RECEIVING THE CHILLER
Inspect the chiller. Check for concealed damage that may have occurred during
shipment. Look for dents, scratches, loose assemblies, evidence of oil, etc. Damage
evident upon receipt should be noted on the freight bill. Damage should be brought to
the attention of the delivering carrier - NOT to us within 15 days of delivery. Save the
carton and packing material and request an inspection. Then file a claim with the
delivering carrier.
We cannot accept responsibility for freight damages; however, we will assist you
in any way possible.
1
Technique data
Model RC-3AF RC-5AF RC-8AF RC-10AF RC-12AF
kW 3.0 4.7 7.9 11.0 13.5
Cooling Capacity 3
10 kcal/h 2.58 4.04 6.79 9.46 11.61
Power Supply V/ph/Hz 380/3/50
Input Power kW 3.1 5.0 7.0 9.5 10.8
Compressor Type Scroll
Compressor Power kW 2.25 3.75 6.0 7.5 9.0
Pump Power kW 0.55 0.75 0.75 1.15 1.15
Pump Head m 22.5 22.0 20.0 22.5 20.0
Chilled Water Flow m3/h 0.89 1.5 2.0 2.5 3.2
Evaporator Type Water Tank Type/Stainless Steel Plate Type
Water Tank Volume L 55 90 120 200 200
Pipe Size DN 25 25 32 40 40
Condenser Coil
3
Air Volume m /h 4000 6800 9300 10600 12000
Fan Power W 150 360 500 500 500
Refrigerant R22/R404
Throttle Mode Capillary Tube/Expansion Valve
Protector Pressure,Overload,Anti-freeze,Delay,Over-temperature,Water Flow
Noise Level dB(A) 58 58 62 62 65
Weight kg 135 175 300 430 550
L mm 950 950 1450 1450 1800
Dimensions W mm 560 560 785 785 800
H mm 1100 1100 1300 1300 1550
Model RC-15AF RC-20AF RC-25AF RC-30AF RC-40AF
kW 16.5 22.0 24.5 27.0 35.0
Cooling Capacity 3
10 kcal/h 14.19 18.92 20.64 23.22 30.1
Power Supply V/ph/Hz 380/3/50
Input Power kW 15.2 20.1 22.2 29.4 35.5
Compressor Type Scroll
Compressor Power kW 11.25 15.0 18.75 22.5 30.0
Pump Power kW 2.25 2.25 2.25 3.75 3.75
Pump Head m 25.5 22.0 20.0 25.5 20.0
3
Chilled Water Flow m /h 4.5 6.0 7.5 9.0 11.0
Evaporator Type Water Tank Type/Stainless Steel Plate Type
Water Tank Volume L 280 350 350 420 480
Pipe Size DN 50 50 65 65 80
Condenser Coil
3
Air Volume m /h 16000 20000 24000 29000 39600
Fan Power W 1200 1600 1700 2200 2700
Refrigerant R22/R404
Throttle Mode Expansion Valve
Protector Pressure,Overload,Anti-freeze,Delay,Over-temperature,Water Flow
Noise Level dB(A) 65 65 68 68 68
Weight kg 750 830 920 1100 1250
L mm 1800 1900 1900 2200 2900
Dimensions W mm 900 1000 1000 1050 1680
H mm 1780 1850 1850 1960 2200
Directions:
1、The cooling capacity is based on a 35℃ ambient temperature, a 0℃ entering water temperature and a-5℃ leaving
water temperature.
2、Design and specification are subject to change without prior notice.
3、All products are our standard products, please contact with us for special design.
2
Unit control
Computer panel
电源 POWER
运行 RUN PV
故障 ERROR
压缩机1 COMP1
压缩机2 COMP2 SV
复位 -调整/ADJUST- 设定
DOWN
RESET SET
UP
水泵 压缩机1 压缩机2 启动 停止
3
Error monitor
Code Name Explanation
15 freezing
2·Capacity adjust
(1) Start unit: press "PUMP" to start unit: start chilled pump----time delay----start fan----time
delay----start compressor according to water temperature.
(2) Turn off unit :Press "OFF" to turn off unit: turn off all compressor---- time delay ----turn off
fan( or cooling pump)----- time delay -----turn off chilled pump.
During water temperature reducing,when T< Ts,turn off one compressor,when T< Ts
4
-ΔT,turn off two compressorressor.
(4) After turn off compressor,fan delay working,when time delay finished, fan turn off.
3·Operate process:
(1) After main program start , PV section show actual water temperature ,SV section show
setting temperature . Press "SET" to adjust the setting temperature , press "DOWN" or
"UP" to adjust the temperature, when adjust finished, press"SET" to exit.
(2) When there is error,PV section show "ERROR", SV section show error code. To find the
relevant error in the monitor, after error eliminated,press "REST" to reset.
(3) "COMPl"、"COMP2” is the start key of compressor1 and compressor2.
When compressor start,the LED indicator light turn on; Only when the unit working,
the "COMPl" key and "COMP2”key is effective.
(4) The indicator light:
POWER—Power indicator light
RUN— Unit working state
COMPl—Compressor1 working state
COMP2—Compressor2 working state
ERROR— Mean error
5
QF5
N
N
T L
Emergency
S Stop
R
KM3 KM4 KM2 KM1
401
402
403
404
Electric schematic diagram
Compressor1
Compressor2
FR1 FR2 FR3
CH1
CH2
4 3 2 1
5 6 7 8
KVS
Compressor2 overload
Compressor2 low pressure
Compressor2 high pressure
Compressor1 overload
Compressor1 low pressure
Compressor1 high pressure
305
304
303
302
301
208
207
206
205
204
control
FR3
FL2
FR2
LP2
HP2
FR1
LP1
HP1
6
Safety Precautions
1. Installation Precautions:
In order to bring into best play the optimum performance of the equipment, please
check the following article notes. If they are not normative, please take effective
measures to solve them prior to operating the unit.
Installation shall be done with the technical guidance of the manufacturer. Poor
installation will cause such disasters as electric leakage, electric shock and etc.
Such accidents as leakage, electric shock and fire may be brought about due to
nonstandard installation.
Should the installation foundation not be firm, the subsidence of unit or personal
injury may take place.
●electric installation
In electric installation there should be special line, which shall be in the charge of the
special electricians. Shortage of power supply in line or wrong power supply shall
give rise to such accidents as electric shock and fire.
●The standard cable and wire shall be used in line connection, and the firmness of
each joint be guaranteed.
High temperature and fire disaster may arise out of loose connection of wire and joint.
The auxiliary equipment shall be the specific product. Wrong choice of such a product
is easy to cause electric shock and fire.
7
●Installation of the unit at the place for possible leakage of inflammable gas is
prohibited.
In case of leakage of inflammable gas and assemblage around the unit the fire will
possibly happen.
●The leakage breaker shall be set and installed in accordance with the technical
standard of electric equipment and standards of indoor wiring.
●The chilled water used in the unit shall comply with the water quality standards.
In addition to damages to the performance and service life of the unit, the
deterioration of water quality may give rise to water leak.
The earth wire can’t be connected with gas pipe, water pipe, lightning arrester. Wrong
methods of grounding shall produce electric shock.
The cooling-water unit can’t be installed in the areas adjacent to hot spring, coast or
full of oil, because the corrosion of the unit arising from these natural elements shall
cause electric shock or fire.
●The power wires can’ be laid in the unit bay for fear of fire disaster.
8
2.Operation Precautions
●In case of abnormality in operation of the unit (such as scorch smell) please have
power cut and contact the distributor immediately.
●Use of any refrigerant but water is not allowed, or fire or explosion shall arise.
●No controlling the operation and stoppage of the unit directly with power switch or
brake, otherwise such an operation shall give rise to electric shock or fire.
The cooling-water unit being installed in the room of mechanical equipment, the
practical measures shall be taken against leakage of refrigerant. In case of leakage of
secondary refrigerant beyond the limit of concentration the anoxia accident shall find
the people.
●The unit can’t be used for other purposes out of the design range. This unit is not
applicable to storage of food, animals and plants, precision instruments, arts and etc.,
or these articles shall deteriorate in quality.
The replacement of fuse by electric wire shall endanger equipment or cause fire.
●No pressing the electromagnetic contactor with fingers to start up the compressor for
fear of electric shock or fire.
●The unit can’t be started up when the door of control box is opened, for fear of
electric shock or fire.
●It is absolutely disallowed to operate the unit with wet hands because such an action
is one of the reasons for electric shock.
9
●Force startup of the unit by emergency apparatus of short circuit is prohibited, which
shall possibly result in such aftermaths as fire and explosion.
●Placement of liquid vessel (such as vase) on the machine body is not allowed.
Provided that the liquid spills and flows into the unit, it shall damage the electrical
device so as to cause electric shock.
●The unit shall be shut down and the power cut off for cleaning, for fear of accidental
injury.
●It is a must to release the remained water completely in case of long disuse of the
unit.
In the period for long disuse of the unit the water pipe shall be filled with
non-freezing solution or the remained water discharged completely, or it shall bring
about the leakage of water pipe.
●Inspection shall be given to the firmness of the foundation after the unit works for a
period.
●Washing the unit with water is forbidden, for fear of electric shock.
●The chilled water and cooling water must fulfill the requirements of water quality.
Deterioration of water quality shall spoil the performance and service life of the unit
and cause leakage.
●It is not allowed to touch the high-temperature part of compressor and the coolant
pipeline for fear of scald.
10
Troubleshooting
11
The exhaust pressure is too Check exhaust pressure, determine and
high. remove the reason for over-high exhaust.
The
Check whether the voltage is consistent with
compressor
The voltage is too high or low. the rated value of the unit. Correct the
stops due to
unbalance of phase if necessary.
cutoff of
The back temperature of Check and remove the reasons for over-high
heat
chilled water is too high. back temperature.
detector in
the motor. The system refrigerant is not
Check the leakage of refrigerant.
adequate.
The infused refrigerant is not
Add the refrigerant.
enough.
The overload protective switch
Check the reasons and repair it. Restart the
is cut off or the control circuit
unit.
fuse burnt up.
12
Maintenance of Unit
1、 In order to keep the unit in the best working condition, regular maintenance shall
be given to the following items. If necessary, adjust it and get done with the
inspection records.
Inspection Central Control
Items Methods Aftermath
Time Targets
Check
Exhaust pressure high-pressure 1.5.2~2.2MPa MPa
gage
Check
The high of
high-pressure <0.1Mpa MPa
compressor
gage
Check
Suction pressure 0.02~0.15Mpa MPa
low-pressure gage
2 、The condenser shall be cleaned once every three months or in case of abnormality
in high pressure.
♦ Incrustant and mildew shall be produced after the cooling tower works a long time
so as to weaken the refrigeration capability of the unit as well as to disable the
protective device in normal operation due to frequent actions.
♦ In the area with no guarantee of water quality, the condenser shall be washed often.
♦ For the detailed washing methods, please contact the local distributors.
4、 In case of long disuse, sometimes the water pump impeller shall be blocked by the
sediments, so the radiator fan of the water pump shall be turned with hands prior to
use of the machine.
13
5、 In case of alarm stoppage in operation of the unit, please let the related personnel
informed promptly for inspection of the unit. If the failures can’t be removed, please
contact the manufacturer or local distributor directly.
6、 Shorting the water-flow switch in the operation of the unit is prohibited for fear of
frost cracking of water pipe.
7、The machine room shall be equipped with related safety apparatus and maintenance
and detecting tools such as pressure gage, thermometer and etc. The tools shall be
emplaced at the fixed positions.
8、Please cut off the main power supply after the shutdown of the unit.
9、In case of long disuse to the unit, all accumulated water in the chilled water and
cooling water systems shall be released completely for fear of rust. The end cap of the
condenser water box shall be sealed.
10 、In case of long disuse to the unit, the maintenance shall be got done with.
11、 It is suggested to change the lubricant when the lubricant deteriorates and the
foreign matters and moisture in the oil increase.
14
WARRANTY:
Please note: Warranty effective at time of shipment.
Our warrant that all material and workmanship are free of defects in quality which
impair the usefulness of the chiller.
A. Voltage variation no greater than plus or minus 10 of nameplate.
B. Frequency variation no greater than plus or minus 3 Hz. of nameplate.
C. Must not exceed minimum and maximum stated temperatures on the nameplate
D. Not to exceed rating, including any heat sink, as indicated on the nameplate
E. The unit must not be restarted for a period of one (1) minute after intentional or
accidental shut-off.
Our warrants that all material and workmanship are free of defects in quality
which impair the usefulness of the filter fan package and all custom chillers and heat
exchangers for a period of one (1) year, except for the filter, when installed and
operated under conditions A, B, C, and D as listed above.
Not covered in this warranty is damage to the chiller or heat exchanger due to the
introduction of other than the nameplate - designated refrigerant. Operation of any our
product that has not been designed with proper protective coatings and/or options and
is in an abnormal or corrosive environment voids the warranty. Prolonged operation
with dirty filters also voids the warranty.
Should any part prove defective within the above warranty period, the customer
may choose to return the defective product that is under warranty to our for repair at
no charge or the customer has the option to repair the defective products at his own
expense and our will supply repair parts at no charge providing the defective part is
returned and found to have failed under warranty. Parts supplied as warranty
replacement parts will assume the balance of the warranty on the part returned for
warranty consideration.
Please be advised: According to the Federal Register, no person maintaining,
servicing, repairing, or disposing of appliances may knowingly vent or otherwise
release into the environment any class I or class II substance used as refrigerant.