160 67-N2 PDF
160 67-N2 PDF
160 67-N2 PDF
MODEL YST
UNITS MANUFACTURED AFTER DECEMBER 2006
LD12189
Issue Date:
January 10, 2014
FORM 160.67-N2
ISSUE DATE: 1/10/2014
IMPORTANT!
READ BEFORE PROCEEDING!
GENERAL SAFETY GUIDELINES
This equipment is a relatively complicated apparatus. which it is situated, as well as severe personal injury or
During installation, operation maintenance or service, death to themselves and people at the site.
individuals may be exposed to certain components or
conditions including, but not limited to: refrigerants, This document is intended for use by owner-authorized
materials under pressure, rotating components, and operating/service personnel. It is expected that these
both high and low voltage. Each of these items has the individuals possess independent training that will en-
potential, if misused or handled improperly, to cause able them to perform their assigned tasks properly and
bodily injury or death. It is the obligation and respon- safely. It is essential that, prior to performing any task
sibility of operating/service personnel to identify and on this equipment, this individual shall have read and
recognize these inherent hazards, protect themselves, understood this document and any referenced mate-
and proceed safely in completing their tasks. Failure rials. This individual shall also be familiar with and
to comply with any of these requirements could result comply with all applicable governmental standards and
in serious damage to the equipment and the property in regulations pertaining to the task in question.
SAFETY SYMBOLS
The following symbols are used in this document to alert the reader to specific situations:
External wiring, unless specified as an optional connection in the manufacturer’s product line, is not
to be connected inside the control cabinet. Devices such as relays, switches, transducers and controls
and any external wiring must not be installed inside the micro panel. All wiring must be in accor-
dance with Johnson Controls’ published specifications and must be performed only by a qualified
electrician. Johnson Controls will NOT be responsible for damage/problems resulting from improper
connections to the controls or application of improper control signals. Failure to follow this warn-
ing will void the manufacturer’s warranty and cause serious damage to property or personal injury.
2 JOHNSON CONTROLS
FORM 160.67-N2
ISSUE DATE: 1/10/2014
ASSOCIATED LITERATURE
MANUAL DESCRIPTION FORM NUMBER
Operation & Maintenance 160.67-O2
Wiring Diagram - Model YST - Field Control Modifications 160.67-PW2
Wiring Diagram - Model YST - Floor Mounted Steam Condenser 160.67-PW4
Wiring Diagram - Model YST - Top Mounted Steam Condenser 160.67-PW5
Wiring Diagram- Model YST 160.67-PW6
Renewal Parts - Unit Components 160.67-RP1
Renewal Parts - Controls and Instrumentation 160.67-RP2
Engineering Guide 160.67-EG1
JOHNSON CONTROLS 3
FORM 160.67-N2
ISSUE DATE: 1/10/2014
NOMENCLATURE
The model number denotes the following characteristics of the unit.
4 JOHNSON CONTROLS
FORM 160.67-N2
ISSUE DATE: 1/10/2014
TABLE OF CONTENTS
SECTION 1 - INTRODUCTION..................................................................................................................................9
Field Assembled Units ...................................................................................................................................... 9
Inspection - Damage - Shortage....................................................................................................................... 9
Shipment........................................................................................................................................................... 9
Turbine Bearing Disassembly To Remove Mylar Shipping Film...................................................................... 12
Flow Rates...................................................................................................................................................... 12
Chilled Water................................................................................................................................................... 13
Refrigerant Condenser Water Circuit.............................................................................................................. 13
Steam Condenser Package............................................................................................................................ 13
Floor Mounted Steam Condenser (Optional).................................................................................................. 13
Steam Turbine Casing Drain Options.............................................................................................................. 13
Remote Steam Turbine Gaugeboard (Optional - Field Installed).................................................................... 14
Chiller Data Plate...................................................................................................................................14
Location..................................................................................................................................................14
Clearance...............................................................................................................................................14
Installation Check - Request For Start-Up Service..........................................................................................14
SECTION 2 - RIGGING............................................................................................................................................15
Chiller Rigging - (Less Surface Condenser).................................................................................................... 15
Steam Condenser Package Rigging............................................................................................................... 17
Rigging Unit To Final Location......................................................................................................................... 17
Locating And Installing Isolator Pads.............................................................................................................. 17
Checking The Isolation Pad Deflection........................................................................................................... 17
Leveling The Unit............................................................................................................................................ 17
JOHNSON CONTROLS 5
FORM 160.67-N2
ISSUE DATE: 1/10/2014
6 JOHNSON CONTROLS
FORM 160.67-N2
ISSUE DATE: 1/10/2014
LIST OF FIGURES
JOHNSON CONTROLS 7
FORM 160.67-N2
ISSUE DATE: 1/10/2014
8 JOHNSON CONTROLS
FORM 160.67-N2
ISSUE DATE: 1/10/2014
SECTION 1 - INTRODUCTION 1
This instruction describes the installation of the YORK INSPECTION - DAMAGE - SHORTAGE
Model YST Centrifugal Liquid Chiller Unit. This unit
The unit shipment should be checked on arrival to see
is completely factory-packaged including; the evapo-
that all major pieces, boxes and crates are received.
rator, refrigerant condenser, compressor, steam turbine,
Each unit should be checked on the trailer or rail car
lubrication systems, power panel, control center, and
when received, before unloading, for any visible signs
all interconnecting unit piping and wiring.
of damage. Any damage or signs of possible damage
The steam condenser package is shipped separately and must be reported to the transportation company imme-
suitable for direct mounting onto the chiller or mount- diately for their inspection.
ing along side the chiller. Refrigerant and oil charges JOHNSON CONTROLS will not be re-
shipped separately unless optional refrigerant condens- sponsible for any damage in shipment
er isolation valves and Form 1 shipment are ordered. or at job site or loss of parts. (Refer to
Chillers shipped dismantled MUST be field assembled shipping damage claims, form 50.15-NM)
under the supervision of a Johnson Controls represen-
tative, but otherwise installation will be as described in
this instruction. When received at the job site all containers should be
opened and contents checked against the packing list.
FIELD ASSEMBLED UNITS Any material shortage should be reported to YORK
A Johnson Controls representative must be used to immediately.
check the installation, supervise the initial start-up and
operation of all chillers installed within Continental SHIPMENT
United States. Units shipped dismantled MUST be re-
The Johnson Controls Warranty may be assembled by, or under the supervision
voided if the following restrictions are not of, a Johnson Controls representative.
adhered to:
1. No valves or connections should be
opened under any circumstances because The chiller may be ordered and shipped in any of the
such action will result in loss of the factory following forms:
nitrogen charge.
Form 1 - Factory Assembled Unit. (steam condenser
2. Do not dismantle or open the chiller for
package shipped separately) refrigerant and oil are fac-
any reason except under the supervision
tory charged.
of a Johnson Controls representative.
3. When units are shipped dismantled, 1. The compressor/turbine driveline assembly
notify the nearest Johnson Controls of- mounted, with all necessary interconnecting pip-
fice in ample time for Johnson Controls ing assembled. OptiView ™ Control Center is
representative to supervise rigging the unit mounted on the unit. Complete unit factory leak
to its operating position and the assembly tested, evacuated and charged with R-134a.
of components. 2. Miscellaneous material - Partial pre-fabricated
4. Do not make final power supply con- steam exhaust piping and four (4) neoprene isola-
nections to the power panel. tion pads.
5. Do not charge the compressor with oil. Form 2 - Factory Assembled Unit. (steam condenser
6. Do not charge the unit with refrigerant. package shipped separately.) Refrigerant and oil charg-
es shipped separately.
7. Do not attempt to start the system.
8. Do not run hot water (110°F / 43°C
max) or steam through the evaporator or
refrigerant condenser at any time.
JOHNSON CONTROLS 9
FORM 160.67-N2
SECTION 1 - INTRODUCTION
ISSUE DATE: 1/10/2014
STEAM TURBINE
VACUUM BREAKER
SOLENOID VALVE
STEAM CONDENSER
PACKAGE
TURBINE OIL
COOLING WATER
INLET VALVE
LD12215
10 JOHNSON CONTROLS
FORM 160.67-N2
SECTION 1 - INTRODUCTION
ISSUE DATE: 1/10/2014
ATMOSPHERIC RELIEF
VALVE
STEAM CONDENSER
PACKAGE
CONDENSATE
OVERBOARD
VALVE
CONDENSATE
RECIRCULATION
VALVE
HOTWELL
CONDENSATE
PUMP #1
120/460VAC
JUNCTION BOX
HOTWELL
CONDENSATE PUMP #2
(OPTIONAL) VACUUM PUMP #1
HOTWELL
CONDENSATE LEVEL VACUUM PUMP #2
INDICATOR / TRANSMITTER
VACUUM PUMP #2
SEALING WATER
SOLENOID VALVE
VACUUM PUMP #2
SEALING WATER
FLOW SWITCH
LD12216
JOHNSON CONTROLS 11
FORM 160.67-N2
SECTION 1 - INTRODUCTION
ISSUE DATE: 1/10/2014
1. The compressor/turbine driveline assembly When more than one chiller is involved, the major
mounted, with all necessary interconnecting pip- parts of each unit will be marked to prevent mixing of
ing assembled. OptiView ™ Control Center is assemblies. Both shells and driveline for a specific unit
mounted on the unit. Complete unit factory leak will be marked with the sales order and alphabetic let-
tested, evacuated and charged with holding charge ter for identification.
of nitrogen.
For example; order number 06-123456-01A, both
2. Miscellaneous material - Partial pre-fabricated shells and driveline will be painted with the identi-
steam exhaust piping and four (4) neoprene isola- fication 06-123456-01A. The next set of shells and
tion pads. driveline will have the sales order with letter B, such as
06-123456-01B.
Form 3 - The compressor/turbine driveline assembly
is separate from the shells - Shipped as three major TURBINE BEARING DISASSEMBLY TO
assemblies. Unit first factory assembled, refrigerant REMOVE MYLAR SHIPPING FILM
piped, wired and leak tested; then dismantled for ship-
Mylar shipping film must be removed
ment. The compressor/turbine driveline assembly is re-
from bearings before any attempts are
moved from the shells and skidded. Evaporator/Refrig-
made to rotate turbine shaft.
erant Condenser is not skidded. The Steam Condenser
package is shipped separately.
All wiring integral with compressor is left on it, and
all conduit is left on shell. Turbine lube system/piping The Murray turbine will be shipped with a Mylar ship-
remains on the driveline skid. All openings on com- ping film between the top bearing assembly and the
pressor, oil separator, and shells are closed and charged turbine shaft on both ends of the turbine. This Mylar
with dry nitrogen (2 to 3 PSIG) (14-21kPa). film should be removed from both capsules before any
attempts are made to rotate the turbine shaft. The bear-
Miscellaneous packaging of control center, tubing, wa-
ing housing and bearing top cap will have to be re-
ter temperature controls, wiring, oil, etc.; refrigerant
moved in order to remove the Mylar film. Care must be
charge shipped separately. Partial pre-fabricated steam
taken during the removal of the mylar film to protect
exhaust piping and neoprene isolation pads are shipped
the vibration probes (if supplied), temperature sensors,
loose.
and other electrical connections that are present on the
Form 7 - Split Shells - Shipped as four major assem- bearing housings. When re-assembling the bearing
blies. Unit first factory assembled, refrigerant piped, housing components, a sealant equal to Tite Seal joint
wired and leak tested; then dismantled for shipment. sealing compound or Permatex Hylomar HPF product
Compressor/turbine driveline assembly removed from will properly seal the split line of the bearing capsule.
shells and skidded. The Steam Condenser package is
shipped separately. FLOW RATES
For normal water chilling duty, evaporator and refrig-
Evaporator and refrigerant condenser shells are sepa-
erant condenser flow rates are permitted at water ve-
rated at tube sheets and are not skidded. Refrigerant
locity levels in the heat exchangers tubes between 3 ft/
lines between shells are flanged and capped, requiring
sec and 12 ft/sec (0.9 m/s and 3.7 m/s). Variable flow
no welding. All wiring integral with compressor is left
applications are possible, however, chiller selections
on it.
must be made using a water velocity within the range
All wiring harnesses on shells are removed. Turbine noted above.
lube system/piping remains on driveline skid. All open- Variable flow in the refrigerant condenser is not recom-
ings on compressor and shells are closed and charged mended, as it generally raises the energy consumption of
with dry nitrogen (2 to 3 PSIG) (14-21kPa). the system by keeping the refrigerant condenser pressure
Miscellaneous packaging of control center, tubing, high in the chiller. Additionally, the rate of fouling in the
water temperature controls, wiring, oil, etc; refrigerant refrigerant and steam condensers will increase at lower
charge shipped separately. Partial pre-fabricated steam water velocities associated with variable flow, raising
exhaust piping and neoprene isolation pads are shipped system maintenance costs. Cooling towers typically
loose. have narrow ranges of operation with respect to flow
rates and will be more effective with full design flow.
12 JOHNSON CONTROLS
FORM 160.67-N2
SECTION 1 - INTRODUCTION
ISSUE DATE: 1/10/2014
CHILLED WATER and crates are received. Each Steam Condenser pack-
age should be checked on the trailer or rail car when 1
Foreign objects which could lodge in, or block flow
received, before unloading, for any visible signs of
through the evaporator and refrigerant condenser tubes
damage. Any damage or signs of possible damage must
must be kept out of the water circuit. All water piping
be reported to the transportation company immediately
must be cleaned or flushed before being connected to
for their inspection.
the chiller, or other equipment.
When the optional factory piping kit is ordered for the
Thermal type water flow switches are factory mounted steam exhaust trunk, lifting lugs are provided loose
in the chilled and condensed water nozzles and are fac- with the piping to be located and welded at the job site,
tory wired to the OptiView ™ control panel. These sol- in a suitable location to enable the rigging of the major
id-state flow sensors have a small internal heating ele- piping assemblies. The optional piping kit is provided
ment and use the cooling effect of the flowing fluid to as partial pre-fabricated to be final trimmed/fitted and
sense when an adequate flow rate has been established. welded at the site. Welding back-up rings are provided
with the piping kit.
REFRIGERANT CONDENSER WATER
CIRCUIT FLOOR MOUNTED STEAM CONDENSER
The chiller is engineered for maximum efficiency at (Optional)
both design and part load operation by taking advantage As an alternative to the standard YST arrangement,
of the colder cooling tower water temperatures which the steam condenser package can be ordered for floor
naturally occur during the winter months. Appreciable mounting adjacent to the chiller package. Prefabricat-
power savings are realized from these reduced heads. ed piping kits for the steam trunk, and water piping
The minimum entering refrigerant condenser water between chiller package and steam condenser are not
temperature for other full and part load conditions is included with a floor mounted arrangement. These in-
provided by the following equation: terconnecting components must be designed, supplied
and installed by others.
Min. ECWT = LCHWT - C RANGE + 17°F
An optional piping kit may be ordered
Min. ECWT = LCHWT - C RANGE + 9.4°C from the factory when the original
equipment is placed.
where:
ECWT = Entering refrigerant Condensing Water Tem-
perature. External piping loads to the steam inlet
LCHWT = Leaving Chilled Water Temperature and water box connections should be
minimized. Allowable nozzle loads are
CONTROL RANGE = refrigerant condensing water available upon request if any concerns
temperature range at the given load condition. develop.
At initial startup, entering condensing water tempera-
ture may be as much as 25°F (14°C) colder than the STEAM TURBINE CASING DRAIN OPTIONS
standby chilled water temperature as long as it is above The steam turbine casing must be provided with a
the minimum ECWT allowed. means of draining during operation (while under vacu-
um). Factory available options are:
STEAM CONDENSER PACKAGE
• Automatic pressure powered pump (standard op-
The Steam Condenser package is shipped separately
tion)
as a packaged assembly. The Steam Condenser pack-
age consists of a skid mounted surface condenser with • Manual condensate drain tank (by special quote)
pre-piped accessories for the condensate and vacuum • Automatic condensate drain tank (by special
systems. The atmospheric relief valve is shipped loose quote)
for field assembly.
When the factory casing drain option is supplied,
The Steam Condenser package shipment should be the equipment is shipped loose for installation at the
checked on arrival to see that all major pieces, boxes jobsite.
JOHNSON CONTROLS 13
FORM 160.67-N2
SECTION 1 - INTRODUCTION
ISSUE DATE: 1/10/2014
14 JOHNSON CONTROLS
FORM 160.67-N2
ISSUE DATE: 1/10/2014
SECTION 2 - RIGGING
LD09288a
Figure 3 - RIGGING
JOHNSON CONTROLS 15
FORM 160.67-N2
SECTION 2 - RIGGING
ISSUE DATE: 1/10/2014
LD09388
Figure 4 - STEAM CONDENSER PACKAGE RIGGING
16 JOHNSON CONTROLS
FORM 160.67-N2
SECTION 2 - RIGGING
ISSUE DATE: 1/10/2014
JOHNSON CONTROLS 17
FORM 160.67-N2
SECTION 2 - RIGGING
ISSUE DATE: 1/10/2014
LD12218 LD12219
UNIT WEIGHT 28,836 to 53,530 LBS. UNIT WEIGHT 53,531 to 100,464 LBS.
(13,108 to 24,332 Kgs.) (24,333 to 45,666 Kgs.)
LD12220
UNIT WEIGHT 100,465 to 130,000 LBS.
45,667 to 58,967
18 JOHNSON CONTROLS
FORM 160.67-N2
ISSUE DATE: 1/10/2014
JOHNSON CONTROLS 19
FORM 160.67-N2
SECTION 3 - CUSTOMER SUPPLIED & INSTALLED COMPONENTS
ISSUE DATE: 1/10/2014
20 JOHNSON CONTROLS
FORM 160.67-N2
ISSUE DATE: 1/10/2014
• Steam condenser vacuum pump seal water dis- • Evaporator relief valve(s)
charge separator drain ** YORK provided pre-fabricated piping for these
• Steam condenser relief valve seal water: trickle connections.
flow **York provided pre-fabricated piping for these con-
• Steam condenser relief valve seal water drain nections.
JOHNSON CONTROLS 21
FORM 160.67-N2
SECTION 4 - CUSTOMER PIPING
ISSUE DATE: 1/10/2014
Air (Instrument Quality Air Source - ISA S7.3) Steam inlet piping for the standard YST condensing
• Bearing seal air purge and governor valve posi- turbines should include a full-size block valve in the
tioner: 80-150 psig (552 - 1030kPa), approx. 13 main steam inlet line.
SCFM (22 sm3/h). Exhaust piping is available as an optional kit for field
• Steam condenser level control system: 80-150 installation. A relief valve to protect the turbine ex-
psig (138 - 1030kPa), approx. 0.5 SCFM (0.9 haust casing and surface condenser is provided on
sm3/h). the steam condenser package for standard YST chill-
ers. Piping for special back pressure turbines should
• Trip and steam control: 80-150 psig include a throttle valve in the steam inlet line and a
(552 - 1030kPa), approx. 0.4 SCFM (0.7 sm3/h). stop valve in the exhaust line. A suitable relief valve
to protect the turbine exhaust casing must be provided
STEAM AND CONDENSATE PIPING between the turbine exhaust flange and the exhaust
A suitable piping arrangement with stop valve. The exhaust relief valve or the rupture disc
flexible type joints and piping supports/ should correspond in size to those indicated for steam
hangers, as required, must be provided and exhaust lines found in APPENDIX-A of NEMA
for the steam inlet line to the turbine. It SM 23-8, Steam Piping Systems manual.
is recommended that a piping analysis
These relief valves serve to protect the turbine casing
be performed by a qualified engineer to
against over-pressurization in case the turbine is started
verify the design adequately protects the
with the exhaust valve closed or the backpressure rises
steam turbine from excessive strains due
for any reason during operation. The relief valve should
to system/thermal loads. Maximum al-
be of sufficient capacity to relieve the rated steam flow
lowable loads on steam connections are
of the turbine at the maximum operating pressure spec-
governed by NEMA SM23 Steam Turbines
ified when all hand valves are Contact YORK Factory
for Mechanical Drive Services.
Service for specifications on sizing the valve, relieving
capacity, and over-pressurization limits.
STEAM PIPING
Steam inlet and exhaust piping (if not supplied by
Inlet and exhaust piping for the steam turbine should
YORK) must be properly designed and supported so
be designed and installed by knowledgeable persons
that its weight and thermal expansion will not produce
experienced in turbine work. The size of steam inlet
excessive strains on the turbine inlet or exhaust flang-
line is based upon velocities in the piping generally ac-
es, either when cold or when at normal operating tem-
cepted as being good practice for runs of straight pipe
perature. The piping must be designed so that it does
up to 200 feet, or the equivalent in valves and fittings.
not have to be sprung into position for bolting to the
The piping contractor must ensure that the steam sup-
turbine flanges when cold. Likewise, the piping must
ply is available at the turbine flange at the temperature
not be spring out of position when everything is at run-
and pressure required to achieve the design capacity of
ning temperature.
the chiller.
Force due to thermal expansion must
Johnson Controls assumes no responsi-
be accounted for, which can cause mis-
bility in regard to pressure or temperature
alignment. Refer to NEMA SM 23, Part
drops. The performance of the turbine
8 (Steam Piping Systems) for additional
specified is based upon the inlet pressure
information.
and temperature as measured at the tur-
bine steam inlet flange.
22 JOHNSON CONTROLS
FORM 160.67-N2
SECTION 4 - CUSTOMER PIPING
ISSUE DATE: 1/10/2014
Factory supplied STANDARD steam ex- there are no forces acting on the turbine steam supply
haust piping does NOT require additional connection point (refer to NEMA SM 23, part 8) when
support or pipe hangers. the steam supply piping is installed, or operated at de-
sign temperature. The governor valve and spool piece
must not be suported from the turbine base.
The governor valve and spool piece must
Moisture in the inlet steam not only increases the steam NOT be supported from the turbine base.
consumption but causes rapid wear of the valve seats, Any external force or moment exerted on
nozzles and turbine blades. A moisture separator and the turbine may lead to drive line mis- 4
steam trap must be installed at the low point of the inlet alignment and subsequent turbine and/
piping to ensure that the turbine receives dry steam. or compressor failure.
Where exhaust piping bends upward after leaving the
turbine, steam traps must be provided to keep the ex- TOP-MOUNTED STEAM CONDENSER
haust line drained to prevent water from building up in (Factory Supplied - Field Installed)
the exhaust pipe and turbine casing. To locate the steam condenser package, the steam con-
Failure to keep the exhaust line drained denser water inlet must be aligned with the refrigerant
may result in a restriction in the exhaust condenser water outlet, before attaching the mount-
line, causing a loss of power and damage ing brackets. Refer to the Steam Condenser Field Kit
to the turbine rotor. Connecting the steam Drawing and associated Field Notes included in the job
line should always begin at the header or manual for detailed installation instructions.
other source, the turbine connection being
See Figure 6 on page 24
made last. If an expansion joint is used in
either line it must be securely anchored to 1. Complete the water line between the (2) connec-
prevent axial strain on the turbine. tions before bolting the angles to the steam con-
denser base, and welding the angles to the refrig-
Be sure to blowout and clean all steam erant condenser tube sheet. See Figure 6 on page
lines before connecting to the turbine. 24.
Failure to do so may result in damage to
the steam strainer screen and other inter- 2. Condenser water outlet to steam condenser may
nal parts. Johnson Controls accepts no be at either end of unit. When required, victaulic
responsibility for damage resulting from couplings are not YORK factory supplied.
the entrance of foreign materials (refer 3. Partial prefabricated pipe caps or covers are fac-
to the procedure covered in this manual). tory supplied to provide reasonable protection of
internally blasted surfaces. Note: brush off blast-
Steam inlet connection must be loosened ing may be required prior to field assembly.
during the pipe strain testing procedure
described in this section 4. Proper handling and storage of prefab piping at
the job site is essential in providing proper pro-
tection for the internally blasted surfaces. Piping
should be unloaded by overhead lifting devices.
Note: Do not drag or damage to caps may occur.
GOVERNOR VALVE AND SPOOL PIECE
(Factory Supplied - Field Installed) 5. Prefabricated piping should not be stored out-
doors. If stored outside. The piping must be cov-
The factory supplied field installed spool piece and ered with a waterproof tarp, and not directly ex-
governor valve must be supported along with the rest posed to the weather. Pipe must not be stood on
of the steam supply piping. It is the installer's/install- end, any and all damage to caps or closures must
ing contractor's responsibility to ensure the steam sup- be repaired immediately.
ply pip opened. ing, field installed governor valve, and
field installed spool piece are fully supported so that
JOHNSON CONTROLS 23
FORM 160.67-N2
SECTION 4 - CUSTOMER PIPING
ISSUE DATE: 1/10/2014
6. The installing contractor must inspect the steam 8. All applicable state, county, city and local laws,
exhaust expansion joint (YORK supplied) prior to rules and regulations pertaining to construction,
installation to verify that the tie rod nuts are set to installation and inspection of steam and water pip-
allow zero compression in the axial direction. ing shall beconformed to.
7. All finish painting. Touching up or special paint- 9. Installing contractor is responsible for fit and
ing to be done in field form of turbine steam and condenser water piping
shown. Unnecessary strain on turbine and con-
denser nozzles must be avoided.
6WHDP
&RQGHQVHU
%DVH
5HIULJHUDQW
&RQGHQVHU
7XEHVKHHW
7<3
'(7$,/³$´
6HH'HWDLO³$´
$WPRVSKHULF
(YDSRUDWRU &RQGHQVHU 5HOLHI9DOYH
6WHDP([KDXVW
:DWHU3LSH
:LWK)ODQJHV :DWHU3LSH
6WHDP&RQGHQVHU
3DFNDJH
([SDQVLRQ-RLQW
&RPSUHVVRU
6WHDP
7XUELQH
&RQGHQVHU 3DFNDJH
:DWHU%R[
([DPSOH2QO\
/'
24 JOHNSON CONTROLS
FORM 160.67-N2
SECTION 4 - CUSTOMER PIPING
ISSUE DATE: 1/10/2014
JOHNSON CONTROLS 25
FORM 160.67-N2
SECTION 4 - CUSTOMER PIPING
ISSUE DATE: 1/10/2014
:36 7DFN:HOG
7<3
1XWV6KDOO%H
7DFN:HOGHG,Q)LHOG
´
7<3
)/2:
/'
Exhaust piping connections must loos- Piping Alignment - Upon completion of piping, a
ened during the Pipe Strain Testing Pro- connection in each line as close to the unit as possi-
cedure listed in this section. ble should be opened, by removing the flange bolts or
coupling and checked for piping alignment. If any of
the bolts are bound in their holes, or if the connection
springs out of alignment, the misalignment must be
INLET STEAM TEMPERATURE SENSOR AND corrected by properly supporting the piping or by ap-
INLET STEAM PRESSURE TRANSDUCER plying heat to anneal the pipe.
(Factory Supplied-Field Installed)
If the piping is annealed to relieve stress,
The inlet steam temp and pressure sensor must be field the inside of the pipe must be cleaned of
installed ahead of the governor valve. See Figure 8 on scale before it is finally bolted in place.
page 27 and Figure 13 on page 34.
26 JOHNSON CONTROLS
FORM 160.67-N2
SECTION 4 - CUSTOMER PIPING
ISSUE DATE: 1/10/2014
SENTINAL WARNING VALVE
* = Supplied in separate kit for Field Installation FIRST STAGE PRESSURE
TRANSMITTER *
OIL
RESERVOIR
28 JOHNSON CONTROLS
FORM 160.67-N2
SECTION 4 - CUSTOMER PIPING
ISSUE DATE: 1/10/2014
JOHNSON CONTROLS 29
FORM 160.67-N2
SECTION 4 - CUSTOMER PIPING
ISSUE DATE: 1/10/2014
Turbine supply steam and condensate piping connec- If it is necessary to run the pipe for a long distance the
tions to the chiller are to be supplied and installed by size should be increased so that back pressure does not
the site piping contractor. build up on the packing gland. This pipe must slope
A suitable piping arrangement with down from the connection point to avoid forming a
flexible type joints and piping supports/ water trap and must not contain a shut-off valve. On
hangers, as required, must be provided non-condensing turbines, a small amount of steam will
for the steam inlet line to the turbine. It pass through this line at all times. The amount of steam
is recommended that a piping analysis passing through the line will depend upon the amount
be performed by a qualified engineer to of back pressure.
verify the design adequately protects the The leak-off steam is commonly piped to a sewer or
steam turbine from excessive strains due open header. If this line becomes partially clogged,
to system/thermal loads. Maximum al- or the back pressure builds up for any reason, steam
lowable loads on steam connections are will blow out the shaft at the packing gland. Some ma-
governed by NEMA SM23-1991 Steam chines may be equipped with an optional gland con-
Turbines for Mechanical Drive Services. denser which condenses the gland leakage as well as
steam leaking from other leak-off connections. The
The turbine exhaust piping to the steam condenser shall
condensate from this gland condenser can be returned
be installed by the piping contractor, however, the de-
to the feed water system.
sign and supply of the exhaust piping and components
may be supplied by YORK depending on the options GLAND LEAK-OFF CONDENSER
chosen. Piping should be adequately supported and (Optional)
braced independently of the chillers. Hangers must al-
low for piping alignment at the operating temperature. This equipment may be specified for use on high back-
pressure applications, those turbines operating with a
Factory supplied, STANDARD steam ex-
high pressure differential across the glands, and which
haust piping does NOT require additional
must operate for long periods of time between shut-
support or pipe hangers.
downs (some low pressure turbines may also use this
equipment).
The condenser is piped to the outer leak-off connec-
The piping contractor is responsible for the form and fit tions of the glands. It creates a slight vacuum on the
of turbine steam piping. The piping must be installed outer leak-off areas, assuring that leakage will leave
with the flanges and bolt holes properly aligned. The through leak-off piping and not past inactive seals. The
bolts should be able to be inserted without any diffi- most common configuration is the gland condenser
culty and no force should be applied to allow the bolts and ejector. The gland condenser is a shell-and-tube
to be inserted or flanges aligned. When the flange bolts type heat exchanger in which cooling water is used to
are tightened, they must not impose any force or mo- condense steam leakage from the glands.
ment on the turbine flanges. The ejector is a steam nozzle which creates a low pres-
All steam piping must be arranged so that strains will sure area to remove any air which has leaked into the
not be imposed on the turbine. The total resultant force system and thus maintains the vacuum in the leak-off
and total resultant moment at any connection should areas. This equipment is available for all types of leak-
not exceed the limits defined by NEMA SM23-1991 off flows. The condensed leakage steam and cooling
for steam turbine systems. water can be recovered and returned to the boiler. Note
that the condenser tubes and ejector both require peri-
GLAND SEAL LEAK-OFF PIPING odic cleaning.
30 JOHNSON CONTROLS
FORM 160.67-N2
SECTION 4 - CUSTOMER PIPING
ISSUE DATE: 1/10/2014
JOHNSON CONTROLS 31
FORM 160.67-N2
SECTION 4 - CUSTOMER PIPING
ISSUE DATE: 1/10/2014
32 JOHNSON CONTROLS
FORM 160.67-N2
SECTION 4 - CUSTOMER PIPING
ISSUE DATE: 1/10/2014
for 150 PSIG DWP on the water side. If job require- REFRIGERANT RELIEF PIPING
ments are for greater than 150 PSIG DWP, check the
Each unit is equipped with pressure relief valves locat-
unit data plate before applying pressure to evapora-
ed on the refrigerant condenser and on the evaporator
tor or refrigerant condenser to determine if the chiller
for purpose of quickly relieving excess pressure of the
has provisions for the required DWP. Inlet and outlet
refrigerant charge to the atmosphere as a safety precau-
connections are identified by labels placed adjacent to
tion in case of an emergency, such as fire. Refrigerant
each nozzle.
relief vent piping (by others), from the relief valves to
CHECKING PIPING CIRCUITS AND VENTING the outside of the building, is required by code in most
AIR areas and should be installed on all chillers. 4
After the water piping is completed, but before any
water box insulation is applied, torque the waterbox Vent to Atmosphere
flange nuts to 30 and 60 ft. lbs. (41 and 81 Nm). Gasket Flanged Joint
shrinkage and handling during transit cause waterbox to Permit Piping Support Vent Piping to Avoid
Disassembly Strain on Relief Piping
flange nuts to loosen. If water pressure is applied be-
fore tightening is done, the gaskets may be damaged Flexible Connector
and need to be replaced. Check the steam condenser
piping connection for leaks. Pipe unions and flanges
may loosen during shipment and installation. Re-tight-
en, if necessary. Condensation
Trap
Refrigerant Condenser
Before the initial operation of the pumps
Relief
both water circuits should be thoroughly Valves
vented of all air at the high points. Failure (See Note)
Evaporator
to do so will result in pass baffle damage.
vent any air from the chiller water boxes. Operate the
pumps manually and carefully check the evaporator, Figure 12 - TYPICAL REFRIGERANT VENT PIPING
refrigerant and steam condenser waterboxes and pip-
ing for leaks. Repair leaks as necessary. The vent line should be sized in accordance with the
ANSI/ASHRAE-15, or local code. The vent line must
INSULATION include a dirt trap in the vertical leg to intercept and
Do NOT field insulate until the unit has permit clean out and trap any vent stack condensation.
been leak tested under the supervision of The piping MUST be arranged to avoid strain on the
the Johnson Controls representative. relief valves, using a flexible connection, if necessary.
See Figure 13 on page 34 for a typical piping ar-
rangement. Also refer to 160.73-AD1 for additional
details.
Insulation of the type specified for the job, or mini-
mum thickness to prevent sweating of 30°F (-1°C)
surfaces should be furnished (by others) and applied
to the evaporator shell, end sheets, liquid feed line to
flow chamber, compressor suction connection, evap-
orator waterboxes, and connections. The waterbox
flange insulation must be removable, to allow water-
box removal for the tube maintenance.
JOHNSON CONTROLS 33
34
Condenser Water* Oil Cooling
Symbols
Vent to Safe Outlet W7 Water Return
Area Outside
Y Type Strainer
Gate Casing Drain (to Pres-
Vent to Safe
From W6 sured Powered Pump or
Check Area Outside
Condensate Tank)
Butterfly Atmospheric Temp
Ball or Plug Relief S4 Indicator Steam Ring
Drain
Drain
SECTION 4 - CUSTOMER PIPING
Steam
* - Exact orientation of Inlet Gland Leak-Off S9
Chilled or Condenser Water S3 1-1/2” = NPT to
Nozzels depends on
Sewer w/out
selected configurations.
Evaporator Positive Head
Exhaust
Relief S6 S2 Moisture
Inlet Steam
Separator
To W5 W3 Oil Cooling
Water Outlet
W6
Oil Cooling
Temp Water Inlet
Indicator W5
Inlet
Water Reference all drawings and installation
W2* Water* instructions supplied by Johnson Controls
Outlet for additional detail on connection desig-
W1
nations and piping requirements.
JOHNSON CONTROLS
LD09346a
ISSUE DATE: 1/10/2014
FORM 160.67-N2
Equalizing Line to Pressure Reference all drawings and installation
Powered Pump or Condensate Tank instructions supplied by Johnson Controls
(1 inch Coupling Located in Appropriate
Location to be Supplied By Installer)
for additional detail on connection desig-
nations and piping requirements.
FORM 160.67-N2
Refrigerant Condenser
Relief, Vent to Safe Area
Outside
JOHNSON CONTROLS
ISSUE DATE: 1/10/2014
Note 1
S7 Discharge Separator,
Relief Valve Vent to Atmosphere
Seal Water
W10
Air Supply
S10 Inlet NOTE 1: Automatic Pressure Powered
Turbine S3 Pump provides pump only. All piping
Relief Valve associated with installation is by the
Casing Drain
Drain field. Location of the Automatic Pres-
sure Powered Pump and piping is for
reference only. Location to be floor-
mounte by the installer.
Condensate
Overboard
W3
Motive
Supply Vacuum Pump
Vacuum Seal Water
Pumping Separator
Drain Note 1
Trap* Sealing
) Water
and Hotwell Fill
Connection
(Potable Water)
Automatic
Pressure Pipe to Steam W11 NOTE:
Powered Condenser Hotwell * Factory supplied and field installed
Pump
35
LD09347d
SECTION 4 - CUSTOMER PIPING
4
FORM 160.67-N2
SECTION 4 - CUSTOMER PIPING
ISSUE DATE: 1/10/2014
36 JOHNSON CONTROLS
FORM 160.67-N2
ISSUE DATE: 1/10/2014
JOHNSON CONTROLS 37
FORM 160.67-N2
SECTION 5 - DRIVELINE ALIGNMENT
ISSUE DATE: 1/10/2014
• Check for piping strain - Reference Section 4 Pipe Dial indicators which are anti-magnetic
Strain Testing are strongly recommended.
Piping strain can cause problems with Make sure the indicator stem is near the
alignment and must be corrected before center of travel before taking readings
operating the unit. and will remain in contact with the flange
surface. Rotate the shaft to insure the in-
dicators will not be impacted or obstructed
when rotated.
• Verify that the Mylar shipping film has been re-
moved from the turbine shaft bearing prior to ro- DIAL INDICATORS
38 JOHNSON CONTROLS
FORM 160.67-N2
SECTION 5 - DRIVELINE ALIGNMENT
ISSUE DATE: 1/10/2014
ments. Refer to the "Checking for Sag" section in this DIAL INDICATORS
measures the same distance as the cou- Figure 16 - TYPICAL "REVERSE INDICATOR" TO
pling span. DETERMINE COLD ALIGNMENT OF
5
SHAFTS
JOHNSON CONTROLS 39
FORM 160.67-N2
SECTION 5 - DRIVELINE ALIGNMENT
ISSUE DATE: 1/10/2014
In recent years people have questioned the value of YORK DBL. TAPER
the traditional “Hot Check Alignment”. Not only is "D" DIMENSION
COUPLING P/N
it costly and time-consuming to bring a machine up to 029-20899-001 4.75
temperature, stop it, break couplings, and attempt to
determine alignment before it cools off, but the results
SHIM QTY. AT LOCATION
are highly questionable. VARIANCE
1 2 3 4
It is normally not possible to make the check quickly 0-0.014 0 0 0 0
enough to accurately determine the thermal growth of 0.015-0.029 1 0 0 0
the equipment. Also any hydraulic forces and torque 0.030-0.044 2 0 0 0
reactions, which can be significant, are never revealed
0.045-0.059 2 1 0 0
by the traditional check methods because the forces
0.060-0.074 2 2 0 0
disappear immediately upon stopping the machine.
0.075-0.089 2 2 1 0
One alternative is to use the cold position of the shafts 0.090-0.104 2 2 2 0
as a benchmark, and deduce the hot alignment by mon- 0.105-0.119 2 2 2 1
itoring the movement of the machine casings, shafts, 0.12 2 2 2 2
or bearing centerlines from the cold position to the
hot position. There are several methods used for this 2. If the measurement is greater than the "D" dimen-
monitoring. A variety of techniques can be applied to sion listed in the table above add the appropriate
the actual determination of casing or shaft movement, shims to the proper shim points as indicated in
which includes optical or electronic (laser) techniques. Figure 17 on page 40. Shims are sent with each
In any event, a "Hot Alignment" check of the driveline coupling and will allow up to an additional .120"
alignment at operating temperatures is required. of face-to-face coupling installation (min. 4.75" to
max. 4.870"). The shims should be installed per
COUPLING SPACER INSTALLATION
table above at the locations stated in Figure 17 on
1. After the unit has operated in it's initial slow roll page 40.
for 30 minutes and the turbine has achieved oper- Some couplings use shims that are cir-
ating temperature, obtain an accurate face-to-face cular and span the entire diameter of the
measurment with the turbine and compressor on coupling reference (see Figure 17).
their normal operating position.
Verify the turbine has stopped rotating
and all power / steam supply sources are
properly locked out and tagged out before
the measurement is obtained.
LD12213
40 JOHNSON CONTROLS
FORM 160.67-N2
ISSUE DATE: 1/10/2014
JOHNSON CONTROLS 41
FORM 160.67-N2
SECTION 6 - FIELD INSTALLED WIRING
ISSUE DATE: 1/10/2014
Inlet Steam
Temp Sensor
LD12499
42 JOHNSON CONTROLS
FORM 160.67-N2
ISSUE DATE: 1/10/2014
NOTES
JOHNSON CONTROLS 43
P.O. Box 1592, York, Pennsylvania USA 17405-1592 800-861-1001 Subject to change without notice. Printed in USA
Copyright © by Johnson Controls 2014 www.johnsoncontrols.com ALL RIGHTS RESERVED
Form 160.67-N2 (114)
Issue Date: January 10, 2014
Supersedes: 160.67-N2 (1109)