Technical Information: Range-Free Controller FA-M3 System Upgrade Guide
Technical Information: Range-Free Controller FA-M3 System Upgrade Guide
Technical Information: Range-Free Controller FA-M3 System Upgrade Guide
www.yokogawa.com/itc/
TI 34M06Z42-01E
2018.06 2nd Edition (YK)
Yokogawa Electric Corporation
1. Introduction 1
1. Introduction
The FA-M3 has been used in many systems since its debut in December 1992.
Early systems now require replacement of parts with service life for preventive
maintenance or system upgrade.
This document focuses on the description of system upgrade to the latest product
models.
■ NOTE
・ Information in this document is current as of May 2018 and subject to
change without notice. Contact Yokogawa’s sales representative for the
latest information.
・ Proper nouns such as product and company names contained herein are
registered trademarks or trademarks of their respective owners.
All Rights Reserved. Copyright © 2018, Yokogawa Electric Corporation TI 34M06Z42-01E 2018.06-00
1. Introduction 2
All Rights Reserved. Copyright © 2018, Yokogawa Electric Corporation TI 34M06Z42-01E 2018.06-00
2. System degradation and recommended replacement cycle 3
All Rights Reserved. Copyright © 2018, Yokogawa Electric Corporation TI 34M06Z42-01E 2018.06-00
2. System degradation and recommended replacement cycle 4
IMPORTANT
・ Recommended replacement cycle is a time period for preventive
maintenance of parts with service life, but is not a guarantee against random
failures.
・ Recommended replacement cycle is a guide, and varies with operating
conditions.
All Rights Reserved. Copyright © 2018, Yokogawa Electric Corporation TI 34M06Z42-01E 2018.06-00
2. System degradation and recommended replacement cycle 5
All Rights Reserved. Copyright © 2018, Yokogawa Electric Corporation TI 34M06Z42-01E 2018.06-00
2. System degradation and recommended replacement cycle 6
IMPORTANT
・ The CPU module uses a large capacity lithium battery, which has continuous
backup capacity beyond its service life (10 years) but replacement (for each
module) at end of service life is recommended.
All Rights Reserved. Copyright © 2018, Yokogawa Electric Corporation TI 34M06Z42-01E 2018.06-00
2. System degradation and recommended replacement cycle 7
■ Modules that use photocouplers (with recommended
replacement cycle below 10 years)
Recommended replacement cycle: 5 years (When used in
high temperature environment (about 45°C or higher))
All Rights Reserved. Copyright © 2018, Yokogawa Electric Corporation TI 34M06Z42-01E 2018.06-00
3. System upgrade procedure 8
■ Upgrade procedure
● STEP 1: Select replacement module
Select a replacement module by referring to replacement product
table.
All Rights Reserved. Copyright © 2018, Yokogawa Electric Corporation TI 34M06Z42-01E 2018.06-00
3. System upgrade procedure 9
All Rights Reserved. Copyright © 2018, Yokogawa Electric Corporation TI 34M06Z42-01E 2018.06-00
3. System upgrade procedure 10
■ Compatibility
● Ladder programs running on discontinued sequence CPU
modules can run on replacement CPU models by updating the
ladder programming tool.
■ Precautions
● Programming tool
Latest programming tool WideField3 is required for using the latest F3SP7□-□S
CPU module. WideField3 is downward compatible with earlier CADM3, WideField
and WideField2.
● About F3SP7□-□N
F3SP7□-□N has been changed to F3SP7□-□S since January 2012 along with
functional upgrade. F3SP7□-□S should be used in future system upgrade.
All Rights Reserved. Copyright © 2018, Yokogawa Electric Corporation TI 34M06Z42-01E 2018.06-00
3. System upgrade procedure 11
■ Changes
● The replacement sequence CPU module has an Ethernet port.
All Rights Reserved. Copyright © 2018, Yokogawa Electric Corporation TI 34M06Z42-01E 2018.06-00
3. System upgrade procedure 12
・RK33-0N RK73-0N
All Rights Reserved. Copyright © 2018, Yokogawa Electric Corporation TI 34M06Z42-01E 2018.06-00
3. System upgrade procedure 13
Discontinued Replacement
Item Compatible Changes
product product
F3BU04-0N
F3PU10-0S
F3SC21-1N ✓
F3SP22-0S
F3WD64-3P
F3SC22-1F F3BU04-0N
F3PU10-0S
✓ ① About Value/Value-2
F3SC23-1F F3SP22-0S
・Sale of Value/Value-2 sets has ended.
F3WD32-3F
・Individual modules need to be purchased
F3SC22-1A F3BU04-0N
henceforth.
F3PU10-0S
Value set F3SP22-0S ✓
F3SC23-1A ②Replacement precautions
F3XD16-3F
・Requires Programming Tool WideField3.
F3YD14-5A
・As the CPU module has higher processing
F3SC22-2F F3BU04-0N
speed, verify system operation after
F3SC23-2P F3PU10-0S
✓ replacement.
F3SP22-0S
F3SC23-2F ・The power supply module uses M4 instead of
F3WD64-3P
M3 terminal screws.
F3BU04-0N
(applicable only when replacing F3SC21-1N)
F3PU10-0S
F3SC23-6P ✓
F3SP22-0S
F3WD64-4P
Service F3SP05-0P
F3PU10-0S
items for ✓
F3SP08-□P F3SP22-0S
Value set
■ Hardware
● Replacement models use the same terminal block, connector, and
pin arrangement as discontinued products so are usable once
replaced.
■ Configuration
● Replacement input module has wider range of input response
speed options.
・ Old product (model suffix N): Input response time: 16 ms, 1 ms
・ Latest product (model suffix F): input response time: Always, 62.5 μs,
250 μs, 1 ms, 16 ms
Note: 64-point module has no 16 ms option.
All Rights Reserved. Copyright © 2018, Yokogawa Electric Corporation TI 34M06Z42-01E 2018.06-00
3. System upgrade procedure 14
■ Programs
● No ladder program change needed for upgrading to replacement
product.
All Rights Reserved. Copyright © 2018, Yokogawa Electric Corporation TI 34M06Z42-01E 2018.06-00
3. System upgrade procedure 15
Discontinued Replacement
Item Compatible Changes
product product
Terminal arrangement changed (common
F3DA02-0N △ terminals independent of output type)
Output type set by software (-10 to 10 V range by
F3DA04-6R default).
Analog output F3DA04-1N △ Output behavior at startup differs (no output until
setting is written)
High impedance.
Output behavior at startup differs (no output until
F3DA08-5N F3DA08-5R △ setting is written)
F3AD04-0V F3AD04-5V ✓ Upward compatible. Wiring and terminal block
cannot be reused.
F3AD04-0N ✓
F3AD04-5R Different external dimensions (depth); terminal
F3AD04-0R ✓ block mounting position is in front.
Analog input F3AD08-1V F3AD08-5V ✓
Upward compatible. Wiring and terminal block
F3AD08-1N ✓ can be reused.
F3AD08-5R External dimensions (depth) differs; terminal
F3AD08-1R ✓
block mounting position is in front.
F3AD08-4V F3AD08-4W ✓
No or minor modification of application programs
needed after replacement if module is used as a
F3HA06-1R △
high-speed AD conversion module, which refers
High-speed data only to constantly updated data without using its
F3HA08-0N
acquisition data acquisition function.
Application is incompatible and needs
F3HA12-1R △ modification if the data acquisition function or
acquisition-related filter function etc. is used.
F3CV04-1N F3CU04-1S × Software modification is needed.
F3CR04-0N F3CU04-0S × Software modification is needed.
PID/Temperatur
F3CR04-1N F3CU04-1S × Software modification is needed.
e control
F3CT04-0N F3CU04-0S × Software modification is needed.
F3CT04-1N F3CU04-1S × Software modification is needed.
F3YP04-0N F3YP24-0P × Software modification is needed.
F3YP08-0N F3YP28-0P × Software modification is needed.
F3YP14-0N F3YP24-0P × Software compatible. However, the number of
Positioning
installable modules changed from 36 (288 axes)
to 16 (128 axes). Hardware incompatible. Need
F3YP18-0N F3YP28-0P × to review external wiring such as changing from
5VDC to 24VDC.
F3LC11-2N F3LC11-2F △ Upward-compatible. Beware of position of rotary
Personal switch.
computer link F3LC11-1N F3LC11-1F △ Software modification is needed only if using
events.
F3RZ81-0F × Software modification is needed. For 1 channel.
Ladder F3RZ81-0N
F3RZ82-0F × Software modification is needed. For 2 channels.
communication
F3RZ91-0N F3RZ91-0F × Software modification is needed.
Software compatible but has no AUI port and has
F3LE01-5T F3LE01-1T ✓
different look (e.g. connector location.)
Software compatible but has different look (e.g.
F3LE01-0T F3LE01-1T ✓
connector location.)
Ethernet
Software compatible but has different look (e.g.
F3LE11-0T F3LE11-1T ✓
connector location.)
Software compatible but has no AUI port and has
F3LE12-0T F3LE12-1T ✓
different look (e.g. connector location.)
Software compatible. Beware of FL-net version.
F3LX01-0N F3LX02-2N ✓ F3LX01 (Ver.1) and F3LX02 (Ver.2) cannot be
FL-net mixed.
Software compatible but has no AUI port and has
F3LX02-1N F3LX02-2N ✓
different look (e.g. connector location.)
All Rights Reserved. Copyright © 2018, Yokogawa Electric Corporation TI 34M06Z42-01E 2018.06-00
3. System upgrade procedure 16
Discontinued Replacement
Item Compatible Changes
product product
Software compatible but has no AUI port and has
NX autonomous F3NX01-0N F3NX01-2N ✓
different look (e.g. connector location.)
distributed F3NX01-1N F3NX01-2N ✓
Software compatible but has no AUI port and has
different look (e.g. connector location.)
F3LP02-0N*2
(Software compatible but hardware incompatible.
F3LP01-0N (F3LP□□-□ ✓
New and old products cannot be mixed)
FA link H N*3)
(F3LP□□-□ (Software compatible but hardware incompatible.
F3LP02-0N*2 ✓
N*3) New and old products cannot be mixed)
*1 F3DA04-6R/DCR with default current (4 to 20 mA) output type is available for customers using current output. Contact
Yokogawa's sales representative for details.
All Rights Reserved. Copyright © 2018, Yokogawa Electric Corporation TI 34M06Z42-01E 2018.06-00
3. System upgrade procedure 17
To be
2006 F3SP66-4S*1 ✓ ✓
discontinued
To be
2006 F3SP67-6S*1 ✓ ✓
discontinued
2011 F3SP22-0S Available ✓
All Rights Reserved. Copyright © 2018, Yokogawa Electric Corporation TI 34M06Z42-01E 2018.06-00
3. System upgrade procedure 18
All Rights Reserved. Copyright © 2018, Yokogawa Electric Corporation TI 34M06Z42-01E 2018.06-00
3. System upgrade procedure 19
● Files to be ported
Executable program file: extension = .PRG
Block files: extensions = .BLK .OBT .CMT
Macro blocks: extensions = .MBL .MOB .MCM
Table 3.8 Programming tool versus supported OS
IMPORTANT
・ In CADM3, project (executable program) and blocks are stored in a folder
(directory) with a name defined by a user using CAM3’s initial design menu.
Normally, programs to be ported are stored near individually defined
directories. (In CADM 3, folder name and project name do not match.)
All Rights Reserved. Copyright © 2018, Yokogawa Electric Corporation TI 34M06Z42-01E 2018.06-00
3. System upgrade procedure 20
■ Converting files
● Opening an executable by selecting [Open File in other formats]
automatically converts it to WideField3 format.
①
②
All Rights Reserved. Copyright © 2018, Yokogawa Electric Corporation TI 34M06Z42-01E 2018.06-00
3. System upgrade procedure 21
■ Redefine configuration
● Configuration revert to factory settings if the CPU model name is
changed.
All Rights Reserved. Copyright © 2018, Yokogawa Electric Corporation TI 34M06Z42-01E 2018.06-00
3. System upgrade procedure 22
CAUTION
① Simultaneity of shared devices
For F3SP28 and newer sequence CPU modules, shared device data can
be specified as Simultaneous or Non-simultaneous in the configuration.
If compatibility with the old CPU is required when upgrading
F3SP20/30/21/25/35, specify as Non-simultaneous (default setting is
Simultaneous).
All Rights Reserved. Copyright © 2018, Yokogawa Electric Corporation TI 34M06Z42-01E 2018.06-00
3. System upgrade procedure 23
All Rights Reserved. Copyright © 2018, Yokogawa Electric Corporation TI 34M06Z42-01E 2018.06-00
3. System upgrade procedure 24
● Various migration guides are available for download from the PLC
(FA-M3)/RTOS Controller (e-RT3) web page on the following FA-
M3 partner portal (member registration and login is required).
https://partner.yokogawa.com/global/itc /index.htm
All Rights Reserved. Copyright © 2018, Yokogawa Electric Corporation TI 34M06Z42-01E 2018.06-00
4. Upgrading related equipment 25
All Rights Reserved. Copyright © 2018, Yokogawa Electric Corporation TI 34M06Z42-01E 2018.06-00
5. Reference Information 26
5. Reference information
5.1 Sequence CPU specifications
comparison
Table 5.1 Specifications comparison of sequence CPU V series and R series
Item F3SP71-4S F3SP76-7S F3SP66-4S F3SP67-6S F3SP22-0S
Program size 60Kstep 260Kstep 56Kstep 120Kstep
10Kstep
Project size 120KStep 520Kstep 112Kstep 240Kstep
Ethernet ✓ ✓ ×
SD card ✓ (SDHC compatible) ✓ ×
Interface
RS-232C × ✓ ✓
USB ✓ ✓ ×
45ns min.
Basic instructions 3.75ns min. per instruction 17.5ns min. per instruction
per instruction
180ns min.
Application instructions 7.5ns min. per instruction 70ns min. per instruction
per instruction
200μs-
Cycle 100μs-25.0ms 200μs-25.0ms
Sensor control 25.0ms
Resolution 10μs 100μs 100μs
Input/output 4,096 8,192 4,096 8,192 4,096
Internal relays 16,384 65,535 16,384 32,768 16,384
Data registers 16,384 65,535 16,384 32,768 16,384
Device/ File registers 32,768 262,144 32,768 262,144 32,768
memory size
Cache registers 131,072 524,288 × ×
Constant definition
16384 words 32768 words 16384 words 32768 words ×
area
RAMDISK 4MB 4MB ×
Login control ✓ × ×
Security Operation log ✓ × ×
Password ✓ ✓ ✓
All Rights Reserved. Copyright © 2018, Yokogawa Electric Corporation TI 34M06Z42-01E 2018.06-00
5. Reference Information 27
All Rights Reserved. Copyright © 2018, Yokogawa Electric Corporation TI 34M06Z42-01E 2018.06-00
5. Reference Information 28
USB × × ×
17.5ns min. per 17.5ns min.
Basic instructions 17.5ns min. per instruction
instruction per instruction
70ns min “per
Application instructions 70ns min. per instruction 70ns min. per instruction
instruction
200μs-
Cycle 200μs-25.0ms 200μs-25.0ms
Sensor control 25.0ms
Resolution 100μs 100μs 100μs
Input/output 4,096 8,192 8,192
Internal relays 16,384 32,768 65,535
Data registers 16,384 32,768 65,535
Device/memory
File registers 32,768 262,144 262,144
size
Cache registers × × ×
Constant definition
× × ×
area
RAMDISK × × ×
Login control × × ×
Security Operation log × × ×
Password ✓ ✓ ✓
All Rights Reserved. Copyright © 2018, Yokogawa Electric Corporation TI 34M06Z42-01E 2018.06-00
5. Reference Information 29
USB × × × × ×
180ns min. 120ns min. 90ns min. 180ns min. 90ns min.
Basic instructions
per instruction per instruction per instruction per instruction per instruction
360ns min. 240ns min. 180ns min. 360ns min. 180ns min.
Application instructions
per instruction per instruction per instruction per instruction per instruction
Cycle × × × × ×
Sensor control
Resolution × × × × ×
Input/output 2,048 4,096 8,192 2,048 2,048
Internal relays 4,096 8,192 16,384 4,096 8,192
Data registers 5,120 8,192 8,192 5,120 8,192
Device/memory
File registers × 32,768 32,768 × ×
size
Cache registers × × × × ×
Constant
× × × × ×
definition area
RAMDISK × × × × ×
Login control × × × × ×
Security Operation log × × × × ×
Password ✓ ✓ ✓ ✓ ✓
CADM3 or CADM3 or
Programming tool CADM3 or later CADM3 or later CADM3 or later
later later
Current consumption 350mA 420mA 560mA 325mA 405mA
All Rights Reserved. Copyright © 2018, Yokogawa Electric Corporation TI 34M06Z42-01E 2018.06-00
5. Reference Information 30
*1
Add-on CPU Module
F3SP21-0N
F3SP22-0S
F3SP25-2N
F3SP35-5N
F3SP28-3□
F3SP38-6□
F3SP53-4□
F3SP58-6□
F3SP59-7S
F3SP6□-□S
F3SP7□-□N
F3SP7□-□S
F3BP20-0N
F3BP30-0N
Max. quantity
F3SP21-0N 4 ✓ ✓ ✓ ✓ ✓ ✓ ✓ ✓ ✓ ✓ ✓*2 ✓ ✓ ✓
F3SP22-0S 4 ✓ ✓ ✓ ✓ ✓ ✓ ✓ ✓ ✓ ✓ ✓ ✓ ✓ ✓
F3SP25-2N 4 ✓ ✓ ✓ ✓ ✓ ✓ ✓ ✓ ✓ ✓ ✓ *2 ✓ ✓ ✓
F3SP35-5N 4 ✓ ✓ ✓ ✓ ✓ ✓ ✓ ✓ ✓ ✓ ✓ *2 ✓ ✓ ✓
F3SP28-3□ 4 ✓ ✓ ✓ ✓ ✓ ✓ ✓ ✓ ✓ ✓ ✓ ✓ ✓ ✓
Main CPU Module
F3SP38-6□ 4 ✓ ✓ ✓ ✓ ✓ ✓ ✓ ✓ ✓ ✓ ✓ ✓ ✓ ✓
F3SP53-4□ 4 ✓ ✓ ✓ ✓ ✓ ✓ ✓ ✓ ✓ ✓ ✓ ✓ ✓ ✓
F3SP58-6□ 4 ✓ ✓ ✓ ✓ ✓ ✓ ✓ ✓ ✓ ✓ ✓ ✓ ✓ ✓
F3SP59-7S 4 ✓ ✓ ✓ ✓ ✓ ✓ ✓ ✓ ✓ ✓ ✓ ✓ ✓ ✓
F3SP6□-□S 4 ✓ ✓ ✓ ✓ ✓ ✓ ✓ ✓ ✓ ✓ ✓ ✓ ✓ ✓
F3SP7□-□N 4 ✓*2 ✓ ✓*2 ✓*2 ✓ ✓ ✓ ✓ ✓ ✓ ✓ ✓*3 ✓*2 ✓*2
F3SP7□-□S 4 ✓ ✓ ✓ ✓ ✓ ✓ ✓ ✓ ✓ ✓ ✓*3 ✓ ✓ ✓
F3BP20-0N 1 ✓ ✓ ✓ ✓ ✓ ✓ ✓ ✓ ✓ ✓ ✓ *2 ✓ × ×
✓ ✓ ✓ ✓ ✓ ✓ ✓ ✓ ✓ ✓ *2 ✓
F3BP30-0N 1 ✓ × ×
*1: Indicates the maximum number of modules that can be used in total including the main CPU module when CPU modules with the same
model name as the main CPU module are used as add-on CPU modules.
*2: Up to two modules can be installed in this combination.
*3: The combination of F3SP7- N + F3SP7-N + F3SP21 (F3SP25, F3SP35/ F3BP20, F3BP30) is not possible.
The combination of F3SP7- N + F3SP7-S + F3SP21 (F3SP25, F3SP35/ F3BP20, F3BP30) is not possible.
The combination of F3SP7- S + F3SP7-S + F3SP21 (F3SP25, F3SP35/ F3BP20, F3BP30) is not possible.
The combination of F3SP7- N + F3SP7-S is possible.
All Rights Reserved. Copyright © 2018, Yokogawa Electric Corporation TI 34M06Z42-01E 2018.06-00
5. Reference Information 31
All Rights Reserved. Copyright © 2018, Yokogawa Electric Corporation TI 34M06Z42-01E 2018.06-00
Rev-1
Revision Information
Title : FA-M3 System Upgrade Guide
Document No. : TI 34M06Z42-01E
All Rights Reserved. Copyright © 2018, Yokogawa Electric Corporation TI 34M06Z42-01E 2018.06.30-00