Reyrolle Test Block

Catalog Reyrolle 7XG222 · Edition 1

siemens.com/reyrolle
Devices and Application
7XG222 2RMLG Test Block and 2RLMB-R Test Plug

Description
The 7XG222 range of test blocks, housed within an Epsilon
enclosure, offers facilities for monitoring and secondary injec-
1.1
tion testing of power system protection schemes in conjunction
with the appropriate multi-fingered test plug.
The 2RMLG Test Block has 14 pairs of spring loaded contacts
which are linked to a terminal block positioned at the rear of the
enclosure.
The 2RMLG07 is coded to only accept the 2RMLB-R7 Test Plug
which has connection terminals 21, 23, 25, and 27, internally.
The 2RMLG08 is coded to only accept the 2RMLB-R8 Test Plug
which has internal pairs 1 and 3, 5 and 7, 9 and 11, and 15 and
17, shorted together internally.
The 2RMLG09 is coded to only accept the 2RMLB-R9 Test Plug
which has terminals 1-3-5-7, 9-11, 17-19 & 21-23-25-27 shorted
together internally..
Each pair of contacts is normally closed completing the circuit
through the test block when the associated protection equip-
ment is in use.
For testing purposes the test block can be accessed by removing
the front cover. The 2RMLG01 has a metallic probe attached to
the front cover assembly which when withdrawn open circuits
the 2 contacts at position 13 and 14.
The main DC auxiliary supply to the protection scheme or relay
can be wired to this circuit to prevent inadvertent tripping of the
[sc_7XG22, 1, --_--]
protection circuit after removal of the cover and during the test
procedure.
The 2RMLG02/07/08/09 do not include the above facility and
• 7XG222 Suitable for vertical or horizontal mounting
contacts 13 and 14 are normally closed. These contacts must • Standard 4U case design
not be used for current circuits, as the relevant contact finger on • Coded test plugs prevent incorrect insertion
the 2RMLB-R test plug is shorter in this position.
The short test finger in position 13 and 14 on the 2RMLB-R will
open contacts 13 and 14 in the test block after the other fingers
have made contact in all other positions.
It is important that the sockets in the test plug which correspond
to the current transformer secondary windings are linked prior
to the test plug being inserted into the test block.
This will ensure that the current transformer secondary wind-
ings are short circuited prior to disconnection from the protec-
tion scheme or relay. If the DC auxiliary supply is to be used
during testing it can be linked using the sockets in the test plug.
Operation of the contacts can be monitored by connecting the
test equipment to the protection scheme or relay with the even
numbered sockets of the test plug. If a number of 2RMLG test
blocks are connected to a relay it is recommended that the DC
supply be routed through each of them to safeguard against
inadvertent operation.

Benefits
The features of the Test Block are:
• Finger safe design
• Finger safe test leads
• Various scheme configurations
• Retention fixings on test plugs

4 Digital Grid ⋅ Reyrolle Test Block (7XG222) Catalog ⋅ Siemens Protection Devices
System
Hardware Construction

Hardware Construction 2RMLB-R7 with Shorting Contacts


The 2RMLG is a size E2 unit in the Epsilon range of enclosures. The 2RMLB-R7 is similar to the 2RMLB-R1 with shorted contact
The rear terminal block has 28 terminals each with an M4 screw pairs 21-23-25-27 and is coded to be used with the MMLG07
outlet for the attachment of external wiring, fitted with ‘L’ Test Socket only.
shaped pre-insulated ring tongue terminations.
2RMLB-R8 with Shorting Contacts
The 2RMLB-R8 is similar to the 2RMLB-R1 with shorted contact
pairs 1-3, 5-7, 9-11, 15-17 and is coded to be used with the 2.1
2RMLG08 Test Socket only.
2RMLB-R9 with Shorting Contacts
The 2RMLB-R9 is similar to the 2RMLB-R1 with shorted contact
pairs 1-3-5-7, 9-11, 17-19, 21-23-25-27 and is coded to be used
with the 2RMLG09 Test Socket only.

NOTE

i BEFORE inserting a Test Plug into a Test Socket


carrying current transformer secondary circuits
ensure that the test plugs corresponding to the
current transformer circuits are short-circuited.
This is to ensure the current transformer secon-
dary circuits are not inadvertently open-circuited
during insertion of the last plug.

NOTE

i
[sc_7XG22_2RMLG, 1, en_US]

Figure 2.1/1 2RMLG BEFORE inserting a Test Plug to measure current


ensure that the ammeter is on the correct range
and that it is connected to its test leads.

The connections will depend upon the scheme and details must
be obtained from the appropriate diagrams. If it is necessary to
use the DC auxiliary supply during testing, then a test link may
be fitted across the sockets in the Test Plug.
Test Block Information
The device terminal label displays the MLFB code, serial number,
relay description, terminal contact details, and safety symbols.

European CE marking

Refer to device documentation

Electrical Hazard

Waste Electrical and Electronic Equip-


ment Directive (WEEE)

Guideline for the Eurasian Market


[sc_7XG22_2RMLB, 1, en_US]

Figure 2.1/2 2RMLB

2RMLB-R Series Multi-Fingered Test Plugs


The 2RMLB-R series is inserted into the 2RMLG test socket and is
securely retained by means of two knurled screws. The 2RMLB-
RI test plug incorporates 28 test sockets, each socket accepting a
shrouded or plain 4 mm diameter plug.

Digital Grid ⋅ Reyrolle Test Block (7XG222) Catalog ⋅ Siemens Protection Devices 5
Technical Documentation
Connection Diagrams

Connection Diagrams

3.1

[dw_7XG22_connection_2RMLG01/02, 1, en_US]

Figure 3.1/1 Typical Application of the 2RMLG01 / 2RMLG02 Test Block and 2RMLB-R1 Test Plug

2RMLG02 13/14 connected as in the same way as


NOTE

i
other positions.
2RMLG01 13/14 open cct when cover is removed
and all other positions are connected.

6 Digital Grid ⋅ Reyrolle Test Block (7XG222) Catalog ⋅ Siemens Protection Devices
Technical Documentation
Connection Diagrams

3.1

[dw_7XG22_connection_2RMLG07, 1, en_US]

Figure 3.1/2 Typical Application of the 2RMLG07 Test Block and 2RMLB-R7 Test Plug

Digital Grid ⋅ Reyrolle Test Block (7XG222) Catalog ⋅ Siemens Protection Devices 7
Technical Documentation
Connection Diagrams

3.1

[dw_7XG22_connection_2RMLG08, 1, en_US]

Figure 3.1/3 Typical Application of the 2RMLG08 Test Block and 2RMLB-R8 Test Plug

[dw_7XG22_connection_2RMLG09, 1, en_US]

Figure 3.1/4 Typical Application of the 2RMLG09 Test Block and 2RMLB-R9 Test Plug

8 Digital Grid ⋅ Reyrolle Test Block (7XG222) Catalog ⋅ Siemens Protection Devices
Technical Documentation
Dimension Drawings

Dimension Drawings
This section displays the different dimensional views of a Test
Block.

3.2

[dw_7XG22_dimension_panelcutout, 1, en_US]

Figure 3.2/1 Panel Cut-out View

[dw_7XG22_dimension_side, 1, en_US]

Figure 3.2/2 Side View (Vertical) Top View (Horizontal)

Digital Grid ⋅ Reyrolle Test Block (7XG222) Catalog ⋅ Siemens Protection Devices 9
Technical Documentation
Dimension Drawings

3.2

[dw_7XG22_dimension_top, 1, en_US]

Figure 3.2/3 Front View

NOTE

i The ∅3.6 holes are for M4 thread forming (trilob-


ular) screws. These are supplied as standard and
are suitable for use in ferrous/aluminum panels
1.6 mm thick and above. For other panels, holes
to be M4 clearance (typically ∅4.5) and relays
mounted using M4 machine screws, nuts and
lockwashers (supplied in panel fixing kit).

10 Digital Grid ⋅ Reyrolle Test Block (7XG222) Catalog ⋅ Siemens Protection Devices
Technical Documentation
Technical Data

Technical Data 2RMLB-R8 As above with the exception of


terminal pairs 1-3, 5-7, 9-11, and
Indication of Conformity
15-17 which are permanently
shorted together as pairs.
This product complies with the 2RMLB-R9 As above with the exception of
directive of the Council of the terminal pairs 1-3-5-7, 9-11,
European Communities on the 17-19, and 21-23-25-27 which are
harmonization of the laws of the permanently shorted together in
Member States relating to electro- groups.
magnetic compatibility (EMC Direc-
tive 2014/30/EU) and concerning
electrical equipment for use within Transient Overvoltage
specified voltage limits (Low IEC 60255-27
Voltage Directive 2014/35/EU) as
well as restriction on usage of
hazardous substances in electrical 2RMLG 01/02/07/08/09 5 kV impulse between all case
and electronic equipment (RoHS terminals connected together and
Directive 2011/65/EU). the case earth terminal.
5 kV impulse between any contact
This conformity has been proved 3.3
pair and either adjacent alternate
by tests conducted by Siemens AG
contact pair, provided the inter-
in accordance of the Council Direc-
mediate contact pair is not used.
tive in accordance with the product
standard IEC/EN 60255-26 for the 2 kV impulse between any contact
EMC directives, and with the pair and either adjacent contact
standard IEC/EN 60255-27 for the pair.
low-voltage directive. 2RMLG 01 only 2 kV impulse between terminals
RoHS directive 2011/65/EU is met 13 and 14 when the cover is
using the standard EN 50581. The removed (e.g. opening the auxil-
device has been designed and iary supply or trip circuit).
produced for industrial use. 2RMLB-R1 As 2RMLG 01 plus 2 kV impulse
between incoming and outgoing
contacts when inserted.
EMC Compliance
2RMLB-R7 As above with the exception of
terminals 21, 23, 25, and 27 which
89/336/EEC These products have been classi-
are permanently shorted together.
fied as electromagnetically benign
and are therefore excluded from 2RMLB-R8 As above with the exception of
the European Community EMC terminal pairs 1-3, 5-7, 9-11, and
Directive. (89/336/EEC) 15-17 which are permanently
shorted together as pairs.
2RMLB-R9 As above with the exception of
General Technical Data
terminal pairs 1-3-5-7, 9-11,
High Voltage Withstand 17-19, and 21-23-25-27 which are
permanently shorted together in
IEC 60255-5 groups.

2RMLG 01/02/07/08/09 5 kVRMS for 1 minute between all


Current and Voltage Withstand
case terminals connected together
and the case earth terminal.
2RMLG 01/02/07/08 All contact circuits rated at 20 A
5 kVRMS for 1 minute between any continuously or 400 A for 1 s, AC
2RMLBR1-R9
contact pair and either adjacent or DC.
alternate contact pair, provided AC 300 V/DC 300 V maximum
the intermediate contact pair is not service voltage.
used.
2 kVRMS for 1 minute between any
Mechanical Tests
contact pair and either adjacent
contact pair.
Test Standard
2RMLG 01 only 1 kVRMS for 1 minute between
Vibration IEC 60255-21-1,
terminals 13 and 14 when the
cover is removed (e.g. opening the Response and endurance,
auxiliary supply or trip circuit).
Class 2
2RMLB-R1 As 2RMLG 01 plus 2 kVRMS for 1
minute between incoming and
outgoing contacts when inserted.
2RMLB-R7 As above with the exception of
terminals 21, 23, 25, and 27 which
are permanently shorted together.

Digital Grid ⋅ Reyrolle Test Block (7XG222) Catalog ⋅ Siemens Protection Devices 11
Technical Documentation
Technical Data

Climatic Environmental Tests


Temperature
IEC 60068-2-1/IEC 60068-2-2/IEC 60255-6

Ambient operating temperature -10 °C to +55 °C


Storage temperature (non-opera- -25 °C to +70 °C
tional)

Humidity
IEC 60068-2-3

Damp heat test, steady state 56 days at 93 % RH and +40 °C

Enclosure Protection (2RMLG only)


3.3 IEC 60529

IP50 (dust protected)

12 Digital Grid ⋅ Reyrolle Test Block (7XG222) Catalog ⋅ Siemens Protection Devices
Technical Documentation
Ordering Information

Ordering Information – 7XG222

Product Description Order Number


1 2 3 4 5 6 7 – 8 9 10 11 12 – 13 14 15 16
Test Modules (2RMLG) 7 X G 2 2 2 0 – □ □ A 0 0 – 0 A A 0
| | | | |
Category | | | | |
Ancillary equipment 2 | | | |
| | | |
Ancillary Equipment | | | |
Modular case test components 2 | | |
| | |
Test Component Type | | |
Test modules (2RMLG) 2 | |
| |
Component Type | |
Test module (2RMLG01) 1 |
3.4
Test module without open circuit facility between terminals 13 and 14 when cover removed 2 |
(2RMLG02)
Test module with automatic CT shorting (2RMLG07) 3 |
Test module with automatic CT shorting (2RMLG08) 4 |
Test module with automatic CT shorting (2RMLG09) 5 |
|
Mounting |
E2 case vertical A
E2 case horizontal B

Digital Grid ⋅ Reyrolle Test Block (7XG222) Catalog ⋅ Siemens Protection Devices 13
Technical Documentation
Ordering Information

Ordering Information – 7XG2241

Product Description Order Number


1 2 3 4 5 6 7 – 8 9 10 11 12 – 13 14 15 16
Test Plugs (2RMLB-R) 7 X G 2 2 4 1 – □ A A 0 0 – 0 A A 0
| | | | |
Category | | | | |
Ancillary equipment 2 | | | |
| | | |
Ancillary Equipment | | | |
Modular case test components 2 | | |
| | |
Test Component Type | | |
Test plugs (2RMLB-R) 4 1 |
|
Component Type |
Multi finger test plug complete with leads (2RMLB-R1) 1
3.4
Multi finger test plug complete with leads and internal shorting links (2RMLB-R7) 3
Multi finger test plug complete with leads and internal shorting links (2RMLB-R8) 4
Multi finger test plug complete with leads and internal shorting links (2RMLB-R9) 5