Air System Sizing Summary for 03-L2- FCU-101-R13

Project Name: DJIBOUTI-LEVEL 2-26-03-18- 04/02/2018


Prepared by: a 10:25AM

Air System Information


Air System Name 03-L2- FCU-101-R13 Number of zones 1
Equipment Class CW AHU Floor Area 26.6 m²
Air System Type SZCAV Location Dubai, United Arab Emirates

Sizing Calculation Information


Calculation Months Jan to Dec Zone L/s Sizing Sum of space airflow rates
Sizing Data Calculated Space L/s Sizing Individual peak space loads

Central Cooling Coil Sizing Data


Total coil load 2.3 kW Load occurs at Sep 1900
Sensible coil load 2.0 kW OA DB / WB 43.9 / 28.2 °C
Coil L/s at Sep 1900 160 L/s Entering DB / WB 25.4 / 18.6 °C
Max block L/s 160 L/s Leaving DB / WB 14.9 / 14.3 °C
Sum of peak zone L/s 160 L/s Coil ADP 13.8 °C
Sensible heat ratio 0.858 Bypass Factor 0.100
m²/kW 11.4 Resulting RH 55 %
W/m² 88.1 Design supply temp. 14.0 °C
Water flow @ 8.9 °K rise 0.06 L/s Zone T-stat Check 1 of 1 OK
Max zone temperature deviation 0.0 °K

Supply Fan Sizing Data


Actual max L/s 160 L/s Fan motor BHP 0.03 BHP
Standard L/s 160 L/s Fan motor kW 0.02 kW
Actual max L/(s-m²) 6.01 L/(s-m²) Fan static 75 Pa

Outdoor Ventilation Air Data


Design airflow L/s 0 L/s L/s/person 0.00 L/s/person
L/(s-m²) 0.00 L/(s-m²)

Hourly Analysis Program v4.90 Page 1 of 138


Zone Sizing Summary for 03-L2- FCU-101-R13
Project Name: DJIBOUTI-LEVEL 2-26-03-18- 04/02/2018
Prepared by: a 10:25AM

Air System Information


Air System Name 03-L2- FCU-101-R13 Number of zones 1
Equipment Class CW AHU Floor Area 26.6 m²
Air System Type SZCAV Location Dubai, United Arab Emirates

Sizing Calculation Information


Calculation Months Jan to Dec Zone L/s Sizing Sum of space airflow rates
Sizing Data Calculated Space L/s Sizing Individual peak space loads

Zone Sizing Data

Maximum Maximum Zone


Cooling Design Minimum Heating Floor
Sensible Airflow Airflow Time of Load Area Zone
Zone Name (kW) (L/s) (L/s) Peak Load (kW) (m²) L/(s-m²)
Zone 1 1.9 160 160 Sep 1800 0.2 26.6 6.01

Zone Terminal Sizing Data


No Zone Terminal Sizing Data required for this system.

Space Loads and Airflows

Cooling Time Air Heating Floor


Zone Name / Sensible of Flow Load Area Space
Space Name Mult. (kW) Load (L/s) (kW) (m²) L/(s-m²)
Zone 1
03-L2-ROOM-13 1 1.9 Sep 1800 160 0.2 26.6 6.01

Hourly Analysis Program v4.90 Page 2 of 138


Air System Sizing Summary for 03-L2- FCU-101-R14
Project Name: DJIBOUTI-LEVEL 2-26-03-18- 04/02/2018
Prepared by: a 10:25AM

Air System Information


Air System Name 03-L2- FCU-101-R14 Number of zones 1
Equipment Class CW AHU Floor Area 27.6 m²
Air System Type SZCAV Location Dubai, United Arab Emirates

Sizing Calculation Information


Calculation Months Jan to Dec Zone L/s Sizing Sum of space airflow rates
Sizing Data Calculated Space L/s Sizing Individual peak space loads

Central Cooling Coil Sizing Data


Total coil load 5.4 kW Load occurs at Jul 2200
Sensible coil load 5.0 kW OA DB / WB 42.3 / 28.6 °C
Coil L/s at Jul 2200 390 L/s Entering DB / WB 25.7 / 18.4 °C
Max block L/s 390 L/s Leaving DB / WB 15.0 / 14.3 °C
Sum of peak zone L/s 390 L/s Coil ADP 13.8 °C
Sensible heat ratio 0.929 Bypass Factor 0.100
m²/kW 5.1 Resulting RH 53 %
W/m² 196.7 Design supply temp. 14.0 °C
Water flow @ 8.9 °K rise 0.15 L/s Zone T-stat Check 1 of 1 OK
Max zone temperature deviation 0.0 °K

Supply Fan Sizing Data


Actual max L/s 390 L/s Fan motor BHP 0.07 BHP
Standard L/s 390 L/s Fan motor kW 0.05 kW
Actual max L/(s-m²) 14.12 L/(s-m²) Fan static 75 Pa

Outdoor Ventilation Air Data


Design airflow L/s 0 L/s L/s/person 0.00 L/s/person
L/(s-m²) 0.00 L/(s-m²)

Hourly Analysis Program v4.90 Page 3 of 138


Zone Sizing Summary for 03-L2- FCU-101-R14
Project Name: DJIBOUTI-LEVEL 2-26-03-18- 04/02/2018
Prepared by: a 10:25AM

Air System Information


Air System Name 03-L2- FCU-101-R14 Number of zones 1
Equipment Class CW AHU Floor Area 27.6 m²
Air System Type SZCAV Location Dubai, United Arab Emirates

Sizing Calculation Information


Calculation Months Jan to Dec Zone L/s Sizing Sum of space airflow rates
Sizing Data Calculated Space L/s Sizing Individual peak space loads

Zone Sizing Data

Maximum Maximum Zone


Cooling Design Minimum Heating Floor
Sensible Airflow Airflow Time of Load Area Zone
Zone Name (kW) (L/s) (L/s) Peak Load (kW) (m²) L/(s-m²)
Zone 1 4.7 390 390 Jul 2100 0.9 27.6 14.12

Zone Terminal Sizing Data


No Zone Terminal Sizing Data required for this system.

Space Loads and Airflows

Cooling Time Air Heating Floor


Zone Name / Sensible of Flow Load Area Space
Space Name Mult. (kW) Load (L/s) (kW) (m²) L/(s-m²)
Zone 1
03-L2-ROOM-14 1 4.7 Jul 2100 390 0.9 27.6 14.12

Hourly Analysis Program v4.90 Page 4 of 138


Air System Sizing Summary for 03-L2- FCU-101-R36
Project Name: DJIBOUTI-LEVEL 2-26-03-18- 04/02/2018
Prepared by: a 10:25AM

Air System Information


Air System Name 03-L2- FCU-101-R36 Number of zones 1
Equipment Class CW AHU Floor Area 27.0 m²
Air System Type SZCAV Location Dubai, United Arab Emirates

Sizing Calculation Information


Calculation Months Jan to Dec Zone L/s Sizing Sum of space airflow rates
Sizing Data Calculated Space L/s Sizing Individual peak space loads

Central Cooling Coil Sizing Data


Total coil load 2.3 kW Load occurs at Aug 1900
Sensible coil load 2.0 kW OA DB / WB 45.6 / 29.3 °C
Coil L/s at Aug 1900 156 L/s Entering DB / WB 25.4 / 18.8 °C
Max block L/s 156 L/s Leaving DB / WB 15.1 / 14.4 °C
Sum of peak zone L/s 156 L/s Coil ADP 13.9 °C
Sensible heat ratio 0.842 Bypass Factor 0.100
m²/kW 11.6 Resulting RH 56 %
W/m² 86.0 Design supply temp. 14.0 °C
Water flow @ 8.9 °K rise 0.06 L/s Zone T-stat Check 1 of 1 OK
Max zone temperature deviation 0.0 °K

Supply Fan Sizing Data


Actual max L/s 156 L/s Fan motor BHP 0.03 BHP
Standard L/s 156 L/s Fan motor kW 0.02 kW
Actual max L/(s-m²) 5.78 L/(s-m²) Fan static 75 Pa

Outdoor Ventilation Air Data


Design airflow L/s 0 L/s L/s/person 0.00 L/s/person
L/(s-m²) 0.00 L/(s-m²)

Hourly Analysis Program v4.90 Page 5 of 138


Zone Sizing Summary for 03-L2- FCU-101-R36
Project Name: DJIBOUTI-LEVEL 2-26-03-18- 04/02/2018
Prepared by: a 10:25AM

Air System Information


Air System Name 03-L2- FCU-101-R36 Number of zones 1
Equipment Class CW AHU Floor Area 27.0 m²
Air System Type SZCAV Location Dubai, United Arab Emirates

Sizing Calculation Information


Calculation Months Jan to Dec Zone L/s Sizing Sum of space airflow rates
Sizing Data Calculated Space L/s Sizing Individual peak space loads

Zone Sizing Data

Maximum Maximum Zone


Cooling Design Minimum Heating Floor
Sensible Airflow Airflow Time of Load Area Zone
Zone Name (kW) (L/s) (L/s) Peak Load (kW) (m²) L/(s-m²)
Zone 1 1.9 156 156 Aug 2000 0.2 27.0 5.78

Zone Terminal Sizing Data


No Zone Terminal Sizing Data required for this system.

Space Loads and Airflows

Cooling Time Air Heating Floor


Zone Name / Sensible of Flow Load Area Space
Space Name Mult. (kW) Load (L/s) (kW) (m²) L/(s-m²)
Zone 1
03-L2-ROOM-36 1 1.9 Aug 2000 156 0.2 27.0 5.78

Hourly Analysis Program v4.90 Page 6 of 138


Air System Sizing Summary for 03-L2- FCU-101-R37
Project Name: DJIBOUTI-LEVEL 2-26-03-18- 04/02/2018
Prepared by: a 10:25AM

Air System Information


Air System Name 03-L2- FCU-101-R37 Number of zones 1
Equipment Class CW AHU Floor Area 27.6 m²
Air System Type SZCAV Location Dubai, United Arab Emirates

Sizing Calculation Information


Calculation Months Jan to Dec Zone L/s Sizing Sum of space airflow rates
Sizing Data Calculated Space L/s Sizing Individual peak space loads

Central Cooling Coil Sizing Data


Total coil load 5.0 kW Load occurs at Jun 2200
Sensible coil load 4.7 kW OA DB / WB 41.7 / 28.6 °C
Coil L/s at Jun 2200 359 L/s Entering DB / WB 26.0 / 18.6 °C
Max block L/s 359 L/s Leaving DB / WB 15.2 / 14.5 °C
Sum of peak zone L/s 359 L/s Coil ADP 14.0 °C
Sensible heat ratio 0.923 Bypass Factor 0.100
m²/kW 5.5 Resulting RH 53 %
W/m² 182.8 Design supply temp. 14.0 °C
Water flow @ 8.9 °K rise 0.14 L/s Zone T-stat Check 0 of 1 OK
Max zone temperature deviation 0.0 °K

Supply Fan Sizing Data


Actual max L/s 359 L/s Fan motor BHP 0.06 BHP
Standard L/s 359 L/s Fan motor kW 0.05 kW
Actual max L/(s-m²) 13.00 L/(s-m²) Fan static 75 Pa

Outdoor Ventilation Air Data


Design airflow L/s 0 L/s L/s/person 0.00 L/s/person
L/(s-m²) 0.00 L/(s-m²)

Hourly Analysis Program v4.90 Page 7 of 138


Zone Sizing Summary for 03-L2- FCU-101-R37
Project Name: DJIBOUTI-LEVEL 2-26-03-18- 04/02/2018
Prepared by: a 10:25AM

Air System Information


Air System Name 03-L2- FCU-101-R37 Number of zones 1
Equipment Class CW AHU Floor Area 27.6 m²
Air System Type SZCAV Location Dubai, United Arab Emirates

Sizing Calculation Information


Calculation Months Jan to Dec Zone L/s Sizing Sum of space airflow rates
Sizing Data Calculated Space L/s Sizing Individual peak space loads

Zone Sizing Data

Maximum Maximum Zone


Cooling Design Minimum Heating Floor
Sensible Airflow Airflow Time of Load Area Zone
Zone Name (kW) (L/s) (L/s) Peak Load (kW) (m²) L/(s-m²)
Zone 1 4.3 359 359 Jun 2200 0.9 27.6 13.00

Zone Terminal Sizing Data


No Zone Terminal Sizing Data required for this system.

Space Loads and Airflows

Cooling Time Air Heating Floor


Zone Name / Sensible of Flow Load Area Space
Space Name Mult. (kW) Load (L/s) (kW) (m²) L/(s-m²)
Zone 1
03-L2-ROOM-37 1 4.3 Jun 2200 359 0.9 27.6 13.00

Hourly Analysis Program v4.90 Page 8 of 138


Air System Sizing Summary for 03-L2- FCU-101-R38
Project Name: DJIBOUTI-LEVEL 2-26-03-18- 04/02/2018
Prepared by: a 10:25AM

Air System Information


Air System Name 03-L2- FCU-101-R38 Number of zones 1
Equipment Class CW AHU Floor Area 32.1 m²
Air System Type SZCAV Location Dubai, United Arab Emirates

Sizing Calculation Information


Calculation Months Jan to Dec Zone L/s Sizing Sum of space airflow rates
Sizing Data Calculated Space L/s Sizing Individual peak space loads

Central Cooling Coil Sizing Data


Total coil load 6.0 kW Load occurs at Jul 2100
Sensible coil load 5.5 kW OA DB / WB 43.3 / 28.8 °C
Coil L/s at Jul 2100 420 L/s Entering DB / WB 25.6 / 18.3 °C
Max block L/s 420 L/s Leaving DB / WB 14.8 / 14.1 °C
Sum of peak zone L/s 420 L/s Coil ADP 13.6 °C
Sensible heat ratio 0.921 Bypass Factor 0.100
m²/kW 5.4 Resulting RH 53 %
W/m² 185.4 Design supply temp. 14.0 °C
Water flow @ 8.9 °K rise 0.16 L/s Zone T-stat Check 1 of 1 OK
Max zone temperature deviation 0.0 °K

Supply Fan Sizing Data


Actual max L/s 420 L/s Fan motor BHP 0.07 BHP
Standard L/s 420 L/s Fan motor kW 0.06 kW
Actual max L/(s-m²) 13.08 L/(s-m²) Fan static 75 Pa

Outdoor Ventilation Air Data


Design airflow L/s 0 L/s L/s/person 0.00 L/s/person
L/(s-m²) 0.00 L/(s-m²)

Hourly Analysis Program v4.90 Page 9 of 138


Zone Sizing Summary for 03-L2- FCU-101-R38
Project Name: DJIBOUTI-LEVEL 2-26-03-18- 04/02/2018
Prepared by: a 10:25AM

Air System Information


Air System Name 03-L2- FCU-101-R38 Number of zones 1
Equipment Class CW AHU Floor Area 32.1 m²
Air System Type SZCAV Location Dubai, United Arab Emirates

Sizing Calculation Information


Calculation Months Jan to Dec Zone L/s Sizing Sum of space airflow rates
Sizing Data Calculated Space L/s Sizing Individual peak space loads

Zone Sizing Data

Maximum Maximum Zone


Cooling Design Minimum Heating Floor
Sensible Airflow Airflow Time of Load Area Zone
Zone Name (kW) (L/s) (L/s) Peak Load (kW) (m²) L/(s-m²)
Zone 1 5.1 420 420 Jun 2200 1.0 32.1 13.08

Zone Terminal Sizing Data


No Zone Terminal Sizing Data required for this system.

Space Loads and Airflows

Cooling Time Air Heating Floor


Zone Name / Sensible of Flow Load Area Space
Space Name Mult. (kW) Load (L/s) (kW) (m²) L/(s-m²)
Zone 1
03-L2-ROOM-38 1 5.1 Jun 2200 420 1.0 32.1 13.08

Hourly Analysis Program v4.90 Page 10 of 138


Air System Sizing Summary for 03-L2- FCU-102-R03
Project Name: DJIBOUTI-LEVEL 2-26-03-18- 04/02/2018
Prepared by: a 10:25AM

Air System Information


Air System Name 03-L2- FCU-102-R03 Number of zones 1
Equipment Class CW AHU Floor Area 32.7 m²
Air System Type SZCAV Location Dubai, United Arab Emirates

Sizing Calculation Information


Calculation Months Jan to Dec Zone L/s Sizing Sum of space airflow rates
Sizing Data Calculated Space L/s Sizing Individual peak space loads

Central Cooling Coil Sizing Data


Total coil load 3.2 kW Load occurs at Aug 1700
Sensible coil load 2.7 kW OA DB / WB 47.9 / 29.8 °C
Coil L/s at Aug 1700 222 L/s Entering DB / WB 25.4 / 18.7 °C
Max block L/s 222 L/s Leaving DB / WB 15.2 / 14.6 °C
Sum of peak zone L/s 222 L/s Coil ADP 14.1 °C
Sensible heat ratio 0.858 Bypass Factor 0.100
m²/kW 10.3 Resulting RH 55 %
W/m² 97.0 Design supply temp. 14.0 °C
Water flow @ 8.9 °K rise 0.09 L/s Zone T-stat Check 1 of 1 OK
Max zone temperature deviation 0.0 °K

Supply Fan Sizing Data


Actual max L/s 222 L/s Fan motor BHP 0.04 BHP
Standard L/s 222 L/s Fan motor kW 0.03 kW
Actual max L/(s-m²) 6.78 L/(s-m²) Fan static 75 Pa

Outdoor Ventilation Air Data


Design airflow L/s 0 L/s L/s/person 0.00 L/s/person
L/(s-m²) 0.00 L/(s-m²)

Hourly Analysis Program v4.90 Page 11 of 138


Zone Sizing Summary for 03-L2- FCU-102-R03
Project Name: DJIBOUTI-LEVEL 2-26-03-18- 04/02/2018
Prepared by: a 10:25AM

Air System Information


Air System Name 03-L2- FCU-102-R03 Number of zones 1
Equipment Class CW AHU Floor Area 32.7 m²
Air System Type SZCAV Location Dubai, United Arab Emirates

Sizing Calculation Information


Calculation Months Jan to Dec Zone L/s Sizing Sum of space airflow rates
Sizing Data Calculated Space L/s Sizing Individual peak space loads

Zone Sizing Data

Maximum Maximum Zone


Cooling Design Minimum Heating Floor
Sensible Airflow Airflow Time of Load Area Zone
Zone Name (kW) (L/s) (L/s) Peak Load (kW) (m²) L/(s-m²)
Zone 1 2.7 222 222 Sep 1700 0.2 32.7 6.78

Zone Terminal Sizing Data


No Zone Terminal Sizing Data required for this system.

Space Loads and Airflows

Cooling Time Air Heating Floor


Zone Name / Sensible of Flow Load Area Space
Space Name Mult. (kW) Load (L/s) (kW) (m²) L/(s-m²)
Zone 1
03-L2-ROOM-03 1 2.7 Sep 1700 222 0.2 32.7 6.78

Hourly Analysis Program v4.90 Page 12 of 138


Air System Sizing Summary for 03-L2- FCU-102-R10
Project Name: DJIBOUTI-LEVEL 2-26-03-18- 04/02/2018
Prepared by: a 10:25AM

Air System Information


Air System Name 03-L2- FCU-102-R10 Number of zones 1
Equipment Class CW AHU Floor Area 32.2 m²
Air System Type SZCAV Location Dubai, United Arab Emirates

Sizing Calculation Information


Calculation Months Jan to Dec Zone L/s Sizing Sum of space airflow rates
Sizing Data Calculated Space L/s Sizing Individual peak space loads

Central Cooling Coil Sizing Data


Total coil load 3.6 kW Load occurs at Oct 1800
Sensible coil load 3.3 kW OA DB / WB 42.9 / 27.3 °C
Coil L/s at Oct 1800 268 L/s Entering DB / WB 25.4 / 18.5 °C
Max block L/s 268 L/s Leaving DB / WB 15.2 / 14.6 °C
Sum of peak zone L/s 268 L/s Coil ADP 14.1 °C
Sensible heat ratio 0.907 Bypass Factor 0.100
m²/kW 8.9 Resulting RH 54 %
W/m² 112.3 Design supply temp. 14.0 °C
Water flow @ 8.9 °K rise 0.10 L/s Zone T-stat Check 1 of 1 OK
Max zone temperature deviation 0.0 °K

Supply Fan Sizing Data


Actual max L/s 268 L/s Fan motor BHP 0.05 BHP
Standard L/s 268 L/s Fan motor kW 0.04 kW
Actual max L/(s-m²) 8.33 L/(s-m²) Fan static 75 Pa

Outdoor Ventilation Air Data


Design airflow L/s 0 L/s L/s/person 0.00 L/s/person
L/(s-m²) 0.00 L/(s-m²)

Hourly Analysis Program v4.90 Page 13 of 138


Zone Sizing Summary for 03-L2- FCU-102-R10
Project Name: DJIBOUTI-LEVEL 2-26-03-18- 04/02/2018
Prepared by: a 10:25AM

Air System Information


Air System Name 03-L2- FCU-102-R10 Number of zones 1
Equipment Class CW AHU Floor Area 32.2 m²
Air System Type SZCAV Location Dubai, United Arab Emirates

Sizing Calculation Information


Calculation Months Jan to Dec Zone L/s Sizing Sum of space airflow rates
Sizing Data Calculated Space L/s Sizing Individual peak space loads

Zone Sizing Data

Maximum Maximum Zone


Cooling Design Minimum Heating Floor
Sensible Airflow Airflow Time of Load Area Zone
Zone Name (kW) (L/s) (L/s) Peak Load (kW) (m²) L/(s-m²)
Zone 1 3.2 268 268 Oct 1700 0.3 32.2 8.33

Zone Terminal Sizing Data


No Zone Terminal Sizing Data required for this system.

Space Loads and Airflows

Cooling Time Air Heating Floor


Zone Name / Sensible of Flow Load Area Space
Space Name Mult. (kW) Load (L/s) (kW) (m²) L/(s-m²)
Zone 1
03-L2-ROOM-10 1 3.2 Oct 1700 268 0.3 32.2 8.33

Hourly Analysis Program v4.90 Page 14 of 138


Air System Sizing Summary for 03-L2- FCU-102-R11
Project Name: DJIBOUTI-LEVEL 2-26-03-18- 04/02/2018
Prepared by: a 10:25AM

Air System Information


Air System Name 03-L2- FCU-102-R11 Number of zones 1
Equipment Class CW AHU Floor Area 32.2 m²
Air System Type SZCAV Location Dubai, United Arab Emirates

Sizing Calculation Information


Calculation Months Jan to Dec Zone L/s Sizing Sum of space airflow rates
Sizing Data Calculated Space L/s Sizing Individual peak space loads

Central Cooling Coil Sizing Data


Total coil load 4.6 kW Load occurs at Aug 1700
Sensible coil load 4.2 kW OA DB / WB 47.9 / 29.8 °C
Coil L/s at Aug 1700 348 L/s Entering DB / WB 25.1 / 18.4 °C
Max block L/s 348 L/s Leaving DB / WB 15.2 / 14.6 °C
Sum of peak zone L/s 348 L/s Coil ADP 14.1 °C
Sensible heat ratio 0.909 Bypass Factor 0.100
m²/kW 7.0 Resulting RH 54 %
W/m² 142.3 Design supply temp. 14.0 °C
Water flow @ 8.9 °K rise 0.12 L/s Zone T-stat Check 1 of 1 OK
Max zone temperature deviation 0.0 °K

Supply Fan Sizing Data


Actual max L/s 348 L/s Fan motor BHP 0.06 BHP
Standard L/s 348 L/s Fan motor kW 0.05 kW
Actual max L/(s-m²) 10.81 L/(s-m²) Fan static 75 Pa

Outdoor Ventilation Air Data


Design airflow L/s 0 L/s L/s/person 0.00 L/s/person
L/(s-m²) 0.00 L/(s-m²)

Hourly Analysis Program v4.90 Page 15 of 138


Zone Sizing Summary for 03-L2- FCU-102-R11
Project Name: DJIBOUTI-LEVEL 2-26-03-18- 04/02/2018
Prepared by: a 10:25AM

Air System Information


Air System Name 03-L2- FCU-102-R11 Number of zones 1
Equipment Class CW AHU Floor Area 32.2 m²
Air System Type SZCAV Location Dubai, United Arab Emirates

Sizing Calculation Information


Calculation Months Jan to Dec Zone L/s Sizing Sum of space airflow rates
Sizing Data Calculated Space L/s Sizing Individual peak space loads

Zone Sizing Data

Maximum Maximum Zone


Cooling Design Minimum Heating Floor
Sensible Airflow Airflow Time of Load Area Zone
Zone Name (kW) (L/s) (L/s) Peak Load (kW) (m²) L/(s-m²)
Zone 1 4.2 348 348 Sep 1700 0.3 32.2 10.81

Zone Terminal Sizing Data


No Zone Terminal Sizing Data required for this system.

Space Loads and Airflows

Cooling Time Air Heating Floor


Zone Name / Sensible of Flow Load Area Space
Space Name Mult. (kW) Load (L/s) (kW) (m²) L/(s-m²)
Zone 1
03-L2-ROOM-11 1 4.2 Sep 1700 348 0.3 32.2 10.81

Hourly Analysis Program v4.90 Page 16 of 138


Air System Sizing Summary for 03-L2- FCU-102-R12
Project Name: DJIBOUTI-LEVEL 2-26-03-18- 04/02/2018
Prepared by: a 10:25AM

Air System Information


Air System Name 03-L2- FCU-102-R12 Number of zones 1
Equipment Class CW AHU Floor Area 32.3 m²
Air System Type SZCAV Location Dubai, United Arab Emirates

Sizing Calculation Information


Calculation Months Jan to Dec Zone L/s Sizing Sum of space airflow rates
Sizing Data Calculated Space L/s Sizing Individual peak space loads

Central Cooling Coil Sizing Data


Total coil load 2.6 kW Load occurs at Sep 1700
Sensible coil load 2.3 kW OA DB / WB 46.3 / 28.7 °C
Coil L/s at Sep 1700 178 L/s Entering DB / WB 25.4 / 18.6 °C
Max block L/s 178 L/s Leaving DB / WB 14.9 / 14.3 °C
Sum of peak zone L/s 178 L/s Coil ADP 13.7 °C
Sensible heat ratio 0.859 Bypass Factor 0.100
m²/kW 12.3 Resulting RH 55 %
W/m² 81.3 Design supply temp. 14.0 °C
Water flow @ 8.9 °K rise 0.07 L/s Zone T-stat Check 1 of 1 OK
Max zone temperature deviation 0.0 °K

Supply Fan Sizing Data


Actual max L/s 178 L/s Fan motor BHP 0.03 BHP
Standard L/s 177 L/s Fan motor kW 0.02 kW
Actual max L/(s-m²) 5.50 L/(s-m²) Fan static 75 Pa

Outdoor Ventilation Air Data


Design airflow L/s 0 L/s L/s/person 0.00 L/s/person
L/(s-m²) 0.00 L/(s-m²)

Hourly Analysis Program v4.90 Page 17 of 138


Zone Sizing Summary for 03-L2- FCU-102-R12
Project Name: DJIBOUTI-LEVEL 2-26-03-18- 04/02/2018
Prepared by: a 10:25AM

Air System Information


Air System Name 03-L2- FCU-102-R12 Number of zones 1
Equipment Class CW AHU Floor Area 32.3 m²
Air System Type SZCAV Location Dubai, United Arab Emirates

Sizing Calculation Information


Calculation Months Jan to Dec Zone L/s Sizing Sum of space airflow rates
Sizing Data Calculated Space L/s Sizing Individual peak space loads

Zone Sizing Data

Maximum Maximum Zone


Cooling Design Minimum Heating Floor
Sensible Airflow Airflow Time of Load Area Zone
Zone Name (kW) (L/s) (L/s) Peak Load (kW) (m²) L/(s-m²)
Zone 1 2.1 178 178 Sep 1800 0.2 32.3 5.50

Zone Terminal Sizing Data


No Zone Terminal Sizing Data required for this system.

Space Loads and Airflows

Cooling Time Air Heating Floor


Zone Name / Sensible of Flow Load Area Space
Space Name Mult. (kW) Load (L/s) (kW) (m²) L/(s-m²)
Zone 1
03-L2-ROOM-12 1 2.1 Sep 1800 178 0.2 32.3 5.50

Hourly Analysis Program v4.90 Page 18 of 138


Air System Sizing Summary for 03-L2- FCU-102-R15
Project Name: DJIBOUTI-LEVEL 2-26-03-18- 04/02/2018
Prepared by: a 10:25AM

Air System Information


Air System Name 03-L2- FCU-102-R15 Number of zones 1
Equipment Class CW AHU Floor Area 31.4 m²
Air System Type SZCAV Location Dubai, United Arab Emirates

Sizing Calculation Information


Calculation Months Jan to Dec Zone L/s Sizing Sum of space airflow rates
Sizing Data Calculated Space L/s Sizing Individual peak space loads

Central Cooling Coil Sizing Data


Total coil load 6.3 kW Load occurs at Jul 2200
Sensible coil load 5.8 kW OA DB / WB 42.3 / 28.6 °C
Coil L/s at Jul 2200 448 L/s Entering DB / WB 25.6 / 18.2 °C
Max block L/s 448 L/s Leaving DB / WB 14.8 / 14.1 °C
Sum of peak zone L/s 448 L/s Coil ADP 13.6 °C
Sensible heat ratio 0.932 Bypass Factor 0.100
m²/kW 5.0 Resulting RH 52 %
W/m² 199.5 Design supply temp. 14.0 °C
Water flow @ 8.9 °K rise 0.17 L/s Zone T-stat Check 1 of 1 OK
Max zone temperature deviation 0.0 °K

Supply Fan Sizing Data


Actual max L/s 448 L/s Fan motor BHP 0.08 BHP
Standard L/s 448 L/s Fan motor kW 0.06 kW
Actual max L/(s-m²) 14.27 L/(s-m²) Fan static 75 Pa

Outdoor Ventilation Air Data


Design airflow L/s 0 L/s L/s/person 0.00 L/s/person
L/(s-m²) 0.00 L/(s-m²)

Hourly Analysis Program v4.90 Page 19 of 138


Zone Sizing Summary for 03-L2- FCU-102-R15
Project Name: DJIBOUTI-LEVEL 2-26-03-18- 04/02/2018
Prepared by: a 10:25AM

Air System Information


Air System Name 03-L2- FCU-102-R15 Number of zones 1
Equipment Class CW AHU Floor Area 31.4 m²
Air System Type SZCAV Location Dubai, United Arab Emirates

Sizing Calculation Information


Calculation Months Jan to Dec Zone L/s Sizing Sum of space airflow rates
Sizing Data Calculated Space L/s Sizing Individual peak space loads

Zone Sizing Data

Maximum Maximum Zone


Cooling Design Minimum Heating Floor
Sensible Airflow Airflow Time of Load Area Zone
Zone Name (kW) (L/s) (L/s) Peak Load (kW) (m²) L/(s-m²)
Zone 1 5.4 448 448 Jul 2100 1.0 31.4 14.27

Zone Terminal Sizing Data


No Zone Terminal Sizing Data required for this system.

Space Loads and Airflows

Cooling Time Air Heating Floor


Zone Name / Sensible of Flow Load Area Space
Space Name Mult. (kW) Load (L/s) (kW) (m²) L/(s-m²)
Zone 1
03-L2-ROOM-15 1 5.4 Jul 2100 448 1.0 31.4 14.27

Hourly Analysis Program v4.90 Page 20 of 138


Air System Sizing Summary for 03-L2- FCU-102-R16
Project Name: DJIBOUTI-LEVEL 2-26-03-18- 04/02/2018
Prepared by: a 10:25AM

Air System Information


Air System Name 03-L2- FCU-102-R16 Number of zones 1
Equipment Class CW AHU Floor Area 31.6 m²
Air System Type SZCAV Location Dubai, United Arab Emirates

Sizing Calculation Information


Calculation Months Jan to Dec Zone L/s Sizing Sum of space airflow rates
Sizing Data Calculated Space L/s Sizing Individual peak space loads

Central Cooling Coil Sizing Data


Total coil load 3.4 kW Load occurs at Jul 1500
Sensible coil load 3.0 kW OA DB / WB 48.9 / 30.0 °C
Coil L/s at Jul 1500 241 L/s Entering DB / WB 25.2 / 18.5 °C
Max block L/s 241 L/s Leaving DB / WB 15.0 / 14.3 °C
Sum of peak zone L/s 241 L/s Coil ADP 13.8 °C
Sensible heat ratio 0.879 Bypass Factor 0.100
m²/kW 9.3 Resulting RH 54 %
W/m² 107.5 Design supply temp. 14.0 °C
Water flow @ 8.9 °K rise 0.09 L/s Zone T-stat Check 1 of 1 OK
Max zone temperature deviation 0.0 °K

Supply Fan Sizing Data


Actual max L/s 241 L/s Fan motor BHP 0.04 BHP
Standard L/s 241 L/s Fan motor kW 0.03 kW
Actual max L/(s-m²) 7.63 L/(s-m²) Fan static 75 Pa

Outdoor Ventilation Air Data


Design airflow L/s 0 L/s L/s/person 0.00 L/s/person
L/(s-m²) 0.00 L/(s-m²)

Hourly Analysis Program v4.90 Page 21 of 138


Zone Sizing Summary for 03-L2- FCU-102-R16
Project Name: DJIBOUTI-LEVEL 2-26-03-18- 04/02/2018
Prepared by: a 10:25AM

Air System Information


Air System Name 03-L2- FCU-102-R16 Number of zones 1
Equipment Class CW AHU Floor Area 31.6 m²
Air System Type SZCAV Location Dubai, United Arab Emirates

Sizing Calculation Information


Calculation Months Jan to Dec Zone L/s Sizing Sum of space airflow rates
Sizing Data Calculated Space L/s Sizing Individual peak space loads

Zone Sizing Data

Maximum Maximum Zone


Cooling Design Minimum Heating Floor
Sensible Airflow Airflow Time of Load Area Zone
Zone Name (kW) (L/s) (L/s) Peak Load (kW) (m²) L/(s-m²)
Zone 1 2.9 241 241 Jul 1600 0.2 31.6 7.63

Zone Terminal Sizing Data


No Zone Terminal Sizing Data required for this system.

Space Loads and Airflows

Cooling Time Air Heating Floor


Zone Name / Sensible of Flow Load Area Space
Space Name Mult. (kW) Load (L/s) (kW) (m²) L/(s-m²)
Zone 1
03-L2-ROOM-16 1 2.9 Jul 1600 241 0.2 31.6 7.63

Hourly Analysis Program v4.90 Page 22 of 138


Air System Sizing Summary for 03-L2- FCU-102-R17
Project Name: DJIBOUTI-LEVEL 2-26-03-18- 04/02/2018
Prepared by: a 10:25AM

Air System Information


Air System Name 03-L2- FCU-102-R17 Number of zones 1
Equipment Class CW AHU Floor Area 32.6 m²
Air System Type SZCAV Location Dubai, United Arab Emirates

Sizing Calculation Information


Calculation Months Jan to Dec Zone L/s Sizing Sum of space airflow rates
Sizing Data Calculated Space L/s Sizing Individual peak space loads

Central Cooling Coil Sizing Data


Total coil load 2.7 kW Load occurs at Jun 1600
Sensible coil load 2.3 kW OA DB / WB 48.0 / 29.9 °C
Coil L/s at Jun 1600 181 L/s Entering DB / WB 25.4 / 18.6 °C
Max block L/s 181 L/s Leaving DB / WB 14.8 / 14.2 °C
Sum of peak zone L/s 181 L/s Coil ADP 13.7 °C
Sensible heat ratio 0.845 Bypass Factor 0.100
m²/kW 11.9 Resulting RH 55 %
W/m² 83.7 Design supply temp. 14.0 °C
Water flow @ 8.9 °K rise 0.07 L/s Zone T-stat Check 1 of 1 OK
Max zone temperature deviation 0.0 °K

Supply Fan Sizing Data


Actual max L/s 181 L/s Fan motor BHP 0.03 BHP
Standard L/s 181 L/s Fan motor kW 0.03 kW
Actual max L/(s-m²) 5.54 L/(s-m²) Fan static 75 Pa

Outdoor Ventilation Air Data


Design airflow L/s 0 L/s L/s/person 0.00 L/s/person
L/(s-m²) 0.00 L/(s-m²)

Hourly Analysis Program v4.90 Page 23 of 138


Zone Sizing Summary for 03-L2- FCU-102-R17
Project Name: DJIBOUTI-LEVEL 2-26-03-18- 04/02/2018
Prepared by: a 10:25AM

Air System Information


Air System Name 03-L2- FCU-102-R17 Number of zones 1
Equipment Class CW AHU Floor Area 32.6 m²
Air System Type SZCAV Location Dubai, United Arab Emirates

Sizing Calculation Information


Calculation Months Jan to Dec Zone L/s Sizing Sum of space airflow rates
Sizing Data Calculated Space L/s Sizing Individual peak space loads

Zone Sizing Data

Maximum Maximum Zone


Cooling Design Minimum Heating Floor
Sensible Airflow Airflow Time of Load Area Zone
Zone Name (kW) (L/s) (L/s) Peak Load (kW) (m²) L/(s-m²)
Zone 1 2.2 181 181 Jul 1600 0.3 32.6 5.54

Zone Terminal Sizing Data


No Zone Terminal Sizing Data required for this system.

Space Loads and Airflows

Cooling Time Air Heating Floor


Zone Name / Sensible of Flow Load Area Space
Space Name Mult. (kW) Load (L/s) (kW) (m²) L/(s-m²)
Zone 1
03-L2-ROOM-17 1 2.2 Jul 1600 181 0.3 32.6 5.54

Hourly Analysis Program v4.90 Page 24 of 138


Air System Sizing Summary for 03-L2- FCU-102-R18
Project Name: DJIBOUTI-LEVEL 2-26-03-18- 04/02/2018
Prepared by: a 10:25AM

Air System Information


Air System Name 03-L2- FCU-102-R18 Number of zones 1
Equipment Class CW AHU Floor Area 32.6 m²
Air System Type SZCAV Location Dubai, United Arab Emirates

Sizing Calculation Information


Calculation Months Jan to Dec Zone L/s Sizing Sum of space airflow rates
Sizing Data Calculated Space L/s Sizing Individual peak space loads

Central Cooling Coil Sizing Data


Total coil load 2.9 kW Load occurs at Jul 1600
Sensible coil load 2.5 kW OA DB / WB 48.6 / 29.9 °C
Coil L/s at Jul 1600 193 L/s Entering DB / WB 25.3 / 18.5 °C
Max block L/s 193 L/s Leaving DB / WB 14.7 / 14.1 °C
Sum of peak zone L/s 193 L/s Coil ADP 13.6 °C
Sensible heat ratio 0.854 Bypass Factor 0.100
m²/kW 11.3 Resulting RH 54 %
W/m² 88.5 Design supply temp. 14.0 °C
Water flow @ 8.9 °K rise 0.08 L/s Zone T-stat Check 1 of 1 OK
Max zone temperature deviation 0.0 °K

Supply Fan Sizing Data


Actual max L/s 193 L/s Fan motor BHP 0.03 BHP
Standard L/s 193 L/s Fan motor kW 0.03 kW
Actual max L/(s-m²) 5.91 L/(s-m²) Fan static 75 Pa

Outdoor Ventilation Air Data


Design airflow L/s 0 L/s L/s/person 0.00 L/s/person
L/(s-m²) 0.00 L/(s-m²)

Hourly Analysis Program v4.90 Page 25 of 138


Zone Sizing Summary for 03-L2- FCU-102-R18
Project Name: DJIBOUTI-LEVEL 2-26-03-18- 04/02/2018
Prepared by: a 10:25AM

Air System Information


Air System Name 03-L2- FCU-102-R18 Number of zones 1
Equipment Class CW AHU Floor Area 32.6 m²
Air System Type SZCAV Location Dubai, United Arab Emirates

Sizing Calculation Information


Calculation Months Jan to Dec Zone L/s Sizing Sum of space airflow rates
Sizing Data Calculated Space L/s Sizing Individual peak space loads

Zone Sizing Data

Maximum Maximum Zone


Cooling Design Minimum Heating Floor
Sensible Airflow Airflow Time of Load Area Zone
Zone Name (kW) (L/s) (L/s) Peak Load (kW) (m²) L/(s-m²)
Zone 1 2.3 193 193 Jun 1600 0.3 32.6 5.91

Zone Terminal Sizing Data


No Zone Terminal Sizing Data required for this system.

Space Loads and Airflows

Cooling Time Air Heating Floor


Zone Name / Sensible of Flow Load Area Space
Space Name Mult. (kW) Load (L/s) (kW) (m²) L/(s-m²)
Zone 1
03-L2-ROOM-18 1 2.3 Jun 1600 193 0.3 32.6 5.91

Hourly Analysis Program v4.90 Page 26 of 138


Air System Sizing Summary for 03-L2- FCU-102-R19
Project Name: DJIBOUTI-LEVEL 2-26-03-18- 04/02/2018
Prepared by: a 10:25AM

Air System Information


Air System Name 03-L2- FCU-102-R19 Number of zones 1
Equipment Class CW AHU Floor Area 32.3 m²
Air System Type SZCAV Location Dubai, United Arab Emirates

Sizing Calculation Information


Calculation Months Jan to Dec Zone L/s Sizing Sum of space airflow rates
Sizing Data Calculated Space L/s Sizing Individual peak space loads

Central Cooling Coil Sizing Data


Total coil load 2.9 kW Load occurs at Jun 1700
Sensible coil load 2.4 kW OA DB / WB 47.4 / 29.8 °C
Coil L/s at Jun 1700 192 L/s Entering DB / WB 25.4 / 18.6 °C
Max block L/s 192 L/s Leaving DB / WB 14.9 / 14.2 °C
Sum of peak zone L/s 192 L/s Coil ADP 13.7 °C
Sensible heat ratio 0.852 Bypass Factor 0.100
m²/kW 11.3 Resulting RH 55 %
W/m² 88.3 Design supply temp. 14.0 °C
Water flow @ 8.9 °K rise 0.08 L/s Zone T-stat Check 1 of 1 OK
Max zone temperature deviation 0.0 °K

Supply Fan Sizing Data


Actual max L/s 192 L/s Fan motor BHP 0.03 BHP
Standard L/s 191 L/s Fan motor kW 0.03 kW
Actual max L/(s-m²) 5.93 L/(s-m²) Fan static 75 Pa

Outdoor Ventilation Air Data


Design airflow L/s 0 L/s L/s/person 0.00 L/s/person
L/(s-m²) 0.00 L/(s-m²)

Hourly Analysis Program v4.90 Page 27 of 138


Zone Sizing Summary for 03-L2- FCU-102-R19
Project Name: DJIBOUTI-LEVEL 2-26-03-18- 04/02/2018
Prepared by: a 10:25AM

Air System Information


Air System Name 03-L2- FCU-102-R19 Number of zones 1
Equipment Class CW AHU Floor Area 32.3 m²
Air System Type SZCAV Location Dubai, United Arab Emirates

Sizing Calculation Information


Calculation Months Jan to Dec Zone L/s Sizing Sum of space airflow rates
Sizing Data Calculated Space L/s Sizing Individual peak space loads

Zone Sizing Data

Maximum Maximum Zone


Cooling Design Minimum Heating Floor
Sensible Airflow Airflow Time of Load Area Zone
Zone Name (kW) (L/s) (L/s) Peak Load (kW) (m²) L/(s-m²)
Zone 1 2.3 192 192 Jun 1600 0.3 32.3 5.93

Zone Terminal Sizing Data


No Zone Terminal Sizing Data required for this system.

Space Loads and Airflows

Cooling Time Air Heating Floor


Zone Name / Sensible of Flow Load Area Space
Space Name Mult. (kW) Load (L/s) (kW) (m²) L/(s-m²)
Zone 1
03-L2-ROOM-19 1 2.3 Jun 1600 192 0.3 32.3 5.93

Hourly Analysis Program v4.90 Page 28 of 138


Air System Sizing Summary for 03-L2- FCU-102-R20
Project Name: DJIBOUTI-LEVEL 2-26-03-18- 04/02/2018
Prepared by: a 10:25AM

Air System Information


Air System Name 03-L2- FCU-102-R20 Number of zones 1
Equipment Class CW AHU Floor Area 32.6 m²
Air System Type SZCAV Location Dubai, United Arab Emirates

Sizing Calculation Information


Calculation Months Jan to Dec Zone L/s Sizing Sum of space airflow rates
Sizing Data Calculated Space L/s Sizing Individual peak space loads

Central Cooling Coil Sizing Data


Total coil load 2.9 kW Load occurs at Jul 1600
Sensible coil load 2.5 kW OA DB / WB 48.6 / 29.9 °C
Coil L/s at Jul 1600 193 L/s Entering DB / WB 25.3 / 18.5 °C
Max block L/s 193 L/s Leaving DB / WB 14.7 / 14.1 °C
Sum of peak zone L/s 193 L/s Coil ADP 13.6 °C
Sensible heat ratio 0.854 Bypass Factor 0.100
m²/kW 11.3 Resulting RH 54 %
W/m² 88.5 Design supply temp. 14.0 °C
Water flow @ 8.9 °K rise 0.08 L/s Zone T-stat Check 1 of 1 OK
Max zone temperature deviation 0.0 °K

Supply Fan Sizing Data


Actual max L/s 193 L/s Fan motor BHP 0.03 BHP
Standard L/s 193 L/s Fan motor kW 0.03 kW
Actual max L/(s-m²) 5.91 L/(s-m²) Fan static 75 Pa

Outdoor Ventilation Air Data


Design airflow L/s 0 L/s L/s/person 0.00 L/s/person
L/(s-m²) 0.00 L/(s-m²)

Hourly Analysis Program v4.90 Page 29 of 138


Zone Sizing Summary for 03-L2- FCU-102-R20
Project Name: DJIBOUTI-LEVEL 2-26-03-18- 04/02/2018
Prepared by: a 10:25AM

Air System Information


Air System Name 03-L2- FCU-102-R20 Number of zones 1
Equipment Class CW AHU Floor Area 32.6 m²
Air System Type SZCAV Location Dubai, United Arab Emirates

Sizing Calculation Information


Calculation Months Jan to Dec Zone L/s Sizing Sum of space airflow rates
Sizing Data Calculated Space L/s Sizing Individual peak space loads

Zone Sizing Data

Maximum Maximum Zone


Cooling Design Minimum Heating Floor
Sensible Airflow Airflow Time of Load Area Zone
Zone Name (kW) (L/s) (L/s) Peak Load (kW) (m²) L/(s-m²)
Zone 1 2.3 193 193 Jun 1600 0.3 32.6 5.91

Zone Terminal Sizing Data


No Zone Terminal Sizing Data required for this system.

Space Loads and Airflows

Cooling Time Air Heating Floor


Zone Name / Sensible of Flow Load Area Space
Space Name Mult. (kW) Load (L/s) (kW) (m²) L/(s-m²)
Zone 1
03-L2-ROOM-20 1 2.3 Jun 1600 193 0.3 32.6 5.91

Hourly Analysis Program v4.90 Page 30 of 138


Air System Sizing Summary for 03-L2- FCU-102-R21
Project Name: DJIBOUTI-LEVEL 2-26-03-18- 04/02/2018
Prepared by: a 10:25AM

Air System Information


Air System Name 03-L2- FCU-102-R21 Number of zones 1
Equipment Class CW AHU Floor Area 31.4 m²
Air System Type SZCAV Location Dubai, United Arab Emirates

Sizing Calculation Information


Calculation Months Jan to Dec Zone L/s Sizing Sum of space airflow rates
Sizing Data Calculated Space L/s Sizing Individual peak space loads

Central Cooling Coil Sizing Data


Total coil load 2.7 kW Load occurs at Jul 1600
Sensible coil load 2.3 kW OA DB / WB 48.6 / 29.9 °C
Coil L/s at Jul 1600 178 L/s Entering DB / WB 25.4 / 18.6 °C
Max block L/s 178 L/s Leaving DB / WB 14.9 / 14.3 °C
Sum of peak zone L/s 178 L/s Coil ADP 13.7 °C
Sensible heat ratio 0.848 Bypass Factor 0.100
m²/kW 11.8 Resulting RH 55 %
W/m² 85.0 Design supply temp. 14.0 °C
Water flow @ 8.9 °K rise 0.07 L/s Zone T-stat Check 1 of 1 OK
Max zone temperature deviation 0.0 °K

Supply Fan Sizing Data


Actual max L/s 178 L/s Fan motor BHP 0.03 BHP
Standard L/s 178 L/s Fan motor kW 0.02 kW
Actual max L/(s-m²) 5.67 L/(s-m²) Fan static 75 Pa

Outdoor Ventilation Air Data


Design airflow L/s 0 L/s L/s/person 0.00 L/s/person
L/(s-m²) 0.00 L/(s-m²)

Hourly Analysis Program v4.90 Page 31 of 138


Zone Sizing Summary for 03-L2- FCU-102-R21
Project Name: DJIBOUTI-LEVEL 2-26-03-18- 04/02/2018
Prepared by: a 10:25AM

Air System Information


Air System Name 03-L2- FCU-102-R21 Number of zones 1
Equipment Class CW AHU Floor Area 31.4 m²
Air System Type SZCAV Location Dubai, United Arab Emirates

Sizing Calculation Information


Calculation Months Jan to Dec Zone L/s Sizing Sum of space airflow rates
Sizing Data Calculated Space L/s Sizing Individual peak space loads

Zone Sizing Data

Maximum Maximum Zone


Cooling Design Minimum Heating Floor
Sensible Airflow Airflow Time of Load Area Zone
Zone Name (kW) (L/s) (L/s) Peak Load (kW) (m²) L/(s-m²)
Zone 1 2.1 178 178 Jul 1600 0.3 31.4 5.67

Zone Terminal Sizing Data


No Zone Terminal Sizing Data required for this system.

Space Loads and Airflows

Cooling Time Air Heating Floor


Zone Name / Sensible of Flow Load Area Space
Space Name Mult. (kW) Load (L/s) (kW) (m²) L/(s-m²)
Zone 1
03-L2-ROOM-21 1 2.1 Jul 1600 178 0.3 31.4 5.67

Hourly Analysis Program v4.90 Page 32 of 138


Air System Sizing Summary for 03-L2- FCU-102-R22
Project Name: DJIBOUTI-LEVEL 2-26-03-18- 04/02/2018
Prepared by: a 10:25AM

Air System Information


Air System Name 03-L2- FCU-102-R22 Number of zones 1
Equipment Class CW AHU Floor Area 32.5 m²
Air System Type SZCAV Location Dubai, United Arab Emirates

Sizing Calculation Information


Calculation Months Jan to Dec Zone L/s Sizing Sum of space airflow rates
Sizing Data Calculated Space L/s Sizing Individual peak space loads

Central Cooling Coil Sizing Data


Total coil load 2.4 kW Load occurs at Jun 1600
Sensible coil load 1.9 kW OA DB / WB 48.0 / 29.9 °C
Coil L/s at Jun 1600 151 L/s Entering DB / WB 25.5 / 18.8 °C
Max block L/s 151 L/s Leaving DB / WB 14.9 / 14.3 °C
Sum of peak zone L/s 151 L/s Coil ADP 13.7 °C
Sensible heat ratio 0.824 Bypass Factor 0.100
m²/kW 13.8 Resulting RH 56 %
W/m² 72.6 Design supply temp. 14.0 °C
Water flow @ 8.9 °K rise 0.06 L/s Zone T-stat Check 1 of 1 OK
Max zone temperature deviation 0.0 °K

Supply Fan Sizing Data


Actual max L/s 151 L/s Fan motor BHP 0.03 BHP
Standard L/s 151 L/s Fan motor kW 0.02 kW
Actual max L/(s-m²) 4.65 L/(s-m²) Fan static 75 Pa

Outdoor Ventilation Air Data


Design airflow L/s 0 L/s L/s/person 0.00 L/s/person
L/(s-m²) 0.00 L/(s-m²)

Hourly Analysis Program v4.90 Page 33 of 138


Zone Sizing Summary for 03-L2- FCU-102-R22
Project Name: DJIBOUTI-LEVEL 2-26-03-18- 04/02/2018
Prepared by: a 10:25AM

Air System Information


Air System Name 03-L2- FCU-102-R22 Number of zones 1
Equipment Class CW AHU Floor Area 32.5 m²
Air System Type SZCAV Location Dubai, United Arab Emirates

Sizing Calculation Information


Calculation Months Jan to Dec Zone L/s Sizing Sum of space airflow rates
Sizing Data Calculated Space L/s Sizing Individual peak space loads

Zone Sizing Data

Maximum Maximum Zone


Cooling Design Minimum Heating Floor
Sensible Airflow Airflow Time of Load Area Zone
Zone Name (kW) (L/s) (L/s) Peak Load (kW) (m²) L/(s-m²)
Zone 1 1.8 151 151 Jul 1600 0.2 32.5 4.65

Zone Terminal Sizing Data


No Zone Terminal Sizing Data required for this system.

Space Loads and Airflows

Cooling Time Air Heating Floor


Zone Name / Sensible of Flow Load Area Space
Space Name Mult. (kW) Load (L/s) (kW) (m²) L/(s-m²)
Zone 1
03-L2-ROOM-22 1 1.8 Jul 1600 151 0.2 32.5 4.65

Hourly Analysis Program v4.90 Page 34 of 138


Air System Sizing Summary for 03-L2- FCU-102-R23
Project Name: DJIBOUTI-LEVEL 2-26-03-18- 04/02/2018
Prepared by: a 10:25AM

Air System Information


Air System Name 03-L2- FCU-102-R23 Number of zones 1
Equipment Class CW AHU Floor Area 32.5 m²
Air System Type SZCAV Location Dubai, United Arab Emirates

Sizing Calculation Information


Calculation Months Jan to Dec Zone L/s Sizing Sum of space airflow rates
Sizing Data Calculated Space L/s Sizing Individual peak space loads

Central Cooling Coil Sizing Data


Total coil load 2.4 kW Load occurs at Jul 1800
Sensible coil load 2.0 kW OA DB / WB 46.9 / 29.6 °C
Coil L/s at Jul 1800 151 L/s Entering DB / WB 25.5 / 18.7 °C
Max block L/s 151 L/s Leaving DB / WB 14.7 / 14.1 °C
Sum of peak zone L/s 151 L/s Coil ADP 13.5 °C
Sensible heat ratio 0.826 Bypass Factor 0.100
m²/kW 13.7 Resulting RH 55 %
W/m² 72.9 Design supply temp. 14.0 °C
Water flow @ 8.9 °K rise 0.06 L/s Zone T-stat Check 1 of 1 OK
Max zone temperature deviation 0.0 °K

Supply Fan Sizing Data


Actual max L/s 151 L/s Fan motor BHP 0.03 BHP
Standard L/s 151 L/s Fan motor kW 0.02 kW
Actual max L/(s-m²) 4.64 L/(s-m²) Fan static 75 Pa

Outdoor Ventilation Air Data


Design airflow L/s 0 L/s L/s/person 0.00 L/s/person
L/(s-m²) 0.00 L/(s-m²)

Hourly Analysis Program v4.90 Page 35 of 138


Zone Sizing Summary for 03-L2- FCU-102-R23
Project Name: DJIBOUTI-LEVEL 2-26-03-18- 04/02/2018
Prepared by: a 10:25AM

Air System Information


Air System Name 03-L2- FCU-102-R23 Number of zones 1
Equipment Class CW AHU Floor Area 32.5 m²
Air System Type SZCAV Location Dubai, United Arab Emirates

Sizing Calculation Information


Calculation Months Jan to Dec Zone L/s Sizing Sum of space airflow rates
Sizing Data Calculated Space L/s Sizing Individual peak space loads

Zone Sizing Data

Maximum Maximum Zone


Cooling Design Minimum Heating Floor
Sensible Airflow Airflow Time of Load Area Zone
Zone Name (kW) (L/s) (L/s) Peak Load (kW) (m²) L/(s-m²)
Zone 1 1.8 151 151 Jul 1600 0.2 32.5 4.64

Zone Terminal Sizing Data


No Zone Terminal Sizing Data required for this system.

Space Loads and Airflows

Cooling Time Air Heating Floor


Zone Name / Sensible of Flow Load Area Space
Space Name Mult. (kW) Load (L/s) (kW) (m²) L/(s-m²)
Zone 1
03-L2-ROOM-23 1 1.8 Jul 1600 151 0.2 32.5 4.64

Hourly Analysis Program v4.90 Page 36 of 138


Air System Sizing Summary for 03-L2- FCU-102-R24
Project Name: DJIBOUTI-LEVEL 2-26-03-18- 04/02/2018
Prepared by: a 10:25AM

Air System Information


Air System Name 03-L2- FCU-102-R24 Number of zones 1
Equipment Class CW AHU Floor Area 32.5 m²
Air System Type SZCAV Location Dubai, United Arab Emirates

Sizing Calculation Information


Calculation Months Jan to Dec Zone L/s Sizing Sum of space airflow rates
Sizing Data Calculated Space L/s Sizing Individual peak space loads

Central Cooling Coil Sizing Data


Total coil load 2.4 kW Load occurs at Jul 1700
Sensible coil load 2.0 kW OA DB / WB 47.9 / 29.8 °C
Coil L/s at Jul 1700 151 L/s Entering DB / WB 25.5 / 18.8 °C
Max block L/s 151 L/s Leaving DB / WB 14.8 / 14.2 °C
Sum of peak zone L/s 151 L/s Coil ADP 13.7 °C
Sensible heat ratio 0.826 Bypass Factor 0.100
m²/kW 13.8 Resulting RH 56 %
W/m² 72.7 Design supply temp. 14.0 °C
Water flow @ 8.9 °K rise 0.06 L/s Zone T-stat Check 1 of 1 OK
Max zone temperature deviation 0.0 °K

Supply Fan Sizing Data


Actual max L/s 151 L/s Fan motor BHP 0.03 BHP
Standard L/s 151 L/s Fan motor kW 0.02 kW
Actual max L/(s-m²) 4.65 L/(s-m²) Fan static 75 Pa

Outdoor Ventilation Air Data


Design airflow L/s 0 L/s L/s/person 0.00 L/s/person
L/(s-m²) 0.00 L/(s-m²)

Hourly Analysis Program v4.90 Page 37 of 138


Zone Sizing Summary for 03-L2- FCU-102-R24
Project Name: DJIBOUTI-LEVEL 2-26-03-18- 04/02/2018
Prepared by: a 10:25AM

Air System Information


Air System Name 03-L2- FCU-102-R24 Number of zones 1
Equipment Class CW AHU Floor Area 32.5 m²
Air System Type SZCAV Location Dubai, United Arab Emirates

Sizing Calculation Information


Calculation Months Jan to Dec Zone L/s Sizing Sum of space airflow rates
Sizing Data Calculated Space L/s Sizing Individual peak space loads

Zone Sizing Data

Maximum Maximum Zone


Cooling Design Minimum Heating Floor
Sensible Airflow Airflow Time of Load Area Zone
Zone Name (kW) (L/s) (L/s) Peak Load (kW) (m²) L/(s-m²)
Zone 1 1.8 151 151 Jul 1600 0.2 32.5 4.65

Zone Terminal Sizing Data


No Zone Terminal Sizing Data required for this system.

Space Loads and Airflows

Cooling Time Air Heating Floor


Zone Name / Sensible of Flow Load Area Space
Space Name Mult. (kW) Load (L/s) (kW) (m²) L/(s-m²)
Zone 1
03-L2-ROOM-24 1 1.8 Jul 1600 151 0.2 32.5 4.65

Hourly Analysis Program v4.90 Page 38 of 138


Air System Sizing Summary for 03-L2- FCU-102-R25
Project Name: DJIBOUTI-LEVEL 2-26-03-18- 04/02/2018
Prepared by: a 10:25AM

Air System Information


Air System Name 03-L2- FCU-102-R25 Number of zones 1
Equipment Class CW AHU Floor Area 32.0 m²
Air System Type SZCAV Location Dubai, United Arab Emirates

Sizing Calculation Information


Calculation Months Jan to Dec Zone L/s Sizing Sum of space airflow rates
Sizing Data Calculated Space L/s Sizing Individual peak space loads

Central Cooling Coil Sizing Data


Total coil load 2.3 kW Load occurs at Jul 1700
Sensible coil load 1.9 kW OA DB / WB 47.9 / 29.8 °C
Coil L/s at Jul 1700 148 L/s Entering DB / WB 25.5 / 18.8 °C
Max block L/s 148 L/s Leaving DB / WB 14.8 / 14.2 °C
Sum of peak zone L/s 148 L/s Coil ADP 13.6 °C
Sensible heat ratio 0.825 Bypass Factor 0.100
m²/kW 13.7 Resulting RH 56 %
W/m² 72.7 Design supply temp. 14.0 °C
Water flow @ 8.9 °K rise 0.06 L/s Zone T-stat Check 1 of 1 OK
Max zone temperature deviation 0.0 °K

Supply Fan Sizing Data


Actual max L/s 148 L/s Fan motor BHP 0.03 BHP
Standard L/s 148 L/s Fan motor kW 0.02 kW
Actual max L/(s-m²) 4.64 L/(s-m²) Fan static 75 Pa

Outdoor Ventilation Air Data


Design airflow L/s 0 L/s L/s/person 0.00 L/s/person
L/(s-m²) 0.00 L/(s-m²)

Hourly Analysis Program v4.90 Page 39 of 138


Zone Sizing Summary for 03-L2- FCU-102-R25
Project Name: DJIBOUTI-LEVEL 2-26-03-18- 04/02/2018
Prepared by: a 10:25AM

Air System Information


Air System Name 03-L2- FCU-102-R25 Number of zones 1
Equipment Class CW AHU Floor Area 32.0 m²
Air System Type SZCAV Location Dubai, United Arab Emirates

Sizing Calculation Information


Calculation Months Jan to Dec Zone L/s Sizing Sum of space airflow rates
Sizing Data Calculated Space L/s Sizing Individual peak space loads

Zone Sizing Data

Maximum Maximum Zone


Cooling Design Minimum Heating Floor
Sensible Airflow Airflow Time of Load Area Zone
Zone Name (kW) (L/s) (L/s) Peak Load (kW) (m²) L/(s-m²)
Zone 1 1.8 148 148 Jul 1600 0.2 32.0 4.64

Zone Terminal Sizing Data


No Zone Terminal Sizing Data required for this system.

Space Loads and Airflows

Cooling Time Air Heating Floor


Zone Name / Sensible of Flow Load Area Space
Space Name Mult. (kW) Load (L/s) (kW) (m²) L/(s-m²)
Zone 1
03-L2-ROOM-25 1 1.8 Jul 1600 148 0.2 32.0 4.64

Hourly Analysis Program v4.90 Page 40 of 138


Air System Sizing Summary for 03-L2- FCU-102-R26
Project Name: DJIBOUTI-LEVEL 2-26-03-18- 04/02/2018
Prepared by: a 10:25AM

Air System Information


Air System Name 03-L2- FCU-102-R26 Number of zones 1
Equipment Class CW AHU Floor Area 32.3 m²
Air System Type SZCAV Location Dubai, United Arab Emirates

Sizing Calculation Information


Calculation Months Jan to Dec Zone L/s Sizing Sum of space airflow rates
Sizing Data Calculated Space L/s Sizing Individual peak space loads

Central Cooling Coil Sizing Data


Total coil load 3.0 kW Load occurs at Aug 1800
Sensible coil load 2.5 kW OA DB / WB 46.9 / 29.6 °C
Coil L/s at Aug 1800 199 L/s Entering DB / WB 25.4 / 18.7 °C
Max block L/s 199 L/s Leaving DB / WB 15.0 / 14.3 °C
Sum of peak zone L/s 199 L/s Coil ADP 13.8 °C
Sensible heat ratio 0.847 Bypass Factor 0.100
m²/kW 10.9 Resulting RH 55 %
W/m² 91.4 Design supply temp. 14.0 °C
Water flow @ 8.9 °K rise 0.08 L/s Zone T-stat Check 1 of 1 OK
Max zone temperature deviation 0.0 °K

Supply Fan Sizing Data


Actual max L/s 199 L/s Fan motor BHP 0.03 BHP
Standard L/s 199 L/s Fan motor kW 0.03 kW
Actual max L/(s-m²) 6.16 L/(s-m²) Fan static 75 Pa

Outdoor Ventilation Air Data


Design airflow L/s 0 L/s L/s/person 0.00 L/s/person
L/(s-m²) 0.00 L/(s-m²)

Hourly Analysis Program v4.90 Page 41 of 138


Zone Sizing Summary for 03-L2- FCU-102-R26
Project Name: DJIBOUTI-LEVEL 2-26-03-18- 04/02/2018
Prepared by: a 10:25AM

Air System Information


Air System Name 03-L2- FCU-102-R26 Number of zones 1
Equipment Class CW AHU Floor Area 32.3 m²
Air System Type SZCAV Location Dubai, United Arab Emirates

Sizing Calculation Information


Calculation Months Jan to Dec Zone L/s Sizing Sum of space airflow rates
Sizing Data Calculated Space L/s Sizing Individual peak space loads

Zone Sizing Data

Maximum Maximum Zone


Cooling Design Minimum Heating Floor
Sensible Airflow Airflow Time of Load Area Zone
Zone Name (kW) (L/s) (L/s) Peak Load (kW) (m²) L/(s-m²)
Zone 1 2.4 199 199 Aug 2000 0.2 32.3 6.16

Zone Terminal Sizing Data


No Zone Terminal Sizing Data required for this system.

Space Loads and Airflows

Cooling Time Air Heating Floor


Zone Name / Sensible of Flow Load Area Space
Space Name Mult. (kW) Load (L/s) (kW) (m²) L/(s-m²)
Zone 1
03-L2-ROOM-26 1 2.4 Aug 2000 199 0.2 32.3 6.16

Hourly Analysis Program v4.90 Page 42 of 138


Air System Sizing Summary for 03-L2- FCU-102-R27
Project Name: DJIBOUTI-LEVEL 2-26-03-18- 04/02/2018
Prepared by: a 10:25AM

Air System Information


Air System Name 03-L2- FCU-102-R27 Number of zones 1
Equipment Class CW AHU Floor Area 32.6 m²
Air System Type SZCAV Location Dubai, United Arab Emirates

Sizing Calculation Information


Calculation Months Jan to Dec Zone L/s Sizing Sum of space airflow rates
Sizing Data Calculated Space L/s Sizing Individual peak space loads

Central Cooling Coil Sizing Data


Total coil load 2.7 kW Load occurs at Aug 2000
Sensible coil load 2.2 kW OA DB / WB 44.3 / 29.0 °C
Coil L/s at Aug 2000 175 L/s Entering DB / WB 25.4 / 18.7 °C
Max block L/s 175 L/s Leaving DB / WB 14.9 / 14.2 °C
Sum of peak zone L/s 175 L/s Coil ADP 13.7 °C
Sensible heat ratio 0.832 Bypass Factor 0.100
m²/kW 12.1 Resulting RH 55 %
W/m² 82.4 Design supply temp. 14.0 °C
Water flow @ 8.9 °K rise 0.07 L/s Zone T-stat Check 1 of 1 OK
Max zone temperature deviation 0.0 °K

Supply Fan Sizing Data


Actual max L/s 175 L/s Fan motor BHP 0.03 BHP
Standard L/s 175 L/s Fan motor kW 0.02 kW
Actual max L/(s-m²) 5.37 L/(s-m²) Fan static 75 Pa

Outdoor Ventilation Air Data


Design airflow L/s 0 L/s L/s/person 0.00 L/s/person
L/(s-m²) 0.00 L/(s-m²)

Hourly Analysis Program v4.90 Page 43 of 138


Zone Sizing Summary for 03-L2- FCU-102-R27
Project Name: DJIBOUTI-LEVEL 2-26-03-18- 04/02/2018
Prepared by: a 10:25AM

Air System Information


Air System Name 03-L2- FCU-102-R27 Number of zones 1
Equipment Class CW AHU Floor Area 32.6 m²
Air System Type SZCAV Location Dubai, United Arab Emirates

Sizing Calculation Information


Calculation Months Jan to Dec Zone L/s Sizing Sum of space airflow rates
Sizing Data Calculated Space L/s Sizing Individual peak space loads

Zone Sizing Data

Maximum Maximum Zone


Cooling Design Minimum Heating Floor
Sensible Airflow Airflow Time of Load Area Zone
Zone Name (kW) (L/s) (L/s) Peak Load (kW) (m²) L/(s-m²)
Zone 1 2.1 175 175 Aug 2000 0.2 32.6 5.37

Zone Terminal Sizing Data


No Zone Terminal Sizing Data required for this system.

Space Loads and Airflows

Cooling Time Air Heating Floor


Zone Name / Sensible of Flow Load Area Space
Space Name Mult. (kW) Load (L/s) (kW) (m²) L/(s-m²)
Zone 1
03-L2-ROOM-27 1 2.1 Aug 2000 175 0.2 32.6 5.37

Hourly Analysis Program v4.90 Page 44 of 138


Air System Sizing Summary for 03-L2- FCU-102-R28
Project Name: DJIBOUTI-LEVEL 2-26-03-18- 04/02/2018
Prepared by: a 10:25AM

Air System Information


Air System Name 03-L2- FCU-102-R28 Number of zones 1
Equipment Class CW AHU Floor Area 32.6 m²
Air System Type SZCAV Location Dubai, United Arab Emirates

Sizing Calculation Information


Calculation Months Jan to Dec Zone L/s Sizing Sum of space airflow rates
Sizing Data Calculated Space L/s Sizing Individual peak space loads

Central Cooling Coil Sizing Data


Total coil load 2.7 kW Load occurs at Jul 2000
Sensible coil load 2.2 kW OA DB / WB 44.3 / 29.0 °C
Coil L/s at Jul 2000 174 L/s Entering DB / WB 25.4 / 18.7 °C
Max block L/s 174 L/s Leaving DB / WB 14.9 / 14.3 °C
Sum of peak zone L/s 174 L/s Coil ADP 13.7 °C
Sensible heat ratio 0.831 Bypass Factor 0.100
m²/kW 12.3 Resulting RH 56 %
W/m² 81.6 Design supply temp. 14.0 °C
Water flow @ 8.9 °K rise 0.07 L/s Zone T-stat Check 1 of 1 OK
Max zone temperature deviation 0.0 °K

Supply Fan Sizing Data


Actual max L/s 174 L/s Fan motor BHP 0.03 BHP
Standard L/s 174 L/s Fan motor kW 0.02 kW
Actual max L/(s-m²) 5.35 L/(s-m²) Fan static 75 Pa

Outdoor Ventilation Air Data


Design airflow L/s 0 L/s L/s/person 0.00 L/s/person
L/(s-m²) 0.00 L/(s-m²)

Hourly Analysis Program v4.90 Page 45 of 138


Zone Sizing Summary for 03-L2- FCU-102-R28
Project Name: DJIBOUTI-LEVEL 2-26-03-18- 04/02/2018
Prepared by: a 10:25AM

Air System Information


Air System Name 03-L2- FCU-102-R28 Number of zones 1
Equipment Class CW AHU Floor Area 32.6 m²
Air System Type SZCAV Location Dubai, United Arab Emirates

Sizing Calculation Information


Calculation Months Jan to Dec Zone L/s Sizing Sum of space airflow rates
Sizing Data Calculated Space L/s Sizing Individual peak space loads

Zone Sizing Data

Maximum Maximum Zone


Cooling Design Minimum Heating Floor
Sensible Airflow Airflow Time of Load Area Zone
Zone Name (kW) (L/s) (L/s) Peak Load (kW) (m²) L/(s-m²)
Zone 1 2.1 174 174 Aug 2000 0.2 32.6 5.35

Zone Terminal Sizing Data


No Zone Terminal Sizing Data required for this system.

Space Loads and Airflows

Cooling Time Air Heating Floor


Zone Name / Sensible of Flow Load Area Space
Space Name Mult. (kW) Load (L/s) (kW) (m²) L/(s-m²)
Zone 1
03-L2-ROOM-28 1 2.1 Aug 2000 174 0.2 32.6 5.35

Hourly Analysis Program v4.90 Page 46 of 138


Air System Sizing Summary for 03-L2- FCU-102-R29
Project Name: DJIBOUTI-LEVEL 2-26-03-18- 04/02/2018
Prepared by: a 10:25AM

Air System Information


Air System Name 03-L2- FCU-102-R29 Number of zones 1
Equipment Class CW AHU Floor Area 32.6 m²
Air System Type SZCAV Location Dubai, United Arab Emirates

Sizing Calculation Information


Calculation Months Jan to Dec Zone L/s Sizing Sum of space airflow rates
Sizing Data Calculated Space L/s Sizing Individual peak space loads

Central Cooling Coil Sizing Data


Total coil load 2.7 kW Load occurs at Aug 1900
Sensible coil load 2.3 kW OA DB / WB 45.6 / 29.3 °C
Coil L/s at Aug 1900 176 L/s Entering DB / WB 25.4 / 18.6 °C
Max block L/s 176 L/s Leaving DB / WB 14.7 / 14.1 °C
Sum of peak zone L/s 176 L/s Coil ADP 13.5 °C
Sensible heat ratio 0.833 Bypass Factor 0.100
m²/kW 12.0 Resulting RH 55 %
W/m² 83.3 Design supply temp. 14.0 °C
Water flow @ 8.9 °K rise 0.07 L/s Zone T-stat Check 1 of 1 OK
Max zone temperature deviation 0.0 °K

Supply Fan Sizing Data


Actual max L/s 176 L/s Fan motor BHP 0.03 BHP
Standard L/s 176 L/s Fan motor kW 0.02 kW
Actual max L/(s-m²) 5.39 L/(s-m²) Fan static 75 Pa

Outdoor Ventilation Air Data


Design airflow L/s 0 L/s L/s/person 0.00 L/s/person
L/(s-m²) 0.00 L/(s-m²)

Hourly Analysis Program v4.90 Page 47 of 138


Zone Sizing Summary for 03-L2- FCU-102-R29
Project Name: DJIBOUTI-LEVEL 2-26-03-18- 04/02/2018
Prepared by: a 10:25AM

Air System Information


Air System Name 03-L2- FCU-102-R29 Number of zones 1
Equipment Class CW AHU Floor Area 32.6 m²
Air System Type SZCAV Location Dubai, United Arab Emirates

Sizing Calculation Information


Calculation Months Jan to Dec Zone L/s Sizing Sum of space airflow rates
Sizing Data Calculated Space L/s Sizing Individual peak space loads

Zone Sizing Data

Maximum Maximum Zone


Cooling Design Minimum Heating Floor
Sensible Airflow Airflow Time of Load Area Zone
Zone Name (kW) (L/s) (L/s) Peak Load (kW) (m²) L/(s-m²)
Zone 1 2.1 176 176 Aug 2000 0.2 32.6 5.39

Zone Terminal Sizing Data


No Zone Terminal Sizing Data required for this system.

Space Loads and Airflows

Cooling Time Air Heating Floor


Zone Name / Sensible of Flow Load Area Space
Space Name Mult. (kW) Load (L/s) (kW) (m²) L/(s-m²)
Zone 1
03-L2-ROOM-29 1 2.1 Aug 2000 176 0.2 32.6 5.39

Hourly Analysis Program v4.90 Page 48 of 138


Air System Sizing Summary for 03-L2- FCU-102-R30
Project Name: DJIBOUTI-LEVEL 2-26-03-18- 04/02/2018
Prepared by: a 10:25AM

Air System Information


Air System Name 03-L2- FCU-102-R30 Number of zones 1
Equipment Class CW AHU Floor Area 32.6 m²
Air System Type SZCAV Location Dubai, United Arab Emirates

Sizing Calculation Information


Calculation Months Jan to Dec Zone L/s Sizing Sum of space airflow rates
Sizing Data Calculated Space L/s Sizing Individual peak space loads

Central Cooling Coil Sizing Data


Total coil load 3.4 kW Load occurs at Aug 2100
Sensible coil load 3.0 kW OA DB / WB 43.3 / 28.8 °C
Coil L/s at Aug 2100 239 L/s Entering DB / WB 25.3 / 18.6 °C
Max block L/s 239 L/s Leaving DB / WB 15.0 / 14.4 °C
Sum of peak zone L/s 239 L/s Coil ADP 13.9 °C
Sensible heat ratio 0.866 Bypass Factor 0.100
m²/kW 9.6 Resulting RH 55 %
W/m² 104.5 Design supply temp. 14.0 °C
Water flow @ 8.9 °K rise 0.09 L/s Zone T-stat Check 1 of 1 OK
Max zone temperature deviation 0.0 °K

Supply Fan Sizing Data


Actual max L/s 239 L/s Fan motor BHP 0.04 BHP
Standard L/s 239 L/s Fan motor kW 0.03 kW
Actual max L/(s-m²) 7.33 L/(s-m²) Fan static 75 Pa

Outdoor Ventilation Air Data


Design airflow L/s 0 L/s L/s/person 0.00 L/s/person
L/(s-m²) 0.00 L/(s-m²)

Hourly Analysis Program v4.90 Page 49 of 138


Zone Sizing Summary for 03-L2- FCU-102-R30
Project Name: DJIBOUTI-LEVEL 2-26-03-18- 04/02/2018
Prepared by: a 10:25AM

Air System Information


Air System Name 03-L2- FCU-102-R30 Number of zones 1
Equipment Class CW AHU Floor Area 32.6 m²
Air System Type SZCAV Location Dubai, United Arab Emirates

Sizing Calculation Information


Calculation Months Jan to Dec Zone L/s Sizing Sum of space airflow rates
Sizing Data Calculated Space L/s Sizing Individual peak space loads

Zone Sizing Data

Maximum Maximum Zone


Cooling Design Minimum Heating Floor
Sensible Airflow Airflow Time of Load Area Zone
Zone Name (kW) (L/s) (L/s) Peak Load (kW) (m²) L/(s-m²)
Zone 1 2.9 239 239 Sep 2000 0.3 32.6 7.33

Zone Terminal Sizing Data


No Zone Terminal Sizing Data required for this system.

Space Loads and Airflows

Cooling Time Air Heating Floor


Zone Name / Sensible of Flow Load Area Space
Space Name Mult. (kW) Load (L/s) (kW) (m²) L/(s-m²)
Zone 1
03-L2-ROOM-30 1 2.9 Sep 2000 239 0.3 32.6 7.33

Hourly Analysis Program v4.90 Page 50 of 138


Air System Sizing Summary for 03-L2- FCU-102-R31
Project Name: DJIBOUTI-LEVEL 2-26-03-18- 04/02/2018
Prepared by: a 10:25AM

Air System Information


Air System Name 03-L2- FCU-102-R31 Number of zones 1
Equipment Class CW AHU Floor Area 32.6 m²
Air System Type SZCAV Location Dubai, United Arab Emirates

Sizing Calculation Information


Calculation Months Jan to Dec Zone L/s Sizing Sum of space airflow rates
Sizing Data Calculated Space L/s Sizing Individual peak space loads

Central Cooling Coil Sizing Data


Total coil load 3.7 kW Load occurs at Aug 2000
Sensible coil load 3.3 kW OA DB / WB 44.3 / 29.0 °C
Coil L/s at Aug 2000 264 L/s Entering DB / WB 25.2 / 18.5 °C
Max block L/s 264 L/s Leaving DB / WB 15.0 / 14.4 °C
Sum of peak zone L/s 264 L/s Coil ADP 13.9 °C
Sensible heat ratio 0.877 Bypass Factor 0.100
m²/kW 8.8 Resulting RH 54 %
W/m² 113.9 Design supply temp. 14.0 °C
Water flow @ 8.9 °K rise 0.10 L/s Zone T-stat Check 1 of 1 OK
Max zone temperature deviation 0.0 °K

Supply Fan Sizing Data


Actual max L/s 264 L/s Fan motor BHP 0.05 BHP
Standard L/s 263 L/s Fan motor kW 0.04 kW
Actual max L/(s-m²) 8.09 L/(s-m²) Fan static 75 Pa

Outdoor Ventilation Air Data


Design airflow L/s 0 L/s L/s/person 0.00 L/s/person
L/(s-m²) 0.00 L/(s-m²)

Hourly Analysis Program v4.90 Page 51 of 138


Zone Sizing Summary for 03-L2- FCU-102-R31
Project Name: DJIBOUTI-LEVEL 2-26-03-18- 04/02/2018
Prepared by: a 10:25AM

Air System Information


Air System Name 03-L2- FCU-102-R31 Number of zones 1
Equipment Class CW AHU Floor Area 32.6 m²
Air System Type SZCAV Location Dubai, United Arab Emirates

Sizing Calculation Information


Calculation Months Jan to Dec Zone L/s Sizing Sum of space airflow rates
Sizing Data Calculated Space L/s Sizing Individual peak space loads

Zone Sizing Data

Maximum Maximum Zone


Cooling Design Minimum Heating Floor
Sensible Airflow Airflow Time of Load Area Zone
Zone Name (kW) (L/s) (L/s) Peak Load (kW) (m²) L/(s-m²)
Zone 1 3.2 264 264 Sep 2000 0.3 32.6 8.09

Zone Terminal Sizing Data


No Zone Terminal Sizing Data required for this system.

Space Loads and Airflows

Cooling Time Air Heating Floor


Zone Name / Sensible of Flow Load Area Space
Space Name Mult. (kW) Load (L/s) (kW) (m²) L/(s-m²)
Zone 1
03-L2-ROOM-31 1 3.2 Sep 2000 264 0.3 32.6 8.09

Hourly Analysis Program v4.90 Page 52 of 138


Air System Sizing Summary for 03-L2- FCU-102-R32
Project Name: DJIBOUTI-LEVEL 2-26-03-18- 04/02/2018
Prepared by: a 10:25AM

Air System Information


Air System Name 03-L2- FCU-102-R32 Number of zones 1
Equipment Class CW AHU Floor Area 32.6 m²
Air System Type SZCAV Location Dubai, United Arab Emirates

Sizing Calculation Information


Calculation Months Jan to Dec Zone L/s Sizing Sum of space airflow rates
Sizing Data Calculated Space L/s Sizing Individual peak space loads

Central Cooling Coil Sizing Data


Total coil load 3.6 kW Load occurs at Aug 2000
Sensible coil load 3.2 kW OA DB / WB 44.3 / 29.0 °C
Coil L/s at Aug 2000 257 L/s Entering DB / WB 25.2 / 18.5 °C
Max block L/s 257 L/s Leaving DB / WB 15.0 / 14.4 °C
Sum of peak zone L/s 257 L/s Coil ADP 13.9 °C
Sensible heat ratio 0.883 Bypass Factor 0.100
m²/kW 9.1 Resulting RH 54 %
W/m² 110.2 Design supply temp. 14.0 °C
Water flow @ 8.9 °K rise 0.10 L/s Zone T-stat Check 1 of 1 OK
Max zone temperature deviation 0.0 °K

Supply Fan Sizing Data


Actual max L/s 257 L/s Fan motor BHP 0.05 BHP
Standard L/s 257 L/s Fan motor kW 0.04 kW
Actual max L/(s-m²) 7.90 L/(s-m²) Fan static 75 Pa

Outdoor Ventilation Air Data


Design airflow L/s 0 L/s L/s/person 0.00 L/s/person
L/(s-m²) 0.00 L/(s-m²)

Hourly Analysis Program v4.90 Page 53 of 138


Zone Sizing Summary for 03-L2- FCU-102-R32
Project Name: DJIBOUTI-LEVEL 2-26-03-18- 04/02/2018
Prepared by: a 10:25AM

Air System Information


Air System Name 03-L2- FCU-102-R32 Number of zones 1
Equipment Class CW AHU Floor Area 32.6 m²
Air System Type SZCAV Location Dubai, United Arab Emirates

Sizing Calculation Information


Calculation Months Jan to Dec Zone L/s Sizing Sum of space airflow rates
Sizing Data Calculated Space L/s Sizing Individual peak space loads

Zone Sizing Data

Maximum Maximum Zone


Cooling Design Minimum Heating Floor
Sensible Airflow Airflow Time of Load Area Zone
Zone Name (kW) (L/s) (L/s) Peak Load (kW) (m²) L/(s-m²)
Zone 1 3.1 257 257 Sep 2000 0.3 32.6 7.90

Zone Terminal Sizing Data


No Zone Terminal Sizing Data required for this system.

Space Loads and Airflows

Cooling Time Air Heating Floor


Zone Name / Sensible of Flow Load Area Space
Space Name Mult. (kW) Load (L/s) (kW) (m²) L/(s-m²)
Zone 1
03-L2-ROOM-32 1 3.1 Sep 2000 257 0.3 32.6 7.90

Hourly Analysis Program v4.90 Page 54 of 138


Air System Sizing Summary for 03-L2- FCU-102-R33
Project Name: DJIBOUTI-LEVEL 2-26-03-18- 04/02/2018
Prepared by: a 10:25AM

Air System Information


Air System Name 03-L2- FCU-102-R33 Number of zones 1
Equipment Class CW AHU Floor Area 32.6 m²
Air System Type SZCAV Location Dubai, United Arab Emirates

Sizing Calculation Information


Calculation Months Jan to Dec Zone L/s Sizing Sum of space airflow rates
Sizing Data Calculated Space L/s Sizing Individual peak space loads

Central Cooling Coil Sizing Data


Total coil load 3.6 kW Load occurs at Aug 2100
Sensible coil load 3.1 kW OA DB / WB 43.3 / 28.8 °C
Coil L/s at Aug 2100 257 L/s Entering DB / WB 25.2 / 18.5 °C
Max block L/s 257 L/s Leaving DB / WB 15.1 / 14.5 °C
Sum of peak zone L/s 257 L/s Coil ADP 14.0 °C
Sensible heat ratio 0.883 Bypass Factor 0.100
m²/kW 9.1 Resulting RH 54 %
W/m² 109.4 Design supply temp. 14.0 °C
Water flow @ 8.9 °K rise 0.10 L/s Zone T-stat Check 1 of 1 OK
Max zone temperature deviation 0.0 °K

Supply Fan Sizing Data


Actual max L/s 257 L/s Fan motor BHP 0.05 BHP
Standard L/s 257 L/s Fan motor kW 0.04 kW
Actual max L/(s-m²) 7.90 L/(s-m²) Fan static 75 Pa

Outdoor Ventilation Air Data


Design airflow L/s 0 L/s L/s/person 0.00 L/s/person
L/(s-m²) 0.00 L/(s-m²)

Hourly Analysis Program v4.90 Page 55 of 138


Zone Sizing Summary for 03-L2- FCU-102-R33
Project Name: DJIBOUTI-LEVEL 2-26-03-18- 04/02/2018
Prepared by: a 10:25AM

Air System Information


Air System Name 03-L2- FCU-102-R33 Number of zones 1
Equipment Class CW AHU Floor Area 32.6 m²
Air System Type SZCAV Location Dubai, United Arab Emirates

Sizing Calculation Information


Calculation Months Jan to Dec Zone L/s Sizing Sum of space airflow rates
Sizing Data Calculated Space L/s Sizing Individual peak space loads

Zone Sizing Data

Maximum Maximum Zone


Cooling Design Minimum Heating Floor
Sensible Airflow Airflow Time of Load Area Zone
Zone Name (kW) (L/s) (L/s) Peak Load (kW) (m²) L/(s-m²)
Zone 1 3.1 257 257 Sep 2000 0.3 32.6 7.90

Zone Terminal Sizing Data


No Zone Terminal Sizing Data required for this system.

Space Loads and Airflows

Cooling Time Air Heating Floor


Zone Name / Sensible of Flow Load Area Space
Space Name Mult. (kW) Load (L/s) (kW) (m²) L/(s-m²)
Zone 1
03-L2-ROOM-33 1 3.1 Sep 2000 257 0.3 32.6 7.90

Hourly Analysis Program v4.90 Page 56 of 138


Air System Sizing Summary for 03-L2- FCU-102-R34
Project Name: DJIBOUTI-LEVEL 2-26-03-18- 04/02/2018
Prepared by: a 10:25AM

Air System Information


Air System Name 03-L2- FCU-102-R34 Number of zones 1
Equipment Class CW AHU Floor Area 32.6 m²
Air System Type SZCAV Location Dubai, United Arab Emirates

Sizing Calculation Information


Calculation Months Jan to Dec Zone L/s Sizing Sum of space airflow rates
Sizing Data Calculated Space L/s Sizing Individual peak space loads

Central Cooling Coil Sizing Data


Total coil load 3.3 kW Load occurs at Sep 2000
Sensible coil load 2.9 kW OA DB / WB 42.7 / 27.9 °C
Coil L/s at Sep 2000 233 L/s Entering DB / WB 25.3 / 18.4 °C
Max block L/s 233 L/s Leaving DB / WB 14.8 / 14.2 °C
Sum of peak zone L/s 233 L/s Coil ADP 13.7 °C
Sensible heat ratio 0.886 Bypass Factor 0.100
m²/kW 9.8 Resulting RH 53 %
W/m² 101.6 Design supply temp. 14.0 °C
Water flow @ 8.9 °K rise 0.09 L/s Zone T-stat Check 1 of 1 OK
Max zone temperature deviation 0.0 °K

Supply Fan Sizing Data


Actual max L/s 233 L/s Fan motor BHP 0.04 BHP
Standard L/s 233 L/s Fan motor kW 0.03 kW
Actual max L/(s-m²) 7.14 L/(s-m²) Fan static 75 Pa

Outdoor Ventilation Air Data


Design airflow L/s 0 L/s L/s/person 0.00 L/s/person
L/(s-m²) 0.00 L/(s-m²)

Hourly Analysis Program v4.90 Page 57 of 138


Zone Sizing Summary for 03-L2- FCU-102-R34
Project Name: DJIBOUTI-LEVEL 2-26-03-18- 04/02/2018
Prepared by: a 10:25AM

Air System Information


Air System Name 03-L2- FCU-102-R34 Number of zones 1
Equipment Class CW AHU Floor Area 32.6 m²
Air System Type SZCAV Location Dubai, United Arab Emirates

Sizing Calculation Information


Calculation Months Jan to Dec Zone L/s Sizing Sum of space airflow rates
Sizing Data Calculated Space L/s Sizing Individual peak space loads

Zone Sizing Data

Maximum Maximum Zone


Cooling Design Minimum Heating Floor
Sensible Airflow Airflow Time of Load Area Zone
Zone Name (kW) (L/s) (L/s) Peak Load (kW) (m²) L/(s-m²)
Zone 1 2.8 233 233 Sep 2000 0.3 32.6 7.14

Zone Terminal Sizing Data


No Zone Terminal Sizing Data required for this system.

Space Loads and Airflows

Cooling Time Air Heating Floor


Zone Name / Sensible of Flow Load Area Space
Space Name Mult. (kW) Load (L/s) (kW) (m²) L/(s-m²)
Zone 1
03-L2-ROOM-34 1 2.8 Sep 2000 233 0.3 32.6 7.14

Hourly Analysis Program v4.90 Page 58 of 138


Air System Sizing Summary for 03-L2- FCU-102-R35
Project Name: DJIBOUTI-LEVEL 2-26-03-18- 04/02/2018
Prepared by: a 10:25AM

Air System Information


Air System Name 03-L2- FCU-102-R35 Number of zones 1
Equipment Class CW AHU Floor Area 32.6 m²
Air System Type SZCAV Location Dubai, United Arab Emirates

Sizing Calculation Information


Calculation Months Jan to Dec Zone L/s Sizing Sum of space airflow rates
Sizing Data Calculated Space L/s Sizing Individual peak space loads

Central Cooling Coil Sizing Data


Total coil load 2.7 kW Load occurs at Aug 2000
Sensible coil load 2.3 kW OA DB / WB 44.3 / 29.0 °C
Coil L/s at Aug 2000 177 L/s Entering DB / WB 25.4 / 18.6 °C
Max block L/s 177 L/s Leaving DB / WB 14.9 / 14.2 °C
Sum of peak zone L/s 177 L/s Coil ADP 13.7 °C
Sensible heat ratio 0.845 Bypass Factor 0.100
m²/kW 12.2 Resulting RH 55 %
W/m² 82.1 Design supply temp. 14.0 °C
Water flow @ 8.9 °K rise 0.07 L/s Zone T-stat Check 1 of 1 OK
Max zone temperature deviation 0.0 °K

Supply Fan Sizing Data


Actual max L/s 177 L/s Fan motor BHP 0.03 BHP
Standard L/s 177 L/s Fan motor kW 0.02 kW
Actual max L/(s-m²) 5.43 L/(s-m²) Fan static 75 Pa

Outdoor Ventilation Air Data


Design airflow L/s 0 L/s L/s/person 0.00 L/s/person
L/(s-m²) 0.00 L/(s-m²)

Hourly Analysis Program v4.90 Page 59 of 138


Zone Sizing Summary for 03-L2- FCU-102-R35
Project Name: DJIBOUTI-LEVEL 2-26-03-18- 04/02/2018
Prepared by: a 10:25AM

Air System Information


Air System Name 03-L2- FCU-102-R35 Number of zones 1
Equipment Class CW AHU Floor Area 32.6 m²
Air System Type SZCAV Location Dubai, United Arab Emirates

Sizing Calculation Information


Calculation Months Jan to Dec Zone L/s Sizing Sum of space airflow rates
Sizing Data Calculated Space L/s Sizing Individual peak space loads

Zone Sizing Data

Maximum Maximum Zone


Cooling Design Minimum Heating Floor
Sensible Airflow Airflow Time of Load Area Zone
Zone Name (kW) (L/s) (L/s) Peak Load (kW) (m²) L/(s-m²)
Zone 1 2.1 177 177 Aug 2000 0.2 32.6 5.43

Zone Terminal Sizing Data


No Zone Terminal Sizing Data required for this system.

Space Loads and Airflows

Cooling Time Air Heating Floor


Zone Name / Sensible of Flow Load Area Space
Space Name Mult. (kW) Load (L/s) (kW) (m²) L/(s-m²)
Zone 1
03-L2-ROOM-35 1 2.1 Aug 2000 177 0.2 32.6 5.43

Hourly Analysis Program v4.90 Page 60 of 138


Air System Sizing Summary for 03-L2- FCU-102-R39
Project Name: DJIBOUTI-LEVEL 2-26-03-18- 04/02/2018
Prepared by: a 10:25AM

Air System Information


Air System Name 03-L2- FCU-102-R39 Number of zones 1
Equipment Class CW AHU Floor Area 32.0 m²
Air System Type SZCAV Location Dubai, United Arab Emirates

Sizing Calculation Information


Calculation Months Jan to Dec Zone L/s Sizing Sum of space airflow rates
Sizing Data Calculated Space L/s Sizing Individual peak space loads

Central Cooling Coil Sizing Data


Total coil load 3.6 kW Load occurs at Jun 1600
Sensible coil load 3.2 kW OA DB / WB 48.0 / 29.9 °C
Coil L/s at Jun 1600 258 L/s Entering DB / WB 25.2 / 18.5 °C
Max block L/s 258 L/s Leaving DB / WB 15.0 / 14.4 °C
Sum of peak zone L/s 258 L/s Coil ADP 13.9 °C
Sensible heat ratio 0.874 Bypass Factor 0.100
m²/kW 8.8 Resulting RH 54 %
W/m² 114.0 Design supply temp. 14.0 °C
Water flow @ 8.9 °K rise 0.10 L/s Zone T-stat Check 1 of 1 OK
Max zone temperature deviation 0.0 °K

Supply Fan Sizing Data


Actual max L/s 258 L/s Fan motor BHP 0.05 BHP
Standard L/s 258 L/s Fan motor kW 0.04 kW
Actual max L/(s-m²) 8.06 L/(s-m²) Fan static 75 Pa

Outdoor Ventilation Air Data


Design airflow L/s 0 L/s L/s/person 0.00 L/s/person
L/(s-m²) 0.00 L/(s-m²)

Hourly Analysis Program v4.90 Page 61 of 138


Zone Sizing Summary for 03-L2- FCU-102-R39
Project Name: DJIBOUTI-LEVEL 2-26-03-18- 04/02/2018
Prepared by: a 10:25AM

Air System Information


Air System Name 03-L2- FCU-102-R39 Number of zones 1
Equipment Class CW AHU Floor Area 32.0 m²
Air System Type SZCAV Location Dubai, United Arab Emirates

Sizing Calculation Information


Calculation Months Jan to Dec Zone L/s Sizing Sum of space airflow rates
Sizing Data Calculated Space L/s Sizing Individual peak space loads

Zone Sizing Data

Maximum Maximum Zone


Cooling Design Minimum Heating Floor
Sensible Airflow Airflow Time of Load Area Zone
Zone Name (kW) (L/s) (L/s) Peak Load (kW) (m²) L/(s-m²)
Zone 1 3.1 258 258 Jul 1600 0.2 32.0 8.06

Zone Terminal Sizing Data


No Zone Terminal Sizing Data required for this system.

Space Loads and Airflows

Cooling Time Air Heating Floor


Zone Name / Sensible of Flow Load Area Space
Space Name Mult. (kW) Load (L/s) (kW) (m²) L/(s-m²)
Zone 1
03-L2-ROOM-39 1 3.1 Jul 1600 258 0.2 32.0 8.06

Hourly Analysis Program v4.90 Page 62 of 138


Air System Sizing Summary for 03-L2- FCU-102-R4
Project Name: DJIBOUTI-LEVEL 2-26-03-18- 04/02/2018
Prepared by: a 10:25AM

Air System Information


Air System Name 03-L2- FCU-102-R4 Number of zones 1
Equipment Class CW AHU Floor Area 32.6 m²
Air System Type SZCAV Location Dubai, United Arab Emirates

Sizing Calculation Information


Calculation Months Jan to Dec Zone L/s Sizing Sum of space airflow rates
Sizing Data Calculated Space L/s Sizing Individual peak space loads

Central Cooling Coil Sizing Data


Total coil load 2.7 kW Load occurs at Aug 1800
Sensible coil load 2.2 kW OA DB / WB 46.9 / 29.6 °C
Coil L/s at Aug 1800 178 L/s Entering DB / WB 25.4 / 18.8 °C
Max block L/s 178 L/s Leaving DB / WB 15.0 / 14.4 °C
Sum of peak zone L/s 178 L/s Coil ADP 13.9 °C
Sensible heat ratio 0.833 Bypass Factor 0.100
m²/kW 12.1 Resulting RH 56 %
W/m² 82.4 Design supply temp. 14.0 °C
Water flow @ 8.9 °K rise 0.07 L/s Zone T-stat Check 1 of 1 OK
Max zone temperature deviation 0.0 °K

Supply Fan Sizing Data


Actual max L/s 178 L/s Fan motor BHP 0.03 BHP
Standard L/s 178 L/s Fan motor kW 0.02 kW
Actual max L/(s-m²) 5.47 L/(s-m²) Fan static 75 Pa

Outdoor Ventilation Air Data


Design airflow L/s 0 L/s L/s/person 0.00 L/s/person
L/(s-m²) 0.00 L/(s-m²)

Hourly Analysis Program v4.90 Page 63 of 138


Zone Sizing Summary for 03-L2- FCU-102-R4
Project Name: DJIBOUTI-LEVEL 2-26-03-18- 04/02/2018
Prepared by: a 10:25AM

Air System Information


Air System Name 03-L2- FCU-102-R4 Number of zones 1
Equipment Class CW AHU Floor Area 32.6 m²
Air System Type SZCAV Location Dubai, United Arab Emirates

Sizing Calculation Information


Calculation Months Jan to Dec Zone L/s Sizing Sum of space airflow rates
Sizing Data Calculated Space L/s Sizing Individual peak space loads

Zone Sizing Data

Maximum Maximum Zone


Cooling Design Minimum Heating Floor
Sensible Airflow Airflow Time of Load Area Zone
Zone Name (kW) (L/s) (L/s) Peak Load (kW) (m²) L/(s-m²)
Zone 1 2.2 178 178 Sep 1800 0.2 32.6 5.47

Zone Terminal Sizing Data


No Zone Terminal Sizing Data required for this system.

Space Loads and Airflows

Cooling Time Air Heating Floor


Zone Name / Sensible of Flow Load Area Space
Space Name Mult. (kW) Load (L/s) (kW) (m²) L/(s-m²)
Zone 1
03-L2-ROOM-04 1 2.2 Sep 1800 178 0.2 32.6 5.47

Hourly Analysis Program v4.90 Page 64 of 138


Air System Sizing Summary for 03-L2- FCU-102-R40
Project Name: DJIBOUTI-LEVEL 2-26-03-18- 04/02/2018
Prepared by: a 10:25AM

Air System Information


Air System Name 03-L2- FCU-102-R40 Number of zones 1
Equipment Class CW AHU Floor Area 32.6 m²
Air System Type SZCAV Location Dubai, United Arab Emirates

Sizing Calculation Information


Calculation Months Jan to Dec Zone L/s Sizing Sum of space airflow rates
Sizing Data Calculated Space L/s Sizing Individual peak space loads

Central Cooling Coil Sizing Data


Total coil load 3.0 kW Load occurs at Jun 1300
Sensible coil load 2.6 kW OA DB / WB 47.3 / 29.8 °C
Coil L/s at Jun 1300 209 L/s Entering DB / WB 25.3 / 18.6 °C
Max block L/s 209 L/s Leaving DB / WB 14.9 / 14.3 °C
Sum of peak zone L/s 209 L/s Coil ADP 13.8 °C
Sensible heat ratio 0.861 Bypass Factor 0.100
m²/kW 10.7 Resulting RH 55 %
W/m² 93.4 Design supply temp. 14.0 °C
Water flow @ 8.9 °K rise 0.08 L/s Zone T-stat Check 1 of 1 OK
Max zone temperature deviation 0.0 °K

Supply Fan Sizing Data


Actual max L/s 209 L/s Fan motor BHP 0.04 BHP
Standard L/s 209 L/s Fan motor kW 0.03 kW
Actual max L/(s-m²) 6.41 L/(s-m²) Fan static 75 Pa

Outdoor Ventilation Air Data


Design airflow L/s 0 L/s L/s/person 0.00 L/s/person
L/(s-m²) 0.00 L/(s-m²)

Hourly Analysis Program v4.90 Page 65 of 138


Zone Sizing Summary for 03-L2- FCU-102-R40
Project Name: DJIBOUTI-LEVEL 2-26-03-18- 04/02/2018
Prepared by: a 10:25AM

Air System Information


Air System Name 03-L2- FCU-102-R40 Number of zones 1
Equipment Class CW AHU Floor Area 32.6 m²
Air System Type SZCAV Location Dubai, United Arab Emirates

Sizing Calculation Information


Calculation Months Jan to Dec Zone L/s Sizing Sum of space airflow rates
Sizing Data Calculated Space L/s Sizing Individual peak space loads

Zone Sizing Data

Maximum Maximum Zone


Cooling Design Minimum Heating Floor
Sensible Airflow Airflow Time of Load Area Zone
Zone Name (kW) (L/s) (L/s) Peak Load (kW) (m²) L/(s-m²)
Zone 1 2.5 209 209 Jun 1300 0.3 32.6 6.41

Zone Terminal Sizing Data


No Zone Terminal Sizing Data required for this system.

Space Loads and Airflows

Cooling Time Air Heating Floor


Zone Name / Sensible of Flow Load Area Space
Space Name Mult. (kW) Load (L/s) (kW) (m²) L/(s-m²)
Zone 1
03-L2-ROOM-40 1 2.5 Jun 1300 209 0.3 32.6 6.41

Hourly Analysis Program v4.90 Page 66 of 138


Air System Sizing Summary for 03-L2- FCU-102-R41
Project Name: DJIBOUTI-LEVEL 2-26-03-18- 04/02/2018
Prepared by: a 10:25AM

Air System Information


Air System Name 03-L2- FCU-102-R41 Number of zones 1
Equipment Class CW AHU Floor Area 32.6 m²
Air System Type SZCAV Location Dubai, United Arab Emirates

Sizing Calculation Information


Calculation Months Jan to Dec Zone L/s Sizing Sum of space airflow rates
Sizing Data Calculated Space L/s Sizing Individual peak space loads

Central Cooling Coil Sizing Data


Total coil load 3.2 kW Load occurs at Jun 1400
Sensible coil load 2.8 kW OA DB / WB 48.0 / 29.9 °C
Coil L/s at Jun 1400 227 L/s Entering DB / WB 25.3 / 18.6 °C
Max block L/s 227 L/s Leaving DB / WB 15.1 / 14.4 °C
Sum of peak zone L/s 227 L/s Coil ADP 13.9 °C
Sensible heat ratio 0.869 Bypass Factor 0.100
m²/kW 10.1 Resulting RH 55 %
W/m² 99.2 Design supply temp. 14.0 °C
Water flow @ 8.9 °K rise 0.09 L/s Zone T-stat Check 1 of 1 OK
Max zone temperature deviation 0.0 °K

Supply Fan Sizing Data


Actual max L/s 227 L/s Fan motor BHP 0.04 BHP
Standard L/s 227 L/s Fan motor kW 0.03 kW
Actual max L/(s-m²) 6.98 L/(s-m²) Fan static 75 Pa

Outdoor Ventilation Air Data


Design airflow L/s 0 L/s L/s/person 0.00 L/s/person
L/(s-m²) 0.00 L/(s-m²)

Hourly Analysis Program v4.90 Page 67 of 138


Zone Sizing Summary for 03-L2- FCU-102-R41
Project Name: DJIBOUTI-LEVEL 2-26-03-18- 04/02/2018
Prepared by: a 10:25AM

Air System Information


Air System Name 03-L2- FCU-102-R41 Number of zones 1
Equipment Class CW AHU Floor Area 32.6 m²
Air System Type SZCAV Location Dubai, United Arab Emirates

Sizing Calculation Information


Calculation Months Jan to Dec Zone L/s Sizing Sum of space airflow rates
Sizing Data Calculated Space L/s Sizing Individual peak space loads

Zone Sizing Data

Maximum Maximum Zone


Cooling Design Minimum Heating Floor
Sensible Airflow Airflow Time of Load Area Zone
Zone Name (kW) (L/s) (L/s) Peak Load (kW) (m²) L/(s-m²)
Zone 1 2.7 227 227 Jun 1300 0.3 32.6 6.98

Zone Terminal Sizing Data


No Zone Terminal Sizing Data required for this system.

Space Loads and Airflows

Cooling Time Air Heating Floor


Zone Name / Sensible of Flow Load Area Space
Space Name Mult. (kW) Load (L/s) (kW) (m²) L/(s-m²)
Zone 1
03-L2-ROOM-41 1 2.7 Jun 1300 227 0.3 32.6 6.98

Hourly Analysis Program v4.90 Page 68 of 138


Air System Sizing Summary for 03-L2- FCU-102-R42
Project Name: DJIBOUTI-LEVEL 2-26-03-18- 04/02/2018
Prepared by: a 10:25AM

Air System Information


Air System Name 03-L2- FCU-102-R42 Number of zones 1
Equipment Class CW AHU Floor Area 32.6 m²
Air System Type SZCAV Location Dubai, United Arab Emirates

Sizing Calculation Information


Calculation Months Jan to Dec Zone L/s Sizing Sum of space airflow rates
Sizing Data Calculated Space L/s Sizing Individual peak space loads

Central Cooling Coil Sizing Data


Total coil load 3.2 kW Load occurs at Jun 1400
Sensible coil load 2.8 kW OA DB / WB 48.0 / 29.9 °C
Coil L/s at Jun 1400 227 L/s Entering DB / WB 25.3 / 18.6 °C
Max block L/s 227 L/s Leaving DB / WB 15.1 / 14.4 °C
Sum of peak zone L/s 227 L/s Coil ADP 13.9 °C
Sensible heat ratio 0.869 Bypass Factor 0.100
m²/kW 10.1 Resulting RH 55 %
W/m² 99.2 Design supply temp. 14.0 °C
Water flow @ 8.9 °K rise 0.09 L/s Zone T-stat Check 1 of 1 OK
Max zone temperature deviation 0.0 °K

Supply Fan Sizing Data


Actual max L/s 227 L/s Fan motor BHP 0.04 BHP
Standard L/s 227 L/s Fan motor kW 0.03 kW
Actual max L/(s-m²) 6.98 L/(s-m²) Fan static 75 Pa

Outdoor Ventilation Air Data


Design airflow L/s 0 L/s L/s/person 0.00 L/s/person
L/(s-m²) 0.00 L/(s-m²)

Hourly Analysis Program v4.90 Page 69 of 138


Zone Sizing Summary for 03-L2- FCU-102-R42
Project Name: DJIBOUTI-LEVEL 2-26-03-18- 04/02/2018
Prepared by: a 10:25AM

Air System Information


Air System Name 03-L2- FCU-102-R42 Number of zones 1
Equipment Class CW AHU Floor Area 32.6 m²
Air System Type SZCAV Location Dubai, United Arab Emirates

Sizing Calculation Information


Calculation Months Jan to Dec Zone L/s Sizing Sum of space airflow rates
Sizing Data Calculated Space L/s Sizing Individual peak space loads

Zone Sizing Data

Maximum Maximum Zone


Cooling Design Minimum Heating Floor
Sensible Airflow Airflow Time of Load Area Zone
Zone Name (kW) (L/s) (L/s) Peak Load (kW) (m²) L/(s-m²)
Zone 1 2.7 227 227 Jun 1300 0.3 32.6 6.98

Zone Terminal Sizing Data


No Zone Terminal Sizing Data required for this system.

Space Loads and Airflows

Cooling Time Air Heating Floor


Zone Name / Sensible of Flow Load Area Space
Space Name Mult. (kW) Load (L/s) (kW) (m²) L/(s-m²)
Zone 1
03-L2-ROOM-42 1 2.7 Jun 1300 227 0.3 32.6 6.98

Hourly Analysis Program v4.90 Page 70 of 138


Air System Sizing Summary for 03-L2- FCU-102-R43
Project Name: DJIBOUTI-LEVEL 2-26-03-18- 04/02/2018
Prepared by: a 10:25AM

Air System Information


Air System Name 03-L2- FCU-102-R43 Number of zones 1
Equipment Class CW AHU Floor Area 32.6 m²
Air System Type SZCAV Location Dubai, United Arab Emirates

Sizing Calculation Information


Calculation Months Jan to Dec Zone L/s Sizing Sum of space airflow rates
Sizing Data Calculated Space L/s Sizing Individual peak space loads

Central Cooling Coil Sizing Data


Total coil load 3.2 kW Load occurs at Jun 1400
Sensible coil load 2.8 kW OA DB / WB 48.0 / 29.9 °C
Coil L/s at Jun 1400 227 L/s Entering DB / WB 25.3 / 18.6 °C
Max block L/s 227 L/s Leaving DB / WB 15.1 / 14.4 °C
Sum of peak zone L/s 227 L/s Coil ADP 13.9 °C
Sensible heat ratio 0.869 Bypass Factor 0.100
m²/kW 10.1 Resulting RH 55 %
W/m² 99.2 Design supply temp. 14.0 °C
Water flow @ 8.9 °K rise 0.09 L/s Zone T-stat Check 1 of 1 OK
Max zone temperature deviation 0.0 °K

Supply Fan Sizing Data


Actual max L/s 227 L/s Fan motor BHP 0.04 BHP
Standard L/s 227 L/s Fan motor kW 0.03 kW
Actual max L/(s-m²) 6.98 L/(s-m²) Fan static 75 Pa

Outdoor Ventilation Air Data


Design airflow L/s 0 L/s L/s/person 0.00 L/s/person
L/(s-m²) 0.00 L/(s-m²)

Hourly Analysis Program v4.90 Page 71 of 138


Zone Sizing Summary for 03-L2- FCU-102-R43
Project Name: DJIBOUTI-LEVEL 2-26-03-18- 04/02/2018
Prepared by: a 10:25AM

Air System Information


Air System Name 03-L2- FCU-102-R43 Number of zones 1
Equipment Class CW AHU Floor Area 32.6 m²
Air System Type SZCAV Location Dubai, United Arab Emirates

Sizing Calculation Information


Calculation Months Jan to Dec Zone L/s Sizing Sum of space airflow rates
Sizing Data Calculated Space L/s Sizing Individual peak space loads

Zone Sizing Data

Maximum Maximum Zone


Cooling Design Minimum Heating Floor
Sensible Airflow Airflow Time of Load Area Zone
Zone Name (kW) (L/s) (L/s) Peak Load (kW) (m²) L/(s-m²)
Zone 1 2.7 227 227 Jun 1300 0.3 32.6 6.98

Zone Terminal Sizing Data


No Zone Terminal Sizing Data required for this system.

Space Loads and Airflows

Cooling Time Air Heating Floor


Zone Name / Sensible of Flow Load Area Space
Space Name Mult. (kW) Load (L/s) (kW) (m²) L/(s-m²)
Zone 1
03-L2-ROOM-43 1 2.7 Jun 1300 227 0.3 32.6 6.98

Hourly Analysis Program v4.90 Page 72 of 138


Air System Sizing Summary for 03-L2- FCU-102-R44
Project Name: DJIBOUTI-LEVEL 2-26-03-18- 04/02/2018
Prepared by: a 10:25AM

Air System Information


Air System Name 03-L2- FCU-102-R44 Number of zones 1
Equipment Class CW AHU Floor Area 32.6 m²
Air System Type SZCAV Location Dubai, United Arab Emirates

Sizing Calculation Information


Calculation Months Jan to Dec Zone L/s Sizing Sum of space airflow rates
Sizing Data Calculated Space L/s Sizing Individual peak space loads

Central Cooling Coil Sizing Data


Total coil load 3.0 kW Load occurs at Jun 1300
Sensible coil load 2.6 kW OA DB / WB 47.3 / 29.8 °C
Coil L/s at Jun 1300 209 L/s Entering DB / WB 25.3 / 18.6 °C
Max block L/s 209 L/s Leaving DB / WB 14.9 / 14.3 °C
Sum of peak zone L/s 209 L/s Coil ADP 13.8 °C
Sensible heat ratio 0.861 Bypass Factor 0.100
m²/kW 10.7 Resulting RH 55 %
W/m² 93.4 Design supply temp. 14.0 °C
Water flow @ 8.9 °K rise 0.08 L/s Zone T-stat Check 1 of 1 OK
Max zone temperature deviation 0.0 °K

Supply Fan Sizing Data


Actual max L/s 209 L/s Fan motor BHP 0.04 BHP
Standard L/s 209 L/s Fan motor kW 0.03 kW
Actual max L/(s-m²) 6.41 L/(s-m²) Fan static 75 Pa

Outdoor Ventilation Air Data


Design airflow L/s 0 L/s L/s/person 0.00 L/s/person
L/(s-m²) 0.00 L/(s-m²)

Hourly Analysis Program v4.90 Page 73 of 138


Zone Sizing Summary for 03-L2- FCU-102-R44
Project Name: DJIBOUTI-LEVEL 2-26-03-18- 04/02/2018
Prepared by: a 10:25AM

Air System Information


Air System Name 03-L2- FCU-102-R44 Number of zones 1
Equipment Class CW AHU Floor Area 32.6 m²
Air System Type SZCAV Location Dubai, United Arab Emirates

Sizing Calculation Information


Calculation Months Jan to Dec Zone L/s Sizing Sum of space airflow rates
Sizing Data Calculated Space L/s Sizing Individual peak space loads

Zone Sizing Data

Maximum Maximum Zone


Cooling Design Minimum Heating Floor
Sensible Airflow Airflow Time of Load Area Zone
Zone Name (kW) (L/s) (L/s) Peak Load (kW) (m²) L/(s-m²)
Zone 1 2.5 209 209 Jun 1300 0.3 32.6 6.41

Zone Terminal Sizing Data


No Zone Terminal Sizing Data required for this system.

Space Loads and Airflows

Cooling Time Air Heating Floor


Zone Name / Sensible of Flow Load Area Space
Space Name Mult. (kW) Load (L/s) (kW) (m²) L/(s-m²)
Zone 1
03-L2-ROOM-44 1 2.5 Jun 1300 209 0.3 32.6 6.41

Hourly Analysis Program v4.90 Page 74 of 138


Air System Sizing Summary for 03-L2- FCU-102-R45
Project Name: DJIBOUTI-LEVEL 2-26-03-18- 04/02/2018
Prepared by: a 10:25AM

Air System Information


Air System Name 03-L2- FCU-102-R45 Number of zones 1
Equipment Class CW AHU Floor Area 32.7 m²
Air System Type SZCAV Location Dubai, United Arab Emirates

Sizing Calculation Information


Calculation Months Jan to Dec Zone L/s Sizing Sum of space airflow rates
Sizing Data Calculated Space L/s Sizing Individual peak space loads

Central Cooling Coil Sizing Data


Total coil load 2.6 kW Load occurs at Jul 1700
Sensible coil load 2.2 kW OA DB / WB 47.9 / 29.8 °C
Coil L/s at Jul 1700 168 L/s Entering DB / WB 25.5 / 18.7 °C
Max block L/s 168 L/s Leaving DB / WB 14.8 / 14.2 °C
Sum of peak zone L/s 168 L/s Coil ADP 13.6 °C
Sensible heat ratio 0.827 Bypass Factor 0.100
m²/kW 12.5 Resulting RH 55 %
W/m² 80.0 Design supply temp. 14.0 °C
Water flow @ 8.9 °K rise 0.07 L/s Zone T-stat Check 1 of 1 OK
Max zone temperature deviation 0.0 °K

Supply Fan Sizing Data


Actual max L/s 168 L/s Fan motor BHP 0.03 BHP
Standard L/s 168 L/s Fan motor kW 0.02 kW
Actual max L/(s-m²) 5.15 L/(s-m²) Fan static 75 Pa

Outdoor Ventilation Air Data


Design airflow L/s 0 L/s L/s/person 0.00 L/s/person
L/(s-m²) 0.00 L/(s-m²)

Hourly Analysis Program v4.90 Page 75 of 138


Zone Sizing Summary for 03-L2- FCU-102-R45
Project Name: DJIBOUTI-LEVEL 2-26-03-18- 04/02/2018
Prepared by: a 10:25AM

Air System Information


Air System Name 03-L2- FCU-102-R45 Number of zones 1
Equipment Class CW AHU Floor Area 32.7 m²
Air System Type SZCAV Location Dubai, United Arab Emirates

Sizing Calculation Information


Calculation Months Jan to Dec Zone L/s Sizing Sum of space airflow rates
Sizing Data Calculated Space L/s Sizing Individual peak space loads

Zone Sizing Data

Maximum Maximum Zone


Cooling Design Minimum Heating Floor
Sensible Airflow Airflow Time of Load Area Zone
Zone Name (kW) (L/s) (L/s) Peak Load (kW) (m²) L/(s-m²)
Zone 1 2.0 168 168 Jul 1600 0.2 32.7 5.15

Zone Terminal Sizing Data


No Zone Terminal Sizing Data required for this system.

Space Loads and Airflows

Cooling Time Air Heating Floor


Zone Name / Sensible of Flow Load Area Space
Space Name Mult. (kW) Load (L/s) (kW) (m²) L/(s-m²)
Zone 1
03-L2-ROOM-45 1 2.0 Jul 1600 168 0.2 32.7 5.15

Hourly Analysis Program v4.90 Page 76 of 138


Air System Sizing Summary for 03-L2- FCU-102-R46
Project Name: DJIBOUTI-LEVEL 2-26-03-18- 04/02/2018
Prepared by: a 10:25AM

Air System Information


Air System Name 03-L2- FCU-102-R46 Number of zones 1
Equipment Class CW AHU Floor Area 32.6 m²
Air System Type SZCAV Location Dubai, United Arab Emirates

Sizing Calculation Information


Calculation Months Jan to Dec Zone L/s Sizing Sum of space airflow rates
Sizing Data Calculated Space L/s Sizing Individual peak space loads

Central Cooling Coil Sizing Data


Total coil load 2.6 kW Load occurs at Jun 1400
Sensible coil load 2.2 kW OA DB / WB 48.0 / 29.9 °C
Coil L/s at Jun 1400 168 L/s Entering DB / WB 25.4 / 18.7 °C
Max block L/s 168 L/s Leaving DB / WB 14.7 / 14.0 °C
Sum of peak zone L/s 168 L/s Coil ADP 13.5 °C
Sensible heat ratio 0.825 Bypass Factor 0.100
m²/kW 12.4 Resulting RH 55 %
W/m² 80.9 Design supply temp. 14.0 °C
Water flow @ 8.9 °K rise 0.07 L/s Zone T-stat Check 1 of 1 OK
Max zone temperature deviation 0.0 °K

Supply Fan Sizing Data


Actual max L/s 168 L/s Fan motor BHP 0.03 BHP
Standard L/s 168 L/s Fan motor kW 0.02 kW
Actual max L/(s-m²) 5.15 L/(s-m²) Fan static 75 Pa

Outdoor Ventilation Air Data


Design airflow L/s 0 L/s L/s/person 0.00 L/s/person
L/(s-m²) 0.00 L/(s-m²)

Hourly Analysis Program v4.90 Page 77 of 138


Zone Sizing Summary for 03-L2- FCU-102-R46
Project Name: DJIBOUTI-LEVEL 2-26-03-18- 04/02/2018
Prepared by: a 10:25AM

Air System Information


Air System Name 03-L2- FCU-102-R46 Number of zones 1
Equipment Class CW AHU Floor Area 32.6 m²
Air System Type SZCAV Location Dubai, United Arab Emirates

Sizing Calculation Information


Calculation Months Jan to Dec Zone L/s Sizing Sum of space airflow rates
Sizing Data Calculated Space L/s Sizing Individual peak space loads

Zone Sizing Data

Maximum Maximum Zone


Cooling Design Minimum Heating Floor
Sensible Airflow Airflow Time of Load Area Zone
Zone Name (kW) (L/s) (L/s) Peak Load (kW) (m²) L/(s-m²)
Zone 1 2.0 168 168 Jul 1600 0.2 32.6 5.15

Zone Terminal Sizing Data


No Zone Terminal Sizing Data required for this system.

Space Loads and Airflows

Cooling Time Air Heating Floor


Zone Name / Sensible of Flow Load Area Space
Space Name Mult. (kW) Load (L/s) (kW) (m²) L/(s-m²)
Zone 1
03-L2-ROOM-46 1 2.0 Jul 1600 168 0.2 32.6 5.15

Hourly Analysis Program v4.90 Page 78 of 138


Air System Sizing Summary for 03-L2- FCU-102-R47
Project Name: DJIBOUTI-LEVEL 2-26-03-18- 04/02/2018
Prepared by: a 10:25AM

Air System Information


Air System Name 03-L2- FCU-102-R47 Number of zones 1
Equipment Class CW AHU Floor Area 32.6 m²
Air System Type SZCAV Location Dubai, United Arab Emirates

Sizing Calculation Information


Calculation Months Jan to Dec Zone L/s Sizing Sum of space airflow rates
Sizing Data Calculated Space L/s Sizing Individual peak space loads

Central Cooling Coil Sizing Data


Total coil load 2.6 kW Load occurs at Jun 1400
Sensible coil load 2.2 kW OA DB / WB 48.0 / 29.9 °C
Coil L/s at Jun 1400 168 L/s Entering DB / WB 25.4 / 18.7 °C
Max block L/s 168 L/s Leaving DB / WB 14.7 / 14.0 °C
Sum of peak zone L/s 168 L/s Coil ADP 13.5 °C
Sensible heat ratio 0.825 Bypass Factor 0.100
m²/kW 12.4 Resulting RH 55 %
W/m² 80.9 Design supply temp. 14.0 °C
Water flow @ 8.9 °K rise 0.07 L/s Zone T-stat Check 1 of 1 OK
Max zone temperature deviation 0.0 °K

Supply Fan Sizing Data


Actual max L/s 168 L/s Fan motor BHP 0.03 BHP
Standard L/s 168 L/s Fan motor kW 0.02 kW
Actual max L/(s-m²) 5.15 L/(s-m²) Fan static 75 Pa

Outdoor Ventilation Air Data


Design airflow L/s 0 L/s L/s/person 0.00 L/s/person
L/(s-m²) 0.00 L/(s-m²)

Hourly Analysis Program v4.90 Page 79 of 138


Zone Sizing Summary for 03-L2- FCU-102-R47
Project Name: DJIBOUTI-LEVEL 2-26-03-18- 04/02/2018
Prepared by: a 10:25AM

Air System Information


Air System Name 03-L2- FCU-102-R47 Number of zones 1
Equipment Class CW AHU Floor Area 32.6 m²
Air System Type SZCAV Location Dubai, United Arab Emirates

Sizing Calculation Information


Calculation Months Jan to Dec Zone L/s Sizing Sum of space airflow rates
Sizing Data Calculated Space L/s Sizing Individual peak space loads

Zone Sizing Data

Maximum Maximum Zone


Cooling Design Minimum Heating Floor
Sensible Airflow Airflow Time of Load Area Zone
Zone Name (kW) (L/s) (L/s) Peak Load (kW) (m²) L/(s-m²)
Zone 1 2.0 168 168 Jul 1600 0.2 32.6 5.15

Zone Terminal Sizing Data


No Zone Terminal Sizing Data required for this system.

Space Loads and Airflows

Cooling Time Air Heating Floor


Zone Name / Sensible of Flow Load Area Space
Space Name Mult. (kW) Load (L/s) (kW) (m²) L/(s-m²)
Zone 1
03-L2-ROOM-47 1 2.0 Jul 1600 168 0.2 32.6 5.15

Hourly Analysis Program v4.90 Page 80 of 138


Air System Sizing Summary for 03-L2- FCU-102-R48
Project Name: DJIBOUTI-LEVEL 2-26-03-18- 04/02/2018
Prepared by: a 10:25AM

Air System Information


Air System Name 03-L2- FCU-102-R48 Number of zones 1
Equipment Class CW AHU Floor Area 31.8 m²
Air System Type SZCAV Location Dubai, United Arab Emirates

Sizing Calculation Information


Calculation Months Jan to Dec Zone L/s Sizing Sum of space airflow rates
Sizing Data Calculated Space L/s Sizing Individual peak space loads

Central Cooling Coil Sizing Data


Total coil load 2.6 kW Load occurs at Jul 1700
Sensible coil load 2.1 kW OA DB / WB 47.9 / 29.8 °C
Coil L/s at Jul 1700 166 L/s Entering DB / WB 25.4 / 18.7 °C
Max block L/s 166 L/s Leaving DB / WB 14.8 / 14.2 °C
Sum of peak zone L/s 166 L/s Coil ADP 13.6 °C
Sensible heat ratio 0.827 Bypass Factor 0.100
m²/kW 12.4 Resulting RH 55 %
W/m² 81.0 Design supply temp. 14.0 °C
Water flow @ 8.9 °K rise 0.07 L/s Zone T-stat Check 1 of 1 OK
Max zone temperature deviation 0.0 °K

Supply Fan Sizing Data


Actual max L/s 166 L/s Fan motor BHP 0.03 BHP
Standard L/s 166 L/s Fan motor kW 0.02 kW
Actual max L/(s-m²) 5.22 L/(s-m²) Fan static 75 Pa

Outdoor Ventilation Air Data


Design airflow L/s 0 L/s L/s/person 0.00 L/s/person
L/(s-m²) 0.00 L/(s-m²)

Hourly Analysis Program v4.90 Page 81 of 138


Zone Sizing Summary for 03-L2- FCU-102-R48
Project Name: DJIBOUTI-LEVEL 2-26-03-18- 04/02/2018
Prepared by: a 10:25AM

Air System Information


Air System Name 03-L2- FCU-102-R48 Number of zones 1
Equipment Class CW AHU Floor Area 31.8 m²
Air System Type SZCAV Location Dubai, United Arab Emirates

Sizing Calculation Information


Calculation Months Jan to Dec Zone L/s Sizing Sum of space airflow rates
Sizing Data Calculated Space L/s Sizing Individual peak space loads

Zone Sizing Data

Maximum Maximum Zone


Cooling Design Minimum Heating Floor
Sensible Airflow Airflow Time of Load Area Zone
Zone Name (kW) (L/s) (L/s) Peak Load (kW) (m²) L/(s-m²)
Zone 1 2.0 166 166 Jul 1600 0.2 31.8 5.22

Zone Terminal Sizing Data


No Zone Terminal Sizing Data required for this system.

Space Loads and Airflows

Cooling Time Air Heating Floor


Zone Name / Sensible of Flow Load Area Space
Space Name Mult. (kW) Load (L/s) (kW) (m²) L/(s-m²)
Zone 1
03-L2-ROOM-48 1 2.0 Jul 1600 166 0.2 31.8 5.22

Hourly Analysis Program v4.90 Page 82 of 138


Air System Sizing Summary for 03-L2- FCU-102-R49
Project Name: DJIBOUTI-LEVEL 2-26-03-18- 04/02/2018
Prepared by: a 10:25AM

Air System Information


Air System Name 03-L2- FCU-102-R49 Number of zones 1
Equipment Class CW AHU Floor Area 32.6 m²
Air System Type SZCAV Location Dubai, United Arab Emirates

Sizing Calculation Information


Calculation Months Jan to Dec Zone L/s Sizing Sum of space airflow rates
Sizing Data Calculated Space L/s Sizing Individual peak space loads

Central Cooling Coil Sizing Data


Total coil load 2.5 kW Load occurs at Jul 1600
Sensible coil load 2.1 kW OA DB / WB 48.6 / 29.9 °C
Coil L/s at Jul 1600 162 L/s Entering DB / WB 25.4 / 18.6 °C
Max block L/s 162 L/s Leaving DB / WB 14.7 / 14.0 °C
Sum of peak zone L/s 162 L/s Coil ADP 13.5 °C
Sensible heat ratio 0.834 Bypass Factor 0.100
m²/kW 12.9 Resulting RH 55 %
W/m² 77.3 Design supply temp. 14.0 °C
Water flow @ 8.9 °K rise 0.07 L/s Zone T-stat Check 1 of 1 OK
Max zone temperature deviation 0.0 °K

Supply Fan Sizing Data


Actual max L/s 162 L/s Fan motor BHP 0.03 BHP
Standard L/s 162 L/s Fan motor kW 0.02 kW
Actual max L/(s-m²) 4.97 L/(s-m²) Fan static 75 Pa

Outdoor Ventilation Air Data


Design airflow L/s 0 L/s L/s/person 0.00 L/s/person
L/(s-m²) 0.00 L/(s-m²)

Hourly Analysis Program v4.90 Page 83 of 138


Zone Sizing Summary for 03-L2- FCU-102-R49
Project Name: DJIBOUTI-LEVEL 2-26-03-18- 04/02/2018
Prepared by: a 10:25AM

Air System Information


Air System Name 03-L2- FCU-102-R49 Number of zones 1
Equipment Class CW AHU Floor Area 32.6 m²
Air System Type SZCAV Location Dubai, United Arab Emirates

Sizing Calculation Information


Calculation Months Jan to Dec Zone L/s Sizing Sum of space airflow rates
Sizing Data Calculated Space L/s Sizing Individual peak space loads

Zone Sizing Data

Maximum Maximum Zone


Cooling Design Minimum Heating Floor
Sensible Airflow Airflow Time of Load Area Zone
Zone Name (kW) (L/s) (L/s) Peak Load (kW) (m²) L/(s-m²)
Zone 1 2.0 162 162 Jul 1600 0.2 32.6 4.97

Zone Terminal Sizing Data


No Zone Terminal Sizing Data required for this system.

Space Loads and Airflows

Cooling Time Air Heating Floor


Zone Name / Sensible of Flow Load Area Space
Space Name Mult. (kW) Load (L/s) (kW) (m²) L/(s-m²)
Zone 1
03-L2-ROOM-49 1 2.0 Jul 1600 162 0.2 32.6 4.97

Hourly Analysis Program v4.90 Page 84 of 138


Air System Sizing Summary for 03-L2- FCU-102-R5
Project Name: DJIBOUTI-LEVEL 2-26-03-18- 04/02/2018
Prepared by: a 10:25AM

Air System Information


Air System Name 03-L2- FCU-102-R5 Number of zones 1
Equipment Class CW AHU Floor Area 31.5 m²
Air System Type SZCAV Location Dubai, United Arab Emirates

Sizing Calculation Information


Calculation Months Jan to Dec Zone L/s Sizing Sum of space airflow rates
Sizing Data Calculated Space L/s Sizing Individual peak space loads

Central Cooling Coil Sizing Data


Total coil load 2.6 kW Load occurs at Sep 1800
Sensible coil load 2.2 kW OA DB / WB 45.2 / 28.4 °C
Coil L/s at Sep 1800 170 L/s Entering DB / WB 25.4 / 18.5 °C
Max block L/s 170 L/s Leaving DB / WB 14.8 / 14.1 °C
Sum of peak zone L/s 170 L/s Coil ADP 13.6 °C
Sensible heat ratio 0.856 Bypass Factor 0.100
m²/kW 12.3 Resulting RH 54 %
W/m² 81.0 Design supply temp. 14.0 °C
Water flow @ 8.9 °K rise 0.07 L/s Zone T-stat Check 1 of 1 OK
Max zone temperature deviation 0.0 °K

Supply Fan Sizing Data


Actual max L/s 170 L/s Fan motor BHP 0.03 BHP
Standard L/s 170 L/s Fan motor kW 0.02 kW
Actual max L/(s-m²) 5.40 L/(s-m²) Fan static 75 Pa

Outdoor Ventilation Air Data


Design airflow L/s 0 L/s L/s/person 0.00 L/s/person
L/(s-m²) 0.00 L/(s-m²)

Hourly Analysis Program v4.90 Page 85 of 138


Zone Sizing Summary for 03-L2- FCU-102-R5
Project Name: DJIBOUTI-LEVEL 2-26-03-18- 04/02/2018
Prepared by: a 10:25AM

Air System Information


Air System Name 03-L2- FCU-102-R5 Number of zones 1
Equipment Class CW AHU Floor Area 31.5 m²
Air System Type SZCAV Location Dubai, United Arab Emirates

Sizing Calculation Information


Calculation Months Jan to Dec Zone L/s Sizing Sum of space airflow rates
Sizing Data Calculated Space L/s Sizing Individual peak space loads

Zone Sizing Data

Maximum Maximum Zone


Cooling Design Minimum Heating Floor
Sensible Airflow Airflow Time of Load Area Zone
Zone Name (kW) (L/s) (L/s) Peak Load (kW) (m²) L/(s-m²)
Zone 1 2.1 170 170 Sep 1800 0.2 31.5 5.40

Zone Terminal Sizing Data


No Zone Terminal Sizing Data required for this system.

Space Loads and Airflows

Cooling Time Air Heating Floor


Zone Name / Sensible of Flow Load Area Space
Space Name Mult. (kW) Load (L/s) (kW) (m²) L/(s-m²)
Zone 1
03-L2-ROOM-05 1 2.1 Sep 1800 170 0.2 31.5 5.40

Hourly Analysis Program v4.90 Page 86 of 138


Air System Sizing Summary for 03-L2- FCU-102-R50
Project Name: DJIBOUTI-LEVEL 2-26-03-18- 04/02/2018
Prepared by: a 10:25AM

Air System Information


Air System Name 03-L2- FCU-102-R50 Number of zones 1
Equipment Class CW AHU Floor Area 32.4 m²
Air System Type SZCAV Location Dubai, United Arab Emirates

Sizing Calculation Information


Calculation Months Jan to Dec Zone L/s Sizing Sum of space airflow rates
Sizing Data Calculated Space L/s Sizing Individual peak space loads

Central Cooling Coil Sizing Data


Total coil load 3.1 kW Load occurs at Jun 1400
Sensible coil load 2.6 kW OA DB / WB 48.0 / 29.9 °C
Coil L/s at Jun 1400 210 L/s Entering DB / WB 25.3 / 18.5 °C
Max block L/s 210 L/s Leaving DB / WB 14.9 / 14.3 °C
Sum of peak zone L/s 210 L/s Coil ADP 13.7 °C
Sensible heat ratio 0.862 Bypass Factor 0.100
m²/kW 10.6 Resulting RH 55 %
W/m² 94.4 Design supply temp. 14.0 °C
Water flow @ 8.9 °K rise 0.08 L/s Zone T-stat Check 1 of 1 OK
Max zone temperature deviation 0.0 °K

Supply Fan Sizing Data


Actual max L/s 210 L/s Fan motor BHP 0.04 BHP
Standard L/s 210 L/s Fan motor kW 0.03 kW
Actual max L/(s-m²) 6.49 L/(s-m²) Fan static 75 Pa

Outdoor Ventilation Air Data


Design airflow L/s 0 L/s L/s/person 0.00 L/s/person
L/(s-m²) 0.00 L/(s-m²)

Hourly Analysis Program v4.90 Page 87 of 138


Zone Sizing Summary for 03-L2- FCU-102-R50
Project Name: DJIBOUTI-LEVEL 2-26-03-18- 04/02/2018
Prepared by: a 10:25AM

Air System Information


Air System Name 03-L2- FCU-102-R50 Number of zones 1
Equipment Class CW AHU Floor Area 32.4 m²
Air System Type SZCAV Location Dubai, United Arab Emirates

Sizing Calculation Information


Calculation Months Jan to Dec Zone L/s Sizing Sum of space airflow rates
Sizing Data Calculated Space L/s Sizing Individual peak space loads

Zone Sizing Data

Maximum Maximum Zone


Cooling Design Minimum Heating Floor
Sensible Airflow Airflow Time of Load Area Zone
Zone Name (kW) (L/s) (L/s) Peak Load (kW) (m²) L/(s-m²)
Zone 1 2.5 210 210 Jul 1600 0.2 32.4 6.49

Zone Terminal Sizing Data


No Zone Terminal Sizing Data required for this system.

Space Loads and Airflows

Cooling Time Air Heating Floor


Zone Name / Sensible of Flow Load Area Space
Space Name Mult. (kW) Load (L/s) (kW) (m²) L/(s-m²)
Zone 1
03-L2-ROOM-50 1 2.5 Jul 1600 210 0.2 32.4 6.49

Hourly Analysis Program v4.90 Page 88 of 138


Air System Sizing Summary for 03-L2- FCU-102-R6
Project Name: DJIBOUTI-LEVEL 2-26-03-18- 04/02/2018
Prepared by: a 10:25AM

Air System Information


Air System Name 03-L2- FCU-102-R6 Number of zones 1
Equipment Class CW AHU Floor Area 32.5 m²
Air System Type SZCAV Location Dubai, United Arab Emirates

Sizing Calculation Information


Calculation Months Jan to Dec Zone L/s Sizing Sum of space airflow rates
Sizing Data Calculated Space L/s Sizing Individual peak space loads

Central Cooling Coil Sizing Data


Total coil load 2.6 kW Load occurs at Aug 1900
Sensible coil load 2.1 kW OA DB / WB 45.6 / 29.3 °C
Coil L/s at Aug 1900 172 L/s Entering DB / WB 25.4 / 18.7 °C
Max block L/s 172 L/s Leaving DB / WB 15.0 / 14.4 °C
Sum of peak zone L/s 172 L/s Coil ADP 13.9 °C
Sensible heat ratio 0.840 Bypass Factor 0.100
m²/kW 12.7 Resulting RH 56 %
W/m² 78.8 Design supply temp. 14.0 °C
Water flow @ 8.9 °K rise 0.07 L/s Zone T-stat Check 1 of 1 OK
Max zone temperature deviation 0.0 °K

Supply Fan Sizing Data


Actual max L/s 172 L/s Fan motor BHP 0.03 BHP
Standard L/s 172 L/s Fan motor kW 0.02 kW
Actual max L/(s-m²) 5.30 L/(s-m²) Fan static 75 Pa

Outdoor Ventilation Air Data


Design airflow L/s 0 L/s L/s/person 0.00 L/s/person
L/(s-m²) 0.00 L/(s-m²)

Hourly Analysis Program v4.90 Page 89 of 138


Zone Sizing Summary for 03-L2- FCU-102-R6
Project Name: DJIBOUTI-LEVEL 2-26-03-18- 04/02/2018
Prepared by: a 10:25AM

Air System Information


Air System Name 03-L2- FCU-102-R6 Number of zones 1
Equipment Class CW AHU Floor Area 32.5 m²
Air System Type SZCAV Location Dubai, United Arab Emirates

Sizing Calculation Information


Calculation Months Jan to Dec Zone L/s Sizing Sum of space airflow rates
Sizing Data Calculated Space L/s Sizing Individual peak space loads

Zone Sizing Data

Maximum Maximum Zone


Cooling Design Minimum Heating Floor
Sensible Airflow Airflow Time of Load Area Zone
Zone Name (kW) (L/s) (L/s) Peak Load (kW) (m²) L/(s-m²)
Zone 1 2.1 172 172 Sep 1800 0.2 32.5 5.30

Zone Terminal Sizing Data


No Zone Terminal Sizing Data required for this system.

Space Loads and Airflows

Cooling Time Air Heating Floor


Zone Name / Sensible of Flow Load Area Space
Space Name Mult. (kW) Load (L/s) (kW) (m²) L/(s-m²)
Zone 1
03-L2-ROOM-06 1 2.1 Sep 1800 172 0.2 32.5 5.30

Hourly Analysis Program v4.90 Page 90 of 138


Air System Sizing Summary for 03-L2- FCU-102-R7
Project Name: DJIBOUTI-LEVEL 2-26-03-18- 04/02/2018
Prepared by: a 10:25AM

Air System Information


Air System Name 03-L2- FCU-102-R7 Number of zones 1
Equipment Class CW AHU Floor Area 32.2 m²
Air System Type SZCAV Location Dubai, United Arab Emirates

Sizing Calculation Information


Calculation Months Jan to Dec Zone L/s Sizing Sum of space airflow rates
Sizing Data Calculated Space L/s Sizing Individual peak space loads

Central Cooling Coil Sizing Data


Total coil load 2.6 kW Load occurs at Aug 1800
Sensible coil load 2.2 kW OA DB / WB 46.9 / 29.6 °C
Coil L/s at Aug 1800 171 L/s Entering DB / WB 25.4 / 18.7 °C
Max block L/s 171 L/s Leaving DB / WB 14.9 / 14.3 °C
Sum of peak zone L/s 171 L/s Coil ADP 13.7 °C
Sensible heat ratio 0.841 Bypass Factor 0.100
m²/kW 12.5 Resulting RH 55 %
W/m² 80.1 Design supply temp. 14.0 °C
Water flow @ 8.9 °K rise 0.07 L/s Zone T-stat Check 1 of 1 OK
Max zone temperature deviation 0.0 °K

Supply Fan Sizing Data


Actual max L/s 171 L/s Fan motor BHP 0.03 BHP
Standard L/s 171 L/s Fan motor kW 0.02 kW
Actual max L/(s-m²) 5.33 L/(s-m²) Fan static 75 Pa

Outdoor Ventilation Air Data


Design airflow L/s 0 L/s L/s/person 0.00 L/s/person
L/(s-m²) 0.00 L/(s-m²)

Hourly Analysis Program v4.90 Page 91 of 138


Zone Sizing Summary for 03-L2- FCU-102-R7
Project Name: DJIBOUTI-LEVEL 2-26-03-18- 04/02/2018
Prepared by: a 10:25AM

Air System Information


Air System Name 03-L2- FCU-102-R7 Number of zones 1
Equipment Class CW AHU Floor Area 32.2 m²
Air System Type SZCAV Location Dubai, United Arab Emirates

Sizing Calculation Information


Calculation Months Jan to Dec Zone L/s Sizing Sum of space airflow rates
Sizing Data Calculated Space L/s Sizing Individual peak space loads

Zone Sizing Data

Maximum Maximum Zone


Cooling Design Minimum Heating Floor
Sensible Airflow Airflow Time of Load Area Zone
Zone Name (kW) (L/s) (L/s) Peak Load (kW) (m²) L/(s-m²)
Zone 1 2.1 171 171 Sep 1800 0.2 32.2 5.33

Zone Terminal Sizing Data


No Zone Terminal Sizing Data required for this system.

Space Loads and Airflows

Cooling Time Air Heating Floor


Zone Name / Sensible of Flow Load Area Space
Space Name Mult. (kW) Load (L/s) (kW) (m²) L/(s-m²)
Zone 1
03-L2-ROOM-07 1 2.1 Sep 1800 171 0.2 32.2 5.33

Hourly Analysis Program v4.90 Page 92 of 138


Air System Sizing Summary for 03-L2- FCU-102-R8
Project Name: DJIBOUTI-LEVEL 2-26-03-18- 04/02/2018
Prepared by: a 10:25AM

Air System Information


Air System Name 03-L2- FCU-102-R8 Number of zones 1
Equipment Class CW AHU Floor Area 32.5 m²
Air System Type SZCAV Location Dubai, United Arab Emirates

Sizing Calculation Information


Calculation Months Jan to Dec Zone L/s Sizing Sum of space airflow rates
Sizing Data Calculated Space L/s Sizing Individual peak space loads

Central Cooling Coil Sizing Data


Total coil load 2.6 kW Load occurs at Aug 1900
Sensible coil load 2.1 kW OA DB / WB 45.6 / 29.3 °C
Coil L/s at Aug 1900 172 L/s Entering DB / WB 25.4 / 18.7 °C
Max block L/s 172 L/s Leaving DB / WB 15.0 / 14.4 °C
Sum of peak zone L/s 172 L/s Coil ADP 13.9 °C
Sensible heat ratio 0.840 Bypass Factor 0.100
m²/kW 12.7 Resulting RH 56 %
W/m² 78.8 Design supply temp. 14.0 °C
Water flow @ 8.9 °K rise 0.07 L/s Zone T-stat Check 1 of 1 OK
Max zone temperature deviation 0.0 °K

Supply Fan Sizing Data


Actual max L/s 172 L/s Fan motor BHP 0.03 BHP
Standard L/s 172 L/s Fan motor kW 0.02 kW
Actual max L/(s-m²) 5.30 L/(s-m²) Fan static 75 Pa

Outdoor Ventilation Air Data


Design airflow L/s 0 L/s L/s/person 0.00 L/s/person
L/(s-m²) 0.00 L/(s-m²)

Hourly Analysis Program v4.90 Page 93 of 138


Zone Sizing Summary for 03-L2- FCU-102-R8
Project Name: DJIBOUTI-LEVEL 2-26-03-18- 04/02/2018
Prepared by: a 10:25AM

Air System Information


Air System Name 03-L2- FCU-102-R8 Number of zones 1
Equipment Class CW AHU Floor Area 32.5 m²
Air System Type SZCAV Location Dubai, United Arab Emirates

Sizing Calculation Information


Calculation Months Jan to Dec Zone L/s Sizing Sum of space airflow rates
Sizing Data Calculated Space L/s Sizing Individual peak space loads

Zone Sizing Data

Maximum Maximum Zone


Cooling Design Minimum Heating Floor
Sensible Airflow Airflow Time of Load Area Zone
Zone Name (kW) (L/s) (L/s) Peak Load (kW) (m²) L/(s-m²)
Zone 1 2.1 172 172 Sep 1800 0.2 32.5 5.30

Zone Terminal Sizing Data


No Zone Terminal Sizing Data required for this system.

Space Loads and Airflows

Cooling Time Air Heating Floor


Zone Name / Sensible of Flow Load Area Space
Space Name Mult. (kW) Load (L/s) (kW) (m²) L/(s-m²)
Zone 1
03-L2-ROOM-08 1 2.1 Sep 1800 172 0.2 32.5 5.30

Hourly Analysis Program v4.90 Page 94 of 138


Air System Sizing Summary for 03-L2- FCU-102-R9
Project Name: DJIBOUTI-LEVEL 2-26-03-18- 04/02/2018
Prepared by: a 10:25AM

Air System Information


Air System Name 03-L2- FCU-102-R9 Number of zones 1
Equipment Class CW AHU Floor Area 32.5 m²
Air System Type SZCAV Location Dubai, United Arab Emirates

Sizing Calculation Information


Calculation Months Jan to Dec Zone L/s Sizing Sum of space airflow rates
Sizing Data Calculated Space L/s Sizing Individual peak space loads

Central Cooling Coil Sizing Data


Total coil load 3.4 kW Load occurs at Sep 1800
Sensible coil load 3.0 kW OA DB / WB 45.2 / 28.4 °C
Coil L/s at Sep 1800 241 L/s Entering DB / WB 25.1 / 18.3 °C
Max block L/s 241 L/s Leaving DB / WB 14.8 / 14.1 °C
Sum of peak zone L/s 241 L/s Coil ADP 13.6 °C
Sensible heat ratio 0.888 Bypass Factor 0.100
m²/kW 9.6 Resulting RH 54 %
W/m² 104.7 Design supply temp. 14.0 °C
Water flow @ 8.9 °K rise 0.09 L/s Zone T-stat Check 1 of 1 OK
Max zone temperature deviation 0.0 °K

Supply Fan Sizing Data


Actual max L/s 241 L/s Fan motor BHP 0.04 BHP
Standard L/s 241 L/s Fan motor kW 0.03 kW
Actual max L/(s-m²) 7.43 L/(s-m²) Fan static 75 Pa

Outdoor Ventilation Air Data


Design airflow L/s 0 L/s L/s/person 0.00 L/s/person
L/(s-m²) 0.00 L/(s-m²)

Hourly Analysis Program v4.90 Page 95 of 138


Zone Sizing Summary for 03-L2- FCU-102-R9
Project Name: DJIBOUTI-LEVEL 2-26-03-18- 04/02/2018
Prepared by: a 10:25AM

Air System Information


Air System Name 03-L2- FCU-102-R9 Number of zones 1
Equipment Class CW AHU Floor Area 32.5 m²
Air System Type SZCAV Location Dubai, United Arab Emirates

Sizing Calculation Information


Calculation Months Jan to Dec Zone L/s Sizing Sum of space airflow rates
Sizing Data Calculated Space L/s Sizing Individual peak space loads

Zone Sizing Data

Maximum Maximum Zone


Cooling Design Minimum Heating Floor
Sensible Airflow Airflow Time of Load Area Zone
Zone Name (kW) (L/s) (L/s) Peak Load (kW) (m²) L/(s-m²)
Zone 1 2.9 241 241 Oct 1700 0.3 32.5 7.43

Zone Terminal Sizing Data


No Zone Terminal Sizing Data required for this system.

Space Loads and Airflows

Cooling Time Air Heating Floor


Zone Name / Sensible of Flow Load Area Space
Space Name Mult. (kW) Load (L/s) (kW) (m²) L/(s-m²)
Zone 1
03-L2-ROOM-09 1 2.9 Oct 1700 241 0.3 32.5 7.43

Hourly Analysis Program v4.90 Page 96 of 138


Air System Sizing Summary for 03-L2- FCU-103-HW3&EL2
Project Name: DJIBOUTI-LEVEL 2-26-03-18- 04/02/2018
Prepared by: a 10:25AM

Air System Information


Air System Name 03-L2- FCU-103-HW3&EL2 Number of zones 1
Equipment Class CW AHU Floor Area 74.8 m²
Air System Type SZCAV Location Dubai, United Arab Emirates

Sizing Calculation Information


Calculation Months Jan to Dec Zone L/s Sizing Sum of space airflow rates
Sizing Data Calculated Space L/s Sizing Individual peak space loads

Central Cooling Coil Sizing Data


Total coil load 11.0 kW Load occurs at Jul 1500
Sensible coil load 8.3 kW OA DB / WB 48.9 / 30.0 °C
Coil L/s at Jul 1500 663 L/s Entering DB / WB 25.3 / 19.2 °C
Max block L/s 663 L/s Leaving DB / WB 14.9 / 14.4 °C
Sum of peak zone L/s 663 L/s Coil ADP 13.8 °C
Sensible heat ratio 0.756 Bypass Factor 0.100
m²/kW 6.8 Resulting RH 58 %
W/m² 146.6 Design supply temp. 14.0 °C
Water flow @ 8.9 °K rise 0.29 L/s Zone T-stat Check 1 of 1 OK
Max zone temperature deviation 0.0 °K

Supply Fan Sizing Data


Actual max L/s 663 L/s Fan motor BHP 0.12 BHP
Standard L/s 662 L/s Fan motor kW 0.09 kW
Actual max L/(s-m²) 8.86 L/(s-m²) Fan static 75 Pa

Outdoor Ventilation Air Data


Design airflow L/s 0 L/s L/s/person 0.00 L/s/person
L/(s-m²) 0.00 L/(s-m²)

Hourly Analysis Program v4.90 Page 97 of 138


Zone Sizing Summary for 03-L2- FCU-103-HW3&EL2
Project Name: DJIBOUTI-LEVEL 2-26-03-18- 04/02/2018
Prepared by: a 10:25AM

Air System Information


Air System Name 03-L2- FCU-103-HW3&EL2 Number of zones 1
Equipment Class CW AHU Floor Area 74.8 m²
Air System Type SZCAV Location Dubai, United Arab Emirates

Sizing Calculation Information


Calculation Months Jan to Dec Zone L/s Sizing Sum of space airflow rates
Sizing Data Calculated Space L/s Sizing Individual peak space loads

Zone Sizing Data

Maximum Maximum Zone


Cooling Design Minimum Heating Floor
Sensible Airflow Airflow Time of Load Area Zone
Zone Name (kW) (L/s) (L/s) Peak Load (kW) (m²) L/(s-m²)
Zone 1 8.0 663 663 Jul 1500 0.1 74.8 8.86

Zone Terminal Sizing Data


No Zone Terminal Sizing Data required for this system.

Space Loads and Airflows

Cooling Time Air Heating Floor


Zone Name / Sensible of Flow Load Area Space
Space Name Mult. (kW) Load (L/s) (kW) (m²) L/(s-m²)
Zone 1
03-L2-HALL WAY-03 1 6.1 Jul 1500 507 0.1 70.3 7.21
03-L2-ELEC RM-02 1 1.9 Jul 1500 156 0.0 4.5 34.60

Hourly Analysis Program v4.90 Page 98 of 138


Air System Sizing Summary for 03-L2- FCU-103-HW6&EL3
Project Name: DJIBOUTI-LEVEL 2-26-03-18- 04/02/2018
Prepared by: a 10:25AM

Air System Information


Air System Name 03-L2- FCU-103-HW6&EL3 Number of zones 1
Equipment Class CW AHU Floor Area 67.9 m²
Air System Type SZCAV Location Dubai, United Arab Emirates

Sizing Calculation Information


Calculation Months Jan to Dec Zone L/s Sizing Sum of space airflow rates
Sizing Data Calculated Space L/s Sizing Individual peak space loads

Central Cooling Coil Sizing Data


Total coil load 10.2 kW Load occurs at Jul 1500
Sensible coil load 7.8 kW OA DB / WB 48.9 / 30.0 °C
Coil L/s at Jul 1500 612 L/s Entering DB / WB 25.2 / 19.0 °C
Max block L/s 612 L/s Leaving DB / WB 14.7 / 14.1 °C
Sum of peak zone L/s 612 L/s Coil ADP 13.5 °C
Sensible heat ratio 0.759 Bypass Factor 0.100
m²/kW 6.6 Resulting RH 58 %
W/m² 150.7 Design supply temp. 14.0 °C
Water flow @ 8.9 °K rise 0.28 L/s Zone T-stat Check 1 of 1 OK
Max zone temperature deviation 0.0 °K

Supply Fan Sizing Data


Actual max L/s 612 L/s Fan motor BHP 0.11 BHP
Standard L/s 611 L/s Fan motor kW 0.08 kW
Actual max L/(s-m²) 9.01 L/(s-m²) Fan static 75 Pa

Outdoor Ventilation Air Data


Design airflow L/s 0 L/s L/s/person 0.00 L/s/person
L/(s-m²) 0.00 L/(s-m²)

Hourly Analysis Program v4.90 Page 99 of 138


Zone Sizing Summary for 03-L2- FCU-103-HW6&EL3
Project Name: DJIBOUTI-LEVEL 2-26-03-18- 04/02/2018
Prepared by: a 10:25AM

Air System Information


Air System Name 03-L2- FCU-103-HW6&EL3 Number of zones 1
Equipment Class CW AHU Floor Area 67.9 m²
Air System Type SZCAV Location Dubai, United Arab Emirates

Sizing Calculation Information


Calculation Months Jan to Dec Zone L/s Sizing Sum of space airflow rates
Sizing Data Calculated Space L/s Sizing Individual peak space loads

Zone Sizing Data

Maximum Maximum Zone


Cooling Design Minimum Heating Floor
Sensible Airflow Airflow Time of Load Area Zone
Zone Name (kW) (L/s) (L/s) Peak Load (kW) (m²) L/(s-m²)
Zone 1 7.4 612 612 Jul 1500 0.1 67.9 9.01

Zone Terminal Sizing Data


No Zone Terminal Sizing Data required for this system.

Space Loads and Airflows

Cooling Time Air Heating Floor


Zone Name / Sensible of Flow Load Area Space
Space Name Mult. (kW) Load (L/s) (kW) (m²) L/(s-m²)
Zone 1
03-L2-HALL WAY-06 1 5.5 Jul 1500 458 0.1 63.4 7.23
03-L2-ELE.ROOM-03 1 1.9 Jul 1500 154 0.0 4.5 34.14

Hourly Analysis Program v4.90 Page 100 of 138


Air System Sizing Summary for 03-L2- FCU-104-SE1&SE2
Project Name: DJIBOUTI-LEVEL 2-26-03-18- 04/02/2018
Prepared by: a 10:25AM

Air System Information


Air System Name 03-L2- FCU-104-SE1&SE2 Number of zones 1
Equipment Class CW AHU Floor Area 43.6 m²
Air System Type SZCAV Location Dubai, United Arab Emirates

Sizing Calculation Information


Calculation Months Jan to Dec Zone L/s Sizing Sum of space airflow rates
Sizing Data Calculated Space L/s Sizing Individual peak space loads

Central Cooling Coil Sizing Data


Total coil load 15.5 kW Load occurs at Oct 1700
Sensible coil load 14.7 kW OA DB / WB 44.0 / 27.5 °C
Coil L/s at Oct 1700 1188 L/s Entering DB / WB 24.8 / 17.8 °C
Max block L/s 1188 L/s Leaving DB / WB 14.6 / 13.9 °C
Sum of peak zone L/s 1188 L/s Coil ADP 13.4 °C
Sensible heat ratio 0.944 Bypass Factor 0.100
m²/kW 2.8 Resulting RH 51 %
W/m² 356.1 Design supply temp. 14.0 °C
Water flow @ 8.9 °K rise 0.42 L/s Zone T-stat Check 1 of 1 OK
Max zone temperature deviation 0.0 °K

Supply Fan Sizing Data


Actual max L/s 1188 L/s Fan motor BHP 0.21 BHP
Standard L/s 1188 L/s Fan motor kW 0.17 kW
Actual max L/(s-m²) 27.26 L/(s-m²) Fan static 75 Pa

Outdoor Ventilation Air Data


Design airflow L/s 0 L/s L/s/person 0.00 L/s/person
L/(s-m²) 0.00 L/(s-m²)

Hourly Analysis Program v4.90 Page 101 of 138


Zone Sizing Summary for 03-L2- FCU-104-SE1&SE2
Project Name: DJIBOUTI-LEVEL 2-26-03-18- 04/02/2018
Prepared by: a 10:25AM

Air System Information


Air System Name 03-L2- FCU-104-SE1&SE2 Number of zones 1
Equipment Class CW AHU Floor Area 43.6 m²
Air System Type SZCAV Location Dubai, United Arab Emirates

Sizing Calculation Information


Calculation Months Jan to Dec Zone L/s Sizing Sum of space airflow rates
Sizing Data Calculated Space L/s Sizing Individual peak space loads

Zone Sizing Data

Maximum Maximum Zone


Cooling Design Minimum Heating Floor
Sensible Airflow Airflow Time of Load Area Zone
Zone Name (kW) (L/s) (L/s) Peak Load (kW) (m²) L/(s-m²)
Zone 1 14.2 1188 1188 Sep 1700 0.3 43.6 27.26

Zone Terminal Sizing Data


No Zone Terminal Sizing Data required for this system.

Space Loads and Airflows

Cooling Time Air Heating Floor


Zone Name / Sensible of Flow Load Area Space
Space Name Mult. (kW) Load (L/s) (kW) (m²) L/(s-m²)
Zone 1
03-L2-SERVICE-01 1 4.5 Jul 1500 374 0.0 13.9 26.89
03-L2-SERVICE-02 1 9.8 Oct 1700 815 0.3 29.7 27.43

Hourly Analysis Program v4.90 Page 102 of 138


Air System Sizing Summary for 03-L2- FCU-105-HW5
Project Name: DJIBOUTI-LEVEL 2-26-03-18- 04/02/2018
Prepared by: a 10:25AM

Air System Information


Air System Name 03-L2- FCU-105-HW5 Number of zones 1
Equipment Class CW AHU Floor Area 59.2 m²
Air System Type SZCAV Location Dubai, United Arab Emirates

Sizing Calculation Information


Calculation Months Jan to Dec Zone L/s Sizing Sum of space airflow rates
Sizing Data Calculated Space L/s Sizing Individual peak space loads

Central Cooling Coil Sizing Data


Total coil load 7.1 kW Load occurs at Jul 1600
Sensible coil load 5.1 kW OA DB / WB 48.6 / 29.9 °C
Coil L/s at Jul 1600 410 L/s Entering DB / WB 25.3 / 19.3 °C
Max block L/s 410 L/s Leaving DB / WB 14.9 / 14.4 °C
Sum of peak zone L/s 410 L/s Coil ADP 13.7 °C
Sensible heat ratio 0.721 Bypass Factor 0.100
m²/kW 8.3 Resulting RH 60 %
W/m² 120.3 Design supply temp. 14.0 °C
Water flow @ 8.9 °K rise 0.19 L/s Zone T-stat Check 1 of 1 OK
Max zone temperature deviation 0.0 °K

Supply Fan Sizing Data


Actual max L/s 410 L/s Fan motor BHP 0.07 BHP
Standard L/s 410 L/s Fan motor kW 0.06 kW
Actual max L/(s-m²) 6.93 L/(s-m²) Fan static 75 Pa

Outdoor Ventilation Air Data


Design airflow L/s 0 L/s L/s/person 0.00 L/s/person
L/(s-m²) 0.00 L/(s-m²)

Hourly Analysis Program v4.90 Page 103 of 138


Zone Sizing Summary for 03-L2- FCU-105-HW5
Project Name: DJIBOUTI-LEVEL 2-26-03-18- 04/02/2018
Prepared by: a 10:25AM

Air System Information


Air System Name 03-L2- FCU-105-HW5 Number of zones 1
Equipment Class CW AHU Floor Area 59.2 m²
Air System Type SZCAV Location Dubai, United Arab Emirates

Sizing Calculation Information


Calculation Months Jan to Dec Zone L/s Sizing Sum of space airflow rates
Sizing Data Calculated Space L/s Sizing Individual peak space loads

Zone Sizing Data

Maximum Maximum Zone


Cooling Design Minimum Heating Floor
Sensible Airflow Airflow Time of Load Area Zone
Zone Name (kW) (L/s) (L/s) Peak Load (kW) (m²) L/(s-m²)
Zone 1 5.0 410 410 Jul 1500 0.0 59.2 6.93

Zone Terminal Sizing Data


No Zone Terminal Sizing Data required for this system.

Space Loads and Airflows

Cooling Time Air Heating Floor


Zone Name / Sensible of Flow Load Area Space
Space Name Mult. (kW) Load (L/s) (kW) (m²) L/(s-m²)
Zone 1
03-L2-HALL WAY-05 1 5.0 Jul 1500 410 0.0 59.2 6.93

Hourly Analysis Program v4.90 Page 104 of 138


Air System Sizing Summary for 03-L2- FCU-106-RS1&KS1
Project Name: DJIBOUTI-LEVEL 2-26-03-18- 04/02/2018
Prepared by: a 10:25AM

Air System Information


Air System Name 03-L2- FCU-106-RS1&KS1 Number of zones 1
Equipment Class CW AHU Floor Area 31.2 m²
Air System Type SZCAV Location Dubai, United Arab Emirates

Sizing Calculation Information


Calculation Months Jan to Dec Zone L/s Sizing Sum of space airflow rates
Sizing Data Calculated Space L/s Sizing Individual peak space loads

Central Cooling Coil Sizing Data


Total coil load 3.0 kW Load occurs at Jun 1500
Sensible coil load 2.2 kW OA DB / WB 48.3 / 30.0 °C
Coil L/s at Jun 1500 174 L/s Entering DB / WB 25.4 / 19.2 °C
Max block L/s 174 L/s Leaving DB / WB 14.7 / 14.1 °C
Sum of peak zone L/s 174 L/s Coil ADP 13.5 °C
Sensible heat ratio 0.738 Bypass Factor 0.100
m²/kW 10.3 Resulting RH 59 %
W/m² 97.4 Design supply temp. 14.0 °C
Water flow @ 8.9 °K rise 0.08 L/s Zone T-stat Check 1 of 1 OK
Max zone temperature deviation 0.0 °K

Supply Fan Sizing Data


Actual max L/s 174 L/s Fan motor BHP 0.03 BHP
Standard L/s 174 L/s Fan motor kW 0.02 kW
Actual max L/(s-m²) 5.56 L/(s-m²) Fan static 75 Pa

Outdoor Ventilation Air Data


Design airflow L/s 0 L/s L/s/person 0.00 L/s/person
L/(s-m²) 0.00 L/(s-m²)

Hourly Analysis Program v4.90 Page 105 of 138


Zone Sizing Summary for 03-L2- FCU-106-RS1&KS1
Project Name: DJIBOUTI-LEVEL 2-26-03-18- 04/02/2018
Prepared by: a 10:25AM

Air System Information


Air System Name 03-L2- FCU-106-RS1&KS1 Number of zones 1
Equipment Class CW AHU Floor Area 31.2 m²
Air System Type SZCAV Location Dubai, United Arab Emirates

Sizing Calculation Information


Calculation Months Jan to Dec Zone L/s Sizing Sum of space airflow rates
Sizing Data Calculated Space L/s Sizing Individual peak space loads

Zone Sizing Data

Maximum Maximum Zone


Cooling Design Minimum Heating Floor
Sensible Airflow Airflow Time of Load Area Zone
Zone Name (kW) (L/s) (L/s) Peak Load (kW) (m²) L/(s-m²)
Zone 1 2.1 174 174 Jul 1500 0.0 31.2 5.56

Zone Terminal Sizing Data


No Zone Terminal Sizing Data required for this system.

Space Loads and Airflows

Cooling Time Air Heating Floor


Zone Name / Sensible of Flow Load Area Space
Space Name Mult. (kW) Load (L/s) (kW) (m²) L/(s-m²)
Zone 1
03-L2-KITCHEN-S1 1 0.9 Jul 1500 75 0.0 5.4 13.80
03-L2-ROOM-S1 1 1.2 Jul 1500 99 0.0 25.8 3.84

Hourly Analysis Program v4.90 Page 106 of 138


Air System Sizing Summary for 03-L2- FCU-107-HW4&TEL
Project Name: DJIBOUTI-LEVEL 2-26-03-18- 04/02/2018
Prepared by: a 10:25AM

Air System Information


Air System Name 03-L2- FCU-107-HW4&TEL Number of zones 1
Equipment Class CW AHU Floor Area 114.2 m²
Air System Type SZCAV Location Dubai, United Arab Emirates

Sizing Calculation Information


Calculation Months Jan to Dec Zone L/s Sizing Sum of space airflow rates
Sizing Data Calculated Space L/s Sizing Individual peak space loads

Central Cooling Coil Sizing Data


Total coil load 19.4 kW Load occurs at Aug 1500
Sensible coil load 15.6 kW OA DB / WB 48.9 / 30.0 °C
Coil L/s at Aug 1500 1273 L/s Entering DB / WB 25.3 / 19.0 °C
Max block L/s 1273 L/s Leaving DB / WB 15.2 / 14.6 °C
Sum of peak zone L/s 1273 L/s Coil ADP 14.1 °C
Sensible heat ratio 0.801 Bypass Factor 0.100
m²/kW 5.9 Resulting RH 57 %
W/m² 170.0 Design supply temp. 14.0 °C
Water flow @ 8.9 °K rise 0.52 L/s Zone T-stat Check 0 of 1 OK
Max zone temperature deviation 0.1 °K

Supply Fan Sizing Data


Actual max L/s 1273 L/s Fan motor BHP 0.22 BHP
Standard L/s 1272 L/s Fan motor kW 0.18 kW
Actual max L/(s-m²) 11.15 L/(s-m²) Fan static 75 Pa

Outdoor Ventilation Air Data


Design airflow L/s 0 L/s L/s/person 0.00 L/s/person
L/(s-m²) 0.00 L/(s-m²)

Hourly Analysis Program v4.90 Page 107 of 138


Zone Sizing Summary for 03-L2- FCU-107-HW4&TEL
Project Name: DJIBOUTI-LEVEL 2-26-03-18- 04/02/2018
Prepared by: a 10:25AM

Air System Information


Air System Name 03-L2- FCU-107-HW4&TEL Number of zones 1
Equipment Class CW AHU Floor Area 114.2 m²
Air System Type SZCAV Location Dubai, United Arab Emirates

Sizing Calculation Information


Calculation Months Jan to Dec Zone L/s Sizing Sum of space airflow rates
Sizing Data Calculated Space L/s Sizing Individual peak space loads

Zone Sizing Data

Maximum Maximum Zone


Cooling Design Minimum Heating Floor
Sensible Airflow Airflow Time of Load Area Zone
Zone Name (kW) (L/s) (L/s) Peak Load (kW) (m²) L/(s-m²)
Zone 1 15.4 1273 1273 Aug 1500 0.9 114.2 11.15

Zone Terminal Sizing Data


No Zone Terminal Sizing Data required for this system.

Space Loads and Airflows

Cooling Time Air Heating Floor


Zone Name / Sensible of Flow Load Area Space
Space Name Mult. (kW) Load (L/s) (kW) (m²) L/(s-m²)
Zone 1
03-L2-HALL WAY-04 1 11.7 Aug 1500 966 0.9 102.0 9.47
03-L2-TEL.ROOM 1 3.7 Jul 1500 308 0.0 12.2 25.21

Hourly Analysis Program v4.90 Page 108 of 138


Air System Sizing Summary for 03-L2- FCU-108-R2&KR2
Project Name: DJIBOUTI-LEVEL 2-26-03-18- 04/02/2018
Prepared by: a 10:25AM

Air System Information


Air System Name 03-L2- FCU-108-R2&KR2 Number of zones 1
Equipment Class CW AHU Floor Area 48.8 m²
Air System Type SZCAV Location Dubai, United Arab Emirates

Sizing Calculation Information


Calculation Months Jan to Dec Zone L/s Sizing Sum of space airflow rates
Sizing Data Calculated Space L/s Sizing Individual peak space loads

Central Cooling Coil Sizing Data


Total coil load 7.3 kW Load occurs at Aug 1500
Sensible coil load 5.8 kW OA DB / WB 48.9 / 30.0 °C
Coil L/s at Aug 1500 477 L/s Entering DB / WB 25.4 / 19.1 °C
Max block L/s 477 L/s Leaving DB / WB 15.2 / 14.6 °C
Sum of peak zone L/s 477 L/s Coil ADP 14.1 °C
Sensible heat ratio 0.796 Bypass Factor 0.100
m²/kW 6.7 Resulting RH 57 %
W/m² 150.3 Design supply temp. 14.0 °C
Water flow @ 8.9 °K rise 0.20 L/s Zone T-stat Check 0 of 1 OK
Max zone temperature deviation 0.0 °K

Supply Fan Sizing Data


Actual max L/s 477 L/s Fan motor BHP 0.08 BHP
Standard L/s 477 L/s Fan motor kW 0.07 kW
Actual max L/(s-m²) 9.77 L/(s-m²) Fan static 75 Pa

Outdoor Ventilation Air Data


Design airflow L/s 0 L/s L/s/person 0.00 L/s/person
L/(s-m²) 0.00 L/(s-m²)

Hourly Analysis Program v4.90 Page 109 of 138


Zone Sizing Summary for 03-L2- FCU-108-R2&KR2
Project Name: DJIBOUTI-LEVEL 2-26-03-18- 04/02/2018
Prepared by: a 10:25AM

Air System Information


Air System Name 03-L2- FCU-108-R2&KR2 Number of zones 1
Equipment Class CW AHU Floor Area 48.8 m²
Air System Type SZCAV Location Dubai, United Arab Emirates

Sizing Calculation Information


Calculation Months Jan to Dec Zone L/s Sizing Sum of space airflow rates
Sizing Data Calculated Space L/s Sizing Individual peak space loads

Zone Sizing Data

Maximum Maximum Zone


Cooling Design Minimum Heating Floor
Sensible Airflow Airflow Time of Load Area Zone
Zone Name (kW) (L/s) (L/s) Peak Load (kW) (m²) L/(s-m²)
Zone 1 5.8 477 477 Aug 1500 0.4 48.8 9.77

Zone Terminal Sizing Data


No Zone Terminal Sizing Data required for this system.

Space Loads and Airflows

Cooling Time Air Heating Floor


Zone Name / Sensible of Flow Load Area Space
Space Name Mult. (kW) Load (L/s) (kW) (m²) L/(s-m²)
Zone 1
03-L2-KITCHEN-R2 1 1.6 Jul 1500 136 0.0 9.0 15.17
03-L2-ROOM-02 1 4.1 Aug 1500 340 0.4 39.8 8.55

Hourly Analysis Program v4.90 Page 110 of 138


Air System Sizing Summary for 03-L2- FCU-108-R51&KR51
Project Name: DJIBOUTI-LEVEL 2-26-03-18- 04/02/2018
Prepared by: a 10:25AM

Air System Information


Air System Name 03-L2- FCU-108-R51&KR51 Number of zones 1
Equipment Class CW AHU Floor Area 46.0 m²
Air System Type SZCAV Location Dubai, United Arab Emirates

Sizing Calculation Information


Calculation Months Jan to Dec Zone L/s Sizing Sum of space airflow rates
Sizing Data Calculated Space L/s Sizing Individual peak space loads

Central Cooling Coil Sizing Data


Total coil load 7.5 kW Load occurs at Aug 1500
Sensible coil load 5.9 kW OA DB / WB 48.9 / 30.0 °C
Coil L/s at Aug 1500 486 L/s Entering DB / WB 25.4 / 19.1 °C
Max block L/s 486 L/s Leaving DB / WB 15.2 / 14.7 °C
Sum of peak zone L/s 486 L/s Coil ADP 14.1 °C
Sensible heat ratio 0.792 Bypass Factor 0.100
m²/kW 6.1 Resulting RH 57 %
W/m² 162.8 Design supply temp. 14.0 °C
Water flow @ 8.9 °K rise 0.20 L/s Zone T-stat Check 0 of 1 OK
Max zone temperature deviation 0.1 °K

Supply Fan Sizing Data


Actual max L/s 486 L/s Fan motor BHP 0.09 BHP
Standard L/s 486 L/s Fan motor kW 0.07 kW
Actual max L/(s-m²) 10.57 L/(s-m²) Fan static 75 Pa

Outdoor Ventilation Air Data


Design airflow L/s 0 L/s L/s/person 0.00 L/s/person
L/(s-m²) 0.00 L/(s-m²)

Hourly Analysis Program v4.90 Page 111 of 138


Zone Sizing Summary for 03-L2- FCU-108-R51&KR51
Project Name: DJIBOUTI-LEVEL 2-26-03-18- 04/02/2018
Prepared by: a 10:25AM

Air System Information


Air System Name 03-L2- FCU-108-R51&KR51 Number of zones 1
Equipment Class CW AHU Floor Area 46.0 m²
Air System Type SZCAV Location Dubai, United Arab Emirates

Sizing Calculation Information


Calculation Months Jan to Dec Zone L/s Sizing Sum of space airflow rates
Sizing Data Calculated Space L/s Sizing Individual peak space loads

Zone Sizing Data

Maximum Maximum Zone


Cooling Design Minimum Heating Floor
Sensible Airflow Airflow Time of Load Area Zone
Zone Name (kW) (L/s) (L/s) Peak Load (kW) (m²) L/(s-m²)
Zone 1 5.9 486 486 Aug 1500 0.4 46.0 10.57

Zone Terminal Sizing Data


No Zone Terminal Sizing Data required for this system.

Space Loads and Airflows

Cooling Time Air Heating Floor


Zone Name / Sensible of Flow Load Area Space
Space Name Mult. (kW) Load (L/s) (kW) (m²) L/(s-m²)
Zone 1
03-L2-KITCHEN R-51 1 2.3 Jul 1500 194 0.0 11.2 17.30
03-L2-ROOM-51 1 3.5 Sep 1500 293 0.4 34.8 8.41

Hourly Analysis Program v4.90 Page 112 of 138


Air System Sizing Summary for 03-L2- FCU-109-R1
Project Name: DJIBOUTI-LEVEL 2-26-03-18- 04/02/2018
Prepared by: a 10:25AM

Air System Information


Air System Name 03-L2- FCU-109-R1 Number of zones 1
Equipment Class CW AHU Floor Area 36.2 m²
Air System Type SZCAV Location Dubai, United Arab Emirates

Sizing Calculation Information


Calculation Months Jan to Dec Zone L/s Sizing Sum of space airflow rates
Sizing Data Calculated Space L/s Sizing Individual peak space loads

Central Cooling Coil Sizing Data


Total coil load 3.8 kW Load occurs at Aug 1600
Sensible coil load 3.3 kW OA DB / WB 48.6 / 29.9 °C
Coil L/s at Aug 1600 261 L/s Entering DB / WB 25.3 / 18.5 °C
Max block L/s 261 L/s Leaving DB / WB 14.9 / 14.2 °C
Sum of peak zone L/s 261 L/s Coil ADP 13.7 °C
Sensible heat ratio 0.870 Bypass Factor 0.100
m²/kW 9.6 Resulting RH 54 %
W/m² 104.2 Design supply temp. 14.0 °C
Water flow @ 8.9 °K rise 0.10 L/s Zone T-stat Check 1 of 1 OK
Max zone temperature deviation 0.0 °K

Supply Fan Sizing Data


Actual max L/s 261 L/s Fan motor BHP 0.05 BHP
Standard L/s 260 L/s Fan motor kW 0.04 kW
Actual max L/(s-m²) 7.20 L/(s-m²) Fan static 75 Pa

Outdoor Ventilation Air Data


Design airflow L/s 0 L/s L/s/person 0.00 L/s/person
L/(s-m²) 0.00 L/(s-m²)

Hourly Analysis Program v4.90 Page 113 of 138


Zone Sizing Summary for 03-L2- FCU-109-R1
Project Name: DJIBOUTI-LEVEL 2-26-03-18- 04/02/2018
Prepared by: a 10:25AM

Air System Information


Air System Name 03-L2- FCU-109-R1 Number of zones 1
Equipment Class CW AHU Floor Area 36.2 m²
Air System Type SZCAV Location Dubai, United Arab Emirates

Sizing Calculation Information


Calculation Months Jan to Dec Zone L/s Sizing Sum of space airflow rates
Sizing Data Calculated Space L/s Sizing Individual peak space loads

Zone Sizing Data

Maximum Maximum Zone


Cooling Design Minimum Heating Floor
Sensible Airflow Airflow Time of Load Area Zone
Zone Name (kW) (L/s) (L/s) Peak Load (kW) (m²) L/(s-m²)
Zone 1 3.1 261 261 Aug 1600 0.4 36.2 7.20

Zone Terminal Sizing Data


No Zone Terminal Sizing Data required for this system.

Space Loads and Airflows

Cooling Time Air Heating Floor


Zone Name / Sensible of Flow Load Area Space
Space Name Mult. (kW) Load (L/s) (kW) (m²) L/(s-m²)
Zone 1
03-L2-ROOM-01 1 3.1 Aug 1600 261 0.4 36.2 7.20

Hourly Analysis Program v4.90 Page 114 of 138


Air System Sizing Summary for 03-L2- FCU-110-HK
Project Name: DJIBOUTI-LEVEL 2-26-03-18- 04/02/2018
Prepared by: a 10:25AM

Air System Information


Air System Name 03-L2- FCU-110-HK Number of zones 1
Equipment Class CW AHU Floor Area 19.4 m²
Air System Type SZCAV Location Dubai, United Arab Emirates

Sizing Calculation Information


Calculation Months Jan to Dec Zone L/s Sizing Sum of space airflow rates
Sizing Data Calculated Space L/s Sizing Individual peak space loads

Central Cooling Coil Sizing Data


Total coil load 1.7 kW Load occurs at Jul 1600
Sensible coil load 1.5 kW OA DB / WB 48.6 / 29.9 °C
Coil L/s at Jul 1600 117 L/s Entering DB / WB 25.4 / 18.6 °C
Max block L/s 117 L/s Leaving DB / WB 15.0 / 14.4 °C
Sum of peak zone L/s 117 L/s Coil ADP 13.8 °C
Sensible heat ratio 0.858 Bypass Factor 0.100
m²/kW 11.4 Resulting RH 55 %
W/m² 88.0 Design supply temp. 14.0 °C
Water flow @ 8.9 °K rise 0.05 L/s Zone T-stat Check 1 of 1 OK
Max zone temperature deviation 0.0 °K

Supply Fan Sizing Data


Actual max L/s 117 L/s Fan motor BHP 0.02 BHP
Standard L/s 117 L/s Fan motor kW 0.02 kW
Actual max L/(s-m²) 6.02 L/(s-m²) Fan static 75 Pa

Outdoor Ventilation Air Data


Design airflow L/s 0 L/s L/s/person 0.00 L/s/person
L/(s-m²) 0.00 L/(s-m²)

Hourly Analysis Program v4.90 Page 115 of 138


Zone Sizing Summary for 03-L2- FCU-110-HK
Project Name: DJIBOUTI-LEVEL 2-26-03-18- 04/02/2018
Prepared by: a 10:25AM

Air System Information


Air System Name 03-L2- FCU-110-HK Number of zones 1
Equipment Class CW AHU Floor Area 19.4 m²
Air System Type SZCAV Location Dubai, United Arab Emirates

Sizing Calculation Information


Calculation Months Jan to Dec Zone L/s Sizing Sum of space airflow rates
Sizing Data Calculated Space L/s Sizing Individual peak space loads

Zone Sizing Data

Maximum Maximum Zone


Cooling Design Minimum Heating Floor
Sensible Airflow Airflow Time of Load Area Zone
Zone Name (kW) (L/s) (L/s) Peak Load (kW) (m²) L/(s-m²)
Zone 1 1.4 117 117 Jul 1500 0.0 19.4 6.02

Zone Terminal Sizing Data


No Zone Terminal Sizing Data required for this system.

Space Loads and Airflows

Cooling Time Air Heating Floor


Zone Name / Sensible of Flow Load Area Space
Space Name Mult. (kW) Load (L/s) (kW) (m²) L/(s-m²)
Zone 1
03-L2-HOUSE KEEPING 1 1.4 Jul 1500 117 0.0 19.4 6.02

Hourly Analysis Program v4.90 Page 116 of 138


Air System Sizing Summary for 03-L2- FCU-111-SU1
Project Name: DJIBOUTI-LEVEL 2-26-03-18- 04/02/2018
Prepared by: a 10:25AM

Air System Information


Air System Name 03-L2- FCU-111-SU1 Number of zones 1
Equipment Class CW AHU Floor Area 40.4 m²
Air System Type SZCAV Location Dubai, United Arab Emirates

Sizing Calculation Information


Calculation Months Jan to Dec Zone L/s Sizing Sum of space airflow rates
Sizing Data Calculated Space L/s Sizing Individual peak space loads

Central Cooling Coil Sizing Data


Total coil load 5.1 kW Load occurs at Jun 2200
Sensible coil load 4.5 kW OA DB / WB 41.7 / 28.6 °C
Coil L/s at Jun 2200 359 L/s Entering DB / WB 25.2 / 18.3 °C
Max block L/s 359 L/s Leaving DB / WB 14.7 / 14.1 °C
Sum of peak zone L/s 359 L/s Coil ADP 13.6 °C
Sensible heat ratio 0.887 Bypass Factor 0.100
m²/kW 7.9 Resulting RH 53 %
W/m² 126.1 Design supply temp. 14.0 °C
Water flow @ 8.9 °K rise 0.14 L/s Zone T-stat Check 1 of 1 OK
Max zone temperature deviation 0.0 °K

Supply Fan Sizing Data


Actual max L/s 359 L/s Fan motor BHP 0.06 BHP
Standard L/s 359 L/s Fan motor kW 0.05 kW
Actual max L/(s-m²) 8.88 L/(s-m²) Fan static 75 Pa

Outdoor Ventilation Air Data


Design airflow L/s 0 L/s L/s/person 0.00 L/s/person
L/(s-m²) 0.00 L/(s-m²)

Hourly Analysis Program v4.90 Page 117 of 138


Zone Sizing Summary for 03-L2- FCU-111-SU1
Project Name: DJIBOUTI-LEVEL 2-26-03-18- 04/02/2018
Prepared by: a 10:25AM

Air System Information


Air System Name 03-L2- FCU-111-SU1 Number of zones 1
Equipment Class CW AHU Floor Area 40.4 m²
Air System Type SZCAV Location Dubai, United Arab Emirates

Sizing Calculation Information


Calculation Months Jan to Dec Zone L/s Sizing Sum of space airflow rates
Sizing Data Calculated Space L/s Sizing Individual peak space loads

Zone Sizing Data

Maximum Maximum Zone


Cooling Design Minimum Heating Floor
Sensible Airflow Airflow Time of Load Area Zone
Zone Name (kW) (L/s) (L/s) Peak Load (kW) (m²) L/(s-m²)
Zone 1 4.3 359 359 Jun 2200 0.5 40.4 8.88

Zone Terminal Sizing Data


No Zone Terminal Sizing Data required for this system.

Space Loads and Airflows

Cooling Time Air Heating Floor


Zone Name / Sensible of Flow Load Area Space
Space Name Mult. (kW) Load (L/s) (kW) (m²) L/(s-m²)
Zone 1
03-L2-SUITE-01 1 4.3 Jun 2200 359 0.5 40.4 8.88

Hourly Analysis Program v4.90 Page 118 of 138


Air System Sizing Summary for 03-L2- FCU-112-SU2&KS2
Project Name: DJIBOUTI-LEVEL 2-26-03-18- 04/02/2018
Prepared by: a 10:25AM

Air System Information


Air System Name 03-L2- FCU-112-SU2&KS2 Number of zones 1
Equipment Class CW AHU Floor Area 59.8 m²
Air System Type SZCAV Location Dubai, United Arab Emirates

Sizing Calculation Information


Calculation Months Jan to Dec Zone L/s Sizing Sum of space airflow rates
Sizing Data Calculated Space L/s Sizing Individual peak space loads

Central Cooling Coil Sizing Data


Total coil load 7.0 kW Load occurs at Aug 1900
Sensible coil load 5.4 kW OA DB / WB 45.6 / 29.3 °C
Coil L/s at Aug 1900 425 L/s Entering DB / WB 25.3 / 19.0 °C
Max block L/s 425 L/s Leaving DB / WB 14.8 / 14.2 °C
Sum of peak zone L/s 425 L/s Coil ADP 13.6 °C
Sensible heat ratio 0.770 Bypass Factor 0.100
m²/kW 8.5 Resulting RH 57 %
W/m² 117.2 Design supply temp. 14.0 °C
Water flow @ 8.9 °K rise 0.19 L/s Zone T-stat Check 1 of 1 OK
Max zone temperature deviation 0.0 °K

Supply Fan Sizing Data


Actual max L/s 425 L/s Fan motor BHP 0.07 BHP
Standard L/s 425 L/s Fan motor kW 0.06 kW
Actual max L/(s-m²) 7.11 L/(s-m²) Fan static 75 Pa

Outdoor Ventilation Air Data


Design airflow L/s 0 L/s L/s/person 0.00 L/s/person
L/(s-m²) 0.00 L/(s-m²)

Hourly Analysis Program v4.90 Page 119 of 138


Zone Sizing Summary for 03-L2- FCU-112-SU2&KS2
Project Name: DJIBOUTI-LEVEL 2-26-03-18- 04/02/2018
Prepared by: a 10:25AM

Air System Information


Air System Name 03-L2- FCU-112-SU2&KS2 Number of zones 1
Equipment Class CW AHU Floor Area 59.8 m²
Air System Type SZCAV Location Dubai, United Arab Emirates

Sizing Calculation Information


Calculation Months Jan to Dec Zone L/s Sizing Sum of space airflow rates
Sizing Data Calculated Space L/s Sizing Individual peak space loads

Zone Sizing Data

Maximum Maximum Zone


Cooling Design Minimum Heating Floor
Sensible Airflow Airflow Time of Load Area Zone
Zone Name (kW) (L/s) (L/s) Peak Load (kW) (m²) L/(s-m²)
Zone 1 5.1 425 425 Aug 1900 0.2 59.8 7.11

Zone Terminal Sizing Data


No Zone Terminal Sizing Data required for this system.

Space Loads and Airflows

Cooling Time Air Heating Floor


Zone Name / Sensible of Flow Load Area Space
Space Name Mult. (kW) Load (L/s) (kW) (m²) L/(s-m²)
Zone 1
03-L2-KITCHEN-S2 1 2.0 Jul 1500 164 0.0 12.9 12.70
03-L2-SUITE-02 1 3.1 Aug 1900 261 0.2 46.9 5.57

Hourly Analysis Program v4.90 Page 120 of 138


Air System Sizing Summary for 03-L2- FCU-112-SU3&KS3
Project Name: DJIBOUTI-LEVEL 2-26-03-18- 04/02/2018
Prepared by: a 10:25AM

Air System Information


Air System Name 03-L2- FCU-112-SU3&KS3 Number of zones 1
Equipment Class CW AHU Floor Area 59.2 m²
Air System Type SZCAV Location Dubai, United Arab Emirates

Sizing Calculation Information


Calculation Months Jan to Dec Zone L/s Sizing Sum of space airflow rates
Sizing Data Calculated Space L/s Sizing Individual peak space loads

Central Cooling Coil Sizing Data


Total coil load 6.4 kW Load occurs at Jul 1600
Sensible coil load 4.8 kW OA DB / WB 48.6 / 29.9 °C
Coil L/s at Jul 1600 371 L/s Entering DB / WB 25.4 / 19.2 °C
Max block L/s 371 L/s Leaving DB / WB 14.7 / 14.2 °C
Sum of peak zone L/s 371 L/s Coil ADP 13.5 °C
Sensible heat ratio 0.744 Bypass Factor 0.100
m²/kW 9.2 Resulting RH 58 %
W/m² 108.3 Design supply temp. 14.0 °C
Water flow @ 8.9 °K rise 0.17 L/s Zone T-stat Check 1 of 1 OK
Max zone temperature deviation 0.0 °K

Supply Fan Sizing Data


Actual max L/s 371 L/s Fan motor BHP 0.06 BHP
Standard L/s 371 L/s Fan motor kW 0.05 kW
Actual max L/(s-m²) 6.26 L/(s-m²) Fan static 75 Pa

Outdoor Ventilation Air Data


Design airflow L/s 0 L/s L/s/person 0.00 L/s/person
L/(s-m²) 0.00 L/(s-m²)

Hourly Analysis Program v4.90 Page 121 of 138


Zone Sizing Summary for 03-L2- FCU-112-SU3&KS3
Project Name: DJIBOUTI-LEVEL 2-26-03-18- 04/02/2018
Prepared by: a 10:25AM

Air System Information


Air System Name 03-L2- FCU-112-SU3&KS3 Number of zones 1
Equipment Class CW AHU Floor Area 59.2 m²
Air System Type SZCAV Location Dubai, United Arab Emirates

Sizing Calculation Information


Calculation Months Jan to Dec Zone L/s Sizing Sum of space airflow rates
Sizing Data Calculated Space L/s Sizing Individual peak space loads

Zone Sizing Data

Maximum Maximum Zone


Cooling Design Minimum Heating Floor
Sensible Airflow Airflow Time of Load Area Zone
Zone Name (kW) (L/s) (L/s) Peak Load (kW) (m²) L/(s-m²)
Zone 1 4.4 371 371 Jul 1500 0.2 59.2 6.26

Zone Terminal Sizing Data


No Zone Terminal Sizing Data required for this system.

Space Loads and Airflows

Cooling Time Air Heating Floor


Zone Name / Sensible of Flow Load Area Space
Space Name Mult. (kW) Load (L/s) (kW) (m²) L/(s-m²)
Zone 1
03-L2-KITCHEN S-03 1 1.9 Jul 1500 156 0.0 13.5 11.53
03-L2-SUITE-03 1 2.6 Jun 2200 215 0.2 45.7 4.71

Hourly Analysis Program v4.90 Page 122 of 138


Air System Sizing Summary for 03-L2- FCU-113-R53
Project Name: DJIBOUTI-LEVEL 2-26-03-18- 04/02/2018
Prepared by: a 10:25AM

Air System Information


Air System Name 03-L2- FCU-113-R53 Number of zones 1
Equipment Class CW AHU Floor Area 34.3 m²
Air System Type SZCAV Location Dubai, United Arab Emirates

Sizing Calculation Information


Calculation Months Jan to Dec Zone L/s Sizing Sum of space airflow rates
Sizing Data Calculated Space L/s Sizing Individual peak space loads

Central Cooling Coil Sizing Data


Total coil load 3.9 kW Load occurs at Jun 2200
Sensible coil load 3.5 kW OA DB / WB 41.7 / 28.6 °C
Coil L/s at Jun 2200 282 L/s Entering DB / WB 25.4 / 18.6 °C
Max block L/s 282 L/s Leaving DB / WB 15.2 / 14.5 °C
Sum of peak zone L/s 282 L/s Coil ADP 14.0 °C
Sensible heat ratio 0.888 Bypass Factor 0.100
m²/kW 8.8 Resulting RH 54 %
W/m² 113.7 Design supply temp. 14.0 °C
Water flow @ 8.9 °K rise 0.10 L/s Zone T-stat Check 1 of 1 OK
Max zone temperature deviation 0.0 °K

Supply Fan Sizing Data


Actual max L/s 282 L/s Fan motor BHP 0.05 BHP
Standard L/s 281 L/s Fan motor kW 0.04 kW
Actual max L/(s-m²) 8.21 L/(s-m²) Fan static 75 Pa

Outdoor Ventilation Air Data


Design airflow L/s 0 L/s L/s/person 0.00 L/s/person
L/(s-m²) 0.00 L/(s-m²)

Hourly Analysis Program v4.90 Page 123 of 138


Zone Sizing Summary for 03-L2- FCU-113-R53
Project Name: DJIBOUTI-LEVEL 2-26-03-18- 04/02/2018
Prepared by: a 10:25AM

Air System Information


Air System Name 03-L2- FCU-113-R53 Number of zones 1
Equipment Class CW AHU Floor Area 34.3 m²
Air System Type SZCAV Location Dubai, United Arab Emirates

Sizing Calculation Information


Calculation Months Jan to Dec Zone L/s Sizing Sum of space airflow rates
Sizing Data Calculated Space L/s Sizing Individual peak space loads

Zone Sizing Data

Maximum Maximum Zone


Cooling Design Minimum Heating Floor
Sensible Airflow Airflow Time of Load Area Zone
Zone Name (kW) (L/s) (L/s) Peak Load (kW) (m²) L/(s-m²)
Zone 1 3.4 282 282 Jun 2200 0.4 34.3 8.21

Zone Terminal Sizing Data


No Zone Terminal Sizing Data required for this system.

Space Loads and Airflows

Cooling Time Air Heating Floor


Zone Name / Sensible of Flow Load Area Space
Space Name Mult. (kW) Load (L/s) (kW) (m²) L/(s-m²)
Zone 1
03-L2-ROOM-53 1 3.4 Jun 2200 282 0.4 34.3 8.21

Hourly Analysis Program v4.90 Page 124 of 138


Air System Sizing Summary for 03-L2- FCU-113-R54
Project Name: DJIBOUTI-LEVEL 2-26-03-18- 04/02/2018
Prepared by: a 10:25AM

Air System Information


Air System Name 03-L2- FCU-113-R54 Number of zones 1
Equipment Class CW AHU Floor Area 32.8 m²
Air System Type SZCAV Location Dubai, United Arab Emirates

Sizing Calculation Information


Calculation Months Jan to Dec Zone L/s Sizing Sum of space airflow rates
Sizing Data Calculated Space L/s Sizing Individual peak space loads

Central Cooling Coil Sizing Data


Total coil load 3.8 kW Load occurs at Jun 2200
Sensible coil load 3.4 kW OA DB / WB 41.7 / 28.6 °C
Coil L/s at Jun 2200 277 L/s Entering DB / WB 25.4 / 18.6 °C
Max block L/s 277 L/s Leaving DB / WB 15.2 / 14.6 °C
Sum of peak zone L/s 277 L/s Coil ADP 14.1 °C
Sensible heat ratio 0.889 Bypass Factor 0.100
m²/kW 8.6 Resulting RH 54 %
W/m² 116.4 Design supply temp. 14.0 °C
Water flow @ 8.9 °K rise 0.10 L/s Zone T-stat Check 1 of 1 OK
Max zone temperature deviation 0.0 °K

Supply Fan Sizing Data


Actual max L/s 277 L/s Fan motor BHP 0.05 BHP
Standard L/s 277 L/s Fan motor kW 0.04 kW
Actual max L/(s-m²) 8.44 L/(s-m²) Fan static 75 Pa

Outdoor Ventilation Air Data


Design airflow L/s 0 L/s L/s/person 0.00 L/s/person
L/(s-m²) 0.00 L/(s-m²)

Hourly Analysis Program v4.90 Page 125 of 138


Zone Sizing Summary for 03-L2- FCU-113-R54
Project Name: DJIBOUTI-LEVEL 2-26-03-18- 04/02/2018
Prepared by: a 10:25AM

Air System Information


Air System Name 03-L2- FCU-113-R54 Number of zones 1
Equipment Class CW AHU Floor Area 32.8 m²
Air System Type SZCAV Location Dubai, United Arab Emirates

Sizing Calculation Information


Calculation Months Jan to Dec Zone L/s Sizing Sum of space airflow rates
Sizing Data Calculated Space L/s Sizing Individual peak space loads

Zone Sizing Data

Maximum Maximum Zone


Cooling Design Minimum Heating Floor
Sensible Airflow Airflow Time of Load Area Zone
Zone Name (kW) (L/s) (L/s) Peak Load (kW) (m²) L/(s-m²)
Zone 1 3.3 277 277 Jun 2200 0.4 32.8 8.44

Zone Terminal Sizing Data


No Zone Terminal Sizing Data required for this system.

Space Loads and Airflows

Cooling Time Air Heating Floor


Zone Name / Sensible of Flow Load Area Space
Space Name Mult. (kW) Load (L/s) (kW) (m²) L/(s-m²)
Zone 1
03-L2-ROOM-54 1 3.3 Jun 2200 277 0.4 32.8 8.44

Hourly Analysis Program v4.90 Page 126 of 138


Air System Sizing Summary for 03-L2- FCU-114-SU4&KS4
Project Name: DJIBOUTI-LEVEL 2-26-03-18- 04/02/2018
Prepared by: a 10:25AM

Air System Information


Air System Name 03-L2- FCU-114-SU4&KS4 Number of zones 1
Equipment Class CW AHU Floor Area 81.5 m²
Air System Type SZCAV Location Dubai, United Arab Emirates

Sizing Calculation Information


Calculation Months Jan to Dec Zone L/s Sizing Sum of space airflow rates
Sizing Data Calculated Space L/s Sizing Individual peak space loads

Central Cooling Coil Sizing Data


Total coil load 10.1 kW Load occurs at Jun 2100
Sensible coil load 7.9 kW OA DB / WB 42.7 / 28.8 °C
Coil L/s at Jun 2100 637 L/s Entering DB / WB 25.3 / 19.0 °C
Max block L/s 637 L/s Leaving DB / WB 14.9 / 14.4 °C
Sum of peak zone L/s 637 L/s Coil ADP 13.8 °C
Sensible heat ratio 0.784 Bypass Factor 0.100
m²/kW 8.1 Resulting RH 57 %
W/m² 124.1 Design supply temp. 14.0 °C
Water flow @ 8.9 °K rise 0.27 L/s Zone T-stat Check 1 of 1 OK
Max zone temperature deviation 0.0 °K

Supply Fan Sizing Data


Actual max L/s 637 L/s Fan motor BHP 0.11 BHP
Standard L/s 637 L/s Fan motor kW 0.09 kW
Actual max L/(s-m²) 7.82 L/(s-m²) Fan static 75 Pa

Outdoor Ventilation Air Data


Design airflow L/s 0 L/s L/s/person 0.00 L/s/person
L/(s-m²) 0.00 L/(s-m²)

Hourly Analysis Program v4.90 Page 127 of 138


Zone Sizing Summary for 03-L2- FCU-114-SU4&KS4
Project Name: DJIBOUTI-LEVEL 2-26-03-18- 04/02/2018
Prepared by: a 10:25AM

Air System Information


Air System Name 03-L2- FCU-114-SU4&KS4 Number of zones 1
Equipment Class CW AHU Floor Area 81.5 m²
Air System Type SZCAV Location Dubai, United Arab Emirates

Sizing Calculation Information


Calculation Months Jan to Dec Zone L/s Sizing Sum of space airflow rates
Sizing Data Calculated Space L/s Sizing Individual peak space loads

Zone Sizing Data

Maximum Maximum Zone


Cooling Design Minimum Heating Floor
Sensible Airflow Airflow Time of Load Area Zone
Zone Name (kW) (L/s) (L/s) Peak Load (kW) (m²) L/(s-m²)
Zone 1 7.6 637 637 Jun 2200 0.5 81.5 7.82

Zone Terminal Sizing Data


No Zone Terminal Sizing Data required for this system.

Space Loads and Airflows

Cooling Time Air Heating Floor


Zone Name / Sensible of Flow Load Area Space
Space Name Mult. (kW) Load (L/s) (kW) (m²) L/(s-m²)
Zone 1
03-L2-KITCHEN S-04 1 2.6 Jul 1500 213 0.0 14.6 14.56
03-L2-SUITE -04 1 5.1 Jun 2200 425 0.5 66.9 6.35

Hourly Analysis Program v4.90 Page 128 of 138


Air System Sizing Summary for 03-L2- FCU-115-HW1
Project Name: DJIBOUTI-LEVEL 2-26-03-18- 04/02/2018
Prepared by: a 10:25AM

Air System Information


Air System Name 03-L2- FCU-115-HW1 Number of zones 1
Equipment Class CW AHU Floor Area 65.2 m²
Air System Type SZCAV Location Dubai, United Arab Emirates

Sizing Calculation Information


Calculation Months Jan to Dec Zone L/s Sizing Sum of space airflow rates
Sizing Data Calculated Space L/s Sizing Individual peak space loads

Central Cooling Coil Sizing Data


Total coil load 10.6 kW Load occurs at Aug 1500
Sensible coil load 8.4 kW OA DB / WB 48.9 / 30.0 °C
Coil L/s at Aug 1500 688 L/s Entering DB / WB 25.3 / 19.1 °C
Max block L/s 688 L/s Leaving DB / WB 15.2 / 14.6 °C
Sum of peak zone L/s 688 L/s Coil ADP 14.1 °C
Sensible heat ratio 0.790 Bypass Factor 0.100
m²/kW 6.1 Resulting RH 57 %
W/m² 162.7 Design supply temp. 14.0 °C
Water flow @ 8.9 °K rise 0.29 L/s Zone T-stat Check 0 of 1 OK
Max zone temperature deviation 0.0 °K

Supply Fan Sizing Data


Actual max L/s 688 L/s Fan motor BHP 0.12 BHP
Standard L/s 688 L/s Fan motor kW 0.10 kW
Actual max L/(s-m²) 10.56 L/(s-m²) Fan static 75 Pa

Outdoor Ventilation Air Data


Design airflow L/s 0 L/s L/s/person 0.00 L/s/person
L/(s-m²) 0.00 L/(s-m²)

Hourly Analysis Program v4.90 Page 129 of 138


Zone Sizing Summary for 03-L2- FCU-115-HW1
Project Name: DJIBOUTI-LEVEL 2-26-03-18- 04/02/2018
Prepared by: a 10:25AM

Air System Information


Air System Name 03-L2- FCU-115-HW1 Number of zones 1
Equipment Class CW AHU Floor Area 65.2 m²
Air System Type SZCAV Location Dubai, United Arab Emirates

Sizing Calculation Information


Calculation Months Jan to Dec Zone L/s Sizing Sum of space airflow rates
Sizing Data Calculated Space L/s Sizing Individual peak space loads

Zone Sizing Data

Maximum Maximum Zone


Cooling Design Minimum Heating Floor
Sensible Airflow Airflow Time of Load Area Zone
Zone Name (kW) (L/s) (L/s) Peak Load (kW) (m²) L/(s-m²)
Zone 1 8.3 688 688 Sep 1500 0.9 65.2 10.56

Zone Terminal Sizing Data


No Zone Terminal Sizing Data required for this system.

Space Loads and Airflows

Cooling Time Air Heating Floor


Zone Name / Sensible of Flow Load Area Space
Space Name Mult. (kW) Load (L/s) (kW) (m²) L/(s-m²)
Zone 1
03-L2-HALL WAY-01 1 8.3 Sep 1500 688 0.9 65.2 10.56

Hourly Analysis Program v4.90 Page 130 of 138


Air System Sizing Summary for 03-L2- FCU-116-LST1
Project Name: DJIBOUTI-LEVEL 2-26-03-18- 04/02/2018
Prepared by: a 10:25AM

Air System Information


Air System Name 03-L2- FCU-116-LST1 Number of zones 1
Equipment Class CW AHU Floor Area 19.4 m²
Air System Type SZCAV Location Dubai, United Arab Emirates

Sizing Calculation Information


Calculation Months Jan to Dec Zone L/s Sizing Sum of space airflow rates
Sizing Data Calculated Space L/s Sizing Individual peak space loads

Central Cooling Coil Sizing Data


Total coil load 1.5 kW Load occurs at Jul 1400
Sensible coil load 1.3 kW OA DB / WB 48.6 / 29.9 °C
Coil L/s at Jul 1400 105 L/s Entering DB / WB 25.2 / 18.6 °C
Max block L/s 105 L/s Leaving DB / WB 15.0 / 14.4 °C
Sum of peak zone L/s 105 L/s Coil ADP 13.9 °C
Sensible heat ratio 0.869 Bypass Factor 0.100
m²/kW 13.1 Resulting RH 55 %
W/m² 76.6 Design supply temp. 14.0 °C
Water flow @ 8.9 °K rise 0.04 L/s Zone T-stat Check 1 of 1 OK
Max zone temperature deviation 0.0 °K

Supply Fan Sizing Data


Actual max L/s 105 L/s Fan motor BHP 0.02 BHP
Standard L/s 105 L/s Fan motor kW 0.01 kW
Actual max L/(s-m²) 5.40 L/(s-m²) Fan static 75 Pa

Outdoor Ventilation Air Data


Design airflow L/s 0 L/s L/s/person 0.00 L/s/person
L/(s-m²) 0.00 L/(s-m²)

Hourly Analysis Program v4.90 Page 131 of 138


Zone Sizing Summary for 03-L2- FCU-116-LST1
Project Name: DJIBOUTI-LEVEL 2-26-03-18- 04/02/2018
Prepared by: a 10:25AM

Air System Information


Air System Name 03-L2- FCU-116-LST1 Number of zones 1
Equipment Class CW AHU Floor Area 19.4 m²
Air System Type SZCAV Location Dubai, United Arab Emirates

Sizing Calculation Information


Calculation Months Jan to Dec Zone L/s Sizing Sum of space airflow rates
Sizing Data Calculated Space L/s Sizing Individual peak space loads

Zone Sizing Data

Maximum Maximum Zone


Cooling Design Minimum Heating Floor
Sensible Airflow Airflow Time of Load Area Zone
Zone Name (kW) (L/s) (L/s) Peak Load (kW) (m²) L/(s-m²)
Zone 1 1.3 105 105 Jul 1500 0.0 19.4 5.40

Zone Terminal Sizing Data


No Zone Terminal Sizing Data required for this system.

Space Loads and Airflows

Cooling Time Air Heating Floor


Zone Name / Sensible of Flow Load Area Space
Space Name Mult. (kW) Load (L/s) (kW) (m²) L/(s-m²)
Zone 1
03-L2-LINEN STO-1 1 1.3 Jul 1500 105 0.0 19.4 5.40

Hourly Analysis Program v4.90 Page 132 of 138


Air System Sizing Summary for 03-L2- FCU-117-SE3&EL1
Project Name: DJIBOUTI-LEVEL 2-26-03-18- 04/02/2018
Prepared by: a 10:25AM

Air System Information


Air System Name 03-L2- FCU-117-SE3&EL1 Number of zones 1
Equipment Class CW AHU Floor Area 36.4 m²
Air System Type SZCAV Location Dubai, United Arab Emirates

Sizing Calculation Information


Calculation Months Jan to Dec Zone L/s Sizing Sum of space airflow rates
Sizing Data Calculated Space L/s Sizing Individual peak space loads

Central Cooling Coil Sizing Data


Total coil load 11.5 kW Load occurs at Jul 1500
Sensible coil load 10.6 kW OA DB / WB 48.9 / 30.0 °C
Coil L/s at Jul 1500 849 L/s Entering DB / WB 24.8 / 17.9 °C
Max block L/s 849 L/s Leaving DB / WB 14.5 / 13.8 °C
Sum of peak zone L/s 849 L/s Coil ADP 13.3 °C
Sensible heat ratio 0.921 Bypass Factor 0.100
m²/kW 3.2 Resulting RH 52 %
W/m² 316.0 Design supply temp. 14.0 °C
Water flow @ 8.9 °K rise 0.31 L/s Zone T-stat Check 1 of 1 OK
Max zone temperature deviation 0.0 °K

Supply Fan Sizing Data


Actual max L/s 849 L/s Fan motor BHP 0.15 BHP
Standard L/s 849 L/s Fan motor kW 0.12 kW
Actual max L/(s-m²) 23.34 L/(s-m²) Fan static 75 Pa

Outdoor Ventilation Air Data


Design airflow L/s 0 L/s L/s/person 0.00 L/s/person
L/(s-m²) 0.00 L/(s-m²)

Hourly Analysis Program v4.90 Page 133 of 138


Zone Sizing Summary for 03-L2- FCU-117-SE3&EL1
Project Name: DJIBOUTI-LEVEL 2-26-03-18- 04/02/2018
Prepared by: a 10:25AM

Air System Information


Air System Name 03-L2- FCU-117-SE3&EL1 Number of zones 1
Equipment Class CW AHU Floor Area 36.4 m²
Air System Type SZCAV Location Dubai, United Arab Emirates

Sizing Calculation Information


Calculation Months Jan to Dec Zone L/s Sizing Sum of space airflow rates
Sizing Data Calculated Space L/s Sizing Individual peak space loads

Zone Sizing Data

Maximum Maximum Zone


Cooling Design Minimum Heating Floor
Sensible Airflow Airflow Time of Load Area Zone
Zone Name (kW) (L/s) (L/s) Peak Load (kW) (m²) L/(s-m²)
Zone 1 10.2 849 849 Jul 1500 0.0 36.4 23.34

Zone Terminal Sizing Data


No Zone Terminal Sizing Data required for this system.

Space Loads and Airflows

Cooling Time Air Heating Floor


Zone Name / Sensible of Flow Load Area Space
Space Name Mult. (kW) Load (L/s) (kW) (m²) L/(s-m²)
Zone 1
03-L2-SERVICE-03 1 6.9 Jul 1500 569 0.0 24.9 22.83
03-L2-ELEC RM-01 1 3.4 Jul 1500 281 0.0 11.5 24.43

Hourly Analysis Program v4.90 Page 134 of 138


Air System Sizing Summary for 03-L2- FCU-118-HW2
Project Name: DJIBOUTI-LEVEL 2-26-03-18- 04/02/2018
Prepared by: a 10:25AM

Air System Information


Air System Name 03-L2- FCU-118-HW2 Number of zones 1
Equipment Class CW AHU Floor Area 69.5 m²
Air System Type SZCAV Location Dubai, United Arab Emirates

Sizing Calculation Information


Calculation Months Jan to Dec Zone L/s Sizing Sum of space airflow rates
Sizing Data Calculated Space L/s Sizing Individual peak space loads

Central Cooling Coil Sizing Data


Total coil load 7.4 kW Load occurs at Jul 1400
Sensible coil load 5.1 kW OA DB / WB 48.6 / 29.9 °C
Coil L/s at Jul 1400 400 L/s Entering DB / WB 25.4 / 19.6 °C
Max block L/s 400 L/s Leaving DB / WB 14.9 / 14.4 °C
Sum of peak zone L/s 400 L/s Coil ADP 13.7 °C
Sensible heat ratio 0.688 Bypass Factor 0.100
m²/kW 9.5 Resulting RH 62 %
W/m² 105.8 Design supply temp. 14.0 °C
Water flow @ 8.9 °K rise 0.20 L/s Zone T-stat Check 1 of 1 OK
Max zone temperature deviation 0.0 °K

Supply Fan Sizing Data


Actual max L/s 400 L/s Fan motor BHP 0.07 BHP
Standard L/s 400 L/s Fan motor kW 0.06 kW
Actual max L/(s-m²) 5.76 L/(s-m²) Fan static 75 Pa

Outdoor Ventilation Air Data


Design airflow L/s 0 L/s L/s/person 0.00 L/s/person
L/(s-m²) 0.00 L/(s-m²)

Hourly Analysis Program v4.90 Page 135 of 138


Zone Sizing Summary for 03-L2- FCU-118-HW2
Project Name: DJIBOUTI-LEVEL 2-26-03-18- 04/02/2018
Prepared by: a 10:25AM

Air System Information


Air System Name 03-L2- FCU-118-HW2 Number of zones 1
Equipment Class CW AHU Floor Area 69.5 m²
Air System Type SZCAV Location Dubai, United Arab Emirates

Sizing Calculation Information


Calculation Months Jan to Dec Zone L/s Sizing Sum of space airflow rates
Sizing Data Calculated Space L/s Sizing Individual peak space loads

Zone Sizing Data

Maximum Maximum Zone


Cooling Design Minimum Heating Floor
Sensible Airflow Airflow Time of Load Area Zone
Zone Name (kW) (L/s) (L/s) Peak Load (kW) (m²) L/(s-m²)
Zone 1 4.8 400 400 Jul 1500 0.0 69.5 5.76

Zone Terminal Sizing Data


No Zone Terminal Sizing Data required for this system.

Space Loads and Airflows

Cooling Time Air Heating Floor


Zone Name / Sensible of Flow Load Area Space
Space Name Mult. (kW) Load (L/s) (kW) (m²) L/(s-m²)
Zone 1
03-L2-HALL WAY-02 1 4.8 Jul 1500 400 0.0 69.5 5.76

Hourly Analysis Program v4.90 Page 136 of 138


Air System Sizing Summary for 03-L2- FCU-119-R52&KR52
Project Name: DJIBOUTI-LEVEL 2-26-03-18- 04/02/2018
Prepared by: a 10:25AM

Air System Information


Air System Name 03-L2- FCU-119-R52&KR52 Number of zones 1
Equipment Class CW AHU Floor Area 37.8 m²
Air System Type SZCAV Location Dubai, United Arab Emirates

Sizing Calculation Information


Calculation Months Jan to Dec Zone L/s Sizing Sum of space airflow rates
Sizing Data Calculated Space L/s Sizing Individual peak space loads

Central Cooling Coil Sizing Data


Total coil load 5.8 kW Load occurs at Aug 1600
Sensible coil load 4.5 kW OA DB / WB 48.6 / 29.9 °C
Coil L/s at Aug 1600 363 L/s Entering DB / WB 25.4 / 19.2 °C
Max block L/s 363 L/s Leaving DB / WB 15.2 / 14.6 °C
Sum of peak zone L/s 363 L/s Coil ADP 14.1 °C
Sensible heat ratio 0.772 Bypass Factor 0.100
m²/kW 6.5 Resulting RH 58 %
W/m² 152.8 Design supply temp. 14.0 °C
Water flow @ 8.9 °K rise 0.16 L/s Zone T-stat Check 0 of 1 OK
Max zone temperature deviation 0.0 °K

Supply Fan Sizing Data


Actual max L/s 363 L/s Fan motor BHP 0.06 BHP
Standard L/s 363 L/s Fan motor kW 0.05 kW
Actual max L/(s-m²) 9.61 L/(s-m²) Fan static 75 Pa

Outdoor Ventilation Air Data


Design airflow L/s 0 L/s L/s/person 0.00 L/s/person
L/(s-m²) 0.00 L/(s-m²)

Hourly Analysis Program v4.90 Page 137 of 138


Zone Sizing Summary for 03-L2- FCU-119-R52&KR52
Project Name: DJIBOUTI-LEVEL 2-26-03-18- 04/02/2018
Prepared by: a 10:25AM

Air System Information


Air System Name 03-L2- FCU-119-R52&KR52 Number of zones 1
Equipment Class CW AHU Floor Area 37.8 m²
Air System Type SZCAV Location Dubai, United Arab Emirates

Sizing Calculation Information


Calculation Months Jan to Dec Zone L/s Sizing Sum of space airflow rates
Sizing Data Calculated Space L/s Sizing Individual peak space loads

Zone Sizing Data

Maximum Maximum Zone


Cooling Design Minimum Heating Floor
Sensible Airflow Airflow Time of Load Area Zone
Zone Name (kW) (L/s) (L/s) Peak Load (kW) (m²) L/(s-m²)
Zone 1 4.4 363 363 Aug 1600 0.4 37.8 9.61

Zone Terminal Sizing Data


No Zone Terminal Sizing Data required for this system.

Space Loads and Airflows

Cooling Time Air Heating Floor


Zone Name / Sensible of Flow Load Area Space
Space Name Mult. (kW) Load (L/s) (kW) (m²) L/(s-m²)
Zone 1
03-L2-KITCHEN R-52 1 1.4 Jul 1500 114 0.0 7.4 15.43
03-L2-ROOM-52 1 3.0 Aug 1600 249 0.4 30.4 8.19

Hourly Analysis Program v4.90 Page 138 of 138