Daznis
Daznis
Daznis
CPIKFrequencyInverter
OperatingManual
n
25R 33R 50R 100R 150R
.c
Control voltage use AC220V
ts
ar
rp
to
la
ca
es
w.
ww
Revised : 2009-06-24
OPERATING MANUAL
TABLEOFCONTENT
1.SAFETY................................................................................................................................................ 1
1.1Explanationofsymbolsused......................................................................................... 1
1.2Generalsafetyinformation............................................................................................ 2
2.PRODUCTDESCRIPTIONANDINSTALLATIONINSTRUCTIONS................................................... 5
2.1RepresentationoffrequencyinverterCPIK....................................................................... 5
2.2DescriptionoffrequencyinverterCPIK............................................................................ 6
2.2.1Warnings.............................................................................................................. 6
n
2.2.2Mountinginstructions............................................................................................. 7
.c
2.2.3Technicaldata...................................................................................................... 8
2.2.3.1Generaldata................................................................................................... 8
ts
2.2.3.2Typespecification........................................................................................... 9
2.2.3.3Externalmodules............................................................................................ 10
2.2.3.4Derating........................................................................................................ 10
ar
2.2.4Generalinstructions............................................................................................... 10
2.2.4.1Mainsvoltage................................................................................................. 10
rp
2.2.4.2Systemconfiguration....................................................................................... 11
2.2.4.3Mainsconnection........................................................................................... 11
to
2.2.4.4Isolationoffrequencyinverter........................................................................... 11
2.2.4.5Leakagecurrent.............................................................................................. 11
la
2.2.4.6Faultcurrent................................................................................................... 11
2.2.4.7DischargetimeofDClinkcapacitors.................................................................. 11
ca
2.2.4.8Electronicground............................................................................................ 11
2.2.4.9RunContactor................................................................................................. 11
2.2.4.10Internalfan.................................................................................................. 11
es
2.3Interface..................................................................................................................... 12
2.3.1Connectiondiagram............................................................................................... 12
w.
2.3.2FrequencyinverterInputandOutputterminals(Non-Regenerative)............................... 12
2.3.2.1Mains............................................................................................................ 12
ww
2.3.2.2MotorandCables........................................................................................... 12
2.3.2.3Brakingresistor.............................................................................................. 12
2.3.2.4Internalvoltage............................................................................................... 12
2.3.2.5Separatelydrivenmotorfan............................................................................. 13
2.3.2.6MotorPTCthermistorconnection....................................................................... 13
2.3.2FrequencyinverterInputandOutputterminals(Regenerative)..................................... 13
ii
OPERATING MANUAL
TABLEOFCONTENT
2.3.2.1Mains............................................................................................................ 13
2.3.2.2MotorandCables........................................................................................... 13
2.3.4EncoderconnectionandCANcommunication............................................................ 14
2.3.4.1Encoderconnection......................................................................................... 14
2.3.4.2EncodersignalsandCANcommunicationtocontrol............................................. 14
2.3.4.3UsingtheCANinterfacetoconnecttheTCM(orTAC50K)controlsystem………….. 14
2.3.4.4SwitchingsequencechartwithTCMcontrol........................................................ 16
2.3.4.5SwitchingsequencechartwithTAC50Kcontrol................................................... 17
n
2.3.5Interfacetotheliftcontrol....................................................................................... 18
.c
2.3.5.1Readymessage……....................................................................................... 18
2.3.5.2Inputsandoutputs.......................................................................................... 18
ts
2.3.5.3Switchingsequencechart................................................................................. 19
2.4Systemperturbations,EMC........................................................................................... 20
2.4.1General................................................................................................................
ar
20
2.4.2MountingInstructions............................................................................................. 20
2.4.3Linechoke............................................................................................................ 20
rp
2.4.4Linefilter.............................................................................................................. 20
2.4.5Installationofothercables...................................................................................... 20
to
2.5Dimensionsheet.......................................................................................................... 21
2.5.1DimensionofCPIKseries........................................................................................ 21
la
2.5.2Externalmodules................................................................................................... 22
2.5.2.1DCchoke……………………………................................................................. 22
ca
2.5.2.2Linefilter(standard,notusedITlines)............................................................... 23
2.5.2.3Linechoke….................................................................................................. 25
3.TRANSPORTANDSTORAGE............................................................................................................. 26
es
3.1General...................................................................................................................... 26
4.PUTTINGINTOOPERATION.............................................................................................................. 28
w.
4.1Safetyinstructions....................................................................................................... 28
4.2Operatinginstructions.................................................................................................. 28
ww
4.3Pointstobeobservedpriortoinitialpoweringon.............................................................. 28
4.4Checkingthevisualdisplaysintheeventoferrors............................................................ 28
4.5Inputoflift-specificvalues............................................................................................. 29
4.6Testingthedriveforcorrectfunctioning........................................................................... 29
4.7Driveoptimization........................................................................................................ 30
4.8Measuringandsetting.................................................................................................. 31
4.8.1LEDandmeasuringpointsonTMI2board………….................................................. 31
4.8.2LEDandmeasuringpointsonRMCboard.............................................................. 32
4.8.3LEDandmeasuringpointsonRMBKboard(Regenerativetype)....................... 33
iii ThyssenKruppElevator(Korea)
OPERATING MANUAL
TABLEOFCONTENT
5.PARAMETERENTRY........................................................................................................................... 34
5.1General...................................................................................................................... 34
5.2Operation................................................................................................................... 34
5.2.1Displayandchangeofparameters........................................................................... 34
5.2.2Displayparameters................................................................................................ 35
5.2.3SavechangedparameterstoEEPROM..................................................................... 35
5.2.4Allparametersasfactory-set.................................................................................. 35
n
5.3Errorstacks................................................................................................................. 36
.c
5.3.1Displayerrorstack................................................................................................. 36
5.3.2Deleteerrorstack.................................................................................................. 36
ts
5.3.3Enderrorstack...................................................................................................... 36
5.3.4Errordescription.................................................................................................... 36
5.4Parameters.................................................................................................................
ar
36
5.4.1Variableparameters............................................................................................... 36
5.4.2Displayparameters................................................................................................ 46
rp
6.SHORT-RUNDEVICE.......................................................................................................................... 48
6.1General...................................................................................................................... 48
to
6.2Settings...................................................................................................................... 48
7.MODERNIZATION............................................................................................................................... 50
la
7.1General...................................................................................................................... 50
7.2Modernizationbyencodermountedonmotorshaft.......................................................... 50
ca
7.2.1Rating.................................................................................................................. 50
7.2.2Motoradaptation................................................................................................... 50
7.2.3Settingsforsynchronousmotors.............................................................................
es
51
7.2.4Settingintooperation............................................................................................. 51
8.ANNEX................................................................................................................................................. 52
w.
8.1DeclarationofConformity.............................................................................................. 52
8.2ParameterSetting........................................................................................................ 55
ww
8.3MonitoringParameter................................................................................................... 57
8.4Errordescription.......................................................................................................... 58
8.5Extrainfoforpulseenablespowerpart(PDPINT).............................................................. 60
8.6Extrainfofor“runcontactorproblems”…....................................................................... 61
8.7Connectiondiagram..................................................................................................... 62
8.8HowtousetheHyper-terminal...................................................................................... 70
iv
OPERATING MANUAL 1. SAFETY
1. SAFETY
1.1 Explanation of symbols used
The following pictographs and designations are used in this operating manual:
Danger
This symbol draws attention to an extreme danger to life or risk of injury to persons.
Disregard of warning means danger to life !
n
Danger
.c
This symbol draws attention to an immediate impending danger to life or risk of injury to
persons caused by electric current.
ts
Warning notices must always be observed!
ar
Warning
Note
la
This symbol draws attention to important information and instructions for operation.
Disregard can lead to damages, hazards or failures.
ca
Inspection
es
1
OPERATING MANUAL 1. SAFETY
n
In addition the rules and requirements concerning the regulations for prevention of accidents
.c
which apply to the installation location must be observed.
ts
Duties of the owner and / or the installer
The owner and / or installer ensures that only persons are authorized to work at the component,
who
ar
• are familiar with the requirements concerning safe working and prevention of accidents and
who were trained how to use the component;
rp
• have read the safety information and the warning notices in this operating manual.
to
Check the compliance of the employee’s method of working with the safety requirements in
regular intervals.
la
Persons who are authorized to perform work at the component are obliged
• to observe the requirements concerning safe working and prevention of accidents;
• to read the safety information and the warning notices in this operating manual prior to start
es
working.
w.
component.
The competence of the employees must be clearly defined for all tasks concerning putting into
service, operation, maintenance and repair work.
Organizational measures
The owner or the installer must provide the necessary personal protective gear. All existing
safety devices must be checked regularly in accordance with the maintenance plan.
2
OPERATING MANUAL 1. SAFETY
Use as intended
n
The FREQUENCY INVERTER is exclusively designed for use as controller in lift drives in
.c
accordance with EN 112015 or EN 12016 as well as EMC directive 89/336/EC.
Installation of the frequency inverter is subject to compliance with the requirements for
ts
installation and use of electrically-operated installations (EN 50 178 / VDE 0160 and VDE
0110).
Any other use or any use exceeding the scope of the above definitions is regarded as use
ar
outside of the intended purpose. ThyssenKrupp Elevator (Korea) Ltd. cannot be hold liable for
any damages resulting from this and for any damages which are caused by any errors of
rp
procedure.
Use within the scope of intended purpose also comprises
to
protective devices
• disregard of instructions of the operating manual
• unauthorized constructional modifications of the FREQUENCY INVERTER
• unsatisfactory supervision of parts which are subject to wear
• inexpert repair work
• catastrophes caused by outside influence and Act of God.
3
OPERATING MANUAL 1. SAFETY
n
The state-of-the art frequency inverter complies with the safety requirements in force. The
.c
frequency inverter shall only be used
• as intended and
ts
• with the safety devices in perfect working condition.
In case of inexpert use there will be the risk of damage to life of the user resp. third parties or
impairment of the component or material property.
ar
Failures which may affect safe operation must be eliminated immediately.
Works on the frequency inverter shall only be performed with the lift installation protected
rp
against unintentional switching on.
See instructions in chapters
to
4
OPERATING MANUAL 2. PRODUCT DESCRIPTION AND INSTALLATION INSTRUCTIONS
n
Try to determine the pulse number per revolution through parameter P 105 if unknown. (See chapter
5.4.2 display parameters).
.c
Adaptation in the course of putting the frequency inverter into operation for third-party motors. (See
chapter 7. Modernization).
The main features of the frequency inverter range CPIK consists of the following points:
ts
• PWM control with 16 kHz pulse frequency, i.e. no motor noise. This frequency will be reduced
automatically by overload.
• Peak current is available for approx. 10 second during operation. Higher current is available for
ar
approx. 4sec in case of overload (in particular “release of safety gear operation”). However the
switching frequency is reduced to 4 kHz (see chapter 2.2.3.2 Type specification).
• Connection of contactors on mains (before the frequency inverter) or motor side (after the frequency
rp
inverter). (See chapter 2.2.4.9 Contactors).
• No integrated fuses. Therefore adaptation of the installation fuses to inverter output
• Regenerative energy is converted to heat by external brake resistor incase of Non-Regenerative.
to
• Device connection without removing of covers. All cable terminals are on top side and lower side
(motor and brake resister) of device; control terminals are accessible from front side.
• Speed to 2.0 m/s with geared drives
ca
(see chapter 4.8.3 Diagram for determining the min. permissible floor-to-floor distances).
2.2.1 Warnings
w.
• Works on the frequency inverter shall only be performed by trained and qualified personnel. They
must observe the appropriate rules for prevention of accidents and shall be informed about the
danger of electric current to be considered.(See chapter 1.2 General safety information).
ww
• Frequency inverters are electronic devices and, therefore, not fail-safe. The owner of the
installation is responsible for the safety of persons and protection of material property.
• Requirements for the installation and operation of electric systems (EN 50 178 / VDE 0160 and
VDE 0110) must be observed for mounting of frequency inverter.
Protective measures to be taken acc. to local conditions and regulations.
• Electric energy may still be present after shutting off the inverter. (Charge of DC link capacitors).
This applies to defective devices in particular. A warning to this effect is displayed on the device
and must also be present in the operating manual of the lift control.
• The integrated heat sink or other components, too, may still have a temperature > 60 °C during
operation or shortly after powering off the device.
• The external brake resistor may have a temperature > 200 °C during operation.
6
OPERATING MANUAL 2. PRODUCT DESCRIPTION AND INSTALLATION INSTRUCTIONS
n
.c
Control Power connection, input
ts
1 phase AC 220 V - 25%, AC240 +10%, without N, 50/60 Hz
Control voltage 1 phase AC 380 V - 25%, AC415 +10%, without N, 50/60 Hz
AC380V AC220V
ar
11M1,15M1,32M1,48M1,
CPIK series 15, 32, 48, 60, 105 15M, 32M, 48M
60M1,105M1
rp
*** Control voltage is changed AC380V to AC220V in case of CPIK xxM1 series
Protection class IP 20
Permissible coolant temperature [°C] 0 ... 45 Derating for higher temperature
la
Max. height of installation site [m NN] 1000 Derating for higher heights
Max. relative humidity [%] 95 No icing
ca
Current harmonic I5/I1 < 0.3, < 0.08 (R- type) With rated input
Total harmonic distortion THD- F
2)
≈35%, ≈10% (R- type) current
1)
ww
1) In case of CPIK with operating capacity < 70 % rated output line reactor with higher inductance
required, see chapter 2.5.2.2 Line choke
2) Total harmonic distortion (harmonic RMS current) related to fundamental-frequency current.
8
OPERATING MANUAL 2. PRODUCT DESCRIPTION AND INSTALLATION INSTRUCTIONS
n
Peak output current for 10 sec [A] 30 45 60 90 120 180
.c
Rated output power [kVA] 10 15 19 29 36 55
Peak rated power for 10 sec [kVA] 18 27 36 55 73 109
2
Cable cross-sectional area [mm ] 4 4 6 10 16 22
ts
Loss power per current [W/A] 17.3 17.3 16.2 16.5 13.6 13.7
Efficiency 0.97
Mechanical data
Dimensions W [mm] 240 240 240 240 344 344
ar
Dimensions H [mm] 450 450 450 450 523 523
Dimensions D [mm] 180 180 180 180 243 243
Minimum top/bottom clearance [mm] 100/100
rp
3
Fan power of device (free air flow) [m /h] 138 138 138 138 276 276
Weight [kg] 13 13 14 14 40 42
DC choke No built-in Built-in
to
(Regenerative type)
RM type R type
Model (CPIK) unit
la
Loss power per current [W/A] 17.3 16.2 16.5 34.6 32.4 42.8 42.8 42.8 42.8
Total Efficiency 0.94
Dimensions W [mm] 440 440 440 440 440 440 600 700 1400
Dimensions H [mm] 1400 1400 1400 140 140 1400 1800 1900 2200
Dimensions D [mm] 250 250 250 250 250 250 290 350 600
Minimum top/bottom clearance [mm] 100/100
3
Fan power of device [m /h] 276 276 414 276 276 414 552
Weight [kg]
EMI filter and AC choke Built in
CPI 300R: To use TKAW product
9
OPERATING MANUAL 2. PRODUCT DESCRIPTION AND INSTALLATION INSTRUCTIONS
n
3 phase line choke
.c
Item unit 15M1 32M1 48M1 60M1 105M1
Inductance [mH] 3 x 1.2 3 x 0.43 3 x 0.29 3 x 0.15
ts
Rated current [A] 24 34 50 90
Model No. ACL16A1200 ACL34A430 ACL50A290 HL-90A-150
ar
Item unit 11M1 15M1 32M1 48M1 60M1 105M1
Recommend value [ Ω] 50 / 28 33 / 28 25 / 20 16 / 14 12 / 10 10 / 8
rp
Minimum value [ Ω] 28 28 20 14 5 5
Power consumption [ kW] 2 / 3.6 3 / 3.6 4 / 5.4 6 / 7.2 8 / 10 10 / 12
to
2.2.3.4 Derating
la
The permissible output current shall be reduced acc. to below charts for installation sites at height >
1000m NN or coolant temperature > 45°C.
ca
es
w.
ww
10
OPERATING MANUAL 2. PRODUCT DESCRIPTION AND INSTALLATION INSTRUCTIONS
n
It interfere suppression by Y capacitors between phase and protective earth conductor of frequency
inverter and line filter.
.c
The arising leakage current is > 3.5 mA.
Therefore cross-section of the protective earth conductor of supply cable shall be at least 10 mm²
Cu in accordance with VDE 0160, chapter 5.3.2.1: April 1998.
ts
2.2.4.6 Fault current
Fault current with zero-frequency quantity can arise in case of earth contact in frequency inverter.
ar
Therefore the leakage current of the Y capacitors make use of protective equipment against
standard fault current (FI) (pulsating current sensitive) impossible.
The operation manual shall inform that use of protective fault current equipment only does not fulfill
rp
the requirements of VDE 0160, chapter 5.2.11.2: April 1998.
to
AC-DC sensitive fault current protection is recommended. Connection notes of manufacturer are to
be observed.
The recommended residual voltage of 60 V after 5 seconds as required acc. To VDE 0113, part 1,
chapter 6.2.3: (June 1993) is not complied with. A warning to this effect is given on the frequency
inverter.
ca
Electronic ground (electronic zero) is electrically connected with the protective earth conductor.
The run contactors can be connected on the line side (before the frequency inverter) or on the
motor side (after the frequency inverter).
Contactors with 60 Hz AC coil excitation can be used if connected on line side.
ww
The shielded motor-cable can also be run to the frequency inverter in accordance with the EMC
requirements and the shielded motor cable connected by suitable cable clips.
Coils with DC coil excitation shall be used for motor side connection. This guarantees delayed
release of contactors. The shielded motor cable can be run to the run contactor in accordance with
the EMC requirements and the shielded motor cable connected by suitable cable clips. Short and
twisted cabling of the motor lines running to 2 run contactor is recommended.
The contactor coils should be provided with overvoltage protection elements (RC element or free-
wheeling diode).
2.2.4.10 Internal fan
The internal fan for cooling the heat sink is turned on during every run.
If the heat sink temperature exceeds a certain value, the fan will continue running until the heat sink
is cooled down accordingly again.
11
OPERATING MANUAL 2. PRODUCT DESCRIPTION AND INSTALLATION INSTRUCTIONS
2.3 Interface
2.3.1 Connection diagram
The connection diagram (see chapter 8.7 connection diagrams) shows an overview of all terminals
required for the operation of the frequency inverter.
2.3.2 Frequency inverter Input and Output terminals (Non-Regenerative)
Terminals of top side
No. Symbol Contents
X1.1 PE Input: PE for control voltage
X1.2 0
Input: Control voltage, 1 phase AC 220V
X1.3 220V
X1.15 RD1
Output: CPIK “Ready contact”
X1.16 RD2
n
X1.17 TM1
.c
Input: Motor temperature
X1.18 TM2
X1.09 DCL DC-link choke ( in case of CPIK 11M1, 15M1, 32M1 and 48M1)
X1.10 DCL If there are no use this choke, must short X1.09 and X1.10
ts
X1.11 L1
X1.12 L2 Input: Main power, 3 phase, AC 380V, 50/60 Hz
ar
X1.13 L3
X1.14 PE Input: PE for Main power
rp
Terminals of lower side
No. Symbol Contents
X1.19 PE Output: PE for Dynamic Braking Resister
to
X1.20 RA1 Output: IGBT collector terminal for Dynamic Braking Resister
X1.21 RA2 Output: DC link P+ terminal for Dynamic Braking Resister
X1.23 N- Output: DC link N- terminal
la
X1.24 U
X1.25 V Output: Motor power
X1.26 W
ca
2.3.2.1 Mains
Line input of frequency inverter L1, L2, L3 without N on terminal strip X1, terminals 11, 12, 13 (PE
w.
at terminal 14)
2.3.2.2 Motor and Cables
At terminal strip X1, motor output of inverter is terminals 24, 25 and 26 including 27 (PE).
ww
The motor must be connected via a four-core screened line. For reasons of electromagnetic
compatibility, the screen must be connected to the mounting plate over a large surface in the
control cabinet in the immediate vicinity of the inverter or run contactor (see chapter 2.2.4.9 run
contactors). Cable clamps to be made provision for adequateness.
The motor cable should not exceed a maximum length of 30 m and the cable should not be run in
parallel to signal lines.
12
OPERATING MANUAL 2. PRODUCT DESCRIPTION AND INSTALLATION INSTRUCTIONS
n
and 16 will be removed (relay contact open).
A new run command can be given after the motor has cooled down (ready message present again).
.c
Connect terminals 17 and 18 with a wire jumper in the absence of a motor PTC thermistor.
ts
2.3.3 Frequency inverter Input and Output terminals (Regenerative)
Magnet Contactor and Connector in RMBK Board
Contactor / Connector Pin No. Symbol Contents
ar
2 L1
Q1 or MCCB 4 L2 Input: Main power, 3 phase, AC 380V, 50/60 Hz
6 L3
rp
2 U
K06.1 4 V Output: Motor power
6 W
to
1 Coil1-1
2 Coil1-2
X515 Brake Coil
la
3 Coil2-1
4 Coil2-2
1 PE Input: PE for Control voltage
ca
X512 2 0
Input: Control voltage
3 220
1 220
es
Brake PTC
2 Th1.2
3 Th2.1
Motor PTC
ww
4 Th2.2
X514
5 0V
Brake contactor
6 LU1
7 0V
Brake contactor
8 LU2
13
OPERATING MANUAL 2. PRODUCT DESCRIPTION AND INSTALLATION INSTRUCTIONS
The motor must be connected via a four-core screened line. For reasons of electromagnetic
compatibility, the screen must be connected to the mounting plate over a large surface in the
control cabinet in the immediate vicinity of the inverter or run contactor (see chapter 2.2.4.9 run
contactors). Cable clamps to be made provision for adequateness.
The motor cable should not exceed a maximum length of 30 m and the cable should not be run in
parallel to signal lines.
n
electromagnetic compatibility, the screen is placed on the plug casing over a large surface both on the
.c
device side and on the encoder side. The maximum length of the encoder cable should not exceed 40 m.
The pulse number of the encoder is 1024 or 4,096, 16,384 incremental type for asynchronous
motor and 2,048 EnDat absolute type for Synchronous motor.
ts
Output signal of incremental encoder use line drive format
Output signal of absolute encoder use line drive format
Pin assignment of incremental encoder Pin assignment of absolute encoder
ar
Signal X 907, Pin Signal X 917, Pin
Ua 1 inverted 1 Ua 1(sinus) 1
rp
Ua 1 2 0V(GND) 2
Ua 2 3 Ua 2 (cosinus) 3
Ua 2 inverted 4 5V 4
Ua 0 5 data 5
to
Ua 0 inverted 6 shield 6
0 Volt 7 clock 7
PE / shield 8 Ua 1 inverse(sinus) 8
la
+ 5 Volt 9 Ua 1(sinus) 9
Ua 2 inverse(cosinus) 11
data inverse 13
ca
clock inverse 15
es
pins) and can be used in the control (path or speed detection, for example).
The CAN interface signals from the TCM control or TAC50K control are connected at TMI2 board on plug
X 906 (D-sub, 15-pole, pins). They are isolated from the frequency inverter electronics by opto-couplers.
Pin assignment:
ww
2.3.4.3 Using the CAN interface to connect the TCM (or TAC50K) control system
The TCM (or TAC50K) interface is used for control command communication and for acknowledge
signals between TCM (or TAC50K) and CPIK via CAN bus and for transmission of motor rotary
encoder impulses from CPIK to TCM (or TAC50K). There is potential separation between TCM (or
TAC50K) and CPIK.
14
OPERATING MANUAL 2. PRODUCT DESCRIPTION AND INSTALLATION INSTRUCTIONS
n
travel contactor on acknowledgment QSP
From TCM
brake released acknowledgment BR1
.c
motor overtemperature MUET
To TCM RPM zero signal N=0
ts
collective fault signal SMR
ar
Control commands from TAC50K (0x33)
Word0 speed command value Vsoll
Word0 pre-torque reference value QLMS
rp
Status signals from TAC50K (0x33)
Word1- Bit0 speed reference / pre-torque reference 0/ 1
to
Word1- Bit10 Temperature motor / break / line choke (Regen type only) Tmot
Word1- Bit11 Acknowledge Break 1 (Regen type only) BK1
Word1- Bit12 Acknowledge Break 2 (Regen type only) BK2
ww
15
OPERATING MANUAL 2. PRODUCT DESCRIPTION AND INSTALLATION INSTRUCTIONS
n
.c
ts
ar
rp
to
la
ca
es
w.
ww
17
OPERATING MANUAL 2. PRODUCT DESCRIPTION AND INSTALLATION INSTRUCTIONS
n
0V 1b, 10a
.c
+24 V 2b, 12a
A three-core cable can be connected as a link to the load-weighing device LMS 1at terminals 10a, 12a
ts
and together with 9b.
ar
Digital control signals from lift control to CPIK, plug X1/TIC
Start and run direction signal upwards UP Optocoupler Input 24Vdc 50mA 3b
rp
Start and run direction signal downwards DOWN Optocoupler Input 24Vdc 50mA 4b
Rated speed VN Optocoupler Input 24Vdc 50mA 5b
Second operating speed V2 Optocoupler Input 24Vdc 50mA 6b
to
Main contactor ack. alternative to QSP QSP1 Optocoupler Input 24Vdc 50mA 10b
Main contactor ack. alternative to QSP1 QSP AC Input 180~250Vac 7a, 8a
es
18
OPERATING MANUAL 2. PRODUCT DESCRIPTION AND INSTALLATION INSTRUCTIONS
n
.c
ts
ar
rp
to
la
ca
es
w.
ww
Hatched areas - signals VN and V0 are allowed to be applied already in the period of the hatched
areas.
19
OPERATING MANUAL 2. PRODUCT DESCRIPTION AND INSTALLATION INSTRUCTIONS
n
• If the contactors are arranged between frequency inverter and motor, short and drilled
.c
connections are to be used between inverter and contactors.
• Screening of motor lines (14) and PTC thermistor lines (12). Cable screens to be contacted with
the zinc-plated mounting plate and the motor casing on both sides to a large surface and
ts
electrically conducting in the vicinity of the frequency inverter (use EMC compliant cable clips or
screwed conduits). The distance between screened motor cable and all other cables or lines
shall be at least 0.2 m.
• If the delivered incremental encoder is used the encoder cable is already properly screened (i.e.
ar
conductor and encoder box screen placed over a large surface). Please note in case other
encoders are used.
• Use EMC compliant connection between housing of the brake resistor and zinc-plated mounting
rp
plate. This can readily be achieved by screwing the housing of the braking resistor to the
inverter cabinet directly by means of a large-surface electrically conducting connection.
In this case, a non-screened connecting cable can be used between inverter and brake resistor,
to
The need for a screened line can be dispensed with, if short connections are used. The cables
must be drilled in this case, however.
The user is responsible for observing the EMC rules. Mounting instructions to be follow.
es
20
OPERATING MANUAL 2. PRODUCT DESCRIPTION AND INSTALLATION INSTRUCTIONS
n
.c
ts
ar
rp
to
la
ca
[A]
HLD-23A2000 23 2.0 75 112.6 90.4 44.4 90 25 CPIK 15M
HLD-30A1800 30 1.8 76 128.6 102.2 50.9 100 25 CPIK 32M
w.
22
OPERATING MANUAL 2. PRODUCT DESCRIPTION AND INSTALLATION INSTRUCTIONS
n
.c
ts
ar
rp
to
la
ATTENUATION CHARACTERISTICS ( dB )
ca
23
OPERATING MANUAL 2. PRODUCT DESCRIPTION AND INSTALLATION INSTRUCTIONS
n
.c
ts
ar
rp
to
la
ATTENUATION CHARACTERISTICS ( dB )
es
24
OPERATING MANUAL 3.TRANSPORT AND STORAGE
Transport:
Transport shall be subject to safety requirements.
• Mind the risk of damage!
• Do not put any heavy objects onto the packed unit.
n
• Protect the unit against shock load and dropping.
.c
• Remove packing material after transport.
Note the pictographs fastened on the packing or other conspicuous places:
ts
ar
rp
to
to heat grippers
It is dimensions of frequency inverter CPIK (without packing between 22 and 40kg dependent on
respective variant).
es
Examine delivered parts and packing for completeness, damage or anything strange.
26
OPERATING MANUAL 3.TRANSPORT AND STORAGE
Unpacking
Dispose packing material in accordance with environmental requirements or make it available for
further use. Do not return special transport aids and transport contrivances to ThyssenKrupp
Elevator (Korea) Ltd.
Intermediate storage
If the component is not installed directly after delivery carefully store it at a
sheltered place and protect by humidity-proof guard cover.
Do not store the component in the open air.
n
.c
Environmental conditions
Storage: the ambient temperature during storage is to be maintained between 0°C to + 50°C.
ts
Maximum relative humidity of air shall not exceed 70 % (no moisture or icing).
Operation: the ambient temperature at the final site of installation shall not exceed 0 °C to +
ar
40 °C and the relative humidity of air 65 %. (No moisture or icing).
rp
to
la
ca
es
w.
ww
27
OPERATING MANUAL 4. PUTTING INTO OPERATION
n
.c
C) Verification of isolation from supply
Attention is drawn to the fact that electric energy may still be present in the device after power
voltage is switched off (capacitor charge).
ts
This particularly applies to defective devices.
Therefore, it is necessary to check for residual voltage prior to starting work on a frequency
inverter.
ar
A suitable multi-function instrument (min. 800 VDC) can be used for testing the link voltage for
residual voltage on terminal strip X1, terminals 20 (RA1) and 23(N-).
rp
Set measuring instrument to DC voltage range !
Work on the device open and with link voltage applied (approx. 700 VDC) to be performed
only in exceptional cases and exercising the utmost care.
to
It is important to be aware that the link voltage has a fixed potential reference to the line voltage
and the protective conductor.
la
• Check all components for correct protective earthing (frequency inverter, motor, box and brake
resistor)
• Check line voltage
• See to it that brake is in proper service condition and correctly adjusted
• Load car with 50 % load, if necessary (load compensation)
28
OPERATING MANUAL 4. PUTTING INTO OPERATION
n
• Acceleration change (jerk) P 19 [m/s³]
.c
• Acceleration P 20 [m/s²]
• Leveling speed V0 P 23 [m/s]
• Inspection speed Vi P 24 [m/s]
ts
• Rated speed Vn P 25 [m/s]
• Intermediate speed V2 P 26 [m/s]
• 2. Intermediate speed Vn2 P 27 [m/s]
ar
• Emergency operation V3 P 28 [m/s]
• Intermediate speed V4 P 29 [m/s]
rp
• Intermediate speed V5 P 30 [m/s]
• Intermediate speed V6 P 31 [m/s]
• Intermediate speed V7 P 32 [m/s]
to
Drive must move in the corresponding direction at desired inspection operation speed.
Should the drive move at proper speed but in the wrong direction, invert direction with parameter
P 3 "control direction".
ca
If the drive is running irregularly or not at correct speed, invert control direction with parameter P
4 "control direction".
If inspection operation speed cannot be reached despite the change of control direction, check
es
whether the incremental encoder is plugged in correctly and/or the encoder pulse number is
correct (see chapter 5.4.2 P 105: pulse number)
w.
The encoder pulse number is 1,024 or 4,096 or 16,384 pulses incremental encoder for
Asynchronous motor and 2,048 pulse absolute encoder for Synchronous motor
ww
29
OPERATING MANUAL 4. PUTTING INTO OPERATION
It must be noted that, dependent on the load direction involved, a lasting control deviation in the
actual speed develops on the setting with “I gain 0“, i.e. the drive cannot accelerate in load
direction under certain circumstances or it will even drive into the wrong direction.
The “P gain” should have a safety clearance to the tendency to oscillate mentioned above
n
(smaller by a factor of approx. 2).
For normal operation, set an “I gain“ unequal “0“ again.
.c
Experience has shown that the specified default values (P = 8 and I = 50 ms) produce rather
favorable running performance.
ts
A recorder can be connected to MP 42A or MP 43A board TMI2 for assessment of the running
characteristic. MP 26 or the inverter housing is the common reference point.
The measurement signals available at these display outputs area selected through parameter
P10 or P11 (see chapter 5. Parameter entry).
ar
Example:
The actual speed value with sign will be displayed at MP 42A with value "0" in P10.
rp
B) Run at rated speed
For optimization of rated speed run, acceleration and acceleration change (jerk) can be changed
with parameters P19 and P20.
to
In so doing, see to it that a minimum jerk (see chapter 4.8.2 Diagram for determination of
minimum jerk) must be set in line with the selected acceleration; if not, no range of constant
acceleration will exist.
la
It must be noted that the floor-to-floor distance is greater than the sum from acceleration and
deceleration distance from rated speed (see diagram). (See chapter 4.8.3 Diagram for
ca
C) Short run
A short run is present, if the floor-to-floor distance is less than the sum from acceleration and
deceleration distance from rated speed, but greater than the deceleration distance from rated
w.
speed.
Rated speed will not be reached in floor-to-floor runs.
How to proceed for activation of short run see chapter 6. Short run device.
ww
D) Load specification
Should the car depart after disengaging the brake, this can be reduced by entry of a starting
torque.
(See chapter 5.4.1 variable parameters P50 to P54).
In the absence of load-weighing device, starting can also be optimized for a specific load
condition.
E) Acceleration precontrol
Should the drive tend to overshoot or undershoot, this can be optimized by activation of
acceleration precontrol.
(See chapter 5.1 General).
30
OPERATING MANUAL 4. PUTTING INTO OPERATION
n
.c
ts
ar
rp
to
la
ca
X96 Aux, CAN interface X912 RS-232C interface for F240 DSP
X901 +24V, GND output X917 Absolute encoder input (Sin/Cosine)
ww
31
OPERATING MANUAL 4. PUTTING INTO OPERATION
n
.c
ts
ar
rp
Vdc(3.5V) = Transformation DC Link (700V), 200 :1
to
Connector
name content name content
la
LED status
Condition No. name content
es
H44- R LS
Fast blinking, Main or Vdc over- voltage
H11- Y Program Run Blinking, program runs
ww
32
OPERATING MANUAL 4. PUTTING INTO OPERATION
n
.c
ts
ar
rp
to
la
ca
es
w.
ww
33
OPERATING MANUAL 5. PARAMETER ENTRY
5. PARAMETER ENTRY
5.1 General
The program permits the parameters of a defined storage area to be changed. The permissible range of
each parameter will be checked whenever an entry is made and limited accordingly. A distinction is made
between variable parameters (e.g maximum speed, direction of rotation or control parameters) and display
parameters for indicating various operating values (e.g. current speed, current reference value, etc.).
The following display will appear on starting the CPIK frequency inverter:
ThyssenKrupp Elevator
System start Vxxx
ThyssenKrupp Elevator
CPIK 32 Vxxx
n
This display of the program number version will appear for 15 seconds only. Program version number to be
quoted for any inquiries made to the factory. If one of the keys is operated during these 15 seconds, the
.c
display of the version number will be discontinued immediately and the selected function will be performed.
If you wait for 15 seconds, the first available parameter will be displayed.
ts
P 0 Reference value start delay
500 ms
The turn-on duration of the display lighting is set to two hours after the key was pressed last.
ar
When a key is operated for the first time after turning off the lighting, the lighting will be turned on again, but
this does not have any effect on the parameter function.
rp
5.2 Operation
Parameter entry permits the following functions:
5.2.1 Display and change of parameters
to
la
ca
es
w.
ww
The parameter number with a short description of the selected parameter is in the first line, the current value
with its physical unit in the second line. A cursor appears below the parameter number.
The desired parameter number can now be selected with the keys “+“ and “-“. By advancing the cursor with
the “cursor“ key, the selection can now proceed in steps of tens or hundreds.
P 5 P gain
8.0
By operating the “parameter“ key, the cursor will go to the numeric value and a change of the numeric value
will be possible.
34
OPERATING MANUAL 5. PARAMETER ENTRY
n
Number of error entries Error description or number
↓ ↓
.c
1/34 Control voltage on
283:45:30 24
ts
↑ ↑
Operating hours Additional information
The old stack entries will be displayed by operating the “-“ key repeatedly. New entries can be displayed
ar
again by pressing the “+“ key.
5.3.2 Delete error stack
rp
Display of stack contents (see chapter Display error stack) and press “save key”. Acknowledge with “+“ key
in response to the display “error stack to be deleted ?“. The entry “error stack deleted“ will then be displayed.
5.3.3 End error stack
to
Parameter selection will be displayed again after the “parameter“ key has been pressed.
5.4 Parameters
la
The delay time between activation of the brake and enabling of the drive can be set in lifts without brake
acknowledgement. The reference value will not be started until the brake is disengaged. Values between 50
and 5000 ms can be set. The typical value is between 300 ms and 800 ms.
ww
This value must be set to 5000 ms in lifts with brake acknowledgement. This means that the reference value
start depends on the brake acknowledgement.
36
OPERATING MANUAL 5. PARAMETER ENTRY
P 3: Direction of rotation
The motor’s direction of rotation can be changed through this parameter. The parameter can be set to "not
inverted" or “inverted“ only.
P 3 Direction of rotation
→ not inverted
A change of this parameter brings about an immediate change of the direction of rotation.
P 4: Control direction
a) Asynchronous motor : The fact that the polarities of reference speed and actual speed values are in a
correct relation to each other is of importance to the speed controller. If this is not the case, the motor will
rotate irregularly at low speed. The control direction can be reversed through parameter P 4. The parameter
n
can be set to 'not inverted' or 'inverted' only. A change of this parameter has the same effect as a reversal of
two phases of the motor line.
.c
b) Synchronous motor : This parameter is not available for synchronous motor. The motor connections U,
ts
V, W of synchronous motors must be connected exactly to prevent wrong assignment to encoder and
magnet positions (poles). i.e. the control direction cannot be changed by interchanging two phases.
ar
P 5: Speed controller - P gain
This is where the speed controller response can be set. (Setting values 0 ... 50 / default value 8).
A change of parameter will become effective immediately.
rp
P 6: Speed controller - I gain
Same as P5, but for the I component (setting values 0 ... 70 / default value 50 ms).
to
The smallest effective value is 4 ms. If the I component is to be deactivated, 0 ms will have to be entered.
P 7: Selection of language
la
This is where the language can be selected. Language selection is in plain text.
P 7 language
→ English
ca
P 8: RS-485 mode
es
This is where a TIC or TCM or TAC50K interface can be preset (default off).
<0> : TCM (if there is no TIC board) or TIC (if there is TIC board)
<5> : TAC50K
w.
37
OPERATING MANUAL 5. PARAMETER ENTRY
The required maximum speed of the motor is automatically calculated from the values of parameters P 13 to
P 16 and then displayed.
P 19: Acceleration change (jerk) Set desired acceleration change (jerk) [m/s³].
P 20: Acceleration Set desired acceleration / deceleration in [m/s²].
n
the acceleration precontrol. This particularly applies to gearless drives.
.c
P 22: Acceleration precontrol value
For assessment of the correct setting of acceleration precontrol, the actual speed value ( P10 to “0”) should
ts
be measured at measuring point 42A and the controller output (P 11 to “7”) should be measured at point 43A.
Setting instructions:
ar
P 21 = “OFF” (precontrol OFF), Controller output to be measured during a run with recorder
rp
to
la
Record further runs and adjust P 22 to such an extend that the speed controller output does no
longer show an acceleration torque (Ma approx. 0):
w.
ww
• When more than one speeds are selected at the same time, the order is as follows:
Inspection speed Vi has priority, i.e. as soon as vi is selected, all other speeds will be ignored.
Leveling speed V0 can always be selected and will not be effective until all the other speeds are inactive.
• After selecting a speed value, a nominal/actual value comparison will be carried out (“tolerance band
monitoring”). Excessive variance causes emergency stop to be activated.
• Emergency stop at inspection speed Vi or emergency operation speed V3 is only be activated if the
39
OPERATING MANUAL 5. PARAMETER ENTRY
n
P 25: Speed Vn Rated speed Vn [m/s]
.c
P 26: Speed V2 Intermediate speed V2 [m/s]
ts
Second intermediate speed Vn2 [m/s] (To be selected by controlling of Vn and V2 at the same time.)
The value ranges of parameters P19, 20 and 23 to 27 are as follows:
Setting range Standard
ar
P 19 Jerk 0.5 ~ 2.00 m/s³ 0.80 m/s³
P 20 Acceleration 0.3 ~ 1.10 m/s² 0.70 m/s²
rp
P 23 Leveling speed V0 0.01 ~ 0.30 m/s 0.03 m/s
P 24 Inspection speed Vi 0.20 ~ 0.63 m/s 0.30 m/s
P 25 Rated speed Vn 0.05 ~ 3.85 m/s 1.00 m/s
to
Further intermediated speeds are available from software versions TMI V15.3 or V5.5:
P 28 : Speed V3
ca
P29 to P32
Select “intermediated speed” in parameter P48 or P49 to activate. Otherwise parameters P29 to P32 cannot
w.
be displayed. Corresponding +24V input signals X1.11a (for P48) or X1.9b to be present.
When selecting Vi or V0 and another intermediated speed at the same time the following will apply:
• inspection speed Vi has priority, i.e. as soon as vi is selected, all other speeds will be ignored.
ww
• Leveling speed V0 can always be selected and will not be effective until all the other speeds and inactive.
P29 : Speed V4 (X1.5b = low and X1.6b = low) Intermediated speed V4 [m/s]
P30 : Speed V5 (X1.5b = high and X1.6b = low) Intermediated speed V5 [m/s]
P31 : Speed V6 (X1.5b = low and X1.6b = high) Intermediated speed V6 [m/s]
P32 : Speed V7 (X1.5b = high and X1.6b = high) Intermediated speed V7 [m/s]
40
OPERATING MANUAL 5. PARAMETER ENTRY
n
Intermediate speed V2 P26 0 X 0 1 0 X
.c
2 Intermediate speed Vn2 P27 0 X 1 1 0 X
Intermediate speed v4 V4 P29 0 X 0 0 1 X
Intermediate speed v5 V5 P30 0 X 1 0 1 X
ts
Intermediate speed v6 V6 P31 0 X 0 1 1 X
Intermediate speed v7 V7 P32 0 X 1 1 1 X
Emergency operation V3 P28 0 X 1 0 0 1
ar
“0” means “off”, “1” means “active”, “X” means “irrelevant”
Table 5-6 Overview speed selection
rp
P 37 : Operating point v < 0.3
to
Speed can be set within a range of 0.15 ~ 0.3 m/s. As soon as the speed falls below the set speed, the
contact at terminals 11b and 12b on board TIC will be closed. The set operating point is provided with a
hysteresis of ±1% of Vn.
la
P 38 : Short-run device
Option of enabling / disabling the short-run device.
ca
41
OPERATING MANUAL 5. PARAMETER ENTRY
n
Reverse rotation of a car on disengagement of the brake can be reduced by entering a starting torque.
.c
This specification is made either with the help of a load-weighing device or it can be entered for a single
specific load condition, if no load-weighing device is available.
ts
a) without load-weighing device
If no load-weighing device is available, the load specification can be enabled/disabled with P 50 and a fixed
value can be entered with P 54. This specification will then be optimal for one load state only. Observe that
ar
the values P51 and P52 must be unequal as internal computation is made by formula [(P 51 - P 52) x P 54].
P 51 = 0, P 52 = 45% (default value) is recommended.
rp
P 51: Current value / load weighing
This is where the current loading state of the car is indicated in % of rated load. (Commonly approx. 45 % in
to
the event of load compensation of car). This implies that the load-weighing device was correctly adjusted
beforehand.
la
1. Establish load compensation (car shall not start spinning with the brake disengaged)
2. Read current value from P 51
3. Enter value into P 52
es
or enter any empirical value, e. g. 45 % means that the counterweight is 45 % of rated load.
During a run at constant speed with emergency electrical operation (e.g. empty UP or Down) the momentary
load current will be displayed. The load specification will be computed internally from this current value by
ww
42
OPERATING MANUAL 5. PARAMETER ENTRY
Intervention gain to be set through parameter P 55. The position controller is disabled at the running
characteristic start to permit control to be effected by the speed controller.
Preparation
TMI2 board: EPROM version from V5.5b. FLASH program from F030701.
P 0 = 280ms re-adjust reference value start delay
P 50 = OFF switch off load weighing
P 55 = 5 (start value) enable control of position controller gain
Setting
When starting from upper-most landing downwards with the car empty, P 55 will be set to a value
reverse rotation. Small values to be selected, preferably.
Check selected setting during performance in opposite run direction and readjust P 55 to avoid
jerk. Values from P 55 = 0.1 to 25 to be selected.
n
Note
.c
Retrofitting of existing installation is possible. The method above does not replace use of
overload sensor. “Occupied”, ”abuse” and “no-load” conditions cannot be recognized.
ts
P55: Position controller gain (only with synchronous machine with EnDat encoder)
The precontrol signal supplied through load weigh device is replaced by a position controller computer. After
entering pulse enable and release of brake, the car is retained in its momentary position through the position
ar
controller. With P55 the position controller gain can be adjusted. Thereby P50 must be switched OFF and P0
must be corrected to 280 ms
rp
P 60: Rated frequency motor See name plate of motor
P 61: Rated voltage motor See name plate of motor
to
P 65: Rotor time constant (Tr) computed To be computed from above values
P 66: No-load current (Id) computed To be computed from above values
P 67: Reference rotor time constant (Tr) Value of P 65 to be entered
ca
(P 40), four new parameters will be available (P 80 ~ P 83). These parameters permit to set the current
controller for the unknown motor.
ww
43
OPERATING MANUAL 5. PARAMETER ENTRY
n
③ Enter the number of pole-pair in parameter P97
.c
- Determine correct rotor position
It is no longer necessary to align the encoder manually. Align the rotor in pre-determined position then align
ts
by storing in encoder EEPROM. The data will be maintained even after disconnecting the supply voltage.
If CPIK is connected, “Ready” LED will light on TMI2 board.
① P86: change operation mode motor, switch from “<0> normal operation” to “<1> Rotor Alignment”
ar
To confirm the change with key button “P/W”
“Ready” LED goes out for some seconds, since DSP reset is carried out
rp
After “Ready” LED lights up again wait approx. 2 seconds until initiation starts
② start adjusting operation by FWD or RVS command
to
seconds “Ready” LED goes out for some seconds, because DSP reset is be carried out.
This indicates that the adjusting procedure is finished.
w.
Check the following entry into error event stack of CPIK: “Rotor Position Stored Encoder”
ww
44
OPERATING MANUAL 5. PARAMETER ENTRY
P 98: Id reduced
If "third-party motor" is selected at P40 (motor selection) of asynchronous motors, the “Id reduced” can adjust
the field current of motor.
n
.c
P 160: Maximum current in % of i-overload
Here you can set limit value for torque current.
For example: In case of to use DTE140S009 Motor and CPIK 48M Inverter
ts
Rated motor capacity 16 kW
Rated motor current 37 A- rms
Permissible motor starting current 67 A- rms
ar
Maximum Inverter current 95 A- rms
45
OPERATING MANUAL 5. PARAMETER ENTRY
-1
P 100: Motor speed Display of current motor speed in min (rpm)
P 101: Actual speed Display of current speed in m/s
The current actual speed of the lift is displayed in m/s. The display will be correct only, if the entries of
parameters P 13, P 14 and P 15 are correct!
n
P 104: Binary outputs for TIC card
.c
All inputs and outputs of the plug will be displayed. This parameter will be displayed in binary. Every bit of
this numerical value corresponds to an input signal at plug X1 of TlC board.
P 103: Binary inputs P 104: Binary outputs
ts
signal Input binary signal output binary
UP X1.3b B00000000 00000001 ESP X1.4a, 5a B00000000 00000001
ar
DOWN X1.4b B00000000 00000010 EBS X1.1a, 2a B00000000 00000010
VN X1.5b B00000000 00000100 V < 0.3 X1.11b, 12b B00000000 00000100
V2 X1.6b B00000000 00001000 Prog X1.13b, 14b B00000000 00001000
rp
V1 X1.7b B00000000 00010000
V0 X1.8b B00000000 00100000
QSP X1.7a, 8a B00000000 01000000
to
encountered. The displayed value must change by the encoder pulse number per motor revolution. (i.e.
change of display = encoder pulse number)
es
P 108: Load current The momentary load current is displayed in Ampere (Field current).
P 109: Load current The momentary load current is displayed in Ampere (Torque current).
ww
P 111: sv calculated
To perform a short run, the distance to be covered by the lift between start of deceleration at rated speed v n
and reaching leveling speed (sv).
The distance is computed from the data of parameters P19, P20, P23 and P25 and will be indicated in P111
for the purpose of checking.
P 112: sv measured
During a run in which Vrated is reached, the deceleration distance will be measured and displayed at the end
46
OPERATING MANUAL 5. PARAMETER ENTRY
of the run. The distance is measured from the moment signal Vn is removed until V0 is reached.
n
.c
P 117: PWM operating frequency
The current operating frequency is indicated in kHz.
ts
P 118: Position of absolute encoder (only with synchronous machines EnDat format encoder)
The display parameter “P118” permits to adjust the encoder. 9999 is displayed as long as the absolute
encoder position is unknown. As soon as “position recognized” is indicated, the pulse numbers will be
ar
displayed in quadruple resolution.
–16384 ~ 0 ~ +16384 is displayed for half motor rotation.
rp
+16384 to –16384 is displayed for the next half motor rotation.
–16384 ~ 0 ~ +16384 is displayed for the motor rotation following next.
to
All outputs of the CAN will be displayed. This parameter will be displayed in binary.
Where: Drive Enable B 0000 0000 0000 0001
ww
47
OPERATING MANUAL 6. SHORT RUN DEVICE
n
P15 Suspension
.c
P19 Jerk
P20 Speed
P23 Speed V0
ts
P25 Speed VN
The deceleration distance VN will be computed from these parameters and indicated in parameter P111. The
deceleration distance will be measured for each normal run (VN is reached) and displayed in P112. However,
ar
this measured distance will not be considered in the short-run calculation.
Short run with "sharper rounding".
rp
This is the case, if the deceleration point is reached during the top rounding of the acceleration phase. If
deceleration with the set jerk is performed, the deceleration distance will be too large. The landing will be
bypassed. To avoid this, the run will have a "sharper rounding" i.e., a greater jerk.
to
6.2 Settings
P 38 : Short-run computer (ON/OFF)
la
There is the option of enabling or disabling the function of short-run computation. Short-run computation only
works if VN is switched to V0.
ca
longer, if lower values are entered, the creep distance will become shorter. Values from –40.0cm to +40.0cm
are possible.
The pattern of running characteristic can be checked at measuring points (MP42A or MP43A). For this
w.
purpose, parameter P10 or P11 must be set to value (11) – running characteristic status. A diagram will
appear at the respective measuring point and this permits the individual phases of the running characteristic
ww
48
OPERATING MANUAL 6. SHORT RUN DEVICE
n
.c
ts
ar
Where :
MP42A/43A
rp
2.50 V V = 0 m/s
3.15 V Rounded from constant speed to constant acceleration
to
49
OPERATING MANUAL 7. MODERNIZATION
n
between 270 and 300 V with the lift running at rated speed. Decrease motor voltage through P 68 (no-load
current Id) (the arising motor voltage based on the no-load current from the name plate data is too high,
.c
normally). The motor voltage in P 76 should be approx. between 270 to 300 V both for UP and DOWN
direction. Increase or decrease the rotor time constant (Tr) in P 67 if the torque required for acceleration
phase is insufficient. This value can be changed step by step by 25 %.
ts
e) Now move the lift with empty car;
This means that motor-driven run under no load shall be performed in DOWN direction and a brake test
during run in UP direction. The motor voltage shall increase by the value of the motor slip with the lift
running in DOWN direction, i.e. approx. 30 V to 50 V; decrease of the motor voltage shall be less in UP
ar
direction (approx. 10 V to 30 V). If this is not the case, change the value of the rotor time constant in P 67
step by step by 25% each. Perform setting when the motor runs at operating temperature (and not with
extremely cold or hot motor).
rp
f) Check setting of speed controller once again.
Set I-gain of controller to 0 ms and increase P-gain until the motor vibrates or hums. Now reduce P-gain to
to
half value. Select I-gain approx. between 10 ms and 100 ms depending on overshooting of running
characteristic. Pre-controlling of the speed controller through acceleration precontrol (P 21 und P 22)
improves running performance. Check running performance with the car running at no-load, half load and
la
full load.
Use below table indicating standard data for values to be entered provided that :
• Data on the name plate of the motor are incomplete or
• The rated point indicated is not standard (indicated deliberately in case of single-speed,
ca
Single speed,
0.75 ~ 0.85 1320 ~ 1400 40 ~ 150 ms 0.5 ~ 0.7 x Irat
pole-changing motor
Frequency inverter motor 0.85 ~ 0.90 1460 250 ~ 400 ms 0.4 x Irat
w.
51
OPERATING MANUAL 8. ANNEX
n
TAC50K TCM TIC
.c
P0 Reference start deceleration SA SA 500ms
P1 Brake application time SA SA SA 700ms
P2 Full scale motor speed SA S:100, A:1500rpm
ts
P3 Direction of rotation SA SA SA Inverted/ Not inverted
P4 Control direction A A A Inverted/ Not inverted
ar
P5 P gain (speed controller) SA SA SA 10.0
P6 I gain (speed controller) SA SA SA 20 ms
rp
P7 Language selection SA SA SA English
P8 Communication SA SA SA (0)
P10 Analog output MP42A SA SA SA (0)
to
55
OPERATING MANUAL 8. ANNEX
n
P48 Input PROGANA SA <2> emergency 220V
P49 Input PROGIN SA <1> load weighing FM
.c
P50 Load pre-setting SA SA SA Off / On
P51 Actual load measuring value SA SA SA + 0%
ts
P53 Adopt load current SA SA SA 000.0A
P54 Load specification gain SA SA SA +65.0%
ar
P55 Gain position controller S S S +65.0%
P60 Rated motor frequency AF AF AF Modernization
P61 Rated motor voltage AF AF AF Modernization
rp
P62 Rated motor speed SAF SAF SAF Modernization
P63 Rated motor current AF AF AF Modernization
to
P81 Comp. values from auto- tuning SAF SAF SAF Modernization
P82 Manual change current controller SAF SAF SAF Modernization
w.
56
OPERATING MANUAL 8. ANNEX
n
P104 Binary outputs SA
P105 Encoder pulse number SA SA SA
.c
P106 Reference value SA SA SA
P107 Load current SA SA SA
ts
P110 Switching sequence index SA SA SA
P111 SV computed SA
ar
P112 SV measured SA
P113 Distance covered SA
P116 DC link voltage SA SA SA
rp
P117 PWM operating frequency SA SA SA
P118 Absolute encoder position S S S
to
57
OPERATING MANUAL 8. ANNEX
n
Control voltage ON Inverter switched on for the first time R
Time error in program sequence of C167
Watchdog error Number of errors Exchange TMI2 board, EEPRO R
.c
processor
SMR to TCM (only with
Collective fault message to TCM Varying error causes R
TCM control)
No SMR present No collective fault message present Error deleted message R
ts
No power part CPIK type is Electronics does not recognized connected power part of inverter.
Undefined value at AD-channel 14 and 15 H and DC link
recognized displayed Check ribbon cable X934 for correct fastening. Exchange complete device.
1) Wrong EEPROM cross sum = 0; EPROM Load default values; set installation dependent parameters; exchange TMI2
EEPROM error R
ar
2) Error in EPROM data set <>0; EEPROM board, if unsuccessful.
Over-temperature Actual motor current H and DC link
Module temperature over 90 °C Check connections to sensor at heat sink
heat sink at error tripping delayed
CAN: R
rp
Actual motor current 1) Check connections to sensor at motor
Over-temperature motor Motor PTC thermistor tripped TIC: H and DC
at error tripping 2) Measure using ohmmeter
link delayed
Error stack deleted Error stack was deleted None
to
1) Motor current sum not zero
1) Perform isolation test at motor windings
2) Time error in program sequence of F240 Actual motor current 1) H
Earth Fault 2) Exchange TMI2 board
3) Encoder of synchronous machine is at error tripping 2) Reset F240
3) Exchange synchronous encoder
defective
la
1) Check 3-phase power input
Actual motor current
DC link under-voltage DC link voltage less than 410 V 2) Compare DC link voltage displayed at PEP and measuring H and DC link
at error tripping
3) Exchange device
1) Check chopper resistor
Actual motor current
DC link over-voltage DC link voltage is greater than 760 V
ca 2) Compare DC link voltage displayed at PEP and measuring H and DC link
at error tripping
3) Exchange device
PDPINT tripped by following errors:
1) Over-current 1) see error “over-current” H for 10sec
es
Power Drive Protection
2) Monitoring saturation voltage of power 2) Power module in CPIK device defective; exchange after 5 x
(event message)
device 3) see error “DC link over-voltage” PDPINT
PDPINT
3) Over-voltage DC link 4) see error “±15V under-voltage” DSP reset
4) Supply voltage error
w.
Does error occur in operating phase, “driving” with “empty car up” or “fully loaded
Hardware suppressor circuit recognized H and DC link
Overcurrent car down” or in both case?
overcurrent DSP reset
Measure motor current: check offset load: car clamped in rails?
1) Sin/cos encoder (EnDat) not connected H
ww
58
OPERATING MANUAL 8. ANNEX
n
±15V undervoltage or Actual motor speed 2) Check reference module MAX675CSA808 H and DC link
Power supply error or DC link voltage error
DC link > 850V at error tripping 3) Chopper module, check braking resistor DSP reset
.c
4) Compare DC link voltage displayed at P116 and actual value using voltmeter
Vist unequal Vsoll ±10%
Monitoring reference-actual speed values, Actual motor speed
(not monitored for CPIK Error output with CPIK devices not connected to CAN bus only H
(“hose error”) at error tripping
ts
with CAN bus)
a) Control does not respond to handshake
telegram = 0 (case a)) 1) Check wiring of CAN bus connection
CAN-error H
b) Control does not transmit reference value = 1 (case b)) 2) load "default values" in CPIK device
ar
telegrams (CPIK with CAN only)
Encoder failure
1) Check motor connection lines
(with synchronous Pulse encoder “EnDat” H
2) Adjust pulse encoder (with “hidden P86”)
machines only)
rp
Flag set (with CPIK with Marking initiated from TCM control through Flag No. from error
Flag from TCM control R
CAN bus only) CAN telegram stack of TCM control
Chopper with pulses Degree of DC link voltage increase causes DC LINK voltage at
to
DC link protection against temporary over-voltage; chopper disconnected again R
disabled chopper connection error tripping
Error
Loose contact, 5V reference voltage faulty, A/D conversion faulty. Check ribbon
Extra info important recognized in
la
Changed coding resistance recognized with cable X934 for correct fastening. Device out of service until device size
Device size changed for software standstill phase
device ON recognized during switching on, is recognized again. Perform reset: switching
development only only.
ON/OFF
Standby supply operation is activated. (No Extra info relevant for
Standby supply
ca PWM frequency switched to 4kHz. Lower threshold for DC LINK undervoltage.
further entry in error stack when standby software
operation active Energy regeneration unit remains switched off.
supply operation is ended.) development only
Actual motor speed P106: check reference value,
Overspeed 120% rated speed exceeded H
es
at error tripping P101: check actual speed
Actual DC LINK
DC LINK > 200V not During DC link charge UDC LINK repeatedly
voltage at error Short circuit DC link, charging resistor defective; power voltage missing?
reached not increased above 200V within 200 ms.
tripping
w.
Unintended movement
a) Re-alien EnDat encoder
Speed Monitor a) EnDat encoder miss aliened Speed in RPM H
b) Check controller and brake
b) moving without speed command
ww
59
OPERATING MANUAL 8. ANNEX
n
Furthermore it is clear that this happened with current controller and PWM active.
.c
PDPINT cause:
Bit number Binary code Error description
ts
Bit 2^0= 1 00 0000 0001 SC (from power module)
Bit 2^1= 2 00 0000 0010 F240 signals PDPINT
ar
Bit 2^2= 4 00 0000 0100 Error with supply voltage (24V,-15V or +15V)
Bit 2^3= 8 00 0000 1000 Error with supply voltage +15V
rp
Bit 2^4= 16 00 0001 0000 DC link over-voltage is recognizes by Software
Bit 2^5= 32 00 0010 0000 DC link over-voltage is recognizes by Hardware
Bit 2^6= 64 00 0100 0000 KS over-current (hardware recognition)
to
Further information:
Bit number Binary code Error description
la
60
OPERATING MANUAL 8. ANNEX
n
6 RK1 and RK2 K06.1 and K06 do not go off
.c
7 RK1 and RK2 K01.1, K01, K06.1 and K06 do not go off
Non-recurring error entry for error numbers 2...7; new disconnection attempts after 1s
ts
- Relay K1 or K2 switched on, wait for acknowledge RK1:
ar
No. Input (connector) possible cause
10 K06 does not go on. Safety circuit (X517) interrupted?
rp
11 K01 does not go on. Safety circuit (X517) interrupted?
14 RK2 K06.1 instead of K06 ON.
15 RK2 K01.1 instead of K01 ON
to
6 RK1 and RK2 K06.1 and K06 ON; K06 expected only
7 RK1 and RK2 K01.1, K01, K06.1 and K06 ON; K06 expected only
la
61
8.7 Connection diagram
n
.c
ts
ar
rp
to
la
ca
es
w.
ww
62
8.7 Connection diagram
n
.c
ts
ar
rp
to
la
ca
es
w.
ww
64
8.7 Connection diagram
n
.c
ts
ar
rp
to
la
ca
es
w.
ww
65
8.7 Connection diagram
n
.c
ts
ar
rp
to
la
ca
es
w.
ww
66
8.7 Connection diagram
n
.c
ts
ar
rp
to
la
ca
es
w.
ww
67
8.7 Connection diagram
n
.c
ts
ar
rp
to
la
ca
es
w.
ww
68
8.7 Connection diagram
n
.c
ts
ar
rp
to
la
ca
es
w.
ww
70
8.8 How to use the Hyper-terminal
CPIK series have two methods for parameter management
a. management by Parameter Entry Panel
b. management by Hyper terminal in computer
This appendix explains how to manage the Parameter in CPIK using Hyper-terminal.
n
Parity bit : no
Stop bit :1
.c
Flow control : no
ts
Press “H”, all available instructors will shows in HELP menu and press “R”, available parameter range shows.
ar
rp
to
la
ca
es
w.
71
8.8.4 Showing Fault history
Fault history shows by press “F” and number of Fault can store 200 items in Fault stack
n
.c
ts
Message of “Control voltage on” means registered at Power On.
ar
rp
8.8.5 Important notice
All information in Hyper-terminal window can store as text file, this text file will use usefully as analysis of
to
>#
Enter Password : > GEHEIM
es
w.
ww
72