R5-3 - 20K-T2 User Manual
R5-3 - 20K-T2 User Manual
R5-3 - 20K-T2 User Manual
-1-
R5 Series
Preface
Thank you for choosing SAJ solar inverter. We are pleased to provide you
first-class products and exceptional service.
This manual includes information for installation, operation, maintenance,
trouble shooting and safety. Please follow the instructions of this manual
so that we can ensure delivery of our professional guidance and
wholehearted service.
Customer-orientation is our forever commitment. We hope this document
proves to be of great assistance in your journey for a cleaner, greener
world.
Please check for the latest version at www.saj-electric.com
-1-
R5 Series
Content
PREFACE ........................................... - 1 -
-2-
R5 Series
-3-
R5 Series
DANGER
·DANGER indicates a hazardous situation which, if not avoided, will result in death or
serious injury.
WARNING
·WARNING indicates a hazardous situation which, if not avoided, can result in death or
serious injury or moderate injury.
CAUTION
·CAUTION indicates a hazardous condition which, if not avoided, can result in minor or
moderate injury.
NOTICE
·NOTICE indicates a situation that can result in potential damage, if not avoided.
1.3 Target Group
Only qualified electricians who have read and fully understood all safety regulations
contained in this manual can install, maintain and repair the inverter. Operators must
be aware of the high-voltage device.
-4-
R5 Series
Chapter 2 Preparation
DANGER
·There is possibility of dying due to electrical shock and high voltage.
·Do not touch the operating component of the inverter, it might result in burning or death.
·To prevent risk of electric shock during installation and maintenance, please make sure that
all AC and DC terminals are plugged out.
·Do not touch the surface of the inverter while the housing is wet, otherwise, it might cause
electrical shock.
·Do not stay close to the inverter while there are severe weather conditions including storm,
lighting, etc.
·Before opening the housing, the SAJ inverter must be disconnected from the grid and PV
generator; you must wait for at least five minutes to let the energy storage capacitors
completely discharged after disconnecting from power source.
WARNING
·The installation, service, recycling and disposal of the inverters must be performed by
qualified personnel only in compliance with national and local standards and regulations.
·Any unauthorized actions including modification of product functionality of any form may
cause lethal hazard to the operator, third parties, the units or their property. SAJ is not
responsible for the loss and these warranty claims.
·The SAJ inverter must only be operated with PV generator. Do not connect any other
source of energy to the SAJ inverter.
·Be sure that the PV generator and inverter are well grounded in order to protect properties
and persons.
CAUTION
·The solar inverter will become hot during operation. Please do not touch the heat sink or
peripheral surface during or shortly after operation.
·Risk of damage due to improper modifications.
-5-
R5 Series
NOTICE
·Public utility only.
·The solar inverter is designed to feed AC power directly to the public utility power grid; do
not connect AC output of the inverter to any private AC equipment.
-6-
R5 Series
Notice, danger!
This is directly connected with electricity generators and public grid.
Without Transformer
This inverter does not use transformer for the isolation function.
CE Mark
Equipment with the CE mark fulfills the basic requirements of the Guideline
Governing Low-Voltage and Electro-magnetic Compatibility.
CQC Mark
The inverter complies with the safety instructions from China's Quality Center.
-7-
R5 Series
B Inverters R5-3K/4K/5K/6K/8K/9K/10K/12K/13K/15K/17K/20K-T2
Metering Standard metering tool for measuring the output electric power
C
equipment of inverters
-8-
R5 Series
-9-
R5 Series
- 10 -
R5 Series
3.4 Datasheet
R5-3K/4K/5K/6K-T2
- 11 -
R5 Series
- 12 -
R5 Series
- 13 -
R5 Series
R5-8K/9K/10K/12K-T2
- 14 -
R5 Series
- 15 -
R5 Series
R5-13K/15K/17K/20K-T2
Type R5-13K-T2 R5-15K-T2 R5-17K-T2 R5-20K-T2
Input (DC)
Max. PV Array Power [Wp]@STC 19500 22500 25500 30000
Max. DC Voltage [V] 1100
MPPT Voltage Range [V] 160-950 180-950
Nominal DC Voltage [V] 600
Start Voltage [V] 180 200
Min. DC Voltage [V] 160 180
Max. DC Input Current [A] 25/12.5 25/25
Max. DC Short Current [A] 30/15 30/15
Number of DC Connection Sets per MPPT 2/1 2/2
Number of MPPT 2
DC Switch Integrated
Output (AC)
Rated AC Power [W] 13000 15000 17000 20000
Max. AC Power [VA]*1 14300 16500 18700 22000
Rated AC Current [A]@230Vac 18.9 21.8 24.7 29.0
Max. AC Current [A] 21.7 25.0 28.4 33.4
Current Inrush [A] 77 90
Max. AC Fault Current [A] 52 63
Max. AC Over Current Protection [A] 57.7 71.1
Nominal AC Voltage/ Range [V] 220/380,230/400,240/415;180-280/312-485
Grid Frequency/ Range [Hz] 50,60/45-55,55-65
Power Factor [cos φ] 0.8 leading~0.8 lagging
Total Harmonic Distortion [THDi] < 2%
Feed-in 3L+N+PE
Efficiency
Max. Efficiency 98.7% 98.8%
Euro Efficiency 98.4% 98.46%
MPPT Accuracy >99.5%
Protection
Internal Over-voltage Protection Integrated
DC Insulation Monitoring Integrated
DCI Monitoring Integrated
GFCI Monitoring Integrated
- 16 -
R5 Series
Grid Monitoring Integrated
AC Short Circuit Current Protection Integrated
AC Grounding Detection Integrated
DC Surge Protection Integrated
AC Surge Protection Integrated
Thermal Protection Integrated
String Current Detection Integrated
Anti-island Protection Monitoring AFD
Interface
AC Connection Terminal Block
DC Connection MC4
Human Machine Interface LED+(Bluetooth/Wi-Fi+APP)
Communication Port RS232(USB)+RS485(RJ45)
Communication Mode Wi-Fi/GPRS/4G(Optional)
General Data
Topology Transformerless
Consumption at Night [W] <0.6
Consumption at Standby [W] <10
Operating Temperature Range -40℃~+60℃[45°C to 60°C with derating]
Cooling Method Natural Convection
Ambient Humidity 0%~100% Non-condensing
Altitude 4000m(>3000m power derating)
Noise [dBA] <29
Ingress Protection IP65
Mounting Rear Panel
Dimensions [H*W*D][mm] 480*440*200 530*490*210
Weight [kg] 26 29
Standard Warranty [Year] 5 (standard)/10/15/20/25 (Optional)
CQC NB/T 32004,EN 62109-1/2,EN 61000-6-1/2/3/4
Applicable Standard EN50438,EN50549,C10/C11,IEC 62116,IEC 61727,RD
1699,UNE 206006,UNE 206007-1,CEI0-16,G99
Note: *1. The maximum AC output power of Belgium is rated AC output power.
2. The above parameters might be slightly modified accoridng to different grid codes.
3. If you need more information about our product certifications, please contact our sales.
- 17 -
R5 Series
DANGER
·Dangerous to life due to potential fire or electricity shock.
·Do not install the inverter near any inflammable or explosive items.
·This inverter will be directly connected with HIGH VOLTAGE power generation device;
the installation must be performed by qualified personnel only in compliance with national
and local standards and regulations.
NOTICE
·This equipment meets the pollution degree II.
·Inappropriate or the harmonized installation environment may jeopardize the life span of
the inverter.
·Installation directly exposed under intensive sunlight is not recommended.
·The installation site must be well ventilated.
Although SAJ’s inverters have surpassed stringent testing and are checked before
they leave the factory, it is uncertain that the inverters may suffer damages during
transportation. Please check the package for any obvious signs of damage, and if
such evidence is present, do not open the package and contact your dealer as soon as
possible
- 18 -
R5 Series
④ When mounting the inverter, please consider the solidity of wall for inverter,
including accessories. Please ensure the Rear Panel tightly.
Before installation, make sure that the wall has enough strength to hold the screws
and bear the weight of the equipment. Please make sure the equipment is installed
properly.
- 19 -
R5 Series
To make sure the installation spot is suitably ventilated, if multiple SAJ on-grid
solar inverters are installed same area, the following safety clearance in Figure 4.2
shall be followed for proper ventilation conditions.
30CM
30CM 50CM 50CM
30CM
The mounting position should be marked as shown in Figure 4.3, Figure 4.4 &
Figure 4.5.
- 20 -
R5 Series
403
17.6 14 14
15 16
23
85
65.2
8
42.5
3-16*8
32.5
130
280
375
Figure 4.4 Dimensions of rear panel of R5-13K/15K-T2
453
425
320
14 130 14
17.6
42.5
85
3-16*8
- 21 -
R5 Series
比例
- 22 -
R5 Series
比例
Carefully mount the inverter to the rear panel as shown in Figure 4.10 and 4.11,
Make sure that the rear part of the equipment is closely mounted to the rear
panel.
- 23 -
R5 Series
Fig. 4.11 Fasten the inverter and hanging panel with screws
- 24 -
R5 Series
- 25 -
R5 Series
DANGER
·Dangerous to life due to potential fire or electricity shock.
· When power-on, the equipment should be in conformity with national rules and
regulations.
·The direct connection between the inverter and high voltage power systems must be
operated by qualified technicians in accordance with local and national power grid standards
and regulations.
WARNING
·When the PV array is exposed to light, it supplies a DC voltage to the inverter.
NOTICE
·Electrical connection should in conformity with proper stipulations, such as stipulations
for cross-sectional area of conductors, fuse and ground protection.
·The overvoltage category on DC input port is II, on AC output port is III.
- 26 -
R5 Series
Code Name
A DC Switch
B Decompression Valves
C DC Input
D RS232 Communication (GPRS/ Wi-Fi /4G)
E Ground Connection
F RS485 Communication
G AC Output
- 27 -
R5 Series
Code Name
A DC Switch
B Decompression Valves
C DC Input
D RS232 Communication(GPRS/ Wi-Fi /4G)
E RS485 Communication
F Ground Connection
G AC Output
- 28 -
R5 Series
5.3 AC Connection
Cross-sectional area of cables(mm²)
External diameter(mm)
Scope Recommended value
6.0-10.0 6.0 5.3~6.7
Table 5.3 Recommended power grid connecting cable specification
If the grid-connection distance is too far, please select AC cable with larger
diameter as per the actual condition.
- 29 -
R5 Series
5. Connect the AC connector to the equipment securely, ensuring the pins are
connected directly. Then the connection of AC cable is completed.
- 30 -
R5 Series
2. Screw off the screws at the AC output wire cover and take out the cover.
Penetrate the AC cable of which the insulation layers has been peeled off through
the AC waterproof locking screw hole of the cover. Lock L1 wire, L2 wire, L3
wire, N wire and PE wire tightly as per the marked connection positions on the
interface board.
- 31 -
R5 Series
3. After fixing the cover at the AC output wire terminal with screws, tighten up the
AC waterproof nut.
- 32 -
R5 Series
2.
NOTICE
· Please place the connector separately after unpacking in order to avoid confusion for
connection of cables.
·Please connect the positive connector to the positive side of the solar panels, and connect
the cathode connector to the cathode side of the solar side. Be sure to connect them in right
position.
Connecting Procedures:
2. Use specified strip tool to strip the insulated enclosure of the positive and cathode
cables with appropriate length.
- 33 -
R5 Series
3. Feed the positive and cathode cables into corresponding lock screws.
4. Put the metal positive and cathode terminals into positive cable and cathode cable
whose insulated enclosure has been stripped, and crimp them tightly with a wire
crimper. Make sure that the withdrawal force of the pressed cable is bigger than
400N.
5. Plug the pressed positive and cathode cables into relevant insulated enclosure,
a“click” should be heard or felt when the contact cable assembly is seated correctly.
6. Fasten the lock screws on positive and negative connectors into respective
insulated enclosure and make them tight.
7. Connect the positive and cathode connectors into positive and negative DC input
terminals of the inverter, a “click” should be heard or felt when the contact cable
assembly is seated correctly.
1. Connection port
NOTICE
·Before inserting the connector into DC input terminal of the inverter, please make sure that
the DC switch of the inverter is OFF.
·Please use the original H4 terminal to install.
- 34 -
R5 Series
1 NC
4 NC
5 NC
6 NC
- 35 -
R5 Series
1. USB interface could be externally connected with eSolar GPRS/4G module, for
operation in details please refer to eSolar GPRS/4G module quick installation guide.
2. USB interface could be externally connected with eSolar WiFi module, for
operation in details please refer to eSolar WiFi module quick installation guide.
- 36 -
R5 Series
- 37 -
R5 Series
● This equipment is standardly equipped with a USB interface which could transfer
GPRS/4G module (with built-in Bluetooth) and Wi-Fi module to monitor running
state of the equipment.
After installing the eSolar GPRS/4G module (with built-in Bluetooh) the mobile
phone could be directly connected with the inverter via Bluetooth.
- 38 -
R5 Series
Connection setting
iOS system operation steps
1. Choose “setting” →choose “Bluetooth””→ open 2. Log in APP → choose “My” interface → choose
“Bluetooth” “Remote control” → choose connection way as
“Bluetooth ”
Connection
Note
(1)Bluetooth is a kind local connection,
currently it supports the following type of
inverters:R series,C series,
A series, H series.
(2)Please start the inverter and turn on
mobile Bluetooth.
Next step
3.Choose “next step” → search for equipment → 4. Connect successfully → set country and grid
click the Bluetooth name matched with the inverter code for first start-up → after inverter start, users
(ex.: R5-4K-T2:00001) can view inverter’s information.
Communication board
firmware version XXXXXXXX
- 39 -
R5 Series
Connection setting
Android system operation steps
1. Choose “setting” → choose “Bluetooth”→ open 2. Log in APP → choose “My” interface → choose
“Bluetooth” “Remote control” → choose connection way as
“Bluetooth ”
Connection
Note
(1)Bluetooth is a kind local connection,
currently it supports the following type of
inverters:R series,C series,
A series, H series.
(2)Please start the inverter and turn on
mobile Bluetooth.
Next step
3.Choose “next step” → search for equipment → 4. Connect successfully → set country and grid
click the Bluetooth name matched with the inverter code for first start-up → after inverter start, users
(ex.: R5-4K-T2:00001) can view inverter’s information.
Communication board
firmware version XXXXXXXX
- 40 -
R5 Series
Equipment information
Device info
Bluetooth:R5-4K-T2:00001
R5T2043G1815E00001
Basic info Running info Power info Event info
Communication board
firmware version XXXXXXXX
- 41 -
R5 Series
Device info
Bluetooth:R5-4K-T2:00001
R5T2043G1815E00001
Basic info Running info Power info Event info
PV information
PV1 XXV XXA
PV2 XXV XXA
PV3 N/V N/A
Grid power information
AC1 XXV XXA XXHz
AC2 XXV XXA XXHz
AC3 XXV XXA XXHz
Battery information
CT1 N/V N/A N/W
CT2 N/V N/A N/W
CT3 N/V N/A N/W
Current power, today energy, monthly energy, yearly energy, total energy could be
checked.
Device info
Bluetooth:R5-4K-T2:00001
R5T2043G1815E00001
Basic info Running info Power info Event info
Read More
- 42 -
R5 Series
Time of the events, events sequence number (referring to fault codes details in
Chapter 7 Fault Codes and Common Troubleshooting) and events content of the
faults of the inverter could be checked.
Device info
Bluetooth:R5-4K-T2:00001
R5T2043G1815E00001
Basic info Running info Power info Event info
Datetime:2018-11-09 18:16:00
1 No:Err73
Content:XXXX
Datetime:2018-11-10 18:16:00
2 No:Err73
Content:XXXX
After installing the eSolar WiFi module, the mobile phone could be directly
connected with the inverter via Wi-Fi.
- 43 -
R5 Series
Connection setting
Please refer to the eSolar WiFi module operating manual for more details in
operation.
Equipment information
Current power, today energy, monthly energy, yearly energy, total energy could be
checked.
Time of the events, events sequence number (referring to fault codes details in
Chapter 7 Fault Codes and Common Troubleshooting) and events content of the
faults of the inverter could be checked.
- 44 -
R5 Series
2. Connect the internet via the eSolar WiFi module, and upload the inverter data
onto the server and customers could monitor running information of the inverter
remotely via the eSolar Web Portal or their mobile customer terminals.
- 45 -
R5 Series
- 46 -
R5 Series
Board Master
50 Interior communication Error Slave
51/52/53 L1/L2/L3 Voltage Consistency Error Slave
54/55/56 L1/L2/L3 Frequency Consistency Error Slave
57 GFCI Consistency Error Slave
58/59/60 L1/L2/L3 DCI Consistency Error Slave
61/63/65 L1/L2/L3 Overvoltage Slave
62/64/66 L1/L2/L3 Under Voltage Slave
67/69/71 L1/L2/L3 Over Frequency Slave
68/70/72 L1/L2/L3 Under Frequency Slave
73/74/75 L1/L2/L3 Grid Lost Error Slave
76/77/80 PV1 /PV2/PV3 Overvoltage Slave
78/79/82 PV1/PV2/PV3 Overcurrent Slave
81 Loss of Communication between Display Panel and Control
Board Master
83 Grounding Detection Error Master
84 PV Input Error Master
86 DRM0 Error Master
- 47 -
R5 Series
- 48 -
R5 Series
This device should not be disposed as residential waste. An inverter that has reached
the end of its life and is not required to be returned to your dealer must be disposed
carefully by an approved collection and recycling facility in your area.
- 49 -
R5 Series
SAJ Innovation Park, No.9, Lizhishan Road, Guangzhou Science City, Guangdong,
P.R.China.
E-mail: service@saj-electric.com
International Sales
E-mail:info@saj-electric.com
Domestic Sales
- 50 -
R5 Series
Starting from the date of shipment from SAJ factory or 60 months (5 years) starting
from the date of purchased invoice marked (whichever is longer).
The purchaser of SAJ inverters should extend the warranty period in 18 months from
the date of settlement or 30 months from the date of shipment from SAJ by
providing the serial number of the unit and purchased receipt (whichever is shorter).
You can purchase the warranty extension for 10 years, 15 years, 20 years or 25 years
but do not apply the extension beyond the specified date, or else your application
will be unacceptable. Please refer to the Warranty Extension Order Form for more
details.
Once the purchase of the warranty extension goes into effect, SAJ will send the
warranty extension certificate to the customer for confirming the extended warranty
period.
If your inverter gets fault and requires troubleshooting, please contact your
distributor or dealer directly. Alternatively, feedback briefly to SAJ service hotline
for logging and send your warranty card to our service department by fax/email to
process the warranty claim.
During the Warranty Period, SAJ covers all costs for replacing any product or parts
of the product proved to be defective in design or manufacture. To claim the
warranty under the warranty policy of SAJ, you need to supply us with the following
information and documentation regarding the faulty inverter:
1. Product Model No.(e.g. R5-4K-T2) and serial number
(e.g.R5T2043G1815E00001).
- 51 -
R5 Series
4. Error message on eSolar Portal (if available ) or any information which would be
helpful to determine the defect.
1.4 After receiving above information, SAJ will decide how to proceed the
service
In the case of an exchange, the remaining portion of the original warranty period will
be transferred to the replacement device. You will not receive a new certificate, as
your entitlement is documented at SAJ.
If the inverters for maintenance are out of warranty, SAJ charges an on-site service
fee, parts, labor cost and logistic fee to end-user. Detailed standard refers to the
listed table.
■ On-site attendance fee: Cost of travel and time for the technician in attending
on-site.
■ Parts: Cost of replacement parts (including any shipping/admin fee that may
apply).
- 52 -
R5 Series
■ Labor: Labor time fee charged for the technician, who is repairing, maintaining,
installing (hardware or software) and debugging the faulty product.
■ Logistic fee: Cost of delivery, tariff and other derived expense when defective
products are sent from user to SAJ or/and repaired products are sent from SAJ to
user.
Any defect caused by the following circumstances will not be covered by the
manufacturer’s warranty (the Dealers or Distributors are responsible and authorized
by SAJ for the following investigation):
◆ Changes, or attempted repairs and erasing of series number or seals by non SAJ
technician;
◆ The inverter has been improperly stored and damaged while being stored by the
Dealer or the end user;
◆ Failure to follow any / all of the user manual, the installation guide and the
maintenance regulations;
- 53 -
R5 Series
Warranty Card
The installer should fill in the second form while installing the inverter. For
warranty claim, please complete the below forms and send this page to SAJ attached
with the Customer’s invoice.
Name:
Information on device
Device type: Serial No.(S/N):
Fault time:
Signature: Date:
- 54 -
R5 Series
Company:
Signature: Date:
- 55 -