10 Amp Digital Low Resistance: Dlro10Hdx

Download as pdf or txt
Download as pdf or txt
You are on page 1of 4

DLRO10HDX

10 A Digital Low Resistance Ohmmeter

DLRO10HDX
10 Amp Digital Low Resistance
■■ NEW Onboard memory storage for test
results up to 200 records (HDX only)
■■ Download to PowerDB
■■ NEW interchangeable test lead terminations
■■ High or low output power selection for
condition diagnosis
■■ Operates from battery or AC mains supply
■■ Protected to 600 V without blowing a fuse,
test lead live voltage warning light
■■ Heavy duty case: IP 65 lid closed,
IP54 operational
■■ Simple rotary switch selection of five test
modes, including auto start on connection

DESCRIPTION ADDITONAL FEATURES AND BENEFITS


Augmenting Megger’s DLRO10 and 10X range the nn Rugged case well suited to transportation with shoulder
DLRO10HDX combines ultimate simplicity of operation with strap and lead set pouch
a rugged IP65 case designed for stable ground and bench nn Removable lid facilitates easy test lead connection
operation and provides memory storage.
nn Operational ingress protection is IP 54 (battery power only)
These units are powered from either rechargeable battery ensuring protection from the elements
or mains power making it suitable for continuous testing in
nn 7Ah lead acid battery provides extended operation and can
production line/repetitive use environments.
be charged whilst operating from line power
Rotary switch controls are simple and easy to operate in all
nn Rotary mode switch with bidirectional (current reversal with
weather conditions and with gloved hands. A large, clear,
averaging cancels thermal EMFs), unidirectional, automatic,
backlit LCD display is easy to read from a distance. The
continuous and inductive modes
DLRO10HDX provides significantly enhanced compliance
and is capable of delivering 10 A into measurements up nn Large, clear LCD display with backlight and contrast
to 250 mΩ and 1 A into measurements up to 2.5 Ω. The adjustment
duration of each test may be up to 60 seconds. nn Auto power off function conserves battery
The DLRO10HDX is rated CAT III 300 V provided the
optional terminal cover is fitted to the instrument. Details of APPLICATIONS
which can be found in the ordering information panel of this
The DLRO10HDX measures low resistance values in applications
data sheet.
ranging from railways and aircraft to resistance of components
The DLRO10HDX provides five test modes each of which is in industry.
selected through a simple rotary control on the Mode selection
Any metallic joint can be measured but users must be aware of
rotary switch. All memory functions, delete, download to
measurement limitations depending on application. For example,
PowerDB and recalling test results are also accessible via the
if a cable manufacturer plans to make resistive measurements
Range Selection rotary switch.
on a thin wire, a low test current should be selected to prevent
A simple control panel enables easy navigation for heating the wire thereby changing its resistance.
configuration settings.
DLRO10HDX
10 A Digital Low Resistance Ohmmeter
Measurements on electric motors and generators will ELECTRICAL SPECIFICATIONS
be inductive and require the user to understand the
Resistance/Current Ranges
inductive mode and charging process before a correct result
is achieved. The green resistance ranges on the keypad indicate low
output power (<0.25 W) outputs. Red ranges indicate higher
2.5 W (1 A) and 25 W (10 A) power outputs.
The DLRO10HDX is well suited to measuring thick conductors,
bonds and quality of welding because of its 10 A range for
resistance values up to 250 mΩ. Resolution and Accuracy
Test current accuracy ±10%
Electromagnetic noise induced into the leads can interfere Voltmeter input impedance >200 kΩ
with a reading. A noise symbol alerts the user and prevents
Resolution Full Max.
a measurement when the instrument detects noise above its Test Resistance Basic
(as scale power
threshold. current range accuracy*
displayed) voltage output
0.1 0 to
0.1 Ω ±0.2% 25 mV 25 μW
When dissimilar metals are joined a thermocouple effect is mA 2500.0 Ω
created. Users should select a bidirectional mode to ensure 0.1 0 to
cancellation of this effect. The instrument measures with 0.01 Ω ±0.2% 25 mV 2.5 μW
mA 250.00 Ω
current flowing in both directions and averages the result. 0 to
1 mA 1 mΩ ±0.2% 25 mV 25 μW
25.000 Ω
Normal mode is initiated by pressing the ‘Test’ button after 0 to
10 mA 0.1 mΩ ±0.2% 25mV 250 μW
connecting the test leads to the unit under test. Continuity 2500.0 mΩ
of all four connections is checked. Current is applied in both 100 0 to
0.01 mΩ ±0.2% 25 mV 2.5 mW
forward and reverse direction following which measurement mA 250.00 mΩ
is displayed. 0 to
1A 1 μΩ ±0.2% 25 mV 25 mW
25.000 mΩ
0 to
Automatic mode is started as soon as the probes make 10 A 0.1 μΩ ±0.2% 25 mV 0.25 W
2500.0 µΩ
contact. Forward and reverse current measurements are made
0 to
and the average value is displayed. This mode is ideal when 1A 0.1 mΩ ±0.2% 2.5 V 2.5 W
2500.0 mΩ
working with handspikes. Each time the probes are removed
0 to
and reconnected to the load a new test will be performed 10 A 0.01 mΩ ±0.2% 2.5 V 25 W
250.00 mΩ
without the need to press the test button.

TEST modes * The accuracy stated assumes forward and reverse


Automatic unidirectional mode applies current in one measurements.
direction only to speed up the measurement process. Inductive mode or undirectional mode will introduce an
However thermal EMF resulting from dissimilar metal bonds undefined error if an external EMF is present.
can cause lower accuracy. Test starts automatically when Basic accuracy at reference conditions.
probes are connected.
GENERAL SPECIFICATIONS
Continuous mode allows repeated measurements to be made Temperature coefficient < 0.01% per ºC, from 5 ºC to
on the same sample. Simply connect the test leads and press 40 ºC
the test button. The measurement is updated every three
Maximum altitude 2000 m (6562 ft) to full safety
seconds until the circuit is broken.
specifications
Display size/type Main 5 digit + 2 x 5 digit
Inductive mode is selected when measuring resistance on, for
example, motors and generators. When measuring inductive secondary displays
loads it is necessary to wait for the voltage to stabilise as the Battery type 6 V, 7Ah sealed lead acid
inductive element is charged. Test leads are firmly connected
to the device under test and the ‘Test’ button pressed. The Voltage input range 100 - 240 V 50 / 60 Hz 90 VA
instrument will pass the selected current through the sample Charge time 8 hours
continuously in one direction only and take repetitive readings
that will gradually decrease to the true value as the voltage Backlight LED backlight
stabilises. The operator decides when the result is stable and Battery life >1000 Auto (3 sec) tests
presses the ‘Test’ button to terminate the test.
DLRO10HDX
10 A Digital Low Resistance Ohmmeter
Auto power down 300s OPTIONAL TERMINAL COVER
Mode selection Rotary switch
The CAT III 300 V rating on the
Range selection Rotary switch
DLRO10HDX is only valid when
Memory features selection Rotary switch the instrument is fitted with
the optional terminal cover to
Weight 6.7 kg (14.8 lb)
provide the required creepage
Case dimensions L 315 x W 285 x H 181 mm and clearances at the instrument
(L 12 x W 11 x H 7 in.) terminals. Although the terminal
cover may be used with any test
Pouch for test leads Yes (lid mounted)
leads, only the Megger DH4,
Test leads included depending on DH5 and DP1-C duplex handspikes, and KC2-C insulated
chosen option: kelvin clips have suitable probe insulation to comply with the
DH4C lead set requirements of IEC61010-1 and the CATIII 300 V rating.
KC1 Kelvin Clip lead set
IP rating IP65 case closed, IP54 battery
operation
Record storage 200 test records
Safety rating
In accordance with IEC61010-1, CATIII 300V when used
with optional terminal cover (details in ordering information)
Operating temperature and humidity
-10 °C to +50 °C
(14 °F to 122 °F) <90% RH
Reference conditions 20 °C ±3 °C (68 °F ±37 °F) SUPPLIED LEADSET OPTIONS
Storage temperature and humidity
-25 °C to +60 °C (-13 °F to +60 °F), <90% RH
EMC
In accordance with IEC61326-1 (Heavy industrial)
Noise rejection
Less than 1% ±20 digits additional error with 100 mV peak
50/60 Hz. on the potential leads. Warning will show if hum
DLRO10HDX
or noise exceeds this level.
Maximum lead resistance
100 mΩ total for 10 A operation irrespective of battery
condition.

+ DH4-C probe 1.5 m leads 

+ KC1 Kelvin clip 3 m leads


+ No test leads supplied 
DLRO10HDX
10 A Digital Low Resistance Ohmmeter
ORDERING INFORMATION
Item (Qty) Order No. Item (Qty) Order No.
DLRO10HDX 1008-075 Duplex Heavy Duty 5cm (2”) C-Clamps. (2)
2m/7ft 242004-7
Standard included accessories
Duplex Heavy Duty 5cm (2”) C-Clamps. (2)
Test lead pouch (lid mounted) 1000-036 5.5m/18ft 242004-18
DLRO10HDX user guide CD Duplex Heavy Duty 5cm (2”) C-Clamps. (2)
9m/30ft 242004-30

Optional Accessories at extra cost


Calibration Shunt,10 Ω, current rating 1 mA. 249000 Duplex handspikes with replaceable
Needle Points 2m/7ft 242003-7
Calibration Shunt, 1 Ω, current rating 10 mA. 249001

Calibration Shunt, 100 mΩ current rating 1A. 249002
Duplex 1.27 cm (1/2 “) Kelvin Clips. (2)
Calibration Shunt, 10 mΩ current rating 10 A. 249003 gold plated 2m/7ft 241005-7
Certificate of Calibration for Shunts, NIST CERT-NIST Duplex 1.27 cm (1/2 “) Kelvin Clips. (2)
silver plated 2m/7ft 242005-7

Optional Test Leads at extra cost


Duplex 3.8 cm (11/2”) Kelvin Clips. (2)
Normal test leads not fitted with in-line connector:
2m/7ft 242006-7
Duplex Leads
Duplex 3.8 cm (11/2”) Kelvin Clips. (2)
DH5 straight duplex handspikes (2) 5.5m/18ft 242006-18
One has indicator lights. 2.5m/8ft 6111-517 Duplex 3.8 cm (11/2”) Kelvin Clips. (2)
Terminal cover (use in conjunction with DH4 test leads 9m/30ft 242006-30
supplied as standard, or optional DH5 test leads for
CATIII 300 V compliance 1002-390 Single handspike (1) for potential measurement.
Duplex Handspikes (2) with spring loaded helical contacts 2m/7ft 242021-7
2m/7ft 242011-7 Single handspike (1) for potential measurement.
5.5m/18ft 242021-18
DH1 2.5m/8ft 1008-026 Single handspike (1) for potential measurement.
DH1 5.5m/18ft 242011-18 9m/30ft 242021-30
Current clip (1) for current connections.
2m/7ft 242041-7
DH2 6m/20ft (only 1 lead supplied) 1008-027
Current clip (1) for current connections
DH2 9m/30ft (only 1 lead supplied) 242011-30 5.5m/18ft 242041-18
Current clip (1) for current connections
Straight Duplex Handspikes (2) Heavy Duty 9m/30ft 242041-30
with fixed contacts. 2m/7ft 242002-7
Straight Duplex Handspikes (2) Heavy Duty
with fixed contacts 5.5m/18ft 242002-18
Straight Duplex Handspikes (2) Heavy Duty
with fixed contacts 9m/30ft 242002-30

SALES OFFICE DLRO10HDX_DS_US_V01


Megger USA - www.megger.com
Valley Forge Corporate Center ISO 9001
2621 Van Buren Avenue, Norristown,
The word ‘Megger’ is a registered trademark
Pennsylvania, 19403, USA
T. 1-610 676 8500
F. 1-610-676-8610

You might also like