1 RCS-985B Generator Protection Instruction Manual PDF
1 RCS-985B Generator Protection Instruction Manual PDF
1 RCS-985B Generator Protection Instruction Manual PDF
Generator Protection
Instruction Manual
Preface
Before using this product, please read this chapter carefully.
This chapter describes the safety precautions recommended when using the equipment. Before
installing and using the equipment, this chapter must be thoroughly read and understood.
CAUTION means the light personal injury or equipment damage may occur if
safety precautions are disregarded. This particularly applies to damage to the device and to
resulting damage of the protected equipment.
WARNING!
The firmware may be upgraded to add new features or enhance/modify existing features, please
make sure that the version of this manual is compatible with the product in your hand.
During operation of electrical equipment, certain parts of these devices are under high voltage.
Severe personal injury or significant equipment damage could result from improper behavior.
Only qualified personnel should work on this equipment or in the vicinity of this equipment. These
personnel must be familiar with all warnings and service procedures described in this manual, as
well as safety regulations.
In particular, the general facility and safety regulations for work with high-voltage equipment must
be observed. Noncompliance may result in death, injury, or significant equipment damage.
DANGER!
Never allow the current transformer (CT) secondary circuit connected to this equipment to be
opened while the primary system is live. Opening the CT circuit will produce a dangerously high
voltage.
WARNING!
Exposed terminals
Do not touch the exposed terminals of this equipment while the power is on, as the high voltage
generated is dangerous.
Residual voltage
Hazardous voltage can be present in the DC circuit just after switching off the DC power supply. It
takes a few seconds for the voltage to discharge.
CAUTION!
Earth
Operating environment
The equipment must only be used within the range of ambient environment detailed in the
specification and in an environment free of abnormal vibration.
Ratings
Before applying AC voltage and current or the DC power supply to the equipment, check that they
conform to the equipment ratings.
Do not attach and remove printed circuit boards when DC power to the equipment is on, as this
may cause the equipment to malfunction.
External circuit
When connecting the output contacts of the equipment to an external circuit, carefully check the
supply voltage used in order to prevent the connected circuit from overheating.
Connection cable
Copyright
Table of Contents
Chapter1 Introduction .................................................................................................................... 1
2.7.8 Longitudinal zero sequence voltage protection for inter-turn fault ......................... 20
3.1 Advantage of duplicated main and backup protection for high rated transformer ... 29
4.3.3 Enabling binary inputs of excitation and stepdown transformer protection.......... 142
4.4.7 Viewing event records via RCSPC support software ........................................... 153
11.6.2 Connection way of protection equipment and personal computer ..................... 411
Chapter1 Introduction
1.1 Application
The RCS-985 series is microprocessor based protection equipment used for generator-transformer
unit of turbo-hydraulic and gas-turbine generator type. It meets the requirements of power plant
automation.
For a large-scale generator-transformer unit, two sets of RCS-985Bs can be used and then main
protection, abnormal operation condition protection and backup protection can be duplicated.
Breaker failure initiation and mechanical protection equipment (RCS-974 series) is installed on a
separate panel. Different CT groups are used by these two RCS-985Bs and main and backup
protection elements in one RCS-985B share one CT group. Outputs of the protection correspond
to various trip coils. Therefore, the following advantages can be achieved:
• Convenient, reliable and secure for operation of equipment and requirements of accident
prevention;
Note:
Connection shown in the figure is that of panel A. However, connection of panel B including
polarity mark of CT is the same as panel A. Although exciter or excitation transformer is drawn in
these figures, either of them is applicable for any scheme.
CZX-12R
RCS-985B RCS-985B
RCS-974A
Transformer
transformer A
transformer B
Station
Station
Generator
220kV
Bus VT
CZX-12R
RCS-985B RCS-985B
RCS-974A
Transformer
transformer A
transformer B
Station
Station
Generator
Exciter
For generator-transformer unit with capacity of 300 MW or above, panel A and B are both equipped
with generator-transformer unit differential protection, main transformer differential protection,
generator differential protection and stepdown transformer differential protection.
For generator-transformer unit with capacity of 100MW – 300MW, panel A is equipped with main
transformer differential protection, generator differential protection and stepdown transformer
differential protection while panel B is equipped with generator-transformer unit differential
protection, generator differential protection and stepdown transformer differential protection.
The scope of differential protection may cover generally LV side of stepdown transformer or its HV
side if necessary.
For differential protection of generator, there are also two kinds of percentage differential protection:
common percentage differential protection and DPFC percentage differential protection.
Panel A and B are equipped with complete set of backup protection of generator-transformer unit.
Different CTs are used for them.
For zero sequence current protection, if there is only one group of zero sequence current CT, it can
be connected to panel A. While panel B can adopt calculated zero sequence current from
bushing CT. Protective ranges of these two kinds of zero sequence current protection are different
to each other. Their setting shall be calculated separately.
As to earth fault protection of rotor, two sets of such protection cannot work simultaneously
otherwise influence between them will appear. Only one set of earth fault protection of rotor can be
enabled during operation. If other set will be put into operation sometimes, this set shall be
quitted firstly.
Main protection and backup protection adopt one common group of CT.
Current sampled at the terminal of generator is included in generator protection and main
transformer differential protection. These two kinds of differential protection can use one common
group of CT without any influence. In fact two groups of CT input channel are provided in
RCS-985B. One of them is reserved for special case.
On 220 kV side, there shall be one group of CT to be adopted dedicatedly for circuit breaker failure
protection and pole disagreement protection.
Panel A and B shall adopt different potential transformer VT or its different windings if possible.
For turn-to-turn fault protection of generator, in order to prevent unwanted operation due to VT
circuit failure on HV side used dedicatedly for this protection, one set of protection shall adopt two
groups of VT. However, if we consider to adopt only independent VT windings, too much VT will
be installed at generator end and it is not reasonable. So it is recommended to equip three
windings of VT there, namely VT1, VT2 and VT3. Panel A adopts voltage from VT1 and VT3 while
panel B VT2 and VT3. During normal operation, panel A adopts VT1 and panel B adopts VT2 while
VT3 is backup to both of them. If circuit of VT1 or VT2 fails, VT3 will be switched on automatically
by software.
For zero sequence voltage, there are two windings adopted by two sets of protection equipments
simultaneously in general.
Circuit breaker failure initiation is very important to power plant. In general, generator-transformer
unit protection tripping contact is an essential to circuit breaker failure initiation. Considering
importance of such protection, it is recommended to realize it as follows:
In order to make it more reliable, circuit breaker failure initiation should be independent equipment
with electric quantity protection equipment.
1.4 Features
1.4.1 High-performance hardware
1.4.1.1 DSP platform
RCS-985B adopts high-performance digital signal processor DSP chip as its core calculating unit.
It is indeed digital protection equipment.
RCS-985B comprises two independent CPU systems where lowpass filter, A/D converter, fault
calculation and logic output are all independent. CPU1 is used for tripping matrix while CPU2 for
fault detector. The equipment will be blocked and issue alarm if any one of CPU fails. So unwanted
operation due to hardware failure can be avoided.
An independent general fault detector is equipped in management module (MON module). Power
source of output relay can be connected only when the fault detector operates. Besides, various
other fault detectors are provided for various protection functions. Tripping outputs of protective
elements on CPU module can be validated only when corresponding fault detector on MON
module picks up. Any component failures during normal condition will not cause unwanted
operation.
The equipment adopts high-speed sampling and parallel calculation. Sampling rate is 24 points
per cycle. Calculation of all protection elements can be performed during one sampling period.
High security, reliability and speed can be reached then.
Variable slope percentage characteristic is adopted for differential protection (refer to Figure 3.4-1).
Slopes Kb11 and Kb12 can be so set that high sensitivity can be got during internal fault and
transient unbalance current can be avoided during external fault. In order to prevent unwanted
operation of differential protection due to CT saturation, measures to discriminate CT saturation
are provided for phase current on each side.
DPEC percentage differential protection reflects only deviation components of differential current
and unrestraint current and is not effected by load current. It can detect small fault within
transformer and generator. Besides, it is insensitive to CT saturation since its restraint coefficient
is set comparatively high.
Inrush current blocking is used for the equipment. Second harmonic and waveform of current can
be used for discrimination of inrush current by option.
According to relation between DPFC of restraint current and differential current of differential
protection, external or internal fault can be discriminated correctly. For external fault, criterion of
waveform of current is adopted. Unwanted operation will not occur if the correct transfer time
from primary to secondary side of CT is not less than 5 ms. As to internal fault, the equipment
will operate quickly.
Transverse differential protection adopts percentage phase current restraint and floating threshold.
The equipment can operate for internal fault with high sensitivity and not operate for external fault
with high security.
DPFC current is used as restraint quantity for external three phase fault.
DPFC and negative sequence current are used as restraint quantity for external unbalance fault.
Longitudinal zero sequence voltage is used as restraint quantity for small turn-to-turn fault of stator.
This protection function adopts third harmonic voltage as the criterion. It can adopt proportion
relation of third harmonic voltages between generator output and neutral point around parallel
operation of the generator with the system. This criterion ensures that no unwanted alarm can be
sent during startup/shutdown process of the generator.
This protection function adopts ping-pong principle. Its DC input uses high performance isolated
amplifier. Real-time display of voltage and insulation resistance of the rotor as well as location of
its ground point can be realized.
This protection function adopts open criterion. Several criterion such as stator impedance, reactive
power, rotor voltage, busbar voltage and reduced active power of stator can be combined flexibly.
Requirements of operation of different type generator-transformer unit can be met then.
Triple impedance elements are adopted by this protection function and system swing and
out-of-step can be discriminated correctly. It can also locate the swing center and can make
real-time record of pole slipping number of internal swing and external swing respectively.
Two groups of VT inputs are equipped for generator end. If one group fails the equipment will
issue alarm and switch to the healthy group automatically. It is not needed to block protective
function relevant to voltage of generator.
This function adopts percentage differential principle. Detection ability of CT circuit failure can
enhanced significantly and unwanted operation can be avoided then.
1.4.3 Intellectuality
1.4.3.1 Friendly HMI interface
The HMI interface with a LCD and a 9-button keypad on the front panel is very friendly to the user.
Real time, connection diagram, phase current, differential current and voltage can be displayed on
1.4.3.2 Transparency
More than 500 sampled data including differential current and phase angle etc. can be displayed
on LCD and more than 1500 internal data of the equipment can be supervised through dedicated
auxiliary software RCSPC that provides user with great convenience to know about the operation
situation of RCS-985.
CPU module: latest 32 groups of fault data and event sequence, 8 groups of fault oscillograms, 32
status changes of binary inputs and 32 self-supervision reports can be recorded.
MON module: when the equipment picks up, oscillograms of all analog sampling quantity,
differential current and operation of the protection equipment can be recorded with duration up to 4
seconds or 8 seconds (depend on sample rate configured).
The format of event or fault report is compatible with international COMTRADE format.
Two rear RS-485 ports with IEC 60870-5-103 protocol or MODBUS protocol which can be
re-configured as optical fiber ports.
Various GPS clock synchronizations: second/minute pulse via binary input or RS-485, message
via communication ports and IRIG-B synchronization.
Operating <70W
condition
2.6 Certifications
ISO9001: 2000
ISO14001:2004
OHSAS18001: 1999
ISO10012:2003
CMMI L3
Current: 0.05In~20In
Voltage: 0.4V~100V
frequency: (90%~~110%)fn
df/dt: 0.3Hz/s~10Hz/s
Scope: 2 Ie – 14 Ie
Note:
Id—differential current
[I_Pkp_PcntREF_HVS]
[I_InstREF_HVS]
Scope: (2 – 50)In
≤30 ms (Iod≥2×[I_Pkp_PcntREF_HVS])
≤25 ms (Iod≥[I_InstREF_HVS])
Note:
Scope: 2 Ie – 10 Ie
≤25ms (Id≥2×[I_Pkp_Pcnt(SPT)Diff_Gen])
≤20 ms (Id≥1.5×[I_Inst(SPT)Diff_Gen])
Note:
Id—differential current.
Scope: 2 Ie – 14 Ie
≤35 ms (Id≥2×[I_Pkp_Diff_Exc(ST)] )
≤25 ms (Id≥1.5×[I_InstDiff_Exc(ST)])
Note:
Id—differential current.
Scope: 1 V –20 V
Scope: 2 V – 20 V
Scope: 0.1 s – 10 s
Scope: ≤40 ms
Scope: 1 V – 20 V
Scope: 1 V – 30 V
Scope: 0.5 – 10
Scope: 0.1 s – 10 s
Scope: 1% – 10%
±2.5% or ±0.01 In
0.1 A – 100 A
0.05 A – 10 A
0.05 A – 10 A
Note:
0.5% - 10% Pn
0.1s – 10s
0.1 s – 100 s
0.01 s – 10.00 s
Frequency range 15 Hz – 65 Hz
Measurements
Voltage: 0.05…2Vn
Performance
• Main protection, backup protection and fail condition protection share the data sampled from
the same CT.
• A transformer is protected by dual relays, each of which includes a complete set of transformer
protection.
With the fast development of electronic technology, especially the extensive application of DSP
(Digital Signal Processor), CPLD (Complex Programmable Logic Device) and FPGA (Field
Programmable Gate Array), it is possible to integrate main and backup protection of a main
transformer into one set of protection equipment.
Because main protection of transformer don’t need communication channel as used in line pilot
protection, the backup protection can be configured simply based on enhanced main protection
by adopting above duplicate protection principle. Simple and safe overcurrent protection is a good
choice for transformer’s backup protection.
For important 220kV or above voltage level substation and large-scale generator-transformer
group, duplicate independent groups of DC storage batteried for protection are provided. For
some substations and generator-transformer not quite important, although only one group of DC
storage batteries is provided considering economic factor, duplicate DC source for protection
equipments can be obtained by dividing the DC source into different DC bus bar by DC breaker.
In the same way, duplicate protection for transformer can share the same output circuit and get
voltage from different AC voltage bus bar whose voltages origin are same VT distributed by AC
breaker. Of course, it is better that independent sets of CTs are provided for the duplicated
protection, one for each. Duplicate protection configuration principle for transformer doesn’t
enlarge the investment of secondary circuit. In fact, on the contrary, the investment in protection
equipment is reduced. At least one protection will clear transformer’s inner fault, which eliminates
the possibility of delay clearance that exists before if only backup protection left when differential
protection fails to operate due to any causes.
Every protective element has its own fault detector element in CPU and DSP respectively. When
NANJING NARI-RELAYS ELECTRIC CO., LTD 29
Chapter3 Description of Operation Theory
the fault detector in CPU picks up, power supply of output relays will be connected. When both
two detector elements and operational element pick up, the protection element will operate to trip.
The additional output blocking circuit controlled by general fault detectors calculated in MON
module makes the output circuit more secure, because not only the relationship between tripping
command sending and additional output blocking circuit is logic “and” in software, but also they
keeps the logic “AND” relationship in hardware. It is displayed in below figure.
+ 24 V FD
controlled by fault
+ 24 V
detectors in MON
module
trip
relay R
tripping G1
commands tripping
=1
from CPU transistor
module
The general fault detectors calculated in MON module and operation elements calculated in CPU
module use their independent data sampled by themselves, so the equipment will not operate by
mistake due to any of module’s data channel’s failure.
Where:
I dφ max is the maximum value of three phase differential currents of generator-transformer unit.
unit.
Where:
I dφ max is the maximum value of three phase differential currents of main transformer.
Where:
∆I dt is the floating threshold value which will arise automatically and gradually according to
increasing of the output of deviation component. In order to ensure that the threshold value of
current is slightly higher than the unbalance output, multiple 1.25 of the deviation component is
reasonable.
• •
∆ I 1 …. ∆ I m are the DPFC current of each side of transformer respectively.
NANJING NARI-RELAYS ELECTRIC CO., LTD 31
Chapter3 Description of Operation Theory
This fault detector is not influenced by the direction of power flow and so it is very sensitive. The
setting is fixed and need not to be set.
Where:
This fault detector will operate if maximum value of three phases current is greater than its setting
value.
∆I > 1.25∆I t + I th
(Equation 3.3-5)
Where:
∆I t is the floating threshold which will arise automatically and gradually according to increasing
of the output of deviation component. In order to ensure that the threshold current is slightly
higher than the imbalance value, multiple 1.25 of the deviation component is reasonable.
∆I is the half-wave integral of phase-to-phase current. I th is the fixed threshold of 0.2In and
This fault detector is used to release the distance protection at relevant side.
3I 0 > [ I _ ROC1(2) _ Tr ]
(Equation 3.3-6)
Where:
This fault detector will operate if the zero sequence current is greater than its setting value.
It is used to release zero sequence overcurrent protection with stage 1, 2 at relevant side.
Where:
I dφ max is the maximum value of three phase differential currents of stepdown transformer.
Where:
Iφ max is the maximum value of three phase currents at HV side of stepdown transformer.
This fault detector will operate if maximum value of three phases current is greater than its setting
value.
Where:
Iφ max is the maximum value of three phase currents at LV side of stepdown transformer.
This fault detector will operate if maximum value of three phase currents of branch of auxiliary
Where:
This fault detector will operate if the zero sequence current is greater than its setting value.
Where:
Where:
• •
∆ I 1 …. ∆ I m are the DPFC current of each side of generator respectively.
This fault detector is not influenced by the direction of power flow and so it is very sensitive. The
setting is fixed and need not to be set on site.
The fault detector will operate when the transverse differential current is greater than the setting
[I_SensTrvDiff_Gen].
The fault detector will operate when the longitudinal zero sequence voltage is greater than the
setting [V_SensROV_Longl_Gen].
The fault detector will operate when the calculated directional element is met operating condition.
The fault detector will operate when the calculated zero sequence voltage is in excess of the
setting [V_SensROV_Sta].
The fault detector will operate when the ratio of 3rd harmonics voltage between neutral point
voltage and generator terminal voltage is greater than its ratio setting
[k_V3rdHRatio_PreSync_Sta] or [k_V3rdHRatio_PostSync_Sta].
The fault detector will operate when the differential 3rd harmonic voltage of neutral point and 3rd
harmonics voltage at the terminal of generator is greater than its setting [k_V3rdHDiff_Sta].
3.3.8.4 Fault detector of stator earth fault protection with injection principle
The fault detector will operate when the calculated earthing resistor is less than the resistor
setting [R_Trp_Inj_EF_Sta].
The fault detector operates when grounded resistance of rotor is less than its setting
[R_1PEF_RotWdg].
The fault detector operates when change of rotor grounding location is greater than its internally
fixed setting.
The fault detector operates when maximum value of three phase currents is greater than its
setting [I_OvLd_Sta].
The fault detector operates when inverse time accumulated value is greater than its setting
[I_InvOvLd_Sta].
The fault detector operates when maximum value of negative sequence current is greater than its
setting [I_NegOC_Gen].
The fault detector operates when inverse time accumulated value is greater than its setting
[I_InvNegOC_Gen].
The fault detector operates when locus of calculated impedance enters into impedance circle.
The fault detector operates when locus of calculated impedance leaves boundary of impedance
operation zone.
The fault detector operates when maximum value of three phase-to-phase voltage is greater than
its setting.
The fault detector operates when measured U/F is greater than definite time setting.
The fault detector operates when over excitation inverse time accumulated value is greater than
inverse time setting.
When measured reverse power is greater than setting, the fault detector of reverse power of
generator picks up.
The fault detector operates when frequency is lower than its setting for a specified time interval.
The fault detector operates when frequency is greater than its setting for a specified time interval.
The fault detector operates when maximum phase current of generator is greater than setting of
unwanted closing protection.
The fault detector operates when negative sequence current of at CB side is greater than setting
of circuit breaker flashover protection.
The fault detector operates when any of the differential current of main transformer, generator,
excitation transformer, and stepdown transformer is greater than its setting, or zero sequence
voltage of generator is greater than its setting.
The fault detector operates when maximum value of three phase differential currents is greater
than its setting.
The fault detector operates when maximum value of three phase currents is greater than its
setting.
NANJING NARI-RELAYS ELECTRIC CO., LTD 37
Chapter3 Description of Operation Theory
The fault detector operates when maximum value of three phase currents of exciter winding is
greater than its definite time setting.
The fault detector operates when inverse time accumulated value is greater than inverse time
setting.
The fault detector operates when duration of operation of mechanical protection is greater than its
delay setting.
Note:
In following logic diagrams, all logic inputs starting with “En_**” represent enabling logic settings
which will be explained in later section, all logic inputs starting with “EBI_**” represent enabling
binary inputs from panel, those starting with “Flg_**” represent internally generated flags
indicating whether or not a certain element is met, those words begin with “Alm_” and “Op_”
represent output for alarming and operation of protective element respectively.
During the normal operation, the magnitude and angle of secondary currents at each side of
transformer are different due to different CT ratios, different voltage levels and different
transformer connection groups. This kind of current differentiations shall be eliminated under
normal operation and compensated in fact by a built-in compensation method.
Sn
I b1n =
3U b1n (Equation 3.4-1)
Where:
U b1n is the rated phase-to-phase voltage at the calculated side of the transformer (i.e.
[U1n_HVS_Tr] or [U1n_LVS_Tr].)
I b1n
Ib2n =
nbLH (Equation 3.4-2)
Where:
I b 2 n −b
K ph =
Ib2n (Equation 3.4-3)
Where:
The currents used in the following analysis have been corrected, that means the currents are the
products of the original secondary current of each side multiplying its own correction coefficient
( K ph ).
By defining which particular connection group the protected transformer belongs to, the proper
calculation routine will be applied.
• The positive polarity of CT at HV and MV side is at busbar side and that at LV side is at branch
side or generator side.
• Polarity of each secondary winding of CT is as same as shown in Figure 1.3-1 to Figure 1.3-2.
The secondary current phase shift compensation for all CTs are achieved by software, Y→Δ
transform method is used for this purpose. For connection Y/Δ-11, the correction equations are as
follows:
At side Y0:
•' • •
I A = ( I A − I B)/ 3
•
' • •
I B = ( I B − I C ) / 3
•' • • (Equation 3.4-4)
I C = ( I C − I A ) / 3
At side Δ:
•' •
I• a = I a
' •
I• b = I b (Equation 3.4-5)
' •
I c = Ic
Where:
• • •
I A , I B , I C are the secondary currents of CT at side Y.
• • •
I ' A , I ' B , I ' C are the corrected current of each phase at side Y.
• • •
I a , I b , I c are the secondary currents of CT at side Δ.
• • •
I ' a , I ' b , I ' c are the corrected currents of each phase at side Δ;
For other connection type,the current can be calculated according to the equations listed above.
The connection type can be selected by following logic settings (refer to power system
parameters in Chapter7).
[Yd11_Conn]
[Yyd11_Conn]
Note:
If your actual transformer connection group is not included in above two groups, please let us
know before you make the order.
Pn / cos θ
I f 1n =
3U f 1n (Equation 3.4-6)
Where:
[U1n_VT_NP_Gen].)
I f 1n
I f 2n =
n fLH (Equation 3.4-7)
Where:
Id
Restraint area
Icdqd Kbl1
0
Ie nIe Ir
I1 + I 2 + I 3 + I 4 + I 5
I r =
2
• • • • •
I = I 1 + I 2 + I 3 + I 4 + I 5
d
Where:
I d is differential current,
I r is restraint current,
I e is rated current.
K bl 1 is the first slope of percentage differential with setting range 0.05 – 0.15. 0.10 is applicable
usually.
K bl 2 is the second slope of percentage differential with setting range 0.50 – 0.80. 0.70 is
applicable usually.
Note:
For differential current of generator-transformer unit and main transformer, redefinition of each
current in (Equation 3.4-8) is different for different program versions and can be found on
individual project-specific document.
Usually, for generator-transformer unit differential protection, I1 represent currents of HVS of main
transformer, I2 represents current of HVS of stepdown transformer, I3 represents current of
neutral point of generator, I4 and I5 is not defined; for differential protection of main transformer,
I1 represents current of HVS1 of main transformerfor, I2 represents the current of HVS of
stepdown transformer, I3 represents the current of LVS of main transformer, I4 and I5 is not
defined.
For differential current of excitation transformer, I1 and I 2 are currents of HV side and LV side
A percentage differential protection with high percentage and high setting is equipped with the
equipment to prevent delayed operation of percentage differential protection caused by CT
saturation and other factors during serious internal fault. This protection is blocked only by inrush
current criterion i.e. second harmonic of differential current or waveform discrimination. It can
prevent influence of steady state and transient CT saturation during external fault and can operate
correctly and quickly during internal fault even if CT is in saturation condition. Operation criterion
of this high setting percentage differential protection is:
I d > 1.2 × I e
(Equation 3.4-9)
I d > 1.0 × I r
Where
When fault occurs, the operation criterion will be discriminated phase by phase and percentage
differential protection will operate if the criterion is met. For more detailed operation characteristic
please see Figure 3.4-3.
Note:
Parameters of this protection have been fixed in program and do not need to be configured by
user.
The aim of unrestrained instantaneous differential protection for transformer is to accelerate the
trip speed for transformer’s inner fault. So the element does not need any block element, but the
setting should be greater than maximum inrush current.
Where:
Note:
All the settings mentioned below are from main transformer for example.
(1) Steady state percentage differential protection element (described in section 3.4.3.1) will not
send tripping signal in case of CT saturation, CT circuit failure (optional), inrush current and
overexcitation condition. It can ensure sensitivity of protection and avoid unwanted operation
when CT is saturated during external fault. Its operation area is tint shadow area.
(2) High setting percentage differential protection element (described in section 3.4.3.2) will not
send tripping signal only due to CT circuit failure (optional) and inrush current. It eliminates
influence of transient and steady saturation of CT during external fault and ensures reliable
operation even if CT is in saturation condition during internal fault by means of its percentage
restraint characteristic. Its operation area is deep shadow area.
(3) Unrestrained instantaneous differential protection element (described in section 3.4.3.3) will
send tripping signal without any blocking if differential current of any phase reaches its setting. Its
operation area is over the above two areas with no shadow.
In the equipment, the second harmonic of differential current can be used to distinguish inrush
current. Its operation criterion is:
Where:
is recommended.
During internal fault, differential currents of various sides transferred by CT are basically
fundamental sinusoidal wave. But when the transformer is energized, lots of harmonics occur.
The waveform is intermittent and unsymmetrical. A special algorithm can be used for
discrimination of the inrush current.
S > kb*S +
(Equation 3.4-12)
S > S t
Where:
S + is full cycle integral of the sum of instantaneous value of differential current and that of half
cycle before.
kb is a fixed constant.
Where:
α is a proportional constant.
If any one of three phases can not meet above equation, the differential current can be
considered as inrush current and percentage differential relay will be blocked.
In this protection equipment, logic setting [Opt_Inrush_Ident_Tr] is provided for user to select the
restraint blocking principle. If the logic setting is set as “0”, discrimination by harmonics is enabled.
Otherwise, discrimination by waveform distortion is enabled.
In order to prevent unwanted operation of steady state percentage differential protection caused
by transient or steady state saturation of CT during external fault, composite harmonics of
secondary differential current is used for the protection equipment to discriminate saturation of CT.
The expression is as following:
Where:
When fault occurs, if DPFC of restraint current and DPFC of differential current appear
simultaneously, this is an internal fault. If DPFC of restraint current appears before DPFC of
differential current, this maybe an external fault and criterion of CT saturation shall be adopted in
this case. So unwanted operation of percentage differential protection due to CT saturation can
be prevented.
3.4.3.7 Differential current abnormality alarm and CT circuit failure blocking function
Differential current abnormality alarm with percentage restraint (see section 4.1.3) and instant CT
circuit failure blocking function are equipped with the equipment.
When a transformer is overexcited, the exciting current will increase sharply which may result in
unwanted operation of differential protection. Therefore the overexcitation shall be discriminated
to block the current differential protection. The fifth harmonic of differential current is used as
criterion of overexcitation discrimination.
Where:
Note:
High setting percentage differential protection is not blocked by fifth harmonic of differential
current.
Note:
The above logic diagram is also suit for differential protection of generator-transformer unit(GTU)
and stepdown transformer.
Where:
[Flg_UIDP _Tr] is the flag indicating whether or not the criterion of UIDP element is met.
[Flg_HSDP _Tr] is the flag indicating whether or not the criterion of HSDP element is met.
[Flg_SPDP _Tr] is the flag indicating whether or not the criterion of SPDP element is met.
[Flg_Inrush] is the flag indicating whether or not the criterion of inrush current detection is met.
[Flg_OvExc_Tr] is the flag indicating whether or not the transformer is in overexcitation state.
Restraint area
Kbl1
Icdqd
0
Ie nIe Ir
(Equation 3.4-16)
• •
I 1+ I2
Ir =
2
• •
I d = I 1 − I 2
Where:
I d is differential current,
I r is restraint current,
K bl 1 is the first slope of percentage differential with setting range 0.05 – 0.15. 0.05 is
recommended usually.
K bl 2 is the second slope of percentage differential with setting range 0.30 – 0.70. 0.50 is
recommended usually.
n is the multiple of restraint current at second percentage restraint coefficient and is fixed at 4.
For differential protection of generator and exciter, I1 and I 2 are currents of terminal and neutral
point respectively.
In order to prevent unwanted operation of steady state percentage differential protection due to
CT transient or steady state saturation during external fault, discrimination of waveform of
differential current principle is adopted as criterion of CT saturation.
When fault occurs, the equipment decides firstly whether it is internal or external fault. If it is
external fault, criterion of CT saturation is enabled. If any phase differential current of differential
protection meets the criterion, it is decided that this differential current comes from CT saturation
and the percentage differential protection will be blocked.
A percentage differential protection with high percentage coefficient and high pick-up setting is
equipped with the equipment to prevent operation of percentage differential protection delayed by
CT saturation and other factors during serious internal fault. It can prevent influence of steady
state and transient CT saturation during external fault due to its percentage restraint characteristic
and can operate correctly and quickly during internal fault and CT being saturated. Operation
criterion of this high setting percentage differential protection is
I d > 1.2 × I e
(Equation 3.4-17)
I d > 1.0 × I r
Where:
Differential current I d and restraint current I r are the same as mentioned above.
When fault occurs, the operation criterion will be discriminated phase by phase and percentage
differential protection will operate if the criterion is met.
Parameters of this protection are configured during manufacturing and not need to be configured
in site.
This protection will operate and trip immediately if differential current of any phase is higher than
its setting.
3.4.4.5 Differential current abnormality alarm and CT circuit failure blocking function
Differential current abnormality alarm with percentage restraint and instant CT circuit failure
blocking function are equipped with the equipment.
[Flag_UIDP_Gen]
&
[EBI_Diff_Gen]
& [Op_InstDiff_Gen]
[En_Diff_Gen]
[En_InstDiff_Gen]
[FD_Diff_Gen]
[Flag_HSDP_Gen]
[En_Diff_Gen]
[En_PcntDiff_Gen]
≥1 [Op_PcntDiff_Gen]
[Flag_CTS]
[FD_Diff_Gen]
[Flag_CTsat]
[Flag_SPDP_Gen]
& & &
[EBI_Diff_Gen]
[En_Diff_Gen]
[En_PcntDiff_Gen]
[Flag_CTS]
[FD_Diff_Gen]
Where:
[Flg_UIDP _Gen] is the flag indicating whether or not the criterion of UIDP element is met.
[Flg_HSDP _Gen] is the flag indicating whether or not the criterion of HSDP element is met.
[Flg_SPDP _Gen] is the flag indicating whether or not the criterion of SPDP element is met.
[EBI_Diff_Gen]: is enabling binary input for all kinds of differential protection of generator.
Where:
∆I dt is floating threshold which increases progressively along with DPFC increasing. Take its
multiple as 1.25 can ensure threshold voltage always a bit higher than imbalance current. So that
unwanted operation of the equipment can be avoided during power swing and frequency
deviation conditions.
Generally, for differential protection of main transformer, ∆I1 , ∆I 2 , ∆I 3 and ∆I 4 are DPFCs of
currents of sides 1 and 2 at HVS of main transformer, generator terminal and HV side of stepdown
transformer respectively. But for some specific design, ∆I1 can represents the HVS current of
For differential protection of generator, ∆I1 and ∆I 2 are currents at the terminal of generator
Note:
Calculation of restraint current of DPFC percentage differential protection is different from the
steady state percentage differential protection, it is difficult to test this function on site, so we
recommend only qualitative function test on site.
DPFC differential protection is equipped to each phase of generator, but user should know that
the restraint DPFC quantity for every phase is the same maximum value among the three phases.
The following figure shows operating characteristic of DPFC percentage differential protection.
? Id
differential current
0.75
0.6
Icdqd
restraint current
2 Ie ? Ir
When fault occurs, the operation criterion will be discriminated phase by phase and percentage
differential protection will operate if the criterion is met. For DPFC percentage differential
protection of main transformer, second harmonic or waveform inrush current blocking and fifth
harmonic over excitation blocking are adopted. It can prevent influence of steady state and
transient CT saturation during external fault due to its percentage restraint characteristic.
This protective element has high ability to eliminate the effect of transient and steady saturation of
CT during the external fault because the restraint coefficient is set at a higher value.
In the figure:
[Flg_DPFC_Diff_Gen] is the flag indicating whether or not the criterion of DPFC differential
element is met.
[EBI_Diff_Gen]: is enabling binary input for all kinds of differential protection of generator.
[En_Diff_Gen]: general logic setting for enabling differential protection of generator.
[Flg_IntanCTS] is the internally generated flag indicating that CT supervision program detects
failure of CT circuit with no delay considered into account.
Settings of DPFC percentage differential protection is are fixed and need not to be set on site.
Restricted earth fault (REF) protection is also called zero-sequence differential protection in this
manual, which includes zero-sequence percentage differential protection element and
unrestrained instantaneous zero-sequence differential protection element. REF protection is used
to protect the main transformer and/or stepdown transformer with neutral point earthed
with/without resistance.
If CTs used for REF have different ratios, then the ratio compensation is needed. Here is the
method.
K TA K TA − max
K ph = × Kb K b = min( ,4)
K TA _ b K TA −b (Equation 3.4-19)
Where:
In principle, this method take the neutral point rated secondary current as the base of calculation
and all other sides will be considered as its multiples. The ratio of the maximum CT ratio to base
CT ratio must be less than 4. If ratio of the maximum to base is less than 4, the multiple of the
base rated current will be taken as 1, and other side will be calculated proportionally. Thus the
maximum setting range of current ration correction coefficient K ph of each side can be up to 4.
The currents used in the following analyze are based on the assumption that they have been
adjusted, that means the currents are the products of original current of each side and its own
adjustment coefficient ( K ph ).
Zero-sequence percentage differential protection is used for earth fault at HV side of main
transformer(Wye connection), LV side of stepdown transformer(Wye connection). Its operation
criteria are as follows:
I 0 d > I 0 cdqd
I > K × I
0 d 0bl 0r
I 0 r = max{ I 01 , I 02 , I 03 , I 0 n }
• • • • (Equation 3.4-20)
I 0 d = I 01 + I 02 + I 03 − I 0 n
Where:
I 01 , I 02 , I 03 are zero sequence currents of branches A1, A2, A3. For HV side of main
transformer, there are only one branch I 01 which is the sum of three-phase currents derived from
backup CT of HV side of main transformer, and other branches have no definition. For LV side of
When equation above is satisfied, the zero-sequence percentage differential protection will
operate. Zero-sequence differential currents on various sides except neutral point are got from
internal calculation, and the polarity check of zero-sequence current transformers (CT) on various
sides is not needed.
WARNING!
The polarity check of neutral point current must be done befor the zero-sequence percentage
differential protection is put into service.
I 0d > [ I _ InstREF ]
(Equation 3.4-21)
The operation of this protection shall trip all breakers at all sides of a transformer when any
unrestrained zero-sequence differential current is higher than its setting. Its operation criterion is:
I 0d > [ I _ InstREF ]
(Equation 3.4-21)
Where:
K0bl
I0cdqd
It I0r
I t will be automatically changed according to the pickup current I 0cdqd and restrict coefficient
K 0bl .
Difference of transient characteristic and saturation of CT will increase zero sequence current in
differential scheme during external three-phase short circuit fault. In order to eliminate this effect,
positive sequence current restraint blocking criterion and CT saturation criterion are used.
Positive sequence current restraint principle can be expressed as following:
I 0 > β 0 * I1
(Equation 3.4-22)
Where:
I0 is the cauculted zero sequence current from the three-phase current of backup CT of HV side
of main transformer.
β 0 is a proportional coefficient.
The relay also adopts 2nd harmonic component to identify the CT saturation.
When the zero sequence differential current is above the alarm setting [I_Alm_REF] for 10s, the
circuit alarm for REF protection [Alm_REF] will be issued. But the REF protection is also in
service.
HV side of main transformer and LV side of stepdown transformer have restricted earth fault
protection and their logics are same. Here take HV side of main transformer as an example.
Figure 3.4-10 Logic diagram of restricted earth fault protection at HV side of main transformer
[Flg_REF_Tr]: is the flag indicating whether or not the criterion of REF element is met.
[Flg_CTsat]: is the internally generated flag indicating that CT is not in saturation condition.
CAUTION!
Before tripping function of REF is put into operation, polarity of CT used for this element must be
carefully checked to ensure it is suited for the requirement of REF to avoid unwanded operation.
Figure 3.4-11 shows operation characteristic of impedance element. In this figure, I is phase
jX
•
I Zp
• •
U− I Zp
ϕm •
U
R
• •
• U + I Zn
− I Zn
Operation criterion:
• •
(U − I Z P )
90 < Arg
o
• •
< 270 o
(U + I Z n ) (Equation 3.4-23)
The fault detector of impedance protection adopts DPFC of phase current and negative sequence
current. Initiation of the fault detector will be lasted for 500 ms and will be kept if impedance relay
operates during this time interval. Operation criterion of the fault detector is
∆I > 1.25∆I t + I th
(Equation 3.4-24)
Where:
∆I t is floating threshold which increases progressively along with DPFC increasing. Take its
multiple as 1.25 can ensure threshold current always a bit higher than imbalance current. So that
unwanted operation of the equipment can be avoided during system swing and frequency
deviation conditions.
I th is the fixed threshold. When DPFC of phase-to-phase current is higher than 0.3 Ie, the fault
detector operates.
The impedance protection will be disabled automatically if the VT circuit failure is discriminated.
[Flg_VTS ]
[Flg_Z1_HVS_Tr] &
[Op_Z1_HVS_Tr]
&
[En_PPF_HVS_Tr]
t
&
[EBI_PPF_HVS_Tr ]
[FD_PPF_Tr]
Where:
[Flg_VTS] is flag indicating whether or not the VT circuit fails. “1” means failure.
Function of overcurrent protection with composite voltage blocking is equipped with RCS-985B.
This protection, consisting of 2 stages and 2 time delays per stage, is used for phase-to-phase
backup protection of main transformer. Of which, function of composite voltage element can be
enabled or disabled by logic setting.
The voltage control element is an element which will operate if phase-to-phase voltage is lower
than the setting [Vpp_VCE_Tr] or negative sequence voltage is greater than its setting
[V_NegOV_VCE_ Tr]..
Criteria:
Where:
All two stages of definite time overcurrent protection can be controlled by voltage element by
configuring related logic settings [En_VCE_Ctrl_OC1_Tr] and [En_VCE_Ctrl_OC2_Tr].
Meanwhile, User can decide by which side voltage overcurrent protection be controlled by
configuring related settings. For example, if the setting [En_LVS.VCE_Ctrl_OC_Tr] is set as “1”,
then the overcurrent protection is controlled not only by HV side voltage element but also by LV
side voltage element.
For self and parallel-excited generator, current will decrease so quick during fault that it may be
lower than overcurrent setting before tripping. So memorizing function for fault current is equipped
with this protection. Logic setting [En_Mem_Curr_Tr] is used for configure of this function.
Note:
When logic setting [En_Mem_Curr_Tr] is enabled, the overcurrent must be controlled by voltage
element.
When VT on one side is under maintenance or bus-tie breaker is used for the transformer but its
VT has not been switched over to the protection equipment, VT circuit failure is detected. Logic
setting [Opt_VTS_Ctrl_OC_Tr] is used to configure performance of voltage control element during
VT circuit failure. When this logic setting is set as “1”, if VT circuit failure is detected, the voltage
control element cannot pick up and the protection will not operate. When this logic setting is set as
“0”, if VT circuit failure is detected on this side, voltage control element is forced to be satisfied,
then the voltage controlled directional overcurrent protection controlled by voltage will becomes a
pure overcurrent protection.
Where:
[Flg_VTS]: is the internally generated flag indicating whether or not the VT circuit fails.
[Opt_VTS_Ctrl_OC_Tr] is the setting to configure the VCE mode under VT circuit failure.
[Op_OCn_Tr] indicates that whether or not the stage n of overcurrent protection operates.
Zero sequence overcurrent relay is mainly used as backup protection of ground fault for
transformer with neutral point earthed. Two stages and two time delays zero sequence
overcurrent relay is equipped with RCS-985B. The zero sequence current is usually adopted from
neutral point CT.
By setting logic settings, following functions of any stages of this protection can be selected:
The direction of zero sequence overcurrent protection points to system definitely with the reach
angle 75º. If the VT failure at HV side occurs, the directional element will be out of service.
The voltage used by directional relay is definitely the calculated voltage. The direction mentioned
above is based on the CT positive polarity for calculated zero sequence current being at the side
of busbar. The details are shown in Figure 1.3-1 to Figure 1.3-2.
Figure 3.4-14 shows operating characteristic of directional protection in which the hatched area is
operation zone.
3U0
f lm = 75 °
I
o
Point to system
Zero sequence voltage element uses definitely the open-delta voltage of VT.
3U0>[V_ROV_VCE_Tr]
=1
[En_VCE.ROV_Ctrl_ROCn_Tr]
[Flg_Dir_ROC_Tr]
=1 & [Op_ROCn_Tr]
[En_Dir_Ctrl_ROCn_Tr] & t
[t_ROCn_Tr]
[Flg_ROCn_Tr]
&
[En_EF_Tr]
[EBI_EF_Tr]
[FD_ROC_Tr]
Where:
[Flg_Dir_ROC_Tr] is flag indicating that whether or not the criterion of directional element is met.
[Flg_ROCn_Tr] is flag indicating that the zero sequence current is above the setting.
[EBI_EF_Tr] is the binary input to enable/disable the earth fault protection of transformer.
[Op_ROCn_Tr] indicates that the stage n of zero sequence overcurrent protection operates.
“Gap” zero sequence overvoltage protection is used for backup protection of main transformer
with neutral point ungrounded or grounded through gap. Zero sequence overvoltage protection
with one stage and two time delays is equipped for this protection.
Zero sequence overvoltage protection can be enabled by enabling binary input from the
protection panel as well as external contact input. If the setting [En_BI_Ctrl_ROC_Gap_Tr] is set
as “0”, the Gap ROV protection is controlled by the enabling binary input only. If the setting
[En_BI_Ctrl_ROC_Gap_Tr] is set as “1”, the Gap ROV protection is enabled only when both the
enabling binary input is energized and binary external input (BI_Reserved) is “1”.
According to the case that circuit breaker is equipped at the terminal of generator, a zero
sequence voltage alarm can be provided on main transformer LV side as the supervision of
earthing fault. The voltage setting is usually set as 10V to 15V. The alarm can be enabled or
disabled by logic setting [En_Alm_ROV_LVS_Tr]. The function outputs alarm signals. To
RCS-985B, AC voltage input is from connectors (9B23, 9B25).
Overload alarm and initial cooling are equipped with backup protection of HV side of main
transformer. Overload alarm and initial cooling can be enabled or disabled by logic settings
[En_OvLd_Tr] and [En_InitCool_OvLd_Tr]. Outputs of initial cooling are three normal open
contacts.
Transverse differential protection installed on connection between two neutral points of generator
is used as main protection of interturn fault of generator’s stator winding, open circuit fault of
branches and short circuit fault between phases.
Since this protection adopts frequency tracing, digital filtering and full cycle Fourier algorithm, the
third harmonic can be reduced to 1/100 within the frequency tracing range and the protection can
response the fundamental component only.
This protection comprises two stages: unsensitive stage (high setting stage) and sensitive stage.
This stage is equivalent to traditional transverse differential protection. When the transverse
differential current is in excess of the setting [I_UnsensTrvDiff_Gen], the protective element
operates.
Phase current percentage restraint principle is used for this stage. The operation criterion is
Where:
Phase current percentage restraint transverse differential principle can ensure no unwanted
operation during external fault and sensitive operation during internal fault. As this principle is
adopted, current setting of the transverse differential protection shall be only higher than
unbalance current during normal operation and much less than that of traditional transverse
differential current protection. Sensitivity for interturn fault of generator can be enhanced then.
This protection has also a floating threshold for high transverse differential unbalance current
during other normal operation conditions.
Operation of the high sensitive transverse differential protection will lead a tripping immediately.
When rotor of generator is grounded at one point, a configurable time delay [t_TrvDiff_Gen] will
be inserted in the tripping course. Figure 3.4-16 shows logic diagram of this protection.
[Flg_1PEF_Rot]
&
t
[En_Alm_1PEF_Rot] &
[Op_TransDiff_Gen] [Op_Sens_TransDiff_Gen]
=1 &
[En_IntTurn_Gen]
&
&
[En_Sens_TransDiff_Gen]
[EBI_IntTurn_Gen]
[FD_TransDiff_Gen]
Where:
[Flag_1PEF_Rot] is internally generated flag indicating the one-point earth fault protection of rotor
operates.
[En_Alm_1PEF_Rot] is logic setting of enabling one-point earth fault alarming of rotor. “1” means
enabled.
Longitudinal zero sequence voltage protection is configured for inter-turn fault of stator winding of
generator. It uses open-delta voltage of dedicated VT at the terminal of generator as the criterion.
Since this protection adopts frequency tracing, digital filtering and full cycle Fourier algorithm, the
third harmonic can be reduced to 1/100 within the frequency tracing range and the protection can
response the basic wave component only.
This protection comprises two stages: unsensitive stage (high setting stage) and sensitive stage.
Setting of this stage shall be higher than maximum unbalance voltage during external fault, whilst
directional flag indicating internal fault must be satisfied. When measured longitudinal zero
sequence voltage is in excess of the setting [V_UnsensROV_Longl_Gen] and lasts for longer
than the delay setting [t_ROV_Longl_Gen], this protective element will trip breakers according to
the configuration of [TrpLog_IntTurn_Gen].
Phase current percentage restraint principle is used for this stage. The operation criterion is
U zo > [ 1 + K zo × I m / I e ] × U zozd
Im = 3 × I2 when I MAX < I e (Equation 3.4-27)
I m = (I MAX - Ie ) + 3 × I 2 when I MAX ≥ I e
Where:
Likely to transverse differential principle, this protective element can ensure no unwanted
operation during external fault and sensitive operation during internal fault. As for the percentage
restraint characteristic, zero sequence voltage setting of the zero sequence voltage protection
shall be only higher unbalance voltage during normal operation. Sensitivity for interturn fault of
generator can be enhanced then.
This protective element has also a floating threshold for high unbalance longitudinal zero
sequence voltage during other operation conditions.
Longitudinal zero sequence voltage protection for inter-turn fault of stator shall be blocked when
the dedicated VT2 circuit at the terminal of generator fails. There are two criteria to decide to
whether or not block the protection.
In the above three criterion, if one of the former two and the third are met simultaneity, the
longitudinal zero sequence voltage protection will be blocked.
| U AB - U ab | > 5V
| U BC - U bc | > 5V
| U CA - U ca | > 5V (Equation 3.4-28)
That any one of these three sub-criteria is met means criterion 2 picks up.
When any of criterion 1 and criterion 2 operates, alarm of VT2 circuit failure will be issued by
delay 40 ms and zero sequence voltage protection will be blocked.
After VT circuit failure reverting to normal condition, blocking can be released by pressing the
Target-reset button on the faceplate of the protection.
[Flg_Dir_NegP]
[Flg_LongiROV_Sta]
&
[Flag_VTS]
&
& t
[En_IntTurn_Gen]
[Op_UnsensROV_Longl_Gen
]
[En_UnsensROV_Longl_Gen]
[EBI_IntTurn_Gen]
[FD_IntTurn_Sta]
[Flg_LongiROV_Sta]
&
[Flg_VTS] [Op_SensROV_Longl_Gen]
&
& t
[En_IntTurn_Gen]
[t_ROV_Longl_Gen]
[En_SensROV_Longl_Gen]
[EBI_IntTurn_Gen]
[FD_IntTurn_Sta]
Where:
[Flag_Dir_NegP] is internally generated flag indicating whether or not the directional element
calculated from negative sequence voltage and current is meet the faulty condition.
• ∧
∆F = Re[∆ U 2 × ∆ I 2 × e jΦ ] > ε + 1.25 × dF (a)
If the three criterions are met simultaneity, the directional flag of protection is set. Under negative
sequence voltage and negative sequence current controlling, the protection operates after
0.2-0.5s time delay.
AC current and voltage input of directional DPFC protection are from the generator terminal
directly. When the VT1 at the generator terminal fails, directional DPFC protection is blocked. The
setting is default setting. The sensitivity is about 3V of longitudinal zero sequence voltage.
Directional DPFC protection for inter-turn fault can’t response to inter-turn fault before the
generator is connected into the power system.
Two stages impedance protection is equipped at the terminal of generator as its phase-to-phase
backup protection. Phase-to-phase current used in impedance relay is derived from CT at the
neutral point of generator. Circular impedance, directional circular impedance or drifted circular
impedance characteristic can be selected to act for these two stages. Circular characteristic suits
case of forward setting of a zone being equal to its reverse setting. Directional circular
characteristic suits case of reverse setting of a zone being set as 0. Drifted circular characteristic
suits for case that forward setting of a zone is higher than its reverse setting. Reach angle of
impedance protection is 78°. Positive direction of the impedance protection is configurable and
generally points to generator.
Operation criterion:
• •
(U − I Z P ) (Equation 3.4-30)
90o < Arg • •
< 270o
(U + I Z n )
DPFC of phase current and negative current element are adopted as fault detector of impedance
protection. Initiation of the fault detector will be extended to 500 ms and will be kept if impedance
relay operates during this time interval. Operation criterion of the fault detector is
∆I > 1.25∆I t + I th
(Equation 3.4-31)
Where:
∆I t is floating threshold which increases gradually along with DPFC increasing. Take its multiple
as 1.25 can ensure threshold voltage always a bit higher than imbalance voltage.
jX
•
I Zp
• •
U − I Zp
ϕm •
U
R
• •
• U + I Zn
− I Zn
Unwanted operation of the equipment can be avoided during conditions of power swing and
frequency deviation from nominal valuess. I th is the fixed threshold. When DPFC of
phase-to-phase current is higher than 0.2 Ie, the fault detector operates.
Note:
[Flg_VTS]
[Flg_Zn_Gen] &
&
[En_PPF_Gen] [Op_Zn_Gen]
& t
[EBI_PPF_Gen]
[t_Zn_Gen]
[FD_Dist_Gen]
Where:
This protection is used as a backup protection of generator, main transformer, HV busbar and
neighboring power lines. There are two stages with their own delay settings respectively. Stage 1
is used to trip bus coupler breaker or other circuit breaker and stage 2 to shut down the generator.
Figure 3.4-20 shows its logic diagram.
For generators with self shunt excitation, current will decrease so quickly during fault that it may
be lower than overcurrent setting before tripping. So memorized function for remember fault
current is equipped with this protection. Logic setting [En_Mem_Curr_Gen] is used for
configuration of this function. See details about the setting in section 7.3.8.
Note:
voltage element.
Overcurrent protection can be blocked not only by composite voltage at terminal of generator but
also by composite voltage on HV side of main transformer. This function can be configured by
setting logic setting [En_HVS.VCE_Ctrl_OC_Gen] as “1”.
Figure 3.4-20 Logic diagram of overcurrent relay with composite voltage blocking
Where:
Single-phase earth fault within 85% - 95% range from terminal of stator winding can be protected
by fundamental zero-sequence overvoltage protection.
This protection comprises two stages: sensitive stage and unsensitive stage (high setting stage).
U n0 > U 0zd
(Equation 3.4-32)
Where:
U 0zd = K rel U unb.max , U 0zd is operation threshold setting of fundamental zero sequence voltage
[V_SensROV_Sta].
To assure its security, user should check the setting by comparing it with the transferred zero
sequence voltage through coupling capacitance between HV side and LV side of transformer
when external earth fault occurs on the HV side of the transformer. Meanwhile, settings, including
time delay and operation setting, should be considered to cooperate with that of earth fault
protection of the system.
U n0 > U 0hzd
(Equation 3.4-33)
Where:
U 0hzd is the zero sequence voltage high setting [V_UnsensROV_Sta]. 20V ~ 25V is
recommended generally.
This protection is designed to cover only about 25% of earth fault of the stator winding away from
generator terminal. Third harmonic voltage of generator terminal is got from its open-delta zero
sequence voltage. Third harmonic voltage of neutral point side is got from neutral point VT of the
generator.
U 3T / U 3N > K 3wzd
(Equation 3.4-34)
Where:
U 3T and U 3N are third harmonic voltage of generator terminal and neutral point respectively.
In addition, settings are provided for deciding whether the ratio protection of third harmonics
voltage is used for alarm or tripping or both.
• • •
U 3T − K t × U 3 N > Kre × U 3 N
(Equation 3.4-35)
Where:
• •
U 3T and U 3 N are third harmonic vector voltage of generator terminal and neutral point,
This protection is enabled automatically when the generator has been connected with the system
and load current is higher than 0.2 Ie (generator rated current) and only issues alarms if operates.
Since open-delta voltages of VT at neutral point and generator terminal are taken for zero
sequence voltage protection of stator, failure of these VT circuits will make this protection fail to
operation. So alarm shall be issued during this case. Third harmonic voltage ratio criterion and
third harmonic voltage differential criterion shall be disabled during VT circuit failure at generator
neutral point.
Positive sequence voltage of secondary winding of generator terminal is higher than 0.9Un and
third harmonic of zero sequence voltage is lower than 0.1V.
VT circuit failure alarm will be issued by delay 10s and reverted automatically by delay 10s when
the failure vanishes.
Secondary circuit failure of VT1 of generator terminal will not influence ground protection of stator.
Primary circuit failure of VT1 of generator terminal will cause basic wave component of zero
sequence voltage of generator terminal increasing and third harmonic component decreasing,
and will not cause unwanted operation of basic wave zero sequence voltage protection and third
harmonic voltage ratio protection. However, it will cause unwanted operation of third harmonic
voltage differential protection, so this protection shall be blocked during this failure. Operation
criterion of this failure is:
When these criterions are met, VT1 primary circuit failure alarm will be sent by short delay and
third harmonic voltage differential protection will be blocked.
Figure 3.4-21 and Figure 3.4-22 show logic diagrams of fundamental zero sequence voltage earth
fault protection and third harmonic voltage earth fault protection respectively.
[En_Alm_ROV_Sta]
[Flg_VTS] [Alm_ROV_Sta]
& t
[Flg_SensROV_Sta] &
[En_EF_Sta]
& [Op_Trp_ROV_Sta]
[En_Trp_ROV_Sta] & t
[EBI_ROV_Sta] [t_ROV_Sta]
[FD_EF_Sta]
Figure 3.4-21 Logic diagram of fundamental zero sequence overvoltage earth fault protection of
stator
Where:
[EBI_ROV_Sta] is binary input of binary input of enabling earth fault protection. “1” means
enabled.
[En_Alm_V3rdHRatio_Sta]
[Alm_V3rdHRatio_Sta]
[Flg_VTS] & t
&
[Op_V3rdHRatio_Sta]
[En_EF_Sta]
[Op_V3rdHRatio_Sta]
& & t
[En_Trp_V3rdHRatio_Sta]
[t_V3rdH_Sta]
[EBI_En_V3rd_Sta]
[FD_EF_Sta]
Figure 3.4-22 Logic diagram of third harmonic voltage earth fault protection of stator
Where:
[EBI_V3rd_Sta] is state flag of binary input of enabling ratio protection of 3rd harmonics voltage.
“1” means enabled.
If an earth fault in the generator neutral point or close to the neutral is not detected, the generator
is running with an “earthing”. A subsequent fault (e.g. a second earth fault) causes a single-pole
short-circuit that may have an extremely high fault current because the generator zero impedance
is very small.
Figure 3.4-23 shows the basic protection principle. An external low-frequency alternating voltage
source (20 Hz) injects into the generator neutral point with a voltage of max. 1% of the rated
generator voltage. If an earth fault occurs in the generator neutral point, the 20 Hz voltage drives a
current through the fault resistance. From the driving voltage and the fault current, the protective
relay determines the fault resistance. The protection principle described here also detects earth
faults at the generator terminals, including connected components such as voltage transformers.
Figure 3.4-23 Circuit Design of the 100% voltage-injecting Stator Earth Fault Protection with
Earthing Transformer
To implement the above concept, some additional equipment is required. Figure 3.4-23 shows
that a 20Hz generator generates a square-wave voltage. This square-wave voltage is fed via a
Resonant/blocking impedor into the loading resistor of the earthing. The resonant/blocking
impedor serves for passing low frequency signals but inhibit 50Hz or 60Hz signal.
The driving 20Hz voltage is picked up directly at the loading resistor via a voltage divider. In
addition, the 20Hz current flow is measured via a intermediate miniature CT. Both quantities (USEF
and ISEF) are fed to the protection device. The voltage to be injected into the generator neutral
point depends on the driving 20Hz voltage (voltage divider: load resistor and band pass filter), and
on the transformation ratio of the earthing transformer.
To prevent the secondary load resistance from becoming too small, a high secondary rated
voltage should be chosen for the earthing or neutral transformer.
RCS-985B provides two settings to issue alarm signals or issue tripping command. The high
setting of earth resistance is used for alarm and the low setting is for tripping. The operation
equation for tripping (the below first equation) and alarming (second equation) are shown as
below:
Where:
The same measuring principle can also be used with a primary loading resistor. The 20Hz voltage
is connected in this case via a voltage transformer, and the neutral point current is directly
measured.
From the two measured quantities USEF and ISEF in Figure 3.4-23, the 20 Hz current and voltage
vectors are calculated, and from the resulting complex impedance the ohmic fault resistance is
determined. This method eliminates disturbances caused by the stator earth capacitance, and
ensures a high sensitivity. The measuring accuracy is further increased by using mean current
and voltage values obtained over several cycles for calculating the resistance.
The model takes into account a transfer resistance RPS that may be present at the neutral,
earthing or voltage transformer. Other error factors are taken into account in the angle error.
In addition to the determination of the earth resistance, the protection function features an earth
current stage which processes the current R.M.S. value and thus takes into account all
frequencies especially fundamental element. It is used as a backup stage and covers approx. 80
to 90 % of the protection zone.
The great advantage of this element is that more close to the terminal of generator the fault point
locates, more high sensitivity the element can get, which can realize 100% stator earth fault
protection cooperated with the earth resistance element. The following equation is executived by
the protection.
I E < I Eset
(Equation 3.4-38)
Where:
I E is earth current of generator stator used in the element without being subjected to digital filter.
A monitoring circuit checks the coupled external 20 Hz voltage and the 20 Hz curren and detects
by evaluating them a failure of the 20 Hz generator or of the 20 Hz connection. In case of a failure,
the resistance determination is blocked. The earth current stage remains active. The equation
shown as below is used for issuing external voltage circuit alarm signals if satisfied:
U 20 < U 20 set
I 20 < I 20 set (Equation 3.4-39)
Where:
The protection function has an alarm stage and a trip stage. Both stages can be delayed with a
timer. The earth current detection acts only on the trip stage. The evaluation of the earth
resistance measurement is blocked under 40 Hz, because in this frequency range a zero voltage
can also be generated by generators starting up or slowing down. Such a zero voltage would then
superimpose the connected 20 Hz voltage, causing measurement errors and overfunctioning.
The resistance measurement function is active with excitation unenergized (i.e. at standstill) and
frequency above 40 Hz. The earth current measurement is active over the entire range.
Figure 3.4-24 Logic diagram of the 100% voltage-injecting Stator Earth Fault Protection
RCS-985U is low frequency power source for injecting current to stator windings of generator,
please refer to the manual developed by our company for details.
If one-point earth fault of rotor occurs, insulation resistance between rotor winding and the axis
will drop down.
Rotor earth fault protection measures earthing resistance Rg of the winding by calculting the leak
current in two different cases of square wave voltage injection, as shown in Figure 3.4-25 and
Figure 3.4-26, earthing resistance Rg and location of the earthing point “Δ α “ can be found by
calculation.
There are two stages equipped for one-point earth protection: sensitive stage and regular stage.
Sensitive stage is used for alarm and regular stage for tripping or alarm.
U r+ Ry
Us
Rg
Rx
αU
U r− Ry
Figure 3.4-25 Measurement of earth resistance with injection at both terminals of rotor
Ur +
Us
Rg Rx
XUR
αU
Ry
Ur − Ry
Figure 3.4-26 Measurement of earth resistance with injection at single terminal of rotor
3.4.12.2 Ping-pang type (Switch-over sampling) rotor one point earth fault protection
If one-point earth fault of rotor occurs, insulation resistance between rotor winding and the axis
will drop down.
Rotor earth fault protection measures earthing resistance Rg of the winding by an unbalance
bridge as shown in Figure 3.4-27. Corresponding equations can be got by switching over S1 and
S2 alternately, and earthing resistance Rg and location of the earthing point “ α “ can be found by
calculation.
There are two stages equipped for one-point earth protection: sensitive stage and regular stage.
Sensitive stage is used for alarm and regular stage for tripping or alarm.
U
+ aU -
rotor
R Rg R
S1 S2 R
R
If one-point earth protection is used for alarm only, when earth resistance Rg is less than setting
of its regular stage [R_1PEF_RotWdg], it will switch over two-point ground protection program by
a delay automatically. If the location of the earthing point varies and the variation reaches its
setting value (fixed value 3%), two points earth fault protection will operate and issue a tripping
command. In order to improve the reliability, the two point earth fault protection can be blocked by
setting [En_VCE_2PEF_RotWdg] as “1”. Figure 3.4-28 and Figure 3.4-29 show logic diagram of
one point and two point earth fault protection of rotor.
Rg < [R_Sens_1PEF_RotWdg]
[Alm_Sens_1PEF_RotWdg]
[En_Alm_Sens_1PEF_RotWdg]
&
[En_Alm_1PEF_RotWdg]
[Alm_1PEF_RotWdg]
[Rg <[R_1PEF_RotWdg] & t
&
[En_EF_RotWdg]
Figure 3.4-28 Logic diagram of Ping-Pang type one-point earth fault protection of rotor
t
[Flag_1PEF_RotWdg]
? a>3% &
[En_EF_RotWdg]
[Flg_V2ndH_VCE_2PEF_RotWdg]
=1 & t [Op_2PEF_RotWdg]
[En_VCE_2PEF_RotWdg]
[t_2PEF_RotWdg]
[En_2PEF_RotWdg]
[EBI_EF_RotWdg]
[FD_EF_Rotor]
Figure 3.4-29 Logic diagram of Ping_Pang type two-points earth fault protection of rotor
There are two stages equipped with definite time stator overload protection: one for alarm and
another for tripping. Figure 3.4-31 shows its logic diagram.
Inverse time stator overload protection consists of three parts: low setting initiator, inverse time
part and upper limit definite time part.
Inverse time part can simulates generator-heating process including heat accumulation and
dissipation. When stator current reaches its low setting I SZD , inverse time part initiates and the
heat is accumulated. When the stator current is lower than rated value, the heat accumulation will
decrease accordingly.
Figure 3.4-30 shows the inverse time curve. In the figure, t min is delay of upper limit of inverse
I
Ih
Iszd
t min t max
[( I I ezd) − (K srzd ) ] × t ≥ KS zd
2 2
(Equation 3.4-40)
Where:
Figure 3.4-32 shows logic diagram of inverse time stator overload protection.
I>[I_Alm_OvLd_Sta]
t [Alm_OvLd_Sta]
&
[En_OvLd_Sta]
I>[I_OvLd_Sta]
&
[En_OvLd_Sta] t [Op_OvLd_Sta]
&
[TrpLog_OvLd_Sta].bit0
&
[EBI_Ovld_Sta]
[FD_Ovld_Sta]
I > [I_InvOvLd_Sta]
&
&
[En_OvLd_Sta] tmin
& [Op_InvOvLd_Sta]
[TrpLog_InvOvLd_Sta].bit0
&
[EBI_EF_Sta]
[FD_InvOvLd_Sta]
Negative sequence overload reflects overheating on surface of the rotor and other abnormality
due to negative sequence current. This protection takes negative sequence current at generator
terminal and neutral point as its criterion.
There are two stages equipped with definite time negative sequence overload protection: one for
alarm and the other for tripping. Figure 3.4-35 shows its logic diagram.
Inverse time negative sequence protection consists of three parts: low setting initiator, inverse
time part and upper limit definite time part.
Inverse time part can simulate generator-heating process including heat accumulation and
dissipation. When negative sequence current reaches its low setting [I_InvNegOC_Gen], inverse
time part initiates and the heat is accumulated. When the stator current is lower than permissive
continuous negative sequence current [I_Neg_Perm_Gen], the heat accumulation will decrease
accordingly.
[( I 2 I ezd) − (I 21 ) ] × t ≥ A
2 2
(Equation 3.4-41)
Where:
Figure 3.4-33 shows the inverse time curve. In the figure, t min ([tmin_InvNegOC_Gen]) is delay of
upper limit of inverse time curve and I 2 SZD ([I_InvNegOC_Gen]) is setting of the inverse time
I2zd
t min t max
Figure 3.4-33 Operation curve of inverse time negative sequence overload protection of generator
[En_NegOC_Gen]
t [Alm_NegOC_Gen]
&
I2>[I_Alm_NegOC_Gen]
[t_Alm_NegOC_Gen]
I2>[I_NegOC_Gen]
&
[En_NegOC_Gen] t
& [Op_NegOC_Gen]
[TrpLog_NegOC_Gen].bit0 [t_NegOCn_Gen]
&
[EBI_NegOC_Gen]
[FD_NegOC_Gen]
Figure 3.4-34 Logic diagram of definite time negative sequence overload protection
I >[I_InvNegOC_Gen]
& &
[En_NegOC_Gen] t min
& [Op_InvNegOC_Gen]
[TrpLog_InvNegOC_Gen].bit0
[EBI_InvNegOC_Gen] &
[FD_InvNegOC_Gen]
Figure 3.4-35 Logic diagram of inverse time negative sequence overload protection
Loss of excitation represents abnormal operation of generator due to excitation failure. There
are four criterion used for loss-of-excitation protection: under voltage, stator side impedance, rotor
side undervoltage/excitation voltage and power output reduction.
Three phase voltages on bus generally and those at generator terminal sometimes are taken as
this criterion. Criterion of simultaneous three phases under voltage is
U pp < U lezd
(Equation 3.4-42)
Where:
When bus voltage is taken as the criterion, if bus VT circuit fails, the protection will be blocked.
When generator terminal voltage is taken as the criterion, if one group of VT circuit fails, the other
group of VT will be switched over automatically.
This criterion is impedance circle including asynchronous impedance circle and steady state
stabilization limit circle. The operation criterion is
Z + jX B
270° ≥ Arg ≥ 90°
Z − jX A (Equation 3.4-43)
Where:
X A can be set as the system impedance Xs for steady state stabilization limit circle and
X B is taken as Xd + 1/2X ' for round rotor generator and (X + X )/2 + X ' /2 for salient
d d q d
pole generator.
The impedance criterion can be combined with reverse reactive power criterion, i.e.,
Q < [Q_RevQ_LossExc_Gen].
Figure 3.4-36 (a) and (b) show operation characteristics of steady state stabilization impedance
relay and asynchronous impedance relay, where the hatched area is operating area, and the
dotted line is operation limit of reverse reactive power.
jx jx
Z1
R Z1
R
-Qzd -Qzd
Z2 Z2
a) b)
(a) (b)
Besides operation criterion mentioned above, there are also auxiliary operation criterion, namely:
Negative sequence voltage U2 is lower than 0.1 Un (rated voltage of generator); and
Where:
Ur is exciting voltage.
Xs is equivalent reactance on system side connected with the generator (per unit value);
U f0
is rated voltage of exciter during generator without load;
K r is reliability coefficient.
If Ur drops to zero or minus value suddenly during loss of excitation, the rotor under voltage
criterion will be met quickly before steady state stability limit of the generator reaches. If Ur drops
to zero or reduces to a value gradually during loss of excitation, the variable excitation voltage
criterion will be reached. Excitation under voltage or loss of excitation will cause out-of-step, and
then excitation voltage and output power of the generator will swing seriously. In this case, the
rotor under voltage criterion and the variable excitation voltage criterion will be met and withdrawn
periodically in general. So the excitation voltage element will revert with delay during out-of-step
condition while the impedance entering the steady state stability limit circle.
When out-of-step occurs during loss of excitation, power output of generator will swing within a
certain range. P represents average power output within an oscillation period. Pzd is the setting
[P_OvPwr_LossExc_Gen].
Three stages are equipped with loss-of-excitation protection: stage 1 is used for reduction of
power output and alarm, stage 2 (with bus undervoltage criterion) is used for tripping, stage 3 is
used for tripping with long delay.
Figure 3.4-37 shows logic diagram of stage 1 of loss-of-excitation protection. If excitation is lost,
this stage will be used to reduce power output to a pre-set level and issue alarm.
Z + jX B
270 ° ≥ Arg ≥ 90 °
Z − jX A
Figure 3.4-38 shows logic diagram of stage 2 of loss of excitation protection. If excitation is lost
and voltage on HV side bus of main transformer is lower than its setting, this stage will trip with
delay. In configuring this stage, considering of security, it is strongly recommended that
impedance criterion should be used as well as busbar criterion rather than the model that only
busbar undervoltage criterion and rotor undervoltage criterion are used.
Upp<[V_BusUV_LossExc_Gen
&
[En_BusUV_LossExc2_Gen] ≥1
Ur<[V_RotUV_LossExc_Gen]
≥1
&
Ur < Kr × Xdz × Sn × Uf0
≥1 Op_LossExc2_Gen
t
&
[En_RotUV_LossExc2_Gen]
Z + jX
270 ° ≥ Arg B
≥ 90 ° &
Z − jX
&
A
≥1
[En_Z_LossExc2_Gen]
Q>[Q_RevQ_LossExc_Gen]
&
[En_RevQ_LossExc_Gen]
[En_LossExc_Gen]
[EBI_LossEXC_Gen]
[TrpLog_LossExc2_Gen].bit 0
[FD_LossExc_Gen]
Figure 3.4-39 shows logic diagram of stage 3 of loss of excitation protection. It is used for
switching over backup excitation or for tripping. It is also used for tripping with long delay in case
that all measures taken by the formers stages, such as power output reduction and switching over
backup excitation, have no effects on the more and more worse system.
Ur<[V_RotUV_LossExc_Gen]
≥1
Ur < Kr × Xdz × Sn × Uf0 &
≥1
[En_RotUV_LossExc3_Gen]
Z + jX
270 ° ≥ Arg B
≥ 90 °
Z − jX A & &
[En_Z_LossExc3_Gen] t Op_LossExc3_Gen
≥1 &
Q>[Q_RevQ_LossExc_Gen]
&
[En_RevQ_LossExc_Gen]
[En_LossExc_Gen]
[EBI_LossEXC_Gen]
[TrpLog_LossExc3_Gen].bit 0
[FD_LossExc_Gen]
Out-of step represents asynchronous operation of generator due to out-of-step. Figure 3.4-40
shows operation characteristic of this protection that comprises three parts: lens part, boundary
part and reactance line part.
jx
Za
U
D Zc
OL
IL 3
2
1 IR 1
OR
0
R
L R
Zb
In Figure 3.4-40, lens ① divides impedance plane into inside part I and outside part O, boundary
② divides the impedance plane into left part L and right part R, and reactance line ③ divides the
impedance plane into upper part U and lower part D.
Considering lens ① and boundary ② comprehensively, the impedance plane is divided into four
areas: OL, IL, IR and OR. If trace of impedance is passing through these four areas in sequence
from right to left or vice versa, and staying in each area for a moment longer than the setting, this
case is considered as system swing. Times of the passing through are accumulated and the
grand total is considered as the times of pole sliding. When the grand total reaches its setting
value, out-of-step protection operates.
As to reactance line ③, if the impedance trace passes through the upper part U, the swing center
is considered outside the generator; if the trace passes through the lower part D, the swing center
is considered within the generator. Settings of times of pole sliding can be configured separately
for these two cases.
Out-of-step protection can be used either for alarm only or tripping. Minimum swing period which
can be identified by this protection is 120 ms.
Upp.max<[V_UV_Gen] &
&
& t Op_UV_Gen
[En_VoltProt_Gen]
[t_UV_Gen]
[TrpLog_UV_Gen].bit0
[EBI_VoltProt_Gen]
[FD_UV_Gen]
Upp>[V_OVn_Gen]
&
[En_VoltProt_Gen] &
& t Op_OVn_Gen
[TrpLog_OVn_Gen].bit0 [t_OVn_Gen]
[EBI_VoltProt_Gen]
[FD_OV_Gen]
[BI_SyncCondenser]
Upp.max<[V_UV_Gen] &
&
& t Op_UV_Gen
[En_VoltProt_Gen]
[t_UV_Gen]
[TrpLog_UV_Gen].bit0
[EBI_VoltProt_Gen]
[FD_UV_Gen]
Two stages for tripping and one stage for alarm are equipped for definite over excitation
protection. Their time delay can be configured.
n = U pu / Fpu
(Equation 3.4-44)
U pu Fpu
Where and are per unit value of voltage and frequency respectively.
Figure 3.4-45 shows logic diagram of definite time over excitation protection.
Inverse time over excitation protection realizes inverse time characteristic by linear processing on
given inverse time operation characteristic, obtaining multiple of over excitation by calculation,
and getting corresponding operation delay by sectional linear insertion. It reflects heat
accumulation and radiation.
Figure 3.4-45 shows inverse time operation characteristics of over excitation protection. It can be
specified by 8 over excitation multiple settings n0 – n7.
U/F
n0
n1
n2
n3
n4
n5
n6
n7
t0 t1 t2 t3 t4 t5 t6 t(s) t7
The over excitation multiple settings n (= U/F) are within range of 1.0 – 1.5 in general. Maximum
time delay t is considered as long as 3000 s. Relation between various settings of n and t are:
n0 ≥ n1 ≥ n2 ≥ n3 ≥ n4 ≥ n5 ≥ n6 ≥ n7
t0 ≤ t1 ≤ t2 ≤ t3 ≤ t4 ≤ t5 ≤ t6 ≤ t7
Figure 3.4-46 shows logic diagram of inverse time over excitation protection.
[En_OvExc_Gen]
t Alm_OvExc_Gen
&
U/F > [k_Alm_OvExc_Gen] [t_Alm_OvExc_Gen]
[FD_OvExc_Gen]
[TrpLog_InvOvExc_Gen].bit0
&
[EBI_OvExc_Gen]
[FD_OvExc_Gen]
Reverse power protection can prevent turbine blades or gears from damage in the case that the
generator transforms into a motor mode and flows reverse power due to loss of its motive force.
P ≤ - [P_RevP_Gen]
(Equation 3.4-45)
Where
P is the power calculated from three phase voltages and currents at terminal of generator.
One stage for tripping and another stage for alarm with independent delay setting respectively are
equipped with this protection.
Range of reverse power setting is 0.5% - 10% Pn, where Pn is rated active power of the generator.
Range of delay is 0.1 s – 600 s.
One stage of underpower protection is equipped for tripping. It is blocked by the binary input for
emergency shutoff generator [BI_UrgBrake].
Four stages of underfrequency protection are equipped for RCS-985B. Stage 1 is usually
configured as accumulating frequency protection, and can be reset to zero only after erasing
reports. Stages 2, 3 and 4 can be configured as continuous frequency protection.
As to over frequency protection, two stages are equipped for RCS-985B and they will issue alarm
or trip when operates.
In the course of generator’s hand turning (low frequency condition), if it has been excited, breaker
closure by accident may lead to asynchronous starting of the generator. The protection is put into
use automatically with time delay t1 when two groups of voltage derived from two independent
VTs are all less than undervoltage setting and exit with time delay t2 (designed to cooperate with
low-frequency blocking criterion) when the two groups of voltage revert to normal level.
In the case that generator breaker is closed by accident in excited condition but frequency is
under normal level which may occur in startup-and-shutdown process. The protection is put into
use automatically with time delay t3 while Low Frequency criterion is met and returns with time
delay t4 after the frequency criteria releases. Here, t4 should be set as long as to ensure the
completion of tripping course.
Considering security of the protection, both currents from generator terminal and neutral point are
used in the logic as
criteria.
protection is provided for this fault. One phase and two phases flashover is considered by this
protection but three phase flashover are ignored.
Excitation has been applied to generator, and generator voltage is greater than setting.
Operation of this protection will shut off excitation and activating circuit breaker failure protection.
Where:
[Flg_OC_Term_Gen] is the flag indicating whether or not the overcurrent current element of
[Flg_OC_NeuP_Gen] is the flag indicating whether or not the overcurrent current element of
generator neutral point operates.
[Flg_UV_Gen] is the flag indicating whether or not the undervoltage element of generator
operates.
Where:
Protections for phase-to-phase fault and stator earth fault are provided during startup and
shutdown process of generator.
Differential overcurrent protections are provided for faults of generator and main transformer
respectively. A zero sequence overvoltage protection is provided for stator earth fault.
Since frequency during startup and shutdown process is usually very low, algorithm independent
of frequency is used for this protection.
Whether the protection should be blocked or not by frequency element or auxiliary contact of
circuit breaker can be determined by logic setting.
Where:
“xx” represent one of the three protective elements, “GenDiff” and “StaROV”. The three protective
elements’ diagrams are so likely that they can be expressed in a figure instead of three for them
respectively.
Excitation winding protection comprises definite time and inverse time protection.
One stage of alarm and one stage of tripping are equipped for definite time excitation winding
overload protection.
Figure 3.4-54 shows logic diagram of definite time excitation winding overload protection.
Inverse time excitation winding overload protection consists of three parts: low setting initiator,
inverse time part and high setting definite part. Minimum operation time delay
([tmin_InvOvLd_RotWdg]) is provided for extreme overload condition.
When current in excitation circuit reaches the low setting [Ib_InvOvLd_RotWdg], the heating
accumulation starts. When the heating accumulation reaches its setting, alarm will be issued. The
inverse time protection can simulate heating accumulation and radiation process.
Il
Ilh
Ilszd
t min t max t
Figure 3.4-53 Operation characteristic of inverse time overload protection of excitation winding
In the figure, I l is the current in excitation circuit, I lh is the high setting of the protection; I lsZD
[tmin_InvOvLd_RotWdg] .
[( I l I jzzd) − 1] × t ≥ KLzd
2
(Equation 3.4-46)
Where:
Figure 3.4-55 shows logic diagram of inverse time excitation winding overload protection.
I>[I_Alm_OvLd_RotWdg]
& t
[En_OvLd_RotWdg] [Alm_OvLd_RotWdg]
I>[I_OvLd_RotWdg]
&
[En_OvLd_RotWdg] t
& [Op_OvLd_RotWdg]
[TrpLog_OvLd_RotWdg].bit0
[EBI_OvLd_RotWdg] &
[FD_OvLd_RotWdg]
Figure 3.4-54 Logic diagram of definite time excitation winding overload protection
I>[I_InvOvLd_RotWdg]
& &
[En_OvLd_RotWdg]
tmin [Op_InvOvLd_RotWdg]
[TrpLog_InvOvLd_RotWdg].bit0 &
[EBI_OvLd_RotWdg] &
[FD_OvLd_RotWdg]
Figure 3.4-55 Logic diagram of inverse time excitation winding overload protection
The criterion is the same to Equation 3.3-8 except the differential current and restraint current.
Here:
For excitation transformer: I1 and I 2 are currents of HV side and LV side respectively.
The differential protection of exciter can adopt the two kinds of frequency: 50Hz and 100Hz
according the setting [fn_Exciter].
Two stages overcurrent protection are equipped for excitation transformer or exciter overcurrent
protection as backup protection. These two stages will trip the circuit breaker with configurable
delay. Figure 3.4-56 shows its logic diagram.
[TrpLog_OC n_Exc].bit0
[FD_Bak_Exc]
Function of voltage controlled overcurrent protection for stepdown transformer is equipped with
RCS-985B. This protection, consisting of 2 stages and 1 time delay per stage, is used for
phase-to-phase backup protection of stepdown transformer. Of which, function of composite
voltage element can be enabled or disabled by configuration of logic setting.
This protection, consisting of 2 stages and 1 time delay per stage, is used for phase-to-phase
backup protection of stepdown transformer. Of which, function of composite voltage element can
be enabled or disabled by configuration of logic setting.
Two stages zero sequence current protection with delay used for tripping is equipped for LV side
of stepdown transformer.
Overload alarm and initial cooling are equipped for backup protection of stepdown transformer.
These functions can be set by logic settings. One normally open contact is used for output of
initial cooling.
Binary output of overcurrent for OLTC(On load tap change) of stepdown transformer is equipped
in RCS-985B.
Where:
If this criterion is met, CT circuit failure alarm will be issued with 10s delay. Once the condition
reverts normal condition, the alarm will be reset with 10s delay.
This function is enabled only when relevant differential protection logic setting is set as enabled.
If the criterion is met, the alarm will be sent by delay 10 s and corresponding differential protection
will not be blocked. When the differential current eliminates, the alarm will be reset by delay 10
s.
In order to increase sensitivity of this alarm, percentage restraint differential current alarm criterion
is adopted as shown as below.
I d > I dbjzd
I d > k bj × I res (Equation 3.4-49)
If the differential current reaches its threshold and reaches differential alarm level of percentage
restraint factor multiplied by restraint current, the differential current alarm will be issued.
If internal fault occurs, at least one of following four conditions will be present:
Any phase current of a certain side increases after fault detector picks up;
If none of above four conditions occurs within 40 ms after differential protection’s fault detectors
picks up, the protection treats it as CT circuit failure. If the logic setting
[Opt_CTS_Blk_PcntDiff_Gen] is set as “1”, the differential protection will be blocked and alarm will
be issued. If this logic setting is set as “0”, the differential protection will trip and alarm will be
issued simultaneously.
If the alarm is issued, the signal can be removed only when the failure is removed and the
equipment is reset by manual.
Positive sequence voltage is greater than 30 V and any phase current is greater than 0.04 In;
If any one condition occurs, VT circuit failure alarm will be issued with delay 10 s, and the alarm
will be removed automatically by delay 10 s when the failure is removed.
Two groups of VT are equipped at generator terminal. VT circuit failure can be detected by
comparison of phase voltage and positive sequence voltage of these two groups of VT.
U AB1 - U AB 2 > 5 V ;
U BC1 - U BC 2 > 5 V ;
U CA1 - U CA 2 > 5 V ; (Equation 3.4-50)
U 11 - U12 > 3 V ;
Where:
UAB1, UBC1, UCA1 and U11 are phase-to-phase voltage and positive sequence voltage of VT
group 1;
UAB2, UBC2, UCA2 and U12 are phase-to-phase voltage and positive sequence voltage of VT
group 2.
If any condition mentioned above occurs, VT circuit failure alarm will be issued with delay 0.2 s
and the VT group used will be switched over.
When only a VT fails, it will not influence the function of related protection such as
loss-of-excitation, out-of-step, overvoltage, over-excitation, reverse power, frequency, impedance
protection and overcurrent protection.
If only one group of VT is provided at generator’s terminal, user can set this function as “disable”.
4.1 Self-supervision
If hardware failure of the equipment itself is detected, protection functions of the equipment will be
blocked and equipment blocking alarm will be issued. Hardware failure includes those on RAM,
EPROM, settings, power supply, DSP and tripping coil.
When following abnormal status is detected, abnormal warning will be issued: AC voltage or
current circuit failure, persist pickup, mismatch state of pickup between CPU and DSP and alarm
of protection element.
The relay includes a number of self-monitoring functions to check the operation of its hardware
and software when it is in service. These are included so that if an error or fault occurs within the
relay’s hardware or software, the relay is able to detect and report the problem and attempt to
resolve it by performing a re-boot. This involves the relay being out of service for a short period of
time that is indicated by the ‘Healthy’ LED on the faceplate of the relay being extinguished and the
watchdog contact at the rear operating. If the restart fails to resolve the problem, then the relay will
take itself permanently out of service. Again this will be indicated by the ‘ALARM’ LED and
watchdog contact. If a problem is detected by the self-monitoring functions, the relay attempts to
store a maintenance record in battery backed-up SRAM to allow the nature of the problem to be
notified to the user.
The self-monitoring is implemented in two stages: firstly a thorough diagnostic check which is
performed when the relay is booted-up, e.g. at power-on, and secondly a continuous self-checking
operation which checks the operation of the relay’s critical functions whilst it is in service.
The self-testing which is carried out when the relay is started takes a few seconds to complete,
during which time the relay’s protection is unavailable. This is signaled by the ‘Healthy’ LED on the
front of the relay which will illuminate when the relay has passed all of the tests and entered
operation. If the testing detects a problem, the relay will remain out of service until it is manually
restored to working order.
The integrity of the flash memory is verified using a checksum before the program code and data
stored in it is copied into SRAM to be used for execution by the processor. When the copy has
been completed the data then held in SRAM is compared to that in the flash to ensure that the two
are the same and that no errors have occurred in the transfer of data from flash to SRAM. The
entry point of the software code in SRAM is then called which is the relay initialization code.
The initialization process includes the operations of initializing the processor registers and
NANJING NARI-RELAYS ELECTRIC CO., LTD 109
Chapter4 Self-supervision, metering and records
interrupts, starting the watchdog timers (used by the hardware to determine whether the software
is still running), starting the real-time operating system and creating and starting the supervisor
task. In the course of the initialization process the relay checks:
• The integrity of the battery backed-up SRAM that is used to store event, fault and disturbance
records.
• The correctness of the settings that ensures relay’s proper response to fault.
• The voltage level of the field voltage supply which is used to drive the opto-isolated inputs.
At the conclusion of the initialization software the supervisor task begins the process of starting the
platform software.
In starting the platform software, the relay checks the integrity of the data held in non-volatile
memory with a checksum. The final test that is made concerns the input and output of data, the
presence and healthy condition of the input board is checked and the analog data acquisition
system is checked through sampling the reference voltage.
At the successful conclusion of all of these tests the relay is entered into service and the protection
started-up.
• The flash containing all program code, setting values and language text is verified by a
checksum
• The code and constant data held in SRAM is checked against the corresponding data in flash to
check for data corruption
• The SRAM containing all data other than the code and constant data is verified with a checksum
• The integrity of the digital signal I/O data from the opto-isolated inputs and the relay contacts is
checked by the data acquisition function every time it is executed. The operation of the analog
data acquisition system is continuously checked by the acquisition function every time it is
executed, by means of sampling the reference voltages.
In the unlikely event that one of the checks detects an error within the relay’s subsystems, the
platform software is notified and it will attempt to log a maintenance record in battery backed-up
SRAM. If the problem is of no importance (no possibility of leading to maloperation), the relay will
continue in operation. However, for problems detected in any important area the relay will initiate a
shutdown and re-boot. This will result in a period of up to 5 seconds when the protection is
unavailable, but the complete restart of the relay including all initializations should clear most
problems that could occur. As described above, an integral part of the start-up procedure is a
thorough diagnostic self-check. If this detects the same problem that caused the relay to restart,
i.e. the restart has not cleared the problem, then the relay will take itself permanently out of service.
This is indicated by the ‘Healthy’ LED on the front of the relay, which will extinguish, and the
watchdog contact that will operate.
If the alarm is issued, the alarm signal can be reset only when the failure is removed and the
equipment is reset by pressing “RESET” button on panel or re-power it up.
• Overload Alarm
On condition that the relay does not picks up, adding current in excess of the setting of overload
protection, alarm messages are displayed and ALARM LED is lit after the timer stage duration
has elapsed.
Tripping output relay driving transistor is always monitored in normal program, and blocking
message will be issued when the equipment finds abnormality of the tripping output circuit.
Alm_CTS_HVS1_Tr Note J
18. Note 18 ● ● ●
Alm_CTS_HVS2_Tr Note J
19. Note 19 ● ● ●
Alm_CTS_Term_Gen Note J
20. Note 20 ● ● ●
Alm_CTS_NP_Gen Note J
21. Note 21 ● ● ●
Alm_CTS_Bak_Gen Note J
22. Note 22 ● ● ●
Alm_CTS_S1_Exc Note J
23. Note 23 ● ● ●
Alm_CTS_S2_Exc Note J
24. Note 24 ● ● ●
Alm_Diff_Gen Note J
25. Note 25 ● ●
Alm_Diff_Exc Note J
26. Note 26 ● ●
Alm_DPFC_IntTurn_Gen Note E
27. Note 27 ● ●
Alm_MechRly1 Note E
28. Note 28 ● ●
Alm_MechRly2 Note E
29. Note 29 ● ●
Alm_MechRly3 Note E
30. Note 30 ● ●
Alm_MechRly4 Note E
31. Note 31 ● ●
Alm_PwrLoss_MechRly Note D
32. Note 32 ● ●
Alm_Inconsist_MechRly Note D
33. Note 33 ● ●
Alm_CTS_Diff_Gen Note K
34. Note 34 ● ●
Alm_CTS_Diff_Exc Note K
35. Note 35 ● ●
Alm_BO_OC_Term_Gen Note E
36. Note 36 ● ●
Alm_On_2PEF_RotWdg Note E
37. Note 37 ● ●
Alm_Ext_OOS_Gen Note E
38. Note 38 ● ●
Alm_Int_OOS_Gen Note E
39. Note 39 ● ●
Alm_Accel_OOS_Gen Note E
40. Note 40 ● ●
Alm_Decel_OOS_Gen Note E
41. Note 41 ● ●
Alm_LossExc_Gen Note E
42. Note 42 ● ●
Alm_OvExc_Gen Note E
43. Note 43 ● ●
Alm_OvLd_Sta Note E
44. Note 44 ● ●
Alm_NegOC_Gen Note E
45. Note 45 ● ●
Alm_OvLd_RotWdg Note E
46. Note 46 ● ●
Alm_ROV_Sta Note E
47. Note 47 ● ●
Alm_V3rdHRatio_Sta Note E
48. Note 48 ● ●
Alm_V3rdHDiff_Sta Note E
49. Note 49 ● ●
Alm_SensInjEF_Sta Note E
50. Note 50 ● ●
Alm_Pwr_Inj_EF_Sta Note E
51. Note 51 ● ●
Alm_Sens1PEF_RotWdg Note E
52. Note 52 ● ●
Alm_1PEF_RotWdg Note E
53. Note 53 ● ●
Alm_UF1_Gen Note E
54. Note 54 ● ●
Alm_UF2_Gen Note E
55. Note 55 ● ●
Alm_UF3_Gen Note E
56. Note 56 ● ●
Alm_OF1_Gen Note E
57. Note 57 ● ●
Alm_OF2_Gen Note E
58. Note 58 ● ●
Alm_RevP_Gen Note E
59. Note 59 ● ●
Alm_VTS_Term_Gen Note J
60. Note 60 ● ● ●
Alm_VTS_HVS_Tr Note J
61. Note 61 ● ● ●
Alm_VTS_LVS_ST Note J
62. Note 62 ● ● ●
Alm_VTS_Br1_ST1 Note L
63. Note 63 ● ● ●
Alm_VTS_Br2_ST1 Note J
64. Note 64 ● ● ●
Alm_VTS_Br1_ST2 Note J
65. Note 65 ● ● ●
Alm_VTS_Br2_ST2 Note J
66. Note 66 ● ● ●
Alm_BO_OC_HVS_ST1 Note J
67. Note 67 ● ●
Alm_BO_OC_HVS_ST2 Note J
68. Note 68 ● ●
Alm_OvLd_Tr Note E
69. Note 69 ● ●
Alm_InitCool1_OvLd_Tr Note E
70. Note 70 ● ●
Alm_OvLd_ST1 Note E
71. Note 71 ● ●
Alm_InitCool_OvLd_ST1 Note E
72. Note 72 ● ●
Alm_OvLd_ST2 Note E
73. Note 73 ● ●
Alm_InitCool_OvLd_ST2 Note E
74. Note 74 ● ●
Alm_InitCool2_OvLd_Tr Note E
75. Note 75 ● ●
Alm_PM_DSP2_CPUBrd Note A
76. Note 76 ●
Alm_CTS_HVS1_Tr Note J
77. Note 77 ● ● ●
Alm_CTS_HVS2_Tr Note J
78. Note 78 ● ● ●
Alm_CTS_LVS_Tr Note J
79. Note 79 ● ● ●
Alm_CTS_HVS_Tr Note J
80. Note 80 ● ● ●
Alm_CTS_HVS_ST1 Note J
81. Note 81 ● ● ●
Alm_CTS_Br1_ST1 Note J
82. Note 82 ● ● ●
Alm_REF_ST1 Note J
83. Note 83 ● ●
Alm_CTS_HVS_ST2 Note J
84. Note 84 ● ● ●
Alm_CTS_Br1_ST2 Note J
85. Note 85 ● ● ●
Alm_REF_ST2 Note J
86. Note 86 ● ●
Alm_Diff_GTU Note J
87. Note 87 ● ●
Alm_Diff_Tr Note J
88. Note 88 ● ●
Alm_Diff_ST1 Note J
89. Note 89 ● ●
Alm_Diff_ST2 Note J
90. Note 90 ● ●
Alm_REF_Tr Note K
91. Note 91 ● ●
Alm_CTS_Diff_GTU Note K
92. Note 92 ● ● ●
Alm_CTS_Diff_Tr Note K
93. Note 93 ● ● ●
Alm_CTS_Diff_ST1 Note K
94. Note 94 ● ● ●
Alm_CTS_Diff_ST2 Note K
95. Note 95 ● ● ●
Alm_OvExc_Tr Note E
96. Note 96 ● ●
Alm_ROV_LVS_Tr Note E
97. Note 97 ● ●
Alm_RAM_CPUBrd Note A
98. Note 98 ●
Alm_ROM_CPUBrd Note A
99. Note 99 ●
Alm_EEPROM_CPUBrd Note A
100. Note 100 ●
Alm_InvalidSetting Note B
101. Note 101 ●
Alm_ModifiedSetting Note C
102. Note 102 ●
Alm_PwrLoss_Opto Note D
103. Note 103 ●
Alm_TripOutput Note A
104. Note 104 ●
Alm_InnerComm Note F
105. Note 105 ● ●
Alm_DSP_CPUBrd Note A
106. Note 106 ●
Alm_PersistFD_CPUBrd Note H
107. Note 107 ● ●
Alm_InconsistFD Note G
108. Note 108 ● ●
Alm_Sample_CPUBrd Note A
109. Note 109 ●
Alm_BI_CPUBrd Note A
110. Note 110 ● ●
Alm_Reboot_CPUBrd Note C
111. Note 111 ●
Alm_RAM_MONBrd Note A
112. Note 112 ●
Alm_ROM_MONBrd Note A
113. Note 113 ●
Alm_EEPROM_MONBrd Note A
114. Note 114 ●
Alm_DSP_MONBrd Note A
115. Note 115 ●
Alm_PersistFD_MONBrd Note H
116. Note 116 ● ●
Alm_MONBrd Note A
117. Note 117 ● ●
Alm_Sample_MONBrd Note A
118. Note 118 ●
Alm_Reboot_CPUBrd Note C
119. Note 119 ●
Note:
Note 1 Alarm indicating VT1 circuit failure and start to switch over voltage circuit.
Note 2 Alarm indicating VT2 circuit failure and start to switch over voltage circuit.
Note 3 Alarm indicating VT1 circuit failure and blocking 3rd harmonics voltage differential
protection.
Note 4 Alarm indicating VT2 circuit failure and blocking interturn protection.
Note 5 Alarm indicating secondary circuit failure of VT at HV side of main transformer.
Note 6 Alarm indicating secondary circuit failure of VT1 at generator terminal.
Note 7 Alarm indicating secondary circuit failure of VT2 at generator terminal.
Note 8 Alarm indicating secondary circuit failure of VT at the neutral point of generator.
Note 9 Alarm indicating secondary circuit failure at open-delta side of VT1 at generator terminal.
Note 10 Alarm indicating secondary circuit failure at open-delta side of VT2 at generator
terminal.
Note 11 Alarm indicating secondary circuit failure of VT for rotor earth fault protection.
Note 12 Alarm indicating failure of injection source for rotor earth fault protection.
Note 13 Alarm indicating the position of circuit breaker at generator terminal is abnormal.
Note 14 Alarm indicating the position of circuit breaker of branch 1 at HV side of stepdown
transformer is abnormal.
Note 15 Alarm indicating the position of circuit breaker of branch 2 at HV side of stepdown
transformer is abnormal.
Note 16 Alarm indicating rotor voltage circuit failure which used by loss-of-excitation
protection.
Note 17 The DSP chip in CPU board damaged.
Note 18 Alarm indicating secondary circuit abnormality of CT at branch 1 of HV side of
transformer.
Note 19 Alarm indicating secondary circuit abnormality of CT at branch 2 of HV side of
transformer.
Note 20 Alarm indicating secondary circuit abnormality of CT at generator terminal.
Note 21 Alarm indicating secondary circuit abnormality of CT at the neutral point of
generator.
Note 22 Alarm indicating secondary circuit abnormality of CT at generator terminal for bak
overcurrent protection.
Note 23 Alarm indicating secondary circuit failure of CT at side1 of excitation set used in
differential protection of excitation.
Note 24 Alarm indicating secondary circuit failure of CT at side2 of excitation set used in
differential protection of excitation.
Note 25 Alarm indicating differential current of generator is in excess of normally endurable
level.
Note 26 Alarm indicating differential current of excitation transformer or exciter is in excess of
Note D Check if the power circuit of OPT module is connected correctly with DC module.
Note K Disable the link and check the secondary circuit. After clear the error, reset the relay.
4.2 Metering
The relay produces a variety of both directly and calculated power system quantities. These
measurement values are updated on a per half second basis and can be viewed in the menu
“VALUES” of the relay or via relay communication.
This relay is able to measure and display the following quantities as summarized:
The relay produces both phase-to-ground and phase-to-phase voltage and current values. They
are produced directly from the DFT (Discrete Fourier Transform) used by the relay protection
functions and present both magnitude and phase angle measurement.
Sequence quantities are produced by the relay from the measured Fourier values; these are
displayed as magnitude and phase angle values.
Rms. phase voltage and current values are calculated by the relay using the sum of the samples
squared over a cycle of sampled data.
Differential current and restrained current calculated in differential protection is displayed to user
for monitoring the correctness of operation or testing of the differential protection.
Note:
The quantities listed in following tables are to be displayed on LCD for RCS-985B,
but for a certain application, some of these quantities may be eliminated due of the
scheme user required, so please look up the devices on site for actual quantities
displayed.
4.2.7.1 Values of generator-transformer unit metering in CPU and MON
GTU METERING
Where:
Id_Diff_GTU Phase A,B and C of per unit value of generator-transformer unit (GTU)
differential current.
Ir_Diff_GTU Phase A,B and C of per unit value of GTU restraint current.
Icr_HVS1_GTU Corrected current of phase A, B and C at HV1 side of GTU.
Icr_HVS2_GTU Corrected current of phase A, B and C at HV2 side of GTU.
Access path in menu is “VALUESà CPU METERINGàGTU METERING” and “VALUESà MON
METERINGàGTU METERING”.
4.2.7.2 Differential currents and related values in transformer metering in CPU and MON
DIFF CURR
Id_Diff_Tr: 000.00 000.00 000.00 Ie
Ir_Diff_Tr: 000.00 000.00 000.00 Ie
Icr_HVS1_Tr: 000.00 000.00 000.00 Ie
Icr_HVS2_Tr: 000.00 000.00 000.00 Ie
Icr_LVS_Tr: 000.00 000.00 000.00 Ie
Icr_ST1_Tr: 000.00 000.00 000.00 Ie
Icr_ST2_Tr: 000.00 000.00 000.00 Ie
Figure 4.2-2 Differential currents and related values in transformer metering in CPU and MON
Where:
Access path in menu is “VALUESà CPU METERINGàTR METERINGà DIFF CURR” and
“VALUESà MON METERINGàTR METERINGà DIFF CURR”.
Note:
The contents inside the first window are the default display seen by user entering this submenu.
User can navigate to the following items by scrolling the arrow keys on the faceplate of the relay.
What user meets similar to this case later can be dealt with in same way.
TR CURR
I_HVS1_Tr: 000.00 000.00 000.00 A
I1_HVS1_Tr: 000.00 A
I2_HVS1_Tr: 000.00 A
I0_HVS1_Tr: 000.00 A
I_HVS2_Tr: 000.00 000.00 000.00 A
I1_HVS2_Tr: 000.00 A
I2_HVS2_Tr: 000.00 A
I0_HVS2_Tr: 000.00 A
Where:
HVS VOLT
U_HVS_Tr: 000.00 000.00 000.00 V
Upp_HVS_Tr: 000.00 000.00 000.00 V
U1_HVS_Tr: 000.00 V
U2_HVS_Tr: 000.00 V
U0_HVS_Tr: 000.00 V
U0_DeltVT_HVS_Tr: 000.00 V
U0_DeltVT_LVS_Tr: 000.00 V
U/F_OvExc_Tr: 00.000
Where:
Access path in menu is “VALUESà CPU METERINGàTR METERINGà HVS VOLT” and
“VALUESà MON METERINGàTR METERINGà HVS VOLT”.
Figure 4.2-5 Differential currents in stepdown transformer A metering in CPU and MON
Where:
Access path in menu is “VALUESà CPU METERINGàST METERINGà ST1 DIFF CURR” and
“VALUESà MON METERINGàST METERINGàST1 DIFF CURR”.
ST1 METERING
I_CT_HVS_ST1: 000.00 000.00 000.00 A
I1_CT_HVS_ST1: 000.00 A
I2_CT_HVS_ST1: 000.00 A
I0_CT_HVS_ST1: 000.00 A
I_CT#_HVS_ST1: 000.00 000.00 000.00 A
I1_CT#_HVS_ST1: 000.00 A
I2_CT#_HVS_ST1: 000.00 A
I0_CT#_HVS_ST1: 000.00 A
Figure 4.2-6 Currents at HV side of stepdown transformer metering in CPU and MON
Where:
Access path in menu is “VALUESà CPU METERINGàST METERINGà ST1 METERING” and
“VALUESà MON METERINGàST METERINGà ST1 METERING”.
Figure 4.2-7 Differential currents in stepdown transformer B metering in CPU and MON
Where:
Access path in menu is “VALUESà CPU METERINGàST METERINGà ST2 DIFF CURR” and
“VALUESà MON METERINGàST METERINGàST2 DIFF CURR”.
ST2 METERING
I_CT_HVS_ST2: 000.00 000.00 000.00 A
I1_CT_HVS_ST2: 000.00 A
I2_CT_HVS_ST2: 000.00 A
I0_CT_HVS_ST2: 000.00 A
I_CT#_HVS_ST2: 000.00 000.00 000.00 A
I1_CT#_HVS_ST2: 000.00 A
I2_CT#_HVS_ST2: 000.00 A
I0_CT#_HVS_ST2: 000.00 A
Where:
Access path in menu is “VALUESà CPU METERINGàST METERINGà ST2 METERING” and
“VALUESà MON METERINGàST METERINGà ST2 METERING”.
DIFF CURR
Id_Diff_Gen: 000.00 000.00 000.00 Ie
Ir_Diff_Gen: 000.00 000.00 000.00 Ie
I_Term_Gen: 000.00 000.00 000.00 A
I1_Term_Gen: 000.00 A
I2_Term_Gen: 000.00 A
I0_Term_Gen: 000.00 A
I_NP_Gen: 000.00 000.00 000.00 A
I1_NP_Gen: 000.00 A
Where:
Id_Diff_Gen Phase A,B and C of per unit value of generator differential current.
Ir_Diff_Gen Phase A,B and C of per unit value of generator restraint current.
I_Term_Gen Phase A,B and C of current derived from CT at generator’ terminal.
I1_Term_Gen Positive sequence current of generator terminal.
I2_Term_Gen Negative sequence current of generator terminal.
I0_Term_Gen Calculated zero sequence current of generator terminal.
I_NP_Gen Phase A,B and C of current derived from CT at generator’ neutral point.
I1_NP_Gen Positive sequence current of generator neutral point.
I2_NP_Gen Negative sequence current of generator neutral point.
I0_NP_Gen Calculated zero sequence current of generator neutral point.
I_Bak_Gen Phase A,B and C of current obtained from backup CT at generator’ terminal.
I1_Bak_Gen Positive sequence current of backup CT.
I2_Bak_Gen Negative sequence current of backup CT.
I0_Bak_Gen Calculated zero sequence current of backup CT.
Access path in menu is “VALUESà CPU METERINGàGEN METERINGà DIFF CURR” and
“VALUESà MON METERINGàGEN METERINGà DIFF CURR”.
TRVDIFF CURR
Id_TrvDiff_Gen: 000.00 A
Id_3rdH_TrvDiff_Gen: 000.00 A
Figure 4.2-10 Transverse differential current and related values in CPU and MON
Where:
Access path in menu is “VALUESà CPU METERINGà GEN METERING à DIFF CURR” and
“VALUESà MON METERINGà GEN METERING à DIFF CURR”.
VOLTAGE
Where:
terminal.
U1_VT1_Term Calculated positive sequence voltage of VT1.
U2_VT1_Term Calculated negative sequence voltage of VT1.
U0_VT1_Term Calculated zero sequence voltage of VT1.
U_VT2_Term Phase A, B and C of voltage derived from VT2 at the generator’s
terminal.
U1_VT2_Term Calculated positive sequence voltage of VT2.
U2_VT2_Term Calculated negative sequence voltage of VT2.
U0_VT2_Term Calculated zero sequence voltage of VT2.
Upp_VT1_Term Phase-to-phase voltage of VT1—Uab, Ubc, Uca.
Upp_VT2_Term Phase-to-phase voltage of VT2—Uab, Ubc, Uca.
U0_DeltVT1_Term Zero sequence voltage derived from open-delta side of VT1 at the
generator’s terminal.
U0_NP_Gen Zero sequence voltage derived from VT at the neutral point of
generator.
U0_3rdH_VT1_Term Calculated 3rd harmonics of VT1 at the generator’s terminal.
U0_3rdH_NP_Gen Calculated 3rd harmonics of VT at the neutral point of generator.
Ud_3rdH_Sta 3rd harmonics differential voltage between the terminal and the
neutral point of generator.
U0_Longl_Gen Longitude zero sequence voltage of generator.
U0_3rdH_Longl_Gen 3rd harmonics voltage in longitude zero voltage.
Access path in menu is “VALUESà CPU METERINGà GEN METERINGà VOLTAGE” and
VALUESà MON METERINGà GEN METERINGà VOLTAGE”.
Where:
4.2.7.13 Injection Stator earth fault Protion Metering in CPU and MON (Optional)
INJ METERING
U0_Gen: 000.00 V
I0_Gen: 000.00 A
U_Inj: 000.00 V
I_Inj: 000.00 mA
O
φui_Inj: 00.000
O
φui_Corr_Inj: 00.000
R_Sec: 000.00 Ω
X_Sec: 000.00 Ω
Where:
Access path in menu is “VALUESà CPU METERINGà GEN METERINGà INJ METERING” and
VALUESà MON METERINGà GEN METERINGà INJ METERING”.
DIFF CURR
Where:
Access path in menu is “VALUESà CPU METERINGà EXC METERING” and VALUESà MON
METERINGà EXC METERING”.
AC METERING
I_S1_Exc: 000.00 000.00 000.00 A
I1_S1_Exc: 000.00 A
I2_S1_Exc: 000.00 A
I0_S1_Exc: 000.00 A
I_S2_Exc: 000.00 000.00 000.00 A
I1_S2_Exc: 000.00 A
I2_S2_Exc: 000.00 A
I0_S2_Exc: 000.00 A
Where:
Access path in menu is “VALUESà CPU METERINGà EXC METERING” and VALUESà MON
METERINGà EXC METERING”.
TR PHASE ANGLE
o
φi_HVS_Tr_&_NP_Gen: 000 000 000
φi_ST1_&_NP_Gen: 000 000 000 o
o
φi_ST1_&_Term_Gen: 000 000 000
φi_ST2_&_Term_Gen: 000 000 000 o
Where:
Where:
Where:
o
Φv_VT1&_VT2_Gen: 000 000 000
o
φ_V3rdH_Gen: 000
o
φvi_Term_Gen: 000 000 000
Where:
Where:
4.3 Signaling
Signals here mean changes of binary inputs. All these signals can be displayed on LCD, locally
printed or sent to automation system of substation via communication channel.
TR PROT EBI
EBI_Diff_GTU: 0
EBI_Diff_Tr: 0
EBI_PPF_Tr: 0
EBI_EF_Tr: 0
EBI_REF_Tr: 0
Where:
Access path in menu is “VALUESà CPU BI STATE à TR PROT EBI” and “VALUESà MON BI
STATE à TR PROT EBI”.
EBI_Diff_Gen: 0
EBI_PPF_Gen: 0
EBI_IntTurn_Gen: 0
EBI_ROV_Sta: 0
EBI_V3rdH_Sta: 0
EBI_EF_RotWdg: 0
EBI_Ovld_Sta: 0
EBI_NegOC_Gen: 0
Where:
Access path in menu is “VALUESà CPU BI STATE à GEN PROT EBI” and “VALUESà MON BI
STATE à GEN PROT EBI”.
EBI_Diff_ST1: 0
EBI_Bak_HVS_ST1: 0
EBI_Bak_Br1_ST1: 0
EBI_REF_ST1: 0
EBI_Diff_ST2: 0
EBI_Bak_HVS_ST2: 0
EBI_REF_ST2: 0
Figure 4.3-3 Enabling Binary Input list of excitation and stepdown transformer protection
Where:
Access path in menu is “VALUESà CPU BI STATE à ET&ST PROT EBI” and “VALUESà MON
BI STATE à ET&ST PROT EBI”.
EBI_Trp_MechRly1: 0
EBI_Trp_MechRly2 0
EBI_Trp_MechRly3: 0
EBI_Trp_MechRly4: 0
BI_MechRly1: 0
BI_MechRly2: 0
BI_MechRly3: 0
BI_MechRly4 0
Where:
Access path in menu is “VALUESà CPU BI STATE à MECH RLY EBI” and “VALUESà MON BI
STATE à MECH RLY EBI”.
AUX BI
BI_52b_GCB: 0
BI_52b_CB_HVS1_Tr: 0
BI_52b_CB_HVS2_Tr: 0
BI_Valve_Turbine: 0
BI_SyncCondenser: 0
BI_Pwr_Superv: 0
BI_Reserved: 0
Where:
Access path in menu is “VALUESà CPU BI STATE à AUX BI” and “VALUESà MON BI STATE
à AUX BI”.
MON FD
MON.FD_Diff_Tr/GTU: 0
MON.FD_PPF/EF_Tr: 0
MON.FD_Diff_ST: 0
MON.FD_Bak_ST: 0
MON.FD_Diff_Gen: 0
MON.FD_EF_Sta/RotWdg: 0
MON.FD_OvLd_Sta: 0
MON.FD_PPF_Gen: 0
Where:
generator.
MON.FD_Pwr/AccEnerg_Gen Internally generated binary input indicating operation of fault
detector of power protection or accidental energization
protection of generator.
MON.FD_StShut_Gen Internally generated binary input indicating operation of fault
detector of startup and shutdown protection of generator.
MON.FD_Prot_Exc Internally generated binary input indicating operation of fault
detector of protections of excitation transformer or exciter.
MON.FD_MechRly Internally generated binary input indicating operation of fault
detector of mechanical protection of excitation transformer.
Access path in menu is “VALUESà CPU BI STATE à MON FD” and “VALUESà MON BI STATE
à MON FD”.
PS SUPERV BI
BI_Pwr_MechRly: 1
BI_Pwr_Opto: 1
BI_RstTarg: 0
BI_Pulse_GPS: 0
BI_Print: 0
Where:
BI_Pwr_Opto Binary input indicating the power supply of optical isolators is in proper
working condition.
Binary input indicating the power supply of all binary input circuit is in proper
BI_Pwr_MechRly
working condition.
BI_RstTarg Binary input of signal reset button.
BI_Pulse_GPS Binary input of GPS clock synchronous pulse.
BI_Print Binary input represents the print button.
Access path in menu is “VALUESà CPU BI STATE à PS SUPERV BI” and “VALUESà MON BI
STATE à PS SUPERV BI”.
4.4.1 Introduction
The RCS-985B is equipped with integral measurements, event, fault and disturbance recording
facilities suitable for analysis of complex system disturbances. The relay is flexible enough to allow
for the programming of these facilities to specific user application requirements and is discussed
below.
The real time clock within the relay provides the time tag to each event, to a resolution of 1ms. The
event records are available for viewing either via the frontplate LCD or remotely, via the
communications ports (courier and MODBUS versions only).
Local viewing on the LCD is achieved in the menu column entitled “REPORT”. This column allows
viewing of event and fault records and is shown by setting sequence No. of the event or fault
report by user. Refer to section 8 for details of operation method.
Where “Record NO.” means the sequence No. of the record which is generated by RCS-985B
automatically. “Date: DD-MM-YY” and “Time: HH:MM:SS:xxxxms” commonly comprise the
absolute time tag of the record. “Binary input Name” shows the name of the binary input whose
state changes. “Changing manner” shows how to change of the state of the binary input. For
instance:
All the binary input that may be shown in the menu can be found in section 4.3, here list them
again.
The above figure shows the abbreviated description that is given to the various alarm conditions
and also a corresponding value between 0 and 31. This value is appended to each alarm event in
a similar way as for the input events previously described. It is used by the event extraction
software, such as RCSPC, to identify the alarm and is therefore invisible if the event is viewed on
the LCD.
The following table shows all of the alarm elements that may be displayed in this item.
Where:
“Record NO.” means the sequence No. of the record which is generated by RCS-985B
automatically.
“Date: xxxx-xx-xx” and “Time: xx:xx:xx:xxxxms” commonly comprise the absolute time tag of the
record.
“Operation Element” shows the name of the operation element. If there are more than one
elements operating, they will scroll one by one to display on LCD.
“xxx ms” shows the relative time of operation element to fault detector of the relay.
The following table lists all the operation elements that may be displayed on LCD.
The MON board can store up to 4 seconds (24 sampling points per cycle) or 8 seconds (12
sampling points per cycle) continual waveform, which including all channels analog quantities
(sampled data, diferential currents and so on), all the binary input changing state, binary output,
pick up flags of fault detectors, alarm signals, operation signals and tripping signals. Disturbance
records continue to be recorded until the available memory is exhausted, at which time the oldest
record(s) are overwritten to make space for the newest one.
It is not possible to view the disturbance records locally via the LCD; they must be extracted using
suitable software such as RCSPC. This process is fully explained in the section 11.6.
The CPU board can also record latest 8 cycles of waveform in normal operation condition, which is
composed of three phases current, corrected current of each side for differential protection, three
phases voltage and zero sequence voltage of each side. This function can help user to check the
pole’s correctness of secondary circuit by comparing the phase of related quantities shown in
wave figure. This manual gives the detail instruction of getting normal operation waveform in
section 8.2.6.
Note:
The case materials of the relay are constructed from pre-finished steel that has a conductive
covering of aluminum and zinc. This provides good earthing at all joints giving a low impedance
path to earth that is essential for performance in the presence of external noise.
The boards and modules use a multi-point earthing strategy to improve the immunity to external
noise and minimize the effect of circuit noise. Ground planes are used on boards to reduce
impedance paths and spring clips are used to ground the module metalwork. Heavy duty terminal
blocks are used at the rear of the relay for the current and voltage signal connections. Medium
duty terminal blocks are used for the digital logic input signals, the output relay contacts, the power
supply and the rear communication port. A BNC connector may be used for the optional IRIG-B
signal. 9-pin female D-connector is used at the front of the relay for data communication.
Inside the protection the PCBs plug into the connector blocks at the rear, and can be removed
from the rear of the relay only. The connector blocks to the relay’s CT inputs are provided with
internal shorting links inside the relay which will automatically short the current generator circuits
before they are broken when the board is removed. The front panel consists of a membrane
keypad with tactile dome keys, an LCD and 5 LEDs mounted on an aluminum face plate.
Components mounted on its front include a 320×240 dot matrix LCD, a 9 button keypad, 5 LED
indicators, a DB9 connector for communication with HELP-90A or PC.
As to the buttons of the keypad, “ENT” is “enter”, “GRP” is “setting group selector” and “ESC” is
“escape”.
1 3 5 7 9 11 13 15 17 19 21 23 25 27 29 1 3 5 7 9 11 13 15 17 19 21 23 25 27 29
1A 1A 1B 1B
2 4 6 8 10 12 14 16 18 20 22 24 26 28 30 2 4 6 8 10 12 14 16 18 20 22 24 26 28 30
1 3 5 7 9 11 13 15 17 19 21 23 25 27 29 1 3 5 7 9 11 13 15 17 19 21 23 25 27 29
2A 2A 2B 2B
2 4 6 8 10 12 14 16 18 20 22 24 26 28 30 2 4 6 8 10 12 14 16 18 20 22 24 26 28 30
1 3 5 7 9 11 13 15 17 19 21 23 25 27 29 1 3 5 7 9 11 13 15 17 19 21 23 25 27 29
3A 3A 3B 3B
2 4 6 8 10 12 14 16 18 20 22 24 26 28 30 2 4 6 8 10 12 14 16 18 20 22 24 26 28 30
1 3 5 7 9 11 13 15 17 19 21 23 25 27 29 1 3 5 7 9 11 13 15 17 19 21 23 25 27 29
4A 4A 4B 4B
2 4 6 8 10 12 14 16 18 20 22 24 26 28 30 2 4 6 8 10 12 14 16 18 20 22 24 26 28 30
1 3 5 7 9 11 13 15 17 19 21 23 25 27 29 1 3 5 7 9 11 13 15 17 19 21 23 25 27 29
5A 5A 5B 5B
2 4 6 8 10 12 14 16 18 20 22 24 26 28 30 2 4 6 8 10 12 14 16 18 20 22 24 26 28 30
1 3 5 7 9 11 13 15 17 19 21 23 25 27 29
6B 6B
2 4 6 8 10 12 14 16 18 20 22 24 26 28 30
1 3 5 7 9 11 13 15 17 19 21 23 25 27 29
7B 7B
2 4 6 8 10 12 14 16 18 20 22 24 26 28 30
1 3 5 7 9 11 13 15 17 19 21 23 25 27 29
8B 8B
2 4 6 8 10 12 14 16 18 20 22 24 26 28 30
1 3 5 7 9 11 13 15 17
1 3 5 7 9 11 13 15 17 19 21 23 25 27 29 17
9B 9B 9C
2 4 6 8 10 12 14 16 18 20 22 24 26 28 30
2 4 6 8 10 12 14 16 18
1 3 5 7 9 11 13 15 17
1 3 5 7 9 11 13 15 17 19 21 23 25 27 29 17
2 4 6 8 10 12 14 16 18
1 3 5 7 9 11 13 15 17 1 3 5 7 9 11 13 15 17
17 17
11B 11C
2 4 6 8 10 12 14 16 18 2 4 6 8 10 12 14 16 18
1 3 5 7 9 11 13 15 17 1 3 5 7 9 11 13 15 17
17 17
12B 12C
2 4 6 8 10 12 14 16 18 2 4 6 8 10 12 14 16 18
opto- binary
AC curren t D SP1 status
and voltag e
LP F A /D D SP2 coupler input
CPLD
output
MMI C PU 1 relay
LC D
C PU m odule
M M I-C PU QDJ
com m ports and
port to printer
E+
MMI
D SP3 opto- bin ary
LPF A /D coup ler status
D SP4 inp ut
DC 220 V
+5 V
or 110 V
CPLD
DC/DC
± 12 V
+ 24 V
MMI C PU 2
± 24 V to
optic-coupler m a nagem en t m odule
co m m po rts and
p ort to printer
The equipment RCS-985B uses Motorola 32 bits monolithic microprocessor MC68332 as control
kernel for output logic and management functions, and high-speed digital signal processor DSP
for protection calculation. Sampling rate of the equipment is 24 points per cycle. Real time data are
processed parallel for all algorithms during whole process of fault. So the equipment can ensure
very high inherent reliability and security.
AC currents and voltages of CT and VT are transferred to low voltage signals by isolating
transformers and are inputted to CPU module and MON module. Data and logic are processed
respectively in these two modules with same hardware. The CPU module carries out functions of
protection algorithms, tripping logic, event record and printing. The MON module comprises
general fault detector and fault recorder. The fault detector will connect positive pole of power
supply of output relays after pickup. Format of the record is compatible with COMTRADE, and the
data recorded can be uploaded via separate serial port for communication or printing.
AC current and voltage are converted to low voltage signals in modules AC1, AC2, AC3 and AC4.
Two ratings of AC current are option, 1A or 5A. It shall be stated definitely during ordering and
checked during commissioning.
Binary output of tripping commands, tripping signal output and status binary input parts are
comprised in five modules: SIG1, SIG2, SIG3, SIG4 and RLY. 24V and 250/220/125/110V
opto-couplers are used here for binary input.
Briefly, the equipment is composed of twelve modules to achieve the work of generator or
generator-transformer unit protection. The modules are AC voltage and current input
module1(AC1), AC current input modules(AC2, AC3 and AC4), management/record
module(MON)、protection CPU module(CPU), power supply module(DC), signal modules(SIG1,
SIG2, SIG3 and SIG4), tripping contacts output(RLY) and human machine interface(HMI).
The relay hardware is based on a modular design whereby the relay is made up of an assemblage
of several modules.
Connectors with 30 pins are used for DC power supply, binary input, communication and printer,
tripping, alarm and other signal output and AC voltage input. Numbers of these connectors are 1A,
1B, 2A, 2B, 3A, 3B, 4A, 4B, 5B, 6B, 7B, 8B, 9B and 10B. Figure 5.2-1 a) shows layout of 30 pins of
these connectors.
Connectors with 18 pins are used for AC voltage input and current input. Numbers of these
connectors are 9C, 10C, 11B, 11C, 12B and 12C. Figure 5.2-1 b) shows layout of pins of these
connectors.
1 3 5 7 9 11 13 15 17 19 21 23 25 27 29 1 3 5 7 9 11 13 15 17
2 4 6 8 10 12 14 16 18 20 22 24 26 28 30 2 4 6 8 10 12 14 16 18
Attention:
For showing the relation of each terminal clearly, the terminal’s location shown in the figure may
be different from the real physical location, and we needn’t figure out the blank terminals.
1 3 5 7 9 11 13 15 17 19 21 23 25 27 29
2 4 6 8 10 12 14 16 18 20 22 24 26 28 30
1A1,1A30 blank
Binary output of tripping:
1A3-1A5 BO_TrpOutp1-1 tripping output channel 1-1
1A7-1A9 BO_TrpOutp1-2 tripping output channel 1-2
1A11-1A13 BO_TrpOutp1-3 tripping output channel 1-3
1A15-1A17 BO_TrpOutp1-4 tripping output channel 1-4
1A19-1A21 BO_TrpOutp2-1 tripping output channel 2-1
1A23-1A25 BO_TrpOutp2-2 tripping output channel 2-2
1A27-1A29 BO_TrpOutp2-3 tripping output channel 2-3
1A2-1A4 BO_TrpOutp3-1 tripping output channel 3-1
1A6-1A8 BO_TrpOutp3-2 tripping output channel 3-2
1A10-1A12 BO_TrpOutp3-3 tripping output channel 3-3
1A14-1A16 BO_TrpOutp3-4 tripping output channel 3-4
1A18-1A20 BO_TrpOutp4-1 tripping output channel 4-1
1A22-1A24 BO_TrpOutp4-2 tripping output channel 4-2
1A26-1A28 BO_TrpOutp5-1 tripping output channel 5-1
1 3 5 7 9 11 13 15 17 19 21 23 25 27 29
2 4 6 8 10 12 14 16 18 20 22 24 26 28 30
tripping
2A2-2A26 BO_EF_Tr Local signal: earth fault protection of transformer tripping
Binary output of remote signal:
2A3 common terminal 1 Remote signal: common terminal 1
2A3-2A9 BO_Diff_Gen; Remote signal: generator differential protection tripping
2A3-2A15 BO_EF_Sta Remote signal: stator earth fault protection tripping
2A3-2A21 BO_OvLd_Sta Remote signal: stator overload protection tripping
2A3-2A27 BO_LossExc Remote signal: generator loss-of-excitation protection
tripping
2A4 common terminal 2 Remote signal: common terminal 2
2A4-2A10 BO_Diff_GTU Remote signal: generator-transformer unit differential
protection tripping
2A4-2A16 BO_Diff_Tr Remote signal: transformer differential protection tripping
2A4-2A22 BO_PPF_Tr Remote signal: phase to phase fault protection of
transformer tripping
2A4-2A28 BO_EF_Tr Remote signal: earth fault protection of transformer tripping
Binary output of event record:
2A5 common terminal 1 Event record: common terminal 1
2A5-2A11 BO_Diff_Gen Event signal: generator differential protection tripping
2A5-2A17 BO_EF_Sta Event signal: stator earth fault protection tripping
2A5-2A23 BO_OvLd_Sta Event signal: stator overload protection tripping
2A5-2A29 BO_LossExc Event signal: generator loss-of-excitation protection tripping
2A6 common terminal 2 Event signal: common terminal 2
2A6-2A12 BO_Diff_GTU Event signal: generator-transformer unit differential
protection tripping
2A6-2A18 BO_Diff_Tr Event signal: transformer differential protection tripping
2A6-2A24 BO_PPF_Tr Event signal: phase to phase fault protection of transformer
tripping
2A6-2A30 BO_EF_Tr Event signal: earth fault protection of transformer tripping
Connector 4A: 30 pins male connector for signal and alarm output.
Connector 4B: 30 pins male connector for alarm and other output
Connector 5A: 30 pins male connector for status input (via 220V/250V or 110V/125V opto-coupler)
5A2-5A6 BO_MechRly4-2
5A2-5A8 BO_MechRly2-2
5A2-5A10 BO_MechRly1-2
Binary output of local signal of mechanical repeaters:
5A11 common terminal
5A11-5A12 BO_MechRly4-3
5A11-5A13 BO_MechRly2-3
5A11-5A14 BI_Pwr_MechRly
5A11-5A15 BO_MechRly3-3
5A11-5A16 BO_MechRly1-3
Binary input (via 220V or 110V opto-coupler) :
5A17 BI_MechRly3 Binary input of external mechanical repeater3
5A18 BI_MechRly4 Binary input of external mechanical repeater4
5A19 BI_MechRly2 Binary input of external mechanical repeater2
5A20 BI_MechRly1 Binary input of external mechanical repeater1
Binary input of auxiliary contact(via 220V or 110V opto-coupler)
5A21 BO_Pwr_Superv Monitoring auxiliary output contact of power supply of
mechanical protection
5A22 BI_52b_GCB Auxiliary contact of generator breaker
5A23 BI_52b_CB_HVS1_Tr Auxiliary contact of breaker A at HV side of main
transformer
5A24 BI_52b_CB_HVS2_Tr Auxiliary contact of breaker B at HV side of main
transformer
5A25 BI_Reserved
5A26 BI_Valve_Turbine Auxiliary contact of valve of steam turbine
5A27 + Positive pole of mechanical repeaters’ power supply.
5A28 Blank
5A29 - Negative pole of mechanical repeaters’ power supply.
5A30 Blank
5B21 EBI_Trp_MechRly3 Enabling binary input of external mechanical repeater 3 for tripping
5B22 EBI_Trp_MechRly4 Enabling binary input of external mechanical repeater 4 for tripping
5B23 EBI_Trp_MechRly2 Enabling binary input of external mechanical repeater 2 for tripping
5B24 EBI_Trp_MechRly1 Enabling binary input of external mechanical repeater 1 for tripping
5B25 EBI_PPF_Gen Enabling binary input of generator backup protection
5B26 EBI_Diff_Exc Enabling binary input of excitation transformer or excitor differential
protection
5B27 Blank
5B28 Blank
1 3 5 7 9 11 13 15 17 19 21 23 25 27 29
24V
DC/DC
0V
2 4 6 8 10 12 14 16 18 20 22 24 26 28 30
stepdown transformer1
6B9 EBI_Bak_Br1 _ST1 Enabling binary input of backup protection of Branch 1 of LV side
of stepdown transformer
6B10 EBI_Bak_Br1_ST2 Enabling binary input of backup protection of Branch 1 of LV side
of stepdown transformer2
6B11 EBI_Bak_Br2 _ST1 Enabling binary input of backup protection of Branch 2 of LV side
of stepdown transformer1
6B12 EBI_Bak_Br2 _ST2 Enabling binary input of backup protection of Branch 2 of LV side
of stepdown transformer2
6B13 BI_Print Binary input of print button
6B14 BI_Pulse_GPS Binary input of clock synchronization pulse
6B15 BI_ResetTarget Binary input of signal reset button
6B18 Blank
6B19 BI_Reserved
6B20 BI_SyncCondenser Binary input indicating the synchronize condenser generator is
put into operation
6B21 Reserved BI
6B22 Reserved BI
6B23 BI_Pwr_Opto Binary input used for monitoring the power supply of all the BIs
6B24 Blank
6B26 Blank
6B28 Blank
6B29 Earth
6B30 Earth
Connector 7B, 8B: 30 pins male connector for communication and printing.
Note:
1 2 3 4 5 6 7 8 9 10 11 12
IAN IA I BN IB I CN IC I AN IA I BN IB I CN IC
13 14 15 16 17 18
1 2 5 6 9 10 13 14 17 18 21 22 25 26 29 30
UAUB UA UB UB UC UB UC UB UC
UB UC UA UB UA UB
3 4 7 8 11 12 15 16 19 20 23 24 27 28
10B23-30 Reserved
20KΩ
I 04 N I 04
I AN IA I BN IB I CN IC I AN IA I BN IB ICN IC
I AN IA I BN IB I CN IC
I AN IA I BN IB ICN IC I AN IA I BN IB ICN IC
I AN IA I BN IB ICN IC
I AN IA I BN IB I CN IC I AN IA I BN IB ICN IC
I AN IA I BN IB ICN IC
I AN IA I BN IB IC N IC I AN IA I BN IB IC N IC
5.3 Output
5.3.1 Tripping outputs
The equipment provides 14 groups of tripping relays with 33 pairs of contacts totally as shown in
following figure. These tripping relays can be configured by tripping output logic setting, and
practical and flexible tripping modes can be provided by each protective function then. Tripping
output logic setting is a specific setting of each certain protective function. Please refer to Chapter
7 for details of setting.
The tripping output logic setting is a 4 digits hexadecimal number or a 16 bits binary number.
Every bit corresponds to a circuit breaker. The breaker will be tripped if the corresponding bit is set
as “1” and not tripped if the bit is set as “0”.
Note:
Outputs of TrpOutp1, 2, 5, 6 are instantaneous contacts, which can be used to trip CB or initial
failure of CB. While other outputs are expand 100ms after contacts operate.
The equipment provides 36 signals and each signal consists of 1 magnetic latching contact (for
local signals) and 2 wiper-type contacts (for SOE and remote signals). See the figure below.
(a) Group 1
(b) Group 2
(c) Group 3
(d) Group 4
o control the logging of records that are generated by the protection software, including alarms
T
and event, fault, and maintenance records.
To store and maintain a database of all of the relay’s settings in non-volatile memory.
o provide the internal interface between the settings database and each of the relay’s user
T
interfaces, i.e. the front panel interface and the front and rear communication ports, using
whichever communication protocol has been specified (Courier, MODBUS, and IEC
60870-5-103).
supervisor task that controls the start-up of the task and deals with the exchange of messages
between the task and the platform software.
After initialization at start-up, the protection and control task is suspended until there are sufficient
samples available for it to process. The acquisition of samples is controlled by a ‘sampling
function’ which is called by the system services software and takes each set of new samples from
the input module and stores them in a two-cycle buffer. The protection and control software
resumes execution when the number of unprocessed samples in the buffer reaches a certain
number. For the RCS-985B protection relay, the protection task is executed as the same speed as
the sampling rate, i.e. the relays finishes calculation of all the relay before next sampling process.
During the residual time, operations by other software tasks take place.
The sampling function provides filtering of the digital input signals from the opto-isolators and
frequency tracking of the analog signals. The digital inputs are checked against their previous
value over 15ms. Hence a change in the state of one of the inputs must be maintained over at
least 15ms before it is registered with the protection and control software.
The frequency tracking of the analog input signals is achieved by a recursive Fourier algorithm
which is applied to one of the input signals, and works by detecting a change in the measured
signal’s phase angle. The calculated value of the frequency is used to modify the sample rate
being used by the AC modules so as to achieve a constant sample rate of 24 samples per cycle of
the power waveform. The value of the frequency is also stored for use by the protection and
control task.
A change in any digital input signal, protection element output signal, operation flags of fault
detectors, tripping flags causes an event record to be created. When this happens, the protection
and control task sends a message to the supervisor task to indicate that an event is available to be
processed and writes the event data to a fast buffer in SRAM which is controlled by the supervisor
task. When the supervisor task receives either an event or fault record message, it instructs the
platform software to create the appropriate log in battery backed-up SRAM. The operation of the
record logging to battery backed-up SRAM is slower than the supervisor’s buffer. This means
that the protection software is not delayed waiting for the records to be logged by the platform
software.
The disturbance recorder operates as a separate task from the protection and control task. It can
record the waveforms for up to 32 analog channels and the values of up to all digital signals of the
RCS-985B. The recording time is user selectable up to a maximum of 8 seconds. The disturbance
recorder is supplied with data by the protection and control task once per sampling period.
The disturbance recorder collates the data that it receives into the required length disturbance
record. The disturbance records can be extracted by RCSPC that can also store the data in
COMTRADE format, thus allowing the use of other packages to view the recorded data.
Hardware requirement
Software requirement:
Downloading method
Note:
Ensure that the board is not a naked one before downloading software to it, i.e., certain version
software exists on the board.
Warning:
If some unexpected cases occur, please do inform the factory firstly instead of dealing with it by
yourself.
RCS-985
GENERATOR PROTECTION
GRP
EN T
2
3
5
2
3
5
Steps:
1. Connect RS-232 communication port of the computer and that mounted on front panel of
RCS-985B protection equipment by a cable with DB-9 connectors on both ends, see Figure 6.4-1.
2. Run the program RCSPC.If the connection and settings are correct, the screen will display
“RCS-985B connected”, such as Figure 6.4-2. But if it doesn’t be connected, please check the
parameter setting of RCSPC whether corresponds with the relay, such as “COM port” and “Baud
rate”, see Figure 6.4-3.
3. Download CPU program. At first, make sure it is at CUP mode as “CPU>”, then press the button
and select the correct program file, such as CPU.s19, to download it into the CPU module.
Make sure the file FLASHCPU.s19 is at the same folder with program file.
4. Download MON program. Change it to MON mode by typing “MON”, then “MON>” will
appearances. Then repeat step 3 to down load MON.s19 to MON module. Make sure the file
FLASHMON.s19 is at the same folder with program file. See Figure 6.4-4.
5.After downloading CPU and MON programs, reset the equipment and download default settings.
Then the ‘HEALTHY’ LED on the front panel of the relay shall be illuminate.
6. Download FACE program. Change it to FACE mode by typing “FACE” or “PNL”, then “PNL>”
will appearances. Press the button and select the 985xx_FACE.hex file to download it into
the panel module. Make sure the file FLASH_FACE.hex is at the same folder with program file.
7. After that course, user should check and ensure the software version, CRC code and
generating time of software are as same as recorded in relevant documentation. Enter the menu
“Version”, then new version of protection will display on LCD, see Figure 6.4-5.
VERSION
CPUBrd: RCS-985G3QM 1.00
ABCDEFGH
2007-01-01 09:00
MONBrd: RCS-985G3QM 1.00
ABCDEFGH
2007-01-01 09:00
HMI: RCS-985G3QM 1.00 ABCD
2007-01-01 09:00 T_060902
SUBQ_ID: SUBQ_12345678
Chapter7 Settings
The relay must be configured to the system and application by means of appropriate settings. The
settings of this relay include system parameters, protection element settings and scheme logic
settings.
Note:
Symbols of the parameter listed in above table are used for communication, printing and
displaying on LCD.
Two setting groups can be configured for the equipment, and only one is active at one time.
However, equipment parameters and system parameters are common for all protection setting
groups.
No.2-- [Equip_ID]
The setting consists of ASCII codes, which is identification for report printing only. It can be
configured according to the name or number of generator.
NANJING NARI-RELAYS ELECTRIC CO., LTD 195
Chapter 7 Settings
No.3-- [Comm_Addr]
The address used for the host computer to identify the equipment, usually provided by substation
system. If the equipment is not connected to automation system, equipment address may be
random.
No.4-- [Com1_Baud]
The baud rate of serial port 1 shall be selected from specified range.
No.5-- [Com2_Baud]
The baud rate of serial port 2 shall be selected from specified range.
No.6--[Printer_Baud]
The baud rate used for printer port shall be selected from specified range.
No.7-- [Protocol]
The logic setting consists of 16 binary digits but four hexadecimal digits can be viewed through
device LCD screen. Every digit has a dedicated meaning and some digits have no definition.
15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0
B: MODBUS
A: MODBUS
B: LFP
A: LFP
A: 103
The definitions of digits are:
Bit Definition
0 communication port A using protocol IEC 60870-5-103
1 communication port A using proprietary protocol LFP
2 communication port A using MODBUS protocol
3 No definition
4 No definition
5 communication port B using proprietary protocol LFP
6 communication port B using MODBUS protocol
7-15 No definitions
For example, if logic setting [Protocol] is set as “0041”, it means communication port A use IEC
60870-5-103 protocol, and port B use MODBUS protocol.
No.8-- [En_Auto_Print]
This setting shall be set as “1” if automatic report printing is expected after the relay operates
when a fault occurs. Otherwise it shall be set as “0”. It is suggested that the user may set this
parameter of the equipment as “1” (i.e. automatic printing), if the equipment is always connected
directly with a printer, or set as “0” (i.e. not automatic printing) if the equipment is connected with a
printer by through switch on panel.
No.9-- [En_Net_Print]
Set it as “1” if shared network printer is used for printing. Set it as “0” if dedicated printer is used.
Network printer means several protection equipments share one printer through a printer
management unit and RS-485 port. Dedicated printer means the protection equipment connected
with a printer through RS232 port directly.
No.10--[En_Remote_Cfg]
Set it as “0” if only local configuration is permitted. Set it as “1” if local and remote configurations
are both permitted.
No.11-- [GPS_Pulse]
Set it as “1” for minute pulse and “0” for second pulse.
Main Menu -> SETTINGS -> EQUIP SETTINGS -> [setting symbol]
Note:
Symbols of the parameter listed in above table are used for communication, printing and
displaying on LCD. Setting marked with “#” means that it is can not be seen on LCD or by printing
and only can be seen through RCSPC software.
No.1-- [En_Diff_GTU]
This is a general logic setting of main protection of generator-transformer unit. It is used for
enabling all differential protection configured for generator-transformer unit in RCS-985B,
including percentage differential and all other differential protection for generator-transformer unit.
The function of this logic setting is similar to the external binary input (BI)“Enable differential
protection” mounted on the panel. In program logic, the relation between this logic setting and the
external binary input is logic “And”. The differential protection will be put into use only when the
logic setting and the external binary input are enabled firstly.
This logic setting is used for configuration of protection functions. Setting it as “1” means the
generator-transformer unit differential protection is enabled and setting as “0” means the
protection is disabled.
No.2-- [En_Diff_Tr]
No.3-- [En_PPF_Tr]
This logic setting is used to enable/disable phase to phase fault protection of main transformer.
No.4-- [En_EF_Tr]
This logic setting is used to enable/disable earth fault protection of main transformer.
No.5-- [En_OvExc_Tr]
This logic setting is used to enable/disable over excitation protection of main transformer.
No.6-- [En_Diff_Gen]
No.7-- [En_IntTurn_Gen]
No.8-- [En_PPF_Gen]
This logic setting is used to enable/disable phase to phase fault protection of generator
No.9—[En_EF_Sta]
This logic setting is used to enable/disable earth fault protection of stator of generator.
No.10—[En_EF_RotWdg]
This logic setting is used to enable/disable earth fault protection of rotor winding.
No.11—[En_OvLd_Sta]
No.12—[En_NegOC_Gen]
No.13—[En_LossExc_Gen]
This logic setting is used to enable/disable loss of excitation protection of rotor winding.
No.14—[En_OOS_Gen]
No.15-- [En_VoltProt_Gen]
This logic setting is used to enable/disable overvoltage and undervoltage protection of generator.
No.16-- [En_OvExc_Gen]
No.17-- [En_PwrProt_Gen]
This logic setting is used to enable/disable overpower and underpower protection of generator.
No.18-- [En_FreqProt_Gen]
No.19-- [En_StShut_Gen]
This logic setting is used to enable/disable all relative protections in Startup/shutdown conditions
of generator.
No.20-- [En_AccEnerg_Gen]
This logic setting is used to enable/disable relevant protection in case of accident energization of
generator.
No.21-- [En_Diff_Exc]
This logic setting is used to enable/disable differential protection of exciting transformer or exciter.
No.22-- [En_Bak_Exc]
This logic setting is used to enable/disable backup protection of exciting transformer or exciter.
No.23-- [En_Diff_ST1]
No.24-- [En_Bak_HVS_ST1]
No.25-- [En_Bak_Br1_ST1]
This logic setting is used to enable/disable backup protection at branch 1 of LV side of stepdown
transformer1.
No.26-- [En_REF_ST1]
No.27-- [En_Diff_ST2]
No.28-- [En_Bak_HVS_ST2]
transformer2.
No.29-- [En_Bak_Br1_ST2]
This logic setting is used to enable/disable backup protection at branch 1 of LV side of stepdown
transformer2.
No.30-- [En_REF_ST2]
No.31-- [En_MechRly]
No.32-- [En_VTComp_Term_Gen]
This logic setting is used to enable/disable voltage balance function of VTs at the generator
terminal.
No.33-- [Opt_InputMode_VT_ST]
This logic setting is to decide which kind of voltage of stepdown transformeris input into RCS-985B,
“0” represents phase-ground voltage, while “1” represents phase-to-phase voltage.
This logic setting is configured especially for equipment debugging status. It is only seen by
RCSPC, which is used for generating messages of alarm or operation element for remote PC.
“Enable”: enable sending all tripping contacts signals, protection tripping signals, alarm signals
and monitoring signals through DBU2000 software.
All logic settings of configuring functions are accessible in the following path:
Main Menu -> SETTINGS -> SYSTEM SETTINGS -> PROT CONFIG -> [setting symbol]
No.1-- [Sn_Tr]
No.2-- [U1n_HVS_Tr]
System rated voltage at HV side of main transformer. This setting is used for calculating the rated
current of main transformer. It should be set according to the real operating voltage of the power
system.
No.3-- [U1n_LVS_Tr]
No.4-- [U1n_VT_HVS_Tr]
No.5-- [U2n_VT_HVS_Tr]
No.6-- [U2n_DeltVT_HVS_Tr]
No.7-- [I1n_CT_HVS_Tr]
No.8-- [I2n_CT_HVS_Tr]
No.9-- [I1n_CT_Bak_HVS_Tr]
No.10-- [I2n_CT_Bak_HVS_Tr]
No.11-- [I1n_CT_LVS_Tr]
No.12-- [I2n_CT_LVS_Tr]
No.13-- [I1n_CT#_HVS_ST1]
No.14-- [I2n_CT#_HVS_ST1]
No.15-- [I1n_CT#_HVS_ST2]
No.16-- [I2n_CT#_HVS_ST2]
No.17-- [I1n_CT_NP_Tr]
No.19-- [I1n_CT_Gap_Tr]
No.20-- [I2n_CT_Gap_Tr]
No.21-- [Yd11_Conn_Tr]
The connection mode of main transformer is Yd-11 mode. The current input for HV side is only
one.
No.22-- [Yyd11_Conn_Tr]
The connection mode of main transformer is Yd-11 mode. The currents input for HV side are two
CTs, such as 3/2 breakers of HV bus.
No.23-- [Opt_GCB]
Logic setting of circuit breaker at terminal of generator. “1” means there is a circuit breaker at
terminal of generator. “0” means there isn’t a circuit breaker at terminal of generator.
No.24-- [Yd1_Conn_Tr]
The connection mode of main transformer is Yd-1 mode. The current input for HV side is only one.
No.25-- [Yyd1_Conn_Tr]
The connection mode of main transformer is Yd-1 mode. The currents input for HV side are two
CTs, such as 3/2 breakers of HV bus.
All settings of transformer system parameters are accessible in the following path:
Main Menu -> SETTINGS -> SYSTEM SETTINGS -> TR SYS SETTINGS -> [setting symbol]
1A 12000
12. I1n_CT_NP_Gen 0-60000 A
1A 5
13. I2n_CT_NP_Gen 1A/5A
0-60000 A 1A 12000
14. I1n_CT_TrvDiff_Gen
1A,5A 1A 5
15. I2n_CT_TrvDiff_Gen
1A 1000
16. I1n_RotWdg 0-60000 A
0-100.00 mV 0.01 mV 75
17. U2n_Shunt_RotWdg
200
18. U1n_Exc 0-600 V 0.01 V
No.1-- [fn_Gen]
This setting indicates the nominal frequency of power system in which the generator protection
equipment is used.
No.2-- [Pn_Gen]
Capacity of active power of the generator shall be configured as its name plate stated.
No.3-- [PF_Gen]
No.4-- [U1n_Gen]
System rated voltage at the terminal of generator. This setting is used for calculating the rated
current of generator. It should be set according to the real operating voltage of the power system.
No.5-- [U1n_VT_Term_Gen]
Rated primary voltage of VT at the terminal of generator. This parameter can be configured as
either phase voltage or phase-to-phase voltage value. For example, if the terminal VT ratio is
No.6-- [U2n_VT_Term_Gen]
No.7-- [U2n_DeltVT_Term_Gen]
No.8-- [U1n_VT_NP_Gen]
No.9-- [U2n_VT_NP_Gen]
No.10-- [I1n_CT_Term_Gen]
No.11-- [I2n_CT_Term_Gen]
No.12-- [I1n_CT_NP_Gen]
No.13-- [I2n_CT_NP_Gen]
No.14-- [I1n_CT_TrvDiff_Gen]
No.15-- [I2n_CT_TrvDiff_Gen]
No.16-- [I1n_RotWdg]
Primary rated current of rotor. This setting and the next one can be set conveniently by inputting
the rated primary and secondary parameters of the shunt.
No.17-- [U2n_Shunt_RotWdg]
No.18-- [U1n_Exc]
All settings of generator system parameters are accessible in the following path:
Main Menu -> SETTINGS -> SYSTEM SETTINGS -> GEN SYS SETTINGS -> [setting symbol]
Note:
These parameters are as important as the settings. They have to be configured according to
actual application on site.
No.1-- [Sn_ST1(2)]
Capacity of the exciter or stepdown transformer shall be configured as its name plate stated.
No.2-- [U1n_HVS_ST1(2)]
No.6-- [I1n_CT_HVS_ST1(2)]
Rated primary current of CT1 with small ratio at HV side of stepdown transformer.
No.7-- [I2n_CT_HVS_ST1(2)]
Rated secondary current of CT1 with small ratio at HV side of stepdown transformer.
No.10-- [I1n_CT_NP_Br_ST1(2)]
No.11-- [I2n_CT_NP_Br_ST1(2)]
No.12-- [Yyy12_Conn_ST]
No.13-- [Ddd12_Conn_ST]
No.14-- [Dyy11_Conn_ST]
No.15-- [Ydd11_Conn_ST]
No.16-- [Dyy1_Conn_ST]
All settings of stepdown transformer system parameters are accessible in the following path:
Main Menu -> SETTING -> SYSTEM SETTINGS -> ST SYS Settings -> [setting symbol]
1A 60
7. I1n_CT_S2_Exc 0-60000 A
5
8. I2n_CT_S2_Exc 1A,5A 1A
9. Opt_Exc 0, 1 0
10. Yy12_Conn_ET 0, 1 0
11. Dd12_Conn_ET 0, 1 0
12. Dy11_Conn_ET 0, 1 0
13. Yd11_Conn_ET 0, 1 1
14. Dy1_Conn_ET 0, 1 0
No.1-- [fn_Exc]
This setting indicates the nominal frequency of exciter. If excitation transformer is used, this setting
can be set as 50Hz and the other settings in this table should be set according to relevant
parameters of excitation transformer.
No.2-- [Sn_Exc]
Capacity of the exciter or excitation transformer shall be configured as its name plate stated.
No.3-- [U1n_S1_Exc]
NANJING NARI-RELAYS ELECTRIC CO., LTD 209
Chapter 7 Settings
The system rated voltage on HV side of the excitation transformer. This setting is used to calculate
the correction coefficient of differential protection of excitation transformer.
If exciter is used, this setting and NO.4 setting are all set as the rated voltage of exciter.
No.4-- [U1n_S2_Exc]
System rated voltage on LV side of the excitation transformer. This setting is used to calculate the
correction coefficient of differential protection of excitation transformer.
No.5-- [I1n_CT_S1_Exc]
Primary rated current of the CT on HV side of the excitation transformer or CT at the terminal of
the exciter.
No.6-- [I2n_CT_S1_Exc]
Secondary rated current of the CT on HV side of the excitation transformer or CT at the terminal of
the exciter.
No.7-- [I1n_CT_S2_Exc]
Primary rated current of the CT on LV side of the excitation transformer or CT at the neutral point
of the exciter.
No.8-- [I2n_CT_S2_Exc]
Secondary rated current of the CT on LV side of the excitation transformer or CT at the neutral
point of the exciter.
No.9-- [Opt_Exc]
Exciter is used in the system. If this setting is set as “1”, that means exciter is used in the generator
system instead of excitation transformer. Otherwise means the contrary.
No.10-- [Yy12_Conn_ET]
Note:
In the symbol of “Yy-12”, the first letter “Y” represents the connection mode of windings on HV side,
and the other “y” represents the connection mode of windings on LV side, “12” represents
connection group between HV and LV windings. The following four settings are similar to this one.
No.11-- [Dd12_Conn_ET]
No.12-- [Dy11_Conn_ET]
No.13-- [Yd11_Conn_ET]
No.14-- [Dy1_Conn_ET]
All settings of excitation system parameters are accessible in the following path:
Main Menu -> SETTING -> SYSTEM SETTINGS -> EXC SYS Settings -> [setting symbol]
The settings in the following list are associated with application-specific primary layout of
generator and exciter, tripping logics. These settings can not be seen on LCD of equipment and
only be viewed and configured on PC through RCSPC software in the submenu “CONFIG
SETTINGS”. These settings are usually configured in factory or configured by field commission
engineer according to the design drawing and project requirement.
Note:
Setting marked with “#” means that it is can not be seen on LCD or by printing and only can be
seen through RCSPC software.
This is the logic setting of connection type between bus, generator, main transformer, and
stepdown transformer, whichi decides the default LCD displaying in normal operation condition.
Each bit from 0 to 8 represents a unique figure displayed on LCD if the bit is set as “1”. The
following table gives the actual meaning of each bit. Only one bit can be set as “1” simultaneously.
7. Bit6 Double bus connection, two two-windings stepdown transformers without terminal
circuit breaker of generator.
8. Bit7 Double bus connection, one three-windings stepdown transformers without
terminal circuit breaker of generator.
9. Bit8 3/2 bus connection, one three-windings stepdown transformers without terminal
circuit breaker of generator.
No.2-- [Cfg_Polar_CT](#)
Generally, CT polarity definition is shown as Table 7.2-7. However if some CT polarity direction is
reversed by incorrect wiring connecting, there is still chance to correct it by configuring this logic
setting easily. Please set the corresponding digit of the logic setting. Bit.1-15 are corresponding to
15 three-phase current channels one by one. If any bit is set as “0”, the program will reverse the
current polarity of this channel before calculation.
15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0
Three-phase channel 15
Three-phase channel 14
Three-phase channel 13
Three-phase channel 12
Three-phase channel 11
Three-phase channel 10
Three-phase channel 9
Three-phase channel 8
Three-phase channel 7
Three-phase channel 6
Three-phase channel 5
Three-phase channel 4
Three-phase channel 3
Three-phase channel 2
Three-phase channel 1
No defination
No.3-- [Cfg_CT_HVS1_Tr](#)
Configurable setting for deciding which channel is chosen to input three-phase current of HVS1
side of main transformer.
Following table gives all the choices that user can decide. Only one bit at most can be set as “1”
simultaneously.
15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0
Three-phase channel 15
Three-phase channel 14
Three-phase channel 13
Three-phase channel 12
Three-phase channel 11
Three-phase channel 10
Three-phase channel 9
Three-phase channel 8
Three-phase channel 7
Three-phase channel 6
Three-phase channel 5
Three-phase channel 4
Three-phase channel 3
Three-phase channel 2
Three-phase channel 1
No defination
No.4-- [Cfg_CT_HVS2_Tr](#)
Configurable setting for deciding which channel is chosen to input three-phase current of HVS2
side of main transformer. The definition is the same to the above table.
No.5—[Cfg_CT_HVS_Tr](#)
Configurable setting for deciding which channel is chosen to input three-phase current of HVS side
of main transformer. This currrent is specially used for backup protection of main transformer. The
definition is the same to the above table except for the bit0. in this setting, if the bit0 is set as “1”,
the protection will recongnize this directly input current as the whole current of HVS side of main
transformer, othewise, the protection will automatically add HVS1 and HVS2 side currents
mentioned aboved to be the whole current of HVS side and ignoring the current input from this
channel.
No.6—No. 27
Configurable setting for deciding which channel is chosen to input each current. The definition of
each bit is the same to that of No.4. The actual meaning of each setting is given in the following
table.
No.28-- [Cfg_CT_Diff_GTU](#)
Logic setting of selecting three-phase current channels for differential protection of generator
transformer unit. If the bit is set as ”1”, it means this group is used in the differential
protection.Following will be seen on PC through RCSPC software.
15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0
CT#_HVS_ST
CT_HVS2_Tr
CT_HVS1_Tr
CT_HVS_ST
CT_NP_Gen
CT_LVS_ST
No.29-- [Cfg_CT_Diff_Tr](#)
Logic setting of selecting three-phase current channels for differential protection of main
transformer. If the bit is set as ”1”, it means this group is used in the differential
protection.Following will be seen on PC through RCSPC software.
15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0
CT#_HVS_ST
CT_HVS2_Tr
CT_HVS1_Tr
CT_HVS_ST
CT_LVS_ST
CT_LVS_Tr
No.30--[Cfg_CT_PwrProt_Gen] (#)
Logic setting of selecting three-phase current CT for reverse power protection of generator.
“0”: CT of P level.
“1”: CT of S level.
No.31--[Opt_WaveRec_MON] (#)
No.32--[Opt_Debug_MON](#)
This logic setting is provided especially for software developing, not for ordinary users.
No.33--[Opt_Dur_WaveRec_MON](#)
No.34--[En_Displ_Pickup](#)
This logic setting is provided especially for software developing, not for ordinary users.
No.1-- [I_Pkp_PcntDiff_GTU]
This is pickup setting of percentage current differential protection, which is also the setting of fault
detector of percentage differential protection. It shall be higher than maximum unbalance current
when the generator-transformer operate on normal rated load.
No.2-- [I_InstDiff_GTU]
No.3-- [Slope1_PcntDiff_GTU]
No.4-- [Slope2_PcntDiff_GTU]
No.5-- [k_Harm_PcntDiff_GTU]
The ratio setting of 2nd harmonic component in differential current. 0.15 is recommended.
No.6-- [TrpLog_PcntDiff_GTU]
Tripping output logic setting of differential protection is used to specify which breaker or breakers
will be tripped by this protection. This word comprises 16 binary bits as follows and is displayed as
a hexadecimal number of 4 digits from 0000H to FFFFH on LCD of equipment. The tripping output
logic settings is specified as follows:
bit 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0
No definition
rpOutput14
TrpOutp13
TrpOutp12
TrpOutp11
TrpOutp10
TrpOutp9
TrpOutp8
TrpOutp7
TrpOutp6
TrpOutp5
TrpOutp4
TrpOutp3
TrpOutp2
TrpOutp1
Function
En_Trp
Note:
“TrpOutp 1” just means to drive tripping output channel 1 and please refer to section 5.3. Set bit0
as “1” means this protection element will trip breaker or breakers. The bit corresponding to the
breaker to be tripped shall be set as“1” and other bits shall be “0”. For example, if differential
protection is defined to trip breaker 5 (tripping output channel 5), the bit0 and bit5 bit shall be set
as “1” and other bits “0”. Then a hexadecimal number 0021H is formed as the tripping output logic
setting.
Please note that tripping output logic settings of the equipment have to be set on basis of
application-specific drawings.
All the tripping logic settings mentioned below is defined as same as this one.
No.7-- [En_InstDiff_GTU]
Unrestrained instantaneous differential protection enabled. If this setting is set as “1”, it means this
protection is enabled. Otherwise it means the protection is disabled.
No.8-- [En_PcntDiff_GTU]
No.9-- [Opt_Inrush_Ident_GTU]
The logic setting to select the method to identify inrush current of transformer.
“1” means to use the second harmonic restraint principle. “0” means to use waveform distortion
discrimination principle.
No.10-- [Opt_CTS_Blk_PcntDiff_GTU]
If this logic setting is set as “1”, it means percentage differential protection will be blocked when CT
circuit failure happens. Otherwise it means the function is disabled.
All settings of differential protection settings are accessible in the following path:
Main Menu -> SETTINGS -> PROT SETTINGS -> GTU DIFF PROT --> [setting symbol]
No.1-- [I_Pkp_PcntDiff_Tr]
This is pickup setting of percentage current differential protection, which is also the setting of fault
218 NANJING NARI-RELAYS ELECTRIC CO., LTD
Chapter7 Settings
detector of percentage differential protection. It shall be higher than maximum unbalanced current
of the transformer during normal rated load, i.e.
Where:
I e is secondary calculated rated current of transformer (please see details in section 3.3.1);
K er is the ratio error of CT (=0.03X2, for class 10P; =0.01X2, for class 5P and class TP);
∆U is the maximum deviation (in percentage of rated voltage) due to tap changing.
∆m is the error caused by the difference between ratios of CT at all side, 0.05 is recommended.
For practical engineering application, I cdqd =(0.3 - 0.5) I e is reasonable and unbalanced current
No.2-- [I_InstDiff_Tr]
Setting of unrestrained instantaneous differential protection, which is used to clear serious internal
fault quickly and prevent operation delay caused by CT saturation. The setting I cdsd (i.e.
[I_InstDiff]) shall be greater than inrush current and maximum unbalanced current due to external
fault or asynchronous closing, generally
Where:
according to the phase-to-phase solid short circuit fault in normal operation condition at installed
No.3-- [Slope1_PcntDiff_Tr]
K bl 1 ≥ K er
(Equation 7.3-3)
Where:
K er is the error of current ratio of CT, no more than 0.1. K bl1 is 0.10-0.20 generally.
The sensitivity coefficient K sen shall be calculated according to phase-to-phase short circuit on
outlet of transformer protected by the differential relay in minimum operation mode. From the
calculated minimum short circuit current I k . min and relevant restraint current I res , corresponding
pickup current I op will be found in the operation characteristic curve of percentage differential
K sen = I k . min / I op
(Equation 7.3-4)
No.4-- [Slope2_PcntDiff_Tr]
Where:
I k . max is the maximum value of fundamental component of external short circuit fault current
(secondary).
K ap is the coefficient of DC component. K ap = 1.0 if CT at both sides are class TP, or K ap = 1.5 -
Where:
∆U h are maximum deviations (in percentage of rated voltage) on HV side due to tap changing.
I k . max is the maximum value of fundamental component of short circuit secondary current flowing
I k .h. max is the maximum value of fundamental component of short circuit secondary current flowing
I k .I . max and I k .II . max are the fundamental components of secondary currents flowing through CT at
∆m I and ∆mII are errors caused by difference between ratios of CT (auxiliary CT included if any)
at relevant sides.
Where:
Definition of I unb. max* , I cdqd * and I k . max* are almost same to I unb. max , I cdqd and
I k . max mentioned above, and the only difference is they are per unit values. I e (secondary
No.5-- [k_Harm_PcntDiff_Tr]
Restraint coefficient of second harmonic. This parameter is the blocking threshold of second
harmonics involving in differential current to against inrush current when the transformer is
energized. The differential protection will be blocked when the percentage of second harmonics
reaches the threshold because the percentage of second harmonics is high in inrush current but
low in fault current. It is recommended that the parameter is set to be 15% -20%.
No.6-- [TrpLog_DIff_Tr]
Tripping output logic setting of differential protection is used to specify which breaker or breakers
will be tripped by this protection.
No.7-- [En_InstDiff_Tr]
Unrestrained instantaneous differential protection enabled. If this setting is set as “1”, it means this
protection is enabled. Otherwise, it means the protection is disabled.
No.8-- [En_PcntDiff_Tr]
Percentage differential protection enabled. If this setting is set as “1”, it means this protection is
enabled. Otherwise, it means the protection is disabled.
No.9-- [En_DPFC_Diff_Tr]
DPFC percentage differential protection enabled. If this setting is set as “1”, it means this
protection is enabled. Otherwise, it means the protection is disabled.
No.10-- [Opt_Inrush_Ident_Tr]
No.11-- [Opt_CTS_Blk_PcntDiff_Tr]
If this logic setting is set as “1”, it means percentage differential protection will be blocked when CT
circuit failure happens. Otherwise, it means the function is disabled.
All settings of differential protection settings are accessible in the following path:
Main Menu -> SETTINGS -> PROT SETTINGS -> TR DIFF PROT --> [setting symbol]
No.1-- [V_NegOV_VCE_Tr]
This is setting of negative sequence voltage control element of main transformer. Setting and
displayed value of negative sequence voltage are U2.
Setting of this relay shall be higher than measured imbalance voltage during normal operation
condition, generally
Where:
U k .2. min
K sen =
U op.2 (Equation 7.3-9)
Where U k .2. min is minimum secondary negative sequence voltage at location of the relay during
phase-to-phase metallic short circuit fault at end of backup protected zone. K sen ≥2.0 is required
for near backup protection and K sen ≥1.5 for remote backup protection.
Note:
When sensitivity factor is checked for current relay and voltage relay, unfavorable normal system
operation condition and unfavorable type of short circuit fault shall be adopted. If sensitivity factor
of under voltage relay is not high enough, function of composite voltage on LV side initiation can
be enabled. Voltage is taken from LV side by configure logic setting [En_LVS.VCE_Ctrl_OC_Tr].
No.2-- [Vpp_UV_VCE_Tr]
Voltage of voltage control element is taken from LV side usually (logic setting
[En_LVS.VCE_Ctrl_OC_TR] is set as 1.). Undervoltage setting shall be higher than the lowest
voltage during starting process of the largest motor connected with the LV busbar.
Setting of phase-to-phase under voltage of composite voltage control element. It shall coordinate
with generator starting condition.
Setting shall be higher than possible minimum voltage during normal operation, namely
U min
U op =
K rel ⋅K r (Equation 7.3-10)
Where K rel is reliability factor, 1.10 – 1.20; K r is release factor, 1.05 – 1.25; U min is possible
minimum voltage during normal operation, 0.9 times of secondary rated line voltage generally.
When VT on HV side of the transformer is used for the under voltage relay
U op = 0.7U n
(Equation 7.3-11)
When step-up transformer is used in a power plant and VT on generator side is used for under
voltage relay, its setting shall be higher than under voltage during operation of generator without
excitation,
U op = (0.5 − 0.6)U n
(Equation 7.3-12)
U op
K sen =
U c. max (Equation 7.3-13)
Where U c. max is maximum secondary residual voltage at location of the relay when
phase-to-phase metallic short circuit fault occurs at the check point during operation condition for
calculation. K sen ≥1.5 is required for near backup protection and K sen ≥1.2 for remote backup
protection.
No.3-- [I_OC1_Tr]
K rel
I op = Ie
Kr (Equation 7.3-14)
where K rel is reliability factor, 1.2 generally; K r is release factor, 0.85 – 0.95; I e is secondary
rated current.
I k( 2. min
)
K sen =
I op (Equation 7.3-15)
where I k( 2. min
)
is minimum fault current through location of the relay during phase-to-phase metallic
short circuit at end of backup protected section. K sen ≥ 1.3 is required for near backup
No.4-- [t_OC1_Tr]
The time delay of stage 1 of overcurrent protection. It shall coordinate with main protection only
and oscillation period is not needed to be considered. It is set as 0.5 s generally.
No.5 – [TrpLog_OC1_Tr]
Tripping output logic setting of the time delay of over current protection stage 1, please refer to
section 7.3.1.
No.6-- [I_OC2_Tr]
No.7-- [t_OC2_Tr]
Tripping output logic setting of the first time delay of over current protection stage 2, please refer to
section 7.3.1
No.9 – [Z1_Fwd_Tr]
If the value of this setting is greater than the next one, then the characteristic of distance protection
is set as excursive impedance circle; if it is equal to the next one, the characteristic is whole
impedance circle; if the next one is set as “0”, the characteristic becomes directional impedance.
Generally, low impedance protection is considered as the backup protection of transformer in case
that voltage-controlled overcurrent protection cannot satisfy the sensitivity requirement of
transformer.
Setting of this impedance relay shall coordinate with that of HV side outlet, namely
Z op = K rel K inf Z
(Equation 7.3-16)
Where K rel is reliability factor, 0.8 generally; Kinf is enhanced factor, taking minimum value of
Sensitivity shall be checked by phase-to-phase short circuit on end of designated protected zone,
namely
Z op
K sen =
Z (Equation 7.3-17)
Where Z is equivalent secondary impedance value of designated protected section. K sen ≥1.3
Is required.
The forward setting can be based on enough sensitivity for fault on terminal of generator and
referred to equation hereinabove. Reverse impedance equals to 5% - 10% of forward impedance.
Reverse setting shall be lower than setting of the shortest zone 1 of impedance protection of outlet
from this side busbar.
NO.10—[Z1_Rev_Tr]
Stage 1 of negative direction impedance setting of distance protection. In general, this setting is
set as 5-10% of the positive direction impedance setting.
NO.11—[t_Z1_Tr]
NO.12—[TrpLog_Z1_Tr]
No.13 – [Z2_Fwd_Tr]
NO.14—[Z2_Rev_Tr]
NO.15—[t_Z2_Tr]
NO.16—[TrpLog_Z2_Tr]
No.17-- [I_Alm_OvLd_Tr]
No.18-- [t_Alm_OvLd_Tr]
No.19-- [I_InitCool1_OvLd_Tr]
No.20-- [t_InitCool1_OvLd_Tr]
No.21-- [I_InitCool2_OvLd_Tr]
No.30-- [t_InitCool2_OvLd_Tr]
No.23-- [En_VCE_Ctrl_OC1_Tr]
No.24-- [En_VCE_Ctrl_OC2_Tr]
No.25 -- [En_LVS.VCE_Ctrl_OC_Tr]
No.26 -- [En_Mem_Curr_Tr]
Note:
For generator with self parallel excitation system, the memory function is usually disabled for
phase to phase backup protection. But if it is enabled, the overcurrent protection must be
configured as voltage controlled overcurrent protection.
No.27-- [Opt_VTS_Ctrl_OC_Tr]
“1”: when VT circuit failure at one side is detected, voltage control element at the same side will be
disabled but overcurrent relay on the same side can still be controlled by voltage control elements
of other side if corresponding logic setting is set as “1”.
“0”: when VT circuit failure at one side is detected, the overcurrent relay will become an
overcurrent relay without voltage element control.
No.28-- [En_OvLd_Tr]
No.29-- [En_InitCool_OvLd_Tr]
Settings of HV side voltage phase to phase fault protection are accessible in the following path:
Main Menu -> Setting -> PROT SETTINGS -> TR PPF BAK PROT--> [setting symbol]
1 7FFF
16. TrpLog_REF_Tr 0000-FFFF
0/1 0
20. En_VCE.ROV_Ctrl_ROC2_Tr
0
21. En_Dir_Ctrl_ROC1_Tr 0/1
0
22. En_Dir_Ctrl_ROC2_Tr 0/1
0
23. En_Alm_ROV_LVS_Tr 0/1
Setting (3U0) of zero-sequence voltage control element for zero-sequence overcurrent protection.
No.2-- [I_ROC1_Tr]
This setting shall coordinate with unrestraint main protection or stage 1 or 2 of zero sequence
overcurrent relay of adjacent power line.
Where:
K brI is branch factor of zero sequence current which is ratio of zero sequence current passing
through the relay and passing through the faulty line during ground fault at end of protected zone
of stage 1 of power line zero sequence overcurrent protection, maximum value for various
operation conditions being Taken;
3I k .o. min
K sen =
I op.o (Equation 7.3-19)
Where:
3I k .o. min is minimum secondary zero sequence current passing through location of the relay
during ground fault at end of protected zone; I op.o is this setting. K sen ≥1.5 Is required.
No.3-- [t_ROC11_Tr]
When earth fault occurs on near end of HV side outlet of startup/standby transformer, it is
protected by both this protection and zero-sequence overcurrent protection stage 2 on remote end,
so the time delay setting of this protection is
t = t II − ∆t
(Equation 7.3-20)
Where:
Tripping output logic setting of zero-sequence overcurrent protection stage 1 with time delay 1.
No.5-- [t_ROC12_Tr]
No.6-- [TrpLog_ROC12_Tr]
Tripping output logic setting of zero-sequence overcurrent protection stage 1 with time delay 2.
No.7-- [I_ROC2_Tr]
The setting shall coordinate with operating current of zero-sequence overcurrent protection of HV
side feeders for remote end earth fault:
(3I 0 ) op
I op.o . II = K c 0 C 0'
nTA (Equation 7.3-21)
Where:
(3I o ) op is the primary operating current of backup zone of zero-sequence overcurrent protection
C 0' is the distribution coefficient of zero sequence current that is equal to the ratio of zero
sequence current passing through this end protection and that passing through the power line,
takes the maximum value in various operation modes; and nTA is current ratio of CT.
No.8-- [t_ROC21_Tr]
No.9-- [TrpLog_ROC21_Tr]
Tripping output logic setting of zero-sequence overcurrent protection stage 2 with time delay 1.
No.10-- [t_ROC22_Tr]
No.11-- [TrpLog_ROC22_Tr]
Tripping output logic setting of zero-sequence overcurrent protection stage 2 with time delay 2.
No.12-- [I_Alm_REF_Tr]
Setting of zero sequence differential current alarm. This setting shall be greater than the maximum
zero sequence unbalance differential current in normal operation condition meanwhile smaller
than REF pickup value.
No.13-- [I_Pkp_PcntREF_Tr]
Pickup setting of zero sequence differential current. Calculation of this setting is based on
secondary rated current of CT. The pick up current of zero sequence differential protection shall
be higher than the maximum unbalance current while transformer operates on normal rated load,
i.e.
Where:
K er is the ratio errors of CT (for type 10P, K er = 0.03×2; for class 5P and class TP, K er =0.01X2);
∆m is the error caused by the difference between ratios of CT at all side, 0.05 is recommended.
For practical engineering calculation, I ocdqd =(0.2 - 0.5) I n is reasonable and imbalance current
Please note that calculation of zero sequence differential current settings is based on the
secondary rated current of CT. If a setting value got from calculation is together with its unit
Ampere, this setting shall be divided by secondary rated current of this side of CT, to get per unit
value.
Sensitivity of zero sequence percentage differential protection shall be checked with the solid
earthed short circuit in its protected zone. K sen ≥ 2 is required. In solid earthed system,
distribution of zero sequence current for single phase to ground fault depends on the configuration
of zero sequence network of power system. Magnitude of the single-phase ground fault current
depends on not only zero sequence distance of system but also positive and negative sequence
distance or power system operation mode. When power system is in maintenance status, in order
to remain the zero sequence network unchanged and increase sensitivity for earth fault protection,
the 220 kV power system is generally compensated by properly changing earth mode of the
transformer. Neutral point of transformer of 400 kV power system is now generally earthed with
small reactance. Therefore, sensitivity of zero sequence differential protection shall be checked in
minimum operation mode for 220 kV power system and minimum operation mode or small
maintenance mode for 400 kV power system.
Note:
Positive polarity of CT is at busbar side on HV side and at neutral point for serial-winding.
No.14-- [I_InstREF_Tr]
No.15-- [Slope_PcntREF_Tr]
No.16-- [TrpLog_REF_Tr]
No.17-- [V_Alm_ROV_LVS_Tr]
No.18-- [t_Alm_ROV_LVS_Tr]
No.19-- [En_VCE.ROC_Ctrl_ROC1_Tr]
No.20-- [En_VCE.ROC_Ctrl_ROC2_Tr]
No.21-- [En_Dir_Ctrl_ROC1_Tr]
No.22-- [En_Dir_Ctrl_ROC2_Tr]
No.23-- [En_Alm_ROV_LVS_Tr]
No.24-- [En_InstREF_Tr]
No.25-- [En_PcntREF_Tr]
Settings of earth fault protection of main transformer are accessible in the following path:
Main Menu -> SETTING -> PROT SETTINGS -> TR EF BAK PROT--> [setting symbol]
No.1-- [k_OvExc1_Tr]
U
B U gn
N = = = U ∗ / f∗ = 1.3 or data provided by the factory
Bn f
f gn
NO.2—[t_OvExc1_Tr]
NO.3—[TrpLog_OvExc1_Tr]
Tripping output logic setting of stage 1 of definite time over excitation protection of main
transformer. The function of this protection is used for islanding, excitation shutting or
programming, excitation reducing etc.
NO.4—[k_Alm_OvExc_Tr]
Setting of over excitation alarm of main transformer. Setting of alarm shall be lower than that of
over excitation protection. 1.1 is recommended.
NO.5—[t_Alm_OvExc_Tr]
NO.6—[k0_InvOvExc_Tr]
NO.7—[t0_InvOvExc_Tr]
Delay of upper limit of inverse time over excitation protection of main transformer.
NO.8—[k1_InvOvExc_Tr]
Inverse time over excitation factor1—n1. Setting range of various inverse time over excitation
coefficient s is 1.1 – 2.0. However setting of upper limit (NO.9) of over excitation factor n0 shall be
higher than that of over excitation factor1 n1, that of factor1 n1 shall be higher than that of factor2
n2, etc.. Finally, setting of over excitation factor6 n6 (NO.23) shall be higher than that of lower
limit.
NO.9—[t1_InvOvExc_Tr]
The range of delay of various inverse time over excitation protection stage is 0s to 6000 s,
ie.,0--50 min. Delay of upper limit (NO.10) of over excitation factor shall be shorter than that of
over excitation factor1, that of factor1 shall be shorter than that of factor2, etc.. Finally, delay of
over excitation factor6 (NO.22) shall be shorter than that of lower limit (NO.24).
NO.10—[k2_InvOvExc_Tr]
NO.11—[t2_InvOvExc_Tr]
NO.12—[k3_InvOvExc_Tr]
NO.13—[t3_InvOvExc_Tr]
NO.14—[k4_InvOvExc_Tr]
NO.15—[t4_InvOvExc_Tr]
NO.16—[k5_InvOvExc_Tr]
NO.17—[t5_InvOvExc_Tr]
NO.18—[k6_InvOvExc_Tr]
NO.19—[t6_InvOvExc_Tr]
NO.20—[k7_InvOvExc_Tr]
NO.21—[t7_InvOvExc_Tr]
NO.22—[TrpLog_InvOvExc_Tr]
Tripping output logic setting of inverse time over excitation protection of main transformer.
Settings of main transformer overexcitation protection are accessible in the following path:
Main Menu -> SETTINGS -> PROT SETTINGS -> TR OVEXC PROT --> [setting symbol]
Note:
The over excitation protection of generator-transformer unit comprises two over excitation
protection: generator over excitation protection and transformer over excitation protection.
Configuration of the generator over excitation protection shall be higher than over excitation
capability of generator, while that of transformer shall be higher than over excitation capability of
transformer. If only one set of over excitation protection is used, configuration of the lower one
shall be adopted.
Note:
Symbol of the parameters listed in above table are used for communication, printing and
displaying on LCD.
No.1-- [I_Pkp_PcntDiff_Gen]
This is pickup setting of percentage current differential protection, which is also the setting of fault
detector of percentage differential protection. It shall be higher than maximum unbalance current
when the generator operates on normal rated load, i.e.
Where:
I f 1n
I f 2n =
n fLH
Where:
Pn / cos θ
I f 1n =
3U f 1n
Where:
I unb.0 is the measured actual unbalance current during rated load of generator, 0.2 I f 2 n -0.3
Where:
No.2-- [I_InstDiff_Gen]
No.3-- [Slope1_PcntDiff_Gen]
Where:
No.4-- [Slope2_PcntDiff_Gen]
With type factor of CT not taken into account, the maximum unbalance current is, ,
Where:
K ap
is non periodic component factor, usually no less than 2.0;
I k . max is periodic component of secondary value of external three phase short circuit current and it
can be taken as 4 times of rated current if it is less than 4 times of rated current.
where:
I unb. max* , I cdqd * and I k . max* are all per unit value of rated current of generator;
If the percentage differential protection is configured based on rules mentioned above, when
phase-to-phase metallic short circuit fault occurs at the terminal of generator, sensitivity factor will
K sen ≥ 2 surely.
meet requirement
No.5-- [TrpLog_Diff_Gen]
Tripping output logic setting of differential protection is used to specify which breaker or breakers
will be tripped by this protection. This word comprises 16 binary bits as follows and is displayed as
a hexadecimal number of 4 digits from 0000H to FFFFH on LCD of equipment. The tripping output
logic settings is specified as follows:
bit 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0
Protection Enabled
TJ14: TrpOutp 14
TJ13: TrpOutp 13
TJ12: TrpOutp 12
TJ11: TrpOutp 11
TJ10: TrpOutp 10
TJ9: TrpOutp 9
TJ8: TrpOutp 8
TJ7: TrpOutp 7
TJ6: TrpOutp 6
TJ5: TrpOutp 5
TJ4: TrpOutp 4
TJ3: TrpOutp 3
TJ2: TrpOutp 2
TJ1: TrpOutp 1
No definition
Function
Note:
Set bit 0 as “1” means this protection element will trip breaker or breakers when operate. The bit
corresponding to the output channal shall be set as“1” and other bits shall be “0”. For example, if
differential protection is defined to trip output channel 5, the bit “0” and “5” bit shall be set as “1”
and other bits “0”. Then a hexadecimal number 0021H is formed as the tripping output logic
setting.
Please note that tripping output logic settings of the equipment have to be set on basis of
application-specific drawings.
All the tripping logic settings mentioned below is defined as same as this one.
No.6-- [En_InstDiff_Gen]
Unrestrained instantaneous differential protection enabled. If this setting is set as “1”, it means this
protection is enabled. Otherwise it means the protection is disabled.
No.7-- [En_PcntDiff_Gen]
No.8-- [En_DPFC_Diff_Gen]
No.9-- [Opt_CTS_Blk_PcntDiff_Gen]
If this logic setting is set as “1”, it means percentage differential protection will be blocked when CT
circuit failure take place. Otherwise it means the blocking function is disabled.
All settings of differential protection settings are accessible in the following path:
Main Menu -> SETTINGS -> PROT SETTINGS -> GEN DIFF PROT --> [setting symbol]
NO.1—[I_SensTrvDiff_Gen]
Setting of this protection shall be higher than maximum unbalance current during normal operation
condition. Reliability factor can be more than 2. The setting value is usually:
I op = 0.05 I f ln / na
(Equation 7.3-27)
Where:
I f ln
is primary rated current of generator and
NO.2—[I_UnsensTrvDiff_Gen]
I op =(0.20 ~ 0.30)I f ln / n a
(Equation 7.3-28)
Where:
I f ln
is primary rated current of generator and
NO.3—[t_TrvDiff_Gen]
Delay of transverse differential protection (act on only after the occurrence of one-point ground of
rotor).
When one point earth fault occurs within rotor of generator and one point earth fault protection
operates, in order to prevent unwanted operation of transverse protection due to instantaneous
two points earth fault within the rotor, operation of this protection shall be delayed for 0.5 s – 1 s.
Note:
When a turn-to-turn fault occurs, the equipment will trip relevant breakers without delay according
to the tripping output logic setting, but a time delay decided by user will act on after occurrence of
one-point ground of rotor.
NO.4—[V_SensROV_Longl_Gen]
Setting of this protection shall be higher than maximum unbalance voltage during normal
operation condition, usually:
U op = 0.5 - 3 V
(Equation 7.3-29)
At beginning of configuration, 2 – 3 V is preferred. After fault waveform analysis, the setting can be
reduced properly and sensitivity of the protection can be improved than.
NO.5—[V_UnsensROV_Longl_Gen]
Setting of this protection shall be higher than maximum unbalance voltage during external fault,
usually:
U op = 8 - 12 V
(Equation 7.3-30)
NO.6—[t_ROV_Longl_Gen]
Delay of longitudinal zero sequence overvoltage. Short delay 0.10 s – 0.20 s is recommended for
operation and output of this protection.
NO.7—[TrpLog_IntTurn_Gen]
NO.8—[En_SensTrvDiff_Gen]
NO.9—[En_UnsensTrvDiff_Gen]
NO.10—[En_SensROV_Longl_Gen]
NO.11—[En_UnsensROV_Longl_Gen]
NO.12—[En_DPFC_IntTurn_Gen]
Main Menu -> SETTINGS -> PROT SETTINGS -> GEN INTTURN PROT --> [setting symbol].
0,1
25. En_BO_UV&OC_Term_Gen 0
No.1-- [V_NegOV_VCE_Gen]
Negative sequence voltage setting of composite voltage control element. Setting and displayed
value of negative sequence voltage are U2.
Setting of negative sequence voltage relay shall be higher than unbalance voltage during normal
operation, generally
Sensitivity factor shall be checked by phase-to-phase short circuit fault on HV side bus of main
transformer:
U 2. min
K sen =
U op 2
(Equation 7.3-32)
Where:
U 2. min is minimum negative sequence voltage at location of the equipment during phase-to-phase
short circuit fault on HV side bus of main transformer. K sen ≥ 1.5 is required.
NO.2—[Vpp_UV_VCE_Gen]
U gn
Where is rated phase-to-phase voltage of generator.
Sensitivity factor shall be checked by three-phase short circuit fault on HV side bus of main
transformer:
U op
K sen =
X t × I k(3. max
)
(Equation 7.3-33)
I k( 3. max
)
Where is maximum secondary fault current during three-phase short circuit on HV side bus
NO.3—[I_OC1_Gen]
K rel
I op = I gn
Kr (Equation 7.3-34)
Where:
I gn
is secondary rated current of generator.
I k( 2. min
)
K sen =
I op
(Equation 7.3-35)
I k( .2min
)
Where is minimum fault current through location of the relay during phase-to-phase
NO.4—[t_OC1_Gen]
Time delay of overcurrent protection stage 1. Delay of this protection shall be higher than that of
operation of backup protection of step-up transformer. This protection is used for islanding and
generator shutting off.
NO.5—[TrpLog_OC1_Gen]
NO.6—[I_OC2_Gen]
Setting of overcurrent protection stage 2. Setting of overcurrent relay shall be higher than rated
current of transformer.
NO.7—[t_OC2_Gen]
NO.8—[TrpLog_OC2_Gen]
NO.9—[Z1_Fwd_Gen]
Positive direction impedance setting of distance protection stage1. Here positive direction means
the direction is pointing to the transformer instead of generator itself.
If the value of this setting is greater than the next one, then the characteristic of distance protection
is set as excursive impedance circle; if it is equal to the next one, the characteristic is whole
impedance circle; if the next one is set as “0”, the characteristic becomes directional impedance.
Generally, low impedance protection is considered as the backup protection of generator in case
that voltage-controlled overcurrent protection can’t satisfy the sensitivity requirement of generator.
NO.10—[Z1_Rev_Gen]
Negative direction impedance setting of distance protection stage1. In general, this setting is set
as 5-10% of the positive direction impedance setting.
NO.11—[t_Z1_Gen]
NO.12—[TrpLog_Z1_Gen]
NO.13—[Z2_Fwd_Gen]
NO.14—[Z2_Rev_Gen]
NO.15—[t_Z2_Gen]
NO.16—[TrpLog_Z2_Gen]
Tripping output logic setting of distance protection stage1. Please refer to the tripping output logic
setting of differential protection of main transformer for details.
NO.17—[I_BO_OC_Term_Gen]
NO.18—[t_BO_OC_Term_Gen]
Time delay setting of overcurrent element for controlling function of a set of contact.
NO.19—[En_VCE_Ctrl_OC1_Gen]
NO.20—[En_VCE_Ctrl_OC2_Gen]
NO.21—[En_HVS.VCE_Ctrl_OC_Gen]
Enable controlling function to overcurrent protection by Composite Voltage Element from HVS of
transformer.
NO.22—[Opt_VTS_Ctrl_OC_Gen]
“1”: when VT circuit failure at one side is detected, composite voltage element will be disabled if
corresponding logic setting is set as “1”.
“0”: when VT circuit failure at one side is detected, the voltage-controlled overcurrent element will
become a pure overcurrent relay without composite voltage element controlling.
NO.23—[En_Mem_Curr_Gen]
That the setting is set as “1” indicates the excitation mode of generator is self shunt excitation
mode. In that case, the protection will remember the current value at the initiation of fault, and
operates based on it, no matter whether the current will decrease due to the descending excitation
voltage result from terminal voltage’s getting down when external fault occurs. Once this setting is
set as “1”, the backup overcurrent protection of generator is always controlled by composite
voltage element.
NO.24—[En_BO_OC_Term_Gen]
Note:
In the above Table,current used in backup protection of generator comes from the backup current
input channel.
Settings of generator phase-to-phase backup protection are accessible in the following path:
Main Menu -> SETTINGS -> PROT SETTINGS -> GEN PPF BAK PROT --> [setting symbol].
No.1-- [V_SensROV_Sta]
Krel is reliability factor, 1.2 – 1.3 generally; Uunb. max is the maximum measured
Where
fundamental unbalance zero sequence voltage derived from single VT at the neutral point of
generator.
To assure its security, user should check the transferred zero sequence voltage through coupling
capacitance between HV side and LV side of transformer when external earth fault occurs on the
HV side of the transformer. Meanwhile, settings, including time delay and operation setting, should
be considered to cooperate with that of earth fault protection of the system.
Note:
The zero sequence voltage used in this protection comes from VT at the neutral point of generator.
NO.2—[V_UnsensROV_Sta]
Only zero sequence voltage at neutral point is taken for high setting zone of fundamental zero
sequence voltage protection. Its setting is usually 20 V – 25 V.
Zero sequence voltage transferred by coupling capacitance per phase between HV and LV side
windings of step-up transformer shall be checked when external fault occurs at HV side of the
transformer. Coordination both on setting and delay between this protection and system earth fault
protection could be achieved then.
NO.3—[t_ROV_Sta]
NO.4—[k_V3rdHRatio_PreSync_Sta]
• •
Let third harmonic voltage at the end and neutral point of generator be Ut and Un , ratio setting of
third harmonic voltage percentage earth fault protection shall be
• •
Ut Un > α
(Equation 7.3-37)
3 × nTVN
and α = K rel during pre-configuration,
nTV 0
Where:
U 3T / U 3N
During incorporation of generator to power system, the ratio changes considerably
owing to variation of equivalent capacitive reactance at generator terminal. So two different
settings are designed for protection before and after connection of generator with system, and
these two settings can be switched over with alternation of contacts’ position of the terminal
breaker.
The setting shall be (1.3 – 1.5)× α 1 before incorporation and (1.3 – 1.5)× α 2 after that.
Where α 1 and α 2 are the maximum real-measured third harmonic voltage ratio before and
NO.5—[k_V3rdHRatio_PostSync_Sta]
NO.6—[k_V3rdHDiff_Sta]
• • • •
U t − k p U n > k zd U n
(Equation 7.3-38)
Where:
•
kp
is vectorial automatic tracing regulation factor;
NO.7—[t_V3rdH_Sta]
Delay of percentage third harmonic voltage earth fault protection. It shall be longer than that of
backup protection against external fault .
NO.8—[TrpLog_EF_Sta]
NO.9—[En_Alm_ROV_Sta]
NO.10—[En_Trp_ROV_Sta]
NO.11—[En_Alm_V3rdHRatio_Sta]
NO.12—[En_Alm_V3rdHDiff_Sta]
NO.13—[En_Trp_V3rdHRatio_Sta]
NO.14—[En_Trp_UnsensRov_Sta]
Settings of stator earth fault protection are accessible in the following path:
Main Menu -> SETTINGS -> PROT SETTINGS -> STA EF PROT --> [setting symbol].
NO.1—[R_Sens1PEF_RotWdg]
General specification of generator specifies that insulation resistance of its excitation winding shall
be higher than 1 MΩ for air cooled and hydrogen-cooled turbine generator during cooling state,
and 2 kΩ for water cooled excitation winding. General specification of hydro-generator specifies
that insulation resistance of its excitation winding shall be higher than 0.5 kΩ in any case.
Sensitive stage of this protection is used for alarm. Its setting could be 20 kΩ – 80 kΩ generally.
NO.2—[R_1PEF_RotWdg]
Setting of one point earth fault protection can be 20 kΩ for air cooled and hydrogen-cooled turbine
generator and 2.5 kΩ for water cooled excitation winding. This protection can be used for alarm
or generator shutting with delay.
NO.3—[t_1PEF_RotWdg]
NO.4--[V2ndH_VCE_2PEF_RotWdg]
NO.5—[t_2PEF_RotWdg]
NO.6—[TrpLog_EF_RotWdg]
NO.7—[En_Alm_Sens1PEF_RotWdg]
Enable alarm function of sensitive stage of one-point earth fault protection of rotor.
NO.8—[En_Alm_1PEF_RotWdg]
NO.9—[En_Trp_1PEF_RotWdg]
NO.10—[En_2PEF_RotWdg]
NO.11—[En_VCE_2PEF_RotWdg]
Settings of rotor earth fault protection are accessible in the following path:
Main Menu -> SETTINGS -> PROT SETTINGS -> ROTWDG EF PROT --> [setting symbol].
NO.1—[I_OvLd_Sta]
Setting of this protection is determined by the requirement of reliable release during permissive
continuous load current of generator.
I gn
I OP = K rel
Kr (Equation 7.3-39)
Where:
Ign
is secondary rated current of generator.
Delay of this protection shall be longer than maximum delay of backup protection. Alarm will be
issued or load will be reduced when it operates.
NO.2—[t_OvLd_Sta]
NO.3—[TrpLog_OvLd_Sta]
NO.4-- [I_Alm_OvLd_Sta]
NO.5—[t_Alm_OvLd_Sta]
NO.6—[I_InvOvLd_Sta]
Characteristic of this protection is indefinite time relationship between multiple of load current and
corresponding permissive duration which is determined by permissive overload capability of stator
provided by the factory.
K tc
t=
I *2 − K sr2
(Equation 7.3-40)
Where:
Minimum delay for upper limit of this protection shall coordinate with unrestraint protection.
Current setting of lower limit of this protection shall coordinate with definite time overload
protection mentioned above, namely
I gn
I OP. min = K c 0 K rel
Kr (Equation 7.3-41)
NO.7—[tmin_InvOvLd_Sta]
NO.8—[A_Therm_Sta]
NO.9—[K_Disspt_Sta]
NO.10—[TrpLog_InvOvLd_Sta]
Main Menu -> SETTINGS -> PROT SETTINGS -> STA OVLD PROT --> [setting symbol].
NO.1—[I_NegOC_Gen]
Setting of this protection is determined by the threshold under which this protection can release
reliably, that threshold value is continuously permissive negative sequence current I 2∞ . So,
I 2∞ I gn
I OP = K rel
Kr (Equation 7.3-42)
Where:
Ign
is secondary rated current of generator.
NO.2—[t_NegOC_Gen]
Delay of this protection shall be longer than maximum delay of backup protection. Alarm will be
issued when it operates.
NO.3—[TrpLog_NegOC_Gen]
NO.4—[I_Alm_NegOC_Gen]
NO.5—[t_Alm_NegOC_Gen]
NO.6—[I_InvNegOC_Gen]
A
t=
I 22* − I 22∞ (Equation 7.3-43)
Where:
Minimum delay for upper limit of this protection shall coordinate with unrestraint protection.
NO.7—[I_Neg_Perm_Gen]
Permitted continuous currents of inverse time negative sequence overcurrent protection for lasting
operation.
Current setting of lower limit of this protection shall be the operating current corresponding to
delay 1000 s, namely
A
I OP. min = + I 22∞
1000 (Equation 7.3-44)
NO.8—[tmin_InvNegOC_Gen]
Delay of upper limit of inverse negative sequence overcurrent protection. Minimum delay for upper
limit of this protection shall coordinate with unrestraint protection.
NO.9—[A_Therm_Rotbody]
NO.10—[TrpLog_InvNegOC_Gen]
Tripping output logic setting of inverse time negative sequence overcurrent protection.
Settings of stator negative sequence overcurrent protection are accessible in the following path:
Main Menu -> SETTINGS -> PROT SETTINGS -> GEN NEGOC PROT --> [setting symbol].
NO.1—[X1_LossExc_Gen]
jx
Xc
R
Xa
Xb
X b . Here
X d' U gn × n a
2
Xa =− ×
2 S gn × n v
(Equation 7.3-45)
X' U gn × n a
2
X b = −( X d + d ) ×
2 S gn × nv
(Equation 7.3-46)
Where:
'
Xd and Xd are unsaturated per unit value of transient reactance and synchronous reactance of
generator,
Ugn Sgn
and are rated voltage and rated apparent power of generator;
X b , here
2
U gn × na
Xc = Xs ×
S gn × n v
(Equation 7.3-47)
X d'
2
U gn × na
X b = −( X d + )×
2 S gn × nv
(Equation 7.3-48)
Where:
Xs is equivalent reactance on system side (including step-up transformer) connected with the
generator (per unit value, reference capacity is apparent power of the generator).
Asynchronous impedance circle and steady state stability limit circle can be selected by logic
setting [Impedance Circle Option] (No. 24).
For practical project, impedance between asynchronous impedance circle and steady state
stability limit circle can be selected for optimal combination of reliability and speed.
NO.2—[X2_LossExc_Gen]
NO.3—[Q_RevQ_LossExc_Gen]
Q jx
Q zd = K rel ×
Pgn
(Equation 7.3-49)
Where:
Qjx
is permissive incoming reactive power to the generator;
Pgn
is rated active power of the generator.
NO.4—[V_RotUV_LossExc_Gen]
Low voltage setting of rotor. There are two low voltages setting of rotor, they are
U fd .op = K rel × U fd 0
(Equation 7.3-50)
Where:
U fd .op
is this setting.
U fd0
is rated excitation voltage of the generator without load, i.e. NO.5 setting.
U fd0
For a generator connecting with power system, there is a necessary excitation voltage for
keeping steady state stability.
P − Pt
U fd .op ≤ K xs × U fd 0 ×
Sn (Equation 7.3-51)
Where:
Xd Xs
and are per unit value of synchronous reactance of generator and equivalent reactance of
system connecting with the generator (referred to rated capacity of the generator);
U fd0
is rated excitation voltage of generator without load;
NO.5—[V_RotNoLoad_LossExc_Gen]
NO.6—[k_RotUV_LossExc_Gen]
NO.7—[V_BusUV_LossExc_Gen]
This criterion is used mainly to prevent voltage collapse due to loss of excitation of generator for a
system without enough spare reactive power. Voltage on bus of system side is adopted for this
criterion.
Where:
This criterion can also be configured as 0.85 – 0.90 times of terminal voltage of generator.
NO.8—[P_OvPwr_LossExc_Gen]
Power setting for reducing power output. This criterion is configured as 40% - 50% of rated
capacity of the generator.
NO.9—[t_LossExc1_Gen]
NO.10—[t_LossExc2_Gen]
NO.11—[t_LossExc3_Gen]
NO.12—[TrpLog_LossExc1_Gen]
NO.13—[TrpLog_LossExc2_Gen]
NO.14—[TrpLog_LossExc3_Gen]
NO.15—[En_Z_LossExc1_Gen]
NO.16—[En_RotUV_LossExc1_Gen]
NO.17—[En_P_LossExc1_Gen]
NO.18—[En_UV_LossExc2_Gen]
Enable the low voltage criterion of busbar or generator terminal in loss-of-excitation protection
stage2
NO.19—[En_Z_LossExc2_Gen]
NO.20—[En_RotUV_LossExc2_Gen]
NO.21—[En_Z_LossExc3_Gen]
NO.22—[En_RotUV_LossExc3_Gen]
NO.23—[En_Alm_LossExc1_Gen]
NO.24—[Opt_Z_LossExc_Gen]
NO.25—[En_RevQ_LossExc_Gen]
NO.26—[Opt_UV_LossExc_Gen]
Note:
Main Menu -> SETTINGS -> PROT SETTINGS -> GEN LOSSEXC PROT --> [setting symbol].
Out-of-step protection operates only when out-of-step occurs in power system. Then, based on
situation at that time, the dispatching center will adopt islanding, generator shutting or restraint and
other necessary measures. Only if center of oscillation situates within the generator or near the
generator, or the oscillation lasts too long, and phase difference of electro-motive force between
two sides of the breaker less than 90°, this protection will trip.
Characteristic of this protection comprises three parts: lens part ②, boundary part ① and
reactance line part ③. See the following figure.
jx
Za
U
D
Zc 3
OL
IL
1 α IR
φ OR
0
R
1
Zb
2
L R
NO.1—[Za_OOS_Gen]
Refer to Figure 7.3-2, this setting can be set by means of the following formula.
2
U gn × na
Za = (X S + XC ) ×
S gn × nv (Equation 7.3-54)
Where:
Ugn Sgn
and are rated voltage and rated apparent power of generator;
NO.2—[Zb_OOS_Gen]
Refer to figure 7.3.2, this setting can be set by means of the following formula.
2
U gn × na
Zb = − X × '
S gn × nv
d
(Equation 7.3-55)
Where:
NO.3—[Zc_OOS_Gen]
Impedance setting C of out-of-step protection. Reactance line is the dividing line of oscillation
center. Refer to Figure 7.3-2, this setting can be set by means of the following formula. In practice,
0.9 times of transformer impedance is recommended.
2
U gn × na
Z c = 0.9 × X c ×
S gn × nv
(Equation 7.3-56)
NO.4—[φ_Reach_OOS_Gen]
NO.5—[φ_Inner_OOS_Gen]
2Z r
α = 180° − 2 arctan
Z a + Zb
1
Zr ≤ RL . min
1.3 (Equation 7.3-57)
NO.6—[n_Slip_Ext_OOS_Gen]
Pole sliding number setting for external fault of generator. When the oscillation center situates
outside the protected section, times of pole sliding shall be set as 2 – 15 for alarm and more than
15 for tripping.
NO.7—[n_Slip_Int_OOS_Gen]
Pole sliding number setting for internal fault of generator. When the oscillation center situates
within the protected section, time of pole sliding shall be set as 1-2 in general.
NO.8—[Ibrk_CB_HVS_Tr]
NO.9—[TrpLog_OOS_Gen]
NO.10—[En_Alm_Ext_OOS_Gen]
NO.11—[En_Trp_Ext_OOS_Gen]
NO.12—[En_Alm_Int_OOS_Gen]
NO.13—[En_Trp_Int_OOS_Gen]
Main Menu -> SETTINGS -> PROT SETTINGS -> GEN OOS PROT --> [setting symbol].
NO.1—[V_OV1_Gen]
Setting of overvoltage protection of stator shall base on permissive overvoltage capability provided
by the factory or insulation condition of the stator.
U op = 1.3U gn
(Equation 7.3-58)
Where:
U gn
is the secondary rated phase-to-phase voltage.
This is used for islanding and excitation shutting with delay 0.5 s.
For hydro-generator,
U op = 1.5U gn
(Equation 7.3-59)
This is used for islanding and excitation shutting with delay 0.5 s.
U op = 1.3U gn
(Equation 7.3-60)
This is used for islanding and excitation shutting with delay 0.3 s.
NO.2—[t_OV1_Gen]
NO.3—[TrpLog_OV1_Gen]
NO.4—[V_OV2_Gen]
NO.5—[t_OV2_Gen]
NO.6—[TrpLog_OV2_Gen]
NO.7—[V_UV_Gen]
NO.8—[t_UV_Gen]
NO.9—[TrpLog_UV_Gen]
Main Menu -> SETTINGS -> PROT SETTINGS -> GEN VOLT PROT --> [setting symbol].
NO.1—[k_OvExc1_Gen]
U
B U gn
N = = = U ∗ / f∗ = 1.3 or data provided by the factory
Bn f
f gn
NO.2—[t_OvExc1_Gen]
NO.3—[TrpLog_OvExc1_Gen]
Tripping output logic setting of stage 1 of definite time over excitation protection. The function of
this protection is used for islanding, excitation shutting or programming, excitation reducing etc.
NO.4—[k_Alm_OvExc_Gen]
Setting of over excitation alarm. Setting of alarm shall be lower than that of over excitation
protection. 1.1 is recommended.
NO.5—[t_Alm_OvExc_Gen]
NO.6—[k0_InvOvExc_Gen]
NO.7—[t0_InvOvExc_Gen]
NO.8—[k1_InvOvExc_Gen]
Inverse time over excitation factor1—n1. Setting range of various inverse time over excitation
coefficient s is 1.0 – 2.0. However setting of upper limit (NO.9) of over excitation factor n0 shall be
higher than that of over excitation factor1 n1, that of factor1 n1 shall be higher than that of factor2
n2, etc. Finally, setting of over excitation factor6 n6 (NO.21) shall be higher than that of lower
limit.
NO.9—[t1_InvOvExc_Gen]
The range of delay of various inverse time over excitation protection stage is 1s to 3000 s,
ie.,0--50 min. Delay of upper limit (NO.10) of over excitation factor shall be shorter than that of
over excitation factor1, that of factor1 shall be shorter than that of factor2, etc.. Finally, delay of
over excitation factor6 (NO.22) shall be shorter than that of lower limit (NO.24).
NO.10—[k2_InvOvExc_Gen]
NO.11—[t2_InvOvExc_Gen]
NO.12—[k3_InvOvExc_Gen]
NO.13—[t3_InvOvExc_Gen]
NO.14—[k4_InvOvExc_Gen]
NO.15—[t4_InvOvExc_Gen]
NO.16—[k5_InvOvExc_Gen]
NO.17—[t5_InvOvExc_Gen]
NO.18—[k6_InvOvExc_Gen]
NO.19—[t6_InvOvExc_Gen]
NO.20—[k7_InvOvExc_Gen]
NO.21—[t7_InvOvExc_Gen]
NO.22—[TrpLog_InvOvExc_Gen]
Main Menu -> SETTINGS -> PROT SETTINGS -> GEN OVEXC PROT --> [setting symbol]
NO.1—[P_RevP_Gen]
Pop = K rel ( P1 + P2 )
(Equation 7.3-61)
Where:
P1 is minimum loss of turbine during reverse power operation, 2% - 4% of rated power generally;
Pgn
is rated power of generator.
Pop
is set as 1% - 2% of rated active power generally, and 1% is recommended.
NO.2—[t_Alm_RevP_Gen]
Delay of reverse power alarm. For reverse power protection without steam valve contact blocking,
delay 15 s for alarm.
NO.3—[t_Trp_RevP_Gen]
Delay of reverse power protection. For reverse power protection without steam valve contact
blocking, according to permissive operation time of reverse power, delay 1 min – 3 min is set for
islanding in general.
For program reverse power protection with steam valve contact blocking, delay 0.5 s – 1.00 s is
set for islanding.
NO.4—[TrpLog_RevP_Gen]
NO.5—[P_UP_Gen]
NO.6—[t_UP_Gen]
NO.7—[TrpLog_UP_Gen]
NO.8—[P_SeqTrpRevP_Gen]
NO.9—[t_SeqTrpRevP_Gen]
For sequent-tripping reverse power protection with steam valve contact blocking, delay 0.5 s –
1.00 s for islanding.
NO.10—[TrpLog_SeqTrpRevP_Gen]
Main Menu -> SETTINGS -> PROT SETTINGS -> GEN PWR PROT --> [setting symbol].
NO.1—[f_UF1_Gen]
Permissive range of frequency during operation for large turbo-generator with capacity more than
300 MW is 48.5 Hz – 50.5 Hz.
Recommended permissive operation time of abnormal frequency for large generator is as follows.
Three stages of under frequency protection are provided in which function of accumulated
operating time is equipped for stage 1(NO.2 setting).
Two zones of over frequency protection are provided, in which no function of accumulated
operating time is equipped.
Each zone can be used for alarm or tripping by configuration of logic setting.
NO.2—[t_UF1_Gen]
NO.3—[f_UF2_Gen]
NO.4-- [t_UF2_Gen]
NO.5—[f_UF3_Gen]
NO.6—[t_UF3_Gen]
NO.7—[TrpLog_UF_Gen]
NO.8—[f_OF1_Gen]
NO.9—[t_OF1_Gen]
NO.10—[f_OF2_Gen]
NO.11—[t_OF2_Gen]
NO.12—[TrpLog_OF_Gen]
NO.13—[En_Alm_UF1_Gen]
NO.14—[En_Trp_UF1_Gen]
NO.15—[En_Alm_UF2_Gen]
NO.16—[En_Trp_UF2_Gen]
NO.17—[En_Alm_UF3_Gen]
NO.18—[En_Trp_UF3_Gen]
NO.19—[En_Alm_OF1_Gen]
NO.20—[En_Trp_OF1_Gen]
NO.21—[En_Alm_OF2_Gen]
NO.22—[En_Trp_OF2_Gen]
Main Menu -> SETTINGS -> PROT SETTINGS -> GEN FREQ PROT --> [setting symbol].
NO.1—[f_UF_StShut_Gen]
Startup and shutdown protection is used for earth fault and phase-to-phase fault of stator during
low speed operation of the generator. Its algorithm is insensitive to variation of frequency.
This protection is auxiliary protection of generator during low frequency operation. Blocking
setting of this protection is 0.8 – 0.9 times of rated frequency.
NO.2—[I_TrDiff_StShut_Gen]
Differential current setting for the differential protection of main transformer in startup/shutdown
condition.
For phase-to-phase fault, differential current protection is used. The equipment comprises
differential current protection of generator, main transformer and stepdown transformer.
Setting of this protection during rated frequency shall be higher than imbalance current in
differential circuit during full load operation,
I op = K rel I unb
(Equation 7.3-62)
Where:
Iunb is imbalance current in differential circuit during full load operation during rated frequency.
NO.3—[I_GenDiff_StShut_Gen]
Differential current setting for the differential protection of generator in startup and shutdown
condition. Setting of this protection shall be higher than unbalance differential current in full load
and rated frequency condition,
I op = K rel I unb
(Equation 7.3-63)
Where:
Iunb
is the unbalance differential current in full load and rated frequency condition.
NO.4—[TrpLog_Diff_StShut_Gen]
Tripping output logic setting of low frequency differential protection of generator in startup and
shutdown condition.
NO.5—[V_StaROV_StShut_Gen]
Zero sequence voltage setting of stator earth fault protection in startup and shutdown condition.
For earth fault, zero sequence voltage derived from neutral point is adopted as criterion with
setting 10 V in general and delay not shorter than that of fundamental zero sequence voltage earth
NO.6—[t_StaROV_StShut_Gen]
NO.7—[TrpLog_StaROV_StShut_Gen]
Tripping output logic setting of stator earth fault protection in startup and shutdown condition.
NO.8—[En_TrDiff_StShut_Gen]
NO.9—[En_GenDiff_StShut_Gen]
NO.10—[En_StaROV_StShut_Gen]
NO.11—[En_UF_Ctrl_StShut_Gen]
Enable low frequency element as blocking criterion in startup&shutup protection logic of generator.
Settings of generator startup and shutdown protection are accessible in the following path:
Main Menu -> SETTINGS -> PROT SETTINGS -> GEN STSHUT PROT --> [setting symbol].
NO.1—[f_UF_AccEnerg_Gen]
Frequency blocking setting shall be 80% - 90% of the rated frequency, i.e., 40 Hz – 45 Hz.
NO.2—[I_OC_AccEnerg_Gen]
Current setting shall be 50% of minimum accidental closing current (generator terminal side)
during process of generator starting up but having not been excited. If accidental closing current of
circuit breaker on auxiliary transformer side shall be taken into account, current setting shall base
on minimum accidental closing current during this condition. The current used for this setting is
derived from the CT at the terminal of generator.
In general, this setting shall be in excess of 1.3 times of rated current of generator.
NO.3—[t_AccEnerg_Gen]
NO.4—[TrpLog_AccEnerg_Gen]
NO.5—[I_NegOC_Flash_CB_HVS_Tr]
This setting shall be higher than possible unbalance current during normal operation. It must be
set according to the secondary current of the CT at the HV side of main transformer.
NO.6—[t_Flash1_CB_HVS_Tr]
NO.7—[TrpLog_Flash1_CB_HVS_Tr]
If impulse current may be higher than capacity of circuit breaker during asynchronous closing, the
protection shall shut off the excitation firstly. If current passing through circuit breaker is lower than
permissive value, the protection can trip the circuit breaker on outlet.
Permissive tripping current of circuit breaker shall be configured as that provided by factory.
NO.8—[En_UF_Ctrl_AccEnerg_Gen]
NO.9—[En_CB_Ctrl_AccEnerg_Gen]
Settings of generator accidental energization protection are accessible in the following path:
Main Menu -> SETTINGS -> PROT SETTINGS -> GEN ACCENERG PROT --> [setting symbol].
NO.1—[I_Pkp_PcntDiff_ST1(2)]
NO.2—[I_InstDiff_ST1(2)]
NO.3—[Slope1_PcntDiff_ST1(2)]
NO.4—[Slope2_PcntDiff_ST1(2)]
NO.5—[k_Harm_PcntDiff_ST1(2)]
NO.6—[TrpLog_Diff_ST1(2)]
NO.7—[En_InstDiff_ST1(2)]
NO.8—[En_PcntDiff_ST1(2)]
NO.9—[Opt_Inrush_Ident_ST1(2)]
NO.10—[Opt_CTS_Blk_PcntDiff_ST1(2)]
Settings of stepdown transformer differential protection are accessible in the following path:
Main Menu -> SETTINGS -> PROT SETTINGS -> ST DIFF PROT --> [setting symbol].
NO.1—[V_NegOV_VCE_HVS_ST1(2)]
Negative sequence voltage setting of composite voltage control element at HVS of stepdown
transformer.
NO.2—[Vpp_UV_VCE_HVS_ST1(2)]
NO.3—[I_OC1_HVS_ST1(2)]
NO.4—[t_OC1_HVS_ST1(2)]
NO.5—[TrpLog_OC1_HVS_ST1(2)]
NO.6—[I_OC2_HVS_ST1(2)]
NO.7—[t_OC2_HVS_ST1(2)]
NO.8—[TrpLog_OC2_HVS_ST1(2)]
NO.9—[I_Alm_OvLd_HVS_ST1(2)]
NO.10—[t_Alm_OvLd_HVS_ST1(2)]
NO.11—[I_InitCool_OvLd_HVS_ST1(2)]
NO.12—[t_InitCool_OvLd_HVS_ST1(2)]
NO.13—[I_BO_OC_HVS_ST1(2)]
NO.14—[t_BO_OC_HVS_ST1(2)]
NO.15—[En_VCE_Ctrl_OC1_ HVS_ST1(2)]
NO.16—[En_VCE_Ctrl_OC2_ HVS_ST1(2)]
NO.17—[En_Mem_Curr_ HVS_ST1(2)]
NO.18—[Opt_VTS_Ctrl_OC_HVS_ST1(2)]
“1”: when VT circuit failure at one side is detected, voltage control element at the same side will be
disabled but overcurrent relay on the same side can still be controlled by voltage control elements
of other side if corresponding logic setting is set as “1”.
“0”: when VT circuit failure at one side is detected, the overcurrent relay will become an
overcurrent relay without voltage element control.
NO.19—[En_Alm_OvLd_HVS_ST1(2)]
NO.20—[En_InitCool_OvLd_HVS_ST1(2)]
NO.21—[En_BO_OC_HVS_ST1(2)]
NO.22—[En_LVSProt_Blk_OC1_HVS_ST1(2)]
Settings of HVS backup protection of stepdown transformer are accessible in the following path:
Main Menu -> SETTINGS -> PROT SETTINGS -> ST1(2) HVS BAK PROT --> [setting symbol].
NO.1—[V_NegOV_VCE_Br1_ST1(2)]
Negative sequence voltage setting of composite voltage control element of branch 1 of stepdown
transformer.
NO.2—[Vpp_UV_VCE_Br1_ST1(2)]
NO.3—[I_OC1_Br1_ST1(2)]
NO.4—[t_OC1_Br1_ST1(2)]
NO.5—[TrpLog_OC1_Br1_ST1(2)]
NO.6—[I_OC2_Br1_ST1(2)]
NO.7—[t_OC2_Br1_ST1(2)]
NO.8—[TrpLog_OC2_Br1_ST1(2)]
NO.9—[I_ROC1_Br1_ST1(2)]
NO.10—[t_ROC1_Br1_ST1(2)]
NO.11—[TrpLog_ROC1_Br1_ST1(2)]
Tripping output logic setting of definite time zero sequence overcurrent protection stage1.
NO.12—[I_ROC2_Br1_ST1(2)]
NO.13—[t_ROC2_Br1_ST1(2)]
NO.14—[TrpLog_ROC2_Br1_ST1(2)]
Tripping output logic setting of definite time zero sequence overcurrent protection stage2.
NO.15—[En_VCE_Ctrl_OC1_ Br1_ST1(2)]
NO.16—[En_VCE_Ctrl_OC2_ Br1_ST1(2)]
NO.17—[Opt_VTS_Ctrl_OC_Br1_ST1(2)]
“1”: when VT circuit failure at one side is detected, voltage control element at the same side will be
disabled but overcurrent relay on the same side can still be controlled by voltage control elements
of other side if corresponding logic setting is set as “1”.
“0”: when VT circuit failure at one side is detected, the overcurrent relay will become an
Settings of LVS backup protection of stepdown transformer are accessible in the following path:
Main Menu -> SETTINGS -> PROT SETTINGS -> ST Br1 BAK PROT --> [setting symbol].
Table 7.3-24 List of restrict earth fault protection settings of stepdown transformer
NO.1—[I_Alm_REF_ST1(2)]
Setting of zero sequence differential current alarm. This setting shall be greater than the maximum
zero sequence unbalance differential current in normal operation condition meanwhile smaller
than REF pickup value.
No.2-- [I_Pkp_PcntREF_ST1(2)]
No.3-- [I_InstREF_ST1(2)]
No.4-- [Slope_PcntREF_ST1(2)]
No.5-- [TrpLog_REF_ST1(2)]
NO.6—[En_InstREF_ST1(2)]
NO.7—[En_PcntREF_ST1(2)]
Settings of restrict earth fault protection are accessible in the following path:
Main Menu -> SETTINGS -> PROT SETTINGS -> ST REF PROT --> [setting symbol].
NO.1—[I_Pkp_PcntDiff_Exc]
NO.2—[I_InstDiff_Exc]
NO.3—[Slope1_PcntDiff_Exc]
NO.4—[Slope2_PcntDiff_Exc]
NO.5—[k_Harm_PcntDiff_Exc]
NO.6—[TrpLog_Diff_Exc]
NO.7—[En_InstDiff_Exc]
NO.8—[En_PcntDiff_Exc]
NO.9—[Opt_Inrush_Ident_Exc]
NO.10—[Opt_CTS_Blk_PcntDiff_Exc]
Main Menu -> SETTINGS -> PROT SETTINGS -> EXC DIFF PROT --> [setting symbol].
NO.1—[I_OC1_Exc]
288 NANJING NARI-RELAYS ELECTRIC CO., LTD
Chapter7 Settings
NO.2—[t_OC1_Exc]
NO.3—[TrpLog_OC1_Exc]
NO.4—[I_OC2_Exc]
NO.5—[t_OC2_Exc]
NO.6—[TrpLog_OC2_Exc]
Main Menu -> SETTINGS -> PROT SETTINGS -> EXC BAK PROT --> [setting symbol].
Note:
The current used in the overcurrent protection is derived from the CT at the HV side of excitation
transformer or the CT at the neutral point of exciter.
NO.1—[I_Alm_OvLd_RotWdg]
NO.2—[t_Alm_OvLd_RotWdg]
NO.3—[I_InvOvLd_RotWdg]
NO.4—[tmin_InvOvLd_RotWdg]
NO.5—[A_Therm_RotWdg]
NO.6—[Ib_InvOvLd_RotWdg]
NO.7—[TrpLog_InvOvLd_RotWdg]
NO.8—[Opt_AC_Input_RotWdg]
Type selection configuration logic setting of current input. “1” is AC current input for overload
protection of rotor winding.
NO.9—[Opt_DC_Input_RotWdg]
Type selection configuration logic setting of current input. “1” is DC current input for overload
protection of rotor winding.
Main Menu -> SETTINGS -> PROT SETTINGS -> EXC BAK PROT --> [setting symbol].
NO.1—[t_MechRly1]
NO.2—[TrpLog_MechRly1]
NO.3—[t_MechRly2]
NO.4—[TrpLog_MechRly2]
NO.5—[t_MechRly3]
NO.6—[TrpLog_MechRly3]
NO.7—[t_MechRly4]
NO.8—[TrpLog_MechRly4]
NO.9—[En_Supv_MechRly]
Main Menu -> SETTINGS -> PROT SETTINGS -> MECH RLY PROT --> [setting symbol].
No.1-- [I1b_SnTr_CT_HVS_Tr]
Sn
Primary rated current at HV side of main transformer. The equation is I b1n = . Please
3U b1n
refer to section 3.4.1 to see more details.
No.2-- [I1b_SnTr_CT_LVS_Tr]
No.3-- [I1b_SnGen_CT_Gen]
Pn / cos θ
Primary rated current of generator. The equation is I f 1n = . Please refer to section 3.4.2
3U f 1n
No.4-- [I1b_SnST_CT_HVS_ST1]
No.5-- [I1b_SnST_CT_Br1_ST1]
No.6-- [I1b_SnST_CT_Br2_ST1]
No.7-- [I1b_SnST_CT_HVS_ST2]
No.8-- [I1b_SnST_CT_Br1_ST2]
No.9-- [I1b_SnST_CT_Br2_ST2]
No.10-- [I1b_SnExc_CT_S1_Exc]
No.11-- [I1b_SnExc_CT_S2_Exc]
Primary rated current at LV side of excitation transformer or neutral point side of exciter.
All settings of calculated primary rated current are accessible in the following path:
Main Menu -> SETTINGS -> CALC SETTINGS -> PRI RATED CURR -> [setting symbol]
No.1-- [I2b_SnTr_CT_HVS_Tr]
I b1n
Secondary rated current at HVS of main transformer. The equation is I b 2 n = . Please refer to
nbLH
section 3.4.1 to see more details.
No.2-- [I2b_SnTr_CT_LVS_Tr]
No.3-- [I2b_SnTr_CT_ST1]
No.4-- [I2b_SnTr_CT_ST2]
No.5-- [I2b_SnTr_CT_Bak_HVS_Tr]
No.6-- [I2b_SnTr_CT_Gen_GTU]
No.7-- [I2b_SnTr_CT_ST1_GTU]
Secondary rated current at HVS of stepdown transformer1. It is used for differential protection of
generator-transformer unit.
No.8-- [I2b_SnTr_CT_ST2_GTU]
Secondary rated current at HVS of stepdown transformer2. It is used for differential protection of
generator-transformer unit.
No.9-- [I2b_SnGen_CT_Term_Gen]
No.10-- [I2b_SnGen_CT_NP_Gen]
294 NANJING NARI-RELAYS ELECTRIC CO., LTD
Chapter7 Settings
No.11-- [I2b_SnST_CT_HVS_ST1]
No.12-- [I2b_SnST_CT_Br1_ST1]
No.13-- [I2b_SnST_CT_Br2_ST1]
No.14-- [I2b_SnST_CT_HVS_ST2]
No.15-- [I2b_SnST_CT_Br1_ST2]
No.16-- [I2b_SnST_CT_Br2_ST2]
No.17-- [I2b_SnExc_CT_S1_Exc]
No.18-- [I2b_SnExc_CT_S2_Exc]
Secondary rated current at LV side of excitation transformer or neutral point side of exciter.
No.1-- [V2b_VT_HVS_Tr]
No.3-- [U2b_VT_Term_Gen]
No.4-- [U2b_DeltVT_Term_Gen]
No.5-- [U2b_NP_Gen]
No.6-- [k_DeltVT_Gen]
The ratio of zero sequence voltage between terminal and neutral point of generator. That is the
ratio between [U2b_DeltVT_Term_Gen] to [U2b_NP_Gen].
No.7-- [U2b_VT_Br1_ST1(2)]
No.8-- [U2b_VT_Br2_ST1(2)]
Differential coefficient of LVS of main transformer. For differential protection of main transformer,
the base side is LV side.
No.3-- [k_ST1_Diff_Tr]
No.4-- [k_ST2_Diff_Tr]
No.5-- [k_TrHVS_Diff_GTU]
Differential coefficient of HVS of main transformer for differential protection of generator and
transformer unit.
No.6-- [k_Gen_Diff_GTU]
No.7-- [k_ST1_Diff_GTU]
No.8-- [k_ST2_Diff_GTU]
No.9-- [k_Term_Diff_Gen]
No.10-- [k_NP_Diff_Gen]
Differential coefficient of neutral point side of generator for differential protection of generator.
No.11-- [k_HVS_Diff_ST1]
No.12-- [k_Br1_Diff_ST1]
No.13-- [k_Br2_Diff_ST1]
No.14-- [k_HVS_Diff_ST2]
No.15-- [k_Br1_Diff_ST2]
No.16-- [k_Br2_Diff_ST2]
No.17-- [k_S1_Diff_Exc]
No.18-- [k_S2_Diff_Exc]
No.19-- [k_NP_REF_Tr]
Differential coefficient of neutral point of main transformer for restrict earth fault protection of main
transformer.
No.20-- [k_REF_Tr]
Differential coefficient of HVS of main transformer for restrict earth fault protection of main
transformer.
No.21-- [k_NP_REF_ST1]
Differential coefficient of neutral point of stepdown transformer 1 for restrict earth fault protection of
stepdown transformer1.
No.22-- [k_REF_ST1]
Differential coefficient of LVS of stepdown transformer1 for restrict earth fault protection of main
transformer1.
No.23-- [k_NP_REF_ST2]
Differential coefficient of neutral point of stepdown transformer2 for restrict earth fault protection of
stepdown transformer2.
No.24-- [k_REF_ST2]
Differential coefficient of LVS of stepdown transformer2 for restrict earth fault protection of main
transformer2.
No.1—No.18
Internal secondary rated current of each current that used in differential protection. All parameters
have the same meaning with those of in section Calculated parameters of secondary rated
current.
This chapter describes human machine interface (HMI), menu tree and LCD display. At the same
time how to input settings using keypad is described in detail. Finally, this chapter introduces the
RCSPC software and wave analysis software.
The front panel of the relay is shown in Figure 8.2-1. The human-machine interface consists of a
human-machine interface (HMI) module which allows a communication as simple as possible for
the user.
The front panel of the relay includes the following, as indicated in Figure 8.2-1:
8.2.2 LCD
A 320*240 dots liquid crystal display (LCD) with LED backlight. The backlight can be switched on
automatically whenever the keypad is operated or operation or alarm issued. Backlight will be
turned off after a while.
The front panel menu has a default display under normal state after powered-up. If there is no
keypad activity for the 5 minutes timeout period, the default will return again and the LCD backlight
will turn off. To provide more information, the default display a typical single-line scheme generator
system and relevant quantities in operation condition, as shown below.
Whenever there is an un-eliminated fault record in the relay, the default display will be replaced by
fault report.
Whenever there is an un-eliminated internal failure record in the relay, the default display will be
replaced by alarm report.
1. Alm_SwOv_VTS1_Gen Alarm indicating VT1 circuit failure and start to switch over
voltage circuit.
2. Alm_SwOv_VTS2_Gen Alarm indicating VT2 circuit failure and start to switch over
voltage circuit.
14. Alm_VTS_LossExc_RotWdg Alarm indicating rotor voltage circuit failure which used by
loss-of-excitation protection.
30. Alm_CTS_Diff_Gen Alarm indicating secondary circuit failure of CTs used for
differential protection of generator.
33. Alm_On_2PEF_RotWdg Alarm indicating 2 points earth fault protection has been put
input operation after operation of 1 point earth fault
protection of rotor.
element.
44. Alm_V3rdHRatio_Sta Alarm indicating operation of 3rd harmonics ratio earth fault
protective element of stator.
96. Alm_PwrLoss_Opto Loss of power supply of the optical couplers for binary
inputs.
98. Alm_InnerComm Alarm indicating that the communication between MON and
CPU interrupts.
101. Alm_InconsistFD Mismatch of pickup of same type fault detectors in CPU and
MON.
103. Alm_BI_CPUBrd Any one of binary input sampled directly doesn’t match with
that of recognition of protection itself.
Whenever there is change of state of any binary input, the default display will be replaced by
change report of binary input as shown as below.
generator
13. EBI_FreqProt_Gen Enabling binary input of frequency protection of
generator
14. EBI_AccEnerg_Gen Enabling binary input of accidental energization
protection of generator
15. EBI_StShut_Gen Enabling binary input of startup and shutdown
protection of generator
16. EBI_Diff_ST2 Enabling binary input of differential protection of
stepdown transformer2.
17. EBI_Bak_HVS_ST2 Enabling binary input of backup protection at HV side of
stepdown transformer2.
18. EBI_Trp_MechRly3 Enabling binary input of tripping function of repeater of
mechanical input 3
19. EBI_Trp_MechRly4 Enabling binary input of tripping function of repeater of
mechanical input 4
20. EBI_Trp_MechRly2 Enabling binary input of tripping function of repeater of
mechanical input 2
21. EBI_Trp_MechRly1 Enabling binary input of tripping function of repeater of
mechanical input 1
22. EBI_PPF_Gen Enabling binary input of backup protection of generator
23. EBI_Diff_Exc Enabling binary input of differential protection of
excitation set
24. BI_Reserved1 Reserved binary input1
25. BI_SyncCondenser Binary input indicating synchronism condenser is put
into operation
26. EBI_Reserved2 Reserved binary input2
27. EBI_Reserved3 Reserved binary input 3
28. BI_Pwr_Superv Binary input circuit monitoring
29. EBI_Diff_Tr Enable binary input of differential protection of
transformer.
30. EBI_PPF_Tr Enabling binary input of phase-to-phase backup
protection of transformer.
31. EBI_EF_Tr Enabling binary input of earth fault protection of
transformer.
32. EBI_REF_Tr Enabling binary input of restrict earth fault protection of
transformer.
33. EBI_Diff_GTU Enabling binary input of differential protection of
generator-transformer unit.
34. EBI_Bak_Exc Enabling binary input of backup protection of excitation
set
35. EBI_Diff_ST1 Enabling binary input of differential protection of
stepdown transformer.
36. EBI_Bak_HVS_ST1 Enabling binary input of backup protection at HV side of
stepdown transformer.
37. EBI_Bak_Br1_ST1 Enabling binary input of backup protection of branch 1
at LV side of stepdown transformer1.
38. EBI_Bak_Br1_ST2 Enabling binary input of backup protection of branch 1
at LV side of stepdown transformer2.
39. EBI_REF_ST1 Enabling binary input of restrict earth fault protection of
stepdown transformer1.
40. EBI_REF_ST2 Enabling binary input of restrict earth fault protection of
stepdown transformer2.
41. BI_Print Binary input represents the print button.
42. BI_Pulse_GPS Binary input of GPS clock synchronous pulse.
43. BI_RstTarg Binary input of signal reset button.
44. BI_Pwr_Opto Binary input indicating the working state of power
supply of optical isolators
45. BI_MechRly2 Binary input indicating the position of mechanical input
2
46. BI_MechRly4 Binary input indicating the position of mechanical input
4
47. BI_MechRly3 Binary input indicating the position of mechanical input
3
48. BI_MechRly1 Binary input indicating the position of mechanical input
1
49. BI_Pwr_MechRly Binary input indicating the working state of power
supply of mechanical input circuit
50. BI_52b_GCB Binary input indicating the position of breaker at
generator terminal
51. BI_52b_CB_HVS1_Tr Binary input of auxiliary contact of close position of
circuit breaker at branch 1 of HV side of transformer.
52. BI_52b_CB_HVS2_Tr Binary input of auxiliary contact of close position of
circuit breaker at branch 2 of HV side of transformer.
53. BI_Reserved Reserved binary input
54. BI_Valve_Turbine Binary input indicating the valve of steam turbine is in
close position.
55. MON.FD_Diff_Tr/GTU Internally generated binary input indicating operation of
fault detector of differential protection of transformer or
transformer-generator unit.
56. MON.FD_PPF/EF_Tr Internally generated binary input indicating operation of
phase to phase fault and earth fault protection of
transformer.
57. MON.FD_Diff_ST Internally generated binary input indicating operation of
differential protection of stepdown transformer.
58. MON.FD_Bak_ST Internally generated binary input indicating operation of
backup protection of stepdown transformer.
“Healthy” (Green) indicates that the relay is in correct working order, and should be on at all times.
It will be extinguished when some internal error in hardware or software have been detected by
self-diagnosing facilities, such as setting error, RAM or ROM error, power source failure, output
circuit failure and so on. The state of the healthy LED is reflected by the watchdog contact at the
rear terminals of the relay. The healthy cannot lighting again automatically even if the failure is
eliminated except that the relay is reset or powered up by manual.
“VT Alarm” (Yellow) indicates that the relay has found any failure of VT circuit.
“CT Alarm” (Yellow) indicates that the relay has found any failure of CT circuit.
“Alarm” (Yellow) indicates that the relay has registered an alarm. This may be triggered by one of
the following failures: defective pickup, failure of analog or digital input circuit, optical isolator
power loss and so on. The LED will constantly illuminate, and will extinguish, when the alarms
have been cleared.
The LED “TRIP” (RED) will be lit up once the corresponding relays operate and remain lit even
after the trip commands go off. It can be turned off by pressing the RESET button on the protection
panel to energized binary input [BI_RstTarg], or by remote resetting command.
P
GR
ESC
Note!
Any setting change operation should start with simply pressing “+”, “◄”, “▲”,and “-” in sequence,
as a password. Without the operation, modifying settings is invalid.
Report delete operation should executed by pressing “+”, “-”, “+”, “-”, “ENT” in sequence after
exiting the main menu.
8.2.5 Menu
8.2.5.1 Menu tree
This part presents the main layout of the menu tree for the local human-machine interface (HMI).
The menu tree includes menus for:
VALUES
REPORT
SETTINGS
CLOCK
VERSION
DEBUG
MON METERING ST
MONMETERING
METERING
PRINT
MON BI STATE GEN METERING
SETTINGS
PHASE ANGLE EXC METERING
CLOCK
VERSION
DEBUG
The default display can be replaced by the menu when press“▲” or “ESC”.
The menu of this relay is arranged as a tree-shaped cascade structure. See Figure 8.2-9. The
menu can be browsed using the keypad.
Starting at the default display, to enter into main menu, press “▲”.
To enter the lower level menu, select the required item and press “ENT”.
To return to the upper level menu, press “ESC” or select “0. Exit” and push “ENT”.
The menu can be browsed using the four arrow keys, following the structure shown in Figure 8.2-8.
Thus, starting at the default display the “▲” key will display the first column heading. To select the
required column heading use the “▲”and “▼” keys. To return to the default display press the clear
key “ESC” from any of the column headings.
MENU
The menu structure contains two levels of access. The level of access is enabled determines what
users can do by entry of password. The levels of access are summarized in the following table:
The password is 4 digits. The factory default passwords is sequent pressing of the keys “+”, “◄”,
“▲”, “-” and “ENT”.
Metering data consists of AC sampled data and phase angle in the submenu VALUES. Take
viewing data relevant to differential protection of CPU metering as an example. User can view data
of MON in the same way by entering “MON METERING” submenu.
Navigate the menu through the following path and you will see the interface of LCD as shown in
Figure 8.2-10.
A scroll bar appears on the right means there are more rows needed to be displayed. Please press
key “▼”to see the next page and press key “ESC” to exit to the upper level submenu.
The status of binary input comprises enabling binary inputs and other binary inputs of auxiliary
contacts.
For instance, navigate the menu through the following path and you will see the interface of LCD
to see binary inputs related to generator’s protection sampled by CPU.
Main menu -> CPU BI STATE-> -> GEN PROT EBI -> [symbols]
Entering into “PHASE ANGLE” submenu, the calculated angles between sampled voltages or
between sampled voltages and currents by CPU system will be displayed on LCD as shown below,
which can be used to check the correctness of secondary circuit wiring.
The angles displayed is that the former value leading to the later one, which varies from -180~+
180, as shown as figure below for example.
GEN PH ANG
o
φ_Term_Gen_&_NP_Gen: 000 000 000
o
φipp_Term_Gen: 000 000 000
o
φipp_NP_Gen: 000 000 000
o
φvpp_VT1_Term_Gen: 000 000 000
o
φvpp_VT2_Term_Gen: 000 000 000
o
φv_VT1_&_VT2_Gen: 000 000 000
o
φ_V3rdH_Gen: 000 000 000
o
φvi_Term_Gen: 000 000 000
REPORTàTRIP REPORT
Scrolling the cursor to this submenu and press “ENT” key, the LCD will display the latest trip report
if exist, otherwise a clew of “NO TRIP REPORT” will appear. If there are several trip reports stored
in memory, user can look up historical record one by one by pushing “▲” key.
RCS-985B can store up to 24 latest trip reports. When the available space is exhausted, the oldest
report is automatically overwritten by the new one .
REPORT—ALARM REPORT
Scrolling the cursor to this submenu and press “ENT” key, the LCD will display the latest alarm
report if exist, otherwise a clew of “NO ALARM REPORT” will appear. If there are several alarm
reports stored in memory, user can look up historical record one by one by pushing “▲” key.
RCS-985B can store up to 64 latest alarm reports. When the available space is exhausted, the
oldest report is automatically overwritten by the new one.
Scrolling the cursor to this submenu and press “ENT” key, the LCD will display the last BI CHG
report if exist, otherwise a clew of “NO BI CHG REPORT” will appear. If there are several BI CHG
reports stored in memory, user can look up historical record one by one by pushing “▲” key.
RCS-985B can store up to 64 latest signaling reports at a resolution of 2ms. When the available
space is exhausted, the oldest report is automatically overwritten by the new one
If you want to delete the content of fault records or event records, you can follow the operating
steps. Note you cannot select which kind of records or which one record to be deleted but delete
all records.
Operating steps:
Press keys “+”, “-”, “+”, “-”, “ENT” in sequence in the main menu to make LCD display Figure
8.2-14.
Press key “ENT” to delete all records or press key “ESC” to exit to main menu. If key “ENT” is
pressed, LCD will display Figure 8.2-15 when equipment is deleting all records. If key “ESC” is
pressed, Figure 8.2-13 will be displayed. LCD will automatically return to Figure 8.2-13 in 3
seconds without pressing any key.
PRINTàSETTINGSà[submenu]
Used for printing of settings. The following figure gives an example of the first submenu.
PRINTàTRIP REPORT
Used for printing of trip report of protection. User can select the report that he wants to print by
pushing ” ▲” and “▼” keys to select the SOE number.
PRINTàALARM REPORT
Used for printing of alarm. User can select the report that he wants to print by pushing ” ▲” and
“▼” keys.
Used for printing of signaling report. User can select the report that he wants to print by pushing ”
▲” and “▼” keys.
PRINTàPRESENT VALUES
Used for printing of present values of relay, including sampled binary inputs, analog quantities and
so on. If you want to see the normal recording waveform, please follow the operating steps.
Operating steps:
Press key “▲” or “▼”to select “PRINT” item by scrolling the cursor upward or downward and then
press the “ENT” to the lower level submenu.
Then press key “▲” or “▼”to select “PRESENT WAVE” by scrolling the cursor upward or
downward. Press key “ENT” to enter the lower level submenu.
Press “TRIGGER” submenu to start recording. The equipment will record 5-cycle waveform after
pressing the key.
Please select the other items in the submenu “PRESENT WAVE” by scrolling cursor to print the
waveform.
SettingsàEquip Settings
To change one of the value of equipment settings, first navigate the “SETTING” menu to display
the relevant cell. Press “ENT” to enter the submenu, then proceed to “Equip Settings” submenu.
Keys “▲” and “▼”are used to select which kind of the settings to be modified by scrolling the
cursor upward or downward. Press key “◄,” or “►” to move the cursor to the digit to be modified.
Press key “+” and “–” to modify data. Press key “ESC” to return back without modification.
Pressing key “ENT” the LCD will prompt to input confirm password, then enter password
mentioned in section 8.2.5.2 and quit to default display by pressing “ESC” key. After a period of
extinguishing of the “HEALTHY” LED and blocking of relay itself, RCS-985B is ready for new
operation to fault according to new settings, the modification is completed. The following figure
shows the path to access this submenu.
SettingsàProt. Settings
To change the value of a setting, first navigate the menu to “SETTING” then corresponding
submenu to display the relevant cell. Please locate the setting you want to change after entering
the right submenu by operating the keypad as described before. Then go on to operate as
following steps.
Press key “◄” or “►” to move the cursor to the digit to be modified. Pressing key “+” and “–” to
change the digit. Press key “+” once to add 1 to the digit and press key “–” once to subtract 1 from
the digit.
Press key “ESC” to cancel the modification and return to upper level submenu.
Press key “ENT” to confirm the modification and the LCD will prompt you to input confirm code.
Press keys “+”,” “◄”, “▲” and “–” in sequence to complete the modification. If the password input
is wrong, prompt for password will appear again. If no operation in 3 seconds, LCD will return to
last display.
If the password inputted is right, then equipment will check setting and Figure 8.2-18 will be
displayed temporarily. If there is no error in checking setting, Equipment will modify setting with
Figure 8.2-19 displayed temporarily. Then LCD will return to upper level submenu automatically.
If errors in settings are detected, the LCD will display wrong setting warning for 3 s.
Then LCD will display the setting list for the operator to modify the wrong setting. The cursor will
stay at the first wrong setting needed to be modified.
Note:
If the group number or protection system parameter is changed, all protection settings will be
invalid and have to be configured again.
Attentions should be paid that before modifying the protection settings, the active group number in
“Equip Settings” should modified firstly, otherwise what is modified will be applied to current active
group.
SettingsàSettings Copy
The relay stores 2 setting groups from No.0 through No.1. Only present setting group is active, the
others are provided for different operating conditions. The equipment settings are shared for the
two setting groups, but the protection settings are independent. Generally the equipment is
delivered with default settings stored in active setting group “0”. The contents of other setting
groups may be invalid. Therefore after application-specific settings for group No.0 have been
ready, it is necessary to copy settings of group No.0 to No. 1 setting groups, and make some
modification afterwards when necessary, so as to avoid entering all settings one by one. Please
copy settings as following steps.
Move cursor to “SETTINGS” item and press key “ENT” or key“►” to enter submenu.
N A RI- R E L A Y S
VALUES
REPORT
EQUP SETTINGS
PRINT
SYSTEM SETTINGS
SETTINGS
PROT SETTINGS
CLOCK SETTINGS COPY
VERSION CALC SETTINGS
DEBUG
Move cursor to “SETTINGS COPY” item and press “ENT” to display following interface.
Press key “+” and “–” to change digit where the cursor stays. Pressing key “+” once will add 1 to
the digit and pressing key “–“once will subtract 1 from the digit. (For example: input 01)
Press “ENT” the LCD will prompt to input confirm code. Please see the figure below.
Please press keys “+”, “◄”, “▲” and “–” in sequence, and then the equipment will copy setting and
display following interface.
Then the contents of setting group 0 will be totally copied to setting group 1 and present active
setting group will be switched to Group1.
Note:
Press “ENT” to confirm, Then settings group 0 will be totally copied to settings group 1 and present
active group will be switched to group 01.
After you press key “ENT”, the following will be displayed on the LCD.
Press keys “▲”, “▼”, “◄” and “►” to select the digit to be modified. Press key “+” and “–” to modify
data. Pressing key “+” once will add 1 to the digit and pressing key “–” once will subtract 1 from the
digit.
Press key “ENT” to confirm the modification and return to the main menu.
The equipment program has following parts. One is CPU module program, one is MON module
program, and another is HMI module program. There are totally independent.
After you press key “ENT”, the follow will be displayed on the LCD.
VERSION
2006-12-12 10:20: shows that CPU software creating time is 10:20 Dec 12th 2006.
2006-12-12 10:20: shows that MON software creating time is 10:20 Dec 12th 2006.
2006-12-11 08:15: shows that HMI software creating time is 08:15 Dec 11th 2006.
Note:
What Figure 8.2-27 shows is just an example to introduce the meaning of VERSION, the actual
program VERSION is application-specific.
COMM STATUS
This submenu is used to monitor communication condition of the equipment with external system.
Display of this submenu is as follows:
485A 485B
Data_Received NO YES
Frame_Valid NO YES
Address_Valid NO YES
Data_Sent NO YES
Columns 485A and 485B display communication condition of RS-485 port1 and RS-485 port2
respectively. If communication condition is normal, “Y” will flash in the related position. If there is
flashing “N” in the position, it mean there are some problems. Please check the communication.
“Received Data” means the equipment has received data from external system. If “N” flashes
means the circuit is open or no data is sent from external system.
“Valid Frame” means the equipment has received complete frame from external system. If “N”
flashes means Configuration of the baud rate or protocol is wrong.
“Valid Address” means the equipment has received related message from external system. If “N”
flashes means Configuration of the address is wrong.
“Sent Data” means the equipment has sent data to external system. If “N” flashes means there is
problem with the message.
MEMPRY DEBUG
The LCD displays real time value in memory of CPU, DSP1 and DSP2. These data are used
mainly for program debugging.
Chapter9 Communications
9.1 Introduction
This section outlines the remote communications interfaces of the RCS-985B. The protection
supports a choice of one of three protocols via the rear communication interface, selected via the
model number by setting.
The rear EIA(RS)485 interface is isolated and is suitable for permanent connection whichever
protocol is selected. The advantage of this type of connection is that up to 32 relays can be ‘daisy
chained’ together using a simple twisted pair electrical connection.
It should be noted that the descriptions contained within this section do not aim to fully detail the
protocol itself. The relevant documentation for the protocol should be referred to for this
information. This section serves to describe the specific implementation of the protocol in the relay.
The following figure shows typical scheme of communication via RS-485 port of RCS-985B used
in substation automation system.
The protocol provided by the relay is indicated in the relay menu in the ‘SETTINGS’ column. Using
the keypad and LCD, check the communication protocol being used by the rear port according to
the definition of relevant settings described in section 7.
The EIA(RS)485 two-wire connection provides a half-duplex fully isolated serial connection to the
product. The connection is polarized and whilst the product’s connection diagrams indicate the
polarization of the connection terminals it should be borne in mind that there is no agreed definition
of which terminal is which. If the master is unable to communicate with the product, and the
communication parameters match, then it is possible that the two-wire connection is reversed.
The EIA(RS)485 bus must have 120Ω (Ohm) ½ Watt terminating resistors fitted at either end
across the signal wires – see Figure 9.1-1. Some devices may be able to provide the bus
terminating resistors by different connection or configuration arrangements, in which case
separate external components will not be required. However, this product does not provide such a
facility, so if it is located at the bus terminus then an external termination resistor will be required.
The EIA(RS)485 standard requires that each device be directly connected to the physical cable
that is the communications bus. Stubs and tees are expressly forbidden, as are star topologies.
Loop bus topologies are not part of the EIA(RS)485 standard and are forbidden by it.
Two-core screened cable is recommended. The specification of the cable will be dependent on the
application, although a multi-strand 0.5mm 2 per core is normally adequate. Total cable length
must not exceed 1000m. The screen must be continuous and connected to ground at one end,
normally at the master connection point; it is important to avoid circulating currents, especially
when the cable runs between buildings, for both safety and noise reasons.
This product does not provide a signal ground connection. If a signal ground connection is present
in the bus cable then it must be ignored, although it must have continuity for the benefit of other
devices connected to the bus. At no stage must the signal ground be connected to the cables
screen or to the product’s chassis. This is for both safety and noise reasons.
• It is extremely important that the 120Ω termination resistors are fitted. Failure to do so will result
in an excessive bias voltage that may damage the devices connected to the bus.
• As the field voltage is much higher than that required, NR cannot assume responsibility for any
damage that may occur to a device connected to the network as a result of incorrect application of
this voltage.
To use the rear port with IEC60870-5-103 communication, the relay’s communication settings
must be configured. To do this use the keypad and LCD user interface. Please refer to section
8.2.5 for detail instructions.
Three settings apply to the rear port using IEC60870-5-103 that are described below.
[Equip_ID] controls the IEC60870-5-103 address of the relay. Up to 32 relays can be connected to
one IEC60870-5-103 spur, and therefore it is necessary for each relay to have a unique address
so that messages from the master control station are accepted by one relay only. IEC60870-5-103
uses an integer number between 0 and 254 for the relay address. It is important that no two relays
have the same IEC60870-5-103 address. The IEC60870-5-103 address is then used by the
master station to communicate with the relay.
9.3.2.1 Settings
Note:
If the item “[En_Remote_Cfg]” in Equipment Settings is set as 0, to modify settings remotely will
not be allowed. Moreover, Equipment Settings & System Settings are not allowed to be modified
remotely whether the item “[En_Remote_Cfg]” is true (=1) or not.
9.3.2.6 BinaryInput
9.4.1 Overview
The RCS-985B relay support several communications protocols to allow connection to equipment
such as personal computers, RTUs, SCADA masters, and programmable logic controllers. The
Modicon Modbus RTU protocol is the most basic protocol supported by the RCS-985B. Modbus is
available via RS485 serial links or via Ethernet (using the Modbus/TCP specification). The
following information is provided intended primarily for users who wish to develop their own master
communication drivers and applies to the serial Modbus RTU protocol. The characteristic is listed
below:
Physical Layer Setup:RS485, 1 start bit,8 data bits, no bit for parity,1 stop bit
Parity: no
The following modbus function codes are supported but re-defined by the relay:
Reads the ON/OFF status of discrete inputs in the slave. The status in the response message is
packed as one input per bit of the data field. Status is indicated as: 1 = ON; 0 = OFF. The LSB of
the first data byte contains the input addressed in the query. The other inputs follow toward the
high order end of this byte, and from ‘low order to high order’ in subsequent bytes.
Example 1: If the master want to fetch Trip Information (0000H~0003H),the query frame would be
as follows(Suppose the slave address was 1):
01 02 00 00 00 04 79 C9
CRC Hi
CRC Lo
Num of Status Lo
Num of Status Hi
The response fame would be as follows (Suppose the value of 0000H~0003H equal to 1,1,0,1
respectively):
01 02 01 0B E0 4F
CRC Hi
CRC Lo
Status
Length
Function Code
Slave Addr
Example 2: If the master want to fetch Trip Information(0002H~000DH),the query frame would be
as follows(Suppose the slave address was 1):
01 02 00 02 00 0C D9 CF
CRC Hi
CRC Lo
Num of Status Lo
Num of Status Hi
The response fame would be as follows (Suppose the value of 0002H~000DH equal to
1,1,0,1,0,0,1,0,1,1,1,0 respectively):
01 02 02 07 4B FB BF
CRC Hi
CRC Lo
Status Lo
Status Hi
Length
Function Code
Slave Addr
202CH BI_Pwr_Opto
The metering values in the response message are packed as two bytes per register. For each
register, the first byte contains the high order bits and the second contains the low order bits.
9.4.3.2 TR Metering
Bit15:En_OvExc_Gen
1001H Protection Config Bit0:En_PwrProt_Gen
Word 2 Bit1:En_FreqProt_Gen
Bit2:En_StShut_Gen
Bit3:En_AccEnerg_Gen
Bit4:En_Diff_ST1
Bit5:En_Bak_HVS_ST1
Bit6:En_Bak_Br1_ST1
Bit7:En_REF_ST1
Bit8:En_Diff_ST2
Bit9:En_Bak_HVS_ST2
Bit10:En_Bak_Br1_ST2
Bit11:En_REF_ST2
Bit12:En_Diff_Exc
Bit13:En_Bak_Exc
Bit14:En_MechRly
Bit15:En_VTComp_Term_Gen
1002H Reserved
Setting Bit1:Yyd11_Conn_Tr
Bit2:Opt_GCB
Bit3:Yd1_Conn_Tr
Bit4:Yyd1_Conn_Tr
1038H I1n_CT_NP_Br_ST1(integer) A
1039H I2n_CT_NP_Br_ST1 A
103AH Logic Bit0:Yyy12_Conn_ST1
Setting Bit1:Ddd12_Conn_ST1
Bit2:Dyy11_Conn_ST1
Bit3:Ydd11_Conn_ST1
Bit4:Dyy1_Conn_ST1
Bit3:En_UV_LossExc2_Gen
Bit4:En_Z_LossExc2_Gen
Bit5:En_RotUV_LossExc2_Gen
Bit6:En_Z_LossExc3_Gen
Bit7:En_RotUV_LossExc3_Gen
Bit8:En_Alm_LossExc1_Gen
Bit9:Opt_Z_LossExc_Gen
Bit10:En_RevQ_LossExc_Gen
Bit11:Opt_UV_LossExc_Gen
20B8H TrpLog_OvExc1_Gen
20B9H k_Alm_OvExc_Gen(decimal digits=2)
20BAH t_Alm_OvExc_Gen(decimal digits=1) S
20BBH k0_InvOvExc_Gen(decimal digits=2)
20BCH t0_InvOvExc_Gen(decimal digits=1) S
20BDH k1_InvOvExc_Gen(decimal digits=2)
20BEH t1_InvOvExc_Gen(decimal digits=1) S
20BFH k2_InvOvExc_Gen(decimal digits=2)
20C0H t2_InvOvExc_Gen(decimal digits=1) S
20C1H k3_InvOvExc_Gen(decimal digits=2)
20C2H t3_InvOvExc_Gen(decimal digits=1) S
20C3H k4_InvOvExc_Gen(decimal digits=2)
20C4H t4_InvOvExc_Gen(decimal digits=1) S
20C5H k5_InvOvExc_Gen(decimal digits=2)
20C6H t5_InvOvExc_Gen(decimal digits=1) S
20C7H k6_InvOvExc_Gen(decimal digits=2)
20C8H t6_InvOvExc_Gen(decimal digits=1) S
20C9H k7_InvOvExc_Gen(decimal digits=2)
20CAH t7_InvOvExc_Gen(decimal digits=1) S
20CBH TrpLog_InvOvExc_Gen
20DCH TrpLog_UF_Gen
20DDH f_OF1_Gen(decimal digits=2) Hz
20DEH t_OF1_Gen(decimal digits=2) M
20DFH f_OF2_Gen(decimal digits=2) Hz
20E0H t_OF2_Gen(decimal digits=2) S
20E1H TrpLog_OF_Gen
20E2H Logic Bit0:En_Alm_UF1_Gen
Setting Bit1:En_Trp_UF1_Gen
Bit2:En_Alm_UF2_Gen
Bit3:En_Trp_UF2_Gen
Bit4:En_Alm_UF3_Gen
Bit5:En_Trp_UF3_Gen
Bit6:En_Alm_OF1_Gen
Bit7:En_Trp_OF1_Gen
Bit8:En_Alm_OF2_Gen
Bit9:En_Trp_OF2_Gen
Modbus function 08 provides a series of tests for checking the communication system between the
master and slave, or for checking various internal error conditions within the slave.
The function uses a two–byte subfunction code field in the query to define the type of test to be
performed. The slave echoes both the function code and subfunction code in a normal response.
The listing below shows the subfunction codes supported by the equipment.
Code Name
00H Return Query Data
01H Restart Comm Option
04H Force Listen Only Mode
0BH Return Bus Message Count
0CH Return Bus Comm. Error Count
0DH Return Bus Exception Error Cnt
0EH Return Slave Message Count
0FH Return Slave No Response Cnt
Except for broadcast messages, When a master device sends a query to a slave device it expects
a normal response. If the slave receives the query without a communication error, but cannot
handle it (for example, if the request is to read a non–existent coil or register), the slave will return
an exception response informing the master of the nature of the error.
The listing below shows the exception codes supported by the equipment.
Code Description
01H Illegal Function
02H Illegal Data Address
03H Illegal Data Value
07H Negative Acknowledge
None of the other pins are connected in the relays. The relays should be connected to the serial
port of a PC, usually called as COM1 or COM2. The serial port pin connections, which is DB9 male,
is as below (if in doubt check you PC manual):
For successful data communication, the Tx pin on the relays must be connected to the Rx pin on
the PC, and Rx pin on the relay must be connected to Tx pin on the PC as shown in Figure 9.5-1.
Note:
There are no parameters need to be set in RCS-985B for communication with printer.
The printer’s port used for communication with RCS-985B is serial port of which the pin definition
is a little different with normal RS232 port as shown as below:
1 2 3 4 5
6 7 8 9
1 2 3 4 5
6 7 8 9
---Event recording
---Fault recording
---Present recording
---Self-supervision
When the relays are connected to the GPS clock, all the relay clocks are synchronized with the
external time standard. There are two way to adjust the relay clock.
Chapter10 Installation
Each printed circuit board incorporates the highest practicable protection for its semiconductor
devices. However, if it becomes necessary to remove a printed circuit board, the following
precautions should be taken to preserve the high reliability and long life for which the relay has
been designed and manufactured.
Before removing a printed circuit board, ensure that you are at the same electrostatic potential as
the equipment by touching the case.
Handle analog input modules by the front panel, frame or edges of the circuit boards.
Printed circuit boards should only be handled by their edges. Avoid touching the electronic
components, printed circuit tracks or connectors.
Do not pass the module to another person without first ensuring you are both at the same
electrostatic potential. Shaking hands achieves equipotential.
Place the module on an anti-static surface, or on a conducting surface that is at the same potential
as you.
If it is necessary to store or transport printed circuit boards removed from the case, place them
individually in electrically conducting anti-static bags.
In the unlikely event that you are making measurements on the internal electronic circuitry of a
relay in service, it is preferable that you are earthed to the case with a conductive wrist strap. Wrist
straps should have a resistance to ground between 500kΩ to 10MΩ. If a wrist strap is not available
you should maintain regular contact with the case to prevent a build-up of electrostatic potential.
Instrumentation which may be used for making measurements should also be earthed to the case
whenever possible.
More information on safe working procedures for all electronic equipment can be found in BS EN
100015: Part 1:1992. It is strongly recommended that detailed investigations on electronic circuitry
or modification work should be carried out in a special handling area such as described in the
British Standard document.
10.3 Storage
If relays are not to be installed immediately upon receipt, they should be stored in a place free from
dust and moisture in their original cartons. Where de-humidifier bags have been included in the
packing they should be retained.
To prevent battery drain during transportation and storage a battery isolation strip is fitted during
manufacture. With the lower access cover open, presence of the battery isolation strip can be
checked by a red tab protruding from the positive polarity side.
Care should be taken on subsequent unpacking that any dust, which has collected on the carton,
does not fall inside. In locations of high humidity the carton and packing may become impregnated
with moisture and the de-humidifier crystals will lose their efficiency.
Prior to installation, relays should be stored at a temperature of between –25°C to +70°C (-13°F to
+158°F).
10.4 Unpacking
Care must be taken when unpacking and installing the relays so that none of the parts are
damaged and additional components are not accidentally left in the packing or lost. Ensure that
any User’s CDROM or technique documentation is NOT discarded – this should accompany the
relay to its destination substation.
Note:
With the lower access cover open, the red tab of the battery isolation strip will be seen protruding
from the positive (“+”) side of the battery compartment. Do not remove this strip because it
prevents battery drain during transportation and storage and will be removed as part of the
commissioning tests. Relays must only be handled by skilled persons.
The site should be well lit to facilitate inspection, clean, dry and reasonably free from dust and
excessive vibration.
Once the tier is complete, the frames are fastened into the racks using mounting angles at each
end of the tier.
530.4
GRP
457.2
190.5
ESC
457.2
190.5
Relays can be mechanically grouped into single tier (8U) or multi-tier arrangements by means of
the rack frame.
The relays can be flush mounted into panels using M4 self-tapping screws with captive 3mm thick
washers.
For applications where relays need to be semi-projection or projection mounted, a range of collars
are available. Where several relays are mounted in a single cutout in the panel, it is advised that
they are mechanically grouped together horizontally and/or vertically to form rigid assemblies prior
to mounting in the panel.
Note:
It is not advised that RCS-985B are fastened using pop rivets as this will not allow the relay to be
easily removed from the panel in the future if repair is necessary.
If it is required to mount a relay assembly on a panel complying to IEC 60529 IP51 enclosure
protection, it will be necessary to fit a metallic sealing strip between adjoining relays and a sealing
ring around the complete assembly.
Loose relays are supplied with sufficient M4 screws for making connections to the rear mounted
terminal blocks using ring terminals, with a recommended maximum of two ring terminals per relay
terminal.
If required, NR can supply M4 90° crimp ring terminals in three different sizes depending on wire
size (see Table 10.6-1).
*To maintain the terminal block insulation requirements for safety, an insulating sleeve should be
fitted over the ring terminal after crimping.
Due to the limitations of the ring terminal, the maximum wire size that can be used for any of the
medium or heavy duty terminals is 6.0mm2 using ring terminals that are not pre-insulated. Where it
required to only use pre-insulated ring terminals, the maximum wire size that can be used is
reduced to 2.63mm 2 per ring terminal. If a larger wire size is required, two wires should be used in
parallel, each terminated in a separate ring terminal at the relay.
The wire used for all connections to the medium and heavy duty terminal blocks, except the
EIA(RS)485 port, should have a minimum voltage rating of 300Vrms.
It is recommended that the auxiliary supply wiring should be protected by a 16A high rupture
capacity (HRC) fuse of type NIT or TIA. For safety reasons, current transformer circuits must
never be fused. Other circuits should be appropriately fused to protect the wire used.
The IRIG-B input and BNC connector have a characteristic impedance of 50Ω. It is recommended
that connections between the IRIG-B equipment and the relay are made using coaxial cable of
type RG59LSF with a halogen free, fire retardant sheath.
Short term connections to the EIA(RS)232 port, located at the bottom of face cover, can be made
using a screened multi-core communication cable up to 15m long, or a total capacitance of
2500pF. The cable should be terminated at the relay end with a 9-way, metal shelled, D-type male
plug. The pin allocations are detailed in section 5.4 about connectors.
The relays can have an optional 10 or 100 Mbps Ethernet port. FO connection is recommended for
use in permanent connections in a substation environment. The 10Mbit port uses type ST
connector and the 100Mbit port uses type SC connector, both compatible with 850nm multi-mode
fiber-optic cable.
The user can connect to either a 10Base-T or a 100Base-TX Ethernet hub; the port will
automatically sense which type of hub is connected. Due to possibility of noise and interference on
this part, it is recommended that this connection type be used for short-term connections and over
short distance. Ideally where the relays and hubs are located in the same cubicle.
The connector for the Ethernet port is a shielded RJ-45. The table shows the signals and pins on
the connector.
4 - Not used
5 - Not used
7 - Not used
8 - Not used
Short term connections to the download/monitor port, located on the front access cover, can be
made using a screened 9-core communication cable up to 4m long. The cable should be
terminated at the relay end with a 9-way, metal shelled, D-type male plug and linked as a serial
data connection.
Chapter11 Commission
11.1 Introduction
This relay is fully numerical in their design, implementing all protection and non-protection
functions in software. The relay employs a high degree of self-checking and in the event of a
failure, will give an alarm. As a result of this, the commissioning test does not need to be as
extensive as with non-numeric electronic or electro-mechanical relays.
To commission numerical relays, it is only necessary to verify that the hardware is functioning
correctly and the application-specific software settings have been applied to the relay. It is
considered unnecessary to test every function of the relay if the settings have been verified by one
of the following methods:
-extracting the settings applied to the relay using appropriate setting software (preferred method)
Blank commissioning test and setting records are provided at the end of this manual for
completion as required.
WARNING!
Before carrying out any work on the equipment, the user should be familiar with the contents of the
safety and technical data sections and the ratings on the equipment’s rating label.
11.2 Precautions
WARNING!
Hazardous voltages are present in this electrical equipment during operation. Non- observance of
the safety rules can result in severe personal injury or property damage.
Only qualified personnel shall work on and around this equipment after becoming thoroughly
familiar with all warnings and safety notices in this manual as well as with the applicable safety
regulations.
The earthing screw of the device must be connected solidly to the protective earth conductor
before any other electrical connection is made.
Hazardous voltages can be present on all circuits and components connected to the supply
voltage or to the measuring and test quantities.
Hazardous voltages can be present in the device even after disconnection of the supply voltage
(storage capacitors!).
The limit values stated in the technique data (Chapter 2) must not be exceeded at all, not even
during testing and commissioning.
When testing the device with secondary test equipment, make sure that no other measurement
quantities are connected. Take also into consideration that the trip circuits and maybe also close
commands to the circuit breakers and other primary switches are disconnected from the device
unless expressly stated.
DANGER!
Current transformer secondary circuits must have been short-circuited before the current leads to
the device are disconnected.
WARNING!
Primary test may only be carried out by qualified personnel, who are familiar with the
commissioning of protection system, the operation of the plant and safety rules and regulations
(switching, earthing, etc.)
--Multifunctional dynamic current and voltage injection test set with interval timer
--Multimeter with suitable AC current range and AC/DC voltage ranges of 0-200V and 0-250V
respectively.
Note:
Modern test set may contain many of the above features in one unit.
Optional equipment
--An electronic or brushless insulation tester with a DC output not exceeding 500 V (for insulation
resistance test when required);
--A portable PC, with appropriate software (this enables the rear communications port to be tested,
if this is to be used, and will also save considerable time during commissioning).
--RCSPC software.
-- A printer.
With the front cover in place all keys are accessible. All menu cells can be read. LEDs and alarms
can be reset. Protection or configuration settings can be changed, or fault and event records
cleared. However, menu cells will require the appropriate password to be entered before changes
can be made.
Alternatively, if a portable PC is available together with suitable setting software (such as RCSPC),
the menu can be viewed a page at a time to display a full column of data and text. This PC
software also allows settings to be entered more easily, saved to a file on disk for future reference
or printed to produce a setting record. Refer to the PC software user manual for details. If the
software is being used for the first time, allow sufficient time to become familiar with its operation.
If the application-specific settings have been applied to the relay prior to commissioning, it is
advisable to make a copy of the settings so as to allow them restoration later. This could be done
by extracting the settings from the relay itself via printer or manually creating a setting record.
The RCS-985 serial plant transformer protection is fully numerical and the hardware is
continuously monitored. Commissioning tests can be kept to a minimum and need only include
hardware tests and conjunctive tests. The function tests are carried out according to user’s
correlative regulations.
The following tests are necessary to ensure the normal operation of the equipment before it is first
put into use.
Hardware tests
These tests are performed for the following hardware to ensure that there is no hardware defect.
NANJING NARI-RELAYS ELECTRIC CO., LTD 395
Chapter11 Commission
Defects of hardware circuits other than the following can be detected by self-monitoring when the
DC power is supplied.
These tests are performed for the following functions that are fully software-based. Tests of the
protection schemes and fault locator require a dynamic test set.
Timers test
Conjunctive tests
The tests are performed after the relay is connected with the primary equipment and other external
equipment.
On-load test
After unpacking the product, check for any damage to the relay case. If there is any damage, the
internal module might also have been affected, contact the vendor. Following items listed is
necessary.
Protection panel
Carefully examine the protection panel, protection equipment inside and other parts inside to see
that no physical damage has occurred since installation.
The rated information of other auxiliary protections should be checked to ensure it is correct for the
particular installation.
Panel wiring
Check the conducting wire used in the panel to assure that their cross section meet the
requirement.
Carefully examine the wiring to see that they are no connection failure exists.
Label
Check all the isolator binary inputs, terminal blocks, indicators, switches and push buttons to make
sure that their labels meet the requirements of this project.
Check each plug-in module of the equipments on the panel to make sure that they are well
installed into the equipment without any screw loosened.
Earthing cable
Check whether the earthing cable from the panel terminal block is safely screwed to the panel
steel sheet.
Check whether all the switches, equipment keypad, isolator binary inputs and push buttons work
normally and smoothly.
11.5.1.2 Insulation
Insulation resistances tests are only necessary during commission if it is required for them to be
done and they have not been performed during installation.
Isolate all wiring from the earth and test the insulation with an electronic or brushless insulation
tester at a DC voltage not exceeding 500V, terminals of the same circuits should be temporarily
connected together.
-Relay contacts
-Case earth
The insulation resistance should be greater than 100MΩ at 500V. On completion of the insulation
resistance tests, ensure all external wiring is correctly reconnected to the relay.
Check that the external wiring is correct to the relevant relay diagram and scheme diagram.
Ensure as far as practical that phasing/phase rotation appears to be as expected.
Check the wiring against the schematic diagram for the installation to ensure compliance with the
customer’s normal practice.
The relay can be operated from either 110/125Vdc or 220/250Vdc auxiliary supply depending on
the relay’s nominal supply rating. The incoming voltage must be within the operating range
specified in the following table, before energizing the relay, measure the auxiliary supply to ensure
it is within the operating range.
It should be noted that the relay can withstand an AC ripple of up to 15% of the upper rated voltage
on the DC auxiliary supply.
Energize the relay only if the auxiliary supply is within the specified operating ranges.
The current and voltage transformer connections must remain isolated from the protection for
these checks. The trip circuit should also remain isolated to prevent accidental operation of the
associated circuit breaker.
This test ensures that the LCD, LEDs and keys function correctly.
◆ LCD display
Only apply the rated DC voltage and check whether the LCD displays normal operation status
report as mentioned former. If there is a failure, for example, VT circuit fail because of not applying
voltage, the LCD displays failure report. If the LCD displays failure report, press the ECS key for 1
second and the LCD will return to normal operation status report.
◆ LED display
Apply the rated DC voltage and check that the "HEALTHY" LED is lighting in green. We need to
emphasize that the "HEALTHY" LED is always lighting in operation course except that the
equipment find serious problems listed in chapter 4.
◆ Keypad
Press key “ESC” or “▲”and enter the command menu. Do some jobs to ensure that all buttons are
in good condition.
Using a continuity tester, check the watchdog contacts (equipment being blocked, BSJ) are in the
states given in Table 11.5-1 below.
Contacts
Terminals
Relay de-energized Relay energized
4A1-4A3
4A2-4A4 Closed Open
4B4-4B26
The method of setting will depend on whether accuracy is being maintained via the RS-485 port
(from GPS in the substation) on the rear of the protection or via the front panel user interface
manually.
Turn on the DC power supply of the equipment and check the software version and time through
the LCD Manual.
This test checks that all the binary inputs on the protection are functioning correctly. The binary
inputs should be energized one at a time. Ensuring correct polarity, connect the field supply
voltage to the appropriate terminals for the input being tested.
There two voltage levels of opto-couple for binary inputs, one is 24V DC and the other is
250/220/125/110V DC. The negative pole of DC 24V and negative pole of DC 250/220/125/110V
have been connected with the corresponding negative pole of opto-couplers through the inner rear
board in equipment. The positive pole terminals of opto-couplers have been connected to the rear
connectors for binary input connecting, and common positive pole has also be connected to the
rear connector.
Please see the panel diagram carefully and find the right connector terminal numbers of common
positive pole of DC 24V and DC 250/220/125/110V.
Note:
The binary inputs may be energized from an external DC auxiliary supply (e.g. the station battery)
in some installations. Check that this is not the case before connecting the field voltage otherwise
damage to the protection may result. The status of each binary input can be viewed using either
RCSPC software installed in a portable PC or by checking the front human-machine interface LCD.
When each binary input is energized the display will change to indicate the new status of the
inputs. Please check binary input both on CPU module and MON module and ensure they are
consistent.
Please note only the positive pole of opto-coupler for binary inputs are listed in following tables.
3. EBI_ROV_Sta 5B29-5B5
4. EBI_V3rdH_Sta 5B29-5B6
5B29-5B7
5. EBI_1PEF_RotWdg
6. EBI_reserved 5B29-5B8
7. EBI_OvLd_Sta 5B29-5B9
8. EBI_NegOC_Gen 5B29-5B10
5B29-5B11
9. EBI_LossExc_Gen
5B29-5B13
11. EBI_VoltProt_Gen
5B29-5B15
13. EBI_PwrProt_Gen
5B29-5B16
14. EBI_FreqProt_Gen
5B29-5B17
15. EBI_AccEnerg_Gen
5B29-5B18
16. EBI_StShut_Gen
5B29-5B20
18. EBI_Bak_HVS_ST2
5B29-5B21
19. EBI_Trp_MechRly3
5B29-5B22
20. EBI_Trp_MechRly4
5B29-5B23
21. EBI_Trp_MechRly2
5B29-5B24
22. EBI_Trp_MechRly1
6B17-6B8
32. EBI_Bak_HVS_ST1
6B17-6B9
33. EBI_Bak_Br1_ST1
6B17-6B10
34. EBI_Bak_Br1_ST2
When detecting a hardware failure in self-supervise, the relay will block all the output and black the
“HEALTY” LED.
All the operation element for alarm operates, the “ALARM” LED will illuminate. At the same time,
the BJJ contact and other alarm contacts will be closed. According to the below table we can
check these contacts.
All the operation element for tripping operates, the “TRIP” LED will illuminate. At the same time,
the tripping signal contacts will be closed. According to the below table we can check these
contacts.
Setting the tripping logic settings refer to table 5-1. The output x will be closed only when the
correspond bit [Output x] is set as “1”. According to the below table we can check these contacts.
3B24-3B26、3B28-3B30
14 TrpOutput 14
Wiring Yes or No
No Output name Equipment
connector number
terminal number
2 BO_Alm_InitCool2_Tr 2B20-2B22
4 BO_Alm_InitCool_ST2 3B20-3B22
This test should only be performed where the protection is to be accessed from a remote location
and will vary depending on the communications standard being adopted.
It is not the intention of the test to verify the operation of the complete system from the relay to the
remote location, just the protection’s rear communications port and any protocol converter
necessary.
Courier communications
Ensure that the RS-232 wire link the RS-232 port in front of the RCS-985B and the communication
baud rate in RCSPC must be set as “9600”.
Check that communications can be established with this protection using the portable PC.
Remote communication
This test is to check the status of communications between RCS-985B and the engineer’s
workstation in SAS(Substation automation system) if it is applicable. Before test, the
communication baud rate in RCS-985B must be set as “1200-38400” depends on Substation
Automation System, and the protection’s [Comm_Adrr] must be set to a value between 1 and 254.
In the menu of “DEBUG”->”COMM STATUS” on the LCD display, “485A”or “485B” indicates
the communication status of 485A port or 485B port. If “Receive Data” is “N”, it means the
equipment has not received data from external system. If “Valid Frame” is ‘N’, it indicates the
setting error of baud rate or protocol while “Valid Address” is “N”, it means the communication
address is set wrongly. ”Send Data” is "N” means datagram sent from the equipment is wrong. If
all those status are ‘Y’, it means communication is established successfully.
This test verifies that the accuracy of current measurement is within the acceptable tolerances.
All protections will leave the factory set for operation at a system frequency of 50Hz or 60Hz.
All relays will be set for operation at a system frequency of 50Hz. If operation at 60Hz is required
then this must be set at menu.
Apply current equal to the current transformer secondary winding rating to each current
transformer input of the corresponding rating in turn, see the following table or external connection
diagram for appropriate terminal numbers, checking its magnitude using a multimeter/test set
readout. The corresponding reading can then be checked in the relays’ menu.
The measurement accuracy of the relay is ±5%. However an additional allowance must be made
for the accuracy of the test equipment being used.
1 I_S1_Exc In
4In
2 I_S2_Exc In
4In
3 I_Term_Gen In
4In
4 I_NP_Gen In
4In
5 I_HVS1_Tr In
4In
6 I_HVS2_Tr In
4In
7 I_HVS_Tr In
4In
8 I_CT_HVS_ST1 In
4In
9 I_Br1_ST1 In
4In
10 I_CT_HVS_ST2 In
4In
11 I_Br1_ST2 In
4In
In *******************
12 Id_TrvDiff_Gen
4In *******************
In *******************
13 I0_NP_HVS_Tr
4In *******************
Note:
To avoid damage the equipment, we can’t inject a high value current (such as 4In or more) to the
equipment for long time, we suggest that the time in high current condition should not over 3
second every time.
The measurement accuracy of the protection is ± 5%. However, an additional allowance must be
made for the accuracy of the test equipment being used.
This test only needs to be performed on models with voltage transformer inputs as it verifies that
the accuracy of voltage measurement is within the acceptable tolerances.
Apply rated voltage to voltage transformer input, checking its magnitude using a multimeter/test
set readout. The corresponding reading can then be checked in the relays menu.
The measurement accuracy of the relay is ±5%. However an additional allowance must be made
for the accuracy of the test equipment being used.
Displayed in LCD
Input
Angle Angle
No. Items
PhA PhB PhC between A between A
value
and B and C
58V
1 U_VT1_Term_Gen
20V
58V
2 U_VT2_Term_Gen
20V
58V
3 U_HVS_Tr
20V
100V
4 U0_DeltVT_HVS_Tr
20V
100V
5 U0_NP_Gen
20V
100V
6 U0_DeltVT1_Term_Gen
20V
100V
7 U0_DeltVT2_Term_Gen
20V
Note:
When check the rotor current channel, 0.075V is equal to 1000A of rotor current, please refer to
section 7.2 [I1n_RotWdg] and [U2n_Shunt_RotWdg]
The measurement accuracy of the protection is ±5%. However, an additional allowance must be
made for the accuracy of the test equipment being used.
Note:
The trip circuit should remain isolated during these checks to prevent accidental operation of the
408 NANJING NARI-RELAYS ELECTRIC CO., LTD
Chapter11 Commission
Transfer them from a pre-prepared setting file to the relay using a portable PC running the
appropriate software via the relay’s RS232 port located on the frontplate of the relay. This method
is preferred for transferring function settings as it is much faster and there is less possiblity for
error.
Tests mentioned above have already demonstrated that the relay is within calibration, thus the
purpose of these tests is as follows:
− To determine that the primary protection functions, such as generator differential protection,
overcurrent protection and so on, can trip according to the correct application settings.
− To verify correct assignment of the trip contacts, by monitoring the response to a selection of
fault injections.
It is not the intension of the test to verify the operation of the complete system from the relay to the
remote location, just the relay’s rear communications port and any protocol converter necessary.
Connect a portable PC to the relay via a EIA(RS) 485-232 converter. Ensure that the relay
address and the baud rate settings in the application software are set the same as those in relay.
If the relay has the optional fiber optic communications port, then a fibre optic-RS232 converter
shall be applied.
-Confirm the external wiring to the current and voltage inputs is correct.
Remove all test leads, temporary shorting leads, etc. and replace any external wiring that has
been removed to allow testing.
If it has been necessary to disconnect any of the external wiring from the relay in order to perform
any the foregoing tests. It should be ensured that all connections are replaced in accordance with
the relevant external connection or scheme diagram.
NANJING NARI-RELAYS ELECTRIC CO., LTD 409
Chapter11 Commission
Voltage connections
Using a multimeter measure the voltage generator secondary voltages to ensure they are correctly
rated. Check that the system phase rotation is correct using a phase rotation meter.
Comparing the values of the secondary phase voltages with the relay’s measured values, which
can be found in the menu.
Current connections
Measure the current transformer secondary values for each input using a multimeter connected in
series with the corresponding current input. (It is preferable to use a tong-test ammeter instead)
Check that the current transformer polarities are correct by measuring the phase angle between
the current and voltage either against a phase meter already installed on site and known to be
correct or by determining the direction of power flow by contacting the networks control center
(NCC).
Compare the values of the secondary phase currents and phase angle with the relay’s measured
values, which can be found in menu.
Remove all test or temporary shorting leads, etc. If it has been necessary to disconnect any of the
external wiring from the relay in order to perform the wiring verification tests, it should be ensured
that all connections (wiring, fuses and links) are replaced in accordance with the relevant external
connection or scheme diagram.
Ensure that all event records, fault records, disturbance records, alarms and LEDs have been
reset before leaving the relay.
Connect RS-232 communication port of the computer and that of RCS-985B protection equipment
by a cable with DB-9 connectors on both ends. Run the program RCSPC. If the connection is
correct, the screen will show “RCS-985B connected”, see Figure 11.6-1. Even if the computer is
off line, this picture will be still shown but the words about connection will disappear.
Set the PC com port’s baud rate which is connected with front series port of RCS-985B as
9600bps.
There are 3 bars on top of the screen, from top to bottom: title bar, menu bar and tool bar, see
Figure 11.6-3.
First, click the first button of tool bar parameter, dialog box of communication parameters is
displayed, see Figure 11.6-4. Only the parameter of [COM port] shall be configured as the port of
computer which is actually connected with the equipment, all other parameters shall be configured
as the same as displayed in Figure 11.6-4.
Here is only brief description of usage. Please refer to dedicated manual of RCSPC for detail.
The function is used for offline parameter setting. First, input setting parameters and saves it in PC,
then connects PC with the protection equipment, executive “DOWNLOAD” command, and the
settings saved in PC will be transferred to the protection equipment, so most part of the setting
operation can be finished in office instead of in substation.
Here is the procedure to input settings offline. Before connect PC with RCS-985B, run the
software of RCSPC,click on “setting” icon, a popup dialog box will appear which asks user
whether or not to set parameter offline, click “yes” and input “985Gxxx” (xxx represents program
version, point ignored) to confirm the relay type and version of the protection program, then
parameter setting interface will appear. The settings displayed first are default settings, user can
replace them with application-specific settings. After modification, save the settings into a file.
When PC is connected with the protection equipment, open the setting file and transfer setting to
protection.
When PC is connecting with RCS-985B, run RCSPC, the PC screen will display “RCS-985Bxxx
connected”, click on “SETTING” icon, then parameter setting interface will appear, the settings
uploaded from RCS-985B will be displayed, user can modify them to application-specific settings.
11.6.4.2 Status
Click button, user can observe real time sampled data and binary inputs status.
11.6.4.3 Report
Click button, entering report view part of the program, choose a report in the table, and click
“report record”, save report data according to following clue on instruction. The data can be used
in the auxiliary analyze software to show us the fault course of power system and the logic
calculation course of RCS-985B again.
Click button, all magnetic latched output relays and signal relays will be reset.
Click button, entering trip test part of the program, click contacts to change the status of
relays displayed, a same operation command to breaker circuit will be issued. This function is
used to test breaker circuit without apply electric quantities to the protection equipment.
Chapter12 Maintenance
RCS series relays are self-supervising and so require less maintenance than earlier designs of
relay. Most problems will result in an alarm so that remedial action can be taken. However, some
periodic tests should be done to ensure that the relay is functioning correctly and the external
wiring is intact.
Before carrying out any work on the equipment, the user should be familiar with the contents of the
Safety and technique Data sections and the ratings on the equipment’s rating label.
12.2.1 Alarms
The alarm status LED should first be checked to identify if any alarm conditions exist. If so, try to
find the cause of the alarm and eliminate it and clear the alarms to extinguish the LED.
Alternatively, the values measured by the relay can be checked against known values injected into
the relay via the test block, if fitted, or injected directly into the relay terminals. Suitable test
methods can be found in relevant manuals. These tests will prove the calibration accuracy is being
maintained.
NANJING NARI-RELAYS ELECTRIC CO., LTD 415
Chapter12 Maintenance
The preferred method is to replace the complete relay as it ensures that the internal circuitry is
protected against electrostatic discharge and physical damage at all times and overcomes the
possibility of incompatibility between replacement PCBs.
Replacing PCBs can reduce transport costs but requires clean, dry conditions on site and higher
skills from the person performing the repair. However, if the repair is not performed by an
approved service center, the warranty will be invalidated.
Before carrying out any work on the equipment, the user should be familiar with the contents of the
Safety and technique Data sections and the ratings on the equipment’s rating label. This should
ensure that no damage is caused by incorrect handling of the electronic components.
Before working at the rear of the relay, isolate all voltage and current supplies to the relay.
Note:
The RCS serials relays have integral current transformer shorting switches which will close when
the connecting terminal is removed.
Disconnect the relay earth, IRIG-B and fiber optic connections, as appropriate, from the rear of the
relay.
Note:
The use of a magnetic bladed screwdriver is recommended to minimize the risk of the screws
being left in the terminal block or lost.
Without exerting excessive force or damaging the scheme wiring, pull the terminal blocks away
from their internal connectors.
Remove the screws used to fasten the relay to the panel, rack, etc. These are the screws with the
Withdraw the relay carefully from the panel, rack, etc. because it will be heavy due to the internal
transformers.
To reinstall the repaired or replacement relay, follow the above instructions in reverse, ensuring
that each terminal block is relocated in the correct position and the case earth, and fiber optic
connections are replaced.
Once reinstallation is complete the relay should be re-commissioned using the instructions in
Chapter11 of this manual.
Before replacing a PCB the auxiliary supply must be removed, and wait 5s for capacitors to
discharge. It is also strongly recommended that the voltage and current transformer connections
and trip circuit are isolated.
The relay, being modular in design, allows for the withdrawal and insertion of modules. Modules
must only be replaced with like modules in their original factory configured slots.
NR Support teams are available world-wide, and it is strongly recommended that any repairs be
entrusted to those trained personnel. For this reason, details on product disassembly and
re-assembly are not included here.
This battery will periodically need changing. If the battery-backed facilities are not required to be
maintained during an interruption of the auxiliary supply, the steps below can be followed to
remove the battery.
Before carrying out any work on the equipment, the user should be familiar with the contents of the
safety and technique data sections and the ratings on the equipment’s rating label.
Gently extract the battery from its socket. If necessary, use a small, insulated screwdriver to prize
the battery free.
Ensure that the metal terminals in the battery socket are free from corrosion, grease and dust.
The replacement battery should be removed from its packaging and placed into the battery holder,
taking care to ensure that the polarity markings on the battery agree with those adjacent to the
socket as shown as below.
Note:
Ensure that the battery is securely held in its socket and that the battery terminals are making
good contact with the metal terminals of the socket.
The battery that has been removed should be disposed of in accordance with the disposal
procedure for Lithium batteries in the country in which the relay is installed.
12.5 Cleaning
Before cleaning the equipment ensure that all AC and DC supplies, current transformer and
voltage transformer connections are isolated to prevent any chance of an electric shock whilst
cleaning.
The equipment may be cleaned using a lint-free cloth moistened with clean water. The use of
detergents, solvents or abrasive cleaners is not recommended as they may damage the relay’s
surface and leave a conductive residue.
13.1 Decommissioning
DANGER: Before disconnecting the power supply cables that connected with the DC
module of the RCS-985B, make sure that the external miniature circuit breaker of the power
supply is switched off.
DANGER: Before disconnecting the cables that are used to connect analog input module
with the primary CTs and VTs, make sure that the circuit breaker for the primary CTs and VTs is
switched off.
13.1.3 Dismantling
The RCS-985B rack may now be removed from the system cubicle, after which the cubicles may
also be removed.
DANGER: When the station is in operation, make sure that there is an adequate safety
distance to live parts, especially as dismantling is often performed by unskilled personnel.
13.2 Disposal
In every country there are companies specialized in the proper disposal of electronic waste.
NOTE: Strictly observe all local and national regulations when disposing of the device.
Equipment type;
To be simplified, user can provide such information by finishing the following table and send it to
manufacture.
NR
Ordering form RCS-985B
Item RCS-985B * * * * * * *
Protective Functions
Standard Configuration
Communication Port
EIA-232 and 2 x EIA-485 A
EIA-232 and 2 x Optical converter B
EIA-232 and 2 x Ethernet*
110/125 Vdc 1
220/250 Vdc 2
Communication medium
Shielded twisted pair wires T
Optical Fiber O
Communication Protocol
IEC 60870-5-103 S
MODBUS M
IEC 61850* E
Terminal Type
Jointing Terminal C
Screw terminal Block S
Color of panel (Inter Grey, Apple green and light camel grey are recommended colors).
Chapter16 ANNEX
1A 5
13. I2n_CT_NP_Gen 1A/5A
0-60000 A 1A 12000
14. I1n_CT_TrvDiff_Gen
1A,5A 1A 5
15. I2n_CT_TrvDiff_Gen
1A 1000
16. I1n_RotWdg 0-60000 A
0-100.00 mV 0.01 mV 75
17. U2n_Shunt_RotWdg
200
18. U1n_Exc 0-600 V 0.01 V
1 7FFF
16. TrpLog_REF_Tr 0000-FFFF
0/1 0
20. En_VCE.ROV_Ctrl_ROC2_Tr
0
21. En_Dir_Ctrl_ROC1_Tr 0/1
0
22. En_Dir_Ctrl_ROC2_Tr 0/1
0
23. En_Alm_ROV_LVS_Tr 0/1
8. En_SensTrvDiff_Gen 0,1 0
9. En_UnsensTrvDiff_Gen 0,1 0
10. En_SensROV_Longl_Gen 0,1 1
11. En_UnsensROV_Longl_Gen 0,1 1
12. En_DPFC_IntTurn_Gen 0,1 0
RCSPC Configuration and testing program (user version) is developed for the user to configure,
test and maintain RCS-985 series protection equipment on site. It comprises four parts: sampled
value display, settings reading and modification, report process and trip test. For RCS-985x, these
four parts correspond to 4 files 985x_status, 985x_set, 985Bx_rpt and 985x_tst respectively and
are described hereinafter (X represents the special type the protection program, for example,
RCS-985B3YD, here, x represent B3YD).
Connect RS-232 communication port of the computer and that mounted on left side of front panel
of RCS-985 protection equipment by a cable with DB-9 connectors on both ends. Run the
program RCSPC. If the connection is correct, the screen will display “RCS-985B3YD connected”,
see Figure 16.2-1 . Even if the computer is off line, this picture will be still displayed but the words
about connection will disappear.
There are 3 bars on top of the screen, from top to bottom: title bar, menu bar and tool bar, see
Figure 16.2-2.
First, click the first button of tool bar parameter, dialog box of communication parameters is
displayed, see Figure 16.2-3. Only the parameter of “COM port” shall be configured as the number
of port of computer that is actually connected with the equipment, other parameters shall be
configured as the same as displayed values in figure.
The title bar shows only title of the program and needs no explanation. Menu bar and tool bar are
described as follows:
1) File
There is only one item in pull-down menu File, i.e., Exit. Click Exit(X), the program will be exited.
2) Execute
There are three items in pull-down menu Execute: Setting(E), Download(D) and Trip_Test(T).
Click Setting(E), entering settings reading and modification part of the program, please refer to
section 16.2.3 for details.
Click Trip_Test(T), entering trip test part of the program, please refer to section 16.2.5 for details.
3) View
There are five items in pull-down menu View: Toolbar(T), Status(S), Report(L), Status(Z) and
Message(M).
Item Toolbar specifies whether the tool bar shall be displayed. When the tool bar is displayed, a
symbol “√” is put before “Toolbar (T)”. If this item is clicked then, the tool bar will be hidden and
the symbol “√” will disappear.
Item Status(S) specifies whether status bar in the bottom of the picture shall be displayed.
Click Report(L), entering Report treatment part of the program, please refer to section 16.2.4 for
details.
Click Status(Z), entering Sampled value display part of the program, see section 16.2.2 for details
Click Message(M), data flow between RCSPC program and the protection equipment will be
displayed. This is used not for the user version but development version of the program.
4) Set
There are five items in pull-down menu Set: Switch_CPU_MON(P), Parameter(C), Back_color(B),
Font-Color(F) and Font(O).
If there is a symbol “√” before item Switch_CPU_MON(P), that means data acquired by module
CPU are displayed currently, see Figure 16.2-1. If the item Switch_CPU_MON(P) is clicked then,
the data displayed will be changed to those acquired by module MON, see Figure 16.2-5.
Meanwhile, symbol “√” will disappear.
Function of item Parameter(C) is the same as the first button of tool bar parameter. Click this
item, dialog box of communication parameters will be displayed, see Figure 16.2-3.
Click Back_Color(B), dialog box of background color is displayed. The user can select preferred
color for background displayed.
Click Font_Color(F), dialog box of font color is displayed. The user can select preferred color for
font displaying.
Click Font(O), dialog box of name, style and size of the font is displayed. The user can select the
preferred ones for font displaying.
5) Help
There are three items in pull-down menu Help: Help(H), Version(N) and About RCSPC.
Click Help(H), commands used for the program will be displayed. It is not necessary for the user
to use these commands, and no further information about them is presented here.
Click Version(N), historical record about time and description of updating of this program is
displayed.
Click About RCSPC, developer of this program and copyright declaration will be displayed.
There are 23 buttons in the tool bar, in which 16 buttons are enabled. They are depicted in
sequence from left to right as follows:
1) Parameter
446 NANJING NARI-RELAYS ELECTRIC CO., LTD
Chapter16 ANNEX
Function of this button is the same as that of item Parameter(C) of menu Set of the menu bar.
Click this button, dialog box of communication parameters will be displayed, see Figure 16.2-3.
2) Data parameter
Click this button, other parameters will be displayed. They are data start address, data block size,
single data block number, report data number, etc, 11 items in total. These parameters are
configured already in the coefficient y and needs no further Configuration on site.
3) Device type
Click this button, a small dialog box “please enter device type” is displayed. Type of the
protection equipment shall be entered. In the RCS-985 case, the device type is 985B3YD. This is
used mainly for the user to make configuration in off line condition.
4) Setting
Function of this button is the same as item Setting(E) of menu Execute of menu bar. Click this
button, i.e. entering settings reading and modification part of the program; Please refer to section
16.2.3 for details.
5) Status
Function of this button is the same as item Status(Z) of menu View of menu bar. Click this button,
entering Sampled value display part of the program; Please refer to section 16.2.2 for details.
6) Report
Function of this button is the same as item Report(L) of menu View of menu bar. Click this button,
entering Report view part of the program; Please refer to section 16.2.2 for details.
7) Trip test
Click this button, entering trip test part of the program; Please refer to section 16.2.2 for details.
8) Switch to command
When several dialog boxes are displayed, and the operator wants to enter Command mode but
not close dialog box, this button can be used to switch on Command and hide dialog boxes.
However, it is not needed for the user on site generally.
9) Download program
10) CPU<–>MON
Function of this button is the same as item Switch_CPU_MON(P) of menu Set of menu bar. Click
this button, data displayed will be changed between those acquired by module CPU and module
MON one after another.
Function of this button is the same as item Font(O) of menu Set of menu bar.
Function of this button is the same as item Font_Color(F) of menu Set of menu bar.
Function of this button is the same as item Back_Color(B) of menu Set of menu bar.
Six buttons on right hand of are all gray. They are used not for this
version but others of this program.
Click this button, all activated output relays and signal relays will be reset.
16) Help
Function of this button is the same as item Help(H) of menu Help of menu bar.
Besides, some shortcut keys on keyboard of the computer have same functions with items of
menu of menu bar or buttons of tool bar:
F1 — same as item Help(H) of menu Help and button Help of tool bar;
F2 — same as item Parameter(C) of menu Set and button Parameter of tool bar;
F3 — same as item Switch_CPU_MON(P) of menu Set and button CPU<->MON of tool bar;
F4 — same as item Setting(E) of menu Execute and button Setting of tool bar;
F5 — same as item Status(S) of menu View and button Status of tool bar;
F6 — same as item Report(L) of menu View and button Report of tool bar.
Click item Status(S) of menu View or button Status of tool bar, real time sampled analog
values will be displayed.
exchanged to each other by clicking two arrows on left hand of the bottom or pull down
Page 2 shows mechanical protection inputs as well as others binary input status where “1” is “yes”
and “0” is “no”.
Page 3 shows pickup of protective elements where “1” is “activated” and “0” is “inactivated”.
Figure 16.2-6 a) and b) are pictures of value of module CPU, and can be changed to value of
module MON by CPU-MON choose item at the right hand of bottom of this page.
Pull down box at right hand of the bottom is gray. That means these values exist only in module
MON and cannot be read from module CPU.
This part is used for reading and modification of settings of the equipment. Click item Setting(E)
of menu Execute or the fourth button Setting of tool bar, settings will be displayed. For
example, Figure 16.2-9 shows the parameters of the equipment.
In the same way, user can click other labels in picture of Setting(E) to read and modification all the
settings of the equipment.
There are 7 buttons in bottom of every picture of the part Settings reading and modification. From
left to right, they are: PRINT, DEFAULT, UPLOAD, DOWNLOAD, READ, SAVE and CLOSE and
depicted as follows:
If default settings are displayed and button UPLOAD is pressed, default settings displayed will be
replaced by actual settings of the protection equipment, in which, the settings different from default
settings will be displayed in red. Vice versa, if actual settings are displayed and button DEFAULT
is pressed, actual settings displayed will be replaced by default settings of the protection
equipment, in which, the settings different from actual settings will be displayed in red.
16.2.4 Report
There are 3 kinds of reports in this program: tripping report, self-diagnose report and change of
status report. The tripping report is displayed first.
Click item Report(L) of menu View, or click the sixth button of tool bar, tripping report will be
displayed for a moment. It is the report of operation of protection relays, including number of the
report, time of pickup of protection, time interval from pickup to operation, name of the operating
protection element and the faulty phase, see Figure 16.2-12.
In order to save time for displaying, report of the latest 3 tripping is displayed firstly. Click the fifth
button REFRESH of eight buttons in the bottom of the picture, complete tripping report will be
displayed after a longer delay.
If oscillogram record of a fault tripping is needed, the record item shall be clicked first, color of this
item will be changed to light blue, click the fourth button RECORD at the bottom, then RCSPC
starts to read oscillogram data from the protection equipment.
Oscillogram data is massive and more time is needed to read it. A dialog block of saving the data
displayed as a file will be displayed when data reading is completed. If these data are saved in a
file and then oscillogram recorded can be displayed by oscillogram analysis program Drawing.exe
or Wave.exe developed by our Company. The oscillogram can be analyzed also if needed.
The sixth button SAVE at the bottom is used for saving the report as a file in the computer. The
seventh button PRINT is used to print the report. All reports of this program can be saved as file
or printed in this way. The eighth button CLOSE is used to close the picture displayed.
After click the second button FAIL at bottom of Figure 16.2-13, self-diagnose report will be
displayed for a moment. It is the report of hardware failures, overload, cooling system initiating or
other abnormal events detected by the equipment.
The records are stored in cyclic non-volatile memory and up to 32 events can be recorded.
After click the third button SW CHG at the bottom of Figure 16.2-13, change of status input report
will be displayed for a moment. It is the report of binary input, starting status of the equipment,
including serial number of record, time of the change and brief description about the change.
The records are stored in cyclic non-volatile memory and up to 32 events can be recorded.
Object of the tripping test is to check activation of the tripping or signal output relays of the
equipment during the test not by applying voltages and currents on the equipment but by operation
of the program.
Object of the communication with the host computer test is to check correctness of the message
sent from the equipment during the test not by applying voltages and currents on the equipment
but by operation of the program.
Then, click item Trip_Test(T) in menu Execute, or click the seventh button of tool bar Trip
test, picture of protection tripping test will be displayed as shown in Figure 16.2-14.
There is only one item in the picture, i.e., Test_Differential_Trip, differential protection tripping test,
click the test button , related output relays will operate, and correspondent signals
will be sent. Correctness of these operations can be checked and this button changes to
then.
Click the red reset button again, all of the operated relays will dropout, test status will be resumed
and the reset button will return to .
First, the parameters of [Test_Trip_Option] and [Test_Comm_Option] (if available) shall be set
as enabled.
Click label in Figure 16.2-15, picture of communication with the host computer will
Click test button of any item, relevant activation of this item will be recorded in the
report.
The report will be sent to the host computer, and correctness of the communication can be
checked then.