Instruction Manual: LX70/700 Multi-Wire Link Module
Instruction Manual: LX70/700 Multi-Wire Link Module
Instruction Manual: LX70/700 Multi-Wire Link Module
3
Safety Instructions
Please read this manual and the related documentation thoroughly and familiarize
yourself with product information, safety instructions and other directions before
installing, operating, performing inspection and preventive maintenance.
Please be aware that the instructions are marked with either a warning symbol or
attention symbol.
4
Overview
Features
The LX-MWLINK and LX70-MWLINK are a multi-functional module for PLC
networking.
LX-MWLINK LX70-MWLINK
(for LX700 PLC system) (for LX70 PLC system)
5
Hardware Description
MWLINK
MWLINK
MWLINK
COM. PLC Link 1
ERR. SPEED
W-Mode TERM
W2-Mode
2 3, 4
4
2
3 ¥ı
¥ı
5
5 4
3
2 5 2
1
1
ON
ON
1. Status LEDs
Link module states such as operation/stop, error/alarm, and
communication status are displayed.
See "Status LEDs" on page 11 for details.
2. Link No. Setting Switch
Link Unit No. in the network is configured.
See "Link Unit No. Setting Switch" on page 10.
3. Mode Setting Switch (1)
Operation mode (PLC link, non-PLC link mode selection, and end station
setting) configuration. (PLC link mode setting should be changed when
power is off. However, end stations settings become valid from the point of
change.) See "Mode Setting Switch" on page 10.
4. Function Mode Setting Switch (2)]
This dip switch should be always OFF.
See "Mode Setting Switch" on page 10.
5. Terminal for Transmission Path (RS485)
Connect a transmission cable.
See "Transmission Cable Specifications" on page 8.
6
Specifications
LISTED
General Specifications UL 62Y6
C ®
US IND. CONT. EQ.
Item Specifications
Operating 0 °C to +55 °C (32 °F to 131 °F)
Temperature
Storage -25 °C to +70 °C (-13 °F to 158 °F)
Operating 30 to 85% RH (Non-condensing)
Humidity
Storage 30 to 85% RH (Non-condensing)
1500V AC for 1 minute between I/O terminal (AC) and frame ground
(power unit)
Withstand voltage
500V AC for 1 minute between I/O terminal (DC) and frame ground
(power unit)
100 MΩ or more at 500 mega V DC between I/O terminal (DC) and
Isolation resistance
frame ground (power unit)
10 to 55 Hz, 1 cycle/minute: double amplitude of 0.75mm, 10
Vibration immunity
minutes on 3 axis (X, Y, Z)
Peak acceleration and duration 15g/11ms, 3 times in each X, Y, Z
Shock immunity
direction
1500Vp-p with 50ns to 1 µs pulse width (generated by noise
Noise immunity
simulator)
Ambience No corrosive gas, no excessive dust
Transmission Specifications
Specifications
Item Remarks
W-mode
Communication
Token bus type
specifications
Transmission method BASE-BAND type
Transmission speed 500k bps
Transmission distance Max. total length 800m See "Transmission Cable
Number of connection Specifications" on page 8 for
Max. 16 stations
stations details about transmission
CRC (Cyclic Redundancy Check) cables.
Transmission error check
method
Synchronization method Start-stop synchronization
Interface RS485 type
Transmission path Twisted-pair cable
7
Performance Specifications
Specifications
Item
W-mode
1. PLC link function
(Max. 16 stations)
2. Computer link function
(Max. 16 stations)
→ CCU unit needed
Communication functions 3. Data transmission function
(Max. 16 stations),
→ 16 words/1 instruction
4. Remote programming function
(Max. 16 stations)
5. Layer link
Function/ PLC link Max. 16 stations
Number of stations Other functions Max. 16 stations
Used Link relay WL fixed
areas Link register Ld fixed
PLC link Setting Setting with system register
Link relay Max. 1,024 points
Capacity
Link register Max. 128 words
Operation • Special relay
Used areas
status/ • Special data register
error report Setting -
Data transmission capacity Max. 16 words
Figure 1 Figure 2
Conductor Conductor
Twisted-pair VCTF cable
cable with shield
Shield
External
External Jacket
Insulator Jacket Insulator
8
Status LEDs
MWLINK MWLINK
MWLINK
MWLINK
COM. PLC Link COM. PLC Link
ERR. SPEED ERR. SPEED
W-Mode TERM W-Mode TERM
W2-Mode W2-Mode
(a) Occurs in the case of transmission error, out-of-range of Link unit No., duplicate station
number and duplicate link area allocation.
9
Mode Setting Switch
Link Unit No. Setting Switch
Up to 16 link units can be connected, and Link Unit No. is configured with this rotary
switch.
Tens Ones
UNIT No.
10
10
LX-MWLINK Mode Setting Switch
5-pole type dip switch on the bottom of LX700 PLC MW-Link module.
Settings(a)
No. Item
W-mode
Setting at All ON 1
1
end station 2
OFF ON
End station
setting
Not an end All OFF 1
2
station 2
OFF ON
(a) All settings are set to OFF (neither PLC link nor end station, W-mode and 500 Kbps speed)
as factory default.
Turn off the power when changing the mode setting switch.
ATTENTION
Settings stored on power-up are maintained even when the switch
is changed during operation. End station settings of the switch 1
and 2 can be changed during operation.
11
LX70-MWLINK Mode Setting Switches
LX70-MWLINK Mode Setting Switch (1)
4-pole type dip switch on the front of LX70 PLC MW-Link module.
Settings(a)
No. Item
W-mode
OFF PLC link mode
Operation
1 Non-PLC link mode (Computer link, data transmission,
mode ON
remote programming and layer link)
2 Unused -
Setting at All ON 3
3
end station 4
End station OFF ON
setting
Not an end All OFF 3
4
station 4
OFF ON
(a) All settings are set to OFF (neither PLC link nor end station) as factory default.
(a) All settings are set to OFF (500 Kbps speed) as factory default.
Turn off the power when changing mode settings (1), (2). Settings
ATTENTION
stored on power-up are maintained even when switch is changed
during operation. End station settings of the mode setting switch (1)
can be changed during operation.
12
12
Installation and Start-up
Installation Dimensions
LX700 PLC System Dimensions (mm)
B
TR OUT
TR OUT
TR OUT
TR OUT
TR OUT
DC IN
DC IN
DC IN
CPU750B
CPU
LX
115.5 118.5
unit (mm)
111.0 Dimensions
Slot Type
A B
3-slot type 205.0 184.0
5-slot type 276.0 254.0
8-slot type 381.0 360.0
10-slot type 452.0 430.0
12-slot type 522.0 501.0
5 .0 * 4
27.5
81.0
unit (mm)
Slot Type P L
3-slot type 205.0 153.8
5-slot type 276.0 224.2
7.0
13
LX700 CPU, Multi-Wire Link Module Dimensions (mm)
MWLINK
MWLINK
CPU750B NX-TC8 NX-TC4
TC
CPU
115.5
35.0 104.0
LX
A
105.0
30.0
38.0
C
4 - M5
14
14
unit (mm)
Catalog Dimensions Dimensions
Slot Types Dimensions (B)
Number (A) (C)
2-slot type LX70-BASE02 157.2 128.6 114.6
3-slot type LX70-BASE03 192.4 163.8 149.8
5-slot type LX70-BASE05 262.8 234.2 220.2
6-slot type LX70-BASE06 298.0 269.4 255.4
8-slot type LX70-BASE08 368.4 339.8 325.8
10-slot type LX70-BASE10 438.8 410.2 396.2
12-slot type LX70-BASE12 508.6 480.6 466.6
MWLINK
COM.
CO PL Link
PLC
ERR.
ER SPEE
SPEED
W-Mode
ode TERM
TER
W2-Mo
-Mode
de
105.0
RS232C
35.0
15
Installation Environment and Precautions
ATTENTION
Precautions for Electrostatic Discharges
Excessive static electricity can be generated in dry conditions, so
please make sure to discharge electrostatic charges by touching a
grounded metal bar before contacting the module.
ATTENTION
Contacting the Module
Do not use thinners, which can damage or degrade PCB circuit
board.
16
16
Mounting/Dismounting Module
Mounting Dismounting
1. Insert the module by inserting the 1. Unfasten the screw that holds the
tab into the groove first and pushing module in place using a
the module against the backplane. screwdriver.
2. Push the top of the module toward 3. Hold on pressing the locking button
the backplane until it is clamped in on the top edge of the module, and
place. pull the module from the backplane.
Locking button
screwdriver
17
Installation Procedure
OFF ON
LX70-MWLINK (for LX70 PLC system)
18
18
Start-up Procedure
Follow these steps when starting up a MW-Link module.
1. Check the settings of Link Unit No., operation mode and end station.
• Check for out-of-range or duplicate Link Unit No.
• Check if the units at the ends are set as end stations.
• Check if PLC link communications units are in PLC link mode, and Unit
numbers of those units are set within the range of 01 to 16.
2. Turn on the power.
3. Check the status LEDs.
• Check for self-diagnosed error, Unit No. setting error, or duplicate error.
(ERR LED)
• On PLC link communication units, check if PLC LINK LEDs are ON.
4. When there is any error, identify the cause and modify settings
• For more information on troubleshooting, refer to the LX70/LX700 Series Multi-
Wire Link Modules (LX70-MWLINK and LX-MWLINK) User Manual.
• Operation status can be checked by reading special relay and special data
register.
5. Now MW-Link unit is ready for operation.
• For PLC link communication, link area (sending area) should be configured at
the system register of CPU unit. Be careful that system register is not
configured by factory default.
• For more information on PLC Link Communication, refer to the LX70/LX700
Series Multi-Wire Link Modules (LX70-MWLINK and LX-MWLINK) User
Manual.
19
Wiring
Terminal Block Wiring
• Connect positive to positive, and negative to negative of transmission path
terminals for each link unit.
• When using F.G (frame ground) terminal, connect one end of transmission cable
shield to ground as illustrated below. (If correct triple grounding is not available,
do not connect F. G. Otherwise, error may occur.)
Shield Shield
Correct wiring MW-Link module MW-Link module MW-Link module MW-Link module
Incorrect wiring MW-Link module MW-Link module MW-Link module MW-Link module
20
20