to trip Inspection Speed Indication
ON OFF ON OFF Speed to trip 90% of Contract Speed Indication
OFF ON ON OFF Speed to trip 95% of Contract Speed Indication
ON ON ON OFF Speed to trip 100% of Contract Speed Indication
OFF OFF OFF ON Speed to trip 110% of Contract Speed Indication
ON OFF OFF ON Delay Before Accepting New Speed in milliseconds
7. Jump Input I-09 on. The previous selection is stored. Output 0 will go off, and Output 1 will come on.
8. Remove the jumper to I-09.
9. Change the jumpers to I-00 to I-07 to select the lower 8 bits of the desired value to be entered,
according to the table shown below. Leave the jumpers on until step 12.
10. Jump Input I-08 on. The previous selection is stored. Output 1 will go off, and Output 2 will come on.
11. Remove the jumper to I-08.
12. Change the jumpers to I-00 to I-07 to select the upper 8 bits of the desired value to be entered,
according to the table shown below. Leave the jumpers on until step 14.
13. Jump Input I-09 on. The previous selection is stored. Output 2 will go off, and Output 3 will come on.
VIRGINIA CONTROLS, INC. MVFAC-3000 User Manual, Rev. 2.11 Page 38
14. Remove any jumpers to all inputs, I-00 to I-09.
15. Jump Input I-08 on. The value is stored for the selected register, and the Adjust Mode is completed.
Outputs 3 and 5 will go off. Output 4 will come on. Remove the jumper to Input I-08.
If an additional value needs to be changed, repeat the complete procedure again from step 1.
NOTE: If the process needs to be interrupted, cycle the power. Output 5 will go off, indicating the Adjust
Mode has been cancelled. Output 4 will come on, indicating the PLC is in normal mode.
To reset all values back to the factory default, jump I-01 while the PLC is NOT in Adjust Mode.

DETERMINING THE JUMPERS FOR ADJUST MODE STEPS 9 and 12.


The desired value must be broken down into a binary number, then the appropriate inputs turned on to
give that number. The following table shows the value for each jumper applied in steps 9 and 12.
INPUT VALUE in LOWER 8 bits, VALUE in UPPER 8 bits,
IF INPUT IS ON (Step 9) IF INPUT IS ON (Step 12)
I-00 1 256
I-01 2 512
I-02 4 1024
I-03 8 2048
I-04 16 4096
I-05 32 8192
I-06 64 16384
I-07 128 32768

For example, the (decimal) value 350 is ( 256 + 64 + 16 + 8 + 4 + 2 ). To set this value jump I-01, I-02, I-03,
I-04, I-06 in step 9 and IN00 in step 12.
The (decimal) value 25 is ( 16 + 8 + 1 ). To set this value jump I-00, I-03, I-04 in step 9 and nothing in step
12.

5.12.4 ALLEN-BRADLEY MICRO830 HSC SETUP.


During installation, on the Allen-Bradley PLC, jump input I-00 on.
Verify that Output 0 on the Allen-Bradley PLC comes on when the car runs up.
If it does not, check the encoder wiring, then swap wires A+ and B+, also swap A- and B-.
If faults are being generated in the main PLC, it may be necessary to either jump the Shutdown Defeat
Input on the main PLC, or turn off the HSC selection in the Adjustable Features of the main PLC.

5.12.5 CALIBRATE THE HIGH SPEED COUNTER.


1. Power should be ON.
2. Jump Input I-00. (If it was already on, then take it off and put it back on)
VIRGINIA CONTROLS, INC. MVFAC-3000 User Manual, Rev. 2.11 Page 39
3. Run the car UP at contract speed. Speed Code outputs O-01, O-02 and O-03 should all be on.
4. Output O-00 must come on when the car runs up.
5. When the car stops, remove the jumper to Input I-00.
6. Calibration is complete.
It can be repeated at any time by repeating the steps shown above.

5.12.6 TROUBLESHOOTING
1. Verify that Output 0 on the Allen-Bradley PLC comes on when the car runs up. If it does not, check
the encoder wiring, then swap wires A+ and B+, also swap A- and B-.
2. Verify that the A and B lights on the HSC Module flash when the car moves. This is most noticeable
when the car is going very slowly.
3. Jump input I-01 on the Allen-Bradley PLC to reset all speed set points back to the factory default
values.

5.12.7 ALLEN-BRADLEY PLC OUTPUTS and INPUTS


O-00 On when the car is running up I-00 Initiate HSC Calibration
O-01 Speed Code 1 I-01 Reset all settings to factory default
O-02 Speed Code 2 I-02-7 Used for Adjust Mode
O-03 Speed Code 3 I-08 Used for Adjust Mode
O-04 HSC is OK I-09 Initiate Adjust Mode
O-05 Adjust Mode

5.12.8 SPEED CODES


O-01 O-02 O-03 Speed
Off Off Off Less than 10fpm
On Off Off Between 10fpm and Doors Open Speed (30fpm)
On On Off Between Doors Open Speed and Inspection Speed (150fpm)
Off On Off Between Inspection Speed (150fpm) and 90% of Contract Speed
Off On On Between 90% and 95% of Contract Speed
On On On Between 95% and 105% of Contract Speed
On Off On Between 105% and 110% of Contract Speed
Off Off On Over 110% of Contract Speed

VIRGINIA CONTROLS, INC. MVFAC-3000 User Manual, Rev. 2.11 Page 40


6. Controller Hardware Description
The controller consists of the Microprocessor system, Power Supply section, and Relay Interface.
The Microprocessor system consists of the Central Processor Board (CPU), which has the microprocessor
central processing unit, the EPROM memory chip, and the appropriate hardware to communicate to the
LCD display, Keypad, and Input/Output boards.
The program is in EPROM (Electrically Programmable Read Only Memory). The floor position and fire
service functions are maintained in battery backed RAM memory. The floor position may need to be
reset when the controller is initially installed.
The Power Supply section includes the required transformers and fuses to power the Microprocessor
system and the Relay Interface.
The Relay Interface includes the required relays and contactors to interface the field signals and devices
to the microprocessor. This usually includes relays or contactors for signals required for each specific
job.

6.1 Transformers

“CCXF” is the Control Circuit Transformer. This will provide the controller with 115VAC. The primary
connections will vary depending on the Building Power. See the schematic for sizing and wiring
information.
“DOXF” is the Door Circuit Transformer(s). The size and quantity of these transformers will depend on
the type of doors used. See the schematic for sizing and wiring information.

VIRGINIA CONTROLS, INC. MVFAC-3000 User Manual, Rev. 2.11 Page 41


6.2 Fuses

The fuse type and rating is shown on the schematic.

NOTE: Only replace fuses with fuses of the same type and rating.

6.3 12VDC Power Supply


The 12VDC Power Supply supplies 12VDC for the micro-processor.
The Power Supply has onboard circuit protection. If the output is shorted, the output will be turned off.
If the Power Supply output is 0volts, remove the load from the Power Supply, then measure the output
again. If the output is now 12VDC, check the load to make sure it is not shorted.

VIRGINIA CONTROLS, INC. MVFAC-3000 User Manual, Rev. 2.11 Page 42


6.4 Safety Interface
The Safety Relay Interface may be provided as a printed circuit board, or as discrete surface mounted
relays, or a combination of both.
The Safety Relay Interface provides interface signals to the Drive, Brake, Door Operator, and Safety
String.
Refer to the schematic to see which type of interface is used.

6.4.1 Bypass Switches


The Bypass Switches bypass the Door Contacts, as required by the appropriate codes. They are only used
on Inspection, and will force the car onto Inspection operation.

6.4.2 Inspection Switches


The Inspection Switches allow the elevator to be run on Inspection, in accord with the appropriate
codes.

6.4.3 Phase Monitor


The unit provides protection for the pump motor by
continuously measuring the voltage of each of the
three phases using a microcomputer circuit designed
to sense under and over voltage, voltage unbalance,
phase loss and phase reversal.
A trip delay is provided to prevent nuisance tripping.
A restart delay is provided to prevent short cycling
after a momentary power outage.
Upon application of line voltage, the restart delay
begins. The output relay is de-energized during
restart delay and the LED flashes green.
Under normal conditions, the output energizes and
the LED glows green after the restart delay.
Under voltage, over voltage and voltage unbalance
must be sensed for a continuous trip delay period
before the output is de-energized. The output will
not de-energize if the fault is corrected during the trip delay. The LED flashes red during the trip delay,
then glows red when the output is de-energized.
The restart delay begins as soon as the output relay de-energizes. If the restart delay is completed when
the fault is corrected, the output relay will energize immediately.
The output relay will not energize if a fault or phase reversal is sensed as the three phase voltage is
applied. The LED alternately flashes green then red if a phase reversal is sensed.

VIRGINIA CONTROLS, INC. MVFAC-3000 User Manual, Rev. 2.11 Page 43


Reset is automatic upon correction of a fault.
The technical characteristics of the phase monitor can be determined from the part number as follows:

Example: TVM 460A 10 0.5S 3S


Restart Delay
Trip Delay
Voltage Unbalance %
Line Voltage
Series

6.4.4 Digiset Timer


This unit is a universal voltage solid-state timer that
will operate from 19 VAC up to 265 VAC and from
10 VDC up to 120 VDC. Any time period between
0.1 second and 102.3 seconds is available in 0.1
second increments and can be set with the dip
switch.
Application of input voltage to the timer starts the
time delay. At the end of the delay period, the load
is energized. To reset, remove the input voltage to
the timer.
To select a time period, simply add up the selected
switches in the “ON” position for the total time
delay in seconds.
This timer provides a delay in the Up Run circuit.

VIRGINIA CONTROLS, INC. MVFAC-3000 User Manual, Rev. 2.11 Page 44


6.5 Microprocessor

6.5.1 CPU

LCD Display

CPU Status
Reset Button LEDs
Termination
Jumpers

Group
Communication Keypad
Connector

I/O Board
Communication
Connector

Battery S2 Slide Sws

12VDC
Power EPROM
Supply Socket

VIRGINIA CONTROLS, INC. MVFAC-3000 User Manual, Rev. 2.11 Page 45


D1
LCD CONNECTOR LCD DISPLAY D2 LEDs
DISPLAY D3
CPU RESET BUTTON D4
D5
TERMINATION JUMPERS
(DUPLEX ONLY) + MOUNTING HOLES (4)
-
COMMUNICATION G CPU KEYPAD CONNECTOR
CONNECTOR
KEYPAD (DASHED)
INPUT/OUTPUT MOUNTED OVER CPU
BUS CONNECTOR

BATTERY S2 SLIDE SWS


CHIP
12VDC INCOMING + + EPROM EPROM SOCKET, LEAVE
POWER CONNECTOR -
D D EMPTY HOLES AT LEFT

The Central Processing Unit (CPU) board contains the hardware that controls the inputs and outputs
which control the elevator. This section describes the major components on the board, and the function
of the connectors and LEDs.

6.5.1.1 CPU Battery


The CPU battery maintains the Real Time Clock, and also the status of key parameters and functions in
the RAM memory. The battery life is approximately 5 years.

WARNING: Replace the battery with RENATA 3V Lithium battery, Part No. CR2032
Only. Use of another battery may present a risk of Fire or Explosion.
VIRGINIA CONTROLS, INC. MVFAC-3000 User Manual, Rev. 2.11 Page 46
WARNING: Orient the battery properly in the battery holder. The positive side of the
battery is marked on the battery, and faces towards the power connector and away
from the EPROM socket.

WARNING: Do not use a metal (or conducting) device to remove or install the battery.
To replace the battery, remove the old battery by gently pushing the top of the battery towards the
EPROM socket, until it is clear of the black housing, and then slide it out of the socket. Insert the new
battery by sliding the edge under the metal retaining finger, then aligning it in the black housing. Be
careful not to short out the battery. Dispose of the old battery properly – do NOT incinerate the battery.

6.5.1.2 LED Description


There are five LEDs located at the upper right edge of the CPU board.

D1D1
- Auto
- Auto

D2D2
- Fire
- Fire

D3D3
- Shutdown
- Shutdown

D4D4
– Communication
– Communication

D5D5
- Watchdog
- Watchdog

The function of these LEDs during normal monitoring is noted on the schematic. The normal description
for these LEDs is as follows:
D1 "Automatic Operation". This LED should be lit during normal operation. It will go out when the
car is on Inspection Service, Independent Service, Fire Service, Low Oil Shutdown, or any other
mode that will cause the car to ignore Hall Calls.
D2 "Fire Service". This LED should be off during normal operation. It will be lit if the car is on Fire
Service Phase 1 (Hall) or Phase 2 (Car).
D3 "Shutdown". This LED should be off during normal operation. It will be lit if the Up Run timer
indicated the car has been running up for a preset adjustable time without passing a floor. This
could be caused by a low oil level; a problem with the motor starter circuit(s); or a problem with
the up valve circuit(s). The car will stop running up, then return to the lowest landing and cycle
the doors. It will then be shut down, with only the Door Open Button and door re-opening
devices being operational. The fault can be reset by cycling the Main Line Disconnect Switch, or
by putting the car on "Inspection" then back to "Automatic".

NOTE: If a Reverse Phase Relay or Emergency Power circuitry is supplied, these will
also initiate a shutdown signal if the inputs are not energized.
D4 “Communication Error”. This LED should be off during normal operation on a Simplex. It will be
lit if the CPU has failed to communicate properly with an Input/Output board. This could be

VIRGINIA CONTROLS, INC. MVFAC-3000 User Manual, Rev. 2.11 Page 47


caused by a loose or faulty cable between the boards, improper addressing of the I/O board(s)
(see the section on I/O board addressing), or incorrect setting of the number of I/O boards in the
CPU (see the section on adjustable settings). Refer to the section on I/O Boards for a description
of the communication Status LED on the I/O Board.
On Duplex or Group systems, the LED also monitors the communication with the other CPU. It
will flash if the communication with the other car(s) is operating normally. If the LED stays off,
then the communication has failed (see the section under Duplexing, Communication). If the
LED stays on, then either the Group communication has failed, or the communication to the I/O
boards has failed, as described above. Check the LEDs on the I/O boards to determine if they are
communicating properly, then check the BADCOMM address as described in the Duplex
Communication section.
D5 "Watchdog". This LED will flash regularly (about once per second) if the CPU is operating
properly. NOTE: The LED will flash every 10 seconds if the car is not in the run mode. If the LED
stops flashing, reset the CPU by cycling the Main Line Disconnect Switch, or pressing the Reset
Button on the CPU.

NOTE: If the diagnostic mode is changed to monitor the Internal Memory, or the
Setup Mode is selected, then the operation of the LEDs will change, as described in the
appropriate sections.

VIRGINIA CONTROLS, INC. MVFAC-3000 User Manual, Rev. 2.11 Page 48


6.5.1.3 Reset Button
The Reset Button is located just below the LCD Display.

It is used to reset the CPU if a lock-up occurs (such as if LED D5 stops flashing when in the normal
operating mode).

WARNING: Pressing the Reset Button will reset the CPU, causing all outputs to be
turned off and the car to stop immediately.

NOTE: The Reset Button should not normally need to be used.


Pressing this Reset Button is NOT the same as doing a factory reset. The Reset Button restarts the CPU
just as if the power had been cycled; whereas a factory reset will reset the settings and features to the
factory default values.

6.5.1.4 CPU Connectors

6.5.1.4.1 Duplex Communication Connector


The Duplex Communication Connector is a terminal block
located on the left side of the CPU board.

A shielded twisted pair is used to connect the two CPU boards


together. The shield is connected to the CPU board mounting
screw (which is grounded) at ONE END OF THE CABLE ONLY. The
termination jumpers next to the connector are factory installed
on duplex systems.

VIRGINIA CONTROLS, INC. MVFAC-3000 User Manual, Rev. 2.11 Page 49


6.5.1.4.2 LCD Display Connector
The LCD Display Connector is located at the top left of the CPU board.

The LCD display is mounted directly on the connector. The LCD display can be removed for replacement.
If it is removed, then set switch 1 on the Slide Switch S2 to the OFF position before turning the power
back on. This will ensure the CPU does not try to write to the LCD screen while it is removed. It is
recommended that the LCD display AND the Keypad be removed together, since if the LCD display only
is removed, and the keypad is activated, the CPU will probably lock up. Make sure the power is turned
OFF before removing either the keypad or the LCD display.

6.5.1.4.3 Keypad Connector


The connector for the Keypad is located behind the keypad. The connector is an 8-pin connector. If the
keypad is removed, make sure the connector is lined up properly when replacing the keypad. Make sure
the power is OFF when removing or installing the keypad.

6.5.1.4.4 Incoming Power Connector


The Incoming Power Connector is a terminal block
located in the bottom left corner of the CPU board.
The incoming power is 12VDC from the power
supply located near the CPU.
If the CPU board is replaced, the incoming power
wires must be connected to the correct terminals.
The upper terminal is "+" and the lower terminal is
"-". The connector is shaped so that the mating
terminal plug cannot be inserted upside down.

6.5.1.4.5 Input/Output Bus Connector

VIRGINIA CONTROLS, INC. MVFAC-3000 User Manual, Rev. 2.11 Page 50


The Input/Output Bus Connector is on the left of
the CPU board.
An RJ45 style cable is used to connect to the first
I/O board.
The other I/O boards are connected to each other
using a daisy chain method, with the CPU
connecting to the I/O COMM IN of board #1, then
the I/O COMM OUT of board #1 connects to I/O
COMM IN of board #2, and so on for all I/O boards.

6.5.1.5 S2 Slide Switch


The S2 Slide Switch is used to set various operating modes or features in the CPU. It is located on the
lower right of the CPU board, just above the program chip.
Currently only the first and third switches are
used. If the other switches are assigned a
particular function, this will be indicated on the
paperwork for the particular job.

VIRGINIA CONTROLS, INC. MVFAC-3000 User Manual, Rev. 2.11 Page 51


6.5.1.5.1 Switch 1 on S2 Slide Switch
If switch 1 is ON, then the LCD Display will show the “Car Status” screen on power up.
If switch 1 is OFF, then the LCD Display will be blank on power up. To activate the display and show the
“Car Status” screen, press any key. This mode should be used if the LCD is to be removed for any reason.
It is recommended that if the LCD Display is removed that you also remove the keypad, since pressing a
key with the LCD removed could lock up the CPU as it attempts to write to the LCD Display.

6.5.1.5.2 Switch 3 on S2 Slide Switch


If switch 3 is ON, then the Redundancy Fault Defeat is enabled. This will prevent a fault from the
Redundancy checks, or a Door Zone Fault. This can be used during initial installation to allow the car to
be run without generating these faults. As a reminder to turn the defeat off after installation, the Fire
Audible Visible will be enabled.
If switch 3 is OFF, then the Redundancy Faults will function as normal.

VIRGINIA CONTROLS, INC. MVFAC-3000 User Manual, Rev. 2.11 Page 52


6.5.2 Input/Output Boards
Refer to the picture or diagram of the IO boards shown below to identify the key components.
Removable
Terminals
Commons

I/O numbers
Programming
Port

Input LEDs Output LEDs


with number with number
below LED below LED
I/O Comm Address
Connector (IN) Switches
Status LED
12VDC I/O
Incoming Communication
Power Connector (OUT)
Input LEDs Output LEDs
with number with number
above LED above LED

VIRGINIA CONTROLS, INC. MVFAC-3000 User Manual, Rev. 2.11 Page 53


TYPICAL I/O BOARD

C1234C5678 Commons
C1234C5678
Jumper Block 1-8 Terminals
Input LEDs 1-8 Output Relays 1-8
Programming
Connector 12345678 12345678 Output LEDs 1-8
I/O Communication Address Sw Block
Bus IN Connector
Status LED I/O Communication Bus
OUT Connector
12VDC Power 9 11 13 15 9 11 13 15
Connector
10 12 14 16 10 12 14 16 Output LEDs 9-16
Input LEDs 9-16
Jumper Block 9-16
Output Relays 9-16
Terminals 9 11 C 14 16 9 11 C 14 16
15 15
C 10 12 13 15 C 10 12 13 15
Commons

Input/Output boards are used to connect the CPU with the field devices. All inputs (unless otherwise
stated) are 115VAC, and outputs (unless otherwise stated) are dry relay contacts.
The boards are available as 16-Input and 16-Output boards, or 16-Input and no outputs.
All inputs and outputs have individual LED indicators.
Wiring is done to the removable terminal blocks at the top and bottom of the I/O boards.
Fuses are provided externally, not on the I/O boards.

6.5.2.1 Addressing
Each Input/Output board is given a unique address by means
of the Address Switch Block on the right of the board, next to
the I/O COMM OUT Connector. The first board connected to
the CPU is address 1, the next is address 2, and so on. The
numbering is consecutive, and no numbers are skipped. To
set the address, refer to the chart below. ON indicates the
switch is set to the right, OFF indicates the switch is set to
the left, as indicated on the switch itself.
Picture at right shows DIP Sw. 1 to the right, and all the
others to the left, which is the address for Board 1, as shown
in the table below.

VIRGINIA CONTROLS, INC. MVFAC-3000 User Manual, Rev. 2.11 Page 54


Board # Sw. 1 Sw. 2 Sw. 3 Sw. 4 Board # Sw. 1 Sw. 2 Sw. 3 Sw. 4
1 ON OFF OFF OFF 5 ON OFF ON OFF
2 OFF ON OFF OFF 6 OFF ON ON OFF
3 ON ON OFF OFF 7 ON ON ON OFF
4 OFF OFF ON OFF 8 OFF OFF OFF ON

NOTE: If a board is replaced, the board must be set up with the SAME ADDRESS as the
board it was replacing. The address of each I/O point is determined by the Board
Number (1 through 8), then the Point Number (1 through 16). The board number is
used in the “Show I/O” screen to indicate which board is being monitored.

6.5.2.2 Terminal Wiring


Wiring to Inputs 1-8 is at the TOP LEFT of the I/O board, wiring to the Outputs 1-8 is at the TOP RIGHT of
the I/O board. Wiring to Inputs 9-16 is at the BOTTOM LEFT of the I/O board, wiring to the Outputs 9-16
is at the BOTTOM RIGHT of the I/O board.
The terminal blocks are removable, so BEFORE power is applied, remove the terminal blocks and check
for grounds at the terminal blocks.
Note also the location of the COMMONS, as shown on the schematic. The far left terminal is the
common for the four I/O points to its immediate right, and the sixth terminal from the left is the
common for the four I/O points to its immediate right.

WARNING: Be very careful not to jump to a common when you intended to jump to
an input or output, as this could damage the controller or other equipment.

Typical I/O Board Terminal Block Layout

Com 0 1 2 3 Com 4 5 6 7

6.5.2.3 Input/Output LEDs


Each Input and Output point has its own LED indicator. These are located towards the center of the
board, and are on the low voltage/CPU side of the optical isolator in the I/O circuitry.

6.5.2.3.1 Input/Output Naming Conventions


Each Input or Output is mapped to a specific address in the CPU. The address of each Input/Output
point is based both on the address of the board and on the location of the point on the board.

VIRGINIA CONTROLS, INC. MVFAC-3000 User Manual, Rev. 2.11 Page 55


The address of each I/O point is determined by the Board Address (1 through 8) and the Point Number (1
through 16). This address is used in the Monitor I/O Menu to show the I/O status.
The Board Address is set by the Address Switch Block S1, as described above. The point number is 1 to 8
starting from the left, for the top group, and 9-16 starting from the left, for the bottom group. The point
numbers are silk-screened on the board adjacent to the actual LEDs for each point. The LEDs have a “D”
number silk-screened next to the LED. This is a component identifier, and does not correspond to their
address. The address number is the slightly larger number between the LED and its resistor. Each LED
point number corresponds to the point number by the terminal blocks.

6.5.2.4 Board Status LED


The Status LED located next to the I/O COMM IN connector shows the status of the board. It will flash
regularly, and the number of flashes indicates its mode of operation.

Flashes Mode of Operation

One Normal operation

Communication Failure. The board is not


communicating with the CPU. This could be
Two
because the CPU is in Setup Mode, or a cable
is defective or disconnected.

Three Bad Address. Check the Address Switches.

Bad Data. Check the cables. Noise is


Four
probably being induced in the wiring.

6.5.3 I/O Board Connectors


6.5.3.1 I/O Bus Communication Connectors
The connector on the left of the I/O board is for the I/O bus from
the CPU board.
It is connected in a daisy chain from the CPU to the I/O boards.
The I/O COMM OUT on the CPU is cabled to the I/O COMM IN of
the first I/O board. The I/O COMM OUT of that board connects
to the I/O COMM IN of the next board, and so on.
The addresses of the boards must correspond to their position in
the daisy chain.

VIRGINIA CONTROLS, INC. MVFAC-3000 User Manual, Rev. 2.11 Page 56


6.5.3.2 Programming Connector
This connector is used to program the microprocessor on the
I/O board. It is not used once the I/O board is programmed.

6.5.3.3 Power Connector


This connector supplies 12VDC to the I/O board.

VIRGINIA CONTROLS, INC. MVFAC-3000 User Manual, Rev. 2.11 Page 57


6.5.3.4 Jumper Blocks
Two sets of jumper blocks are provided in the
upper middle, and lower middle of the board. They
allow the inputs and outputs to be jumped
together.
The silk-screening by the jumpers indicates which
points are connected to which pins.
Putting a jumper block on two horizontally adjacent
pins is the same as putting a jumper from the
output point to the same numbered input point.
For example, a jumper placed on the pins labeled
“3” would jump input point 3 to output point 3.

WARNING: When an input and


output are jumped together,
always connect the field wiring to
the OUTPUT terminal. Do NOT
connect the field wiring to the
Input terminal, as this could
overload the wiring on the board.
Inputs and outputs are normally connected
together on the car and hall call buttons and lights.

NOTE: If a board is replaced, the


board must be set up with the
SAME JUMPERS as the board it
was replacing.

VIRGINIA CONTROLS, INC. MVFAC-3000 User Manual, Rev. 2.11 Page 58


6.6 ETSD Monitoring System
The ETSD board by Virginia Controls is a hardware system for
traction elevator controllers that provides a level of
redundancy for a specific set of control functions required by
the A17.1 Safety Code for Elevators and Escalators.
These functions are accomplished by three control sub-
systems that are combined into a single ETSD Board. The
three individual ETSD Board sub-systems are known as:
1. Unintended Car Movement (UCM) System
2. Over-Speed (O-S) System
3. Emergency Terminal Stopping Device (ETSD) System
The operational integrity of each of these three sub-systems
is verified by the elevator controller micro-processor.
The ETSD Monitoring System includes:
1. ETSD Printed Circuit Board
2. Speed (Photo) Sensor &
3. Sensor Mounting Bracket
4. Sensor Cable (30Ft/10m)
5. Striped ETSD Adhesive Tape

Figure 20 - ETSD Monitoring System

VIRGINIA CONTROLS, INC. MVFAC-3000 User Manual, Rev. 2.11 Page 59


6.6.1 Unintended Car Movement (UCM) System
6.6.1.1 Requirements for UCM System
The ASME A17.1 Safety Code for Elevators, under section Unintended Car Movement Protection,
requires a traction elevator controller be equipped to detect uncontrolled movement by the elevator
away from a landing for any reason while the elevator doors are open. Upon detection, the required
braking device is activated. It may act directly on the elevator ropes or on the drive sheave. This system
must meet the following requirements:
• It activates if the elevator leaves the door zone of a landing, and both car and hoistway doors are
open, whether on Normal operation or on Inspection.
• If the UCM System requires power for operation, then the loss of power results in the
application of the UCM braking device.
• When activated, the elevator shall not be restored to operation until the UCM system is
manually reset.

NOTE: Cycling power is not considered a valid reset.

• If activated, the UCM System may remove power from machine motor & brake.
• The braking device may be applied (not activated) to a stopped elevator, and may be applied
(not activated) when an Electrical Protective Device (EPD) is opened.
• The UCM System is classified by code as an Electrical Protective Device (EPD).

6.6.1.2 Description of UCM System


1. The UCM System mimics in hardware what the controller micro-processor performs in software
using a small number of control signals shared between them.
2. When operating, Relays RBP1 & RBP2 energize +1.0 second after power-up. Relays RBCX1 &
RBCX2 remain de-energized until integrity checking is initiated.
3. If the car should move out of the door zone with its gate and hall door open, the UCM system
will release Relays RBP1 & RBP2 causing a UCM System fault.
4. A UCM System fault may occur in one of two specific situations, one occurring while on Normal
operation and the other occurring while on Inspection.
a. When on Normal operation with the elevator in the Door Zone, if the Gate and Hall Door
Contacts have been open and remain open, and if the Door Zone Input is lost, then the
UCM System faults.
b. When on Inspection, if the Gate and Hall Door Contacts have been open and remain
open, and the Safe Input is high (“P” Contactor is released), and if the elevator speed
exceeds 2.5FPM for 1.0 second, then the UCM System faults.

VIRGINIA CONTROLS, INC. MVFAC-3000 User Manual, Rev. 2.11 Page 60


5. When faulted, the UCM System lights the “UCM TRIP” LED. A UCM System fault is latched
through a power loss until reset.

Figure 21 - UCM TRIP Indicator


6. The UCM System is reset when Input SHTDFT goes high with power on.

NOTE: Input SHTDFT defeats the UCM System if jumped at power-up, then left in
place. It will not reset a UCM System fault at power-up. Use only during construction.
7. The operational integrity of the UCM System is checked prior to leaving a landing when on
Normal operation and is performed differently for Rope Brake operation versus Emergency
Brake operation.
8. When equipped for Rope Brake operation, the controller is provided with Relays: RB, RBX & RBC,
from which UCM System Inputs RB & RBC synchronize the integrity checking of UCM System
Relays: RBP1, RBP2 & RBCX1, RBCX2.
a. To start, the processor energizes controller Relay RBC causing UCM System Input RBC to
go high, which prompts the UCM System to energize Relays RBCX1 & RBCX2 causing TB-
RCM, as monitored by the processor to go high.
b. Next, the processor releases controller Relays RB & RBX causing UCM System Input RB
to go low. This prompts the release of UCM System Relays RBP1 & RBP2 causing UCM
System TB-RM, as monitored by the processor to go low indicating proper operation of
these UCM System relays.

VIRGINIA CONTROLS, INC. MVFAC-3000 User Manual, Rev. 2.11 Page 61


c. This done, the processor re-energizes controller Relays RP & RPX causing UCM Input RB
to go high, prompting the UCM System to re-energize Relays RBP1 & RBP2.
d. Lastly, the processor releases controller Relay RBC causing UCM Input RBC to go low,
prompting the UCM System to release Relays RBCX1 & RBCX2 causing UCM System TB-
RCM, as monitored by the processor to go low indicating proper operation of these
UCM System relays.
9. When equipped for Emergency Brake operation, there are situations where the controller is
permitted to release the Emergency Brake due to lack of demand or due to the machine
manufacturer’s specifications for the Emergency Brake itself. In this case, the controller is not
provided with Relays RB, RBX & RBC, therefore integrity checking of the UCM System is initiated
by processor Output RBC.
a. To start, UCM System Input RBC, which is connected to processor Output RBC, goes high
when integrity checking is initiated, prompting the UCM System to energize Relays
RBCX1 & RBCX2 causing TB-RCM, as monitored by the processor, to go high.
b. After a brief timed interval, the UCM System releases Relays RBP1 & RBP2 causing TB-
RM, as monitored by the processor, to go low indicating proper operation of these UCM
System relays.
c. After another brief interval, the UCM System re-energizes Relays RBP1 & RBP2.
d. After a final brief interval, the UCM System releases Relays RBCX1 & RBCX2 causing TB-
RCM, as monitored by the processor to go low indicating proper operation of these
UCM System relays.
10. Any deviation from these integrity checking sequences would result in an UCM System
Redundancy fault.
11. If the micro-processor detects both its inputs at terminal blocks: RM & RCM of the ETSD Board
are low, then it logs a fault of the UCM System.

VIRGINIA CONTROLS, INC. MVFAC-3000 User Manual, Rev. 2.11 Page 62


6.6.2 Over-Speed System (O-S) System
6.6.2.1 Requirements for O-S System
The ASME A17.1 Safety Code for Elevators, under section Control and Operating Circuits, states that a
failure of a software system designed without a SIL rating in circuits that control car speed while Leveling
with doors open, or while operating on Inspection or Hoistway Access, shall not permit elevator speed to
exceed 150fpm. A system, known as the Over Speed or O-S System, satisfies the safety code by meeting
the following requirements:
• This system is not defined in the code as an Electrical Protective Device (EPD), but is described in
virtually identical terms.
• A hardware based system is then used to monitor and limit car speed.

6.6.2.2 Description of O-S System


1. The O-S System provides the electronic hardware and a speed (photo) sensor, which is aimed at
a striped adhesive tape affixed to the machine drive sheave, to monitor elevator speed without
the need to determine elevator direction.
2. This speed monitoring hardware is also used by the ETSD System (required above 200fpm),
which is calibrated at a higher percentage of contact speed.
3. The O-S System is calibrated at and operates with a 150fpm threshold.
4. When provided, the High Speed Counter of the controller processor, is retained as a backup to
the O-S System, but is calibrated at a lower speed, so it will act first.

NOTE: The High Speed Counter of the controller processor is calibrated at a 125FPM
threshold for Inspection and at a 50FPM threshold while Leveling with doors open.

5. When tuned and operating and if Input EII is high, the O-S System energizes Relays EX1 & EX2 at
+1.0seconds after power-up. The O-S System also energizes Relays ET1 & ET2 when the
controller is on Normal operation and out of Door Zone, or when on Normal operation and in
the Door Zone with doors closed.
6. Relays ET1 & ET2 are released when on Normal operation (Input Auto is high) and the elevator
has been sitting in the Door Zone, and Gate and Door Contacts have been open and remain
open with the Safe Input low (Drive is enabled) for 1.0 second. Relays ET1 & ET2 are de-
energized on Inspection and remain so.
7. During either of these two conditions, if 150FPM is exceeded, Relays EX1 & EX2 de-energize,
opening the safety string and causing the O-S System to fault.

VIRGINIA CONTROLS, INC. MVFAC-3000 User Manual, Rev. 2.11 Page 63


8. When faulted, the “O-S TRIP” LED lights and latches UCM System Relay XXA, Low Speed Monitor.

Figure 22 - O-S TRIP Indicator

NOTE: O-S System faults are latched through a loss of power.


9. An O-S System fault is reset via the “O-S RESET” Push Button or by re-tuning.

Figure 23 - O-S RESET Push Button

NOTE: If the O-S System is re-tuned, the ETSD System must be re-tuned also.
10. For troubleshooting, a tuned O-S System can be defeated by jumping Input OSC high with power
applied.

NOTE: Do not cycle power with Input OSC jumped or O-S calibration will be lost!
11. A tuned, but defeated O-S System maintains Relays EX1 & EX2 regardless of car speed. Relays
ET1 & ET2 function normally per the previous description.
VIRGINIA CONTROLS, INC. MVFAC-3000 User Manual, Rev. 2.11 Page 64
12. A tuned O-S System energizes its Relay XXA when car speed exceeds 150FPM. This output
serves as “Low Speed Monitor” or LSM Input for the controller micro-processor.
13. The operational integrity of the speed monitoring system is checked as the controller micro-
processor verifies its Input LSM (O-S System Relay XXA) energizes when car speed exceeds
150FPM and de-energizes when car speed drops below 50FPM.
14. The operational integrity of Relays ET1 & ET2 is checked as the controller micro-processor
verifies TB-ETM goes low (i.e.: Relays ET1 and ET2 drop) when on Inspection or on Normal
operation when Leveling with doors open.
15. When the controller micro-processor Input ETSD is energized, then the operational integrity of
the O-S System (Relays ET1, ET2 & Output XXA) is not checked.
16. If the controller micro-processor detects both its inputs at terminal blocks: EXM & ETM of the
ESTD Board are low, and its Input LSM is high, then it logs a fault of the O-S System.

VIRGINIA CONTROLS, INC. MVFAC-3000 User Manual, Rev. 2.11 Page 65


6.6.3 Emergency Terminal Slowdown Device (ETSD) System
6.6.3.1 Requirements for ETSD System
The ASME A17.1 Safety Code for Elevators, under section Emergency Terminal Stopping Device, requires
a traction elevator with static control and a contract speed over 200FPM to have a speed and position
monitoring system that stops the car when excessive speed is detected as the elevator approaches a
terminal landing. This system, known as the Emergency Terminal Stopping Device or ETSD System, has
the following code requirements:
• It is activated in response to a failure of both the normal stopping means and the normal
terminal stopping device to slowdown and stop the elevator at or near a terminal landing.
• The ETSD System must function independently of the normal terminal stopping device and the
normal speed control system.
• When activated, the ETSD System shall remove power from the driving machine motor and
brake without regard for where the elevator comes to a stop.
• The general intent of this system is to prevent the car or counterweight from running onto their
buffers at or above contract speed.
• The ETSD System is classified by code as an Electrical Protective Device (EPD).

6.6.3.2 Description of ETSD System:


1. The ETSD System requires a speed monitoring system with inputs for a set of hoistway switches
that signal when the elevator approaches a terminal landing.
2. The speed monitoring hardware is provided for and shared with the O-S System where it is
calibrated at the lower speed of 150FPM.
3. In the case of the ETSD System, the calibration speed is 90% of contract speed whenever
contract speed is greater than 200FPM.
4. The ETSD System will verify that the elevator has slowed down to 90% of its contract speed with
50% or half of its slowdown distance remaining per the placement of Up & Down ETS Switches
at terminal blocks: 31X & 32X.

VIRGINIA CONTROLS, INC. MVFAC-3000 User Manual, Rev. 2.11 Page 66


Table 2 - Recommended ETS Switch Placement (one N.C. switch per terminal & direction)
Car Speed
Switch Placement
(FPM)
225 2’-3”
250 2’-6”
300 3’-6”
350 4’-3”
400 5’-3”
450 6’-6”
500 7’-6”

5. Minimum ETS Switch Cam lengths are 6ft for +200-500FPM to provide approximately 0.5
seconds of dwell time. ETS Switches may also be maintained to the Final Limit Switch as most
cam lengths are the height of the car.
6. When tuned and operating and if Input EII is high, the ETSD System energizes Relays EX1 & EX2
at +1.0seconds after power-up. The ETSD System also energizes Relays ET1 & ET2 when the
elevator is on Normal operation (Input Auto is high) and Inputs ETU & ETD are high (off of the
ETS Switches in hoistway).
7. Relays EX1 & EX2 remain energized until car speed exceeds 90% of contract speed at which time
they are released causing the safety string to be subject to Relays ET1 & ET2. Relays EX1 & EX2
re-energize just below 90% of contract speed.
8. Relays ET1 & ET2 remain energized until the elevator rides onto one of the ETS Switches in the
hoistway causing either Input ETU or Input ETD to go low.
9. On a “typical” full speed run into a terminal landing, the elevator decelerates below 90% of
contract speed before it encounters an ETS Switch. This allows Relays EX1 & EX2 to re-energize
before Relays ET1 & ET2 release.
10. On an “over-speed” run into a terminal landing (+90% of contract speed with just 50% of
slowdown distance remaining), Relays EX1 & EX2 stay released while over 90% of car speed.
Then, as an ETU or ETD Switch is encountered, Relays ET1 & ET2 are released, opening the
safety string and causing an ETSD System fault.
11. When faulted, the “ESTD TRIP” LED lights.

VIRGINIA CONTROLS, INC. MVFAC-3000 User Manual, Rev. 2.11 Page 67


Figure 24 - ETSD TRIP Indicator

NOTE: ETSD System faults are latched through a power loss.


12. An ETSD System fault is reset via the “ETSD RESET” Push Button while on Automatic operation or
by re-tuning.

Figure 25 - ETSD RESET Push Button

NOTE: The ETSD System must be re-tuned, if the O-S System is re-tuned.
13. For troubleshooting, a tuned ETSD System can be defeated by jumping Input ETSDFT, or by
putting the controller on Inspection operation.
14. A defeated, but tuned ETSD System maintains Relays ET1 & ET2, regardless of Inputs ETU & ETD.
Relays EX1 & EX2 remain subject to car speed.
15. The operational integrity of the ETSD System is continuously checked by the controller micro-
processor per the following.

VIRGINIA CONTROLS, INC. MVFAC-3000 User Manual, Rev. 2.11 Page 68


16. The operational integrity of Relays EX1 and EX2 is checked as the controller micro-processor
verifies TB-EXM goes low (i.e. Relays EX1 & EX2 drop) when traveling at over 90% of contract
speed on Normal operation.
17. The operational integrity of Relays ET1 and ET2 is checked as the controller micro-processor
verifies that TB-ETM goes low (i.e. Relays ET1 and ET2 drop) when the elevator encounters an
ETS Switch in the hoistway (i.e. Input ETU or Input ETD goes low) while approaching a terminal
landing on Normal operation.
18. Likewise, the controller micro-processor verifies that TB-ETM is high (i.e. Relays ET1 & ET2
energized) when off both ETS Switches (Inputs ETU & ETD are high).
19. When provided, the High Speed Counter of the processor provides a redundant ETSD System
using the same ETS Switch Inputs, and using the motor mounted encoder to determine car
speed.
20. ETS Switches, at TB-31X & TB-32X, are compared by the controller micro-processor against
known car position. If these switches fail to open when the car slows down and stops at a
terminal landing, an ETSD Hardware Fault occurs.
21. When controller micro-processor Input ETSD is energized, then the operational integrity of
Relays EX1, EX2 & ET1, ET2 of the ETSD System is not being checked along with that of Inputs
ETU/TB-31X and ETD/TB-32X as well.
22. If the controller micro-processor detects both its inputs at terminal blocks: EXM & ETM of the
ETSD Board are low, and its Input LSM is low, then it logs a fault of the ETSD System.

6.6.4 ETSD Monitoring System Routine Maintenance


1. Check the ETSD Tape for dirt, oil or grease. If present, wipe gently with a clean soft cloth until
removed. Replace the tape if it becomes damaged.

Figure 26 - ETSD Tape

VIRGINIA CONTROLS, INC. MVFAC-3000 User Manual, Rev. 2.11 Page 69


2. Check the lens of the Speed Sensor for dust & dirt. If present, wipe gently with a clean soft cloth
until removed.

Figure 27 - Speed Sensor

3. Check the alignment and focus of the Speed Sensor light beam. It should appear in the center of
the ETSD tape as a bright red dot 1/16” in size. If otherwise, see the “Setup of the O-S System”
Section 4.11.2 for mounting, aligning and adjusting the Speed Sensor.

VIRGINIA CONTROLS, INC. MVFAC-3000 User Manual, Rev. 2.11 Page 70


4. Check the “+24V” & “+3.3V” LED’s on the ETSD Board. If not lit, check the “+24V” & “COM” and
“+3.3V” & “COM” Test Points on the ETSD Board.

Figure 28 - +24V and +3.3V Indicators& Test Points

5. Check for the green “POWER” LED on the Speed Sensor. If not lit, check “PHOTO” Connector
terminal blocks 1 & 3 for 24VDC.

Figure 29 - Sensor POWER LED Indicator

VIRGINIA CONTROLS, INC. MVFAC-3000 User Manual, Rev. 2.11 Page 71


6. Check that the yellow “SENS.” LED of the Speed Sensor and “PHOTO- 1” LED on ETSD Board
operate in unison, and both are lit on a “White” segment of the ETSD Tape. If otherwise, see
“Setup of the O-S System” Section 4.11.2 for Speed Sensor adjustment.

Figure 30 - Sensor SENS. LED Indicator

Figure 31 - PHOTO-1 Indicator

VIRGINIA CONTROLS, INC. MVFAC-3000 User Manual, Rev. 2.11 Page 72


6.6.5 ETSD Board Specifications
Input Power 24VDC @ ⅓ amp (external)
On-board Power 3.3VDC
I/O 16 – 120VAC Inputs / 10 – Relay Outputs
+24V (voltage present)
+3.3V (voltage present)
LED Indicators (Green) 16 – 120VAC Inputs (energized)
10 – Relay Outputs (energized)
ETSD TUNED (ETSD sub-system operational)
O-S TUNED (O-S sub-system operational)
PHOTO-1 (indicating white segment of ETSD tape)
LED Indicators PHOTO-0 (indicating black segment of ETSD tape)
(Yellow)
S0 – S7 (Monitors states of 3 control sub-systems, and
indicates car speed when “AUX” DIP Switch is selected.)
ETSD TRIP (ETSD Sub-System fault)
LED Indicators (Red) O-S TRIP (O-S Sub-System fault)
UCM TRIP (UCM Sub-System fault)
SYSTEM RESET (Returns the 3 sub-systems to initial state.)
Push Buttons ETSD RESET (Resets an ETSD System Fault.)
O-S RESET (Resets an Over-Speed Fault.)
O-S; ETS; UCM; AUX (One selection to be made at a time.)
DIP Switches
Selects among the sub-systems to be monitored, or car speed.

UCM SELECT (selects Rope Brake or Emergency Brake


Jumpers
operation)
Test Points +24V; +3.3V & COM
1/BN – Brown wire; +24VDC supply to Speed Sensor

2/WH – White wire; no function


Connectors
3/BU – Blue wire; common supply to Speed Sensor
PHOTO; 4-pole
4/BK – Black wire; output signal from Speed Sensor

Ring Lug – braided Drain wire from Speed Sensor Cable


Dimensions 10”H x 6”W on ⅝” stand-offs
Environment
Ambient Temp. 32° - 104°F (0° - 40°C)
Operating Temp. 32° - 122°F (0° - 50°C)
Storage 14° - 140°F (-10° - 60°C)
Humidity 5% - 95% non-condensing

VIRGINIA CONTROLS, INC. MVFAC-3000 User Manual, Rev. 2.11 Page 73


Figure 32 - ETSD Board

VIRGINIA CONTROLS, INC. MVFAC-3000 User Manual, Rev. 2.11 Page 74


6.6.6 Speed (Photo) Sensor & Cable Specifications

Figure 33 - Speed (Photo) Sensor & Cable

WARNING: The Speed Sensor is Class 1 Laser Product. Avoid eye contact with Red
light source.

Manufacturer Pepperl+Fuchs
VT18-8-400-M-LAS/40a/118/128 – P/N: 801135 Note: Class 1 Laser
Model: (Photo Sensor)
Product
(Shielded Cables)
V1-G-10M-PUR-ABG – P/N: 221508 (10 meter length) Or,
V1-W-10M-PUR-ABG – P/N: 219640 (10 meter length w/90° Connector)
⅝”W x 10’L (36” max. sheave diameter); ¼” alternating black & white
ETSD Speed Tape
stripes

Mounting (Bracket) Steel angle bracket (2 ¼-20 bolts) w/Rubber Grommets & 2 Fiber Washers
(Position) Position photo sensor slightly off perpendicular from tape by 5⁰ - 15⁰ to
inhibit reflection (an ON state) while on a “Black” segment of ETSD Tape.

Distance (Sensor to Tape) 5” (±1/4”) between Sensor face (Red) & Tape on Sheave

Output 5VDC @ 9mA (ON state) square wave

Frequency (Max.) 500Hz from Sensor Output


Speed: (Max.) 1250FPM (500Hz) w/1:1 Roping
(Operating) 1000FPM (400Hz; 20% safety margin)
Adjustment: (Rotary
L/D (Light / Dark) Default = “L” – Light Examine carefully!
Sw.)
SENS. (2-turn with clutch) Default = centered at on turn.
(Potentiometer)

Indicators: (Green) POWER (Flashes if sensor output is shorted.)


(Yellow) SENS. (Lights when beam is reflected by WHITE segment of tape.)

VIRGINIA CONTROLS, INC. MVFAC-3000 User Manual, Rev. 2.11 Page 75


NOTE: Be certain to retain all Pepperl+Fuchs product information for troubleshooting.

7. MH-3000 Screens and Diagnostics


7.1 Run Mode
When the controller is powered up, or the Reset Button is pushed, the microprocessor will be in the Run
Mode. In this mode the microprocessor will allow the Inputs and Outputs to operate properly, and the
elevator to run. (The only other mode is the Setup Mode, as described below. In the Setup Mode the
elevator is shutdown, and all outputs are turned off.)
Several diagnostic screens are available in the Run Mode, and each is accessed by scrolling through the
selections until the desired item is located, and Ent is pressed.
The display will show either the “Car Status” screen or a blank screen, depending on the setting of S2
switch 1 on the CPU. If S2 switch 1 is ON then the “Car Status” screen will be displayed, and if S2 switch
1 is OFF then the screen will be blank until a key is pressed. It will then show the “Car Status” screen.
Press Esc to return to the Run Mode menu screens.
Pressing Nxt or Prv will scroll through the available screens in the Run Mode. To select a display, press
Nxt or Prv to show the desired item, then press Ent to show the desired screen.

7.1.1 Run Mode Screens


The screens available in the Run Mode are:
1. Show I/O Status
2. Show Fault Log
3. Show Internal Memory
4. Show Car Status
5. Go to Set-Up Mode

VIRGINIA CONTROLS, INC. MVFAC-3000 User Manual, Rev. 2.11 Page 76


RUN MODE SCREENS

(BLANK SCREEN) From Setup Mode

To “Go to Setup Menu”, (see below)


Note: LCD will display
VA CONTROLS Press ENTER to AUTO PwrOk Car Status Screen or
(BANNER SCREEN) SHOW CAR STATUS 2 UP CLSD Blank Screen on start
up, depending on the
Press ENTER to 0400 00 00 00 00 setting of S2 switch 1.
SHOW INT MEMORY 0404 00 00 00 00

Press ENTER to 01 09:40 FLTCODE Note: Press “.” to show


SHOW FAULT LOG 2 0000 0000 0000 the current time.

Press ENTER to INPUTS 0000 0000


SHOW I/O STATUS Board1 0000 0000

Press ENTER to Warning: PROGRAM Virginia Controls


GO TO SETUP MENU & CAR WILL STOP! MAIN SETUP MENU

To “Show Car Status”,


(see above) To Setup Mode

= Press “Nxt”
The normal sequence is to press “Nxt”
= Press “Prv” to select the desired menu item.
= Press “Ent” Press “Ent” to use the menu item.
Press “Esc” when you are finished.
= Press “Esc”

7.1.1.1 Banner Screen


A "Banner” screen showing the program information is available. This is accessed by pressing Esc from
the Run Mode. A sample banner screen is shown here.

VaControls.DS03A
12345.1.040705..

The "Banner” screen shows "VaControls" on the top line, followed by a code showing the program
family. In the example above this is “DS03A”. The code on the bottom line shows the Virginia Controls
Job Number (in the example above this is “12345”), the program revision number (in the example above
this is “1”), and a date code for the program in the format MMDDYY (in the example above this is
“040705” for April 7th, 2005). The controller displays the "Car Status" screen when the "Set-up Mode" is
exited.

VIRGINIA CONTROLS, INC. MVFAC-3000 User Manual, Rev. 2.11 Page 77


7.1.2 Show I/O Status
The "Show I/O Status" display allows the screen to display the status of the Inputs or Outputs on one
board. This display is useful for checking the integrity of the I/O boards and the communications
between the CPU board and the I/O boards. The display should agree with the corresponding LEDs on
the I/O boards.
The board number corresponds to the address set by the Address Switches on each I/O board. The top
left shows whether inputs or outputs are being monitored, and the bottom left shows the board number
being displayed.

INPUTS 0011 0010


Board2 0100 0110

The right side shows the status of the inputs or outputs. The status will be a "1" if the signal is on, or a
"0" if the signal is off. The order of the bits corresponds to the order of the LEDs on the I/O board, that
is, the top left bit corresponds to Point 1, top right is point 8, bottom left is point 9 and bottom right is
point 16. In the example above, the Inputs on Board # 2 are being monitored, and points 3,4,7 (top line)
and points 10,14,15 (bottom line) are all on.
If an I/O Fault is showing on the Status Screen, and the data on the Show I/O Screen matches the I/O
boards, then the checksum in the communication is incorrect. This will cause the CPU to ignore the
data, and not pass it to the main program. To determine which board is causing the communication
failure, refer to the section on troubleshooting suggestions for I/O board faults.

7.1.2.1 Moving Around in I/O Status Screen


Press Nxt or Prv to scroll through the I/O.
Press Aux to toggle between Inputs and Outputs.
Press Esc to return to the Run Mode menu screens.
The keys 0 - 9 , . and Ent are not used in this mode.

7.1.3 Show Fault Log


The “Show Fault Log” screen allows the controller fault log to be viewed. This log shows the fault
number, the time stamp of the fault, the fault code, and critical data when the fault occurred, including
the floor position of the car and the status of certain key signals.
As shown in the description of the faults below, some of the faults logged are not faults, but events that
are useful to know in the maintenance and operation of the elevator.
The controller stores the last 63 faults in battery backed RAM memory.
When a new fault occurs, all the existing faults are moved down to the next fault location, and fault 63 is
erased. The most recent fault is stored in fault location 00, and the order of the faults in the fault log is
the order in which the faults were logged, with the most recent faults at the top of the fault log table.
If a new fault is logged while viewing the fault log, the screen is not changed, it will continue to show the
old fault. This allows the fault data to be viewed if several faults are logged rapidly. To refresh the
screen, and show the current fault in that fault location, press Ent.
VIRGINIA CONTROLS, INC. MVFAC-3000 User Manual, Rev. 2.11 Page 78
NOTE: All faults will be cleared when a Factory Reset is performed.

Non-shutdown faults can be prevented from being logged, if desired. See the list of
Adjustable Features on sheet “MH-3000 Settings”. One of the Bit Features will be labeled “Disable Non-
Shutdown Faults in the Fault Log”. Turn this feature on to disable non-shutdown faults. This may be
useful if you are trying to track down a specific fault, and you do not want the fault log to contain minor
faults. Refer to the section on Changing Features for instructions on settings the proper Bit Feature to
disable non-shutdown faults.

7.1.3.1 Typical Fault Screen


This is the “Fault Log” screen layout, showing a typical fault message:

Fault Time Stamp


Fault Number
Fault Code
Fault Number
01 09:40 Fault Code
Fault Log Status Signals FLTCODE
01 09:40
Fault Log Status Signals
01 09:40FLTCODE
Fault Log Status Signals FLTCODE Fault Log Status Signals
2 1100 0011
2 1100 00110010
2 1100 0011

7.1.3.2 Fault Number


“01” is the fault number, shown on the top left of the “Fault Log” screen. It is a hexadecimal number
from 00 to 3E (decimal 62), with 00 being the most recent fault. Press Nxt to scroll through the fault log,
showing the next older fault. Press Prv to show the next most recent fault. You can press 0 to jump to
the most recent fault (fault 00).

7.1.3.3 Fault Time Stamp


“09:40” is the time stamp for the fault, shown in the middle of the top line of the “Fault Log” screen. The
time is displayed in 24hour format. The time stamp is accurate to within 10 minutes, so if the fault time
is 09:40, as shown above, then the fault occurred between 9:40 and 9:49.

NOTE: Faults that happen within 10 minutes of each other may log the same time.
The fault # will indicate the order of occurrence.
If the real time clock is set correctly, then this will be the time of the fault.

NOTE: To set the clock, refer to the section on setting the time under MH-3000
Screens and Diagnostics/Set-Up Mode/Set the Time.

To verify that the real time clock is set, press . to display the current time and date as shown here.
Press Ent to return to the fault log.

CURRENT TIME
13:23 11/13/01
VIRGINIA CONTROLS, INC. MVFAC-3000 User Manual, Rev. 2.11 Page 79
7.1.3.4 Fault Code
“FLTCODE” is the code for the fault, shown on the top right of the “Fault Log” screen. It is an
alphanumeric designation up to 7 characters that indicates what the fault was. The following fault codes
are standard.

NOTE: If a code is shown that is not in this list, check the paperwork for your specific
job to determine the meaning of the code, and the cause of the fault.
Non-shutdown faults can be prevented from being logged, if desired. See the list of Adjustable Features
on sheet “MH-3000 Settings”. One of the Bit Features will be labeled “Disable Non-Shutdown Faults in
the Fault Log”. Turn this feature on to disable non-shutdown faults. This may be useful if you are trying
to track down a specific fault, and you do not want the fault log to contain minor faults.
Refer to the section on Changing Features for instructions on settings the proper Bit Feature to disable
non-shutdown faults. The following faults will be disabled: This will prevent faults TDOPEN, TDCLOSE,
TDOPN-R, TDCLO-R, CARSTUK, DRCONTS, OUT-DZ, COMMFLT, FIRE, MRSMOKE, SHUNT, FLOOD from
being logged.

VIRGINIA CONTROLS, INC. MVFAC-3000 User Manual, Rev. 2.11 Page 80


CODE DESCRIPTION
ROLLOVR This code is logged every 24 hours, to indicate the faults after this point are from the previous
day. The data displayed on the bottom line is not the car status. The month and date for the
following faults are shown on the left, and the number of days without faults is shown on the
lower right. For example, the screen below indicates that fault 23 is a rollover, so that fault
24 and older faults occurred on 11/13 and fault 22 and earlier faults occurred on 11/14.

23 00:00 ROLLOVR
11/13 0

Several consecutive rollover faults will be combined into one rollover fault, and the number
on the lower right will indicate how many additional rollovers were combined, indicating
there were no faults for that many additional days.

23 00:00 ROLLOVR
11/13 2

24 09:30 LOW OIL


3 0110 1001 0000

25 00:00 ROLLOVR
11/07 5

For example, if faults 23, 24 and 25 were as shown above, this indicates a rollover code 25
was combined with five more (on 11/08 to 11/12) so that no faults occurred between 11/08
and 11/12, and fault 24 occurred on 11/13, since that is the date of the next earliest rollover.

NOTE: If the power is off when a rollover would have occurred (at
midnight) then no rollover code will be logged. If power is left on, then the
date of any fault is the date shown on the most recent (lower fault
number) rollover code.
RUN Tmr Running Shutdown Timer. The car ran for the time specified by the "Shutdown Time" setting
without passing a floor. The car will stop and shut down immediately. The doors may be
opened if the car is in the Door Zone. Check that the setting of the shutdown timer is long
enough for the car to run between floors. The normal shutdown timer setting is 25 seconds.
NOTE: If 2010 ANSI Code is enabled, then shutdown faults must be reset by momentarily
turning on the CPU DIP Switch #4, or by momentarily jumping the Fault Reset Input.
TDOPEN Door Open Fault. The Door Open Limit Switch failed to open after the doors had been
opening for the time specified by the "Door Fault" setting. The probable causes are: (1) The
Door Open Limit failure. (2) door operator failure. (3) door control circuitry failure. This fault
can be disabled on Manual Door systems.
TDCLOSE Door Close Fault. The doors failed to close properly when they were parking, or when the car
was ready to run for the next call. This fault will not be caused by keeping the doors open
VIRGINIA CONTROLS, INC. MVFAC-3000 User Manual, Rev. 2.11 Page 81
CODE DESCRIPTION
through the normal means (Door Open Button, Safety Edge, Infra-red Unit, etc.), but only if
the doors should be closing but were not able to close. The probable causes are: (1) Door
Close Limit failure. (2) Door Contacts failure. (3) door operator failure. (4) door control circuit
failure.
TDOPN-R Rear Door Open Fault. This is the same as fault TDOPEN, except it is for the rear door. This
fault is only used on elevators with selective open doors (with a front and rear door at the
same landing). This fault can be disabled on Manual Door systems.
TDCLO-R Rear Door Close Fault. This is the same as fault TDCLOSE, except it is for the rear door. This
fault is only used on elevators with selective open doors (with a front and rear door at the
same landing).
CARSTUK Car Stuck Fault. The car was held at a floor for the time set by the "Car Stuck Time" setting,
without running. This may be caused by a stuck button, or just by a passenger holding the
car.
EmPower Emergency Power. The elevator went on Emergency Power. Normal operation (Automatic
Return) is for the car to return to the Main Ldg, then shut down until the Emergency Power
Run Input is turned on. The controller can be set up to provide Manual Return, so that the
Emergency Power Run Input must be on to allow the car to return. The car will not return
automatically if it is on Inspection, Fire Service, Independent Service, or is prevented from
running for some other reason.
DRCONTS Door Contact Fault. The Door Contact Input turned off while the car was running. This fault
could be caused by the car tipping a door contact, or another of the devices in the safety
string. It could also be caused by a failure of the "DC" Door Contact relay.
OUT-DZ Door Zone Fault. The car stopped between floors. This is normal when the car is being taken
off Inspection Service. This fault will usually be seen with fault 08, since the car will usually
stop outside the door zone if the safety string is broken.
COMMFLT Communication Failure on Duplex. This will occur when the power on the other car is turned
off, or the other car fails to communicate properly for 5 seconds. Check the communication
cable, and the termination jumpers, which are located by the communication cable terminal
strip.
DRCHECK Door Check Fault. The Car or Hall Door Contacts Input was on (indicating the doors are
closed) while the Door Close Limit was on (indicating the doors are open). This check is
performed when the doors are fully open (Door Open Limit is off) and the car is not on a
Leveling Switch. The car will be held with the doors open until the Door Contacts input goes
off. The Car Door and Hall Door Contacts are both checked independently. If this fault is not
caused by a jumper on the Door Contacts, then check the Car and Hall Door Contacts very
carefully, and check the wiring to the Door Contact Inputs and Door Close Limit Input.
LEV SWS Leveling Switch Fault. Both Leveling Switch Inputs are on. This will shut the car down. Check
the Leveling Switches to make sure one of them has not stuck. The switches must be adjusted
so that only one leveling switch is energized at a time. Then check the wiring for shorts.
Cycle the power, or put the car on Inspection to clear the fault. In some short floor situations,
there may be an overlap of the leveling switches between the floors. In this case special

VIRGINIA CONTROLS, INC. MVFAC-3000 User Manual, Rev. 2.11 Page 82


CODE DESCRIPTION
programming will allow an overlap without causing a fault.
FIRE Fire Service Phase 1 or Phase 2 was initiated. This does not indicate a fault in the controller
operation.

NOTE: If Fire Service is not provided, or it is desired to bypass Fire Service


during initial installation, then jump the Hall Fire Switch Bypass Position
Input.
MRSMOKE The Machine Room or Shaftway Fire Sensors were initiated. This signal is required by the
1998 ANSI code, and will start the Fire Light flashing. It must be reset by turning the Hall Fire
Switch to “Bypass”.
SHUNT The Shunt Trip Input was initiated. The car will stop at the next floor, and open its doors. An
output will then come on that can be used to initiate the Shunt Trip Breaker, and turn power
off to the controller.
DZFAULT The Door Zone Switch was energized when it should not have been, such as when the car was
running between floors. The car will shut down at the next stop.
RED1ROP Redundancy Fault in the ESB Emergency Stop Sw Bypass circuit or the Rope Brake Monitoring
circuit. The input that monitors the Emergency Stop Switch Bypass function indicated the
Emergency Stop Switch was bypassed when it should not have been, OR the Rope Brake
monitoring inputs (RB6, RBC6) were on when the corresponding Rope Brake outputs (RB,
RBX, RBC) were off. Check the ESB relay, or ESB monitoring input, and its associated wiring.
Check the Rope Brake relays and circuits. Cycle the power to reset the fault.
NOTE: If 2010 ANSI Code is enabled, and the setting to require manual resets on Redundancy
Fault is enabled, then shutdown faults must be reset by momentarily turning on the CPU DIP
Switch #4, or by momentarily jumping the Fault Reset Input.
RED2RUN Redundancy Fault in the running or leveling circuits. The Door Contact Bypass circuit
monitoring point (LV) was energized when it should not have been, OR one of the run inputs
(UD1, UD2) was still on after the car stopped. Check the external circuits for stuck relays (UL,
DL, DZ, LV1, LV2, U1, U2, D1, D2) or a stuck input. Cycle the power to reset the fault.
NOTE: If 2010 ANSI Code is enabled, and the setting to require manual resets on Redundancy
Fault is enabled, then shutdown faults must be reset by momentarily turning on the CPU DIP
Switch #4, or by momentarily jumping the Fault Reset Input.
FSRELAY FS Relay Fault. The car attempted to run floor to floor 20 times, but did not make a floor
change. This is normally caused by the FS relay failing to cut out the leveling switches, so that
the car cannot leave the floor. When this fault is detected, the fault will be logged, and the
car will shut down.
RED3SAF Redundancy Fault in the Safety Circuit. The condition of the Door Fault Monitor input (DF6)
was not correct, OR the Car Gate Input (4X) or Door Contacts Input (5X) was not correct, OR
the Stop Sw input (3X) was not correct. This may be caused by temporary jumpers added
during initial installation, or a short in the Safety Circuit. Cycle the power to reset the fault.
NOTE: If 2010 ANSI Code is enabled, and the setting to require manual resets on Redundancy

VIRGINIA CONTROLS, INC. MVFAC-3000 User Manual, Rev. 2.11 Page 83


CODE DESCRIPTION
Fault is enabled, then shutdown faults must be reset by momentarily turning on the CPU DIP
Switch #4, or by momentarily jumping the Fault Reset Input.
RED4INS Redundancy Fault in the Inspection Door Bypass circuits. One of the inputs that monitors the
circuits that bypass the Door Contacts on Inspection or Access operation was closed when the
car was not on Inspection or Access, or terminal 3 or 4 was not hot. Check the Door Contact
circuit for jumpers or shorts. Cycle the power to reset the fault.
NOTE: If 2010 ANSI Code is enabled, and the setting to require manual resets on Redundancy
Fault is enabled, then shutdown faults must be reset by momentarily turning on the CPU DIP
Switch #4, or by momentarily jumping the Fault Reset Input.
SafeFlt The Safe Input failed to operate properly. The Safe Input should be ON when the car is
stopped, and turn OFF when the car starts to run. If the Safe Input does not change state
properly, then this fault will be logged.
BrakeSw The Brake Micro Switch did not operate properly. The Brake Micro Switch Input should go off
when the car starts to run.
Drv.Run The Drive Run Input did not operate properly. The Drive Run input should be on when the
Drive is running, and go off when the car stops.
Drv.Rdy The Drive Ready to Run Signal went off. The controller will attempt to reset the drive. Check
the Drive for any fault indications.
OverSpd An Over Speed was detected. If the Over Speed Input goes high when the car is running with
the doors open, the car will shut down. The Over Speed Input should be set to turn on when
the car speed exceeds 150fpm. It may be adjusted for a lower speed if desired, to provide
additional protection.
ROPE-DZ The Rope Brake set because the car moved out of the Door Zone with the Doors open and
without a run signal. To reset this fault, momentarily turn on the Shutdown Defeat input. To
test this feature, with the car floor level and the doors open, unplug the DZ relay to simulate
the car moving out of the Door Zone.
ROPE-BS The Rope Brake set because the car stopped and the Brake Micro Sw did not drop. To reset
this fault, momentarily turn on the Shutdown Defeat input. To test this feature, with the car
stopped, disconnect the Brake Micro Sw input (29).
ROPE-CK The Rope Brake relay monitor detected a fault in the Rope Brake pilot relays. When the car is
ready to start, the Rope Brake relays are cycled to confirm they are operating correctly. If
this test is not passed, this fault is generated, and the car is shut down.
ROPEBRK Rope Brake Fault. This is caused by either the Rope Brake relay monitor detected a fault in
the Rope Brake pilot relays. When the car is ready to start, the Rope Brake relays are cycled
to confirm they are operating correctly. If this test is not passed, this fault is generated, and
the car is shut down. The fault can also be generated if the High Speed Counter in the Allen-
Bradley Micro830 PLC detects that the car is running when it should be stopped. This will
cause the Rope Brake to drop.
RED-UCM Redundancy Fault detected in the ETSD/UCM Board circuits. Check the Status data and the
table shown later in this section to determine the specific fault and its cause.

VIRGINIA CONTROLS, INC. MVFAC-3000 User Manual, Rev. 2.11 Page 84


CODE DESCRIPTION
HSC-ETS High Speed Counter or Emergency Terminal Speed Fault. The High Speed Counter Fault is
generated if the car exceeds 110% of contract speed, 150fpm on Inspection, 150fpm with the
doors open, speed (or tach) loss or running the wrong direction. The Emergency Terminal
Speed Fault is generated if the car exceeds the set speed after hitting the ETS Switched at the
terminal Landings; or if the ETS Sw does not open as the car stops at the terminal landing.
Check the Status data and the table shown later in this section to determine the specific fault
and its cause.
FAULT1E This is a custom fault reserved for future use. If it used on a specific job, it will be described
on the “MH3000 Settings” sheet in the schematic.
FAULT1F This is a custom fault reserved for future use. If it used on a specific job, it will be described
on the “MH3000 Settings” sheet in the schematic.
IOFLT?? IO Board Fault. The I/O boards did not communicate properly with the CPU. The two
numbers after “IOFLT” indicate which boards failed. The code consists of 80Hex ANDED with
the bit pattern for the board(s) that failed to communicate. That is “81” indicates the first
board failed; “83” = the 1st and 2nd boards; “8A” = 2nd and 4th boards; etc. Check the
Address Switches for all boards. Check the setting in the CPU for the number of IO Boards.
Check the cables between boards.

NOTE: If the boards NEVER communicate, a fault will not be logged, since
the fault is ignored during power up. The fault is only logged if the boards
were communicating properly and then stopped.
(OTHER) Other Fault Codes may occasionally be provided on specific jobs. If this is the case, then refer
to the additional documentation for that job to see what the codes and descriptions are for
those faults.

I/O BOARD FAULT TABLE


Right
x0 x1 x2 x3 x4 x5 x6 x7
Number
Board1 OK Fault OK Fault OK Fault OK Fault
Board2 OK OK Fault Fault OK OK Fault Fault
Board3 OK OK OK OK Fault Fault Fault Fault
Board4 OK OK OK OK OK OK OK OK
Right
x8 x9 xA xB xC xD xE xF
Number
Board1 OK Fault OK Fault OK Fault OK Fault
Board2 OK OK Fault Fault OK OK Fault Fault
Board3 OK OK OK OK Fault Fault Fault Fault
Board4 Fault Fault Fault Fault Fault Fault Fault Fault
Left Number
0x 1x 2x 3x 4x 5x 6x 7x
Board5 OK Fault OK Fault OK Fault OK Fault
Board6 OK OK Fault Fault OK OK Fault Fault

VIRGINIA CONTROLS, INC. MVFAC-3000 User Manual, Rev. 2.11 Page 85


Board7 OK OK OK OK Fault Fault Fault Fault
Left Number
8x 9x Ax Bx Cx Dx Ex Fx
Board5 OK Fault OK Fault OK Fault OK Fault
Board6 OK OK Fault Fault OK OK Fault Fault
Board7 OK OK OK OK Fault Fault Fault Fault

7.1.3.5 Fault Log Status Signals


The bottom row of the “Fault Log” screen shows the car position and the status of key signals that help
determine what the car was doing when the fault occurred. The car position is a number between 1 and
9, and every other value is either 1 (the signal was on) or 0 (the signal was off).
To match the description with the location of each signal, the values in the screen below have been
replaced with letters, but in the actual log they would be 1’s and 0’s, as shown in the sample screen at
the top of this section. Match the letter shown in the sample screen below with the table below, to
determine the description of that signal.

NOTE: The Fault Status Signals are the same for all faults EXCEPT for the Redundancy
Faults RED-RUN, RED-SAF, and RED-INS. Refer to the tables below for the description
of the signals for those faults.

01 09:40 FLTCODE
P ABCD EFGH IJKL

Refer to the correct table below, depending on the fault.

SIGNAL DESCRIPTION for STANDARD FAULTS


P The car floor position when the fault occurred. The number will be between 1 and 9, with 1
indicating the bottom floor, 2 the second floor, etc. If the value is 9, then the car did not
have a floor position.
A The last direction the car ran. 1 = Up, 0 = Down.
B The last direction selected (as shown by the direction indicators). 1 = Up, 0 = Down.
C The car was running. 1 = Yes, 0 = No.
D The car was running fast speed. 1 = Yes, 0 = No.
E The car was running between floors (not re-leveling). 1 = Yes, 0 = No.
F The Door Contacts Input was On. 1 = Yes, 0 = No.
G The Door Close Limit Input was On. (With selective doors, this indicates either Door Close
Limit was On, that is, one or both of the doors was open). 1 = Yes (door open), 0 = No
(door closed).
H The Door Open Limit Input was On. (With selective doors, this indicates both Door Open
Limits were On, that is, neither door was full open). 1 = Yes (door not fully open), 0 = No

VIRGINIA CONTROLS, INC. MVFAC-3000 User Manual, Rev. 2.11 Page 86


(fully open).
I Up Level Input was On. 1 = Yes, 0 = No.
J Down Level Input was On. 1 = Yes, 0 = No.
K Car was in the Door Zone. 1 = Yes, 0 = No.
L “LV” Input (monitors the contacts in parallel with the Door Contacts, in the Safety String)
was On. 1 = Yes, 0 = No.

SIGNAL DESCRIPTION for RED1ROP FAULT


P The car floor position when the fault occurred. The number will be between 1 and 9, with 1
indicating the bottom floor, 2 the second floor, etc. If the value is 9, then the car did not
have a floor position.
NOTE The status bits should all be off for normal operation. The bit that is ON indicates the fault
condition that caused this fault.
A Output “ROPEX” and Output “ROPE” were Off. Input “ROPE” was On.
B Output “ROPEC” and Output “ROPE” were Off. Input “ROPE” was On.
C Output “ROPEC” was Off. Input “ROPEC” was On.
D Output “ESB” was Off and Input “SB” was On.
E–L Not Used

SIGNAL DESCRIPTION for RED2RUN FAULT


P The car floor position when the fault occurred. The number will be between 1 and 9, with 1
indicating the bottom floor, 2 the second floor, etc. If the value is 9, then the car did not
have a floor position.
NOTE The status bits should all be off for normal operation. The bit that is ON indicates the fault
condition that caused this fault.
A Up and Down Level Inputs were OFF but LV Input was ON.
B Up and Down Level Inputs and LV Input were all ON.
C Door Zone Input was OFF and LV Input was ON.
D Input “3” (Pit Sw) was OFF and LV Input was ON.
E Input “3” (Pit Sw) was OFF and Input “UD1” was ON.
F The car had stopped running and Input “UD1” was ON.
G Input “3” (Pit Sw) was OFF and Input “UD2” was ON.

VIRGINIA CONTROLS, INC. MVFAC-3000 User Manual, Rev. 2.11 Page 87


H The car had stopped running and Input “UD2” was ON.
I Special Redundancy feature was ON.
J–L Not Used

SIGNAL DESCRIPTION for RED3SAF FAULT


P The car floor position when the fault occurred. The number will be between 1 and 9, with 1
indicating the bottom floor, 2 the second floor, etc. If the value is 9, then the car did not
have a floor position.
NOTE The status bits should all be off for normal operation. The bit that is ON indicates the fault
condition that caused this fault.
A Input “DFM” (Door Check Monitor) was OFF. Input “4” and Output “DF” were ON.
B Input “DFM” (Door Check Monitor) was ON. Output “DF” was OFF.
C Input “DFM” (Door Check Monitor) was ON. Input “5” was OFF.
D Input “3” (Pit Sw) was OFF. The Door Contacts Input was On.
E Input “4” was OFF. The Door Contacts Input was On.
F Input “3” (Pit Sw) was OFF. The Car Gate Contacts Input was On.
G Input “4” was OFF. The Car Gate Contacts Input was On.
H Input “3” (Pit Sw) was OFF. Input “3X” (Stop Sw) was On.
I–L Not Used

SIGNAL DESCRIPTION for RED4INS FAULT


P The car floor position when the fault occurred. The number will be between 1 and 9, with 1
indicating the bottom floor, 2 the second floor, etc. If the value is 9, then the car did not
have a floor position.
NOTE The status bits should all be off for normal operation. The bit that is ON indicates the fault
condition that caused this fault.
A Input “3” (Pit Sw) or Input “4” was OFF, and Input “IN1” was On.
B Input “23” (Inspection Sw) was ON, and Input “IN1” was On.
C Input “3” (Pit Sw) or Input “4” was OFF, and Input “IN2” was On.
D Input “23” (Inspection Sw) was ON, and Input “IN2” was On.
E Input “3” (Pit Sw) or Input “4” was OFF, and Input “IA1” was On.
F Input “23” (Inspection Sw) was ON, and Input “IA1” was On.

VIRGINIA CONTROLS, INC. MVFAC-3000 User Manual, Rev. 2.11 Page 88


G Input “3” (Pit Sw) or Input “4” was OFF, and Input “IA2” was On.
H Input “23” (Inspection Sw) was ON, and Input “IA2” was On.
I Input “3” (Pit Sw) or Input “4” was OFF, and Input “IA3” was On.
J Input “23” (Inspection Sw) was ON, and Input “IA3” was On.
K–L Not Used

SIGNAL DESCRIPTION for RED-UCM FAULT (Used with ETSD/UCM Board)


P The car floor position when the fault occurred.
A I_LSM Input was Off when running Fast Speed. The I_LSM input should be on when the car
is at contract speed, and off when the car is stopped.
B I_LSM Input was On after the car stopped. The I_LSM input should be on when the car is at
contract speed, and off when the car is stopped. Check the operation of the LSM output on
the UCM Board.
C I_ETM and I_EXM Inputs were both off, and I_LSM Input was on. The UCM Board detected
an overspeed or ETSD fault. Check the UCM Board lights.
D I_ETM and I_EXM Inputs were both off, and I_LSM Input was off. The UCM Board detected
an overspeed or ETSD fault. Check the UCM Board lights.
E I_EXM Input was On and the car was running over 95% of contract speed.
F I_ETM Input did not match the ETS Sw inputs, and I_ETM was OFF.
G I_ETM Input did not match the ETS Sw inputs, and I_ETM was ON.
H I_ETM Input was On and the car was running with the Doors open.
I I_ETM Input was On when the car was on Inspection.
J I_RM And I_RCM Inputs were Off. The UCM Board dropped the Rope Brake.
K Car was in the Door Zone
L LV Input was on

SIGNAL DESCRIPTION for HSC-ETS FAULT (Used with A-BMicro830 PLC)


P The car floor position when the fault occurred.
A The car was running up. (Off=car was running down)
B The car speed exceeded 110% of contract speed.
C The car speed exceeded 150fpm on Inspection.
D The car speed exceeded 50fpm with the doors open.
E The car speed was below 10fpm on a fast speed run.
F The car speed showed the car was running the wrong direction.
G The car did not slow below 90% of contract speed after hitting an ETS Switch.
H An ETS Switch did not open when the car reached a terminal landing.

VIRGINIA CONTROLS, INC. MVFAC-3000 User Manual, Rev. 2.11 Page 89


I Car Speed Code Input 1 was ON
J Car Speed Code Input 2 was ON
K Car Speed Code Input 3 was ON
L HSC Up Input was ON.

7.1.3.6 Moving Around in the Fault Log


Press Nxt or Prv to scroll through the Fault Log.
Press Aux to jump to the “Show Internal Memory” screen.
Press Ent to refresh the display.
Press Esc to return to the Run Mode menu screens.
Press . to show the current time.
Press 0 to jump to the first fault.
The keys 1 - 9 are not used in this mode.

7.1.3.7 LED Description in "Show Fault Log" Mode


The LEDs D1, D2, D3, D4 change operation in the Show Fault Log Mode. They now show the
status of the fault being viewed, in the same manner as the LEDs work in the Shown Internal
Memory mode. (Specifically, D1 shows the status of the 1st bit of the time stamp; D2 shows
the status of the 2nd bit of the fault code; D3 shows the status of the 3rd bit of the fault status;
and D4 shows the status of the 4th bit of the second fault status word).

7.1.3.8 Historical Log


The Historical Log contains the number of faults, floor to floor runs, and door operations over a specific
time period. They are counted and stored in memory addresses $0520 to $052F, along with the starting
date of the log, according to the following list.

VIRGINIA CONTROLS, INC. MVFAC-3000 User Manual, Rev. 2.11 Page 90


Address Description
$0520 Month of start of current historical log
$0521 Date of start of current historical log
$0522 Number of Faults, Characters 1 and 2
$0523 Number of Faults, Characters 3 and 4
$0524 Number of Floor to Floor Runs, Characters 1 and 2
$0525 Number of Floor to Floor Runs, Characters 3 and 4
$0526 Number of Door Cycles, Characters 1 and 2
$0527 Number of Door Cycles, Characters 3 and 4
$0528 Month of start of previous historical log
$0529 Date of start of previous historical log
$052A Number of Faults in previous log, Characters 1 and 2
$052B Number of Faults in previous log, Characters 3 and 4
$052C Number of Floor to Floor Runs in previous log, Characters 1 and 2
$052D Number of Floor to Floor Runs in previous log, Characters 3 and 4
$052E Number of Door Cycles in previous log, Characters 1 and 2
$052F Number of Door Cycles in previous log, Characters 3 and 4
The number of faults, runs and door cycles are shown in two registers each, to allow the maximum
number recorded to be over 65000.

VIRGINIA CONTROLS, INC. MVFAC-3000 User Manual, Rev. 2.11 Page 91


To view the data, use the “Show Internal Memory" function to show address $0520. A sample screen is
shown below.

Month of start of current log


Date of start of current log
Address of Number of Faults since the start
Fault Log of this log
0520 05 11 00 14
0524 13 5F 16 19

Number of Runs since the Number of Door Cycles since the


start of this log start of this log

The number of faults, runs and door cycles are in hexadecimal. You can use the table below to convert
the value to decimal.
Match the first hex character in the value to the decimal equivalent in the first two columns in the table;
match the second character to the value in the next two columns; etc. Then add up the decimal
equivalents for all the values to get the decimal value.
In the example shown above, the number of faults is “0014”(hex). Using the table, this is 0 (1st char hex)
= 0 (decimal equivalent from 1st two columns)
0 (2nd char hex) = 0 (decimal equivalent from 2nd1st two columns)
1 (3rd char hex) = 16 (decimal equivalent from 3rd two columns)
4 (4th char hex) = 4 (decimal equivalent from 4th two columns)
0014(hex) = 0+0+16+4 = 20(decimal).
The number of runs is “135F”(hex), which is 4096+768+80+15=4959(dec)
The number of door cycles is “1619”(hex), which is 4096+1536+16+9=5657(dec)
After the number of days set in address $0401 (default is 60) the values from the current Historical Log
(addresses $0520-0527) are moved to the Previous Log (addresses $0528-052F) and the current log is
cleared out. The current date is loaded into the start addresses for the new current historical log.

VIRGINIA CONTROLS, INC. MVFAC-3000 User Manual, Rev. 2.11 Page 92


Table to determine the Decimal Value of a 4-digit Hexadecimal number.
1st Character 2nd Character 3rd Character 4th Character
Hex Decimal Hex Decimal Hex Decimal Hex Decimal
0 0 0 0 0 0 0 0
1 4096 1 256 1 16 1 1
2 8192 2 512 2 32 2 2
3 12288 3 768 3 48 3 3
4 16384 4 1024 4 64 4 4
5 20480 5 1280 5 80 5 5
6 24576 6 1536 6 96 6 6
7 28672 7 1792 7 112 7 7
8 32768 8 2048 8 128 8 8
9 36864 9 2304 9 144 9 9
A 40960 A 2560 A 160 A 10
B 45056 B 2816 B 176 B 11
C 49152 C 3072 C 192 C 12
D 53248 D 3328 D 208 D 13
E 57344 E 3584 E 224 E 14
F 61440 F 3840 F 240 F 15

7.1.4 Show Internal Memory


The "Show Internal Memory" screen (abbreviated to "Show Int. Memory" on the LCD display) shows the
contents of the internal memory. This can be used to check the status of internal registers, to show the
operation of the system.
When this display is selected, the display will show five numbers on each row. The left number in each
row is a 4-digit hexadecimal number showing the memory address of the number immediately to its
right. The memory is 8-bit, so the 4 pairs of numbers on the right show the contents of each of four
consecutive memory addresses in hexadecimal format. A “$” before a number indicates the number is in
hexadecimal not decimal. All memory addresses are hexadecimal, and the contents will be shown in
hexadecimal.
Contents of Memory Address
shown at top left ($1024)
Contents of next Memory
Address ($1025)
Contents of next Memory
Address ($1026)
Memory Address of
top left value Contents of next Memory
1024 FF 00 2D 14 Address ($1027)
Memory Address of
bottom left value 1028 00 FF 00 10
Contents of next four Memory
Addresses ($1028, $1029, $102A,
$102B)
VIRGINIA CONTROLS, INC. MVFAC-3000 User Manual, Rev. 2.11 Page 93
For example, if the display reads "1024 FF 00 2D 14", as shown above, then the top left number "1024"
shows the address of the first value; the contents of address "1024" is "FF"; the contents of address
"1025" is "00"; the contents of address "1026" is "2D"; and the contents of address "1027" is "14" (with
each value being shown in hexadecimal).

NOTE: For addresses that show an ON or OFF condition, "00" is OFF, and "FF" is ON.

7.1.4.1 Moving Around in the Internal Memory


Press Nxt to increase the addresses being displayed by
4. 1000 100 10 4
Press Prv to decrease the addresses being displayed
by 4.
1000 100 10 4
Press 3 to increase the addresses being displayed by
10(Hex).
Press 6 to decrease the addresses being displayed by 1
10(Hex).
Press 2 to increase the addresses being displayed by
100(Hex).
Press 5 to decrease the addresses being displayed by
100(Hex).
Press 1 to increase the addresses being displayed by
1000(Hex).
Press 4 to decrease the addresses being displayed by 1000(Hex).
Press Aux to increase the addresses being shown by 1.
Press Esc to return to the menu screens.

7.1.4.2 LED Description in "Show Internal Memory" Mode


The LEDs D1, D2, D3, D4 change operation in the Show Internal Memory Mode. They now
show the status of the top 4 words being displayed.
Specifically, D1 shows the status of the 1st bit of the top left word being displayed; D2 shows
the status of the 2nd bit of the 2nd left word being displayed; D3 shows the status of the 3rd
bit of the 3rd top left word being displayed; and D4 shows the status of the 4th bit of the 4th top left
word being displayed.
This allows the LEDs to show rapid changes in the status of internal memory that the LCD display would
not be quick enough to respond to.

VIRGINIA CONTROLS, INC. MVFAC-3000 User Manual, Rev. 2.11 Page 94


7.1.4.3 Changing values in the “Show Internal Memory” Mode
If the password has been entered, it is possible to change data in the Show Internal Memory mode.

WARNING: Changing data could cause unexpected and dangerous results. Do not do
this unless you are fully aware of the value that needs to be changed, and how to
change it. Take all necessary precautions to prevent an unsafe condition, such as
disconnecting the terminal blocks from the outputs, removing the appropriate fuses,
or opening the appropriate safety circuits.

Use the normal keys to navigate to the memory location that is to be changed, as shown in “Moving
Around” above. You can only change the value that is in the top left of the display. For example, if the
top line of the display shows “2012 04 37 82 34” then memory location 2012 can be changed from its
current value of 04.
To change a value, press . (the top left character will flash briefly) then press one of the following keys:
Press Nxt to increase the addresses being displayed by 1.
Press Prv to decrease the addresses being displayed by 1.
Press 3 to increase the addresses being displayed by 4.
Press 6 to decrease the addresses being displayed by 4.
Press 2 to increase the addresses being displayed by 10(Hex).
Press 5 to decrease the addresses being displayed by 10(Hex).
Press 1 to increase the addresses being displayed by 40(Hex).
Press 4 to decrease the addresses being displayed by 40(Hex).
Press 8 to enter a value of (“FF”(Hex) minus the old value).
Press 9 to enter a value of “FF”(Hex).
Press 0 to enter a value of “0”.
Press 7 or Aux or . or Ent to leave the value unchanged
Press Esc to return to the menu screens.

7.1.5 Show Car Status


The “Show Car Status” screen displays the car status. Each area of the screen will display one of several
messages that allow the user to see what the elevator is doing. The only key that is active in this screen
is the Esc key, which returns to the menu selection screens. Leaving the “Car Status” screen on the LCD
will slow the scan time down very slightly, since writing to the LCD is a fairly slow process. The writing is
done while the I/O boards are being polled, so there is little overall impact on scan time. Consequently

VIRGINIA CONTROLS, INC. MVFAC-3000 User Manual, Rev. 2.11 Page 95


it is acceptable to leave the “Car Status” screen on the LCD, thus allowing a technician to quickly see a
fault without having to scroll to that screen.

7.1.5.1 Messages Displayed on the “Car Status” Screen


Each area of the screen will display one of several messages. The numbers in the sample screen below
indicate the message areas. Each group of numbers will be replaced by the appropriate message,
depending on the status of the car.

111 222222333333
4 55 66 7777 888

Message # 1 will be replaced with one of the following messages:


1. “BAT” – the CPU Battery is low.
2. “INS” – the car is on Inspection Operation.
3. “MEC” – the car is on Medical Emergency in the car, or EMT (Emergency Medical Technician Service)
in the car.
4. “IDS” – the car is on Independent Service.
5. “MEH” – the car is responding to a Medical Emergency Call from the Hall, or an EMT call from the
Hall.
6. “ATT” – the car is on Attendant Service.
7. “(no message)” – the car is not on one of the special operations shown above.

Message # 2 will be replaced with one of the following messages:


1. “RopeBk” – the Rope Brake tripped. Check the Fault Log to see what caused this. To reset this fault,
the Shutdown Defeat Input must be turned on momentarily. If it is already on, turn it off then back
on.
2. “DrvFlt” – the Drive Ready Input is not on. Check the Drive.
3. “RunFlt” – the running timer fault has tripped. The car ran too long between floors.
4. “SeqFlt” – the run relays did not sequence properly when the car started or stopped.
5. “RedROP” – a Redundancy Fault in the ESB Emergency Stop Sw Bypass circuit or the Rope Brake
monitoring circuits has been detected. The input that monitors the Emergency Stop Switch Bypass
function indicated the Emergency Stop Switch was bypassed when it should not have been, OR one
of the Rope Brake monitoring inputs (RB6, RBC6) did not match the corresponding Rope Brake
outputs (RB, RBX, RBC). The car will shut down at the next stop. Check the ESB relay, or ESB
monitoring input, and its associated wiring, and the Rope Brake relays and monitoring inputs. Cycle
the power to reset the fault.
6. “RedRUN” – a Redundancy Fault in the running or leveling circuits has been detected. The car will
shut down at the next stop. Cycle the power to reset the fault.
Controllers using the MH5 printed circuit board – The Door Contact Bypass circuit monitoring point
VIRGINIA CONTROLS, INC. MVFAC-3000 User Manual, Rev. 2.11 Page 96
(LV) was energized when it should not have been, OR the run input (UD1 or UD2) was still on after
the car stopped. Check the external circuits for stuck relays (UL, DL, DZ, LV, LVX, U, D, etc) or a stuck
input.
7. “RedSAF” – a Redundancy Fault in the Safety Circuit has been detected. The car will shut down at
the next stop. The condition of the Door Fault Monitor input (DFM) was not correct, OR the Car Gate
Input (5) or Door Contacts Input (5X) was not correct. This may be caused by temporary jumpers
added during initial installation, or a short in the Safety Circuit. Cycle the power to reset the fault.
8. “RedINS” – a Redundancy Fault in the Inspection Door Bypass circuits has been detected. The car
will shut down at the next stop. One of the inputs that monitors the circuits that bypass the Door
Contacts on Inspection or Access operation was closed when the car was not on Inspection or
Access, or terminal 4 was not hot. Check the Door Contact circuit for jumpers or shorts. Cycle the
power to reset the fault.
9. “DZFlt” - – a Door Zone Fault was detected. The Door Zone input was on while the car was running
fast speed, OR the Door Zone Input came on before an Up or Down Level Sw came on. Check the
Door Zone Switch.
10. “LevSws” – both of the Leveling“LevStk” – both of the Leveling Switches are on at the same time.
11. “OvrSpd” – the car was running too fast with the doors open.
12. “SHUNT” – the Shunt Trip input is enabled. The car will stop at the next landing, open its doors, and
shutdown.
13. “SMOKE” – the Machine Room/Shaftway Fire detectors Input is energized.
14. “FIRE2 ” – the car is on Fire Service Phase 2 (car).
15. “FIRE1 ” – the car is on Fire Service Phase 1 (hall).
16. “OutDZ” – the car has stopped outside the Door Zone
17. “ Auto “ – the car is in automatic operation. It will respond to car and hall calls.
18. “ NoHC ” – the car is not answering Hall Calls. This may be caused by Inspection, Independent
Service, Fire Service, Medical Emergency Service, Shutdown, Door Check Fault. The cause is usually
shown in one of the other status messages.

Message # 3 will be replaced with one of the following messages:


1. “Em.Pwr” – the Reverse Phase Input or the Emergency Power Input is off.
2. “ SHTDN” – the car is in shutdown.
3. “ PwrOK” – none of the other faults exist. The car is on normal power, and not on shutdown.

Message # 4 will be replaced with one of the following messages:


1. The car position will be shown as a number between 1 and 8, with 1 as the bottom landing.
2. If the floor position is not known (such as on initial installation) then message #4 will show “?”.
Message # 5 will be replaced with one of the following messages:

VIRGINIA CONTROLS, INC. MVFAC-3000 User Manual, Rev. 2.11 Page 97


1. “UP” – the car is running up.
2. “DN” – the car is running down.
3. “DC” – the doors closed input is on.
4. “DO” – the doors closed input is off. The car cannot run.

Message # 6 will be replaced with one of the following messages:


1. “UL” – the car is leveling up.
2. “DL” – the car is leveling down.
3. “DZ” – the car is in the Door Zone.
4. “FS” – the car is running fast speed.
5. “SS” – the car is running slow speed.
6. “(no message)” – the car is not running, and it is not in the door zone.

If the appropriate fault exists, Message # 7 and #8 will be replaced with one of the following messages:
1. “IO-FAULT” – the communication with one or more of the I/O boards has failed.
2. “DrChkFLT” – the Door Closed Input is on, and the Door Closed Limit is on, indicating the Door
Contacts have been jumped.
3. “DrLmtFLT” – the Door Open Limit and the Door Close Limit are both off.
4. If none of these three faults are present, then messages # 7 and # 8 will show the door status as
shown below.

Message # 7 will be replaced with one of the following messages:


1. “OPNG” – the doors are opening.
2. “CLSG” – the doors are closing. This is also displayed when the car is running, and the Door Close
output is on.
3. “OPEN” – the doors are fully open.
4. “CLSD” – the doors are fully closed.
5. “STOP” – the doors have stopped and are not fully open or fully closed.

Message # 8 will be replaced with one of the following messages:


1. “NUD” – Nudging Operation has been initiated.
2. “TDO” – the Door Open Timer has tripped. The doors failed to open fully in the preset time.
3. “TDC” – the Door Close Timer has tripped. The doors failed to close fully in the preset time.
4. “TEE” – the Electric Eye Cutout Timer has tripped. The Electric Eye Input will be cut out.
VIRGINIA CONTROLS, INC. MVFAC-3000 User Manual, Rev. 2.11 Page 98
5. “(no message)” – none of the four conditions above are present.

7.1.6 Go To Set-Up Mode


This selection allows the controller to be taken out of normal operation, and put in the Set-up Mode, so
that features and settings may be changed.
When Ent is pressed at this selection, a warning screen will be displayed, indicating that the
controller will stop.
If Ent is pressed again, then the controller will turn off all outputs and the controller will go
into the Set-up Mode. A banner will be displayed for 1 second indicating the Set-up Mode has been
entered. The first selection of the Set-up Menu will then be displayed.
If any other key is pressed from the warning screen, the controller will return to the Run Mode, and the
controller will continue operating as normal.
LED D5 will flash every 10 seconds in the Set-up Mode, indicating that the CPU is still running normally.

7.1.7 Effect of Diagnostic Modes on Scan Time


The micro-processor scan time is very fast, with each scan taking about 7 milliseconds. Servicing the LCD
display is one of the more time consuming tasks that the micro-processor does, so when the LCD display
needs to be updated regularly, the micro-processor must slow down to allow it to accept the data.
Consequently, the scan time is slower when in the "Show I/O Status" and "Show Internal Memory"
Modes, than when displaying other screens. The car will still operate normally, but it is recommended
that the display not be left in those modes when those screens are not specifically being used. The LCD
can be left showing the “Show Car Status” screen, since this updates the screen while the I/O is being
polled, consequently the impact on the scan time is minimal.
With program version 3A, dated March 2005, the scan time has been optimized for IO communication,
so the impact on scan time is minimal no matter what screen is being viewed.

VIRGINIA CONTROLS, INC. MVFAC-3000 User Manual, Rev. 2.11 Page 99


7.2 Set-Up Mode

7.2.1 How to Enter Set-Up Mode


In the Run Mode, press Nxt until the selection "Go To Setup Menu" is shown, then press Ent.
Press Ent when the "Warning" message is displayed.

WARNING: The elevator will stop immediately and be completely shut down, as all
outputs will be turned off when the Set-up Mode is entered.
The LEDs D1-D4 are not updated in the Setup Mode, so they will remain in their last state. LED D5 will
flash once every 10 seconds, to indicate the CPU is not locked up.

7.2.2 How to Exit Set-Up Mode


Press Esc from the Set-up Menu to return to the Run Mode. The controller will start running again, and
will be in the Show Car Status Mode. LED D5 will start flashing about once a second, indicating the CPU
is scanning. LEDs D1-D4 will revert to their normal operation.

NOTE: It may be necessary to press Esc to exit a sub-menu and return to the Set-up
Menu, before going back to the Run Mode.

7.2.3 Set-Up Mode Screens


The following Menu items are available in the Set-up Mode:
1. Reset Settings.
2. Change Settings.
3. Change Features.
4. Show Fault Log.
5. Show Internal Memory.
6. Set The Time.
7. Enter Password.
8. Test I/O Boards.

VIRGINIA CONTROLS, INC. MVFAC-3000 User Manual, Rev. 2.11 Page 100
SETUP MODE SCREENS
To CHANGE SETTINGS, (see below)

Virginia Controls Press ENTER to ALL SETTINGS


MAIN SETUP MENU RESET SETTINGS HAVE BEEN RESET

To Run Mode, Press ENTER to WARNING: TEST


Car Status Screen TEST I/O BOARD ACTIVATES RELAYS

= Press “Nxt” Press ENTER to ENTER PASSWORD


ENTER PASSWORD
= Press “Prv”
= Press “Ent” Press ENTER to (Enter the Time
SET THE TIME and Date)
= Press “Esc”
Press ENTER to 0400 00 00 00 00
The normal sequence is to press “Nxt” SHOW INT MEMORY 0404 00 00 00 00
to select the desired menu item.
Press “Ent” to use the menu item.
Press ENTER to 01 09:40 FLTCODE
Press “Esc” when you are finished.
SHOW FAULT LOG 2 1100 0011 0010

Press ENTER to (Display and Change


WARNING: CHANGE FEATURES Adjustable Features)
IN SETUP MODE,
THE CAR IS SHUT DOWN. Press ENTER to (Display and Change
CHANGE SETTINGS Adjustable Settings)

To RESET SETTINGS, (see above)

Press the Nxt or Prv keys to move through the Set-up Menu to the desired item, then press Ent to
select the menu item.

7.2.4 Reset Settings


This selection allows all settings and features to be reset to the factory values that are stored in the
EPROM. This should be done on initial installation, and is recommended if the operation of the car
seems strange. (See the warning below.)
Press Ent to reset all settings and features to the values programmed from the factory. After pressing
Ent the password entry screen will be shown. This prevents accidentally resetting the default values.
The password must be entered each time the Reset Settings is attempted. Enter the password “911”
then press Ent to reset all settings and features to the factory default. Press Esc to exit without
resetting the settings and features. If the job is a standard job, then the specific settings and features for
your job must be entered after doing a factory reset. (See the warning note below)
Press Nxt or Prv to move to another item in the Set-up Menu.
Press Esc to return to the Run Mode.

VIRGINIA CONTROLS, INC. MVFAC-3000 User Manual, Rev. 2.11 Page 101
NOTE: An internal memory check is done on each power up. So if a corrupted memory
is detected, a factory reset will be done automatically.

WARNING: On standard jobs, the factory reset will return the settings and features to
a generic default. The actual settings and values for the specific job must now be
entered to customize the job for the particular application. To determine if a
particular controller has a standard program, go to the banner screen. If the value in
the lower left of the screen is the Virginia Controls Job Number, then the chip is
specific for that job, and a factory reset will load the values for that job. If the value is
not the job number, (it will start with “DSS”, “DDS”, “DAS”, or something similar) then
the program is a standard, and the actual values for the job need to be entered. These
values are provided with the controller in the schematic, and are based on the
requirements of the job, as conveyed to Virginia Controls.

A factory reset can also be done without the keypad as follows:


1. Turn off the power
2. Turn the Inspection Switch to "Inspection" (or remove the field wire from terminal 23)
3. Jump terminals 1 to 21 and 22 (Up and Down Level Switch Inputs)
4. Turn the power back on for 10 seconds. Inputs 1 and 2 on Board 1 should both be ON, and Input 3
on Board 1 should be OFF.
5. Turn off the power
6. Remove all jumpers and put the car back on normal operation.

7.2.5 Change Settings


Use this selection to change the settings described below. Each setting contains a value from 0 to 255.
As you scroll through the settings, the current value will be displayed. A new value may be entered over
the old value, as desired.

NOTE: The Password “911” is required to gain access to this menu selection, unless the
password has already been entered in another sequence.

Press Nxt to go to the next setting, without changing the current setting.
Press Prv to go to the previous setting, without changing the current setting.
Press a numeric key ( 0 - 9 ) to enter a new value. (The decimal point key . is not used)
Press Ent after entering a new value to load the new value into memory. (The message “VALUE
SAVED!” is displayed for 1 second, indicating the new entry has been accepted, then the display will
show the setting and the new value) If Nxt, Prv or Esc is pressed after entering a new value, the new
value will NOT be stored in memory.
Press Esc to go back to the Setup Menu.

VIRGINIA CONTROLS, INC. MVFAC-3000 User Manual, Rev. 2.11 Page 102
If an incorrect value is entered, press Esc to clear the value before it is accepted, then enter the correct
value; or press Nxt or Prv to move to the next setting. If the value was already entered, by pressing
Ent, then press Nxt or Prv to return to the incorrect setting, enter the proper value, and press Ent.

7.2.5.1 Description of Settings


Refer to the sheet MH-3000 Settings in the schematic to see the settings and features provided for each
particular job. The following Settings are standard:

NOTE: A value of 0 to 255 can be entered unless otherwise stated.

• Number of I/O Boards - (Display shows "NUM.OF IO BOARDS") This is the number of Input and
Output Boards that the CPU will address, and is a value between 1 and 8. If a value out of this range
is entered, then a default value of 2 will be entered when the car is put back into the Run Mode.
• Number of Landings - (Display shows "NUMBER OF LDGS") This is the number of landings that the
controller can serve, and is a value between 2 and 8. If the controller is set up to serve future
landings, then this value can be used to temporarily cut off future upper landings. This value also
determines which floor the controller will reset to when a top landing reset is initiated with a pulsing
selector.
• Main Fire Landing - (Display shows "MAIN FIRE LDG") This is the number corresponding to the Main
Fire Landing, and is a number between 1 and 8. The value set is based on the bottom floor being
"1", the 2nd floor is "2" etc., even if this does not match the building designations.

CAUTION: If it is set to a value greater than the number of landings served, the car will
go to the top landing, but it will not open its doors.
• Alternate Fire Landing - (Display shows "ALT. FIRE LDG") This is the number corresponding to the
Alternate Fire Landing, and is a number between 1 and 8. The value set is based on the bottom floor
being "1", the 2nd floor is "2" etc., even if this does not match the building designations.

CAUTION: If it is set to a value greater than the number of landings served, the car will
go to the top landing, but it will not open its doors.
• Home Landing (SIMPLEX ONLY) - (Display shows "HOME LANDING") This is the home landing for a
simplex car. The car can be selected to home to this landing, if desired. This value can be set to any
valid landing, as determined by the number of landings setting.
• Dispatch Landing (DUPLEX ONLY) - (Display shows "DISPATCH LDG") This is the dispatch landing for
duplex systems. One car will always home here. This value can be set to any valid landing, as
determined by the number of landings setting.
• Upper Home Landing (DUPLEX ONLY) - (Display shows "UPPER HOME LDG") This is the home
landing for the free car in a duplex system. The free car can be selected to home to this landing, if
desired. This value should be set to be inside the upper zone, as determined by the Low Zone
assignments shown later in the features settings.
• Front Door Code - (Display shows "FRONT DOOR CODE") This is a binary coded value used to select
which front openings are enabled. Each bit corresponds to a landing. If the bit for a landing is on,
then the front doors at that landing will be enabled. Use the chart shown in the schematic to
VIRGINIA CONTROLS, INC. MVFAC-3000 User Manual, Rev. 2.11 Page 103
determine the proper value. Add up the value for each floor to determine the total value for this
setting. A value of “255” will enable the front doors at all floors.
• Rear Door Code - (Display shows "REAR DOOR CODE ") This is a binary coded value used to select
which rear openings are enabled. Each bit corresponds to a landing. If the bit for a landing is on,
then the rear doors at that landing will be enabled. Use the chart in the schematic to determine the
proper value. Add up the value for each floor to determine the total value for this setting. A value
of “0” will disable the rear doors at all floors.
• Low Zone Code (DUPLEX ONLY) – (Display shows “LOW ZONE CODE”) This value determines which
floors are in the Low Zone. The floors will normally be served by the Lobby car, other floors will
normally be served by the Free car. Each bit corresponds to a landing. If the bit for a landing is on,
then that floor is in the Low Zone. Use the chart shown in the schematic to determine the proper
value. Add up the value for each floor to determine the total value for this setting. A value of “3”
will set the Low Zone as the bottom two floors.
The Bit Features are multiple features combined into several settings. Each setting consists of 8 features
that can be turned on or off individually. Refer to the sheet MH-3000 Settings in the schematic for a
breakdown of each setting. A description of the standard features that may be part of the Bit Features
are listed in a following section, after the standard settings.
• Bit Features # 1 - (Display shows "BIT FEATURES # 1") This is a binary coded value used to select
various features as shown in the chart in the schematic on the MH-3000 SETTINGS sheet. Each bit
corresponds to a different feature. If the bit for a feature is on, then that feature is enabled. Use
the chart to determine the proper value. Add up the value for all the features that should be
enabled to determine the total value for this setting.
• Bit Features # 2 - (Display shows "BIT FEATURES # 2") Similar to Bit Features #1.
• Bit Features # 3 - (Display shows "BIT FEATURES # 3") Similar to Bit Features #1.
• Bit Features # 4 - (Display shows "BIT FEATURES # 4") Similar to Bit Features #1.
• Bit Features # 5 - (Display shows "BIT FEATURES # 5") Similar to Bit Features #1.
• Bit Features # 6 - (Display shows "BIT FEATURES # 6") Similar to Bit Features #1.
• Bit Features # 7 - (Display shows "BIT FEATURES # 7") Similar to Bit Features #1.
• Bit Features # 8 - (Display shows "BIT FEATURES # 8") Similar to Bit Features #1.
• Bit Features # 9 - (Display shows "BIT FEATURES # 9") Similar to Bit Features #1.
• Bit Features # 10 - (Display shows "BIT FEATURES # 10") Similar to Bit Features #1.
• Custom Time #0.1 – (Display shows “CUSTOM TIME #0.1”) This is a reserved value that is not
assigned, but may be assigned a function for a specific job. The time base for this timer is not
preset, and may change depending on its use. Refer to the Settings sheet in the schematic to see if
and how this setting is used.
• Custom Time #0.2 – (Display shows “CUSTOM TIME #0.2”) Similar to Custom Time #0.1.
• Custom Time #0.3 – (Display shows “CUSTOM TIME #0.3”) Similar to Custom Time #0.1.
• Custom Time #0.4 – (Display shows “CUSTOM TIME #0.4”) Similar to Custom Time #0.1.

VIRGINIA CONTROLS, INC. MVFAC-3000 User Manual, Rev. 2.11 Page 104
• # of Fault Resets – (Display shows “# Fault Resets.”) This is the number of automatic fault resets
allowed. The controller can be set up to automatically reset the Running Timer Fault and the
Start/Stop Sequence Fault. This can be done for the number of times set by this setting. The count
of automatic resets is reset if the car is put on Inspection, or the power is cycled, or the car runs
without a fault for 40 minutes.
• Door Time, Hall (in tenths of a second) - (Display shows "DOOR TIME, HALL") This is the time in
tenths of a second, that the doors will remain open, after they have opened fully, when the car has
stopped in response to a hall call. After this time, the doors will start to close.

NOTE: If a car call is entered while the doors are open, the door time will be reduced
to the "Door Time, Car" setting. If the Door Close Button is pressed while the doors
are open, the door time will be reduced to the "Door Time, Short" setting. This setting
is normally 50, for a time of 5 seconds.

• Door Time, Car (in tenths of a second) - (Display shows "DOOR TIME, CAR") This is the time in tenths
of a second, that the doors will remain open, after they have opened fully, when the car has stopped
in response to a car call only. After this time, the doors will start to close.

NOTE: If a car call is entered, or the Door Close Button is pressed, while the doors are
open, the door time will be reduced to the "Door Time, Short" setting. This normal
setting is 20, for a time of 2 seconds.

• Door Time, Short (in tenths of a second) - (Display shows "DOOR TIME, SHORT") This is the time in
tenths of a second, that the doors will remain open, after they have opened fully, when the doors
have reopened in response to a Door Open Button/Safety edge/Electric Eye/Infra-red Curtain, and
no hall call is entered. After this time, the doors will start to close. The normal setting is 10, for a
time of 1 second.
• Leveling Cutout Time (in tenths of a second) - (Display shows "LEVELING LOCKOUT") This is the time
in tenths of a second that the leveling switches are cut out after the start of a floor to floor run. It
allows the external relays to energize and lock out the leveling switches externally. The normal
setting is 20, for a time of 2 seconds.
• Back Call Delay (DUPLEX ONLY) (in tenths of a second) - (Display shows "BACK CALL DELAY") This is
the time in tenths of a second that the back call signal will be delayed before letting the other car
respond to calls behind this car. The normal setting is 10, for a time of 1 second.
• Custom Time #1.1 (in tenths of a second) - (Display shows "CUSTOM TIME #1.1") This is a reserved
value that is not assigned, but may be assigned a function for a specific job.
• Custom Time #1.2 (in tenths of a second) - (Display shows "CUSTOM TIME #1.2") See Custom Time #
1.1
• Custom Time #1.3 (in tenths of a second) - (Display shows "CUSTOM TIME #1.3") See Custom Time #
1.1
• Shutdown Time (in seconds) - (Display shows "SHUTDOWN TIME") If the car runs up without
passing a floor for this time, then shutdown will be initiated. The car will stop, and run down to the
bottom landing, and cycle its doors. It will then be shut down. The car can be returned to service by
cycling the Inspection Switch, or the Main Line Disconnect Sw. The normal setting is 25 seconds.

VIRGINIA CONTROLS, INC. MVFAC-3000 User Manual, Rev. 2.11 Page 105
• Door Nudging Time (in seconds) - (Display shows "NUDGING TIME") This is the time delay before
initiating door close nudging, if that feature is provided. A call must be registered, and the car must
be in automatic operation. The timer is reset when the doors get fully closed, or when the car starts
a floor to floor run. The normal setting is 25 seconds.
• Electric Eye Cutout Time (in seconds) - (Display shows "EYE CUTOUT TIME") This is the time delay
before cutting out the Electric Eye Input, after it has been continuously energized. It is reset when
the car runs to the next floor. The normal setting is 20 seconds.
• Homing Delay Time (in seconds) - (Display shows "HOMING DELAY") This is the delay before homing
a car to the home landing, after it has answered all calls, and is sitting with its doors closed. The
normal setting is 10 seconds.
• Car Stuck Time (in seconds) - (Display shows "CAR STUCK TIME") This is the time delay before calls
at the same landing as the car are disabled, so that the car can answer other registered calls. This
operates as a stuck button timer. The normal setting is 15 seconds.
• Door Stuck Time (in seconds) - (Display shows "DOOR STUCK TIME") This is the time delay before
stopping a door open or close cycle. The normal setting is 20 seconds
• Door Stuck Reset Time (in seconds) - (Display shows "DOOR RESET TIME") This is the time that the
doors are held open after failing to close properly, before retrying to close. The normal setting is 10
seconds.
• Delay Before Canceling Independent Service on Fire Service - (Display shows "KILL IDS ON EFS1")
This is the time delay before Independent Service is cut out, when Fire Service Phase 1 is initiated.
This feature can be modified by the Bit Features described above that determine if and when
Independent Service is cut out on Fire Service. The normal setting is 30 seconds.
• Door Close Delay Time on Fire Service (in seconds) - (Display shows "DR CLOSE ON FIRE") This is the
delay before closing the doors after the car has returned on Fire Service Phase 1 to the Main Ldg. It
may be required, depending on the Fire Code used.
• The normal setting is 30 seconds.
• Call Help Time (DUPLEX ONLY) (in seconds) - (Display shows "CALL HELP TIME") This is the amount
of time a hall call can be registered before the other car not assigned this call will respond to the
call. The normal setting is 30 seconds.
• Non Interference Time (SAPB ONLY) (in seconds) - (Display shows “NON INTERFERENCE”) This is the
time that the In Use Light will remain on after the car has answered a call and cycled its doors. Hall
Call Buttons will be disabled during this time. The normal setting is 6 seconds.
• Custom Time #2.1 (in seconds) - (Display shows "CUSTOM TIME #2.1") This is a reserved value that
is not assigned, but may be assigned a function for a specific job.
• Custom Time #2.2 (in seconds) - (Display shows "CUSTOM TIME #2.2") See Custom Time # 2.1
• Custom Time #2.3 (in seconds) - (Display shows "CUSTOM TIME #2.3") See Custom Time # 2.1
• Position Indicator Cutout Time (in tens of seconds) - (Display shows "PI CUT OUT TIME ") This is the
time delay before turning off the Position Indicators, after the car has become idle. If the doors are
opened, or the car starts in response to a call, then the Position Indicators will turn on again. The

VIRGINIA CONTROLS, INC. MVFAC-3000 User Manual, Rev. 2.11 Page 106
normal setting is 30, for a time of 5 minutes. To keep the PI’s on at all times, enter a value of “0” for
the Cutout Time.
• Custom Time #3.1 (in tens of seconds) - (Display shows "CUSTOM TIME #3.1") This is a reserved
value that is not assigned, but may be assigned a function for a specific job.
• Custom Time #3.2 (in tens of seconds) - (Display shows "CUSTOM TIME #3.2") See Custom Time #
3.1
• Custom Time #3.3 (in tens of seconds) - (Display shows "CUSTOM TIME #3.3") See Custom Time #
3.1
Some installations require specific settings or features that are not included in the standard program. In
this case, a separate sheet (or sheets) will be provided that describe the operation of these settings or
features, and what the factory default settings are.

7.2.5.2 Description of Bit Feature Settings


The following features are combined into the Bit Features 1 through 10. Refer to the sheet MH-3000
Settings in the schematic to see the settings and features provided for each particular job. The following
Settings are standard.
• Disable Fire Service – Turn this feature on to disable Fire Service. This feature should be turned on if
Fire Service is not provided. It may also be turned on during initial installation, if the Smoke Sensors
or Fire Switches have not yet been installed.
• Enable 2000 ANSI Fire Code – Turn this feature on to enable 2000 or 2004 National Fire Code. The
default code is 1998 Fire Code.
• Enable 2005+ ANSI Fire Code – Turn this feature on to enable 2005 or later National Fire Code. You
must also turn on the 2000+ Fire Code feature.
• Flash Fire Light per 2005 Code – Turn this feature on to make the Fire Light flash based on the
requirements of 2005 and later ANSI codes. With this enabled, the Fire Light will only flash if Fire
Service was initiated by the Smoke Sensors connected to terminal 82F (Machine Room and Hoistway
Smoke Sensors). If those sensors trip after Fire Service is already initiated, then the Fire Light will not
flash.
• Enable New York Fire Code – Turn this feature on to enable New York Fire Code.
• Enable 2001 Chicago Fire Code – Turn this feature on to enable 2001 Chicago Fire Code
• Enable 1998 Chicago Fire Code – Turn this feature on to enable 1998 Chicago Fire Code
• Use 2 Inputs for 1998 Chicago Fire Code – Turn this feature on to use 2 inputs for the Fire Inputs for
Chicago 1998 Fire Code.
• Enable Canadian Fire Code – Turn this feature on to enable 1998 Canadian B44 Fire Code
• Enable Bldg Fire Sw for 2000 Fire Code – Turn this feature on to enable the Remote Fire Sw on 2000
Fire Code. The input for this feature must have been assigned for this feature to work properly.
• Kill Independent immediately on Fire Service – Turn this feature on to allow Fire Service to override
Independent Service immediately.

VIRGINIA CONTROLS, INC. MVFAC-3000 User Manual, Rev. 2.11 Page 107
• No Timed Kill of Independent on Fire Service – Turn this feature on to prevent Fire Service from
overriding Independent Service. Independent Service must be turned off or the doors closed by the
operator to allow the car to run on Fire Service.
• Never kill Indep. on Fire Service – Turn this feature on to prevent Fire Service from overriding
Independent Service. Independent Service must be turned off to allow the car to run on Fire
Service.
• Main Fire Landing at Rear Opening – Turn this feature on to use the rear opening at the designated
fire opening, instead of the front opening. If there is only one opening at the designated fire
landing, then this feature will have no effect.
• Alternate Fire Landing at Rear Opening – Turn this feature on to use the rear opening at the
alternate fire opening, instead of the front opening. If there is only one opening at the alternate fire
landing, then this feature will have no effect.
• Disable Shunt Trip on Fire Service Phase 2 – Turn this feature on to disable Shunt Trip operation
when the car is on Fire Service Phase 2.
• Enable Shunt Trip on Inspection – Turn this feature on to enable Shunt Trip operation when the car
is on Inspection.
• Disable ECReturn Latch on 2000 Fire Code – Turn this feature on to disable the holding circuit on
Fire Service Phase 2 Return on 2000 (or later) Code. This allows the Return mode to be cancelled by
turning the Fire Switch to the “On” position. Check the appropriate code to see if this is required or
allowed.
• Enable Pulsing Selector (off=Floor Sws) – Turn this feature on to enable a pulsing floor selector,
rather than individual Floor Switches. With a pulsing arrangement, there is an up or a down pulse to
change floors. Additionally at the terminal landings, enabling the up pulse input and the door zone
input will reset to the top landing, while energizing the down pulse and door zone will reset the floor
position to the bottom landing.
• Enable Separate Call I/O (4 Wire Calls) – Turn this feature on to enable separate wiring for the
inputs and outputs for the car and hall calls. If this feature is disabled then the car and hall call
inputs are connected to the corresponding outputs.
• Enable Door Check Feature – Turn this feature on to enable the Door Check feature. This allows the
status of the Car Door and the Hall Doors to be checked according to the appropriate codes.
• Enable Redundancy Fault Checking – Turn this feature on to enable 2000 (or later) code redundancy
fault checking. This enables the redundancy fault timers, and checks the leveling inputs and running
inputs for stuck relays or contacts, according to the 2000 (or later) code.
• Use Car Lantern outputs for Hall Lanterns – Turn this feature on to use the Car Lantern outputs as
Hall Lanterns. If there are only two landings, then the Hall Lanterns can be connected directly to the
Car Lantern outputs. If there are more than two landings, then additional external relays are needed
to enable the appropriate lantern at each floor.
• Do Not Run On Fire Service and BORIS – Turn this feature on to prevent the car from running if Fire
Service is enabled while on battery backup operation.

VIRGINIA CONTROLS, INC. MVFAC-3000 User Manual, Rev. 2.11 Page 108
• Do Not Run on Fire Service and Shutdown – Turn this feature on to prevent the car from running if
Fire Service is enabled while on shutdown. If this feature is not enabled the car will be allowed to
run down on Fire Service and shutdown.
• Allow Door Zone Fault on Fast Speed – Turn this feature on to allow the Door Zone Fault to be
initiated if the car is running fast speed and the input is on. False trips are prevented by the Leveling
Cutout Timer, which prevents a fault as the car starts, and before the FSU/FSD relays energize.
• Allow Stop at Upper Floor on Shutdown – Turn this feature on to allow the car to stop at an upper
floor on shutdown if it is the main floor. Check with the appropriate codes to see if this is allowed or
required.
• Enable CKO on Independent – Turn this feature on to energize the CKO Car Call Cutout Override
output on Independent Service. This will allow car calls to be registered without the use of access
keys.
• Fire Sensors are Normally Open Inputs – Turn this feature on if the Smoke Sensor inputs are
normally open on normal operation, and close when a fire is detected. The default is to use Smoke
Sensors that are closed on normal operation and open when a fire is detected.
• Dir Indicators show actual direction on Attend. – Turn this feature on to make the Attendant
Direction Indicators show the direction that the car will run next. If this feature is not enabled then
they will show whether there are calls registered in either direction. For example, with this feature
off, and the car at an intermediate floor with calls above and below the car, then both Attendant
Direction Indicators would be on, since there are calls above and below the car. If the feature was
enabled, then the indicators would be the same as the normal Direction Indicators, and only one
indicator would be on, depending on which direction had actually been selected.
• Med Emerg Buzzer on Independent only – Turn this feature on to change the operation of the
Medical Emergency Buzzer output. With the feature disabled (factory default) the buzzer will come
on while the car is returning to the Medical Emergency floor in response to the hall Medical
Emergency Switch. If the feature is enabled, the buzzer will come on if the car is on Independent
Service and a hall Medical Emergency Switch is turned on. This alerts the operator to release the
car.
• Always Enable DOB at Front Openings – Turn this feature on to allow the Front Door Open Button
to always open the doors at selective openings (where there is a front and rear opening at the same
landing). With this feature disabled, the doors must have been opened, or still be open, for the Door
Open Button to operate. This allows a measure of security at these landings.
• Always Enable DOB at Rear Openings – Turn this feature on to allow the Rear Door Open Button to
always open the doors at selective openings (where there is a front and rear opening at the same
landing). With this feature disabled, the doors must have been opened, or still be open, for the Door
Open Button to operate. This allows a measure of security at these landings.
• Disable Non-Shutdown Faults in Fault Log – Turn this feature on to disable faults from being logged
into the Fault Log that are not shutdown faults. This keeps the fault log clear of non-essential faults.
The following faults will not be logged if this feature is enabled: TDOPEN, TDCLOSE, TDOPN-R,
TDCLO-R, CARSTUK, DRCONTS, OUT-DZ, COMMFLT, FIRE, MRSMOKE, SHUNT, FLOOD
• Flood Return Ldg is 3 (not 2) – Turn this feature on to make the car return to the third landing from
the bottom if Flood Service is initiated. The default floor is the second floor from the bottom.

VIRGINIA CONTROLS, INC. MVFAC-3000 User Manual, Rev. 2.11 Page 109
• Flood Return Ldg is Top Ldg (not 2) – Turn this feature on to make the car return to the top landing
if Flood Service is initiated. The default floor is the second floor from the bottom.
• Flood overrides Independent, Attendant, Med Emerg – Turn this feature on to allow Flood Service
to override Independent Service, Attendant Operation and Medical Emergency Operation. If this
feature is not enabled, then the car will remain under the control of the operator if the Flood Service
input is energized.
• Flood overrides Shutdown (Low Oil, Rev. Phase, etc.) – Turn this feature on to allow Flood Service
to override shutdown functions that would normally return the car to the bottom landing. The car
will still not be able to run up, but Flood Service will remain in effect even though a shutdown
feature is in effect.
• Do Not Run on Flood and BORIS – Turn this feature on to prevent the car from running if Flood
Service and BORIS Battery Backup operation are initiated at the same time.
• Do Not Run Down Below Main on Flood and Shutdown – Turn this feature on to prevent the car
from running if it is at or below the Main Floor and the car is on Flood Service and Shutdown
Operation.
• Fire Service Overrides Flood Operation – Turn this feature on to allow Fire Service to override Flood
Service. The car will return to the Main Fire Floor, even if that is the bottom landing.
• Flood Operation Overrides Hall Fire Service – Turn this feature on to allow Flood Service to override
Fire Service, and cause the car to leave the bottom landing, even if that is the designated Fire
landing. If this feature is not set, then whichever feature (Fire Service or Flood Service) is initiated
first will take precedence.
• Disable Non-Shutdown Faults in the Fault Log – Turn on to prevent non-shutdown faults from being
logged in the fault log. This will prevent faults TDOPEN, TDCLOSE, TDOPN-R, TDCLO-R, CARSTUK,
DRCONTS, OUT-DZ, COMMFLT, FIRE, MRSMOKE, SHUNT, FLOOD from being logged.
• Enable Shunt Trip Feature – Turn on to enable the Shunt Trip feature. The input and output for this
feature must have been assigned for this feature to work properly. This feature can be turned off to
disable the Shunt Trip if it was supplied, but is not required. Shunt Trip operation can be
accomplished externally to the controller, if desired.
• Enable Rear Door Open Output – Turn on to enable the Rear Door Open output at point 8 on the
first output board.
• Enable RD (RearDoor) Output – Turn on to enable the RD output at point 8 on the first output
board. This is used with front and rear doors only.
• Enable 1UL - 4DL Hall Lantern Outputs – Turn on to enable specific Hall Lantern outputs. The
outputs for this feature must have been assigned for this feature to work properly.
• Enable Nudging Output – Turn on to enable the Nudging Output. This is not required for Nudging
Operation, as the Nudging Buzzer output is the only output specifically required. The output for this
feature must have been assigned for this feature to work properly.
• Enable CKO Output – Turn on to enable the CKO, Car Call Cutout Override, output. The output for
this feature must have been assigned for this feature to work properly.

VIRGINIA CONTROLS, INC. MVFAC-3000 User Manual, Rev. 2.11 Page 110
• Enable PI Blanking Fire Output – Turn on to use the Fire Light output as a Position Indicator Blanking
output.
• Enable Car To Lobby Input – Turn on to enable the Car To Lobby Shutdown inputs. The input for this
feature must have been assigned for this feature to work properly.
• Enable Park With Doors Open – Turn on to make the car park with the doors open at the Main
Landing.
• Enable Park With Doors Open at All Ldgs – Turn on to make the car park with the doors open at all
landings.
• Manual Reset on Redundancy and Door Zone Faults - Enable this bit feature to require Redundancy
and Door Zone faults to be reset manually. Cycling power will not reset those faults. This feature is
used in conjunction with the Latched Fault feature described above.
• Disable Reset at Intermediate Floors - Enable this bit feature to disable position resets at
intermediate floors. The car will still reset at terminal landings, based on the Door Zone input and
the Up or Down Slowdown inputs.
• Disable Fault Latch Feature – Turn this feature on to disable the feature that latches faults. Faults
are latched for compliance with the 2010 and later codes. If this feature is NOT turned on, then
faults must be reset by jumping the Fault Reset Input or by turning on Sw4 on the CPU Dip Sw block.
With this feature on, faults can be reset by cycling power or by cycling the Inspection Sw.

7.2.5.3 Features used on Duplex controllers only


• Elev A Select (A=ON, B=OFF) – Turn this feature on to enable
• Only this car serves Front Calls at Ldg 1 – Turn this feature on if the other car in the duplex does not
serve this opening, but this car does.
• Only this car serves Front Calls at Ldg 2 – Turn this feature on if the other car in the duplex does not
serve this opening, but this car does.
• Only this car serves Front Calls at Ldg 3 – Turn this feature on if the other car in the duplex does not
serve this opening, but this car does.
• Only this car serves Front Calls at Ldg 4 – Turn this feature on if the other car in the duplex does not
serve this opening, but this car does.
• Only this car serves Front Calls at Ldg 5 – Turn this feature on if the other car in the duplex does not
serve this opening, but this car does.
• Only this car serves Front Calls at Ldg 6 – Turn this feature on if the other car in the duplex does not
serve this opening, but this car does.
• Only this car serves Front Calls at Ldg 7 – Turn this feature on if the other car in the duplex does not
serve this opening, but this car does.
• Only this car serves Front Calls at Ldg 8 – Turn this feature on if the other car in the duplex does not
serve this opening, but this car does.

VIRGINIA CONTROLS, INC. MVFAC-3000 User Manual, Rev. 2.11 Page 111
• Only this car serves Rear Calls at Ldg 1 – Turn this feature on if the other car in the duplex does not
serve this opening, but this car does.
• Only this car serves Rear Calls at Ldg 2 – Turn this feature on if the other car in the duplex does not
serve this opening, but this car does.
• Only this car serves Rear Calls at Ldg 3 – Turn this feature on if the other car in the duplex does not
serve this opening, but this car does.
• Only this car serves Rear Calls at Ldg 4 – Turn this feature on if the other car in the duplex does not
serve this opening, but this car does.
• Only this car serves Rear Calls at Ldg 5 – Turn this feature on if the other car in the duplex does not
serve this opening, but this car does.
• Only this car serves Rear Calls at Ldg 6 – Turn this feature on if the other car in the duplex does not
serve this opening, but this car does.
• Only this car serves Rear Calls at Ldg 7 – Turn this feature on if the other car in the duplex does not
serve this opening, but this car does.
• Only this car serves Rear Calls at Ldg 8 – Turn this feature on if the other car in the duplex does not
serve this opening, but this car does.

7.2.5.4 Features used with Single Automatic Pushbutton controllers only


• Enable Single Button Collective Operation – Turn this feature on to enable Single Button Collective
operation instead of Single Automatic Pushbutton operation. Single Button Collective allows
multiple calls to be entered, with calls being answered in sequence as the car reaches them. Single
Automatic Pushbutton operation only allows one calls at a time.
• Enable Door Auto Close – Turn this feature on to enable the Automatic Door Close outputs. The
Door Close outputs and the appropriate external interface circuits for the Door Operator must be
provided for this feature to work. Unless additional features affecting the Door Close output are
energized, the Automatic Door Close output will be energized on Fire Service Phase 1 (Hall) to close
the doors and allow the car to return to the designated landing.
• Enable Door Auto Close from Car Buttons – Turn this feature on to allow the automatic Door Close
output to be energized when a Car Call Button is pressed.
• Enable Door Auto Close from Hall Buttons – Turn this feature on to allow the automatic Door Close
output to be energized when a Hall Call Button is pressed.
• Drop ESB with Door Open Limit – Turn this feature on to de-energize the ESB Stop Switch Bypass
output when the car has returned to the designated landing and opened the doors.
• Drop MF Output on Fire 2000 Code – Turn this feature on to allow the MF output to de-energize if
the car has returned to the designated fire landing, and is on shutdown. With 2000 Fire Code, the
doors should close under these circumstances.
• Enable Shunt with Door Open Limit – Turn this feature on to enable the Shunt Trip output when the
Door Open Limit indicates the doors are open. If this feature is disabled, the Shunt Trip output will
come on shortly after the car stops, even if the doors have not opened. This feature should only be
VIRGINIA CONTROLS, INC. MVFAC-3000 User Manual, Rev. 2.11 Page 112
enabled if there are power operated doors that also have a Door Open Limit signal connected to the
controller.
• Enable Timed Door Open Fault in Fault Log – Turn this feature on to enable the TDOPEN fault in the
Fault Log. This feature should only be enabled with power operated doors. If it is enabled with
manual doors, then a fault will be logged every time the car stops and the doors are not opened.
• Enable Door Reopen for Courion Doors – Turn this feature on to enable the ECH signal to the power
operated doors when the car is on Fire Service and the Car Fire Sw is turned from the Off position
back to Hold or On. This is used with Courion door operators to reopen the doors.

7.2.5.5 Features used with Triplex controllers only


• DISPATCH FAILURE CALLS
• Run to 1st Ldg on Dispatch Failure – Turn this feature on to make the car run to this landing if it
loses communication with the dispatcher. Set the desired calls to allow the cars to provide service
to the building if the dispatcher fails. The car will park with its doors open if it has no registered
calls, and the communication has failed.
• Run to 2nd Ldg on Dispatch Failure – Turn this feature on to make the car run to this landing if it
loses communication with the dispatcher.
• Run to 3rd Ldg on Dispatch Failure – Turn this feature on to make the car run to this landing if it
loses communication with the dispatcher.
• Run to 4th Ldg on Dispatch Failure – Turn this feature on to make the car run to this landing if it
loses communication with the dispatcher.
• Run to 5th Ldg on Dispatch Failure – Turn this feature on to make the car run to this landing if it
loses communication with the dispatcher.
• Run to 6th Ldg on Dispatch Failure – Turn this feature on to make the car run to this landing if it
loses communication with the dispatcher.
• Run to 7th Ldg on Dispatch Failure – Turn this feature on to make the car run to this landing if it
loses communication with the dispatcher.
• Run to 8th Ldg on Dispatch Failure – Turn this feature on to make the car run to this landing if it
loses communication with the dispatcher.

7.2.5.6 SPECIAL ADJUSTMENTS with ETSD/UCM BOARD, HSC


This section shows the standard definitions of any Custom Times and Features used for ETSD/UCM
Board and the High Speed Counter.
• HSC FAULT DELAY. (Value is in tenths of a second) This sets the delay before a High Speed Counter
fault is initiated. The car will shut down, and the cause of the fault will be logged.

• HSC START DELAY. (Value is in tenths of a second) This sets the delay after the start of a run before
the speed is checked for movement, and for proper direction.

VIRGINIA CONTROLS, INC. MVFAC-3000 User Manual, Rev. 2.11 Page 113
• ETS FAULT DELAY. (Value is in tenths of a second) This sets the delay before an Emergency Terminal
Speed fault is initiated. The car will shut down, and the cause of the fault will be logged.
• UCM FAULT DELAY. (Value is in tenths of a second) This sets the delay before an ETSD/UCM
Monitoring Fault is logged. It should be set long enough to prevent nuisance faults.
• 1FR HOLD DELAY. (Value is in tenths of a second) This sets the delay to hold the 1FR output when
the car is running full speed and slows down. It allows the car to pass the leveling zone of the
previous floor, so that it stops at the correct floor.

• ENABLE ETSD/UCM BOARD. Enable this bit feature when the ETSD/UCM Board is used. It enables
the Rope Brake check and Redundancy Faults used with the ETSD/UCM Board.
• DISABLE UCM BOARD REDUNDANCY FAULTS. Enable this bit feature to disable Redundancy Faults
from the UCM Board.
• ENABLE HIGH SPEED COUNTER. Enable this bit feature when using an external PLC with a High
Speed Counter. This can be turned off temporarily during setup to disable HSC faults.
• ENABLE EMERGENCY TERMINAL SLOWDOWNS (ETS). Enable this bit feature when using an ETS
system with the ETSD/UCM Board.
• ENABLE ONE AND TWO FLOOR RUN SPEEDS. Enable this bit feature when a separate speed is
provided for One Floor Runs.
• ENABLE LONG FLOOR FROM ? to ?. Enable one of these bit features when there is a long floor at the
specified floors. The car will then run full speed between those two floors.

7.2.6 Change Features


Use this selection to change the features described below. Each feature is either on (value of 255) or off
(value of 0). As you scroll through the features, the feature will be shown as enabled (ON) or disabled
(OFF). The feature may be changed by pressing Aux to select the desired operation (on/enabled or
off/disabled), then press Ent to store the value.

NOTE: The Password “911” is required to gain access to this menu selection, unless the
password has already been entered during another sequence.

Press Nxt to go to the next feature, without changing the current feature.
Press Prv to go to the previous feature, without changing the current feature.
Press Aux to toggle the feature between on/enabled or off/disabled.
(The keys 0 - 9 and . are not used)
Press Ent after selecting a new value to load the new value into memory. (The message “VALUE
SAVED!” is displayed for 1 second, to indicate the new value has been accepted.) If Nxt, Prv or Esc is
pressed after entering a new value, the new value will NOT be stored in memory.
VIRGINIA CONTROLS, INC. MVFAC-3000 User Manual, Rev. 2.11 Page 114
Press Esc to go back to the Setup Menu.

7.2.6.1 Description of Features


Refer to the sheet MH-3000 Settings in the schematic to see the settings and features provided for each
particular job. The following features are standard (All features are normally off/disabled, unless
otherwise specified):
• No Shortened Door Time - (Display shows "NO SHORTDOORTIME") Normally the door time will be
shortened by the Door Open Button/Safety Edge/Electric Eye/Infra-red Curtain. Enable this feature
to prevent these devices from shortening the door time. This is normally required in nursing
homes, where the passengers need more time to enter the car. The Door Close Button will still
shorten the door time.
• Timed Electric Eye Cutout - (Display shows "TIMED EYE CUTOUT") Enable this feature to allow the
Electric Eye input to be disabled after the preset time (see the setting above for the delay before
cutting out the Electric Eye). This feature is often provided in the Electric Eye unit itself.
• Door Nudging - (Display shows "DOOR NUDGING") Enable this feature to activate door close
nudging. Nudging will be initiated if a call is registered and the doors have been prevented from
closing for the preset Door Nudging time. The Electric Eye will be disabled, the Nudging Buzzer will
come on, and the Nudging Output will come on if the Electric Eye input is energized. This means the
door will only close at slow speed if the Electric Eye is blocked.

NOTE: Door Nudging operation requires an optional Nudging Buzzer output and
Reduced Speed Door Closing output.
• One Stroke Down Lanterns - (Display shows "1 STROKE DN LANT") The lanterns are normally
provided with two strokes for the down direction. Enable this feature to provide only one stroke for
the down direction.
• Slow Speed on Inspection - (Display shows "SLOW ON INSPECT") Enable this feature to run slow
speed on Inspection. This is normally required if the car speed is 125fpm or above.
• Proximity Detector - (Display shows "PROXIMITY DETECT") Enable this feature if a Proximity
Detector (such as an infra-red curtain) is used. Enabling this feature will cause the Safety Edge input
to be disabled on Fire Service, and the Door Nudging feature to be initiated while the doors are
closing on Fire Service. The Proximity Detector may be connected to the Safety Edge Input or the
Electric Eye Input, as desired. (The Electric Eye Input is subject to the Timed Electric Eye Cutout and
Nudging, whereas the Safety Edge Input is not.)

NOTE: Door Nudging operation requires an optional Nudging Buzzer output and
Reduced Speed Door Closing output.

• Short Floor - (Display shows "SHORT FLOORS") The Short Floor selection applies to installations with
Floor Switches or Pulsing Switches where the floor height is less than twice the slowdown distance,
but more than the slowdown distance plus the leveling zone. If Floor Switches are used, then the
Short Floor Setting should be enabled if the Floor Switches overlap at any floor. If Pulsing Switches
are used, then the Short Floor Setting should be enabled if the top of any Up target is BELOW the
bottom of the Down target for the floor below. With Floor Switches or a Pulsing Selector, if the

VIRGINIA CONTROLS, INC. MVFAC-3000 User Manual, Rev. 2.11 Page 115
slowdown overlaps the leveling zone of the adjacent floor, then special short floor circuitry is
required, and this setting will not normally apply. (Check for specific instructions for the job.)
• Enable Homing - (Display shows "ENABLE HOMING" on Simplex, or "HOME #2 TO MAIN" on Duplex)
Enable this feature to enable the homing feature on a Simplex. This will cause the car to home to
the Home Landing, when it has been idle for the adjustable Homing delay time.

NOTE: On a Duplex, one car will always home to the Dispatch Main Landing, and, if
this feature is set, then the FREE car will also home to the Dispatch Main Landing.
• Enable Free Car Homing (Duplex Only) - (Display shows "HOME TO HI ZONE") Enable this feature to
home the free car to the Upper Home Landing. If this is not set, then the car will remain where it
last stopped.
Some installations require specific settings or features that are not included in the standard program. In
this case, a separate sheet (or sheets) will be provided that describe the operation of these settings or
features, and what the factory default settings are.

7.2.7 Show Fault Log


This selection is the same as the Show Fault Log in the Run Mode section. The screen shows the fault
log, which consists of the last 63 faults and events recorded by the controller. The controller will not log
faults in the Setup Mode, but existing faults can be viewed.
Refer to the descriptions in the Show Fault Log section in the Run Mode for a full description of the
operation when viewing this screen, and for a description of the fault codes displayed.

7.2.8 Show Internal Memory


This selection is the same as the Show Internal Memory in the Run Mode section. The screen shows the
contents of the internal memory. This can be used to check the status of internal registers, to show the
operation of the system. Keep in mind that in the Setup Mode, the car is stopped, and all Inputs and
Outputs are off.
If the password has not been entered in another screen, then when this screen is selected, the
“Password Entry” screen will be displayed. If the password (“911”) is entered correctly, then the internal
memory can be changed. If it is not entered correctly, then the memory can still be viewed, but cannot
be changed.
Refer to the descriptions in the Show Internal Memory section in the Run Mode for a full description of
the operation when viewing this screen.

7.2.9 Set the Time


This screen allows the real time clock to be set up. When this selection is made, the current time is
displayed, showing the time in 24hour format, and the month, date, and year.

CURRENT TIME
12:22 11/13/01

If these are correct, then press Esc to return to the Setup Menu.
VIRGINIA CONTROLS, INC. MVFAC-3000 User Manual, Rev. 2.11 Page 116
If you want to change the time and/or date, then press any other key to continue with the next menu
item.
You will be prompted to enter the year (00-99), month (1-12), date (1-31), hour (0-23), and minute (0-
59).

ENTER YEAR 00-99


01

In each case, press Ent to accept the current value, or enter the correct value then press Ent.
If an incorrect value is entered, just enter the correct value again, and press Ent. If you press Esc during
this sequence, then the time and date will not be updated, and the display will return to the setup menu.
After all the data has been entered, the screen will display the new time and date, with the prompt
“Enter to accept”.

ENTER TO ACCEPT
12:23 11/13/01

Press Ent to accept the values. At this point the new time and date will be accepted, and the seconds
value will be set to zero. If you press Esc, then you will return to the setup menu without entering the
new time and date.
The battery is required to keep the real time clock running when power is turned off. Consequently, the
real time clock will need to be reset when the battery is changed.

7.2.10 Enter Password


A common password is provided for all controllers. This common password is "911". The password is
required when changing a setting (such as Door Time, Fire Return Landing, etc.) or a feature (such as Fire
Service Code, Front and Rear Door selections, etc.).
The password can be entered from the Setup Menu, as described below. Each time the Setup Menu is
entered, the password access is cleared, so the password must be entered again. If the password is
required for a menu item, a “Password Entry” screen will be displayed. Just press "911" then Ent to
access the menu item.
From the “Enter Password” menu item, press Ent to show the “Password Entry” screen.
Enter the password, “911”, then press Ent.
A message will briefly be displayed indicating whether the password was correct or not.
The display will then move back to the Setup Menu.
If the password has been successfully entered, and it is desired to restore password protection, so that
the password must be re-entered to gain access to the protected menu items, select the "Enter
Password" menu item and enter an incorrect password. Password protection is also restored whenever
the controller goes from the Run Mode to the Setup Mode.

VIRGINIA CONTROLS, INC. MVFAC-3000 User Manual, Rev. 2.11 Page 117
The password can be entered by pressing the 7 key when the display is activated from the blank screen
(after a power cycle), or when the "VA.CONTROLS" banner is displayed (after pressings Esc from the Run
Mode menus). This allows the password to be entered without stopping the controller.
The password can be given to all authorized personnel, which is those who would need to change
settings or features on the controller.

WARNING: It is recommended that the password NOT be written on the prints, or


controller itself, as this would allow anyone to access settings and features that could
cause damage to personnel or equipment.

WARNING: Use great care in changing settings and features, as this may cause
unexpected operation. Make sure you understand the consequences of any changes
before making them.

7.2.11 Test I/O Boards


This selection allows specific outputs to be turned on as desired, so that they can be tested for proper
operation.
This selection is password protected. The password must be entered each time this menu item is
selected, even if the password has been correctly entered before. The generic password "911" may be
used. This prevents unauthorized personnel from activating this feature, and also prevents accidentally
entering this feature.
After pressing Ent to select this item, enter the password “911” and then press Ent.
The LCD screen will display "'Ent' = START TEST, OTHER KEY = QUIT". Press the Ent key to start the test
feature, or press any other key to return to the setup menu.

WARNING: When the test feature is activated, outputs may be turned on that may
cause the car to move, the doors to operate and other signals to come on. It is the
operator’s responsibility to make sure an unsafe condition does not exist. Take any
and all the necessary precautions to prevent a dangerous situation.
This could include:
• unplugging the terminal blocks on the output boards (this is strongly recommended),
• removing the fuses in the output circuits,
• opening the appropriate safety devices.
While the test feature is activated, each input that is on will turn on the corresponding output on the
same board (Input Point 1 will turn on Output Point 1; Input Point 2 will turn on Output Point 2 etc.).
This allows the inputs and outputs to be tested by jumping the desired input on, and verifying that the
proper output comes on. Note: The outputs are updated once every tenth of a second, so there may be
a slight delay in turning on the output after the input has been energized.

VIRGINIA CONTROLS, INC. MVFAC-3000 User Manual, Rev. 2.11 Page 118
WARNING: Be very careful when jumping the inputs on. Make sure you do not jump
to the common on the input terminal strips. This will blow a fuse, and could damage
the input board components. The input commons are the first and sixth terminals
from the left on the input terminal strip (see the schematic).
While the outputs are being tested, a meter can be used to verify that each output is actually coming on.
The test will be stopped, and the outputs turned off, when any key is pressed.

VIRGINIA CONTROLS, INC. MVFAC-3000 User Manual, Rev. 2.11 Page 119
8. Controller Nomenclature
The symbols listed below are typical symbols. Refer to the schematic for all relays and contactors
actually used on a particular job. The function of the relay or contactor will be show on the schematic by
its coil.
SYMBOL DESCRIPTION
AF, BF, CF, etc. BINARY CODED FLOOR POSITION RELAYS
BK1, BK2 BRAKE CONTACTORS
C DOOR CLOSE RELAY
D / D1-2, DX DOWN RUN REVERSING CONTACTOR / RELAYS
DC DOOR CLOSED RELAY
DL DOWN LEVEL RELAY
DOLX DOOR CHECK RELAY
DZ DOOR ZONE RELAY
ES, EST EMERGENCY STOP SWITCH RELAY
ESB EMERGENCY STOP SWITCH BY-PASS RELAY
FL, FLR FIELD LOSS RELAYS
FS, FSX FAST SPEED RUN CONTACTOR OR RELAYS
IAS, IAX INSPECTION ACCESS RELAY
INS INSPECTION RELAY
LC LEVELING CUTOUT RELAY
LV LEVELING RELAY
MG, MG1-2 MOTOR GENERATOR CONTACTOR, RELAYS
N DOOR CLOSE NUDGING RELAY
O DOOR OPEN RELAY (IN MODSS ON TOP OF THE CAR, IF USED)
OSF OVERSPEED FAULT RELAY
P, PP, PX POTENTIAL CONTACTOR, RELAY
RDY DRIVE READY TO RUN RELAY
RU MOTOR RUN CONTACTOR (WYE-DELTA START)
RUX / RUXP M.G. SET RUNNING CONTACTOR / TIMER
SAF1-2 SAFETY CIRCUIT RELAYS
STR MOTOR START CONTACTOR (WYE-DELTA START)
SU SUICIDE CONTACTOR
TRU WYE-DELTA MOTOR RUN RELAY (WYE-DELTA START)
TRUP WYE-DELTA MOTOR RUN TIMER (WYE-DELTA START)
U / U1-2, UX UP RUN REVERSING CONTACTOR / RELAYS
UD CAR RUNNING RELAY
UDT, UDTX CAR RUNNING DELAY DROP OUT RELAYS
UL UP LEVEL RELAY
VR VOLTAGE RELAY (OPTIONAL)

VIRGINIA CONTROLS, INC. MVFAC-3000 User Manual, Rev. 2.11 Page 120
9. Parts List
ITEM DESCRIPTION MANUFACTURER PART NO

RELAYS
A1 4PDT, 120VAC, PLUG-IN RELAY Idec or equivalent RU4S-A110
A2 4PDT, 110VDC, PLUG-IN RELAY Idec or equivalent RU4S-D110
A3 SURFACE MOUNT RELAY SOCKET P&B 27E894
A4 TIMER, 0-102.3 SECONDS AIRTRONICS THCU102S3E
A5 3PDT, 120VAC, PLUG-IN RELAY P&B or equivalent KUP-14A35

CONTACTORS, STARTERS, OVERLOAD


B1 Y-D REVERSING CONTACTOR (NEMA) SQD S__0__V02
B2 3 POLE THERMAL OVERLOAD (NEMA) SQD SE0____
B3 ACROSS-THE-LINE STARTER (NEMA) SQD S__0__V02
B4 HEATERS FOR 3 POLE OVERLOAD (NEMA) SQD (Types: B, CC, DD)
B5 Y-D REVERSING CONTACTOR (IEC) SQD/Telemechaniqu LC2-____G6
e
B6 ACROSS-THE-LINE STARTER (IEC) SQD/Telemechaniqu LC1-____G6
e
B7 3 POLE OVERLOAD (IEC) SQD/Telemechaniqu LR____
e

TRANSFORMERS, FUSES, TERMINALS


C1 460-230-208/230-115, (600VA & 300VA) SQD 9070K____D48
C2 250V INSTANTANEOUS FUSE BUSSMAN TYPE BAF
C3 250V FUSEHOLDER CURTIS PW1F
C4 TRACK FOR 250V FUSEHOLDERS CURTIS SW192
C5 3 POLE TERMINAL, 600V, 50AMP CURTIS 3PSWT
C6 MOUNTING TRACK FOR TERMINALS CURTIS SW192

MICRO-PROCESSOR
D1 MICROPROCESSOR CPU BOARD V.C. MH3000-CPU
D2 16-IN/16-OUTPUT MODULE V.C. MH3000-16IO
D3 KEYPAD V.C. MH3000-KEYPAD
D4 LCD SCREEN V.C. MH3000-LCD
D5 CPU BATTERY PANASONIC CR2032

MISCELLANEOUS COMPONENTS & HARDWARE


E1 PRINTED CIRCUIT BOARD V.C. MH-4
E2 PHASE MONITOR (208V / 230V / 460V) SSAC TVM____A100.5S3S
E3 1"W X 2"H DUCT TAYLOR 91020
E4 1"W X 3"H DUCT TAYLOR 91030
E5 1"W DUCT COVER TAYLOR 99010
E6 1"W DUCT MOUNTING CLIPS TAYLOR 08010
E7 CONTROLLER ENCLOSURE V.C. (SIZE)
VIRGINIA CONTROLS, INC. MVFAC-3000 User Manual, Rev. 2.11 Page 121
E8 STARTER ENCLOSURE V.C. (SIZE)

RESISTORS - PART # IS RESISTANCE & WATTAGE - SEE


THE SCHEMATIC
F1 POWER PANEL RESISTOR VALUES RESISTORS, INC.
375WATT= 4, 8, 10, 25 OHMS
200WATT= 50, 100, 250, 500, 1000, 1500, 2500
OHMS
F2 RELAY PANEL RESISTOR VALUES RESISTORS, INC.
25 WATT = 1.5K OHMS
10 WATT = 12K, 350 OHMS
2 WATT = 1.5K OHMS
F3 DYNAMIC BRAKING RESISTOR ASSEMBLY SEE SCHEMATIC

MISCELLANEOUS
G1 NEONS, ON RELAY PANEL I.D.I. 1030
G2 VARISTORS (SEE SCHEMATIC) G.E. V150LA2
G3 PUSHBUTTON, ON RELAY PANEL ARROW-HART 80511E
G4 TOGGLE SWITCH, ON RELAY PANEL ARROW-HART 82601
G5 10 POSITION SELECTOR SWITCH CENTRALAB PA1001

All parts are commercially available from the manufacturer, or from Virginia Controls Inc. (ask for the
Parts Department or send an email to parts@vacontrols.com). Parts are subject to change without
notice. Consult Virginia Controls, Inc., for current pricing information. Non-standard material is
identified on the schematic.

VIRGINIA CONTROLS, INC. MVFAC-3000 User Manual, Rev. 2.11 Page 122
10. Troubleshooting Suggestions
Troubleshooting is similar to any other controller, and has several features to speed up determining the
cause of any problem. No special knowledge of the operation of the microprocessor is required to be
able to troubleshoot it.
A safety relay interface is provided to prevent dangerous operation due to a failure of the
microprocessor. It is possible that the microprocessor may turn on an output point, yet the field safety
switches may prevent the associated device from energizing.
For example, if the up run output energizes, but the up normal switch is open, then the up run relays will
not energize.

10.1 Locating Faults


Once the system has been installed, and is running properly, the most common problem will be the
failure of an external device. The first step in locating the cause is to determine whether the fault is in
the microprocessor or whether it is in the external wiring.
For example, if a position indicator light is not lit, check the output module for the appropriate output
point to determine if the microprocessor is trying to turn the light on or not. If the output light is on,
then confirm that there is voltage at the module terminal. If there is voltage at the module terminal,
then the problem is external to the microprocessor. It could be in the wiring to the position indicator,
or perhaps the position indicator light has burned out. Similarly with input points, check that the input
module light is on, that there is power at the terminal, and if not then the problem is external.
If it is determined that the problem is with the microprocessor, then the next step is to determine if the
problem is in the hardware or the software. Using the keypad, press Nxt to display the "Show I/O
Status" menu item. Press Ent. The screen will show the address on the top line and the I/O status on
the bottom line. Press Nxt or Prv to show the desired I/O address, and see if the CPU is responding by
showing the correct status of the I/O points. If it is not, then the fault is probably with the I/O hardware;
if it is on, then the fault is probably with the software.
If an input or output board fails, it may be possible to temporarily replace that defective board with
another board that is used for non-essential functions (such as call register lights), thus providing
elevator service while a replacement board is being obtained. See the section on I/O Board
Replacement for further information.
If this does not correct the problem, the power supply or the CPU module could be faulty. If the CPU
fails, it will probably stop flashing LED D5. The CPU and I/O modules can be affected by high transient
surges in the power supply, such as the building being hit by lightning. This may damage the CPU, or
alter the contents of the program. Proper grounding will protect the controller from most of these
problems.

VIRGINIA CONTROLS, INC. MVFAC-3000 User Manual, Rev. 2.11 Page 123
10.1.1 Troubleshooting I/O Board Communication Problems
If the IOFAULT error message is shown on the Status Screen, there are several ways to determine which
board is causing the fault.
The communication light on the I/O board will usually indicate the problem. The normal status is for
that light to blink once. If it blinks 2 or more times then the board is detecting an error in the
communication it is receiving, as described in the section on I/O Boards, Board Status LED.
Additionally the CPU can be monitored to check its communication with the I/O boards.
Address 0051 and 0052 should both be 00, but will show a code corresponding to the board that is not
communicating with the CPU. Using the SHOW INT MEMORY screen, navigate to address 0050, then
check the value in 0051 (refer to the example shown below with address 0051 in bold).

0050 04 03 03 04
0054 00 00 00 00

In the example shown here, a fault code “03” is seen in 0051. This indicates there is a communication
problem with boards 1 and 2. Refer to the chart below for the codes for the board faults. The top
section shows the boards for the right code number, and the bottom section shows the codes for the left
code number.

Right
Number x0 x1 x2 x3 x4 x5 x6 x7 x8 x9 xA xB xC xD xE xF
Board1 OK Fault OK Fault OK Fault OK Fault OK Fault OK Fault OK Fault OK Fault
Board2 OK OK Fault Fault OK OK Fault Fault OK OK Fault Fault OK OK Fault Fault
Board3 OK OK OK OK Fault Fault Fault Fault OK OK OK OK Fault Fault Fault Fault
Board4 OK OK OK OK OK OK OK OK Fault Fault Fault Fault Fault Fault Fault Fault
Left
Number 0x 1x 2x 3x 4x 5x 6x 7x 8x 9x Ax Bx Cx Dx Ex Fx
Board5 OK Fault OK Fault OK Fault OK Fault OK Fault OK Fault OK Fault OK Fault
Board6 OK OK Fault Fault OK OK Fault Fault OK OK Fault Fault OK OK Fault Fault
Board7 OK OK OK OK Fault Fault Fault Fault OK OK OK OK Fault Fault Fault Fault
Board8 OK OK OK OK OK OK OK OK Fault Fault Fault Fault Fault Fault Fault Fault

Also addresses 0048 to 004F show the communication attempts to each of the boards. Refer to the
sample shown below.

0048 F* F* 0* 00
004C 00 00 00 00

If a board is not communicating properly, the left number corresponding to the board will be “F” or “E”.
The right number will change very quickly. If the board is communicating properly, the left number will
be “0” or “1”, and the right number will be changing quickly. If the CPU is not attempting to
communicate to a board, the value will stay at “00”. In the example above, the CPU is attempting to
communicate with boards 1, 2, and 3. Board 3 is communicating properly, but boards 1 and 2 are not.
The “*” in the example above indicate numbers that are changing quickly.
Address 051E counts the number of failed IO board communication attempts. This should be 0, as
shown in the sample below.
VIRGINIA CONTROLS, INC. MVFAC-3000 User Manual, Rev. 2.11 Page 124
051C 2E E0 00 00
0520 00 00 00 00

If there are intermittent problems, such as noise causing communication errors, then this value will
gradually increase. Check the addressing of the boards, and that all cables are fitted properly. Also
check the grounding of the controller. See the section Show Internal Memory for instructions on
viewing internal memory addresses.

10.2 I/O Board Replacement


WARNING: When replacing a board, the Address Switch setting on the new board
must be set to match the old board.
To replace an I/O board, TURN THE POWER OFF. Unplug all the terminal blocks at the top and bottom of
the board. Unplug the Power Connector and the I/O Bus Connectors. Remove the screws holding the
board in place. Install the new module by reversing the above steps.

10.3 Factory Assistance


IMPORTANT: IF TROUBLESHOOTING ASSISTANCE IS REQUIRED FROM VIRGINIA CONTROLS, GET THE
FOLLOWING INFORMATION BEFORE CALLING (ADDITIONAL TROUBLESHOOTING INSTRUCTIONS MAY BE
GIVEN, DEPENDING ON THE NATURE OF THE PROBLEM):
• THE VIRGINIA CONTROLS DRAWING NUMBER (located at the bottom right of the schematic).
• AN EXACT DESCRIPTION OF THE PROBLEM.
• THE STATUS OF ALL THE INPUT AND OUTPUT POINTS.
• THE STATUS OF THE LIGHTS ON THE CPU.

VIRGINIA CONTROLS, INC. MVFAC-3000 User Manual, Rev. 2.11 Page 125
10.4 Changes for Program Revisions
The following section lists the changes that are included in program revision.

10.4.1 Program Revision 3B


Approximate Date of implementation – 05/1/2005
The following changes were incorporated:
• Redundancy Faults were given specific Fault Codes and Status Screen Messages.
• The Fault Status Codes in the Fault Log were customized for Redundancy Faults.
• The Rollover Fault code was modified so that consecutive Rollovers would be combined into one
fault, with the number of fault free days shown on the lower right.

10.4.2 Program Revision 3C


Approximate Date of implementation – 05/1/2008
The following changes were incorporated:
• Redundancy Fault Codes were added for latest Redundancy Faults, as used on Program Versions
VA3C and VS3C. Additional tables were added for these new Fault Codes

VIRGINIA CONTROLS, INC. MVFAC-3000 User Manual, Rev. 2.11 Page 126
11. Controller Maintenance
WARNING: MAKE SURE THE POWER IS OFF BEFORE CONNECTING OR DISCONNECTING
ANY CONNECTORS, ADDRESS JUMPERS OR CABLES ON THE CPU OR I/O BOARDS.

11.1 Periodic Maintenance


WARNING: Turn off the power before touching the terminals or wiring.
Check that all wires are tight, and properly located in the terminals. Make sure no stray stands of wire
are sticking out of the terminal strips.
Check the Motor Starter contacts and Door Operator contacts (if provided) for wear.
Make sure all relays are fully seated in their sockets.
If any varistors are provided in parallel with inductive loads (such as the Valve Solenoids or Motor
Starter) check that they are physically sound. Look for signs of burn marks. Replace it if it looks
damaged.
Check the CPU battery. This can be done by cycling the power, then checking to make sure the onboard
clock is still correct. To check the time, press Nxt until the display shows “Press ENTER to SHOW FAULT
LOG”. Then press Ent, then press . to show the current time. If the date had been set, and it now
shows the date as 01/01/00 then the battery is dead. Change the battery and set the time.
Keep the controller clean and dry. Power supplies and processor chips in particular should be keep clean
of dust and other debris. Keeping the machine room itself clean will help keep the controller clean.

11.2 Parts Replacement

11.2.1 CPU Exchange


To swap out the CPU board:
1. Turn off the power to the controller.
2. Note the location of all cables and wires. It is recommended that all cables and wires be marked so
that they can be returned to the correct terminal or connector, and be oriented properly.
3. Unplug the incoming power wiring connector from the bottom left terminal block.
4. Unplug the duplex communication connector from the duplex connector (if used).
5. Unplug the I/O Bus Connector.
6. Remove the four screws holding the CPU board in place.
7. Remove the CPU board.
8. Install the new CPU board in the reverse order.
VIRGINIA CONTROLS, INC. MVFAC-3000 User Manual, Rev. 2.11 Page 127
11.2.2 EPROM Memory Chip Exchange
WARNING: IF YOU NEED TO CHANGE THE EPROM PROGRAM CHIP ON THE CPU
BOARD, MAKE SURE YOU READ THE INSTRUCTIONS AND KNOW EXACTLY HOW TO
INSTALL THE NEW CHIP. PLUGGING THE EPROM IN UPSIDE-DOWN MAY DAMAGE
YOUR CHIP. STATIC ELECTRICITY CAN DAMAGE THE EPROM, SO AVOID TOUCHING THE
PINS ON THE CHIP, AND GROUND YOURSELF (BY TOUCHING THE CONTROLLER
CABINET) BEFORE TOUCHING THE CHIP OR THE CONTROLLER. DO NOT EXPOSE THE
EPROM PROGRAM CHIP TO BRIGHT LIGHT, AND DO NOT REMOVE THE LABEL OVER
THE EPROM PROGRAM CHIP WINDOW.
To exchange the EPROM memory chip on the CPU board:
1. Turn off power to the controller.
2. Using a small screwdriver, or other appropriate tool, pry out the old EPROM chip by inserting the
screwdriver between the chip and its socket from the right side. Gradually work the chip out, trying
to avoid swinging it out, which would bend the pins at one end, but rather prying it straight out by
working the screwdriver under the chip.
3. Insert the new EPROM chip by orienting it properly, so that the notch is at the left, to match the
socket, and all the pins line up with the socket. LEAVE TWO EMPTY HOLES AT THE LEFT END OF THE
CHIP (the end next to the notch). It should not be necessary to use force to insert the EPROM chip,
but apply slight sideways pressure to line up the rows of pins with the holes in the socket, if

Notch
EPROM Chip Positioning

necessary, then evenly press the EPROM chip into place.


4. Do not apply power until the orientation of the chip has been checked. Also verify that ALL pins are
properly in the socket, and that none of them have been bent out of place.

VIRGINIA CONTROLS, INC. MVFAC-3000 User Manual, Rev. 2.11 Page 128
11.2.3 Input/Output Board Exchange
To exchange on I/O board:
1. Change the Address Switches on the new I/O board to match the board it will replace.
2. Turn off the power to the controller.
3. Unplug all the removable I/O terminal strips from the top and bottom of the I/O board. It is not
usually necessary to mark the terminal blocks, since the wiring will normally hold them in the proper
place so that it is obvious which block goes where. If there is any doubt about their location, then
mark the terminal blocks to show where they should be re-installed.
4. Unplug the I/O Bus Connectors and power connector.
5. Remove the screws holding the I/O board in place.
6. Install the new I/O board by reversing the previous steps.

VIRGINIA CONTROLS, INC. MVFAC-3000 User Manual, Rev. 2.11 Page 129
12. Frequently Asked Questions
Suggestions for other Frequently Asked Questions are welcomed. Please submit them via email to
eng@vacontrols.com.

12.1 Questions on Field Devices

12.2 Questions on Field Devices


Q. Are the Reset Targets necessary when using a pulsing selector?
Yes.
The reset targets are required at the terminal landings, as shown on the car top selector installation
sheet, to establish or reset the floor position at the terminal landings.

Q. Why are Two Position Indicators energized at the same time?


With Floor Switches, if there is an overlap of the slowdown targets, or a Floor Switch sticks on, then
when the car hits a new Floor Switch, all floors that have a Floor Switch input energized will be turned
on.
If the problem happens intermittently, it is probably caused by a sticking Floor Switch. If it happens
regularly at a particular floor, there is probably an overlap between Floor Switches. In this case, either
separate the Floor Switches (or targets) so there is no overlap, or turn on the "Short Floor" feature,
described above in the features section.

Q. The doors do not operate properly on Fire Service


Check the Door Open and Door Close Limit Switches for proper operation. Most problems with Fire
Service are a result of one or both of these switches not operating properly. Also check to make sure the
correct Fire Code has been selected in the Adjustable Settings and Features. Refer to the schematic
adjustment sheet.

VIRGINIA CONTROLS, INC. MVFAC-3000 User Manual, Rev. 2.11 Page 130
12.3 Questions on the Controller
Q. How Do I Reset All Settings and Features Back to the Original Values?
1. With the controller running normally, press Nxt repeatedly until the menu item shows "GO TO
SETUP MENU".
2. Press Ent. The display will show a warning message. Make sure the car is stopped before
continuing.
3. Press Ent. The display will show you have entered the Setup Mode, then display the "RESET
SETTINGS" menu item.
4. Press Ent to reset all settings to the factory defaults.
5. Press Esc to return the controller to normal operation.

NOTE: If the program is a standard program, then the settings for the specific job must
be re-entered.

Q. How do I determine if I have a standard program?


1. Go to the Banner screen, by pressing Esc until the top line of the display shows “VA.CONTROLS” at
the left.
2. If the text on the lower left is the job number, then the program is NOT standard. It has been set up
for the particular job.
3. If the text on the lower left starts with letters (such as “E” or “Q”) then the program is standard. If a
factory reset is performed, the standard default values will be loaded. Check the schematic for the
particular values for your installation, and change the values as required.

Q. How do I check the current values of the settings and features?


4. Go to the Setup Menu.
5. Select the menu item "Change Settings", and press Ent, then enter the password, “911”.
6. Scroll through the settings by pressing Nxt. The settings will not be changed unless a new value is
entered and then Ent is pressed.
7. Press Esc then Nxt to go to the "Change Features" menu item.
8. Press Ent, then enter the password, and press Ent.
9. Press Nxt to scroll through the features. The features will not be changed unless you press Aux then
Ent.
10. Press Esc twice to return to normal operation (Run Mode).

VIRGINIA CONTROLS, INC. MVFAC-3000 User Manual, Rev. 2.11 Page 131
Q. Why is the LCD Display blank?
The LCD Display goes blank after the CPU resets if S2 switch 1 is in the OFF position. This will happen
when the power to the CPU is cycled, or when the Reset Button on the CPU board is pressed.
Press any key to activate the screen.
If the screen does not activate, the problem could be with the Keypad (momentarily touch pins 1 and 8
on the keypad connector to simulate pushing a key) or the CPU (check that LED D5 is flashing), or the
LCD Display.
Q. Why is the Fire Audible Visible output On but the car is not on Fire Service?
Switch 3 on the CPU Slide Switch S2 is in the ON position.
This switch defeats the Redundancy Faults. This may be useful during initial installation, and the Fire
Audible Visible is turned on to remind you to turn off this defeat after installation. Slide the switch down
to turn it off.

VIRGINIA CONTROLS, INC. MVFAC-3000 User Manual, Rev. 2.11 Page 132
13. Drive Special Instructions
Refer to the job schematic for connection information.
The drive has been set up and tested, so only minor adjustments should be necessary.
If the motor data is different from that supplied to Virginia Controls (motor horsepower, currents,
voltages, etc.) then consult with Virginia Controls before powering up the system.
Refer to the Parameter sheet in the schematic for the actual settings for each particular job.
For additional explanations of drive parameters, see the Magnetek Technical Manual.
Customer should record any parameter changes and keep this information in a safe place for future
reference.

13.1 Over Speed Test


It is recommended that the over speed test be done with the car on "Inspection". This allows complete
control of the car at all times. When the test is complete, restore all parameters back to their original
values.
Refer to the Parameter sheet in the schematic for additional details.

14. ETSD Monitoring System Testing


NOTE: When performing these tests, especially while the elevator is on Normal
operation, first verify that the car is empty and that Hall Calls are cut out.

14.1 UCM System Testing

14.1.1 When equipped for Rope Brake Operation


1. Power down the system.
2. Remove the controller wire at Input DZ, “Door Zone”, on the ETSD Board. Clip this controller
wire to a short wire temporarily installed in its place.
3. Power up the system.
4. Run the elevator on Automatic to the top landing.

NOTE: Be sure to take the necessary steps to prevent anyone from boarding the
elevator during the test.

VIRGINIA CONTROLS, INC. MVFAC-3000 User Manual, Rev. 2.11 Page 133
5. As the elevator opens its doors at the top landing, remove the controller wire clipped to the
temporary wire at Input DZ on the ETSD Board.
6. The UCM System will cause the “UCM TRIP” LED to light, and the Rope Brake to set.
7. Power down the system.
8. Restore the controller wiring at Input DZ.
9. Power up and briefly touch a wire from controller TB-1 (120VAC Hot) to Input SHTDFT on the
ETSD Board to reset the UCM System and the Rope Brake.

14.1.2 When equipped for Emergency Brake Operation


1. Run the elevator on Automatic to top landing.

NOTE: Be sure to take the necessary steps to prevent anyone from boarding the
elevator during the test.
2. Power down the system with the doors closed.
3. Remove the field wires at controller terminal blocks: 21 & 22, Up & Down Leveling Switches.
Temporarily place a short wire in TB-22.
4. Power up the system.
5. Briefly touch a wire from controller TB-1 (120VAC Hot) to controller TB-27, Door Open Button
Input, to open the elevator doors.
6. With the doors open, clip the wire from controller TB-1 to the short wire just installed at
controller TB-22, Down Level Switch.
7. The elevator will level down slowly until it rides out of the Door Zone.
8. UCM System will cause the “UCM TRIP” LED to light, and the Emergency Brake to set.
9. Power down the system.
10. Restore the field wires at controller terminal blocks: 21 & 22, Up & Down Leveling Switches.
11. Power up the system.
12. Touch a wire from TB-1 of the controller to Input SHTDFT of the ETSD Board to reset the UCM
System and Rope Brake.
13. The elevator will close its door and relevel back to the floor.

14.2 O-S System Testing


1. With car at mid-hatch, place elevator on Inspection Operation from controller.
2. Power down the system.

VIRGINIA CONTROLS, INC. MVFAC-3000 User Manual, Rev. 2.11 Page 134
3. Install a jumper from controller TB-1 to controller Input or TB: “SHTDFT”. See the controller
drawings for the location of this input or terminal.
4. Power up the system.
5. Set the drive for an Inspection Speed of 175FPM and run car.
6. The O-S System will fault causing the “O-S TRIP” LED to light, and stop the car.
7. Power down the system.
8. Remove the jumper from controller TB-1 to Input or TB: “SHTDFT”.
9. Power up the system.
10. Restore the drive to its original Inspection Speed.
11. Use the “O-S RESET” Push Button on the ETSD Board to reset the O-S System.
12. Restore elevator to Normal Operation.

14.3 ETSD System Testing


1. With car at mid-hatch on Normal Operation, and at floor level, power down the system.
2. Install a jumper from controller TB-1 to controller Input or TB: “SHTDFT”. See the controller
drawings for the location of this input or terminal.
3. Remove the field wire from controller TB-31X, Up ETS Switch, and clip this field wire to a short
piece of wire temporarily installed in its place.
4. Power up the system.
5. Set a Car Call in the Up direction that causes the car to run multiple floors at contract speed.
6. Monitor car speed by observing Relay Output LED’s: “EX1 & EX2”.
7. When these LED’s go out, remove the field wire clipped to TB-31X.
8. The ETSD System will fault causing the “ETSD TRIP” LED to light, and stop the car.
9. Power down the system.
10. Remove the jumper from controller TB-1 to Input or TB: “SHTDFT”.
11. Restore the field wire at controller TB-31X, Up ETS Switch.
12. Power up the system.
13. Use the “ETSD RESET” Push Button on the ETSD Board to reset ETSD System.
14. The elevator will level to a landing on Normal Operation.
15. If desired, repeat steps in Down Direction using TB-32X, the Down ETS Switch.

VIRGINIA CONTROLS, INC. MVFAC-3000 User Manual, Rev. 2.11 Page 135
INDEX

A F
Access · 13 Factory Reset · 18
Addressing · 54 Failure Timers · 21
Adjustable Features · 22 Fault Code · 80
Fault Log · 78, 79, 80, 86, 90, 100, 116
Features · 18, 22, 100, 104, 106, 114, 115, 130,
B 131
Fire Service · 13, 17, 21, 23, 24, 47, 82, 83, 97,
Banner Screen · 77
106, 109, 115, 117, 130
Battery · 46, 127
Flood · 109, 110
Bit Features · 79, 80, 104, 107

C G
Grounding · 9, 11, 14, 16
Calls · 20, 23, 47, 97
Car Start · 23
CAUTION · 8, 103 H
Code · 80, 103, 104, 106, 117, 130
Communication · 24, 49, 56, 82, 124 Hexadecimal Conversion Table · 93
CPU · 11, 14, 19, 24, 41, 45, 46, 47, 48, 49, 56, Historical Log · 90
85, 99, 121, 123, 125, 127, 132 Homing · 24, 106, 116
Humidity · 10
D
I
Diagnostic · 99
Display · 50, 52, 103, 105, 115, 116, 132 I/O Status · 78
Door Operation · 20 Independent · 19, 24, 47, 82, 96, 97, 106
Drive · 15, 17, 21, 84, 96 Inspection · 17, 18, 21, 24, 47, 82, 96, 97, 102,
Duplex · 23, 24, 48, 49, 82, 116 105, 115, 133
Internal Memory · 48, 90, 93, 94, 95, 99, 100,
116
E IO Fault · 98, 124
Emergency Terminal Stopping Device · 34, 59,
66 J
EPROM · 8, 19, 41, 47, 101, 128
ETSD · 25, 26, 27, 28, 29, 30, 31, 33, 34, 35, 36, Jumper · 58
59, 62, 63, 64, 65, 66, 67, 68, 69, 70, 71, 72,
73, 75, 133, 134, 135
ETSD Monitoring System · 25, 59
K
Keypad · 41, 50, 132

VIRGINIA CONTROLS, INC. MVFAC-3000 User Manual, Rev. 2.11 Page 136
L S
LED · 20, 21, 24, 47, 48, 49, 54, 55, 56, 90, 94, 99, S2 · 132
100, 123, 124, 132 S2 Slide Sw · 50, 51, 76
Selector · 12, 115
Settings · 18, 22, 100, 101, 102, 103, 104, 107,
M 115, 130, 131
Set-Up Mode · 99, 100
Maintenance · 127
Start-Up · 16
Status · 48, 52, 56, 76, 77, 78, 86, 95, 96, 99, 100,
N 123, 124
Stuck Button · 21
Next Car · 23 Switches · 12, 13, 56, 78, 82, 85, 97, 129, 130
Noise · 125 Leveling · 12, 13, 22, 82, 85, 97, 105, 129
NOTE · 8, 11, 13, 16, 19, 20, 21, 42, 48, 49, 79, Limit · 12, 13, 19, 81, 85, 86, 97, 98, 129, 130
81, 86, 94, 100, 102, 103, 105, 114, 131 Slowdown · 12, 13, 19, 85, 97, 129
Zone · 12, 13, 22, 83, 85, 87, 97, 98, 103, 129
O
T
O-S · 26, 27, 28, 32, 33, 36, 59, 64, 73
Over Speed · 28, 63 Temperature · 10
Over-Speed · 59, 63 Temporary · 17
Terminal Wiring · 55
Test · 118
P
Time · 46, 79, 81, 100, 116
Parts List · 121 Troubleshooting · 123, 124
Parts Replacement · 127
Password · 100, 102, 114, 116, 117 U
Position Indicators · 19
UCM · 26, 33, 36, 59, 60, 61, 62, 64, 65, 73
Unintended Car Movement · 26, 59, 60
R
Redundancy · 86, 96, 97, 108, 126 W
Reset Button · 48, 49, 76, 132
Revision · 126 WARNING · 8, 14, 16, 17, 23, 46, 47, 49, 55, 58,
Run Mode · 76, 77, 78, 90, 99, 100, 101, 103, 95, 100, 102, 118, 119, 127, 128
116, 117, 118, 131 Watchdog · 48
Running Timers · 21

VIRGINIA CONTROLS, INC. MVFAC-3000 User Manual, Rev. 2.11 Page 137

You might also like