supported. Fig. 3 illustrates a Bergeron specification of a 400kV
overhead line given in fig.1.
The model is based on the Bergeron’s traveling wave
method used by the Electromagnetic Transient Program
(EMTP) [3]. In this model, the losses distributed LC line is
characterized by two values (for a single phase line): the surge
impedance Zc = L / C and the phase velocity
V LC C V LC C V
I
I
I
I-365
Fig.7. Voltage value at phase Ⱥ, ȼ, ɋ of transposed line
I-366
Phase-to-phase fault of B and C phases with and without 3. Conclusion
transposition has been investigated as well.
The model of untransposed line during the phase-to-phase At line length of 100km and more the measures should be
fault of B and C phases in ATP-EMTP is presented on Figure undertaken for limiting the unbalance in relation to untransposed
11. line. As a rule, the utilization of one cycle of transposition is
enough to eliminate the unbalance coefficient up to allowable
V LC C V LCC V parameters.
I SA I
I When analyzing the transposition scheme it should be
considered that the results for classical transposition scheme and
simplified transposition scheme will be similar because the
extreme phases are allocated symmetrically to average phase, as
it was noted in [5].
In lines with horizontal allocation at length exceeding
100km, the usage of line phase transposition is be required.
Considering all the aforesaid, the results gained testify to the
continuation of investigations in this way and also can be used
Fig.11.The model of untransposed line during the phase-to- for solving the problems of provision of allowable unbalance
phase fault of B and C phases in ATP-EMTP level in longer lines.
Computing results of voltage and current during the phase-to- 4. References
phase fault of B and C phases without transposition are shown
on Figure 12, 13. [1]. N.N. Mirolyubov On transmission line electrical asymmetri.
Proceedings of LPI, #3, 1948 [in Russian].
[2]. M.M.Adibi, D.P.Milanicz, T.L. Volkmann Asymmetry issues
in power system restoration. IEEE Trans on Power System,
1999, 14(3):1085-1091.
[3]. H.Dommel Digital Computer Solution of Electromagnetic
Transients in Single and Multiple Netwoks, IEEE
Transactions on Power Apparatus and Systems, Vol PAS-88,
No.4, April 1969.
[4]. “Alternative Transients Program (ATP) – Rule Book”,
Canadian/American EMTP User Group, 1987-1998.
[5]. M.V. Kostenko, L.S. Perelman Three-phase aerial line
simplest scheme of transposition. Electricity, #8, 1980 [in
Russian].
.
Fig. 12. Voltage value during the phase-to-phase fault without
transposition
I-367