GUIDE

SPECIFICATIONS
EC Series 1/2-6 Ton R-410A

GENERAL
Units shall be performance certified to ISO standard 13256-1 for coaxial water-to-refrigerant heat exchanger shall be constructed
Water Loop Heat Pump, Ground Water Heat Pump and Ground of a convoluted copper (optional cupronickel) inner tube and steel
Loop Heat Pump applications. Units intended for use on ground outer tube with a designed refrigerant working pressure of 450
loop applications shall have an optional extended range package PSIG (3100 kPa) and designed water side working pressure of no
installed. Units shall be Underwriter Laboratories (UL and cUL) listed less than 400 PSIG (2750 kPa).
for safety on all models. Each unit shall be run tested at the factory.
Each unit shall be pallet mounted and stretch wrapped. The units EXTENDED RANGE PACKAGE
shall be manufactured in an ISO9001:2000 certified facility. An optional extended range package shall include a bi-flow
balanced port expansion valve metering device in place of capillary
The units shall be warranted by the manufacturer against defects tubes and insulated water to refrigerant heat exchanger.
in materials and workmanship for a period of one year on all parts,
and 5 years on the compressor. FAN MOTOR & ASSEMBLY
The fan shall be direct drive centrifugal forward curved type with
The units shall be designed to operate with entering fluid a dynamically balanced wheel. The housing and wheel shall be
temperatures between 50˚F (10˚C) and 100˚F (38˚C) in cooling and designed for quiet low velocity operation. The fan housing shall
between 50˚F (10˚C) and 80˚F (27˚C) in heating. With the optional be removable from the unit without disconnecting the supply air
factory installed extended range package units shall operate with ductwork for servicing of the fan motor. The fan motor shall be three
entering fluid temperatures between 50˚F (10˚C) and 110˚F (43.3˚C) speed PSC type for direct drive units and single speed for belt drive
in cooling and between 25˚F (-3.9˚C) and 80˚F (27˚C) in heating. units. The motor shall be permanently lubricated and have thermal
overload protection.
CASING & CABINET
The cabinet shall be fabricated from heavy-gauge steel finished with ELECTRICAL
Galvalume® plus, an aluminum-zinc alloy with a clear acrylic coating Controls and safety devices will be factory wired and mounted within
for additional corrosion protection. The interior shall be insulated the unit. Controls shall include fan relay, compressor contactor, 24V
with !” (12.7mm) thick, multi density, coated, glass fiber. All units transformer, reversing valve coil and solid state lockout controller
shall allow sufficient service access to replace the compressor (UPM) The UPM controller shall include the following features:
without unit removal. One blower and two compressor compartment Anti-short cycle time delay, random start, brown out/surge/power
access panels shall be removable with supply and return ductwork interruption protection, 120 second low pressure switch bypass
in place. A duct collar shall be provided on the supply air opening. timer, shutdown on high or low refrigerant pressure safety switch
A 2" (50.8mm) return air filter rack/duct collar with 1" (25.4mm) inputs, shutdown for the optional freezestat or high level condensate
thick filters shall be provided with each unit. The units shall have sensors, 24 VAC alarm output for remote fault indication, unit reset
an insulated divider panel between the air handling section and the at thermostat or disconnect, ability to defeat time delays for servicing
compressor section to minimize the transmission of compressor and automatic intelligent reset. The UPM shall automatically reset
noise, and to permit service testing without air bypass. Units shall after a safety shut down and restart the unit, if the cause of the shut
have a stainless steel condensate drain pan. down no longer exists, after the anti-short cycle and random start
timers expire. Should a fault re-occur within 60 minutes after reset,
Units shall have a floating base pan consisting of a !” (12 mm) then a permanent lockout will occur. A light emitting diode (LED)
thick high density rubber pad between the compressor/condenser shall annunciate the following alarms: high refrigerant pressure,
base plate and the unit base pan. low refrigerant pressure, low water temperature and a high level
of condensate in the drain pan (when equipped with the optional
REFRIGERATION CIRCUITS low water temperature and high level condensate sensors). The
Units shall utilize refrigerant R-410A. All units shall contain a sealed LED will display each fault condition as soon as the fault occurs.
refrigerant circuit including a hermetic compressor, capillary tube If a permanent lockout occurs, then the fault LED will display the
metering device with strainer or balance port expansion valve, type of fault until the unit is reset.
refrigerant drier, finned tube air-to-refrigerant heat exchanger, Safety devices include a low pressure cutout set a 40 PSIG (280
refrigerant reversing valve and service ports. Compressor shall kPa) for loss of charge protection (freezestat and/or high discharge
be high efficiency, designed for heat pump duty, internally spring gas temperature sensor is not acceptable) and a high pressure
isolated (if reciprocating type) for maximum sound attenuation cutout control set at 600 PSIG (4125 kPa).
and mounted on rubber vibration isolators. Compressor motors
shall be equipped with overload protection. Refrigerant reversing An optional energy management relay that allows unit control by
valves shall be pilot operated sliding piston type with replaceable an external source shall be factory installed. A terminal block with
encapsulated magnetic coils energized only during the cooling screw terminals shall be provided for control wiring.
cycle. The finned tube coil shall be constructed of lanced aluminum
fins not exceeding fourteen fins per inch bonded to rifled copper PIPING
tubes in a staggered pattern not less than three rows deep and Supply, return water and condensate drain connections shall be
have a 450 PSIG (3100 kPa) working pressure. Coils shall have brass female pipe thread fittings and mounted flush to cabinet
a baked polyester enamel coating for protection against most exterior with optional stainless steel, Braided hose kit with swivel
airbourn chemicals. The coil shall have aluminum end sheets. The connectors. ECSPECS.INDD REV: 4-09
FHP Manufacturing Co.
601 N.W. 65th Court
Fort Lauderdale, FL 33309
Phone: (954) 776-5471 EC Series Vertical Dimensions
Fax: (800) 776-5529
http://www.fhp-mfg.com

A B C D E F G H J K M N P Q Condenser Recommended
MODEL R/A Duct R/A Duct Filter Rack Water Replacement
Width Depth Height Flg Width Flg Height Height Connections Nominal Filter Size
EC007, 009 19.00 19.00 24.25 11.75 7.75 3.50 8.25 2.38 4.88 7.38 15.00 8.00 10.00 8.25 3/4" F.P.T. 10 X 16 X 1
EC012 19.00 19.00 24.25 11.75 7.75 3.50 9.75 2.38 4.88 7.38 15.00 8.00 10.00 5.00 3/4" F.P.T. 10 X 16 X 1
EC015 21.50 21.50 32.25 11.75 9.75 5.88 7.88 2.38 7.38 13.25 17.50 14.00 16.00 7.88 3/4" F.P.T. 16 X 20 X 1
EC018 21.50 21.50 32.25 16.25 13.75 1.75 5.62 2.38 7.38 13.25 17.50 14.00 16.00 5.62 3/4" F.P.T. 16 X 20 X 1
EC024 21.50 21.50 36.25 16.25 13.75 1.75 5.62 2.38 7.38 12.50 17.50 16.00 18.00 5.62 3/4" F.P.T. 18 X 20 X 1
EC030 21.50 21.50 39.25 16.25 13.75 1.75 5.62 2.38 7.38 12.50 17.50 18.00 20.00 5.62 3/4" F.P.T. 20 X 20 X 1
EC036 21.50 26.00 43.25 16.25 15.75 4.75 5.00 2.38 8.38 14.75 22.00 22.00 24.00 5.00 3/4" F.P.T. 24 X 24 X 1
EC041 21.50 21.50 39.25 16.25 13.75 1.75 5.62 2.38 8.38 14.75 17.50 18.00 20.00 5.62 3/4" F.P.T. 20 X 20 X 1
EC042 21.50 26.00 43.25 16.25 15.75 4.75 5.00 2.38 8.38 14.75 22.00 22.00 24.00 5.00 3/4" F.P.T. 24 X 24 X 1
EC048 24.00 32.50 45.25 17.75 17.75 7.38 5.12 2.63 8.38 14.75 28.00 22.00 24.00 5.12 1" F.P.T. 24 X 30 X 1
EC051 26.00 26.00 43.25 17.75 17.75 2.12 7.12 2.38 6.25 9.75 22.00 28.00 30.00 7.12 1" F.P.T. 24 X 30 X 1
EC060 24.00 32.50 45.25 17.75 17.75 7.38 5.12 3.00 9.63 16.63 28.00 22.00 24.00 5.12 1" F.P.T. 24 X 30 X 1
EC061 26.00 26.00 43.25 17.75 17.75 2.12 7.12 2.38 6.25 9.75 22.00 28.00 30.00 7.12 1" F.P.T. 24 X 30 X 1
EC070 26.00 33.25 58.25 17.75 17.75 9.50 6.50 3.38 8.38 17.38 28.00 30.00 32.00 6.50 1" F.P.T. 16X30X1 (2)

Left Hand
Return
(FLT)

NOTES: All dimensions within +/- 0.125".


Right Hand All condensate drain connections are 3/4" FPT.
Return EC051 and 061 only available in vertical configuration.
ECVTGDIP FLA.P65 REV: 03-05 (FRT) Specifications subject to change without notice.
FHP Manufacturing Co.
601 N.W. 65th Court
Fort Lauderdale, FL 33309
Phone: (954) 776-5471 EC Series Horizontal Dimensions
Fax: (800) 776-5529
http://www.fhp-mfg.com

A B C D E F G H J K M N P Q R T Condenser Recommended
MODEL R/A Duct Filter Rack R/A Duct Water Replacement
Width Depth Height Flg Width Height Flg Height Connections Nom. Filter Size
EC007, 009 19.00 31.00 13.25 2.00 15.00 14.00 2.38 7.38 2.25 11.75 1.25 7.75 2.25 1.88 10.00 8.00 3/4" F.P.T. 10 X 16 X 1
EC012 19.00 31.00 13.25 2.00 15.00 14.00 2.38 7.38 2.50 11.75 1.25 7.75 2.25 1.88 10.00 8.00 3/4" F.P.T. 10 X 16 X 1
EC015 21.50 43.00 17.00 2.00 17.50 23.50 2.38 13.25 4.00 11.75 1.25 9.75 2.25 1.88 16.00 14.00 3/4" F.P.T. 16 X 20 X 1
EC018 21.50 43.00 17.00 2.00 17.50 23.50 2.38 13.25 3.50 11.75 1.25 13.75 3.50 1.75 16.00 14.00 3/4" F.P.T. 16 X 20 X 1
EC024 21.50 43.00 19.00 2.00 17.50 23.50 2.38 12.50 3.25 11.75 3.25 13.75 3.25 1.75 18.00 16.00 3/4" F.P.T. 18 X 20 X 1
EC030 22.00 45.00 19.00 2.00 19.50 23.50 2.38 12.50 2.50 13.75 1.50 15.75 2.50 1.50 18.00 16.00 3/4" F.P.T. 18 X 20 X 1
EC036 22.00 54.50 19.00 2.00 29.00 23.50 2.38 14.75 2.50 13.75 1.50 15.75 2.50 1.50 18.00 16.00 3/4" F.P.T. 18 X 30 X 1
EC041 21.50 43.00 22.00 2.00 17.50 23.50 2.38 14.75 2.50 13.75 3.00 15.75 3.25 3.00 20.00 18.00 3/4" F.P.T. 20 X 20 X 1
EC042 22.00 54.50 19.00 2.00 29.00 23.50 2.38 14.75 2.50 13.75 1.50 15.75 2.50 1.50 18.00 16.00 3/4" F.P.T. 18 X 30 X 1
EC048 36.00 43.00 21.00 2.25 33.75 7.00 2.63 14.75 10.13 15.75 2.50 15.75 3.00 2.50 20.00 18.00 1" F.P.T. 18 X 20 X 1 (2)
EC060 36.00 43.00 21.00 2.25 33.75 7.00 3.00 16.63 10.13 15.75 1.50 17.75 3.25 1.50 20.00 18.00 1" F.P.T. 18 X 20 X 1 (2)
EC070 26.00 78.00 21.50 2.50 44.00 31.50 3.12 18.50 2.75 17.75 2.75 17.75 2.75 1.25 20.50 18.50 1" F.P.T. 18 X 20 X 1 (2)

Left Hand Return


(Note: Models EC048 & 060 Left Hand
Left Hand Return Left Hand Return
Return units have condenser water
End Blow (FLE) Straight Through (FLS)
connections on the front right and elec-
trical knockouts on the front left.)

Right Hand Return

Right Hand Return


Straight Through (FRS)
Right Hand Return
NOTES: All dimensions within +/- 0.125". All condensate drain connections are 3/4" FPT.
End Blow (FRE)
Specifications subject to change without notice. EC015-070 can be field
ECHZDGIP.P65 c FHP Manufacturing Company REV:05-09 converted between end blow and straight through supply air configurations
FHP Manufacturing Co.
601 N.W. 65th Court
Fort Lauderdale, FL 33309
Phone: (954) 776-5471 EC Series Counterflow Dimensions
Fax: (800) 776-5529
http://www.fhp-mfg.com

A B C D E F G H J K M N P Condenser Recommended
MODEL Blower Blower R/A Duct R/A Duct Filter Rack Water Replacement
Width Depth Height Opening Opening Flg Width Flg Height Height Connections Nominal Filter Size
EC007, 009 19.00 19.00 24.25 6.25 4.25 6.00 10.25 5.00 10.00 10.25 15.00 8.00 10.00 3/4" F.P.T. 10 X 16 X 1
EC012 19.00 19.00 24.25 5.25 4.00 7.00 12.38 5.00 10.00 7.75 15.00 8.00 10.00 3/4" F.P.T. 10 X 16 X 1
EC015 21.50 21.50 32.25 6.25 4.25 6.50 12.00 5.88 16.75 12.00 17.50 14.00 16.00 3/4" F.P.T. 16 X 20 X 1
EC018 21.50 21.50 32.25 9.63 9.25 8.13 8.00 5.88 16.75 8.00 17.50 14.00 16.00 3/4" F.P.T. 16 X 20 X 1
EC024 21.50 21.50 36.25 9.63 9.25 8.13 8.00 5.88 16.00 8.00 17.50 16.00 18.00 3/4" F.P.T. 18 X 20 X 1
EC030 21.50 21.50 39.25 9.63 9.25 8.13 8.00 5.88 16.00 8.00 17.50 18.00 20.00 3/4" F.P.T. 20 X 20 X 1
EC036 21.50 26.00 43.25 10.25 9.25 10.00 8.75 4.38 16.75 8.75 22.00 22.00 24.00 3/4" F.P.T. 24 X 24 X 1
EC041 21.50 21.50 39.25 10.25 9.25 7.25 7.75 4.38 16.75 7.75 17.50 18.00 20.00 3/4" F.P.T. 20 X 20 X 1
EC042 21.50 26.00 43.25 10.25 9.25 10.00 8.75 4.38 16.75 8.75 22.00 22.00 24.00 3/4" F.P.T. 24 X 24 X 1
EC048 24.00 32.50 45.25 11.75 10.75 9.25 9.00 6.00 18.25 9.00 28.00 22.00 24.00 1" F.P.T. 24 X 30 X 1
EC060 24.00 32.50 45.25 12.50 12.00 9.00 8.00 4.25 17.75 8.00 28.00 22.00 24.00 1" F.P.T. 24 X 30 X 1
EC070 26.00 33.25 58.25 12.00 12.50 10.63 9.00 3.00 18.50 9.00 28.00 30.00 32.00 1" F.P.T. 16 X 30 X 1 (2)

Left Hand Right Hand


Return Return
(FLB) (FRB)

NOTES: All dimensions within +/- 0.125".


All condensate drain connections are 3/4" FPT.
ECCFDGIP.P65 REV: 09-06 Specifications subject to change without notice.
EC007
PACKAGED UNITS
SPECIFICATION DATA SHEET
FHP MANUFACTURING HIGH-EFFICIENCY WATER SOURCE HEAT PUMPS AQUARIUS SERIES
ELECTRICAL SPECIFICATIONS MECHANICAL SPECIFICATIONS
Electrical Elect. Compressor Blower Loop Pump Min. Max. Refrigerant: R-410A
Characteristics Symbol Circuit Fuse/ Air Coil
RLA LRA FLA HP FLA HP Amps Breaker Square Rows Tube Fins/
115-1-60 -0 6.6 29.8 2.2 1/10 - - 10.5 15 Feet Deep O.D. Inch
208/230-1-60 -1 3.1 15.9 1.0 1/10 - - 4.8 15 0.90 3 3/8 14
Water Coil
Type Work Press
Coaxial 450 psig
BLOWER PERFORMANCE Blower Size Compr Type
4x6 DD Rotary
Available External Static Pressure (Inches of Water, Gauge. Wet Coil and Filter Included)
Net Weight Ship Weight
Blower
0.10 0.20 0.30 0.40 0.50 0.60 0.70 0.80 0.90 1.00 1.10 1.20 118 lbs 127 lbs
Speed
High 410 380 350 315 280 210 - - - - - - FLUID PRESSURE DROP
Medium 390 360 330 300 260 - - - - - - - Fluid Pressure
Low 370 340 295 250 - - - - - - - - Flow Drop
(GPM) (FOH) (PSIG)
ISO 13256-1 CERTIFIED PERFORMANCE DATA Rated at 300 CFM and 2.0 GPM 1.0 1.7 0.7
Water Loop Ground Water Ground Loop (Ext. Range Required) 1.5 3.5 1.5
Cooling Heating Cooling Heating Cooling Heating 2.0 5.9 2.5
Capacity EER Capacity COP Capacity EER Capacity COP Capacity EER Capacity COP 2.5 8.8 3.8
6,200 12.5 8,000 5.1 7,200 20.0 6,000 4.0 6,500 15.0 4,500 3.2 3.0 12.2 5.3

CAPACITY DATA All performance at 300 CFM and 2.0 GPM


EFT Range (Standard) EFT Range (Ext. Range Option) EFT Range (Standard) EFT Range (Ext. Range Option)
COOLING 50oF to 100oF 45oF to 110oF HEATING 50oF to 80oF 25oF to 80oF

Entering Entering Sensible Heat Entering Entering Heat


Fluid Air Total Sensible to Power of Fluid Air Total Power of
Temp. Temp. Capacity Capacity Total Input Reject EER Temp. Temp. Capacity Input Abs. COP
(oF) (oF) (MBtuH) (MBtuH) Ratio (kW) (MBtuH) (oF) (oF) (MBtuH) (kW) (MBtuH)
50o 6.30 4.13 0.66 0.35 7.51 17.8 50o 6.66 0.48 5.03 4.1
60o 70odb 5.99 3.96 0.66 0.40 7.36 14.9 60o 7.65 0.49 5.98 4.6
60o
70o 61owb 5.68 3.80 0.67 0.45 7.21 12.6 70o 8.64 0.50 6.92 5.0
85o 5.21 3.58 0.69 0.52 6.99 10.0 80o 9.63 0.52 7.87 5.5
100o 4.74 3.37 0.71 0.60 6.77 8.0 50o 6.30 0.48 4.64 3.8
50o 6.76 4.96 0.73 0.36 7.97 19.0 60o 7.23 0.50 5.53 4.3
70o
60o 75odb 6.42 4.75 0.74 0.40 7.80 15.9 70o 8.17 0.51 6.42 4.7
70o 63owb 6.09 4.56 0.75 0.45 7.63 13.5 80o 9.10 0.52 7.31 5.1
85o 5.59 4.30 0.77 0.53 7.38 10.6 50o 5.88 0.49 4.19 3.5
100o 5.09 4.05 0.80 0.60 7.13 8.5 60o 6.75 0.51 5.01 3.9
80o
50o 7.42 5.48 0.74 0.36 8.65 20.7 70o 7.62 0.52 5.84 4.3
60o 80odb 7.06 5.26 0.74 0.41 8.45 17.3 80o 8.49 0.54 6.66 4.6
70o 67owb 6.69 5.05 0.75 0.46 8.25 14.7 Extended Range Option Required
85o 6.14 4.75 0.77 0.53 7.95 11.6 LOW TEMP HEATING Antifreeze Required

100o 5.60 4.48 0.80 0.60 7.65 9.3 25o 4.10 0.44 2.58 2.7
50o 8.09 6.01 0.74 0.36 9.32 22.5 30o 60o 4.59 0.45 3.05 3.0
60o 85odb 7.69 5.76 0.75 0.41 9.09 18.8 40o 5.56 0.46 3.97 3.5
70o 71owb 7.30 5.53 0.76 0.46 8.86 15.9 25o 3.88 0.45 2.34 2.5
85o 6.70 5.22 0.78 0.53 8.52 12.6 30o 70o 4.34 0.46 2.78 2.8
100o 6.10 4.92 0.81 0.61 8.18 10.0 40o 5.26 0.47 3.65 3.3
Units are complete packages containing compressor, reversing valve, capillary tube metering device, and heat exchangers. 25o 3.63 0.46 2.06 2.3
Also included are safety controls: Overload protection for motors, high and low refrigerant pressure switches and a lock-out
circuit. 30o 80o 4.06 0.47 2.46 2.5
Extended range option includes expansion valve metering device, insulated water coil and solid state lock-out controls. 40o 4.91 0.48 3.27 3.0
Performance based on ARI/ISO rated air flow, fluid flow and voltage. For conditions other than rated, consult the FHP EAD
selection software. Due to variations in installation actual performance may vary marginally from tabulated values. FHP MANUFACTURING COMPANY
As a result of continuing research and development, specifications are subject to change without notice. 601 N.W. 65th Court - Fort Lauderdale, FL 33309
EC007ip6 mod1 Rev: 06-09 Phone: (954) 776-5471 - Fax: (800) 776-5529
http://www.fhp-mfg.com
EC009
PACKAGED UNITS
SPECIFICATION DATA SHEET
FHP MANUFACTURING HIGH-EFFICIENCY WATER SOURCE HEAT PUMPS AQUARIUS SERIES
ELECTRICAL SPECIFICATIONS MECHANICAL SPECIFICATIONS
Electrical Elect. Compressor Blower Loop Pump Min. Max. Refrigerant: R-410A
Characteristics Symbol Circuit Fuse/ Air Coil
RLA LRA FLA HP FLA HP Amps Breaker Square Rows Tube Fins/
115-1-60 -0 8.3 40.0 2.2 1/10 - - 12.6 20 Feet Deep O.D. Inch
208/230-1-60 -1 3.7 22.0 1.0 1/10 - - 5.7 15 0.90 3 3/8 14
265-1-60 -2 3.3 16.0 0.9 1/10 - - 5.0 15 Water Coil
Type Work Press
Coaxial 450 psig
BLOWER PERFORMANCE Blower Size Compr Type
4x6 DD Rotary
Available External Static Pressure (Inches of Water, Gauge. Wet Coil and Filter Included)
Net Weight Ship Weight
Blower
0.10 0.20 0.30 0.40 0.50 0.60 0.70 0.80 0.90 1.00 1.10 1.20 120 lbs 129 lbs
Speed
High 410 380 350 315 280 210 - - - - - - FLUID PRESSURE DROP
Medium 390 360 330 300 260 - - - - - - - Fluid Pressure
Low 370 340 295 250 - - - - - - - - Flow Drop
(GPM) (FOH) (PSIG)
ISO 13256-1 CERTIFIED PERFORMANCE DATA Rated at 350 CFM and 2.5 GPM 1.0 1.4 0.6
Water Loop Ground Water Ground Loop (Ext. Range Required) 1.5 2.9 1.3
Cooling Heating Cooling Heating Cooling Heating 2.0 4.9 2.1
Capacity EER Capacity COP Capacity EER Capacity COP Capacity EER Capacity COP 2.5 7.3 3.2
7,800 13.7 11,400 4.7 9,000 20.0 8,600 3.8 8,100 14.8 6,400 3.2 3.0 10.2 4.4

CAPACITY DATA All performance at 350 CFM and 2.5 GPM


EFT Range (Standard) EFT Range (Ext. Range Option) EFT Range (Standard) EFT Range (Ext. Range Option)
COOLING 50oF to 100oF 45oF to 110oF HEATING 50oF to 80oF 25oF to 80oF
Entering Entering Sensible Heat Entering Entering Heat
Fluid Air Total Sensible to Power of Fluid Air Total Power of
Temp. Temp. Capacity Capacity Total Input Reject EER Temp. Temp. Capacity Input Abs. COP
(oF) (oF) (MBtuH) (MBtuH) Ratio (kW) (MBtuH) (oF) (oF) (MBtuH) (kW) (MBtuH)
50o 7.88 5.22 0.66 0.43 9.35 18.3 50 o 9.32 0.66 7.06 4.1
60o 70odb 7.52 5.02 0.67 0.48 9.14 15.8 60o 10.71 0.70 8.34 4.5
60o
70o 61owb 7.15 4.84 0.68 0.52 8.94 13.7 70o 12.10 0.73 9.61 4.9
85o 6.60 4.58 0.69 0.59 8.62 11.1 80o 13.49 0.76 10.89 5.2
100o 6.05 4.35 0.72 0.66 8.31 9.1 50o 8.81 0.67 6.51 3.8
50o 8.45 6.25 0.74 0.43 9.92 19.5 60o 10.13 0.71 7.71 4.2
70o
60o 75odb 8.05 6.01 0.75 0.48 9.69 16.8 70o 11.44 0.74 8.91 4.5
70o 63owb 7.66 5.79 0.76 0.53 9.46 14.6 80o 12.76 0.78 10.10 4.8
85o 7.07 5.48 0.78 0.60 9.11 11.9 50o 8.22 0.69 5.87 3.5
100o 6.48 5.20 0.80 0.67 8.76 9.7 60o 9.44 0.72 6.97 3.8
80o
50o 9.27 6.90 0.74 0.44 10.76 21.3 70o 10.67 0.76 8.07 4.1
60o 80odb 8.84 6.64 0.75 0.48 10.49 18.3 80o 11.89 0.79 9.18 4.4
70o 67owb 8.41 6.39 0.76 0.53 10.22 15.9
Extended Range Option Required
85o 7.77 6.06 0.78 0.60 9.82 12.9 LOW TEMP HEATING Antifreeze Required
100o 7.12 5.75 0.81 0.67 9.41 10.6 25o 5.72 0.58 3.75 2.9
50o 10.10 7.56 0.75 0.44 11.60 23.0 30o 60o 6.41 0.59 4.38 3.2
60o 85odb 9.63 7.27 0.75 0.49 11.29 19.8 40o 7.77 0.63 5.63 3.6
70o 71owb 9.16 7.00 0.76 0.53 10.99 17.1 25o 5.42 0.59 3.41 2.7
85o 8.46 6.64 0.78 0.61 10.53 14.0 30o 70o 6.06 0.60 4.00 2.9
100o 7.76 6.30 0.81 0.68 10.07 11.5 40o 7.35 0.64 5.17 3.4
Units are complete packages containing compressor, reversing valve, capillary tube metering device, and heat exchangers. 25o 5.05 0.60 3.00 2.5
Also included are safety controls: Overload protection for motors, high and low refrigerant pressure switches and a lock-out
circuit. 30o 80o 5.65 0.62 3.54 2.7
Extended range option includes expansion valve metering device, insulated water coil and solid state lock-out controls. 40o 6.85 0.65 4.62 3.1
Performance based on ARI/ISO rated air flow, fluid flow and voltage. For conditions other than rated, consult the FHP EAD
selection software. Due to variations in installation actual performance may vary marginally from tabulated values. FHP MANUFACTURING COMPANY
As a result of continuing research and development, specifications are subject to change without notice. 601 N.W. 65th Court - Fort Lauderdale, FL 33309
E C009ip6 mod1 Rev: 05-09 Phone: (954) 776-5471 - Fax: (800) 776-5529
http://www.fhp-mfg.com
EC012
PACKAGED UNITS
SPECIFICATION DATA SHEET
FHP MANUFACTURING HIGH-EFFICIENCY WATER SOURCE HEAT PUMPS AQUARIUS SERIES
ELECTRICAL SPECIFICATIONS MECHANICAL SPECIFICATIONS
Electrical Elect. Compressor Blower Loop Pump Min. Max. Refrigerant: R-410A
Characteristics Symbol Circuit Fuse/ Air Coil
RLA LRA FLA HP FLA HP Amps Breaker Square Rows Tube Fins/
115-1-60 -0 8.3 40.0 2.2 1/10 - - 12.6 20 Feet Deep O.D. Inch
208/230-1-60 -1 4.0 20.0 1.0 1/10 - - 6.0 15 0.97 3 3/8 14
265-1-60 -2 3.3 16.0 0.9 1/10 - - 5.0 15 Water Coil
Type Work Press
Coaxial 450 psig
BLOWER PERFORMANCE Blower Size Compr Type
4x7 DD Rotary
Available External Static Pressure (Inches of Water, Gauge. Wet Coil and Filter Included)
Net Weight Ship Weight
Blower
0.10 0.20 0.30 0.40 0.50 0.60 0.70 0.80 0.90 1.00 1.10 1.20 129 lbs 140 lbs
Speed
High 425 410 390 371 350 325 300 - - - - - FLUID PRESSURE DROP
Medium 410 395 375 355 330 305 - - - - - - Fluid Pressure
Low 385 370 350 330 305 - - - - - - - Flow Drop
(GPM) (FOH) (PSIG)
ISO 13256-1 CERTIFIED PERFORMANCE DATA Rated at 400 CFM and 3.0 GPM 1.5 3.2 1.4
Water Loop Ground Water Ground Loop (Ext. Range Required) 2.0 5.3 2.3
Cooling Heating Cooling Heating Cooling Heating 2.5 7.9 3.4
Capacity EER Capacity COP Capacity EER Capacity COP Capacity EER Capacity COP 3.0 11.0 4.8
11,000 13.0 14,500 4.5 12,400 19.0 11,500 3.6 11,500 14.5 8,700 3.1 3.5 14.5 6.3

CAPACITY DATA All performance at 400 CFM and 3.0 GPM


EFT Range (Standard) EFT Range (Ext. Range Option) EFT Range (Standard) EFT Range (Ext. Range Option)
COOLING 50oF to 100oF 45oF to 110oF HEATING 50oF to 80oF 25oF to 80oF
Entering Entering Sensible Heat Entering Entering Heat
Fluid Air Total Sensible to Power of Fluid Air Total Power of
Temp. Temp. Capacity Capacity Total Input Reject EER Temp. Temp. Capacity Input Abs. COP
(oF) (oF) (MBtuH) (MBtuH) Ratio (kW) (MBtuH) (oF) (oF) (MBtuH) (kW) (MBtuH)
50o 10.93 7.14 0.65 0.60 12.97 18.3 50o 12.22 0.90 9.16 4.0
60o 70 dbo
10.48 6.91 0.66 0.67 12.77 15.7 60o 13.91 0.94 10.71 4.4
60o
70o 61owb 10.04 6.70 0.67 0.74 12.56 13.6 70o 15.59 0.97 12.27 4.7
85o 9.38 6.42 0.68 0.84 12.26 11.1 80o 17.28 1.01 13.82 5.0
100o 8.71 6.17 0.71 0.95 11.96 9.2 50o 11.56 0.92 8.43 3.7
50o 11.71 8.53 0.73 0.60 13.76 19.5 60o 13.15 0.95 9.89 4.0
70o
60o 75odb 11.23 8.25 0.73 0.67 13.53 16.7 70o 14.74 0.99 11.35 4.4
70o 63owb 10.76 8.00 0.74 0.74 13.29 14.5 80o 16.33 1.03 12.81 4.6
85o 10.05 7.67 0.76 0.85 12.95 11.8 50o 10.77 0.94 7.58 3.4
100o 9.34 7.38 0.79 0.96 12.60 9.8 60o 12.25 0.98 8.93 3.7
80o
50o 12.85 9.42 0.73 0.61 14.91 21.2 70o 13.74 1.01 10.27 4.0
60o 80odb 12.33 9.11 0.74 0.68 14.64 18.2 80o 15.22 1.05 11.62 4.2
70o 67owb 11.81 8.84 0.75 0.75 14.36 15.8
Extended Range Option Required
85o 11.03 8.47 0.77 0.86 13.95 12.9 LOW TEMP HEATING Antifreeze Required
100o 10.25 8.15 0.79 0.96 13.54 10.6 25o 7.86 0.81 5.11 2.9
50o 13.98 10.31 0.74 0.61 16.07 22.9 30o 60o 8.68 0.82 5.87 3.1
60o 85odb 13.42 9.98 0.74 0.68 15.75 19.7 40o 10.33 0.86 7.39 3.5
70o 71owb 12.86 9.68 0.75 0.75 15.43 17.0 25o 7.43 0.82 4.63 2.7
85o 12.01 9.28 0.77 0.86 14.95 13.9 30o 70o 8.21 0.84 5.35 2.9
100o 11.16 8.92 0.80 0.97 14.47 11.5 40o 9.77 0.88 6.78 3.3
Units are complete packages containing compressor, reversing valve, capillary tube metering device, and heat exchangers. 25o 6.93 0.84 4.07 2.4
Also included are safety controls: Overload protection for motors, high and low refrigerant pressure switches and a lock-out
circuit. 30o 80o 7.66 0.86 4.73 2.6
Extended range option includes expansion valve metering device, insulated water coil and solid state lock-out controls. 40o 9.11 0.90 6.05 3.0
Performance based on ARI/ISO rated air flow, fluid flow and voltage. For conditions other than rated, consult the FHP EAD
selection software. Due to variations in installation actual performance may vary marginally from tabulated values. FHP MANUFACTURING COMPANY
As a result of continuing research and development, specifications are subject to change without notice. 601 N.W. 65th Court - Fort Lauderdale, FL 33309
EC012ip6 mod1 Rev: 01-09 Phone: (954) 776-5471 - Fax: (800) 776-5529
http://www.fhp-mfg.com
EC015
PACKAGED UNITS
SPECIFICATION DATA SHEET
FHP MANUFACTURING HIGH-EFFICIENCY WATER SOURCE HEAT PUMPS AQUARIUS SERIES
ELECTRICAL SPECIFICATIONS MECHANICAL SPECIFICATIONS
Electrical Elect. Compressor Blower Loop Pump Min. Max. Refrigerant: R-410A
Characteristics Symbol Circuit Fuse/ Air Coil
RLA LRA FLA HP FLA HP Amps Breaker Square Rows Tube Fins/
208/230-1-60 -1 6.8 31.2 1.0 1/10 - - 9.5 15 Feet Deep O.D. Inch
265-1-60 -2 5.8 27.0 0.9 1/10 - - 8.1 15 1.42 3 3/8 14
Water Coil
Type Work Press
Coaxial 450 psig
Blower Size Compr Type
BLOWER PERFORMANCE
4x7 DD Rotary
Available External Static Pressure (Inches of Water, Gauge. Wet Coil and Filter Included)
Net Weight Ship Weight
Blower
0.10 0.20 0.30 0.40 0.50 0.60 0.70 0.80 0.90 1.00 1.10 1.20 158 lbs 170 lbs
Speed
High 540 515 490 460 430 390 340 - - - - - FLUID PRESSURE DROP
Medium 410 400 390 380 360 330 - - - - - - Fluid Pressure
Low 300 290 280 - - - - - - - - - Flow Drop
(GPM) (FOH) (PSIG)
ISO 13256-1 CERTIFIED PERFORMANCE DATA Rated at 500 CFM and 4.0 GPM 2.0 3.9 1.7
Water Loop Ground Water Ground Loop (Ext. Range Required) 2.5 5.9 2.5
Cooling Heating Cooling Heating Cooling Heating 3.0 8.2 3.5
Capacity EER Capacity COP Capacity EER Capacity COP Capacity EER Capacity COP 4.0 13.7 5.9
14,000 13.0 18,000 4.6 15,800 19.0 13,500 3.8 14,500 15.0 10,100 3.3 4.5 16.9 7.3

CAPACITY DATA All performance at 500 CFM and 4.0 GPM


EFT Range (Standard) EFT Range (Ext. Range Option) EFT Range (Standard) EFT Range (Ext. Range Option)
COOLING 50oF to 100oF 45oF to 110oF HEATING 50oF to 80oF 25oF to 80oF
Entering Entering Sensible Heat Entering Entering Heat
Fluid Air Total Sensible to Power of Fluid Air Total Power of
Temp. Temp. Capacity Capacity Total Input Reject EER Temp. Temp. Capacity Input Abs. COP
(oF) (oF) (MBtuH) (MBtuH) Ratio (kW) (MBtuH) (oF) (oF) (MBtuH) (kW) (MBtuH)
50o 13.91 9.08 0.65 0.76 16.50 18.3 50o 14.76 1.07 11.12 4.1
60o 70 dbo
13.35 8.79 0.66 0.85 16.24 15.8 60o 17.00 1.14 13.11 4.4
60o
70o 61owb 12.79 8.52 0.67 0.93 15.98 13.7 70o 19.24 1.21 15.10 4.7
85o 11.95 8.17 0.68 1.07 15.59 11.2 80o 21.47 1.28 17.09 4.9
100o 11.11 7.86 0.71 1.20 15.20 9.3 50o 13.96 1.09 10.25 3.8
50o 14.90 10.85 0.73 0.76 17.51 19.5 60o 16.07 1.16 12.11 4.1
70o
60o 75odb 14.30 10.50 0.73 0.85 17.21 16.8 70o 18.18 1.23 13.97 4.3
70o 63owb 13.71 10.19 0.74 0.94 16.91 14.6 80o 20.30 1.31 15.83 4.5
85o 12.81 9.77 0.76 1.07 16.47 11.9 50o 13.02 1.11 9.22 3.4
100o 11.91 9.41 0.79 1.20 16.02 9.9 60o 14.98 1.19 10.93 3.7
80o
50o 16.36 11.98 0.73 0.77 18.99 21.2 70o 16.95 1.26 12.64 3.9
60o 80odb 15.70 11.60 0.74 0.86 18.63 18.3 80o 18.91 1.34 14.35 4.1
70o 67owb 15.04 11.25 0.75 0.95 18.28 15.9
Extended Range Option Required
85o 14.06 10.79 0.77 1.08 17.75 13.0 LOW TEMP HEATING Antifreeze Required
100o 13.07 10.39 0.79 1.21 17.22 10.8 25o 9.00 0.89 5.97 3.0
50o 17.81 13.12 0.74 0.78 20.46 22.9 30o 60o 10.09 0.92 6.94 3.2
60o 85odb 17.10 12.70 0.74 0.87 20.05 19.8 40o 12.28 0.99 8.89 3.6
70o 71owb 16.38 12.32 0.75 0.95 19.64 17.2 25o 8.51 0.90 5.43 2.8
85o 15.31 11.82 0.77 1.09 19.03 14.1 30o 70o 9.55 0.94 6.34 3.0
100o 14.24 11.38 0.80 1.22 18.41 11.6 40o 11.62 1.01 8.16 3.4
Units are complete packages containing compressor, reversing valve, capillary tube metering device, and heat exchangers. 25o 7.94 0.92 4.79 2.5
Also included are safety controls: Overload protection for motors, high and low refrigerant pressure switches and a lock-out
circuit. 30o 80o 8.90 0.96 5.63 2.7
Extended range option includes expansion valve metering device, insulated water coil and solid state lock-out controls. 40o 10.83 1.04 7.30 3.1
Performance based on ARI/ISO rated air flow, fluid flow and voltage. For conditions other than rated, consult the FHP EAD
selection software. Due to variations in installation actual performance may vary marginally from tabulated values. FHP MANUFACTURING COMPANY
As a result of continuing research and development, specifications are subject to change without notice. 601 N.W. 65th Court - Fort Lauderdale, FL 33309
EC015ip6 mod1 Rev: 01-09 Phone: (954) 776-5471 - Fax: (800) 776-5529
http://www.fhp-mfg.com
EC018
PACKAGED UNITS
SPECIFICATION DATA SHEET
FHP MANUFACTURING HIGH-EFFICIENCY WATER SOURCE HEAT PUMPS AQUARIUS SERIES
ELECTRICAL SPECIFICATIONS MECHANICAL SPECIFICATIONS
Electrical Elect. Compressor Blower Loop Pump Min. Max. Refrigerant: R-410A
Characteristics Symbol Circuit Fuse/ Air Coil
RLA LRA FLA HP FLA HP Amps Breaker Square Rows Tube Fins/
208/230-1-60 -1 8.4 48.0 1.8 1/4 - - 12.3 20 Feet Deep O.D. Inch
265-1-60 -2 7.1 44.0 1.6 1/4 - - 10.5 15 1.88 3 3/8 14
Water Coil
Type Work Press
Coaxial 450 psig
BLOWER PERFORMANCE Blower Size Compr Type
9x7 DD Reciprocating
Available External Static Pressure (Inches of Water, Gauge. Wet Coil and Filter Included)
Net Weight Ship Weight
Blower
0.10 0.20 0.30 0.40 0.50 0.60 0.70 0.80 0.90 1.00 1.10 1.20 180 lbs 195 lbs
Speed
High 770 700 680 650 610 570 530 515 - - - - FLUID PRESSURE DROP
Medium 670 650 615 570 530 515 - - - - - - Fluid Pressure
Low 560 520 510 - - - - - - - - - Flow Drop
(GPM) (FOH) (PSIG)
ISO 13256-1 CERTIFIED PERFORMANCE DATA Rated at 650 CFM and 5.0 GPM 2.5 5.9 2.5
Water Loop Ground Water Ground Loop (Ext. Range Required) 3.0 8.2 3.5
Cooling Heating Cooling Heating Cooling Heating 4.0 13.7 5.9
Capacity EER Capacity COP Capacity EER Capacity COP Capacity EER Capacity COP 4.5 17.0 7.3
18,500 13.0 24,000 4.4 21,400 19.0 18,000 3.8 19,800 14.1 13,400 3.3 5.0 20.5 8.9

CAPACITY DATA All performance at 650 CFM and 5.0 GPM


EFT Range (Standard) EFT Range (Ext. Range Option) EFT Range (Standard) EFT Range (Ext. Range Option)
COOLING 50oF to 100oF 45oF to 110oF HEATING 50oF to 80oF 25oF to 80oF
Entering Entering Sensible Heat Entering Entering Heat
Fluid Air Total Sensible to Power of Fluid Air Total Power of
Temp. Temp. Capacity Capacity Total Input Reject EER Temp. Temp. Capacity Input Abs. COP
(oF) (oF) (MBtuH) (MBtuH) Ratio (kW) (MBtuH) (oF) (oF) (MBtuH) (kW) (MBtuH)
50 o 18.96 12.35 0.65 1.06 22.58 17.9 50 o 19.75 1.44 14.84 4.0
60o 70odb 18.08 11.87 0.66 1.18 22.10 15.4 60o 22.75 1.55 17.46 4.3
60o
70o 61owb 17.21 11.44 0.66 1.29 21.61 13.3 70o 25.75 1.66 20.08 4.5
85o 15.90 10.85 0.68 1.46 20.89 10.9 80o 28.75 1.77 22.70 4.8
100o 14.59 10.30 0.71 1.63 20.17 8.9 50o 18.67 1.46 13.68 3.7
50o 20.32 14.77 0.73 1.07 23.96 19.0 60o 21.51 1.58 16.13 4.0
70o
60o 75odb 19.38 14.21 0.73 1.18 23.42 16.4 70o 24.34 1.69 18.58 4.2
70o 63owb 18.45 13.70 0.74 1.30 22.88 14.2 80o 27.18 1.80 21.02 4.4
85o 17.05 12.99 0.76 1.47 22.06 11.6 50o 17.42 1.49 12.32 3.4
100o 15.64 12.34 0.79 1.64 21.25 9.5 60o 20.06 1.61 14.56 3.6
80o
50o 22.30 16.32 0.73 1.08 25.97 20.7 70o 22.70 1.73 16.80 3.9
60o 80odb 21.28 15.70 0.74 1.19 25.35 17.9 80o 25.33 1.84 19.05 4.0
70o 67owb 20.26 15.13 0.75 1.31 24.72 15.5
Extended Range Option Required
85o 18.72 14.35 0.77 1.48 23.78 12.6 LOW TEMP HEATING Antifreeze Required
100o 17.18 13.63 0.79 1.66 22.83 10.4 25o 12.01 1.16 8.05 3.0
50o 24.29 17.88 0.74 1.08 27.99 22.4 30o 60o 13.48 1.21 9.33 3.3
60o 85odb 23.18 17.20 0.74 1.20 27.28 19.3 40o 16.42 1.33 11.89 3.6
70o 71owb 22.06 16.58 0.75 1.32 26.56 16.7 25o 11.36 1.18 7.34 2.8
85o 20.39 15.73 0.77 1.49 25.49 13.7 30o 70o 12.75 1.24 8.53 3.0
100o 18.72 14.94 0.80 1.67 24.42 11.2 40o 15.53 1.35 10.92 3.4
Units are complete packages containing compressor, reversing valve, capillary tube metering device, and heat exchangers. 25o 10.60 1.20 6.49 2.6
Also included are safety controls: Overload protection for motors, high and low refrigerant pressure switches and a lock-out
circuit. 30o 80o 11.90 1.26 7.59 2.8
Extended range option includes expansion valve metering device, insulated water coil and solid state lock-out controls. 40o 14.49 1.38 9.78 3.1
Performance based on ARI/ISO rated air flow, fluid flow and voltage. For conditions other than rated, consult the FHP EAD
selection software. Due to variations in installation actual performance may vary marginally from tabulated values. FHP MANUFACTURING COMPANY
As a result of continuing research and development, specifications are subject to change without notice. 601 N.W. 65th Court - Fort Lauderdale, FL 33309
EC018ip6 mod1 Rev: 01-09 Phone: (954) 776-5471 - Fax: (800) 776-5529
http://www.fhp-mfg.com
EC024
PACKAGED UNITS
SPECIFICATION DATA SHEET
FHP MANUFACTURING HIGH-EFFICIENCY WATER SOURCE HEAT PUMPS AQUARIUS SERIES
ELECTRICAL SPECIFICATIONS MECHANICAL SPECIFICATIONS
Electrical Elect. Compressor Blower Loop Pump Min. Max. Refrigerant: R-410A
Characteristics Symbol Circuit Fuse/ Air Coil
RLA LRA FLA HP FLA HP Amps Breaker Square Rows Tube Fins/
208/230-1-60 -1 9.0 48.0 1.8 1/4 - - 13.1 20 Feet Deep O.D. Inch
265-1-60 -2 7.7 44.0 1.6 1/4 - - 11.3 15 2.12 3 3/8 14
208/230-3-60 -3 6.5 58.0 1.8 1/4 10.0 15 Water Coil
460-3-60 -4 3.6 30.0 0.9 1/4 5.4 15 Type Work Press
Coaxial 450 psig
Blower Size Compr Type
BLOWER PERFORMANCE
9x7 DD Reciprocating
Available External Static Pressure (Inches of Water, Gauge. Wet Coil and Filter Included)
Net Weight Ship Weight
Blower
0.10 0.20 0.30 0.40 0.50 0.60 0.70 0.80 0.90 1.00 1.10 1.20 205 lbs 228 lbs
Speed
High 900 850 800 760 710 690 680 670 - - - - FLUID PRESSURE DROP
Medium 750 720 690 670 - - - - - - - - Fluid Pressure
Low 670 - - - - - - - - - - - Flow Drop
(GPM) (FOH) (PSIG)
ISO 13256-1 CERTIFIED PERFORMANCE DATA Rated at 850 CFM and 6.0 GPM 3.0 3.5 1.5
Water Loop Ground Water Ground Loop (Ext. Range Required) 4.0 5.9 2.6
Cooling Heating Cooling Heating Cooling Heating 5.0 8.9 3.8
Capacity EER Capacity COP Capacity EER Capacity COP Capacity EER Capacity COP 6.0 12.3 5.3
25,000 13.8 30,000 4.5 28,200 20.6 23,800 3.8 26,500 15.2 17,900 3.3 7.0 16.3 7.0

CAPACITY DATA All performance at 850 CFM and 6.0 GPM


EFT Range (Standard) EFT Range (Ext. Range Option) EFT Range (Standard) EFT Range (Ext. Range Option)
COOLING 50oF to 100oF 45oF to 110oF HEATING 50oF to 80oF 25oF to 80oF
Entering Entering Sensible Heat Entering Entering Heat
Fluid Air Total Sensible to Power of Fluid Air Total Power of
Temp. Temp. Capacity Capacity Total Input Reject EER Temp. Temp. Capacity Input Abs. COP
(oF) (oF) (MBtuH) (MBtuH) Ratio (kW) (MBtuH) (oF) (oF) (MBtuH) (kW) (MBtuH)
50o 25.03 16.38 0.65 1.24 29.25 20.2 50 o 25.08 1.83 18.85 4.0
60o 70odb 24.08 15.89 0.66 1.40 28.87 17.1 60o 28.44 1.93 21.86 4.3
60o
70o 61owb 23.12 15.45 0.67 1.57 28.49 14.7 70o 31.79 2.02 24.88 4.6
85o 21.70 14.88 0.69 1.82 27.92 11.9 80o 35.15 2.12 27.90 4.8
100o 20.27 14.38 0.71 2.08 27.35 9.8 50o 23.70 1.86 17.36 3.7
50o 26.81 19.56 0.73 1.24 31.05 21.6 60o 26.88 1.96 20.18 4.0
70o
60o 75odb 25.79 18.97 0.74 1.41 30.61 18.3 70o 30.05 2.06 23.01 4.3
70o 63owb 24.77 18.45 0.74 1.58 30.17 15.7 80o 33.22 2.16 25.84 4.5
85o 23.24 17.77 0.76 1.83 29.50 12.7 50o 22.09 1.90 15.60 3.4
100o 21.71 17.18 0.79 2.09 28.84 10.4 60o 25.05 2.01 18.20 3.7
80o
50o 29.41 21.58 0.73 1.25 33.69 23.5 70o 28.00 2.11 20.80 3.9
60o 80odb 28.29 20.93 0.74 1.42 33.15 19.9 80o 30.96 2.21 23.40 4.1
70o 67owb 27.18 20.36 0.75 1.59 32.61 17.1
Extended Range Option Required
85o 25.50 19.60 0.77 1.85 31.81 13.8 LOW TEMP HEATING Antifreeze Required
100o 23.82 18.95 0.80 2.10 31.00 11.3 25o 16.36 1.58 10.97 3.0
50o 32.01 23.62 0.74 1.26 36.32 25.3 30o 60o 18.00 1.63 12.45 3.2
60o 85odb 30.80 22.91 0.74 1.43 35.69 21.5 40o 21.29 1.73 15.40 3.6
70o 71owb 29.58 22.28 0.75 1.61 35.06 18.4 25o 15.46 1.61 9.98 2.8
85o 27.76 21.46 0.77 1.86 34.12 14.9 30o 70o 17.02 1.66 11.37 3.0
100o 25.93 20.75 0.80 2.12 33.17 12.2 40o 20.13 1.76 14.13 3.4
Units are complete packages containing compressor, reversing valve, capillary tube metering device, and heat exchangers. 25o 14.42 1.64 8.82 2.6
Also included are safety controls: Overload protection for motors, high and low refrigerant pressure switches and a lock-out
circuit. 30o 80o 15.87 1.69 10.09 2.7
Extended range option includes expansion valve metering device, insulated water coil and solid state lock-out controls. 40o 18.76 1.80 12.63 3.1
Performance based on ARI/ISO rated air flow, fluid flow and voltage. For conditions other than rated, consult the FHP EAD
selection software. Due to variations in installation actual performance may vary marginally from tabulated values. FHP MANUFACTURING COMPANY
As a result of continuing research and development, specifications are subject to change without notice. 601 N.W. 65th Court - Fort Lauderdale, FL 33309
EC024ip6 mod1 Rev: 05-09 Phone: (954) 776-5471 - Fax: (800) 776-5529
http://www.fhp-mfg.com
EC030
PACKAGED UNITS
SPECIFICATION DATA SHEET
FHP MANUFACTURING HIGH-EFFICIENCY WATER SOURCE HEAT PUMPS AQUARIUS SERIES
ELECTRICAL SPECIFICATIONS MECHANICAL SPECIFICATIONS
Electrical Elect. Compressor Blower Loop Pump Min. Max. Refrigerant: R-410A
Characteristics Symbol Circuit Fuse/ Air Coil
RLA LRA FLA HP FLA HP Amps Breaker Square Rows Tube Fins/
208/230-1-60 -1 10.9 60.0 1.8 1/4 - - 15.5 25 Feet Deep O.D. Inch
265-1-60 -2 9.7 58.0 1.6 1/4 - - 13.8 20 2.29 3 3/8 14
208/230-3-60 -3 8.9 58.0 1.8 1/4 - - 13.0 20 Water Coil
460-3-60 -4 4.5 30.0 0.9 1/4 - - 6.6 15 Type Work Press
Coaxial 450 psig
BLOWER PERFORMANCE Blower Size Compr Type
9x7 DD Reciprocating
Available External Static Pressure (Inches of Water, Gauge. Wet Coil and Filter Included)
Net Weight Ship Weight
Blower
0.10 0.20 0.30 0.40 0.50 0.60 0.70 0.80 0.90 1.00 1.10 1.20 230 lbs 245 lbs
Speed
High 1250 1170 1120 1070 940 830 740 650 - - - - FLUID PRESSURE DROP
Medium 1050 980 920 830 760 700 - - - - - - Fluid Pressure
Low 975 910 870 740 640 - - - - - - - Flow Drop
(GPM) (FOH) (PSIG)
ISO 13256-1 CERTIFIED PERFORMANCE DATA Rated at 950 CFM and 7.0 GPM 3.5 3.9 1.7
Water Loop Ground Water Ground Loop (Ext. Range Required) 5.0 7.4 3.2
Cooling Heating Cooling Heating Cooling Heating 6.0 10.3 4.5
Capacity EER Capacity COP Capacity EER Capacity COP Capacity EER Capacity COP 7.0 13.6 5.9
29,000 13.0 35,000 4.3 33,000 18.6 28,400 3.8 31,000 14.4 21,000 3.3 9.0 21.4 9.3

CAPACITY DATA All performance at 950 CFM and 7.0 GPM


EFT Range (Standard) EFT Range (Ext. Range Option) EFT Range (Standard) EFT Range (Ext. Range Option)
COOLING 50oF to 100oF 45oF to 110oF HEATING 50oF to 80oF 25oF to 80oF
Entering Entering Sensible Heat Entering Entering Heat
Fluid Air Total Sensible to Power of Fluid Air Total Power of
Temp. Temp. Capacity Capacity Total Input Reject EER Temp. Temp. Capacity Input Abs. COP
(oF) (oF) (MBtuH) (MBtuH) Ratio (kW) (MBtuH) (oF) (oF) (MBtuH) (kW) (MBtuH)
50o 29.02 18.86 0.65 1.74 34.95 16.7 50o 30.19 2.28 22.42 3.9
60o 70 dbo
27.83 18.24 0.66 1.91 34.35 14.6 60o 34.13 2.42 25.87 4.1
60o
70o 61owb 26.65 17.68 0.66 2.08 33.76 12.8 70o 38.08 2.56 29.33 4.4
85o 24.87 16.94 0.68 2.34 32.86 10.6 80o 42.02 2.71 32.78 4.5
100o 23.09 16.28 0.70 2.60 31.97 8.9 50o 28.56 2.32 20.65 3.6
50o 31.11 22.59 0.73 1.75 37.07 17.8 60o 32.28 2.46 23.88 3.8
70o
60o 75odb 29.84 21.85 0.73 1.92 36.39 15.5 70o 36.01 2.61 27.10 4.0
70o 63owb 28.57 21.19 0.74 2.09 35.72 13.6 80o 39.73 2.75 30.33 4.2
85o 26.67 20.30 0.76 2.35 34.70 11.3 50o 26.64 2.37 18.56 3.3
100o 24.77 19.51 0.79 2.61 33.69 9.5 60o 30.11 2.52 21.52 3.5
80o
50o 34.16 24.96 0.73 1.76 40.17 19.4 70o 33.58 2.67 24.48 3.7
60o 80odb 32.77 24.15 0.74 1.93 39.37 16.9 80o 37.05 2.81 27.44 3.9
70o 67owb 31.38 23.41 0.75 2.11 38.58 14.9
Extended Range Option Required
85o 29.29 22.44 0.77 2.37 37.39 12.3 LOW TEMP HEATING Antifreeze Required
100o 27.21 21.57 0.79 2.64 36.20 10.3 25o 19.93 1.92 13.38 3.0
50o 37.21 27.36 0.74 1.77 43.27 21.0 30o 60o 21.87 1.99 15.07 3.2
60o 85odb 35.70 26.47 0.74 1.95 42.36 18.3 40o 25.73 2.13 18.45 3.5
70o 71owb 34.19 25.66 0.75 2.13 41.45 16.1 25o 18.87 1.95 12.20 2.8
85o 31.92 24.60 0.77 2.39 40.08 13.4 30o 70o 20.69 2.03 13.78 3.0
100o 29.65 23.65 0.80 2.66 38.72 11.2 40o 24.35 2.17 16.93 3.3
Units are complete packages containing compressor, reversing valve, capillary tube metering device, and heat exchangers. 25o 17.61 2.00 10.80 2.6
Also included are safety controls: Overload protection for motors, high and low refrigerant pressure switches and a lock-out
circuit. 30o 80o 19.31 2.07 12.25 2.7
Extended range option includes expansion valve metering device, insulated water coil and solid state lock-out controls. 40o 22.72 2.22 15.14 3.0
Performance based on ARI/ISO rated air flow, fluid flow and voltage. For conditions other than rated, consult the FHP EAD
selection software. Due to variations in installation actual performance may vary marginally from tabulated values. FHP MANUFACTURING COMPANY
As a result of continuing research and development, specifications are subject to change without notice. 601 N.W. 65th Court - Fort Lauderdale, FL 33309
EC030ip6 mod1 Rev: 01-09 Phone: (954) 776-5471 - Fax: (800) 776-5529
http://www.fhp-mfg.com
EC036
PACKAGED UNITS
SPECIFICATION DATA SHEET
FHP MANUFACTURING HIGH-EFFICIENCY WATER SOURCE HEAT PUMPS AQUARIUS SERIES
ELECTRICAL SPECIFICATIONS MECHANICAL SPECIFICATIONS
Electrical Elect. Compressor Blower Loop Pump Min. Max. Refrigerant: R-410A
Characteristics Symbol Circuit Fuse/ Air Coil
RLA LRA FLA HP FLA HP Amps Breaker Square Rows Tube Fins/
208/230-1-60 -1 14.8 83.0 3.9 1/2 - - 22.4 35 Feet Deep O.D. Inch
265-1-60 -2 11.6 79.0 2.3 1/2 - - 16.8 25 3.50 3 3/8 14
208/230-3-60 -3 10.0 78.0 3.9 1/2 - - 16.4 25 Water Coil
460-3-60 -4 5.4 40.0 2.0 1/2 - - 8.8 15 Type Work Press
Coaxial 450 psig
BLOWER PERFORMANCE Blower Size Compr Type
9x7 DD Reciprocating
Available External Static Pressure (Inches of Water, Gauge. Wet Coil and Filter Included)
Net Weight Ship Weight
Blower
0.10 0.20 0.30 0.40 0.50 0.60 0.70 0.80 0.90 1.00 1.10 1.20 253 lbs 273 lbs
Speed
High 1500 1440 1370 1290 1210 1120 1000 900 - - - - FLUID PRESSURE DROP
Medium 1410 1350 1290 1220 1150 1060 900 - - - - - Fluid Pressure
Low 1290 1250 1200 1150 1080 1000 - - - - - - Flow Drop
(GPM) (FOH) (PSIG)
ISO 13256-1 CERTIFIED PERFORMANCE DATA Rated at 1,200 CFM and 9.0 GPM 4.0 2.1 0.9
Water Loop Ground Water Ground Loop (Ext. Range Required) 5.0 3.2 1.4
Cooling Heating Cooling Heating Cooling Heating 7.5 6.5 2.8
Capacity EER Capacity COP Capacity EER Capacity COP Capacity EER Capacity COP 9.0 9.1 3.9
36,000 13.8 46,000 4.5 40,200 19.5 36,200 4.0 37,800 15.5 27,400 3.3 11.0 13.0 5.6

CAPACITY DATA All performance at 1,200 CFM and 9.0 GPM


EFT Range (Standard) EFT Range (Ext. Range Option) EFT Range (Standard) EFT Range (Ext. Range Option)
COOLING 50oF to 100oF 45oF to 110oF HEATING 50oF to 80oF 25oF to 80oF
Entering Entering Sensible Heat Entering Entering Heat
Fluid Air Total Sensible to Power of Fluid Air Total Power of
Temp. Temp. Capacity Capacity Total Input Reject EER Temp. Temp. Capacity Input Abs. COP
(oF) (oF) (MBtuH) (MBtuH) Ratio (kW) (MBtuH) (oF) (oF) (MBtuH) (kW) (MBtuH)
50 o 34.99 22.71 0.65 2.08 42.10 16.8 50o 39.07 2.87 29.29 4.0
60o 70odb 33.74 22.07 0.65 2.28 41.53 14.8 60o 44.48 3.03 34.13 4.3
60o
70o 61owb 32.48 21.52 0.66 2.48 40.96 13.1 70o 49.88 3.20 38.97 4.6
85o 30.59 20.80 0.68 2.79 40.10 11.0 80o 55.28 3.36 43.81 4.8
100o 28.70 20.21 0.70 3.09 39.24 9.3 50o 36.96 2.92 27.01 3.7
50o 37.52 27.22 0.73 2.09 44.67 17.9 60o 42.07 3.08 31.54 4.0
70o
60o 75odb 36.17 26.46 0.73 2.30 44.01 15.8 70o 47.17 3.25 36.07 4.3
70o 63owb 34.83 25.80 0.74 2.50 43.35 13.9 80o 52.27 3.42 40.60 4.5
85o 32.81 24.95 0.76 2.80 42.37 11.7 50o 34.49 2.98 24.32 3.4
100o 30.79 24.24 0.79 3.10 41.38 9.9 60o 39.24 3.15 28.49 3.7
80o
50o 41.22 30.09 0.73 2.11 48.42 19.5 70o 43.99 3.32 32.65 3.9
60o 80odb 39.74 29.26 0.74 2.31 47.63 17.2 80o 48.74 3.49 36.82 4.1
70o 67owb 38.26 28.52 0.75 2.52 46.85 15.2
Extended Range Option Required
85o 36.05 27.59 0.77 2.82 45.68 12.8 LOW TEMP HEATING Antifreeze Required
100o 33.84 26.81 0.79 3.13 44.51 10.8 25o 25.07 2.45 16.70 3.0
50o 44.91 32.99 0.73 2.12 52.16 21.1 30o 60o 27.72 2.54 19.06 3.2
60o 85odb 43.31 32.08 0.74 2.33 51.26 18.6 40o 33.01 2.70 23.80 3.6
70o 71owb 41.70 31.28 0.75 2.54 50.36 16.4 25o 23.73 2.50 15.22 2.8
85o 39.29 30.25 0.77 2.84 49.00 13.8 30o 70o 26.23 2.58 17.43 3.0
100o 36.89 29.40 0.80 3.15 47.64 11.7 40o 31.24 2.75 21.86 3.3
Units are complete packages containing compressor, reversing valve, capillary tube metering device, and heat exchangers. 25o 22.16 2.55 13.47 2.5
Also included are safety controls: Overload protection for motors, high and low refrigerant pressure switches and a lock-out
circuit. 30o 80o 24.49 2.63 15.50 2.7
Extended range option includes expansion valve metering device, insulated water coil and solid state lock-out controls. 40o 29.15 2.81 19.58 3.0
Performance based on ARI/ISO rated air flow, fluid flow and voltage. For conditions other than rated, consult the FHP EAD
selection software. Due to variations in installation actual performance may vary marginally from tabulated values. FHP MANUFACTURING COMPANY
As a result of continuing research and development, specifications are subject to change without notice. 601 N.W. 65th Court - Fort Lauderdale, FL 33309
EC036ip6 mod1 Rev: 01-09 Phone: (954) 776-5471 - Fax: (800) 776-5529
http://www.fhp-mfg.com
EC041
PACKAGED UNITS
SPECIFICATION DATA SHEET
FHP MANUFACTURING HIGH-EFFICIENCY WATER SOURCE HEAT PUMPS AQUARIUS SERIES
ELECTRICAL SPECIFICATIONS MECHANICAL SPECIFICATIONS
Electrical Elect. Compressor Blower Loop Pump Min. Max. Refrigerant: R-410A
Characteristics Symbol Circuit Fuse/ Air Coil
RLA LRA FLA HP FLA HP Amps Breaker Square Rows Tube Fins/
208/230-1-60 -1 18.0 105.0 3.9 1/2 - - 26.4 40 Feet Deep O.D. Inch
265-1-60 -2 17.3 88.0 2.3 1/2 - - 24.0 40 2.29 4 3/8 14
208/230-3-60 -3 10.6 78.0 3.9 1/2 - - 17.2 25 Water Coil
460-3-60 -4 5.8 40.0 2.0 1/2 - - 9.3 15 Type Work Press
Coaxial 450 psig
BLOWER PERFORMANCE Blower Size Compr Type
9x7 DD Reciprocating
Available External Static Pressure (Inches of Water, Gauge. Wet Coil and Filter Included)
Net Weight Ship Weight
Blower
0.10 0.20 0.30 0.40 0.50 0.60 0.70 0.80 0.90 1.00 1.10 1.20 265 lbs 280 lbs
Speed
High 1260 1180 1100 1030 960 870 810 620 - - - - FLUID PRESSURE DROP
Medium 1210 1150 1070 1010 940 850 750 - - - - - Fluid Pressure
Low 1160 1100 1040 980 910 830 - - - - - - Flow Drop
(GPM) (FOH) (PSIG)
ISO 13256-1 CERTIFIED PERFORMANCE DATA Rated at 1,150 CFM and 9.0 GPM 5.0 3.2 1.4
Water Loop Ground Water Ground Loop (Ext. Range Required) 7.0 5.8 2.5
Cooling Heating Cooling Heating Cooling Heating 9.0 9.1 3.9
Capacity EER Capacity COP Capacity EER Capacity COP Capacity EER Capacity COP 11.0 13.0 5.6
38,000 12.5 49,000 4.2 40,400 16.1 39,000 3.7 39,200 14.1 28,500 3.1 13.0 17.6 7.6

CAPACITY DATA All performance at 1,150 CFM and 9.0 GPM


EFT Range (Standard) EFT Range (Ext. Range Option) EFT Range (Standard) EFT Range (Ext. Range Option)
COOLING 50oF to 100oF 45oF to 110oF HEATING 50oF to 80oF 25oF to 80oF
Entering Entering Sensible Heat Entering Entering Heat
Fluid Air Total Sensible to Power of Fluid Air Total Power of
Temp. Temp. Capacity Capacity Total Input Reject EER Temp. Temp. Capacity Input Abs. COP
(oF) (oF) (MBtuH) (MBtuH) Ratio (kW) (MBtuH) (oF) (oF) (MBtuH) (kW) (MBtuH)
50o 35.06 22.64 0.65 2.34 43.04 15.0 50 o 40.98 3.06 30.53 3.9
60o 70odb 34.32 22.35 0.65 2.52 42.93 13.6 60o 46.93 3.27 35.76 4.2
60o
70o 61owb 33.58 22.15 0.66 2.70 42.82 12.4 70o 52.88 3.48 40.99 4.4
85o 32.48 21.98 0.68 2.98 42.65 10.9 80o 58.84 3.70 46.22 4.7
100o 31.38 21.98 0.70 3.25 42.48 9.6 50o 38.74 3.12 28.10 3.6
50o 37.55 27.04 0.72 2.35 45.58 16.0 60o 44.36 3.33 32.98 3.9
70o
60o 75odb 36.76 26.70 0.73 2.54 45.42 14.5 70o 49.98 3.55 37.87 4.1
70o 63owb 35.98 26.45 0.74 2.72 45.26 13.2 80o 55.61 3.76 42.76 4.3
85o 34.79 26.26 0.75 3.00 45.02 11.6 50o 36.10 3.19 25.22 3.3
100o 33.61 26.26 0.78 3.27 44.78 10.3 60o 41.34 3.41 29.71 3.6
80o
50o 41.20 29.84 0.72 2.37 49.30 17.4 70o 46.58 3.63 34.19 3.8
60o 80odb 40.34 29.46 0.73 2.56 49.07 15.8 80o 51.81 3.85 38.67 3.9
70o 67owb 39.48 29.19 0.74 2.74 48.84 14.4
Extended Range Option Required
85o 38.18 28.98 0.76 3.02 48.49 12.6 LOW TEMP HEATING Antifreeze Required
100o 36.88 28.98 0.79 3.30 48.14 11.2 25o 25.59 2.53 16.95 3.0
50o 44.85 32.67 0.73 2.39 53.01 18.8 30o 60o 28.50 2.64 19.50 3.2
60o 85odb 43.92 32.25 0.73 2.58 52.71 17.0 40o 34.34 2.85 24.62 3.5
70o 71owb 42.98 31.96 0.74 2.76 52.41 15.5 25o 24.19 2.58 15.40 2.8
85o 41.57 31.73 0.76 3.04 51.96 13.7 30o 70o 26.95 2.69 17.78 2.9
100o 40.16 31.72 0.79 3.32 51.50 12.1 40o 32.46 2.90 22.56 3.3
Units are complete packages containing compressor, reversing valve, capillary tube metering device, and heat exchangers. 25o 22.56 2.63 13.56 2.5
Also included are safety controls: Overload protection for motors, high and low refrigerant pressure switches and a lock-out
circuit. 30o 80o 25.12 2.75 15.75 2.7
Extended range option includes expansion valve metering device, insulated water coil and solid state lock-out controls. 40o 30.26 2.97 20.13 3.0
Performance based on ARI/ISO rated air flow, fluid flow and voltage. For conditions other than rated, consult the FHP EAD
selection software. Due to variations in installation actual performance may vary marginally from tabulated values. FHP MANUFACTURING COMPANY
As a result of continuing research and development, specifications are subject to change without notice. 601 N.W. 65th Court - Fort Lauderdale, FL 33309
EC041ip6 mod1 Rev: 1-08 Phone: (954) 776-5471 - Fax: (800) 776-5529
http://www.fhp-mfg.com
EC042
PACKAGED UNITS
SPECIFICATION DATA SHEET
FHP MANUFACTURING HIGH-EFFICIENCY WATER SOURCE HEAT PUMPS AQUARIUS SERIES
ELECTRICAL SPECIFICATIONS MECHANICAL SPECIFICATIONS
Electrical Elect. Compressor Blower Loop Pump Min. Max. Refrigerant: R-410A
Characteristics Symbol Circuit Fuse/ Air Coil
RLA LRA FLA HP FLA HP Amps Breaker Square Rows Tube Fins/
208/230-1-60 -1 18.0 105.0 3.9 1/2 - - 26.4 40 Feet Deep O.D. Inch
265-1-60 -2 17.3 88.0 2.3 1/2 - - 24.0 40 3.50 3 3/8 14
208/230-3-60 -3 10.6 78.0 3.9 1/2 - - 17.2 25 Water Coil
460-3-60 -4 5.8 40.0 2.0 1/2 - - 9.3 15 Type Work Press
Coaxial 450 psig
BLOWER PERFORMANCE Blower Size Compr Type
9x7 DD Reciprocating
Available External Static Pressure (Inches of Water, Gauge. Wet Coil and Filter Included)
Net Weight Ship Weight
Blower
0.10 0.20 0.30 0.40 0.50 0.60 0.70 0.80 0.90 1.00 1.10 1.20 256 lbs 276 lbs
Speed
High 1560 1500 1420 1340 1260 1170 1070 950 - - - - FLUID PRESSURE DROP
Medium 1470 1410 1340 1270 1200 1110 1010 - - - - - Fluid Pressure
Low 1340 1300 1250 1200 1130 1050 - - - - - - Flow Drop
(GPM) (FOH) (PSIG)
ISO 13256-1 CERTIFIED PERFORMANCE DATA Rated at 1,500 CFM and 10.0 GPM 5.0 3.2 1.4
Water Loop Ground Water Ground Loop (Ext. Range Required) 7.0 5.8 2.5
Cooling Heating Cooling Heating Cooling Heating 10.0 11.0 4.8
Capacity EER Capacity COP Capacity EER Capacity COP Capacity EER Capacity COP 11.0 13.0 5.6
42,000 13.0 53,000 4.2 44,500 18.5 42,000 3.8 43,800 14.2 32,200 3.3 13.0 17.6 7.6

CAPACITY DATA All performance at 1,500 CFM and 10.0 GPM


EFT Range (Standard) EFT Range (Ext. Range Option) EFT Range (Standard) EFT Range (Ext. Range Option)
COOLING 50oF to 100oF 45oF to 110oF HEATING 50oF to 80oF 25oF to 80oF
Entering Entering Sensible Heat Entering Entering Heat
Fluid Air Total Sensible to Power of Fluid Air Total Power of
Temp. Temp. Capacity Capacity Total Input Reject EER Temp. Temp. Capacity Input Abs. COP
(oF) (oF) (MBtuH) (MBtuH) Ratio (kW) (MBtuH) (oF) (oF) (MBtuH) (kW) (MBtuH)
50 o 38.76 25.36 0.65 2.17 46.17 17.9 50 o 44.95 3.33 33.60 4.0
60o 70odb 38.09 25.13 0.66 2.48 46.56 15.4 60o 50.80 3.55 38.67 4.2
60o
70o 61owb 37.42 25.00 0.67 2.79 46.96 13.4 70o 56.66 3.78 43.74 4.4
85o 36.42 24.97 0.69 3.26 47.55 11.2 80o 62.51 4.01 48.81 4.6
100o 35.41 25.13 0.71 3.73 48.14 9.5 50o 42.49 3.39 30.93 3.7
50o 41.52 30.28 0.73 2.18 48.97 19.0 60o 48.02 3.62 35.66 3.9
70o
60o 75odb 40.81 30.01 0.74 2.50 49.32 16.4 70o 53.55 3.85 40.39 4.1
70o 63owb 40.09 29.85 0.74 2.81 49.67 14.3 80o 59.08 4.09 45.12 4.2
85o 39.01 29.82 0.76 3.28 50.20 11.9 50o 39.60 3.46 27.78 3.4
100o 37.94 30.01 0.79 3.75 50.73 10.1 60o 44.75 3.70 32.11 3.5
80o
50o 45.56 33.41 0.73 2.20 53.06 20.7 70o 49.90 3.94 36.44 3.7
60o 80odb 44.77 33.11 0.74 2.51 53.36 17.8 80o 55.05 4.18 40.78 3.9
70o 67owb 43.99 32.94 0.75 2.83 53.65 15.5
Extended Range Option Required
85o 42.81 32.91 0.77 3.31 54.09 13.0 LOW TEMP HEATING Antifreeze Required
100o 41.63 33.12 0.80 3.78 54.53 11.0 25o 29.72 2.75 20.33 3.2
50o 49.59 36.58 0.74 2.22 57.16 22.4 30o 60o 32.59 2.87 22.81 3.3
60o 85odb 48.74 36.25 0.74 2.53 57.39 19.2 40o 38.33 3.10 27.77 3.6
70o 71owb 47.88 36.06 0.75 2.85 57.62 16.8 25o 28.10 2.80 18.54 2.9
85o 46.60 36.02 0.77 3.33 57.97 14.0 30o 70o 30.81 2.92 20.85 3.1
100o 45.32 36.25 0.80 3.81 58.32 11.9 40o 36.23 3.15 25.47 3.4
Units are complete packages containing compressor, reversing valve, capillary tube metering device, and heat exchangers. 25o 26.20 2.86 16.42 2.7
Also included are safety controls: Overload protection for motors, high and low refrigerant pressure switches and a lock-out
circuit. 30o 80o 28.72 2.98 18.54 2.8
Extended range option includes expansion valve metering device, insulated water coil and solid state lock-out controls. 40o 33.77 3.22 22.77 3.1
Performance based on ARI/ISO rated air flow, fluid flow and voltage. or conditions other than rated, consult the FHP EAD
selection software. Due to variations in installation actual performance may vary marginally from tabulated values. FHP MANUFACTURING COMPANY
As a result of continuing research and development, specifications are subject to change without notice. 601 N.W. 65th Court - Fort Lauderdale, FL 33309
EC042ip6 mod1 Rev:01-09 Phone: (954) 776-5471 - Fax: (800) 776-5529
http://www.fhp-mfg.com
EC048
PACKAGED UNITS
SPECIFICATION DATA SHEET
FHP MANUFACTURING HIGH-EFFICIENCY WATER SOURCE HEAT PUMPS AQUARIUS SERIES
ELECTRICAL SPECIFICATIONS MECHANICAL SPECIFICATIONS
Electrical Elect. Compressor Blower Loop Pump Min. Max. Refrigerant: R-410A
Characteristics Symbol Circuit Fuse/ Air Coil
RLA LRA FLA HP FLA HP Amps Breaker Square Rows Tube Fins/
208/230-1-60 -1 21.2 113.0 5.2 3/4 - - 31.7 45 Feet Deep O.D. Inch
208/230-3-60 -3 16.1 120.0 5.2 3/4 - - 25.4 40 4.50 3 3/8 14
460-3-60 -4 8.4 60.0 2.5 3/4 - - 13.0 20 Water Coil
575-3-60 -5 6.4 42.0 2.6 3/4 - - 10.6 15 Type Work Press
Coaxial 450 psig
BLOWER PERFORMANCE Blower Size Compr Type
10x8 DD Scroll
Available External Static Pressure (Inches of Water, Gauge. Wet Coil and Filter Included)
Net Weight Ship Weight
Blower
0.10 0.20 0.30 0.40 0.50 0.60 0.70 0.80 0.90 1.00 1.10 1.20 326 lbs 350 lbs
Speed
High 1980 1960 1930 1840 1800 1730 1680 1610 1500 - - - FLUID PRESSURE DROP
Medium 1940 1910 1850 1770 1740 1690 1660 1530 - - - - Fluid Pressure
Low 1900 1870 1810 1730 1710 1600 - - - - - - Flow Drop
(GPM) (FOH) (PSIG)
ISO 13256-1 CERTIFIED PERFORMANCE DATA Rated at 1,600 CFM and 12.0 GPM 6.0 2.9 1.3
Water Loop Ground Water Ground Loop (Ext. Range Required) 9.0 6.1 2.6
Cooling Heating Cooling Heating Cooling Heating 12.0 10.2 4.4
Capacity EER Capacity COP Capacity EER Capacity COP Capacity EER Capacity COP 14.0 13.5 5.9
48,000 14.0 58,000 4.8 58,000 20.6 46,600 4.2 52,000 15.4 36,800 3.5 16.0 17.2 7.4

CAPACITY DATA All performance at 1,600 CFM and 12.0 GPM


EFT Range (Standard) EFT Range (Ext. Range Option) EFT Range (Standard) EFT Range (Ext. Range Option)
COOLING 50oF to 100oF 45oF to 110oF HEATING 50oF to 80oF 25oF to 80oF
Entering Entering Sensible Heat Entering Entering Heat
Fluid Air Total Sensible to Power of Fluid Air Total Power of
Temp. Temp. Capacity Capacity Total Input Reject EER Temp. Temp. Capacity Input Abs. COP
(oF) (oF) (MBtuH) (MBtuH) Ratio (kW) (MBtuH) (oF) (oF) (MBtuH) (kW) (MBtuH)
50 o 51.49 33.42 0.65 2.89 61.34 17.8 50o 50.51 3.52 38.49 4.2
60o 70odb 48.35 31.63 0.65 3.12 58.99 15.5 60o 56.66 3.66 44.15 4.5
60o
70o 61owb 45.22 29.94 0.66 3.35 56.64 13.5 70o 62.80 3.81 49.82 4.8
85o 40.51 27.52 0.68 3.69 53.12 11.0 80o 68.95 3.95 55.48 5.1
100o 35.81 25.16 0.70 4.04 49.60 8.9 50o 47.79 3.58 35.57 3.9
50o 55.20 40.05 0.73 2.90 65.11 19.0 60o 53.60 3.73 40.88 4.2
70o
60o 75odb 51.85 37.93 0.73 3.13 62.54 16.5 70o 59.40 3.87 46.19 4.5
70o 63owb 48.49 35.91 0.74 3.37 59.98 14.4 80o 65.21 4.02 51.50 4.8
85 o 43.46 33.02 0.76 3.71 56.13 11.7 50o 44.60 3.66 32.12 3.6
100o 38.42 30.21 0.79 4.06 52.28 9.5 60o 50.00 3.80 37.02 3.9
80o
50o 60.64 44.28 0.73 2.92 70.61 20.7 70o 55.41 3.95 41.92 4.1
60o 80odb 56.96 41.93 0.74 3.16 67.73 18.0 80o 60.82 4.10 46.82 4.3
70o 67owb 53.28 39.70 0.75 3.39 64.85 15.7
Extended Range Option Required
85o 47.76 36.53 0.76 3.74 60.53 12.8 LOW TEMP HEATING Antifreeze Required
100o 42.24 33.43 0.79 4.09 56.21 10.3 25o 34.45 3.17 23.65 3.2
50o 66.08 48.54 0.73 2.94 76.12 22.4 30o 60o 37.47 3.24 26.42 3.4
60o 85odb 62.07 45.97 0.74 3.18 72.93 19.5 40o 43.49 3.38 31.96 3.8
70o 71owb 58.07 43.54 0.75 3.42 69.73 17.0 25o 32.62 3.22 21.63 3.0
85o 52.07 40.06 0.77 3.77 64.93 13.8 30o 70o 35.47 3.29 24.23 3.2
100o 46.07 36.68 0.80 4.12 60.14 11.2 40o 41.16 3.44 29.43 3.5
Units are complete packages containing compressor, reversing valve, capillary tube metering device, and heat exchangers. 25o 30.46 3.28 19.25 2.7
Also included are safety controls: Overload protection for motors, high and low refrigerant pressure switches and a lock-out
circuit. 30o 80o 33.12 3.36 21.65 2.9
Extended range option includes expansion valve metering device, insulated water coil and solid state lock-out controls. 40o 38.42 3.51 26.45 3.2
Performance based on ARI/ISO rated air flow, fluid flow and voltage. For conditions other than rated, consult the FHP EAD
selection software. Due to variations in installation actual performance may vary marginally from tabulated values. FHP MANUFACTURING COMPANY
As a result of continuing research and development, specifications are subject to change without notice. 601 N.W. 65th Court - Fort Lauderdale, FL 33309
EC048ip6 mod1 Rev: 09-08 Phone: (954) 776-5471 - Fax: (800) 776-5529
http://www.fhp-mfg.com
EC051
PACKAGED UNITS
SPECIFICATION DATA SHEET
FHP MANUFACTURING HIGH-EFFICIENCY WATER SOURCE HEAT PUMPS AQUARIUS SERIES
ELECTRICAL SPECIFICATIONS MECHANICAL SPECIFICATIONS
Electrical Elect. Compressor Blower Loop Pump Min. Max. Refrigerant: R-410A
Characteristics Symbol Circuit Fuse/ Air Coil
RLA LRA FLA HP FLA HP Amps Breaker Square Rows Tube Fins/
208/230-1-60 -1 21.2 113.0 5.2 3/4 31.7 45 Feet Deep O.D. Inch
208/230-3-60 -3 16.1 120.0 5.2 3/4 - - 25.4 40 4.10 3 3/8 14
460-3-60 -4 8.4 60.0 2.5 3/4 - - 13.0 20 Water Coil
Type Work Press
Coaxial 450 psig
BLOWER PERFORMANCE Blower Size Compr Type
10x8 DD Scroll
Available External Static Pressure (Inches of Water, Gauge. Wet Coil and Filter Included)
Net Weight Ship Weight
Blower
0.10 0.20 0.30 0.40 0.50 0.60 0.70 0.80 0.90 1.00 1.10 1.20 310 lbs 334 lbs
Speed
High 1650 1630 1610 1530 1500 1440 1400 1340 1250 - - - FLUID PRESSURE DROP
Medium 1615 1590 1540 1475 1450 1410 1380 1275 - - - - Fluid Pressure
Low 1585 1560 1510 1440 1425 1335 - - - - - - Flow Drop
(GPM) (FOH) (PSIG)
ISO 13256-1 CERTIFIED PERFORMANCE DATA Rated at 1,500 CFM and 12.0 GPM 6.0 2.9 1.3
Water Loop Ground Water Ground Loop (Ext. Range Required) 9.0 6.1 2.6
Cooling Heating Cooling Heating Cooling Heating 12.0 10.2 4.4
Capacity EER Capacity COP Capacity EER Capacity COP Capacity EER Capacity COP 14.0 13.5 5.9
47,500 13.8 53,500 4.7 58,000 20.6 46,600 4.2 51,000 15.5 37,800 3.6 16.0 17.2 7.4

CAPACITY DATA All performance at 1,500 CFM and 12.0 GPM


EFT Range (Standard) EFT Range (Ext. Range Option) EFT Range (Standard) EFT Range (Ext. Range Option)
COOLING 50oF to 100oF 45oF to 110oF HEATING 50oF to 80oF 25oF to 80oF
Entering Entering Sensible Heat Entering Entering Heat
Fluid Air Total Sensible to Power of Fluid Air Total Power of
Temp. Temp. Capacity Capacity Total Input Reject EER Temp. Temp. Capacity Input Abs. COP
(oF) (oF) (MBtuH) (MBtuH) Ratio (kW) (MBtuH) (oF) (oF) (MBtuH) (kW) (MBtuH)
50o 47.48 31.27 0.66 2.76 56.91 17.2 50o 49.89 3.45 38.10 4.2
60o 70 dbo
45.54 30.24 0.66 3.00 55.78 15.2 60o 54.44 3.54 42.36 4.5
60o
70o 61owb 43.59 29.31 0.67 3.24 54.65 13.5 70o 59.00 3.63 46.62 4.8
85o 40.68 28.07 0.69 3.59 52.95 11.3 80o 63.56 3.71 50.88 5.0
100o 37.77 26.97 0.71 3.95 51.25 9.6 50o 47.19 3.51 35.20 3.9
50o 50.89 37.44 0.74 2.78 60.38 18.3 60o 51.49 3.60 39.20 4.2
70o
60o 75odb 48.81 36.21 0.74 3.02 59.11 16.2 70o 55.80 3.69 43.20 4.4
70o 63owb 46.74 35.10 0.75 3.26 57.85 14.4 80o 60.10 3.78 47.20 4.7
85o 43.62 33.63 0.77 3.61 55.95 12.1 50o 44.01 3.59 31.77 3.6
100o 40.50 32.32 0.80 3.97 54.05 10.2 60o 48.02 3.68 35.47 3.8
80o
50o 55.89 41.36 0.74 2.80 65.44 20.0 70o 52.03 3.77 39.17 4.0
60o 80odb 53.61 40.01 0.75 3.04 63.99 17.6 80o 56.04 3.86 42.87 4.3
70o 67owb 51.33 38.79 0.76 3.28 62.53 15.6
Extended Range Option Required
85o 47.91 37.17 0.78 3.64 60.34 13.2 LOW TEMP HEATING Antifreeze Required
100o 44.50 35.73 0.80 4.00 58.15 11.1 25o 37.74 3.23 26.70 3.4
50o 60.88 45.33 0.74 2.82 70.51 21.6 30o 60o 39.97 3.28 28.78 3.6
60o 85odb 58.40 43.85 0.75 3.06 68.86 19.1 40o 44.44 3.36 32.96 3.9
70o 71owb 55.93 42.51 0.76 3.31 67.21 16.9 25o 35.71 3.29 24.48 3.2
85o 52.21 40.74 0.78 3.67 64.73 14.2 30o 70o 37.82 3.34 26.43 3.3
100o 48.49 39.16 0.81 4.03 62.25 12.0 40o 42.04 3.42 30.35 3.6
Units are complete packages containing compressor, reversing valve, capillary tube metering device, and heat exchangers. 25o 33.32 3.36 21.85 2.9
Also included are safety controls: Overload protection for motors, high and low refrigerant pressure switches and a lock-out
circuit. 30o 80o 35.29 3.41 23.66 3.0
Extended range option includes expansion valve metering device, insulated water coil and solid state lock-out controls. 40o 39.22 3.50 27.28 3.3
Performance based on ARI/ISO rated air flow, fluid flow and voltage. For conditions other than rated, consult the FHP EAD
selection software. Due to variations in installation actual performance may vary marginally from tabulated values. FHP MANUFACTURING COMPANY
As a result of continuing research and development, specifications are subject to change without notice. 601 N.W. 65th Court - Fort Lauderdale, FL 33309
EC051ip6 mod1 Rev: 01-09 Phone: (954) 776-5471 - Fax: (800) 776-5529
http://www.fhp-mfg.com
EC060
PACKAGED UNITS
SPECIFICATION DATA SHEET
FHP MANUFACTURING HIGH-EFFICIENCY WATER SOURCE HEAT PUMPS AQUARIUS SERIES
ELECTRICAL SPECIFICATIONS MECHANICAL SPECIFICATIONS
Electrical Elect. Compressor Blower Loop Pump Min. Max. Refrigerant: R-410A
Characteristics Symbol Circuit Fuse/ Air Coil
RLA LRA FLA HP FLA HP Amps Breaker Square Rows Tube Fins/
208/230-1-60 -1 29.0 145.0 5.2 3/4 41.5 60 Feet Deep O.D. Inch
208/230-3-60 -3 18.0 123.0 5.2 3/4 - - 27.7 45 4.50 3 3/8 14
460-3-60 -4 9.7 70.0 2.5 3/4 - - 14.7 20 Water Coil
575-3-60 -5 7.7 53.0 2.6 3/4 - - 12.3 20 Type Work Press
Coaxial 450 psig
BLOWER PERFORMANCE Blower Size Compr Type
11x9 DD Scroll
Available External Static Pressure (Inches of Water, Gauge. Wet Coil and Filter Included)
Net Weight Ship Weight
Blower
0.10 0.20 0.30 0.40 0.50 0.60 0.70 0.80 0.90 1.00 1.10 1.20 363 lbs 387 lbs
Speed
High 2160 2090 2030 1960 1870 1800 1730 1680 1640 1600 1550 1500 FLUID PRESSURE DROP
Medium 2110 2040 1990 1910 1820 1760 1690 1630 1600 - - - Fluid Pressure
Low 2060 1990 1950 1860 1760 1710 1640 - - - - - Flow Drop
(GPM) (FOH) (PSIG)
ISO 13256-1 CERTIFIED PERFORMANCE DATA Rated at 2,000 CFM and 15.0 GPM 8 3.5 1.5
Water Loop Ground Water Ground Loop (Ext. Range Required) 10 5.2 2.2
Cooling Heating Cooling Heating Cooling Heating 13 8.3 3.6
Capacity EER Capacity COP Capacity EER Capacity COP Capacity EER Capacity COP 15 10.7 4.6
62,000 13.2 79,000 4.4 67,000 18.3 61,500 3.9 63,600 14.7 50,000 3.3 20 18.0 7.8

CAPACITY DATA All performance at 2,000 CFM and 15.0 GPM


EFT Range (Standard) EFT Range (Ext. Range Option) EFT Range (Standard) EFT Range (Ext. Range Option)
COOLING 50oF to 100oF 45oF to 110oF HEATING 50oF to 80oF 25oF to 80oF
Entering Entering Sensible Heat Entering Entering Heat
Fluid Air Total Sensible to Power of Fluid Air Total Power of
Temp. Temp. Capacity Capacity Total Input Reject EER Temp. Temp. Capacity Input Abs. COP
(oF) (oF) (MBtuH) (MBtuH) Ratio (kW) (MBtuH) (oF) (oF) (MBtuH) (kW) (MBtuH)
50o 58.20 37.95 0.65 3.44 69.95 16.90 50 o 68.82 5.07 51.50 3.97
60o 70odb 56.69 37.28 0.66 3.82 69.73 14.84 60o 76.95 5.30 58.86 4.26
60o
70o 61owb 55.18 36.74 0.67 4.20 69.51 13.15 70o 85.08 5.52 66.23 4.51
85o 52.92 36.17 0.68 4.76 69.17 11.11 80o 93.21 5.75 73.59 4.75
100o 50.66 35.84 0.71 5.33 68.84 9.51 50o 65.07 5.17 47.43 3.69
50o 62.36 45.39 0.73 3.46 74.18 18.01 60o 72.75 5.40 54.33 3.95
70o
60o 75odb 60.75 44.59 0.73 3.84 73.86 15.81 70o 80.43 5.62 61.24 4.19
70o 63owb 59.13 43.95 0.74 4.22 73.54 14.01 80o 88.11 5.85 68.14 4.41
85o 56.71 43.27 0.76 4.79 73.06 11.84 50o 60.66 5.28 42.64 3.37
100o 54.29 42.87 0.79 5.36 72.58 10.13 60o 67.82 5.51 49.00 3.60
80o
50o 68.45 50.12 0.73 3.49 80.36 19.62 70o 74.97 5.75 55.35 3.82
60o 80odb 66.68 49.23 0.74 3.87 79.90 17.23 80o 82.12 5.98 61.70 4.02
70o 67owb 64.91 48.53 0.75 4.25 79.43 15.26
Extended Range Option Required
85o 62.26 47.78 0.77 4.83 78.73 12.90 LOW TEMP HEATING Antifreeze Required
100o 59.60 47.35 0.79 5.40 78.04 11.04 25o 47.54 4.51 32.14 3.09
50o 74.55 54.89 0.74 3.52 86.55 21.20 30o 60o 51.52 4.62 35.74 3.26
60o 85odb 72.62 53.93 0.74 3.90 85.94 18.62 40o 59.50 4.85 42.95 3.59
70o 71owb 70.70 53.16 0.75 4.29 85.33 16.49 25o 44.96 4.59 29.28 2.87
85o 67.81 52.34 0.77 4.86 84.41 13.94 30o 70o 48.73 4.71 32.66 3.03
100o 64.92 51.86 0.80 5.44 83.50 11.93 40o 56.26 4.94 39.41 3.34
Units are complete packages containing compressor, reversing valve, capillary tube metering device, and heat exchangers. 25o 41.94 4.69 25.92 2.62
Also included are safety controls: Overload protection for motors, high and low refrigerant pressure switches and a lock-out
circuit. 30o 80o 45.44 4.81 29.02 2.77
Extended range option includes expansion valve metering device, insulated water coil and solid state lock-out controls. 40o 52.46 5.05 35.24 3.05
Performance based on ARI/ISO rated air flow, fluid flow and voltage. For conditions other than rated, consult the FHP EAD
selection software. Due to variations in installation actual performance may vary marginally from tabulated values. FHP MANUFACTURING COMPANY
As a result of continuing research and development, specifications are subject to change without notice. 601 N.W. 65th Court - Fort Lauderdale, FL 33309
EC060ip6 mod1 Rev: 05-09 Phone: (954) 776-5471 - Fax: (800) 776-5529
http://www.fhp-mfg.com
EC061
PACKAGED UNITS
SPECIFICATION DATA SHEET
FHP MANUFACTURING HIGH-EFFICIENCY WATER SOURCE HEAT PUMPS AQUARIUS SERIES
ELECTRICAL SPECIFICATIONS MECHANICAL SPECIFICATIONS
Electrical Elect. Compressor Blower Loop Pump Min. Max. Refrigerant: R-410A
Characteristics Symbol Circuit Fuse/ Air Coil
RLA LRA FLA HP FLA HP Amps Breaker Square Rows Tube Fins/
208/230-1-60 -1 29.0 145.0 5.2 3/4 41.5 60 Feet Deep O.D. Inch
208/230-3-60 -3 18.0 123.0 5.2 3/4 - - 27.7 45 4.10 3 3/8 14
460-3-60 -4 9.7 70.0 2.5 3/4 - - 14.7 20 Water Coil
Type Work Press
Coaxial 450 psig
BLOWER PERFORMANCE Blower Size Compr Type
11x9 DD Scroll
Available External Static Pressure (Inches of Water, Gauge. Wet Coil and Filter Included)
Net Weight Ship Weight
Blower
0.10 0.20 0.30 0.40 0.50 0.60 0.70 0.80 0.90 1.00 1.10 1.20 415 lbs 435 lbs
Speed
High 2160 2090 2030 1960 1870 1800 1730 1680 1640 1600 1550 1500 FLUID PRESSURE DROP
Medium 2110 2040 1990 1910 1820 1760 1690 1630 1600 - - - Fluid Pressure
Low 2060 1990 1950 1860 1760 1710 1640 - - - - - Flow Drop
(GPM) (FOH) (PSIG)
ISO 13256-1 CERTIFIED PERFORMANCE DATA Rated at 1,800 CFM and 15.0 GPM 9 4.3 1.9
Water Loop Ground Water Ground Loop (Ext. Range Required) 11 6.1 2.7
Cooling Heating Cooling Heating Cooling Heating 13 8.3 3.6
Capacity EER Capacity COP Capacity EER Capacity COP Capacity EER Capacity COP 15 10.7 4.6
59,000 13.9 68,000 4.6 63,000 19.7 55,400 4.1 61,000 15.8 44,600 3.5 20 18.0 7.8

CAPACITY DATA All performance at 1,800 CFM and 15.0 GPM


EFT Range (Standard) EFT Range (Ext. Range Option) EFT Range (Standard) EFT Range (Ext. Range Option)
COOLING 50oF to 100oF 45oF to 110oF HEATING 50oF to 80oF 25oF to 80oF
Entering Entering Sensible Heat Entering Entering Heat
Fluid Air Total Sensible to Power of Fluid Air Total Power of
Temp. Temp. Capacity Capacity Total Input Reject EER Temp. Temp. Capacity Input Abs. COP
(oF) (oF) (MBtuH) (MBtuH) Ratio (kW) (MBtuH) (oF) (oF) (MBtuH) (kW) (MBtuH)
50o 53.94 35.42 0.66 3.12 64.58 17.3 50o 59.99 4.25 45.49 4.1
60o 70 dbo
52.72 34.91 0.66 3.49 64.63 15.1 60o 66.78 4.43 51.66 4.4
60o
70o 61owb 51.50 34.54 0.67 3.87 64.69 13.3 70o 73.58 4.61 57.83 4.7
85o 49.67 34.20 0.69 4.43 64.77 11.2 80o 80.37 4.80 64.00 4.9
100o 47.84 34.12 0.71 4.99 64.85 9.6 50o 56.75 4.32 42.01 3.8
50o 57.84 42.47 0.73 3.13 68.53 18.5 60o 63.17 4.51 47.79 4.1
70o
60o 75odb 56.53 41.86 0.74 3.51 68.51 16.1 70o 69.59 4.69 53.57 4.3
70o 63owb 55.23 41.42 0.75 3.89 68.49 14.2 80o 76.01 4.88 59.35 4.6
85o 53.27 41.02 0.77 4.45 68.45 12.0 50o 52.95 4.41 37.90 3.5
100o 51.31 40.91 0.80 5.01 68.42 10.2 60o 58.93 4.60 43.22 3.8
80o
50o 63.54 46.95 0.74 3.16 74.32 20.1 70o 64.91 4.79 48.55 4.0
60o 80odb 62.11 46.28 0.75 3.54 74.18 17.6 80o 70.89 4.99 53.87 4.2
70o 67owb 60.68 45.79 0.75 3.91 74.04 15.5
Extended Range Option Required
85o 58.53 45.35 0.77 4.48 73.83 13.1 LOW TEMP HEATING Antifreeze Required
100o 56.39 45.24 0.80 5.05 73.63 11.2 25o 42.16 3.79 29.23 3.3
50o 69.25 51.48 0.74 3.18 80.10 21.8 30o 60o 45.49 3.88 32.24 3.4
60o 85odb 67.69 50.75 0.75 3.56 79.85 19.0 40o 52.15 4.06 38.28 3.8
70o 71owb 66.13 50.21 0.76 3.94 79.59 16.8 25o 39.90 3.85 26.75 3.0
85o 63.80 49.73 0.78 4.52 79.21 14.1 30o 70o 43.05 3.95 29.58 3.2
100o 61.46 49.61 0.81 5.09 78.84 12.1 40o 49.35 4.13 35.24 3.5
Units are complete packages containing compressor, reversing valve, capillary tube metering device, and heat exchangers. 25o 37.26 3.93 23.84 2.8
Also included are safety controls: Overload protection for motors, high and low refrigerant pressure switches and a lock-out
circuit. 30o 80o 40.19 4.03 26.44 2.9
Extended range option includes expansion valve metering device, insulated water coil and solid state lock-out controls. 40o 46.05 4.22 31.65 3.2
Performance based on ARI/ISO rated air flow, fluid flow and voltage. For conditions other than rated, consult the FHP EAD
selection software. Due to variations in installation actual performance may vary marginally from tabulated values. FHP MANUFACTURING COMPANY
As a result of continuing research and development, specifications are subject to change without notice. 601 N.W. 65th Court - Fort Lauderdale, FL 33309
EC061ip6 mod1 Rev: 6-04 Phone: (954) 776-5471 - Fax: (800) 776-5529
http://www.fhp-mfg.com
EC070
PACKAGED UNITS
SPECIFICATION DATA SHEET
FHP MANUFACTURING HIGH-EFFICIENCY WATER SOURCE HEAT PUMPS AQUARIUS SERIES
ELECTRICAL SPECIFICATIONS MECHANICAL SPECIFICATIONS
Electrical Elect. Compressor Blower Loop Pump Min. Max. Refrigerant: R-410A
Characteristics Symbol Circuit Fuse/ Air Coil
RLA LRA FLA HP FLA HP Amps Breaker Square Rows Tube Fins/
208/230-1-60 -1 28.8 169.0 5.0 3/4 - - 41.0 70 Feet Deep O.D. Inch
208/230-3-60 -3 19.3 129.0 5.0 3/4 - - 29.1 40 6.00 3 3/8 14
460-3-60 -4 9.7 75.0 2.5 3/4 - - 14.7 20 Water Coil
Type Work Press
Coaxial 450 psig
BLOWER PERFORMANCE Blower Size Compr Type
11x9 DD Scroll
Available External Static Pressure (Inches of Water, Gauge. Wet Coil and Filter Included)
Net Weight Ship Weight
Blower
0.10 0.20 0.30 0.40 0.50 0.60 0.70 0.80 0.90 1.00 1.10 1.20 427 lbs 452 lbs
Speed
High 2260 2229 2202 2177 2139 2093 2040 1977 1917 1855 1790 1729 FLUID PRESSURE DROP
Medium 1990 1961 1945 1930 1908 1876 1838 1795 1750 1700 1646 - Fluid Pressure
Low 1720 16902 1687 1682 1677 1659 1635 1613 1583 1545 - - Flow Drop
(GPM) (FOH) (PSIG)
ISO 13256-1 CERTIFIED PERFORMANCE DATA Rated at 2,200 CFM and 16.0 GPM 8 4.3 1.9
Water Loop Ground Water Ground Loop 10 6.4 2.8
Cooling Heating Cooling Heating Cooling Heating 12 8.9 3.8
Capacity EER Capacity COP Capacity EER Capacity COP Capacity EER Capacity COP 16 14.9 6.5
68,000 13.5 80,000 4.5 76,000 19.8 68,000 4.0 70,000 15.2 53,000 3.3 20 22.3 9.6

CAPACITY DATA All performance at 2,200 CFM and 16.0 GPM


EFT Range (Standard) EFT Range (Standard)
COOLING 45oF to 110oF HEATING 25oF to 80oF
Entering Entering Sensible Heat Entering Entering Heat
Fluid Air Total Sensible to Power of Fluid Air Total Power of
Temp. Temp. Capacity Capacity Total Input Reject EER Temp. Temp. Capacity Input Abs. COP
(oF) (oF) (MBtuH) (MBtuH) Ratio (kW) (MBtuH) (oF) (oF) (MBtuH) (kW) (MBtuH)
50o 66.64 44.01 0.66 3.53 78.67 18.9 50 o 71.44 5.01 54.33 4.2
60o 70odb 64.14 42.71 0.67 3.95 77.64 16.2 60o 78.97 5.18 61.31 4.5
60o
70o 61owb 61.64 41.57 0.67 4.38 76.60 14.1 70o 86.50 5.34 68.29 4.7
85o 57.90 40.07 0.69 5.02 75.05 11.5 80o 94.04 5.50 75.26 5.0
100o 54.16 38.79 0.72 5.67 73.50 9.6 50o 67.55 5.10 50.13 3.9
50o 71.40 52.62 0.74 3.55 83.50 20.1 60o 74.67 5.27 56.68 4.2
70o
60o 75odb 68.73 51.08 0.74 3.98 82.30 17.3 70o 81.78 5.43 63.23 4.4
70o 63owb 66.06 49.71 0.75 4.41 81.10 15.0 80o 88.90 5.60 69.78 4.7
85o 62.05 47.93 0.77 5.05 79.30 12.3 50o 62.98 5.22 45.18 3.5
100o 58.05 46.41 0.80 5.70 77.50 10.2 60o 69.61 5.38 51.23 3.8
80o
50o 78.37 58.10 0.74 3.57 90.57 21.9 70o 76.24 5.55 57.28 4.0
60o 80odb 75.44 56.40 0.75 4.01 89.12 18.8 80o 82.86 5.72 63.33 4.2
70o 67owb 72.52 54.89 0.76 4.44 87.67 16.3
85o 68.12 52.93 0.78 5.09 85.51 13.4 LOW TEMP HEATING Antifreeze Required

100o 63.73 51.25 0.80 5.74 83.34 11.1 25o


51.58 4.61 35.85 3.3
50o 85.34 63.63 0.75 3.60 97.63 23.7 30o 60o 55.27 4.69 39.27 3.5
60o 85odb 82.16 61.77 0.75 4.04 95.94 20.3 40o 62.65 4.85 46.10 3.8
70o 71owb 78.97 60.12 0.76 4.48 94.25 17.6 25o 48.78 4.69 32.78 3.0
85o 74.20 57.98 0.78 5.13 91.71 14.5 30o 70o 52.27 4.77 35.98 3.2
100o 69.42 56.14 0.81 5.79 89.18 12.0 40o 59.25 4.94 42.40 3.5
Units are complete packages containing compressor, reversing valve, expansion valve metering device, and heat 25o 45.50 4.79 29.15 2.8
exchangers. Also included are safety controls: Overload protection for motors, high and low refrigerant pressure
switches and a lock-out circuit. 30o 80o 48.75 4.88 32.11 2.9
Extended range option includes insulated water coil and solid state lock-out controls. 40o 55.25 5.05 38.03 3.2
Performance based on ARI/ISO rated air flow, fluid flow and voltage. For conditions other than rated, consult the FHP EAD
selection software. Due to variations in installation actual performance may vary marginally from tabulated values. FHP MANUFACTURING COMPANY
As a result of continuing research and development, specifications are subject to change without notice. 601 N.W. 65th Court - Fort Lauderdale, FL 33309
EC070ip6 mod1 Rev: 01-09 Phone: (954) 776-5471 - Fax: (800) 776-5529
http://www.fhp-mfg.com