MSR127 Minotaur Monitoring Safety Relays: Installation Instructions
MSR127 Minotaur Monitoring Safety Relays: Installation Instructions
MSR127 Minotaur Monitoring Safety Relays: Installation Instructions
Original Instructions
Topic Page
Rockwell Automation cannot accept responsibility for failure of this device if the
procedures given in these instructions are not followed or if it is used outside the
Summary of Changes 1
recommended specifications in these instructions.
Safety 1
Declaration of Conformity 1
Functional Description 1
IMPORTANT The safety inputs of these products are described as
normally closed (N.C.), that is, with the guard closed,
Diagnostics 1 actuator in place (where relevant) and the machine able to
Safety Input 2 be started. Exposure to shock and/or vibration in excess
of what is stated in IEC 60068 part: 2-6/7 must be avoided.
Reset 2 Adherence to the recommended inspection and
Wiring Examples 2 maintenance instructions forms part of the warranty.
Circuit Diagram 2
Approximate Dimensions 3
Installation 3
Repair
Safety Specification 3
Technical Specifications 3
ATTENTION: MSR127 safety relays are not repairable.
Summary of Changes If there is any malfunction or damage, do not attempt to repair. The unit must be
This publication contains the following new or updated information. This list replaced before machine operation is allowed.
includes substantive updates only and is not intended to reflect all changes.
Translated versions are not always available for each revision.
Declaration of Conformity
Topic Page
Rockwell Automation declares that all MSR127 safety relays are in
Updated title of publication 1 conformity with Directives 2014/30/EU, 2006/42/EC, 2011/65/EU as
Updated Declaration of Conformity section 1 specified in the Declaration of Conformity available from
Updated Positive Edge section 2 rok.auto/certifications.
Updated Circuit Diagram section 2
Updated Safety Specification section 3
Functional Description
Safety The unit is enabled once supply is powered up and the safety circuits are closed.
The PWR status indicator is on.
This device is intended to be part of the safety-related control system of a
machine. A valid reset operation activates the safety outputs. The CH1 and CH2 status
indicators of the output are lit. At demand of the safety function and if any fault,
the safety outputs are de-energized within the specified response time.
Safety Notes
Before installation, a risk assessment must be performed to determine whether Fault Detection
the specifications of this device are suitable for all foreseeable operational and
environmental characteristics of the machine to which it is to be fitted. At regular If a fault occurs, the internal relay circuit forces the safety outputs off. One or both
intervals during the life of the machine, check whether the characteristics output status indicators may be off. The PWR indicator may be flashing. Remove
foreseen remain valid. the fault and cycle the safety input to re-enable the device. Cycling power to the
safety relay can also clear the fault condition.
ATTENTION: Danger of serious injuries.
Misuse can result in malfunction.
• Only authorized and trained personnel must start up, Diagnostics
assemble, install, manipulate, or retrofit the device. Auxiliary (N.C.) outputs 41…42 monitor the safety output state.
• Installation must be in accordance with these instructions.
• Do not defeat, tamper, remove, or bypass this unit.
MSR127 Minotaur Monitoring Safety Relays Installation Instructions
Open
K1
MSR 127RP
Reset K1 K2 M
Reset modes — Unit is available with automatic/manual start (MSR127T/TP) and max PLe, SIL3
manual monitored reset (MSR127R/RP).
A valid start/reset can only be operated if the feedback circuit is closed. Feedback
contacts of controlled actuators are connected in series with start/reset circuit Circuit Diagram
(S12-S34).
A1 S11 S52 S12 S34 13 23 33 41 …S34 13 23 33 43
(S10) (S33)
T - Automatic/manual Start Reset
In automatic/manual start mode, the reset circuit S12-S34 is not monitored against K2
signal changes (no edge detection). The reset circuit can be closed before or after
the safety inputs are closed. Unit is active once the safety inputs are closed and
the reset circuit has been closed. If the safety inputs and reset circuit are K1
concurrently closed during powerup, unit is activated immediately.
A2 S21 S22 14 24 34 42 14 24 34 44
MSR127 MSR127.1
MSR127/(MSR127.1) MSR127.1
MSRxxxR
440R-xxxxM K1
S11 S52 S12
S21 S22 S34
K2
Attribute Value
TM (PTI) [a] 20
dop [d] / hop [h] (1) 365 / 24
tcycle [h]/[s] (2) 8 / 28,800
(1) Operation time (day, hour)
(2) Cycle time (hour, second)
At the end of life, this equipment should be collected separately from any unsorted municipal waste.
Rockwell Automation maintains current product environmental information on its website at rok.auto/pec.
Your comments help us serve your documentation needs better. If you have any suggestions on how to improve our content, complete the form at rok.auto/docfeedback.
For technical support, visit rok.auto/support.
Rockwell Otomasyon Ticaret A.Ş. Kar Plaza İş Merkezi E Blok Kat:6 34752 İçerenkÖy, İstanbul, Tel: +90 (216) 5698400 EEE YÖnetmeliğine Uygundur
Allen-Bradley, expanding human possibility, Minotaur, Rockwell Automation, and Rockwell Software are trademarks of Rockwell Automation, Inc.
Trademarks not belonging to Rockwell Automation are property of their respective companies.