VF-3000 Traction User Manual PDF
VF-3000 Traction User Manual PDF
VF-3000 Traction User Manual PDF
email: eng@vacontrols.com
website: www.vacontrols.com
Revision 2.11
Revision 3.02
VIRGINIA CONTROLS, INC. MVFAC-3000 User Manual, Rev. 2.11 Page 1
Table of Contents
6.5 Microprocessor..............................................................................................................................45
6.5.1 CPU ..................................................................................................................................................... 45
6.5.2 Input/Output Boards ........................................................................................................................... 53
6.5.3 I/O Board Connectors.......................................................................................................................... 56
WARNING: If you need to change the EPROM program chip on the CPU board, make
sure you read the instructions and know exactly how to install the new chip. Plugging
the EPROM chip in upside-down may damage the chip. Static electricity can damage
the EPROM, so avoid touching the pins on the chip, and ground yourself (by touching
the controller cabinet) before touching the chip or the controller. Do not expose the
EPROM program chip to bright light, and do not remove the label over the EPROM
program chip window.
WARNING: This equipment is designed and built to comply with ANSI A17.1, ASME
A17.5 and CAN/CSA B44.1 and must be installed by a qualified contractor. It is the
VIRGINIA CONTROLS, INC. MVFAC-3000 User Manual, Rev. 2.11 Page 8
responsibility of the contractor to make sure that the final installation complies with
all applicable local, state and national codes, and is installed safely.
WARNING: The 3 phase AC power supply to this equipment must come from a fused
disconnect switch or circuit breaker which is sized in accordance with all applicable
national, state and local electrical codes, in order to provide the necessary overload
protection for the controller and motor. Incorrect motor branch circuit protection
may create a hazardous condition.
WARNING: Proper grounding is vital for the safe operation of your system. Bring the
ground wire to the ground stud that is labeled "GND" or "G". You must choose the
proper conductor size. See national electrical code article 250-95, or the related local
applicable code.
NOTE: Recommended slowdown distance is about 6" for every 25fpm of car speed,
for speeds of up to 200fpm. Minimum recommended target length for the floor
switches is 1".
If there are short floors, refer to the schematic for special instructions, if required.
NOTE: The terminal landing Floor Switches must be maintained while the car is within
door zone of the terminal landing.
NOTE: Recommended slowdown distance is about 6" for every 25fpm of car speed,
for speeds of up to 200fpm. Minimum recommended target length for the floor
switches is 1".
NOTE: Many problems in operation can be attributed to failures in the Door Open or
Close Limit Switches (including long door times, improper door operation on Fire
Service, inability to go on to or to clear Fire Service, etc.) Always check the Door Open
and Close Limit Switches if unusual operation of the elevator is observed.
NOTE: It is recommended that the Door Close Limit Switch be adjusted so that, as the
doors are closing, the Car Door Contact closes before the Door Close Limit opens.
Consult the Door Operator Manufacturer's installation instructions for further details
on the adjustment of the doors.
NOTE: 2000 (or later) code compliant controllers will not run without the Door Close
Limit operation properly.
NOTE: If a solid state door operator unit is being used, check the appropriate
schematics to see if any changes are required on the actual operator. These may
include changing resistors in the operator, and adding a diode for proper open and
close torque.
WARNING: Do not allow any metal shavings to get into relays or contactors, or in or
behind the electronic components, as these could cause serious damage to personnel
or the equipment.
3.3.2 Grounding
WARNING: PROPER GROUNDING IS VITAL FOR THE SAFE OPERATION OF YOUR
SYSTEM. BRING THE GROUND WIRE TO THE GROUND STUD THAT IS LABELED "GND"
OR "G1". YOU MUST CHOOSE THE PROPER CONDUCTOR SIZE AND MINIMIZE THE
RESISTANCE TO GROUND BY USING SHORTEST POSSIBLE ROUTING. SEE NATIONAL
ELECTRICAL CODE ARTICLE 250-95, OR THE RELATED LOCAL APPLICABLE CODE.
Proper grounding is vital for the safe operation of your system, and will also reduce the
likelihood of noise-induced problems, which could include CPU crashes, or I/O communication
errors.
NOTE: If the fuses are not removed, the meter will read a short through the windings
of the main control circuit transformer.
With the fuses still removed, apply power to the controller, and verify that the voltage at the secondary
of the main control circuit transformer ("CCXF") is 110-125VAC.
WARNING: Each output point should be isolated from ground and the hot side.
VIRGINIA CONTROLS, INC. MVFAC-3000 User Manual, Rev. 2.11 Page 16
4.2 Applying Power
Remove all fuses before applying power. Reinsert the fuses, one circuit at a time, checking each circuit
before adding the next.
It is recommended that you start up the controller in Inspection mode, which can be done by opening
the Inspection Switch, or removing the field wire(s) from terminal 23.
NOTE: If Hoistway Access is used to get on top of the car, then the doors will be open
when Top of Car Inspection is initiated. In this case, the doors will close when the Up
(or Down) Run and Run (or Enable) buttons are pressed. If it is required that the doors
should only operate manually on Inspection, then the Bit Feature to “Disable Door
NOTE: If 2000 (or later) Code is provided, then the controller is expecting terminal 3 to
go low when the Inspection Run Buttons are not being pressed. If a temporary run
station is being used that is not wired as shown on the schematics, then the controller
will show a fault if terminal 3 does not go low when the car stops. The redundancy
fault can be temporarily defeated by turning Switch 3 on the CPU Slide Switch S2 to
the ON position. This will also turn on the Fire Audible Visible output, as a reminder to
turn off the defeat when the car is ready for full operation.
NOTE: If floor switches are used, they should be maintained at the terminal landings,
so that they are energized whenever the car is in the slowdown zone at that landing.
Make your final adjustments for the slowdown targets. All slowdown distances should be equal.
If a pulsing selector arrangement is used, remember to install the reset targets at the terminal landings.
NOTE: To run the car from the machine room, without the doors opening, turn off the
DOL Cutout Switch. This will de-energize the Door Open Limit Sw Input, and prevent
the doors from opening.
VIRGINIA CONTROLS, INC. MVFAC-3000 User Manual, Rev. 2.11 Page 19
NOTE: If the car does not run, verify that no door protective device (Door Open
Button, Safety Edge, Electric Eye, Infra-red Curtain) is holding the doors open. Verify
that the car is not stuck in leveling. Verify that the Door Contacts input is energized
and the Door Close Limit input is de-energized.
NOTE: On DUPLEX systems the doors must be allowed to operate for the calls to be
canceled properly.
Each call will be canceled when the car initiates slowdown for the call, or when the doors start to re-
open for the call if the car is already at the floor.
If both hall calls are entered at an intermediate landing, and no other calls are in the system, the doors
will close after answering one of the calls, then re-open in response to the other call.
NOTE: To reset Hall Fire Service (Phase 1), most codes require the Bypass input be
energized. To disable Hall Fire Service, jump the Hall Bypass input on. On 2000 (or
later) Fire Code, Fire Service (Phase 1) is reset when the Hall Fire Switch is turned from
Bypass to Off.
NOTE: If Car Fire Service (Phase 2) appears to be operating incorrectly, check the Door
Open and Close Limits for proper operation. Most codes require that the doors be
fully open before allowing a change in the mode of operation on Car Fire Service.
Most codes require that Hall Fire Service (Phase 1) be in effect for the car to return
automatically to the main fire landing when the Car Fire Switch is turned to the off
position.
NOTE: If a Reverse Phase Relay or Emergency Power circuitry is supplied, these will
also initiate a shutdown signal if the inputs are not energized.
A sequence fault timer monitors key inputs from the drive system, such as Drive Enabled, Brake Micro
Switch, and contacts of the key drive contactors. If these fail to change state properly as the car starts or
stops, then the car will be shut down. The fault can be reset by cycling the Main Line Disconnect Switch,
or by putting the car on "Inspection" then back to "Automatic".
WARNING: Be careful not to mix the power supplies from one car with the other car.
Signals that are common to both controllers must be connected to a common supply,
as shown on the schematic.
5.10.4 Homing
If there are no cars at the Main Dispatch landing, the "Next" car in the Lobby Zone will home, or return,
to the Main Dispatch Landing. If there is no "Next Car" in the Lobby Zone, then the first available car will
home to the Lobby. If desired, the "Free" car can be set up to home to a specific (adjustable) landing in
the upper zone, or to home to the Main landing. (See the separate description on Feature Adjustments.)
A car will home if the following conditions have been met for 10 seconds:
1. The car is in group operation (not on Inspection, Independent Service, Fire Service, Load Weighing
etc.).
2. The Stop Switch is not thrown.
3. The car is not stuck.
4. The doors are closed.
5. The car is not at the Main Dispatch Landing.
6. The car is not running.
7. The other car is in group operation.
8. The other car is not next in the Lobby Zone.
9. The other car is not running down.
10. The other car is not homing.
5.10.5 Communication
Confirm that the termination jumpers have been installed to connect the termination resistors. These
are two small jumpers just below the Duplex Communication Connector block in the upper left corner of
the CPU. (Refer to the diagram of the CPU below)
Connect the communication cable from the Duplex Communication Connector block of one car to the
other car. The negative terminal on one car only should be connected to ground.
When both cars are in operation, the LED L4 should flash repeatedly. This indicates the two CPUs are
communicating properly.
If LED L4 is not flashing, check the communication cable, the termination jumpers, and the grounding. If
these look OK, but the CPUs are not communicating, do a factory reset on both cars. Memory location
0508 shows the number of successful communications (it should be constantly changing when both cars
are operating) and memory location 0509 shows the number of bad communication attempts (this
should be 0). (Note: These memory locations are subject to change.)
NOTE: Follow the prints for setting the UCM Select Jumper. If a label was applied to
the board for setting this jumper, then follow it, but it should agree with the prints.
2. To begin construction, defeat the UCM System (and O-S & ETSD Systems) by placing a jumper from
controller TB-1 to Inputs SHTDFT and ETSDFT.
3. Power up the controller and verify that Input LED’s: “EII, ETSDFT & SHTDFT” are lit.
Figure 4 - EX1, EX2, ET1, ET2, RBP1 & RBP2 Output Indicators
5. Construction of the elevator may now proceed until it is decided that the O-S System should be
tuned.
6. Once the O-S System is tuned per the next “Setup of the O-S System” Section, the jumper from
controller TB-1 to Input SHTDFT will be removed.
7. The jumper from controller TB-1 to Input ETSDFT will be removed when the ETSD System is tuned
per the final “Setup of the ETSD System” Section. (Required if car speed is greater than 200FPM.)
4. Use the mounting bracket to position the Speed Sensor approximately 5” (±1/4”) away from the
ETSD Tape at an angle that is nearly, but slightly off (approx. 10⁰) perpendicular to the tape.
5. With power off, route the 30ft Speed Sensor Cable through a metal conduit to the ETSD Board.
NOTE: Be sure the metal conduit is grounded at the motor end, and if possible, also
ground the other metal conduit containing the motor leads in the same manner.
6. Wire the cable per markings the 4-Pole “PHOTO” connector on the ETSD board. Shorten the cable at
the ETSD Board once its route through conduit is determined. Do not coil cable within the
controller.
10. Verify that the Yellow “SENS.” LED of the Speed Sensor and the “PHOTO -1” LED on the ETSD Board
are lit only when the red light beam of the Speed Sensor is pointed at a white segment of the ETSD
Tape.
12. Important Step: Perform the following checks to insure that “PHOTO-1” LED on the ETSD Board
lights only when the sensor is pointed at a white segment of the ETSD Tape, and to prevent “PHOTO-
0 & PHOTO-1” LED’s from oscillating while the sheave is still, and perhaps pointed at a black
segment:
• “L/D” (Light/Dark) Switch of Speed Sensor is set to “L” or Light position. (Check carefully!)
• “SENS.” Potentiometer of Speed Sensor (2-turn w/clutch) is set on turn - middle.
• Speed Sensor is about 5” (±1/4”) away from the ETSD Tape.
• Speed Sensor is aligned slightly off (approx. 10°) perpendicular from tape.
NOTE: Car speed should be checked with hand tachometer, or repeat when available.
17. If elevator contract speed is 150FPM or lower, then set the drive (in previous step…) to 80%-90% of
contract speed.
18. When the elevator comes to a stop, remove jumper at Input OSC with power on. The “O-S TUNED”
LED will light indicating a valid calibration of O-S System.
24. Important: If the O-S System should fault intermittently, it is most likely caused by “noise” that is
picked up by the Speed Sensor Cable due to its proximity to the motor leads of the Drive, or by a
poorly aligned or adjusted Speed Sensor. See Step 12 (above) and Steps 25 & 26 (below).
25. Important: Car speed can be monitored on LED’s “S0-S7” by turning on DIP SW-4, “AUX”, only.
These LED’s show car speed as a binary count that should ramp up & down with Accel & Decel and
appear stable at constant speed, with dithering (or flashing…) on the lowest one or two bits only.
LED’s “SO-S7” represent an 8 Bit count (1, 2, 4, etc…) where each bit accounts for 5FPM (or, one ¼”
of tape travel sampled over 250mS). Example: LED’s “S1 + S2 + S3 + S4” = ( 2 + 4 + 8 + 16 ) x 5 =
150FPM.
Leave the SW-4, “AUX” in the ON/Up position.
26. Important: While running, if LED’s “S0-S7” flash off and on randomly, without a pattern: check that
the Speed Sensor Cable is ran separate and away from line & motor leads; check conduit grounding;
The un-tuned ETSD System was previously defeated in the “Setup of the O-S System”
Section by jumping from controller TB-1 to Input ETSDFT.
If the elevator contract speed is 200FPM or less, then the ETSD System is not tuned,
and the jumper from controller TB-1 to Input ETSDFT remains in place. Stop here!
If contract speed is greater than 200fpm, proceed with ETSD tuning.
The ETSD System can be tuned only after the O-S System has been tuned.
An un-tuned ETSD System powers up with “ETSD TRIP” & “ETSD TUNED” LED’s off.
NOTE: Minimum ETS Switch Cam lengths are 6ft for +200-500FPM to provide
approximately 0.5 Sec of dwell time. The ETS Switches may also be maintained to the
Final Limit Switch as most cam lengths are the height of the car.
Once the elevator has been fully adjusted for Normal operation (Contract Speed set
along with Accel/Decel & Jerk Rates), and the ETS Switches and Cam are installed,
then ETSD System can be tuned.
Table 1 - Recommended ETS Switch Placement (one N.C. switch per terminal & direction)
Car Speed
Switch Placement
(FPM)
225 2’-3”
250 2’-6”
300 3’-6”
350 4’-3”
400 5’-3”
450 6’-6”
500 7’-6”
1. Power down controller, and move the jumper from Input ETSDFT to Input ETSC.
2. Power up controller, and verify that Input LED’s: “EII, ETSC & AUTO” are lit.
4. Set the drive for a High Speed setting of 90% of contract speed, and send the elevator on a multi-
floor run on Normal operation. Verify that the elevator obtains this speed.
5. When elevator comes to a stop, remove jumper at Input ETSC with power on. The “ETSD TUNED”
LED will light indicating a valid calibration of the ETSD System.
13. Important: While running, if LED’s “S0-S7” flash off and on randomly without a pattern: check that
the Speed Sensor Cable is ran separate and away from line & motor leads; check conduit grounding;
check the alignment and adjustment of the Speed Sensor per Step 12 of Section 4.11.2.
Then, recalibrate both O-S & ETSD Systems.
For example, the (decimal) value 350 is ( 256 + 64 + 16 + 8 + 4 + 2 ). To set this value jump I-01, I-02, I-03,
I-04, I-06 in step 9 and IN00 in step 12.
The (decimal) value 25 is ( 16 + 8 + 1 ). To set this value jump I-00, I-03, I-04 in step 9 and nothing in step
12.
5.12.6 TROUBLESHOOTING
1. Verify that Output 0 on the Allen-Bradley PLC comes on when the car runs up. If it does not, check
the encoder wiring, then swap wires A+ and B+, also swap A- and B-.
2. Verify that the A and B lights on the HSC Module flash when the car moves. This is most noticeable
when the car is going very slowly.
3. Jump input I-01 on the Allen-Bradley PLC to reset all speed set points back to the factory default
values.
6.1 Transformers
“CCXF” is the Control Circuit Transformer. This will provide the controller with 115VAC. The primary
connections will vary depending on the Building Power. See the schematic for sizing and wiring
information.
“DOXF” is the Door Circuit Transformer(s). The size and quantity of these transformers will depend on
the type of doors used. See the schematic for sizing and wiring information.
NOTE: Only replace fuses with fuses of the same type and rating.
6.5.1 CPU
LCD Display
CPU Status
Reset Button LEDs
Termination
Jumpers
Group
Communication Keypad
Connector
I/O Board
Communication
Connector
12VDC
Power EPROM
Supply Socket
The Central Processing Unit (CPU) board contains the hardware that controls the inputs and outputs
which control the elevator. This section describes the major components on the board, and the function
of the connectors and LEDs.
WARNING: Replace the battery with RENATA 3V Lithium battery, Part No. CR2032
Only. Use of another battery may present a risk of Fire or Explosion.
VIRGINIA CONTROLS, INC. MVFAC-3000 User Manual, Rev. 2.11 Page 46
WARNING: Orient the battery properly in the battery holder. The positive side of the
battery is marked on the battery, and faces towards the power connector and away
from the EPROM socket.
WARNING: Do not use a metal (or conducting) device to remove or install the battery.
To replace the battery, remove the old battery by gently pushing the top of the battery towards the
EPROM socket, until it is clear of the black housing, and then slide it out of the socket. Insert the new
battery by sliding the edge under the metal retaining finger, then aligning it in the black housing. Be
careful not to short out the battery. Dispose of the old battery properly – do NOT incinerate the battery.
D1D1
- Auto
- Auto
D2D2
- Fire
- Fire
D3D3
- Shutdown
- Shutdown
D4D4
– Communication
– Communication
D5D5
- Watchdog
- Watchdog
The function of these LEDs during normal monitoring is noted on the schematic. The normal description
for these LEDs is as follows:
D1 "Automatic Operation". This LED should be lit during normal operation. It will go out when the
car is on Inspection Service, Independent Service, Fire Service, Low Oil Shutdown, or any other
mode that will cause the car to ignore Hall Calls.
D2 "Fire Service". This LED should be off during normal operation. It will be lit if the car is on Fire
Service Phase 1 (Hall) or Phase 2 (Car).
D3 "Shutdown". This LED should be off during normal operation. It will be lit if the Up Run timer
indicated the car has been running up for a preset adjustable time without passing a floor. This
could be caused by a low oil level; a problem with the motor starter circuit(s); or a problem with
the up valve circuit(s). The car will stop running up, then return to the lowest landing and cycle
the doors. It will then be shut down, with only the Door Open Button and door re-opening
devices being operational. The fault can be reset by cycling the Main Line Disconnect Switch, or
by putting the car on "Inspection" then back to "Automatic".
NOTE: If a Reverse Phase Relay or Emergency Power circuitry is supplied, these will
also initiate a shutdown signal if the inputs are not energized.
D4 “Communication Error”. This LED should be off during normal operation on a Simplex. It will be
lit if the CPU has failed to communicate properly with an Input/Output board. This could be
NOTE: If the diagnostic mode is changed to monitor the Internal Memory, or the
Setup Mode is selected, then the operation of the LEDs will change, as described in the
appropriate sections.
It is used to reset the CPU if a lock-up occurs (such as if LED D5 stops flashing when in the normal
operating mode).
WARNING: Pressing the Reset Button will reset the CPU, causing all outputs to be
turned off and the car to stop immediately.
The LCD display is mounted directly on the connector. The LCD display can be removed for replacement.
If it is removed, then set switch 1 on the Slide Switch S2 to the OFF position before turning the power
back on. This will ensure the CPU does not try to write to the LCD screen while it is removed. It is
recommended that the LCD display AND the Keypad be removed together, since if the LCD display only
is removed, and the keypad is activated, the CPU will probably lock up. Make sure the power is turned
OFF before removing either the keypad or the LCD display.
I/O numbers
Programming
Port
C1234C5678 Commons
C1234C5678
Jumper Block 1-8 Terminals
Input LEDs 1-8 Output Relays 1-8
Programming
Connector 12345678 12345678 Output LEDs 1-8
I/O Communication Address Sw Block
Bus IN Connector
Status LED I/O Communication Bus
OUT Connector
12VDC Power 9 11 13 15 9 11 13 15
Connector
10 12 14 16 10 12 14 16 Output LEDs 9-16
Input LEDs 9-16
Jumper Block 9-16
Output Relays 9-16
Terminals 9 11 C 14 16 9 11 C 14 16
15 15
C 10 12 13 15 C 10 12 13 15
Commons
Input/Output boards are used to connect the CPU with the field devices. All inputs (unless otherwise
stated) are 115VAC, and outputs (unless otherwise stated) are dry relay contacts.
The boards are available as 16-Input and 16-Output boards, or 16-Input and no outputs.
All inputs and outputs have individual LED indicators.
Wiring is done to the removable terminal blocks at the top and bottom of the I/O boards.
Fuses are provided externally, not on the I/O boards.
6.5.2.1 Addressing
Each Input/Output board is given a unique address by means
of the Address Switch Block on the right of the board, next to
the I/O COMM OUT Connector. The first board connected to
the CPU is address 1, the next is address 2, and so on. The
numbering is consecutive, and no numbers are skipped. To
set the address, refer to the chart below. ON indicates the
switch is set to the right, OFF indicates the switch is set to
the left, as indicated on the switch itself.
Picture at right shows DIP Sw. 1 to the right, and all the
others to the left, which is the address for Board 1, as shown
in the table below.
NOTE: If a board is replaced, the board must be set up with the SAME ADDRESS as the
board it was replacing. The address of each I/O point is determined by the Board
Number (1 through 8), then the Point Number (1 through 16). The board number is
used in the “Show I/O” screen to indicate which board is being monitored.
WARNING: Be very careful not to jump to a common when you intended to jump to
an input or output, as this could damage the controller or other equipment.
Com 0 1 2 3 Com 4 5 6 7
• If activated, the UCM System may remove power from machine motor & brake.
• The braking device may be applied (not activated) to a stopped elevator, and may be applied
(not activated) when an Electrical Protective Device (EPD) is opened.
• The UCM System is classified by code as an Electrical Protective Device (EPD).
NOTE: Input SHTDFT defeats the UCM System if jumped at power-up, then left in
place. It will not reset a UCM System fault at power-up. Use only during construction.
7. The operational integrity of the UCM System is checked prior to leaving a landing when on
Normal operation and is performed differently for Rope Brake operation versus Emergency
Brake operation.
8. When equipped for Rope Brake operation, the controller is provided with Relays: RB, RBX & RBC,
from which UCM System Inputs RB & RBC synchronize the integrity checking of UCM System
Relays: RBP1, RBP2 & RBCX1, RBCX2.
a. To start, the processor energizes controller Relay RBC causing UCM System Input RBC to
go high, which prompts the UCM System to energize Relays RBCX1 & RBCX2 causing TB-
RCM, as monitored by the processor to go high.
b. Next, the processor releases controller Relays RB & RBX causing UCM System Input RB
to go low. This prompts the release of UCM System Relays RBP1 & RBP2 causing UCM
System TB-RM, as monitored by the processor to go low indicating proper operation of
these UCM System relays.
NOTE: The High Speed Counter of the controller processor is calibrated at a 125FPM
threshold for Inspection and at a 50FPM threshold while Leveling with doors open.
5. When tuned and operating and if Input EII is high, the O-S System energizes Relays EX1 & EX2 at
+1.0seconds after power-up. The O-S System also energizes Relays ET1 & ET2 when the
controller is on Normal operation and out of Door Zone, or when on Normal operation and in
the Door Zone with doors closed.
6. Relays ET1 & ET2 are released when on Normal operation (Input Auto is high) and the elevator
has been sitting in the Door Zone, and Gate and Door Contacts have been open and remain
open with the Safe Input low (Drive is enabled) for 1.0 second. Relays ET1 & ET2 are de-
energized on Inspection and remain so.
7. During either of these two conditions, if 150FPM is exceeded, Relays EX1 & EX2 de-energize,
opening the safety string and causing the O-S System to fault.
NOTE: If the O-S System is re-tuned, the ETSD System must be re-tuned also.
10. For troubleshooting, a tuned O-S System can be defeated by jumping Input OSC high with power
applied.
NOTE: Do not cycle power with Input OSC jumped or O-S calibration will be lost!
11. A tuned, but defeated O-S System maintains Relays EX1 & EX2 regardless of car speed. Relays
ET1 & ET2 function normally per the previous description.
VIRGINIA CONTROLS, INC. MVFAC-3000 User Manual, Rev. 2.11 Page 64
12. A tuned O-S System energizes its Relay XXA when car speed exceeds 150FPM. This output
serves as “Low Speed Monitor” or LSM Input for the controller micro-processor.
13. The operational integrity of the speed monitoring system is checked as the controller micro-
processor verifies its Input LSM (O-S System Relay XXA) energizes when car speed exceeds
150FPM and de-energizes when car speed drops below 50FPM.
14. The operational integrity of Relays ET1 & ET2 is checked as the controller micro-processor
verifies TB-ETM goes low (i.e.: Relays ET1 and ET2 drop) when on Inspection or on Normal
operation when Leveling with doors open.
15. When the controller micro-processor Input ETSD is energized, then the operational integrity of
the O-S System (Relays ET1, ET2 & Output XXA) is not checked.
16. If the controller micro-processor detects both its inputs at terminal blocks: EXM & ETM of the
ESTD Board are low, and its Input LSM is high, then it logs a fault of the O-S System.
5. Minimum ETS Switch Cam lengths are 6ft for +200-500FPM to provide approximately 0.5
seconds of dwell time. ETS Switches may also be maintained to the Final Limit Switch as most
cam lengths are the height of the car.
6. When tuned and operating and if Input EII is high, the ETSD System energizes Relays EX1 & EX2
at +1.0seconds after power-up. The ETSD System also energizes Relays ET1 & ET2 when the
elevator is on Normal operation (Input Auto is high) and Inputs ETU & ETD are high (off of the
ETS Switches in hoistway).
7. Relays EX1 & EX2 remain energized until car speed exceeds 90% of contract speed at which time
they are released causing the safety string to be subject to Relays ET1 & ET2. Relays EX1 & EX2
re-energize just below 90% of contract speed.
8. Relays ET1 & ET2 remain energized until the elevator rides onto one of the ETS Switches in the
hoistway causing either Input ETU or Input ETD to go low.
9. On a “typical” full speed run into a terminal landing, the elevator decelerates below 90% of
contract speed before it encounters an ETS Switch. This allows Relays EX1 & EX2 to re-energize
before Relays ET1 & ET2 release.
10. On an “over-speed” run into a terminal landing (+90% of contract speed with just 50% of
slowdown distance remaining), Relays EX1 & EX2 stay released while over 90% of car speed.
Then, as an ETU or ETD Switch is encountered, Relays ET1 & ET2 are released, opening the
safety string and causing an ETSD System fault.
11. When faulted, the “ESTD TRIP” LED lights.
NOTE: The ETSD System must be re-tuned, if the O-S System is re-tuned.
13. For troubleshooting, a tuned ETSD System can be defeated by jumping Input ETSDFT, or by
putting the controller on Inspection operation.
14. A defeated, but tuned ETSD System maintains Relays ET1 & ET2, regardless of Inputs ETU & ETD.
Relays EX1 & EX2 remain subject to car speed.
15. The operational integrity of the ETSD System is continuously checked by the controller micro-
processor per the following.
3. Check the alignment and focus of the Speed Sensor light beam. It should appear in the center of
the ETSD tape as a bright red dot 1/16” in size. If otherwise, see the “Setup of the O-S System”
Section 4.11.2 for mounting, aligning and adjusting the Speed Sensor.
5. Check for the green “POWER” LED on the Speed Sensor. If not lit, check “PHOTO” Connector
terminal blocks 1 & 3 for 24VDC.
WARNING: The Speed Sensor is Class 1 Laser Product. Avoid eye contact with Red
light source.
Manufacturer Pepperl+Fuchs
VT18-8-400-M-LAS/40a/118/128 – P/N: 801135 Note: Class 1 Laser
Model: (Photo Sensor)
Product
(Shielded Cables)
V1-G-10M-PUR-ABG – P/N: 221508 (10 meter length) Or,
V1-W-10M-PUR-ABG – P/N: 219640 (10 meter length w/90° Connector)
⅝”W x 10’L (36” max. sheave diameter); ¼” alternating black & white
ETSD Speed Tape
stripes
Mounting (Bracket) Steel angle bracket (2 ¼-20 bolts) w/Rubber Grommets & 2 Fiber Washers
(Position) Position photo sensor slightly off perpendicular from tape by 5⁰ - 15⁰ to
inhibit reflection (an ON state) while on a “Black” segment of ETSD Tape.
Distance (Sensor to Tape) 5” (±1/4”) between Sensor face (Red) & Tape on Sheave
= Press “Nxt”
The normal sequence is to press “Nxt”
= Press “Prv” to select the desired menu item.
= Press “Ent” Press “Ent” to use the menu item.
Press “Esc” when you are finished.
= Press “Esc”
VaControls.DS03A
12345.1.040705..
The "Banner” screen shows "VaControls" on the top line, followed by a code showing the program
family. In the example above this is “DS03A”. The code on the bottom line shows the Virginia Controls
Job Number (in the example above this is “12345”), the program revision number (in the example above
this is “1”), and a date code for the program in the format MMDDYY (in the example above this is
“040705” for April 7th, 2005). The controller displays the "Car Status" screen when the "Set-up Mode" is
exited.
The right side shows the status of the inputs or outputs. The status will be a "1" if the signal is on, or a
"0" if the signal is off. The order of the bits corresponds to the order of the LEDs on the I/O board, that
is, the top left bit corresponds to Point 1, top right is point 8, bottom left is point 9 and bottom right is
point 16. In the example above, the Inputs on Board # 2 are being monitored, and points 3,4,7 (top line)
and points 10,14,15 (bottom line) are all on.
If an I/O Fault is showing on the Status Screen, and the data on the Show I/O Screen matches the I/O
boards, then the checksum in the communication is incorrect. This will cause the CPU to ignore the
data, and not pass it to the main program. To determine which board is causing the communication
failure, refer to the section on troubleshooting suggestions for I/O board faults.
Non-shutdown faults can be prevented from being logged, if desired. See the list of
Adjustable Features on sheet “MH-3000 Settings”. One of the Bit Features will be labeled “Disable Non-
Shutdown Faults in the Fault Log”. Turn this feature on to disable non-shutdown faults. This may be
useful if you are trying to track down a specific fault, and you do not want the fault log to contain minor
faults. Refer to the section on Changing Features for instructions on settings the proper Bit Feature to
disable non-shutdown faults.
NOTE: Faults that happen within 10 minutes of each other may log the same time.
The fault # will indicate the order of occurrence.
If the real time clock is set correctly, then this will be the time of the fault.
NOTE: To set the clock, refer to the section on setting the time under MH-3000
Screens and Diagnostics/Set-Up Mode/Set the Time.
To verify that the real time clock is set, press . to display the current time and date as shown here.
Press Ent to return to the fault log.
CURRENT TIME
13:23 11/13/01
VIRGINIA CONTROLS, INC. MVFAC-3000 User Manual, Rev. 2.11 Page 79
7.1.3.4 Fault Code
“FLTCODE” is the code for the fault, shown on the top right of the “Fault Log” screen. It is an
alphanumeric designation up to 7 characters that indicates what the fault was. The following fault codes
are standard.
NOTE: If a code is shown that is not in this list, check the paperwork for your specific
job to determine the meaning of the code, and the cause of the fault.
Non-shutdown faults can be prevented from being logged, if desired. See the list of Adjustable Features
on sheet “MH-3000 Settings”. One of the Bit Features will be labeled “Disable Non-Shutdown Faults in
the Fault Log”. Turn this feature on to disable non-shutdown faults. This may be useful if you are trying
to track down a specific fault, and you do not want the fault log to contain minor faults.
Refer to the section on Changing Features for instructions on settings the proper Bit Feature to disable
non-shutdown faults. The following faults will be disabled: This will prevent faults TDOPEN, TDCLOSE,
TDOPN-R, TDCLO-R, CARSTUK, DRCONTS, OUT-DZ, COMMFLT, FIRE, MRSMOKE, SHUNT, FLOOD from
being logged.
23 00:00 ROLLOVR
11/13 0
Several consecutive rollover faults will be combined into one rollover fault, and the number
on the lower right will indicate how many additional rollovers were combined, indicating
there were no faults for that many additional days.
23 00:00 ROLLOVR
11/13 2
25 00:00 ROLLOVR
11/07 5
For example, if faults 23, 24 and 25 were as shown above, this indicates a rollover code 25
was combined with five more (on 11/08 to 11/12) so that no faults occurred between 11/08
and 11/12, and fault 24 occurred on 11/13, since that is the date of the next earliest rollover.
NOTE: If the power is off when a rollover would have occurred (at
midnight) then no rollover code will be logged. If power is left on, then the
date of any fault is the date shown on the most recent (lower fault
number) rollover code.
RUN Tmr Running Shutdown Timer. The car ran for the time specified by the "Shutdown Time" setting
without passing a floor. The car will stop and shut down immediately. The doors may be
opened if the car is in the Door Zone. Check that the setting of the shutdown timer is long
enough for the car to run between floors. The normal shutdown timer setting is 25 seconds.
NOTE: If 2010 ANSI Code is enabled, then shutdown faults must be reset by momentarily
turning on the CPU DIP Switch #4, or by momentarily jumping the Fault Reset Input.
TDOPEN Door Open Fault. The Door Open Limit Switch failed to open after the doors had been
opening for the time specified by the "Door Fault" setting. The probable causes are: (1) The
Door Open Limit failure. (2) door operator failure. (3) door control circuitry failure. This fault
can be disabled on Manual Door systems.
TDCLOSE Door Close Fault. The doors failed to close properly when they were parking, or when the car
was ready to run for the next call. This fault will not be caused by keeping the doors open
VIRGINIA CONTROLS, INC. MVFAC-3000 User Manual, Rev. 2.11 Page 81
CODE DESCRIPTION
through the normal means (Door Open Button, Safety Edge, Infra-red Unit, etc.), but only if
the doors should be closing but were not able to close. The probable causes are: (1) Door
Close Limit failure. (2) Door Contacts failure. (3) door operator failure. (4) door control circuit
failure.
TDOPN-R Rear Door Open Fault. This is the same as fault TDOPEN, except it is for the rear door. This
fault is only used on elevators with selective open doors (with a front and rear door at the
same landing). This fault can be disabled on Manual Door systems.
TDCLO-R Rear Door Close Fault. This is the same as fault TDCLOSE, except it is for the rear door. This
fault is only used on elevators with selective open doors (with a front and rear door at the
same landing).
CARSTUK Car Stuck Fault. The car was held at a floor for the time set by the "Car Stuck Time" setting,
without running. This may be caused by a stuck button, or just by a passenger holding the
car.
EmPower Emergency Power. The elevator went on Emergency Power. Normal operation (Automatic
Return) is for the car to return to the Main Ldg, then shut down until the Emergency Power
Run Input is turned on. The controller can be set up to provide Manual Return, so that the
Emergency Power Run Input must be on to allow the car to return. The car will not return
automatically if it is on Inspection, Fire Service, Independent Service, or is prevented from
running for some other reason.
DRCONTS Door Contact Fault. The Door Contact Input turned off while the car was running. This fault
could be caused by the car tipping a door contact, or another of the devices in the safety
string. It could also be caused by a failure of the "DC" Door Contact relay.
OUT-DZ Door Zone Fault. The car stopped between floors. This is normal when the car is being taken
off Inspection Service. This fault will usually be seen with fault 08, since the car will usually
stop outside the door zone if the safety string is broken.
COMMFLT Communication Failure on Duplex. This will occur when the power on the other car is turned
off, or the other car fails to communicate properly for 5 seconds. Check the communication
cable, and the termination jumpers, which are located by the communication cable terminal
strip.
DRCHECK Door Check Fault. The Car or Hall Door Contacts Input was on (indicating the doors are
closed) while the Door Close Limit was on (indicating the doors are open). This check is
performed when the doors are fully open (Door Open Limit is off) and the car is not on a
Leveling Switch. The car will be held with the doors open until the Door Contacts input goes
off. The Car Door and Hall Door Contacts are both checked independently. If this fault is not
caused by a jumper on the Door Contacts, then check the Car and Hall Door Contacts very
carefully, and check the wiring to the Door Contact Inputs and Door Close Limit Input.
LEV SWS Leveling Switch Fault. Both Leveling Switch Inputs are on. This will shut the car down. Check
the Leveling Switches to make sure one of them has not stuck. The switches must be adjusted
so that only one leveling switch is energized at a time. Then check the wiring for shorts.
Cycle the power, or put the car on Inspection to clear the fault. In some short floor situations,
there may be an overlap of the leveling switches between the floors. In this case special
NOTE: If the boards NEVER communicate, a fault will not be logged, since
the fault is ignored during power up. The fault is only logged if the boards
were communicating properly and then stopped.
(OTHER) Other Fault Codes may occasionally be provided on specific jobs. If this is the case, then refer
to the additional documentation for that job to see what the codes and descriptions are for
those faults.
NOTE: The Fault Status Signals are the same for all faults EXCEPT for the Redundancy
Faults RED-RUN, RED-SAF, and RED-INS. Refer to the tables below for the description
of the signals for those faults.
01 09:40 FLTCODE
P ABCD EFGH IJKL
The number of faults, runs and door cycles are in hexadecimal. You can use the table below to convert
the value to decimal.
Match the first hex character in the value to the decimal equivalent in the first two columns in the table;
match the second character to the value in the next two columns; etc. Then add up the decimal
equivalents for all the values to get the decimal value.
In the example shown above, the number of faults is “0014”(hex). Using the table, this is 0 (1st char hex)
= 0 (decimal equivalent from 1st two columns)
0 (2nd char hex) = 0 (decimal equivalent from 2nd1st two columns)
1 (3rd char hex) = 16 (decimal equivalent from 3rd two columns)
4 (4th char hex) = 4 (decimal equivalent from 4th two columns)
0014(hex) = 0+0+16+4 = 20(decimal).
The number of runs is “135F”(hex), which is 4096+768+80+15=4959(dec)
The number of door cycles is “1619”(hex), which is 4096+1536+16+9=5657(dec)
After the number of days set in address $0401 (default is 60) the values from the current Historical Log
(addresses $0520-0527) are moved to the Previous Log (addresses $0528-052F) and the current log is
cleared out. The current date is loaded into the start addresses for the new current historical log.
NOTE: For addresses that show an ON or OFF condition, "00" is OFF, and "FF" is ON.
WARNING: Changing data could cause unexpected and dangerous results. Do not do
this unless you are fully aware of the value that needs to be changed, and how to
change it. Take all necessary precautions to prevent an unsafe condition, such as
disconnecting the terminal blocks from the outputs, removing the appropriate fuses,
or opening the appropriate safety circuits.
Use the normal keys to navigate to the memory location that is to be changed, as shown in “Moving
Around” above. You can only change the value that is in the top left of the display. For example, if the
top line of the display shows “2012 04 37 82 34” then memory location 2012 can be changed from its
current value of 04.
To change a value, press . (the top left character will flash briefly) then press one of the following keys:
Press Nxt to increase the addresses being displayed by 1.
Press Prv to decrease the addresses being displayed by 1.
Press 3 to increase the addresses being displayed by 4.
Press 6 to decrease the addresses being displayed by 4.
Press 2 to increase the addresses being displayed by 10(Hex).
Press 5 to decrease the addresses being displayed by 10(Hex).
Press 1 to increase the addresses being displayed by 40(Hex).
Press 4 to decrease the addresses being displayed by 40(Hex).
Press 8 to enter a value of (“FF”(Hex) minus the old value).
Press 9 to enter a value of “FF”(Hex).
Press 0 to enter a value of “0”.
Press 7 or Aux or . or Ent to leave the value unchanged
Press Esc to return to the menu screens.
111 222222333333
4 55 66 7777 888
If the appropriate fault exists, Message # 7 and #8 will be replaced with one of the following messages:
1. “IO-FAULT” – the communication with one or more of the I/O boards has failed.
2. “DrChkFLT” – the Door Closed Input is on, and the Door Closed Limit is on, indicating the Door
Contacts have been jumped.
3. “DrLmtFLT” – the Door Open Limit and the Door Close Limit are both off.
4. If none of these three faults are present, then messages # 7 and # 8 will show the door status as
shown below.
WARNING: The elevator will stop immediately and be completely shut down, as all
outputs will be turned off when the Set-up Mode is entered.
The LEDs D1-D4 are not updated in the Setup Mode, so they will remain in their last state. LED D5 will
flash once every 10 seconds, to indicate the CPU is not locked up.
NOTE: It may be necessary to press Esc to exit a sub-menu and return to the Set-up
Menu, before going back to the Run Mode.
VIRGINIA CONTROLS, INC. MVFAC-3000 User Manual, Rev. 2.11 Page 100
SETUP MODE SCREENS
To CHANGE SETTINGS, (see below)
Press the Nxt or Prv keys to move through the Set-up Menu to the desired item, then press Ent to
select the menu item.
VIRGINIA CONTROLS, INC. MVFAC-3000 User Manual, Rev. 2.11 Page 101
NOTE: An internal memory check is done on each power up. So if a corrupted memory
is detected, a factory reset will be done automatically.
WARNING: On standard jobs, the factory reset will return the settings and features to
a generic default. The actual settings and values for the specific job must now be
entered to customize the job for the particular application. To determine if a
particular controller has a standard program, go to the banner screen. If the value in
the lower left of the screen is the Virginia Controls Job Number, then the chip is
specific for that job, and a factory reset will load the values for that job. If the value is
not the job number, (it will start with “DSS”, “DDS”, “DAS”, or something similar) then
the program is a standard, and the actual values for the job need to be entered. These
values are provided with the controller in the schematic, and are based on the
requirements of the job, as conveyed to Virginia Controls.
NOTE: The Password “911” is required to gain access to this menu selection, unless the
password has already been entered in another sequence.
Press Nxt to go to the next setting, without changing the current setting.
Press Prv to go to the previous setting, without changing the current setting.
Press a numeric key ( 0 - 9 ) to enter a new value. (The decimal point key . is not used)
Press Ent after entering a new value to load the new value into memory. (The message “VALUE
SAVED!” is displayed for 1 second, indicating the new entry has been accepted, then the display will
show the setting and the new value) If Nxt, Prv or Esc is pressed after entering a new value, the new
value will NOT be stored in memory.
Press Esc to go back to the Setup Menu.
VIRGINIA CONTROLS, INC. MVFAC-3000 User Manual, Rev. 2.11 Page 102
If an incorrect value is entered, press Esc to clear the value before it is accepted, then enter the correct
value; or press Nxt or Prv to move to the next setting. If the value was already entered, by pressing
Ent, then press Nxt or Prv to return to the incorrect setting, enter the proper value, and press Ent.
• Number of I/O Boards - (Display shows "NUM.OF IO BOARDS") This is the number of Input and
Output Boards that the CPU will address, and is a value between 1 and 8. If a value out of this range
is entered, then a default value of 2 will be entered when the car is put back into the Run Mode.
• Number of Landings - (Display shows "NUMBER OF LDGS") This is the number of landings that the
controller can serve, and is a value between 2 and 8. If the controller is set up to serve future
landings, then this value can be used to temporarily cut off future upper landings. This value also
determines which floor the controller will reset to when a top landing reset is initiated with a pulsing
selector.
• Main Fire Landing - (Display shows "MAIN FIRE LDG") This is the number corresponding to the Main
Fire Landing, and is a number between 1 and 8. The value set is based on the bottom floor being
"1", the 2nd floor is "2" etc., even if this does not match the building designations.
CAUTION: If it is set to a value greater than the number of landings served, the car will
go to the top landing, but it will not open its doors.
• Alternate Fire Landing - (Display shows "ALT. FIRE LDG") This is the number corresponding to the
Alternate Fire Landing, and is a number between 1 and 8. The value set is based on the bottom floor
being "1", the 2nd floor is "2" etc., even if this does not match the building designations.
CAUTION: If it is set to a value greater than the number of landings served, the car will
go to the top landing, but it will not open its doors.
• Home Landing (SIMPLEX ONLY) - (Display shows "HOME LANDING") This is the home landing for a
simplex car. The car can be selected to home to this landing, if desired. This value can be set to any
valid landing, as determined by the number of landings setting.
• Dispatch Landing (DUPLEX ONLY) - (Display shows "DISPATCH LDG") This is the dispatch landing for
duplex systems. One car will always home here. This value can be set to any valid landing, as
determined by the number of landings setting.
• Upper Home Landing (DUPLEX ONLY) - (Display shows "UPPER HOME LDG") This is the home
landing for the free car in a duplex system. The free car can be selected to home to this landing, if
desired. This value should be set to be inside the upper zone, as determined by the Low Zone
assignments shown later in the features settings.
• Front Door Code - (Display shows "FRONT DOOR CODE") This is a binary coded value used to select
which front openings are enabled. Each bit corresponds to a landing. If the bit for a landing is on,
then the front doors at that landing will be enabled. Use the chart shown in the schematic to
VIRGINIA CONTROLS, INC. MVFAC-3000 User Manual, Rev. 2.11 Page 103
determine the proper value. Add up the value for each floor to determine the total value for this
setting. A value of “255” will enable the front doors at all floors.
• Rear Door Code - (Display shows "REAR DOOR CODE ") This is a binary coded value used to select
which rear openings are enabled. Each bit corresponds to a landing. If the bit for a landing is on,
then the rear doors at that landing will be enabled. Use the chart in the schematic to determine the
proper value. Add up the value for each floor to determine the total value for this setting. A value
of “0” will disable the rear doors at all floors.
• Low Zone Code (DUPLEX ONLY) – (Display shows “LOW ZONE CODE”) This value determines which
floors are in the Low Zone. The floors will normally be served by the Lobby car, other floors will
normally be served by the Free car. Each bit corresponds to a landing. If the bit for a landing is on,
then that floor is in the Low Zone. Use the chart shown in the schematic to determine the proper
value. Add up the value for each floor to determine the total value for this setting. A value of “3”
will set the Low Zone as the bottom two floors.
The Bit Features are multiple features combined into several settings. Each setting consists of 8 features
that can be turned on or off individually. Refer to the sheet MH-3000 Settings in the schematic for a
breakdown of each setting. A description of the standard features that may be part of the Bit Features
are listed in a following section, after the standard settings.
• Bit Features # 1 - (Display shows "BIT FEATURES # 1") This is a binary coded value used to select
various features as shown in the chart in the schematic on the MH-3000 SETTINGS sheet. Each bit
corresponds to a different feature. If the bit for a feature is on, then that feature is enabled. Use
the chart to determine the proper value. Add up the value for all the features that should be
enabled to determine the total value for this setting.
• Bit Features # 2 - (Display shows "BIT FEATURES # 2") Similar to Bit Features #1.
• Bit Features # 3 - (Display shows "BIT FEATURES # 3") Similar to Bit Features #1.
• Bit Features # 4 - (Display shows "BIT FEATURES # 4") Similar to Bit Features #1.
• Bit Features # 5 - (Display shows "BIT FEATURES # 5") Similar to Bit Features #1.
• Bit Features # 6 - (Display shows "BIT FEATURES # 6") Similar to Bit Features #1.
• Bit Features # 7 - (Display shows "BIT FEATURES # 7") Similar to Bit Features #1.
• Bit Features # 8 - (Display shows "BIT FEATURES # 8") Similar to Bit Features #1.
• Bit Features # 9 - (Display shows "BIT FEATURES # 9") Similar to Bit Features #1.
• Bit Features # 10 - (Display shows "BIT FEATURES # 10") Similar to Bit Features #1.
• Custom Time #0.1 – (Display shows “CUSTOM TIME #0.1”) This is a reserved value that is not
assigned, but may be assigned a function for a specific job. The time base for this timer is not
preset, and may change depending on its use. Refer to the Settings sheet in the schematic to see if
and how this setting is used.
• Custom Time #0.2 – (Display shows “CUSTOM TIME #0.2”) Similar to Custom Time #0.1.
• Custom Time #0.3 – (Display shows “CUSTOM TIME #0.3”) Similar to Custom Time #0.1.
• Custom Time #0.4 – (Display shows “CUSTOM TIME #0.4”) Similar to Custom Time #0.1.
VIRGINIA CONTROLS, INC. MVFAC-3000 User Manual, Rev. 2.11 Page 104
• # of Fault Resets – (Display shows “# Fault Resets.”) This is the number of automatic fault resets
allowed. The controller can be set up to automatically reset the Running Timer Fault and the
Start/Stop Sequence Fault. This can be done for the number of times set by this setting. The count
of automatic resets is reset if the car is put on Inspection, or the power is cycled, or the car runs
without a fault for 40 minutes.
• Door Time, Hall (in tenths of a second) - (Display shows "DOOR TIME, HALL") This is the time in
tenths of a second, that the doors will remain open, after they have opened fully, when the car has
stopped in response to a hall call. After this time, the doors will start to close.
NOTE: If a car call is entered while the doors are open, the door time will be reduced
to the "Door Time, Car" setting. If the Door Close Button is pressed while the doors
are open, the door time will be reduced to the "Door Time, Short" setting. This setting
is normally 50, for a time of 5 seconds.
• Door Time, Car (in tenths of a second) - (Display shows "DOOR TIME, CAR") This is the time in tenths
of a second, that the doors will remain open, after they have opened fully, when the car has stopped
in response to a car call only. After this time, the doors will start to close.
NOTE: If a car call is entered, or the Door Close Button is pressed, while the doors are
open, the door time will be reduced to the "Door Time, Short" setting. This normal
setting is 20, for a time of 2 seconds.
• Door Time, Short (in tenths of a second) - (Display shows "DOOR TIME, SHORT") This is the time in
tenths of a second, that the doors will remain open, after they have opened fully, when the doors
have reopened in response to a Door Open Button/Safety edge/Electric Eye/Infra-red Curtain, and
no hall call is entered. After this time, the doors will start to close. The normal setting is 10, for a
time of 1 second.
• Leveling Cutout Time (in tenths of a second) - (Display shows "LEVELING LOCKOUT") This is the time
in tenths of a second that the leveling switches are cut out after the start of a floor to floor run. It
allows the external relays to energize and lock out the leveling switches externally. The normal
setting is 20, for a time of 2 seconds.
• Back Call Delay (DUPLEX ONLY) (in tenths of a second) - (Display shows "BACK CALL DELAY") This is
the time in tenths of a second that the back call signal will be delayed before letting the other car
respond to calls behind this car. The normal setting is 10, for a time of 1 second.
• Custom Time #1.1 (in tenths of a second) - (Display shows "CUSTOM TIME #1.1") This is a reserved
value that is not assigned, but may be assigned a function for a specific job.
• Custom Time #1.2 (in tenths of a second) - (Display shows "CUSTOM TIME #1.2") See Custom Time #
1.1
• Custom Time #1.3 (in tenths of a second) - (Display shows "CUSTOM TIME #1.3") See Custom Time #
1.1
• Shutdown Time (in seconds) - (Display shows "SHUTDOWN TIME") If the car runs up without
passing a floor for this time, then shutdown will be initiated. The car will stop, and run down to the
bottom landing, and cycle its doors. It will then be shut down. The car can be returned to service by
cycling the Inspection Switch, or the Main Line Disconnect Sw. The normal setting is 25 seconds.
VIRGINIA CONTROLS, INC. MVFAC-3000 User Manual, Rev. 2.11 Page 105
• Door Nudging Time (in seconds) - (Display shows "NUDGING TIME") This is the time delay before
initiating door close nudging, if that feature is provided. A call must be registered, and the car must
be in automatic operation. The timer is reset when the doors get fully closed, or when the car starts
a floor to floor run. The normal setting is 25 seconds.
• Electric Eye Cutout Time (in seconds) - (Display shows "EYE CUTOUT TIME") This is the time delay
before cutting out the Electric Eye Input, after it has been continuously energized. It is reset when
the car runs to the next floor. The normal setting is 20 seconds.
• Homing Delay Time (in seconds) - (Display shows "HOMING DELAY") This is the delay before homing
a car to the home landing, after it has answered all calls, and is sitting with its doors closed. The
normal setting is 10 seconds.
• Car Stuck Time (in seconds) - (Display shows "CAR STUCK TIME") This is the time delay before calls
at the same landing as the car are disabled, so that the car can answer other registered calls. This
operates as a stuck button timer. The normal setting is 15 seconds.
• Door Stuck Time (in seconds) - (Display shows "DOOR STUCK TIME") This is the time delay before
stopping a door open or close cycle. The normal setting is 20 seconds
• Door Stuck Reset Time (in seconds) - (Display shows "DOOR RESET TIME") This is the time that the
doors are held open after failing to close properly, before retrying to close. The normal setting is 10
seconds.
• Delay Before Canceling Independent Service on Fire Service - (Display shows "KILL IDS ON EFS1")
This is the time delay before Independent Service is cut out, when Fire Service Phase 1 is initiated.
This feature can be modified by the Bit Features described above that determine if and when
Independent Service is cut out on Fire Service. The normal setting is 30 seconds.
• Door Close Delay Time on Fire Service (in seconds) - (Display shows "DR CLOSE ON FIRE") This is the
delay before closing the doors after the car has returned on Fire Service Phase 1 to the Main Ldg. It
may be required, depending on the Fire Code used.
• The normal setting is 30 seconds.
• Call Help Time (DUPLEX ONLY) (in seconds) - (Display shows "CALL HELP TIME") This is the amount
of time a hall call can be registered before the other car not assigned this call will respond to the
call. The normal setting is 30 seconds.
• Non Interference Time (SAPB ONLY) (in seconds) - (Display shows “NON INTERFERENCE”) This is the
time that the In Use Light will remain on after the car has answered a call and cycled its doors. Hall
Call Buttons will be disabled during this time. The normal setting is 6 seconds.
• Custom Time #2.1 (in seconds) - (Display shows "CUSTOM TIME #2.1") This is a reserved value that
is not assigned, but may be assigned a function for a specific job.
• Custom Time #2.2 (in seconds) - (Display shows "CUSTOM TIME #2.2") See Custom Time # 2.1
• Custom Time #2.3 (in seconds) - (Display shows "CUSTOM TIME #2.3") See Custom Time # 2.1
• Position Indicator Cutout Time (in tens of seconds) - (Display shows "PI CUT OUT TIME ") This is the
time delay before turning off the Position Indicators, after the car has become idle. If the doors are
opened, or the car starts in response to a call, then the Position Indicators will turn on again. The
VIRGINIA CONTROLS, INC. MVFAC-3000 User Manual, Rev. 2.11 Page 106
normal setting is 30, for a time of 5 minutes. To keep the PI’s on at all times, enter a value of “0” for
the Cutout Time.
• Custom Time #3.1 (in tens of seconds) - (Display shows "CUSTOM TIME #3.1") This is a reserved
value that is not assigned, but may be assigned a function for a specific job.
• Custom Time #3.2 (in tens of seconds) - (Display shows "CUSTOM TIME #3.2") See Custom Time #
3.1
• Custom Time #3.3 (in tens of seconds) - (Display shows "CUSTOM TIME #3.3") See Custom Time #
3.1
Some installations require specific settings or features that are not included in the standard program. In
this case, a separate sheet (or sheets) will be provided that describe the operation of these settings or
features, and what the factory default settings are.
VIRGINIA CONTROLS, INC. MVFAC-3000 User Manual, Rev. 2.11 Page 107
• No Timed Kill of Independent on Fire Service – Turn this feature on to prevent Fire Service from
overriding Independent Service. Independent Service must be turned off or the doors closed by the
operator to allow the car to run on Fire Service.
• Never kill Indep. on Fire Service – Turn this feature on to prevent Fire Service from overriding
Independent Service. Independent Service must be turned off to allow the car to run on Fire
Service.
• Main Fire Landing at Rear Opening – Turn this feature on to use the rear opening at the designated
fire opening, instead of the front opening. If there is only one opening at the designated fire
landing, then this feature will have no effect.
• Alternate Fire Landing at Rear Opening – Turn this feature on to use the rear opening at the
alternate fire opening, instead of the front opening. If there is only one opening at the alternate fire
landing, then this feature will have no effect.
• Disable Shunt Trip on Fire Service Phase 2 – Turn this feature on to disable Shunt Trip operation
when the car is on Fire Service Phase 2.
• Enable Shunt Trip on Inspection – Turn this feature on to enable Shunt Trip operation when the car
is on Inspection.
• Disable ECReturn Latch on 2000 Fire Code – Turn this feature on to disable the holding circuit on
Fire Service Phase 2 Return on 2000 (or later) Code. This allows the Return mode to be cancelled by
turning the Fire Switch to the “On” position. Check the appropriate code to see if this is required or
allowed.
• Enable Pulsing Selector (off=Floor Sws) – Turn this feature on to enable a pulsing floor selector,
rather than individual Floor Switches. With a pulsing arrangement, there is an up or a down pulse to
change floors. Additionally at the terminal landings, enabling the up pulse input and the door zone
input will reset to the top landing, while energizing the down pulse and door zone will reset the floor
position to the bottom landing.
• Enable Separate Call I/O (4 Wire Calls) – Turn this feature on to enable separate wiring for the
inputs and outputs for the car and hall calls. If this feature is disabled then the car and hall call
inputs are connected to the corresponding outputs.
• Enable Door Check Feature – Turn this feature on to enable the Door Check feature. This allows the
status of the Car Door and the Hall Doors to be checked according to the appropriate codes.
• Enable Redundancy Fault Checking – Turn this feature on to enable 2000 (or later) code redundancy
fault checking. This enables the redundancy fault timers, and checks the leveling inputs and running
inputs for stuck relays or contacts, according to the 2000 (or later) code.
• Use Car Lantern outputs for Hall Lanterns – Turn this feature on to use the Car Lantern outputs as
Hall Lanterns. If there are only two landings, then the Hall Lanterns can be connected directly to the
Car Lantern outputs. If there are more than two landings, then additional external relays are needed
to enable the appropriate lantern at each floor.
• Do Not Run On Fire Service and BORIS – Turn this feature on to prevent the car from running if Fire
Service is enabled while on battery backup operation.
VIRGINIA CONTROLS, INC. MVFAC-3000 User Manual, Rev. 2.11 Page 108
• Do Not Run on Fire Service and Shutdown – Turn this feature on to prevent the car from running if
Fire Service is enabled while on shutdown. If this feature is not enabled the car will be allowed to
run down on Fire Service and shutdown.
• Allow Door Zone Fault on Fast Speed – Turn this feature on to allow the Door Zone Fault to be
initiated if the car is running fast speed and the input is on. False trips are prevented by the Leveling
Cutout Timer, which prevents a fault as the car starts, and before the FSU/FSD relays energize.
• Allow Stop at Upper Floor on Shutdown – Turn this feature on to allow the car to stop at an upper
floor on shutdown if it is the main floor. Check with the appropriate codes to see if this is allowed or
required.
• Enable CKO on Independent – Turn this feature on to energize the CKO Car Call Cutout Override
output on Independent Service. This will allow car calls to be registered without the use of access
keys.
• Fire Sensors are Normally Open Inputs – Turn this feature on if the Smoke Sensor inputs are
normally open on normal operation, and close when a fire is detected. The default is to use Smoke
Sensors that are closed on normal operation and open when a fire is detected.
• Dir Indicators show actual direction on Attend. – Turn this feature on to make the Attendant
Direction Indicators show the direction that the car will run next. If this feature is not enabled then
they will show whether there are calls registered in either direction. For example, with this feature
off, and the car at an intermediate floor with calls above and below the car, then both Attendant
Direction Indicators would be on, since there are calls above and below the car. If the feature was
enabled, then the indicators would be the same as the normal Direction Indicators, and only one
indicator would be on, depending on which direction had actually been selected.
• Med Emerg Buzzer on Independent only – Turn this feature on to change the operation of the
Medical Emergency Buzzer output. With the feature disabled (factory default) the buzzer will come
on while the car is returning to the Medical Emergency floor in response to the hall Medical
Emergency Switch. If the feature is enabled, the buzzer will come on if the car is on Independent
Service and a hall Medical Emergency Switch is turned on. This alerts the operator to release the
car.
• Always Enable DOB at Front Openings – Turn this feature on to allow the Front Door Open Button
to always open the doors at selective openings (where there is a front and rear opening at the same
landing). With this feature disabled, the doors must have been opened, or still be open, for the Door
Open Button to operate. This allows a measure of security at these landings.
• Always Enable DOB at Rear Openings – Turn this feature on to allow the Rear Door Open Button to
always open the doors at selective openings (where there is a front and rear opening at the same
landing). With this feature disabled, the doors must have been opened, or still be open, for the Door
Open Button to operate. This allows a measure of security at these landings.
• Disable Non-Shutdown Faults in Fault Log – Turn this feature on to disable faults from being logged
into the Fault Log that are not shutdown faults. This keeps the fault log clear of non-essential faults.
The following faults will not be logged if this feature is enabled: TDOPEN, TDCLOSE, TDOPN-R,
TDCLO-R, CARSTUK, DRCONTS, OUT-DZ, COMMFLT, FIRE, MRSMOKE, SHUNT, FLOOD
• Flood Return Ldg is 3 (not 2) – Turn this feature on to make the car return to the third landing from
the bottom if Flood Service is initiated. The default floor is the second floor from the bottom.
VIRGINIA CONTROLS, INC. MVFAC-3000 User Manual, Rev. 2.11 Page 109
• Flood Return Ldg is Top Ldg (not 2) – Turn this feature on to make the car return to the top landing
if Flood Service is initiated. The default floor is the second floor from the bottom.
• Flood overrides Independent, Attendant, Med Emerg – Turn this feature on to allow Flood Service
to override Independent Service, Attendant Operation and Medical Emergency Operation. If this
feature is not enabled, then the car will remain under the control of the operator if the Flood Service
input is energized.
• Flood overrides Shutdown (Low Oil, Rev. Phase, etc.) – Turn this feature on to allow Flood Service
to override shutdown functions that would normally return the car to the bottom landing. The car
will still not be able to run up, but Flood Service will remain in effect even though a shutdown
feature is in effect.
• Do Not Run on Flood and BORIS – Turn this feature on to prevent the car from running if Flood
Service and BORIS Battery Backup operation are initiated at the same time.
• Do Not Run Down Below Main on Flood and Shutdown – Turn this feature on to prevent the car
from running if it is at or below the Main Floor and the car is on Flood Service and Shutdown
Operation.
• Fire Service Overrides Flood Operation – Turn this feature on to allow Fire Service to override Flood
Service. The car will return to the Main Fire Floor, even if that is the bottom landing.
• Flood Operation Overrides Hall Fire Service – Turn this feature on to allow Flood Service to override
Fire Service, and cause the car to leave the bottom landing, even if that is the designated Fire
landing. If this feature is not set, then whichever feature (Fire Service or Flood Service) is initiated
first will take precedence.
• Disable Non-Shutdown Faults in the Fault Log – Turn on to prevent non-shutdown faults from being
logged in the fault log. This will prevent faults TDOPEN, TDCLOSE, TDOPN-R, TDCLO-R, CARSTUK,
DRCONTS, OUT-DZ, COMMFLT, FIRE, MRSMOKE, SHUNT, FLOOD from being logged.
• Enable Shunt Trip Feature – Turn on to enable the Shunt Trip feature. The input and output for this
feature must have been assigned for this feature to work properly. This feature can be turned off to
disable the Shunt Trip if it was supplied, but is not required. Shunt Trip operation can be
accomplished externally to the controller, if desired.
• Enable Rear Door Open Output – Turn on to enable the Rear Door Open output at point 8 on the
first output board.
• Enable RD (RearDoor) Output – Turn on to enable the RD output at point 8 on the first output
board. This is used with front and rear doors only.
• Enable 1UL - 4DL Hall Lantern Outputs – Turn on to enable specific Hall Lantern outputs. The
outputs for this feature must have been assigned for this feature to work properly.
• Enable Nudging Output – Turn on to enable the Nudging Output. This is not required for Nudging
Operation, as the Nudging Buzzer output is the only output specifically required. The output for this
feature must have been assigned for this feature to work properly.
• Enable CKO Output – Turn on to enable the CKO, Car Call Cutout Override, output. The output for
this feature must have been assigned for this feature to work properly.
VIRGINIA CONTROLS, INC. MVFAC-3000 User Manual, Rev. 2.11 Page 110
• Enable PI Blanking Fire Output – Turn on to use the Fire Light output as a Position Indicator Blanking
output.
• Enable Car To Lobby Input – Turn on to enable the Car To Lobby Shutdown inputs. The input for this
feature must have been assigned for this feature to work properly.
• Enable Park With Doors Open – Turn on to make the car park with the doors open at the Main
Landing.
• Enable Park With Doors Open at All Ldgs – Turn on to make the car park with the doors open at all
landings.
• Manual Reset on Redundancy and Door Zone Faults - Enable this bit feature to require Redundancy
and Door Zone faults to be reset manually. Cycling power will not reset those faults. This feature is
used in conjunction with the Latched Fault feature described above.
• Disable Reset at Intermediate Floors - Enable this bit feature to disable position resets at
intermediate floors. The car will still reset at terminal landings, based on the Door Zone input and
the Up or Down Slowdown inputs.
• Disable Fault Latch Feature – Turn this feature on to disable the feature that latches faults. Faults
are latched for compliance with the 2010 and later codes. If this feature is NOT turned on, then
faults must be reset by jumping the Fault Reset Input or by turning on Sw4 on the CPU Dip Sw block.
With this feature on, faults can be reset by cycling power or by cycling the Inspection Sw.
VIRGINIA CONTROLS, INC. MVFAC-3000 User Manual, Rev. 2.11 Page 111
• Only this car serves Rear Calls at Ldg 1 – Turn this feature on if the other car in the duplex does not
serve this opening, but this car does.
• Only this car serves Rear Calls at Ldg 2 – Turn this feature on if the other car in the duplex does not
serve this opening, but this car does.
• Only this car serves Rear Calls at Ldg 3 – Turn this feature on if the other car in the duplex does not
serve this opening, but this car does.
• Only this car serves Rear Calls at Ldg 4 – Turn this feature on if the other car in the duplex does not
serve this opening, but this car does.
• Only this car serves Rear Calls at Ldg 5 – Turn this feature on if the other car in the duplex does not
serve this opening, but this car does.
• Only this car serves Rear Calls at Ldg 6 – Turn this feature on if the other car in the duplex does not
serve this opening, but this car does.
• Only this car serves Rear Calls at Ldg 7 – Turn this feature on if the other car in the duplex does not
serve this opening, but this car does.
• Only this car serves Rear Calls at Ldg 8 – Turn this feature on if the other car in the duplex does not
serve this opening, but this car does.
• HSC START DELAY. (Value is in tenths of a second) This sets the delay after the start of a run before
the speed is checked for movement, and for proper direction.
VIRGINIA CONTROLS, INC. MVFAC-3000 User Manual, Rev. 2.11 Page 113
• ETS FAULT DELAY. (Value is in tenths of a second) This sets the delay before an Emergency Terminal
Speed fault is initiated. The car will shut down, and the cause of the fault will be logged.
• UCM FAULT DELAY. (Value is in tenths of a second) This sets the delay before an ETSD/UCM
Monitoring Fault is logged. It should be set long enough to prevent nuisance faults.
• 1FR HOLD DELAY. (Value is in tenths of a second) This sets the delay to hold the 1FR output when
the car is running full speed and slows down. It allows the car to pass the leveling zone of the
previous floor, so that it stops at the correct floor.
• ENABLE ETSD/UCM BOARD. Enable this bit feature when the ETSD/UCM Board is used. It enables
the Rope Brake check and Redundancy Faults used with the ETSD/UCM Board.
• DISABLE UCM BOARD REDUNDANCY FAULTS. Enable this bit feature to disable Redundancy Faults
from the UCM Board.
• ENABLE HIGH SPEED COUNTER. Enable this bit feature when using an external PLC with a High
Speed Counter. This can be turned off temporarily during setup to disable HSC faults.
• ENABLE EMERGENCY TERMINAL SLOWDOWNS (ETS). Enable this bit feature when using an ETS
system with the ETSD/UCM Board.
• ENABLE ONE AND TWO FLOOR RUN SPEEDS. Enable this bit feature when a separate speed is
provided for One Floor Runs.
• ENABLE LONG FLOOR FROM ? to ?. Enable one of these bit features when there is a long floor at the
specified floors. The car will then run full speed between those two floors.
NOTE: The Password “911” is required to gain access to this menu selection, unless the
password has already been entered during another sequence.
Press Nxt to go to the next feature, without changing the current feature.
Press Prv to go to the previous feature, without changing the current feature.
Press Aux to toggle the feature between on/enabled or off/disabled.
(The keys 0 - 9 and . are not used)
Press Ent after selecting a new value to load the new value into memory. (The message “VALUE
SAVED!” is displayed for 1 second, to indicate the new value has been accepted.) If Nxt, Prv or Esc is
pressed after entering a new value, the new value will NOT be stored in memory.
VIRGINIA CONTROLS, INC. MVFAC-3000 User Manual, Rev. 2.11 Page 114
Press Esc to go back to the Setup Menu.
NOTE: Door Nudging operation requires an optional Nudging Buzzer output and
Reduced Speed Door Closing output.
• One Stroke Down Lanterns - (Display shows "1 STROKE DN LANT") The lanterns are normally
provided with two strokes for the down direction. Enable this feature to provide only one stroke for
the down direction.
• Slow Speed on Inspection - (Display shows "SLOW ON INSPECT") Enable this feature to run slow
speed on Inspection. This is normally required if the car speed is 125fpm or above.
• Proximity Detector - (Display shows "PROXIMITY DETECT") Enable this feature if a Proximity
Detector (such as an infra-red curtain) is used. Enabling this feature will cause the Safety Edge input
to be disabled on Fire Service, and the Door Nudging feature to be initiated while the doors are
closing on Fire Service. The Proximity Detector may be connected to the Safety Edge Input or the
Electric Eye Input, as desired. (The Electric Eye Input is subject to the Timed Electric Eye Cutout and
Nudging, whereas the Safety Edge Input is not.)
NOTE: Door Nudging operation requires an optional Nudging Buzzer output and
Reduced Speed Door Closing output.
• Short Floor - (Display shows "SHORT FLOORS") The Short Floor selection applies to installations with
Floor Switches or Pulsing Switches where the floor height is less than twice the slowdown distance,
but more than the slowdown distance plus the leveling zone. If Floor Switches are used, then the
Short Floor Setting should be enabled if the Floor Switches overlap at any floor. If Pulsing Switches
are used, then the Short Floor Setting should be enabled if the top of any Up target is BELOW the
bottom of the Down target for the floor below. With Floor Switches or a Pulsing Selector, if the
VIRGINIA CONTROLS, INC. MVFAC-3000 User Manual, Rev. 2.11 Page 115
slowdown overlaps the leveling zone of the adjacent floor, then special short floor circuitry is
required, and this setting will not normally apply. (Check for specific instructions for the job.)
• Enable Homing - (Display shows "ENABLE HOMING" on Simplex, or "HOME #2 TO MAIN" on Duplex)
Enable this feature to enable the homing feature on a Simplex. This will cause the car to home to
the Home Landing, when it has been idle for the adjustable Homing delay time.
NOTE: On a Duplex, one car will always home to the Dispatch Main Landing, and, if
this feature is set, then the FREE car will also home to the Dispatch Main Landing.
• Enable Free Car Homing (Duplex Only) - (Display shows "HOME TO HI ZONE") Enable this feature to
home the free car to the Upper Home Landing. If this is not set, then the car will remain where it
last stopped.
Some installations require specific settings or features that are not included in the standard program. In
this case, a separate sheet (or sheets) will be provided that describe the operation of these settings or
features, and what the factory default settings are.
CURRENT TIME
12:22 11/13/01
If these are correct, then press Esc to return to the Setup Menu.
VIRGINIA CONTROLS, INC. MVFAC-3000 User Manual, Rev. 2.11 Page 116
If you want to change the time and/or date, then press any other key to continue with the next menu
item.
You will be prompted to enter the year (00-99), month (1-12), date (1-31), hour (0-23), and minute (0-
59).
In each case, press Ent to accept the current value, or enter the correct value then press Ent.
If an incorrect value is entered, just enter the correct value again, and press Ent. If you press Esc during
this sequence, then the time and date will not be updated, and the display will return to the setup menu.
After all the data has been entered, the screen will display the new time and date, with the prompt
“Enter to accept”.
ENTER TO ACCEPT
12:23 11/13/01
Press Ent to accept the values. At this point the new time and date will be accepted, and the seconds
value will be set to zero. If you press Esc, then you will return to the setup menu without entering the
new time and date.
The battery is required to keep the real time clock running when power is turned off. Consequently, the
real time clock will need to be reset when the battery is changed.
VIRGINIA CONTROLS, INC. MVFAC-3000 User Manual, Rev. 2.11 Page 117
The password can be entered by pressing the 7 key when the display is activated from the blank screen
(after a power cycle), or when the "VA.CONTROLS" banner is displayed (after pressings Esc from the Run
Mode menus). This allows the password to be entered without stopping the controller.
The password can be given to all authorized personnel, which is those who would need to change
settings or features on the controller.
WARNING: Use great care in changing settings and features, as this may cause
unexpected operation. Make sure you understand the consequences of any changes
before making them.
WARNING: When the test feature is activated, outputs may be turned on that may
cause the car to move, the doors to operate and other signals to come on. It is the
operator’s responsibility to make sure an unsafe condition does not exist. Take any
and all the necessary precautions to prevent a dangerous situation.
This could include:
• unplugging the terminal blocks on the output boards (this is strongly recommended),
• removing the fuses in the output circuits,
• opening the appropriate safety devices.
While the test feature is activated, each input that is on will turn on the corresponding output on the
same board (Input Point 1 will turn on Output Point 1; Input Point 2 will turn on Output Point 2 etc.).
This allows the inputs and outputs to be tested by jumping the desired input on, and verifying that the
proper output comes on. Note: The outputs are updated once every tenth of a second, so there may be
a slight delay in turning on the output after the input has been energized.
VIRGINIA CONTROLS, INC. MVFAC-3000 User Manual, Rev. 2.11 Page 118
WARNING: Be very careful when jumping the inputs on. Make sure you do not jump
to the common on the input terminal strips. This will blow a fuse, and could damage
the input board components. The input commons are the first and sixth terminals
from the left on the input terminal strip (see the schematic).
While the outputs are being tested, a meter can be used to verify that each output is actually coming on.
The test will be stopped, and the outputs turned off, when any key is pressed.
VIRGINIA CONTROLS, INC. MVFAC-3000 User Manual, Rev. 2.11 Page 119
8. Controller Nomenclature
The symbols listed below are typical symbols. Refer to the schematic for all relays and contactors
actually used on a particular job. The function of the relay or contactor will be show on the schematic by
its coil.
SYMBOL DESCRIPTION
AF, BF, CF, etc. BINARY CODED FLOOR POSITION RELAYS
BK1, BK2 BRAKE CONTACTORS
C DOOR CLOSE RELAY
D / D1-2, DX DOWN RUN REVERSING CONTACTOR / RELAYS
DC DOOR CLOSED RELAY
DL DOWN LEVEL RELAY
DOLX DOOR CHECK RELAY
DZ DOOR ZONE RELAY
ES, EST EMERGENCY STOP SWITCH RELAY
ESB EMERGENCY STOP SWITCH BY-PASS RELAY
FL, FLR FIELD LOSS RELAYS
FS, FSX FAST SPEED RUN CONTACTOR OR RELAYS
IAS, IAX INSPECTION ACCESS RELAY
INS INSPECTION RELAY
LC LEVELING CUTOUT RELAY
LV LEVELING RELAY
MG, MG1-2 MOTOR GENERATOR CONTACTOR, RELAYS
N DOOR CLOSE NUDGING RELAY
O DOOR OPEN RELAY (IN MODSS ON TOP OF THE CAR, IF USED)
OSF OVERSPEED FAULT RELAY
P, PP, PX POTENTIAL CONTACTOR, RELAY
RDY DRIVE READY TO RUN RELAY
RU MOTOR RUN CONTACTOR (WYE-DELTA START)
RUX / RUXP M.G. SET RUNNING CONTACTOR / TIMER
SAF1-2 SAFETY CIRCUIT RELAYS
STR MOTOR START CONTACTOR (WYE-DELTA START)
SU SUICIDE CONTACTOR
TRU WYE-DELTA MOTOR RUN RELAY (WYE-DELTA START)
TRUP WYE-DELTA MOTOR RUN TIMER (WYE-DELTA START)
U / U1-2, UX UP RUN REVERSING CONTACTOR / RELAYS
UD CAR RUNNING RELAY
UDT, UDTX CAR RUNNING DELAY DROP OUT RELAYS
UL UP LEVEL RELAY
VR VOLTAGE RELAY (OPTIONAL)
VIRGINIA CONTROLS, INC. MVFAC-3000 User Manual, Rev. 2.11 Page 120
9. Parts List
ITEM DESCRIPTION MANUFACTURER PART NO
RELAYS
A1 4PDT, 120VAC, PLUG-IN RELAY Idec or equivalent RU4S-A110
A2 4PDT, 110VDC, PLUG-IN RELAY Idec or equivalent RU4S-D110
A3 SURFACE MOUNT RELAY SOCKET P&B 27E894
A4 TIMER, 0-102.3 SECONDS AIRTRONICS THCU102S3E
A5 3PDT, 120VAC, PLUG-IN RELAY P&B or equivalent KUP-14A35
MICRO-PROCESSOR
D1 MICROPROCESSOR CPU BOARD V.C. MH3000-CPU
D2 16-IN/16-OUTPUT MODULE V.C. MH3000-16IO
D3 KEYPAD V.C. MH3000-KEYPAD
D4 LCD SCREEN V.C. MH3000-LCD
D5 CPU BATTERY PANASONIC CR2032
MISCELLANEOUS
G1 NEONS, ON RELAY PANEL I.D.I. 1030
G2 VARISTORS (SEE SCHEMATIC) G.E. V150LA2
G3 PUSHBUTTON, ON RELAY PANEL ARROW-HART 80511E
G4 TOGGLE SWITCH, ON RELAY PANEL ARROW-HART 82601
G5 10 POSITION SELECTOR SWITCH CENTRALAB PA1001
All parts are commercially available from the manufacturer, or from Virginia Controls Inc. (ask for the
Parts Department or send an email to parts@vacontrols.com). Parts are subject to change without
notice. Consult Virginia Controls, Inc., for current pricing information. Non-standard material is
identified on the schematic.
VIRGINIA CONTROLS, INC. MVFAC-3000 User Manual, Rev. 2.11 Page 122
10. Troubleshooting Suggestions
Troubleshooting is similar to any other controller, and has several features to speed up determining the
cause of any problem. No special knowledge of the operation of the microprocessor is required to be
able to troubleshoot it.
A safety relay interface is provided to prevent dangerous operation due to a failure of the
microprocessor. It is possible that the microprocessor may turn on an output point, yet the field safety
switches may prevent the associated device from energizing.
For example, if the up run output energizes, but the up normal switch is open, then the up run relays will
not energize.
VIRGINIA CONTROLS, INC. MVFAC-3000 User Manual, Rev. 2.11 Page 123
10.1.1 Troubleshooting I/O Board Communication Problems
If the IOFAULT error message is shown on the Status Screen, there are several ways to determine which
board is causing the fault.
The communication light on the I/O board will usually indicate the problem. The normal status is for
that light to blink once. If it blinks 2 or more times then the board is detecting an error in the
communication it is receiving, as described in the section on I/O Boards, Board Status LED.
Additionally the CPU can be monitored to check its communication with the I/O boards.
Address 0051 and 0052 should both be 00, but will show a code corresponding to the board that is not
communicating with the CPU. Using the SHOW INT MEMORY screen, navigate to address 0050, then
check the value in 0051 (refer to the example shown below with address 0051 in bold).
0050 04 03 03 04
0054 00 00 00 00
In the example shown here, a fault code “03” is seen in 0051. This indicates there is a communication
problem with boards 1 and 2. Refer to the chart below for the codes for the board faults. The top
section shows the boards for the right code number, and the bottom section shows the codes for the left
code number.
Right
Number x0 x1 x2 x3 x4 x5 x6 x7 x8 x9 xA xB xC xD xE xF
Board1 OK Fault OK Fault OK Fault OK Fault OK Fault OK Fault OK Fault OK Fault
Board2 OK OK Fault Fault OK OK Fault Fault OK OK Fault Fault OK OK Fault Fault
Board3 OK OK OK OK Fault Fault Fault Fault OK OK OK OK Fault Fault Fault Fault
Board4 OK OK OK OK OK OK OK OK Fault Fault Fault Fault Fault Fault Fault Fault
Left
Number 0x 1x 2x 3x 4x 5x 6x 7x 8x 9x Ax Bx Cx Dx Ex Fx
Board5 OK Fault OK Fault OK Fault OK Fault OK Fault OK Fault OK Fault OK Fault
Board6 OK OK Fault Fault OK OK Fault Fault OK OK Fault Fault OK OK Fault Fault
Board7 OK OK OK OK Fault Fault Fault Fault OK OK OK OK Fault Fault Fault Fault
Board8 OK OK OK OK OK OK OK OK Fault Fault Fault Fault Fault Fault Fault Fault
Also addresses 0048 to 004F show the communication attempts to each of the boards. Refer to the
sample shown below.
0048 F* F* 0* 00
004C 00 00 00 00
If a board is not communicating properly, the left number corresponding to the board will be “F” or “E”.
The right number will change very quickly. If the board is communicating properly, the left number will
be “0” or “1”, and the right number will be changing quickly. If the CPU is not attempting to
communicate to a board, the value will stay at “00”. In the example above, the CPU is attempting to
communicate with boards 1, 2, and 3. Board 3 is communicating properly, but boards 1 and 2 are not.
The “*” in the example above indicate numbers that are changing quickly.
Address 051E counts the number of failed IO board communication attempts. This should be 0, as
shown in the sample below.
VIRGINIA CONTROLS, INC. MVFAC-3000 User Manual, Rev. 2.11 Page 124
051C 2E E0 00 00
0520 00 00 00 00
If there are intermittent problems, such as noise causing communication errors, then this value will
gradually increase. Check the addressing of the boards, and that all cables are fitted properly. Also
check the grounding of the controller. See the section Show Internal Memory for instructions on
viewing internal memory addresses.
VIRGINIA CONTROLS, INC. MVFAC-3000 User Manual, Rev. 2.11 Page 125
10.4 Changes for Program Revisions
The following section lists the changes that are included in program revision.
VIRGINIA CONTROLS, INC. MVFAC-3000 User Manual, Rev. 2.11 Page 126
11. Controller Maintenance
WARNING: MAKE SURE THE POWER IS OFF BEFORE CONNECTING OR DISCONNECTING
ANY CONNECTORS, ADDRESS JUMPERS OR CABLES ON THE CPU OR I/O BOARDS.
Notch
EPROM Chip Positioning
VIRGINIA CONTROLS, INC. MVFAC-3000 User Manual, Rev. 2.11 Page 128
11.2.3 Input/Output Board Exchange
To exchange on I/O board:
1. Change the Address Switches on the new I/O board to match the board it will replace.
2. Turn off the power to the controller.
3. Unplug all the removable I/O terminal strips from the top and bottom of the I/O board. It is not
usually necessary to mark the terminal blocks, since the wiring will normally hold them in the proper
place so that it is obvious which block goes where. If there is any doubt about their location, then
mark the terminal blocks to show where they should be re-installed.
4. Unplug the I/O Bus Connectors and power connector.
5. Remove the screws holding the I/O board in place.
6. Install the new I/O board by reversing the previous steps.
VIRGINIA CONTROLS, INC. MVFAC-3000 User Manual, Rev. 2.11 Page 129
12. Frequently Asked Questions
Suggestions for other Frequently Asked Questions are welcomed. Please submit them via email to
eng@vacontrols.com.
VIRGINIA CONTROLS, INC. MVFAC-3000 User Manual, Rev. 2.11 Page 130
12.3 Questions on the Controller
Q. How Do I Reset All Settings and Features Back to the Original Values?
1. With the controller running normally, press Nxt repeatedly until the menu item shows "GO TO
SETUP MENU".
2. Press Ent. The display will show a warning message. Make sure the car is stopped before
continuing.
3. Press Ent. The display will show you have entered the Setup Mode, then display the "RESET
SETTINGS" menu item.
4. Press Ent to reset all settings to the factory defaults.
5. Press Esc to return the controller to normal operation.
NOTE: If the program is a standard program, then the settings for the specific job must
be re-entered.
VIRGINIA CONTROLS, INC. MVFAC-3000 User Manual, Rev. 2.11 Page 131
Q. Why is the LCD Display blank?
The LCD Display goes blank after the CPU resets if S2 switch 1 is in the OFF position. This will happen
when the power to the CPU is cycled, or when the Reset Button on the CPU board is pressed.
Press any key to activate the screen.
If the screen does not activate, the problem could be with the Keypad (momentarily touch pins 1 and 8
on the keypad connector to simulate pushing a key) or the CPU (check that LED D5 is flashing), or the
LCD Display.
Q. Why is the Fire Audible Visible output On but the car is not on Fire Service?
Switch 3 on the CPU Slide Switch S2 is in the ON position.
This switch defeats the Redundancy Faults. This may be useful during initial installation, and the Fire
Audible Visible is turned on to remind you to turn off this defeat after installation. Slide the switch down
to turn it off.
VIRGINIA CONTROLS, INC. MVFAC-3000 User Manual, Rev. 2.11 Page 132
13. Drive Special Instructions
Refer to the job schematic for connection information.
The drive has been set up and tested, so only minor adjustments should be necessary.
If the motor data is different from that supplied to Virginia Controls (motor horsepower, currents,
voltages, etc.) then consult with Virginia Controls before powering up the system.
Refer to the Parameter sheet in the schematic for the actual settings for each particular job.
For additional explanations of drive parameters, see the Magnetek Technical Manual.
Customer should record any parameter changes and keep this information in a safe place for future
reference.
NOTE: Be sure to take the necessary steps to prevent anyone from boarding the
elevator during the test.
VIRGINIA CONTROLS, INC. MVFAC-3000 User Manual, Rev. 2.11 Page 133
5. As the elevator opens its doors at the top landing, remove the controller wire clipped to the
temporary wire at Input DZ on the ETSD Board.
6. The UCM System will cause the “UCM TRIP” LED to light, and the Rope Brake to set.
7. Power down the system.
8. Restore the controller wiring at Input DZ.
9. Power up and briefly touch a wire from controller TB-1 (120VAC Hot) to Input SHTDFT on the
ETSD Board to reset the UCM System and the Rope Brake.
NOTE: Be sure to take the necessary steps to prevent anyone from boarding the
elevator during the test.
2. Power down the system with the doors closed.
3. Remove the field wires at controller terminal blocks: 21 & 22, Up & Down Leveling Switches.
Temporarily place a short wire in TB-22.
4. Power up the system.
5. Briefly touch a wire from controller TB-1 (120VAC Hot) to controller TB-27, Door Open Button
Input, to open the elevator doors.
6. With the doors open, clip the wire from controller TB-1 to the short wire just installed at
controller TB-22, Down Level Switch.
7. The elevator will level down slowly until it rides out of the Door Zone.
8. UCM System will cause the “UCM TRIP” LED to light, and the Emergency Brake to set.
9. Power down the system.
10. Restore the field wires at controller terminal blocks: 21 & 22, Up & Down Leveling Switches.
11. Power up the system.
12. Touch a wire from TB-1 of the controller to Input SHTDFT of the ETSD Board to reset the UCM
System and Rope Brake.
13. The elevator will close its door and relevel back to the floor.
VIRGINIA CONTROLS, INC. MVFAC-3000 User Manual, Rev. 2.11 Page 134
3. Install a jumper from controller TB-1 to controller Input or TB: “SHTDFT”. See the controller
drawings for the location of this input or terminal.
4. Power up the system.
5. Set the drive for an Inspection Speed of 175FPM and run car.
6. The O-S System will fault causing the “O-S TRIP” LED to light, and stop the car.
7. Power down the system.
8. Remove the jumper from controller TB-1 to Input or TB: “SHTDFT”.
9. Power up the system.
10. Restore the drive to its original Inspection Speed.
11. Use the “O-S RESET” Push Button on the ETSD Board to reset the O-S System.
12. Restore elevator to Normal Operation.
VIRGINIA CONTROLS, INC. MVFAC-3000 User Manual, Rev. 2.11 Page 135
INDEX
A F
Access · 13 Factory Reset · 18
Addressing · 54 Failure Timers · 21
Adjustable Features · 22 Fault Code · 80
Fault Log · 78, 79, 80, 86, 90, 100, 116
Features · 18, 22, 100, 104, 106, 114, 115, 130,
B 131
Fire Service · 13, 17, 21, 23, 24, 47, 82, 83, 97,
Banner Screen · 77
106, 109, 115, 117, 130
Battery · 46, 127
Flood · 109, 110
Bit Features · 79, 80, 104, 107
C G
Grounding · 9, 11, 14, 16
Calls · 20, 23, 47, 97
Car Start · 23
CAUTION · 8, 103 H
Code · 80, 103, 104, 106, 117, 130
Communication · 24, 49, 56, 82, 124 Hexadecimal Conversion Table · 93
CPU · 11, 14, 19, 24, 41, 45, 46, 47, 48, 49, 56, Historical Log · 90
85, 99, 121, 123, 125, 127, 132 Homing · 24, 106, 116
Humidity · 10
D
I
Diagnostic · 99
Display · 50, 52, 103, 105, 115, 116, 132 I/O Status · 78
Door Operation · 20 Independent · 19, 24, 47, 82, 96, 97, 106
Drive · 15, 17, 21, 84, 96 Inspection · 17, 18, 21, 24, 47, 82, 96, 97, 102,
Duplex · 23, 24, 48, 49, 82, 116 105, 115, 133
Internal Memory · 48, 90, 93, 94, 95, 99, 100,
116
E IO Fault · 98, 124
Emergency Terminal Stopping Device · 34, 59,
66 J
EPROM · 8, 19, 41, 47, 101, 128
ETSD · 25, 26, 27, 28, 29, 30, 31, 33, 34, 35, 36, Jumper · 58
59, 62, 63, 64, 65, 66, 67, 68, 69, 70, 71, 72,
73, 75, 133, 134, 135
ETSD Monitoring System · 25, 59
K
Keypad · 41, 50, 132
VIRGINIA CONTROLS, INC. MVFAC-3000 User Manual, Rev. 2.11 Page 136
L S
LED · 20, 21, 24, 47, 48, 49, 54, 55, 56, 90, 94, 99, S2 · 132
100, 123, 124, 132 S2 Slide Sw · 50, 51, 76
Selector · 12, 115
Settings · 18, 22, 100, 101, 102, 103, 104, 107,
M 115, 130, 131
Set-Up Mode · 99, 100
Maintenance · 127
Start-Up · 16
Status · 48, 52, 56, 76, 77, 78, 86, 95, 96, 99, 100,
N 123, 124
Stuck Button · 21
Next Car · 23 Switches · 12, 13, 56, 78, 82, 85, 97, 129, 130
Noise · 125 Leveling · 12, 13, 22, 82, 85, 97, 105, 129
NOTE · 8, 11, 13, 16, 19, 20, 21, 42, 48, 49, 79, Limit · 12, 13, 19, 81, 85, 86, 97, 98, 129, 130
81, 86, 94, 100, 102, 103, 105, 114, 131 Slowdown · 12, 13, 19, 85, 97, 129
Zone · 12, 13, 22, 83, 85, 87, 97, 98, 103, 129
O
T
O-S · 26, 27, 28, 32, 33, 36, 59, 64, 73
Over Speed · 28, 63 Temperature · 10
Over-Speed · 59, 63 Temporary · 17
Terminal Wiring · 55
Test · 118
P
Time · 46, 79, 81, 100, 116
Parts List · 121 Troubleshooting · 123, 124
Parts Replacement · 127
Password · 100, 102, 114, 116, 117 U
Position Indicators · 19
UCM · 26, 33, 36, 59, 60, 61, 62, 64, 65, 73
Unintended Car Movement · 26, 59, 60
R
Redundancy · 86, 96, 97, 108, 126 W
Reset Button · 48, 49, 76, 132
Revision · 126 WARNING · 8, 14, 16, 17, 23, 46, 47, 49, 55, 58,
Run Mode · 76, 77, 78, 90, 99, 100, 101, 103, 95, 100, 102, 118, 119, 127, 128
116, 117, 118, 131 Watchdog · 48
Running Timers · 21
VIRGINIA CONTROLS, INC. MVFAC-3000 User Manual, Rev. 2.11 Page 137