Location via proxy:   [ UP ]  
[Report a bug]   [Manage cookies]                

Digital Earth Resistance Tester: AC V DC V

Download as pdf or txt
Download as pdf or txt
You are on page 1of 2

Digital Earth Resistance Tester

Ideal for earth rods and lightning conductors

Technical Datasheet
MT330
The MT330 is an ideal earth resistance tester for the measurement
of earth rods and lighting conductors. New ranges have been
included such as AC voltage measurement up to 750V and DC
voltage up to 1000V, plus a 200kΩ resistance range. The large
backlit dual display LCD indicates the range measured as well as
the battery voltage. The advanced circuit design permits the
instrument to operate with minimum influence from earth voltage
and earth resistance of auxiliary spikes. The double mould rubber
injection housing ensures that the meter can handle the rough
terrain when used in the field while performing earth tests.

AUTO
Ω LCD 0 AC DC H
Auxiliary Spike
Tolerance
Direct
Readout
One Touch Zero
Adjustment V V Data Hold

Specifications Detailed specifications on page 2

FUNCTION RANGE
Earth Resistance Range 20Ω, 200Ω, 2000Ω

Display Large LCD with dual display

Multimeter 200kΩ, 750VAC, 1000VDC


Function Range

Sampling Rate 2.5 times per second

Zero Adjustment Automatic adjustment

IEC IEC Overrange Indicator Number 1 of highest digit is displayed


61010-1 61010-1
CAT lll CAT lV Low Battery Indication The " " is displayed when the battery voltage
1000V 600V drops below the operating voltage.

Auto Power Off To conserve battery life, the meter will


automatically turn off after approx.
15 minutes of non-use. To turn the meter back on,
turn the rotary switch to OFF, then to the desired
Features function.
Ÿ Earth Resistance 200Ω
Ÿ Earth voltage to 200V Operating 0°C to 40°C (32°F to 104°F) and humidity below
Ÿ Indicates if resistance of auxiliary spikes is within tolerance Temperature 80% RH
Ÿ Direct readout of the earth resistance on the LCD display
Ÿ 750V AC, 1000V DC Storage -10°C to 60°C (14°F to 140°F) and humidity below
Ÿ Overrange indicator Temperature 70% R
Ÿ Zero adjustment of leads
Ÿ Data Hold Power source 6 X 1.5V Size "AA" battery or equivalent (DC9V)
Ÿ Overmould casing
Dimensions 200(L) X 92(W) X 50(H) mm
Ÿ Dual LCD with backlight
Ÿ Ideal for earth rods and lightning conductors
Weight 582g

Standard Accessories
Test leads, 6pcs AA battery, rubber holster, 4-wire cable and iron rod x 2, carrying case,
instruction manual.

Ordering Information Join us on Facebook


Digital Earth Resistance Tester
Ideal for earth rods and lightning conductors

Technical Datasheet

Earth resistance 200Ω Direct readout of earth 750V AC; 1000V DC


resistance on LCD display

Measurement Range Resolution Accuracy


Earth Resistance 20Ω 0.01Ω ± (2% + 10d)
200Ω 0.1Ω ± (2% + 3d)
2000Ω 1Ω ± (2% + 3d)
Earth Voltage 200V 0.1V ± (3% + 3d)
Measurement Range Resolution Accuracy Overload Protection
OHMS 200kΩ 0.1kΩ ± (1% + 2d) 250Vrms
Measurement Range Resolution Accuracy Input Impedance Overload Protection
DC Voltage 1000V 1V ± (0.8% + 3d) 10MΩ 1000Vrms
AC Voltage
750V 1V ± (1.2% + 10d) 10MΩ 750Vrms
(40Hz ~ 400Hz)

Standard Accessories
Test leads, 6pcs AA battery, rubber holster, 4-wire cable and iron rod x 2, carrying case,
instruction manual.

Ordering Information Join us on Facebook