General Data and Information:: Item Description Checked

Download as docx, pdf, or txt
Download as docx, pdf, or txt
You are on page 1of 2

Commissioning Service Department

Commissioning Standard Test Formats

Description: TRIP CKT. SUPERVISION XR350 Record No. :


Bay no.: Drawing ref.: Sheet : 1 of 2
Contractor : Contract no.: Substation No :

1. GENERAL DATA AND INFORMATION:

Bay no. Serial No.


Bay name Model No. EPXR350S51130606
Make REYROLLE Voltage 125 VDC
Flag Type SELF RESET No. of Contacts 3 NC + 1 NO

2. MECHANICAL CHECKS AND VISUAL INSPECTION:

ITEM DESCRIPTION CHECKED


1 Inspect for any physical damage or defects.

2 Check reset operation

3 Check serial no. of relay matching with serial no. of case

3. ELECTRICAL TESTS:
3.1. FUNCTION TEST:

ITEM DESCRIPTION CHECKED


1 All contact checked

2 All output contacts resistance checked

3 Flag Operation Checked

3.2. PICK UP/DROP OFF TEST:

PICK UP DROP OFF


Relay Cut-off
COIL VOLTAGE CURRENT VOLTAGE CURRENT
Terminals Contacts
(V) (mA) (V) (mA)
Coil A 21 – 22
Coil B 13 – 14
Coil C 27 – 28

Operating range : 80 -110 %Vn ( According to relay catalogue )

Tested by: ENG. Witnessed by: ENG.

Signature & Date: Signature & Date:


Commissioning Service Department
Commissioning Standard Test Formats

Description: TRIP CKT. SUPERVISION XR350 Record No. :


Bay no.: Drawing ref.: Sheet : 2 of 2
Contractor : Contract no.: Substation No :

3.3. TIMING TEST:

Contacts Pick up Time Resetting Time


COIL
Number (m sec) (m sec)

Coil C

Limits: Resetting Time: > 400 mSec at Vn to 0 ( According to relay catalogue )

3.4. BURDEN:

Current
Coil Voltage (V) WATTS (W)
(mA)

CB OPEN Coil A

CB CLOSE Coil B

ALARM CIRCUIT Coil C

Limits: CB Open : 1 W , CB Close : 2 W , Alarm Circuit : 4 W ( According to relay catalogue )

Tested by: ENG. Witnessed by: ENG.

Signature & Date: Signature & Date: