Chapter Three: Steam Generators 3.1 Definition
Chapter Three: Steam Generators 3.1 Definition
Chapter Three: Steam Generators 3.1 Definition
Chapter Three
Steam Generators
3.1 Definition
A steam generator or a boiler is defined as a closed vessel in which water
is converted into steam by burning of fuel in presence of air at desired
temperature, pressure and at desired mass flow rate.
According to American society of Mechanical Engineers (A.S.M.E.), a
steam generator or a boiler is defined as "a combination of apparatus for
producing, finishing or recovering heat together with the apparatus for
transferring the heat so made available to the fluid being heated and
vaporized.
The boiler is the part of a steam power plant process that produces the
steam and thus provides the heat.
A steam boiler as show in figure 3.1 fulfills the following statements:
• It is part of a type of heat engine or process
• Heat is generated through combustion (burning)
• It has a working fluid, heat carrier that transfers the generated heat
away from the boiler.
• The heating media and working fluid are separated by wall.
1
Power Plant Steam Generators
gases (hot fluid) temperature decreases and at lower temperature hot fluid is
thrown into the atmosphere via stack/chimney. The function of boiler is to
facilitate the generation of steam by providing the necessary heat transfer
surfaces as show in figure 3-2 , space for storage of water and steam, furnace
for burning the fuel and necessary equipment’s for control of safe operation
the large variety of
The steam or hot water under pressure can then be used for transferring
heat to a process that consumes the heat in the steam and turns it into work.
In a modern boiler, there are two main types of boilers when considering
the heat transfer means from flue gases to feed water, these type can be
classified as follow:-
3
Power Plant Steam Generators
in figure 3-3. The heat from the flue gases is transferred from the tubes to
the water in the container, thus the water is heated into steam. An easy way
to remember the principle is to say that a fire tube boiler has "fire in the
tubes". A fire tube boiler is simple and its initial cost is low and used in
industrial plants to produce saturated steam up to (18 bar) pressure about (6
kg/s) capacity.
4
Power Plant Steam Generators
Major disadvantages associated with fire tube boilers are mentioned below:
The conditions are the opposite of a fire tube boiler. The water circulates
in many parallel-connected tubes. The tubes are situated in the flue gas
channel, and are heated by the flue gases, which led from the furnace
through the flue gas passage. In a modern boiler, the water circulates in the
tubes, which are welded together and form the furnace walls. Therefore the
water tubes are directly exposed to radiation and gases from the combustion
Figure 3-4. Similarly to the fire tube boiler, the water tube boiler received its
name from having "water in the tubes". A modern utility boiler is usually a
water tube boiler, because a fire tube boiler is limited in capacity and only
feasible in small systems. Water tube boiler is classified as:
Vertical tube boiler
5
Power Plant Steam Generators
6
Power Plant Steam Generators
These boilers are less suitable for use with impure and dirty water. Because
of scale formation on tubes, overheating and bursting of the tubes is likely to
occur.
• Skilled persons are required for inspection.
• The cost of maintenance is high when compared to fire tube boilers.
7
Power Plant Steam Generators
8
Power Plant Steam Generators
3.6.1 General
The natural circulation is one of the oldest principles for steam/water
circulation in boilers. Its use has decreased during the last decades due to
technology advances in other circulation types. Natural circulation principle
is usually implemented on small and medium sized boilers. Typically the
pressure drop for a natural circulation boiler is about 5-10 % of the steam
pressure in the steam drum and the maximum steam temperature varies from
540 to 560 °C.
9
Power Plant Steam Generators
The saturated water flows next from the steam drum through downcomer
tubes to a mud drum (header). There are usually a couple of downcomer
tubes, which are unheated and situated outside the boiler.
The name "mud drum" is based on the fact that a part of the impurities in
the water will settle and this 'mud' can then be collected and removed from
the drum.
The saturated water continues from the header to the riser tubes and
partially evaporates. The riser tubes are situated on the walls of the boiler for
efficient furnace wall cooling. The rises tubes are sometimes also called
generating tubes because they absorb heat efficiently to the water/steam
mixture. The riser tubes forms the evaporator unit in the boiler.
10
Power Plant Steam Generators
Where:-
g : is the gravitational acceleration (9,81 m/s2).
H : the heights are according to Figure 3.6 [m].
(ρdc − ρr ) : the difference in the average density between the downcomers
(dc) and raiser (r) tubes [kg/m3].
11
Power Plant Steam Generators
The boiling height, i.e. the height where water has high enough
temperature to boil, can be calculated using the circulation ratio and
water/steam enthalpies:
Where:-
h”: is the enthalpy [kJ/kg] of saturated steam,
h’ : enthalpy of saturated water (at the pressure of the steam drum),
U: is the circulation ratio, and
Δh: is the enthalpy change caused by the rise in evaporation pressure
because of the subcooling of water in downcomer tubes).
3.7.1 General
In contrast to natural circulation boilers, forced circulation is based on
pump-assisted internal water/steam circulation. The circulation pump is the
main difference between natural and forced circulation boilers. In the most
common forced circulation boiler type, the principles of forced circulation
are basically the same as for natural circulation, except for the circulation
pump. The operation pressure level of forced circulation boiler can be
slightly higher than a natural circulation boiler, but since the steam/water
separation in the steam drum is based on the density difference between
steam and water, these boilers are not either suitable for supercritical
pressures (>221 bar). Practically the maximum operation pressure for a
forced circulation boiler is 190 bar and the pressure drop in the boiler is
about 2-3 bar.
12
Power Plant Steam Generators
The water/steam circulation begins from the feed water tank, from where
feed water is pumped. The feedwater pump raises the pressure of the
feedwater to the wanted boiler pressure. In practice, the final steam pressure
is below 190 bar, in order to keep the steam steadily in the subcritical region.
The feed water is then preheated in the economizer almost up to the boiling
point of the water at the current pressure.
13
Power Plant Steam Generators
The variations in circulation ratio result from the pressure level of the
boiler, therefore high pressure boilers have low ratios and low- construction
of the recovery boiler using natural circulation drum.
14
Power Plant Steam Generators
15
Power Plant Steam Generators
3.9.2 Economizer
It is also known as ‘Feed water heater’. It is used to heat the feed-water by
utilizing the heat of the waste flue gases before they are discharged to the
atmosphere through chimney. Figure 3.10 show types of economizers.
16
Power Plant Steam Generators
17
Power Plant Steam Generators
The steam generated may be either wet steam (or) dry steam (or)
superheated steam. The wet steam must be separated from the dry steam
before letting it enter the main steam line figure 3.13. This separation is done
by steam separator. It prevents the wet steam from entering the main steam
line, thus prevents the turbine blades from corrosion.
18
Power Plant Steam Generators
For the smallest drops (less than 10 microns) fiber mist eliminators are
used. As the particles become larger, impingement devices like screens are
adopted. As they get still larger, chevrons are used. Finally, for the larger
drops, cyclones are adopted. They can operate for the entire range of liquid-
to-gas-phase flow rates.
19
Power Plant Steam Generators
The mass flow rate of drops less than 10 microns in diameter is quite
small in typical steam generation installations so the mass fraction of liquid
flowing out of the separator section for installation of this type is typically of
the order of 0.1 percent.
20
Power Plant Steam Generators
The simplest separator is the gravity separator shows in figure 3.15. The
superficial velocity of vapor at the free surface should be less than 0.3 m/s.
When the velocity is greater than this the carryover increases rapidly. Often
these separators are constructed as large-diameter inclined pipes in which
the two-phase mixture enters at the bottom of the high end, and separated
liquid is removed from the bottom of the low end. Vapor is removed from
the top of the high end. In excess of 99 percent of the entrained liquid can
be removed in gravity separators though some small drops are carried over
for all flow rates. These separators can be horizontal or vertical cylinders or
spheres.
21
Power Plant Steam Generators
22
Power Plant Steam Generators
Figure 3.16 . Chevron Separator with Scoops Showing the Path of the
Air or Vapor.
23
Power Plant Steam Generators
bundle of fibers arranged so that the separated liquid can drain away easily,
and the gas can continue on through the filter material see Figure 3.17.
As the velocity through these separators increases, they also fail in the
same way as the wire mesh or chevron separators; the liquid is re-entrained
before it has a chance to drain away.
Pressure drop in separators is the penalty we must pay to separate the two
phases. It is important to be able to estimate the pressure drops through the
separator and select a separator type which is suitable for the application in
question. Table 3.2 summarizes the performance of these kinds of separators
in terms of the dimensional quantity given below.
24
Power Plant Steam Generators
3.9.6 Injector
An injector is used to feed water into boiler using steam from the same
boiler as show in figure 3.18 A&B.
25
Power Plant Steam Generators
26
Power Plant Steam Generators
Given parameters
Pressure losses
The pressure losses in the heat exchanger units of the boiler are estimated
according to the following approximations:
• Economizer: the pressure loss is 5-10 % of the pressure of the
feedwater entering the economizer.
• Evaporator:
1- Once through boilers: in once-through boilers the pressure loss of the
evaporator is between 5 and 30 %.
2- Forced and natural circulation boilers: the pressure drop in the
evaporator part of drum based boilers does not affect the pressure loss
of the main steam/water flow through the boiler. This means that
saturated steam leaving the steam drum has the same pressure as the
feedwater entering the steam drum. The pressure loss of the
evaporator has to be overcome using the driving force (natural
circulation) or circulation pump (forced circulation).
• Superheater: the total pressure drop of all superheater packages is
less than 10 % of the pressure of the superheated steam.
27
Power Plant Steam Generators
3. Specific enthalpy of saturated water and steam (in the steam drum) can
be read from an h-s diagram or steam tables, as the pressure in the steam
drum is known. In once-through boilers the determination of specific
enthalpy after the evaporator is based on the temperature. The reason for
this is the unclear state of supercritical steam after the evaporator in
once-through circulation. The temperature after the evaporator in once-
through boilers is typically between 400 and 450 °C.
28
Power Plant Steam Generators
the steam drum. Normally the mass flow rate of blowdown is 1-3 % of
the mass flow rate of feedwater coming into steam drum.
29
Power Plant Steam Generators
30
Power Plant Steam Generators
and the location of the spray water nozzle. An example of a possible heat
load share between the superheater stages is shown in figure 3.19.
Normally the mass flow rate of superheated steam (live steam) is known.
Thus, mass flow rate calculations start usually by calculating the mass flow
rate of spray water to the last spray water group (which is in this example
between the second and third superheater stages). The mass flow rates can
be solved with energy and mass balance equations. With the equations
below (equation 1 ), the mass flow rate of steam after second superheater
stage and mass flow rate of spray water to the last spray water group can be
calculated. The mass flow rate of spray water to the first spray water group
can be calculated along the same procedure:
……….. (1)
31
Power Plant Steam Generators
Figure 3.20: Flow chart of the PCF boiler arrangement used in this
heat load calculation model.
32
Power Plant Steam Generators
33
Power Plant Steam Generators
34
Power Plant Steam Generators
steam to L.P.Turbine
2
@ T2 , P2 , h2 , m
5
steam from H .P.Turbine @T5 , P5 , h5 , m
3.10.1 Boiler efficiency: it is defined as the ratio between the total heat
output (to convert water to steam and to reheat the steam) to the heat input as
fuel. Each kg of fuel has a chemical energy known as "heating value" or
calorific value”.
m s (hs hw ) m 1 (h2 h1 )
b
m f .C.V
35
Power Plant Steam Generators
(m s / m f )(hs hw )
E.E
2257
Where the value 2257 represent the latent heat of evaporation at 100oC.
Example 1:
A steam generator works at 15 bar absolute pressure. The
economizer receives the water at 35o C and heats it to 104o C while
the super heater receives wet steam from steam drum at x 0.97
and heats it to 300o C . The coal used as a fuel has a heating value of
33.5MJ / kg and the steam produced per kg coal is 10kgs / kg f . The
air is drawn by the forced draft fan to the boiler at
20o C and 20kga / kg f . The flue gases are discharged to the chimney
at150o C . Assuming Cp g 1.008kJ / kg..K :
1. Determine the b ; E.E
2. Draw the heat balance sheet.
36
Power Plant Steam Generators
Solution:
300C
104C
35C X=0.97
Qeconomizer m
sf * Cp w * (T2 T1 ) 10 * 4.2 * (104 35) 2898kJ / kg f
Qevaporator m
sf * (h3 h2 ) 10 * (2731 437) 22940kJ / kg f
Qsuperheater m
sf * (h4 h3 ) 10 * (3039 2731) 3080kJ / kg f
m a m f
Qchimney m gf * Cp g * (Tg Ta ) .Cp g * (Tg Ta ) (1 m af ) * Cp g * (Tg Ta )
m f
(1 20) * 1.008 * (150 20) 2751.84kJ / kg f
37
Power Plant Steam Generators
Economizer 2898
8.4
Chimney 2752 8
38
Power Plant Steam Generators
EXAMPLE 2
The following results were obtained from a boiler trail. Feed water
temperature 36C, steam pressure = 14.8 bar, with dry saturated steam.
Duration of trail = 10 hrs. Total Quantity of steam generated = 50,000 kg.
Total coal burned = 6000 kg, C.V of coal = 30,000 kJ/kg. Total grate area
3 m2.
Calculate (i) Amount of coal burned per m2 grate area per hour, (ii) boiler
efficiency, (iii) equivalent evaporation.
SOLUTION:
39
Power Plant Steam Generators
From steam tables, corresponding to steam pressure = 14.8 bar, dry saturated
steam h hg 2789.4 kJ/kg
From steam tables , corresponding to feed water temperature 36C,
hf 150.7 kJ/kg
From steam tables, corresponding to 100C
hfg 2256.9 kJ/kg
40
Power Plant Steam Generators
2‐ Calculate the mass of flue gases flowing through the chimney when
draught produced is equal to 1.9 cm of water. Temperature of flue gases is
290C and the ambient temperature is 20C. The flue gases formed per kg
of fuel burnt are 23 kg. Neglect the losses and take the diameter of chimney
as 1.8 m.
Answers: H 34.67 m , H1 29.05 m of air, mg 39.8 kg/s
41
Power Plant Steam Generators
Problems
Q2/a steam power plant of a 25-MW electric output power has a medium
water tube steam generator of the following specifications
42
Power Plant Steam Generators
Q3/a 3-MW steam power plant have a water tubes boiler of the following
specification:
43