Multi MAX Multi: Indoor Unit Engineering Manual
Multi MAX Multi: Indoor Unit Engineering Manual
Multi MAX Multi: Indoor Unit Engineering Manual
EM_MultiF_IDU_09_19
For continual product development, LG reserves the right to change specifications without notice.
©LG Electronics Inc.
TABLE OF SYMBOLS
This symbol indicates an imminently hazardous situation which, if not avoided, will result in death or
DANGER serious injury.
This symbol indicates a potentially hazardous situation which, if not avoided, could result in death or
WARNING serious injury.
This symbol indicates a potentially hazardous situation which, if not avoided, may result in minor or
CAUTION moderate injury.
Note: This symbol indicates situations that may result in equipment or property damage accidents only.
This document, as well as all reports, illustrations, data, information, and other materials are the property of LG Electronics U.S.A., Inc.
MULTI F TABLE OF CONTENTS
MULTI F MAX
Convergence of Technology, Factory Supplied Parts and Materials / Installation ������������������������� 105
Innovation, Flexibility, & Style.....................................................4 Installation and Best Layout Practices.............................................. 106
Unit Nomenclature........................................................................5 Four-Way Ceiling Cassette Indoor Units................................114
Mechanical Specifications and Features...........................................115
Functions, Controls and General Data / Specifications............................................................116
Options Overview.........................................................................6 Dimensions........................................................................................117
Art Cool Mirror Indoor Units......................................................10 Cooling Capacity Table......................................................................119
Mechanical Specifications and Features............................................ 10 Heating Capacity Table..................................................................... 121
General Data / Specifications..............................................................11 Acoustic Data................................................................................... 123
Dimensions......................................................................................... 12 Air Velocity and Temperature Distribution......................................... 125
Cooling Capacity Table....................................................................... 14 Refrigerant Flow Diagram................................................................. 127
Heating Capacity Table....................................................................... 16 Wiring Diagram................................................................................. 128
Acoustic Data..................................................................................... 17 Factory Supplied Parts and Materials............................................... 129
Air Velocity and Temperature Distribution........................................... 18 Installation and Best Layout Practices.............................................. 130
Refrigerant Flow Diagram................................................................... 19 Two-Way VAHU Indoor Units...................................................138
Wiring Diagram................................................................................... 20 Mechanical Specifications and Features.......................................... 139
Factory Supplied Parts and Materials................................................. 21 General Data / Specifications........................................................... 140
Installation and Best Layout Practices................................................ 22 Dimensions....................................................................................... 141
Art Cool Gallery Indoor Units....................................................29 Cooling Capacity Table..................................................................... 142
Mechanical Specifications and Features............................................ 29 Heating Capacity Table..................................................................... 143
General Data / Specifications............................................................. 30 External Static Pressure................................................................... 144
Dimensions......................................................................................... 31 Acoustic Data................................................................................... 145
Cooling Capacity Table....................................................................... 32 Refrigerant Flow Diagram................................................................. 146
Heating Capacity Table....................................................................... 33 Wiring Diagram................................................................................. 147
Acoustic Data..................................................................................... 34 Factory Supplied Parts and Materials............................................... 149
Air Velocity and Temperature Distribution........................................... 35 Installation and Best Layout Practices.............................................. 150
Introduction
Refrigerant Flow Diagram................................................................... 36 Four-Way VAHU Indoor Units..................................................158
Wiring Diagram................................................................................... 37 Mechanical Specifications and Features.......................................... 159
Factory Supplied Parts and Materials................................................. 38 General Data / Specifications........................................................... 160
Installation and Best Layout Practices................................................ 39 Dimensions....................................................................................... 161
Standard Wall-Mounted Indoor Units.......................................49 Cooling Capacity Table..................................................................... 162
Mechanical Specifications and Features............................................ 49 Heating Capacity Table..................................................................... 164
General Data / Specifications............................................................. 50 External Static Pressure and Airflow Ranges................................... 166
Dimensions......................................................................................... 51 Acoustic Data................................................................................... 169
Cooling Capacity Table....................................................................... 53 Refrigerant Flow Diagram................................................................. 171
Heating Capacity Table....................................................................... 56 Wiring Diagram................................................................................. 172
Acoustic Data..................................................................................... 58 Factory Supplied Parts and Materials............................................... 174
Air Velocity and Temperature Distribution........................................... 60 Installation and Best Layout Practices.............................................. 175
Refrigerant Flow Diagram................................................................... 62 Application Guidelines.............................................................184
Wiring Diagram................................................................................... 63 Equipment Selection Procedure....................................................... 185
Factory Supplied Parts and Materials................................................. 65 Placement Considerations................................................................ 192
Installation and Best Layout Practices................................................ 66
Refrigerant Piping Design.......................................................198
Duct (Low Static) Indoor Units..................................................72 Design Guideline Summary.............................................................. 199
Mechanical Specifications and Features............................................ 73 Creating a Balanced System / Manual Layout Procedure 203
General Data / Specifications............................................................. 74 Condensate Drain Piping.................................................................. 204
Dimensions......................................................................................... 75
Cooling Capacity Table....................................................................... 76 Electrical Connections.............................................................205
Heating Capacity Table....................................................................... 78 General Information.......................................................................... 206
External Static Pressure..................................................................... 79 Power Wiring (208-230V) and Comm Cable Details ����������������������� 209
Acoustic Data..................................................................................... 80 Remote Controller Connections....................................................... 219
Refrigerant Flow Diagrams................................................................. 81 Indoor Unit Group Control................................................................ 220
Wiring Diagram................................................................................... 83 Acronyms..................................................................................221
Factory Supplied Parts and Materials................................................. 85
Installation and Best Layout Practices................................................ 86
Duct (High Static) Indoor Units.................................................95
Mechanical Specifications and Features............................................ 96
General Data / Specifications............................................................. 97
Dimensions......................................................................................... 98
Cooling Capacity Table....................................................................... 99
Heating Capacity Table..................................................................... 100
External Static Pressure / Acoustic Data.......................................... 101
Refrigerant Flow Diagrams............................................................... 102
Wiring Diagrams............................................................................... 104
INTRODUCTION | 3
CONVERGENCE OF TECHNOLOGY,
INNOVATION, FLEXIBILITY, & STYLE
About LG Electronics, Inc. be used with different controllers, allowing the customer to set the
temperature individually. Indoor units are available in several dif-
LG Electronics is a global leader and technology innovator in con-
ferent configurations: Art Cool™ Mirror-mounted, Art Cool Gallery
sumer electronics, mobile communications, and home appliances.
wall-mounted, standard wall-mounted, four-way ceiling cassettes,
LG Electronics comprises five business units—Home Entertainment,
ceiling-concealed duct (high and low static), and vertical-horizontal air
Mobile Communications, Air Conditioning, Business Solutions, and
handling models. Multi F MAX systems can operate up to eight indoor
Home Appliance. LG is one of the world’s leading producers of flat
units through two-, three-, or four-port branch distribution units.
panel televisions, audio and video products, mobile handsets, air
conditioners, and washing machines. LG’s commercial air condition-
ing business unit was established in 1968 and has built its lineup of Adaptable and Flexible
Multi F and Multi F MAX Indoor Unit Engineering Manual
residential and commercial products to include VRF, Multi F, duct- Multi F outdoor units can be adapted to a wide range of building ap-
free split systems, packaged terminal air conditioners (PTACs), and plications and sizes such as schools, hotels, hospitals, offices, and
room air conditioners. In 2011, the air conditioning and energy solu- residences. The system components are lightweight and compact so
tions business unit grew to include LED lighting and solar products. they can be placed in buildings without expensive cranes, they easily
For more information, visit www.lg.com. fit into most service elevators, and they can be set in place with
minimal structural reinforcements requirements.
Multi-Zone Systems Multi F technology allows you to pipe farther by reaching areas of the
LG HVAC systems offer a range of solutions that are cost efficient, building that would require the installation of a second system when
quiet and attractive. Multi-zone systems are “split” into indoor and using traditional direct-expansion cooling and heating equipment. Multi
outdoor units, and provide a smart alternative to both central HVAC F provides the designer with uncompromised pipe system engineering
and window-mounted air conditioners. These inverter heat pump sys- flexibility—long pipe runs and large elevation differences. Whether your
tems are available in a variety of configurations to suit different cool- building is a condominium, a hotel, a school, or an office complex, Multi
ing and heating situations. Installation by a trained HVAC contractor F is best suited to reach the farthest corners and elevations.
is safe and easy – little to no duct work or sheet metal is required.
Multi F Systems Smaller Chases and Plenums
LG’s inverter heat pumps can support two, three, or four indoor LG Multi F systems use refrigerant piping to move heat, resulting in
units that are typically installed in separate rooms. Indoor units can smaller space requirements for piping as compared to chilled water
or roof top systems. This helps reduce the overall construction and
Benefits of Multi F Systems material cost of the building, and gives back leasable space. Flexible
and logical placement of system components, reduced back-and-
• Individual zone control
forth pipe lengths, and fewer joints lowers installation costs and
• Long refrigerant piping lengths minimizes potential leaking.
• High refrigerant piping elevation differences
• Maximum flexibility
Quality Commitment
• Operating ranges of 14°F to 118°F (DB) in cooling and -4°F to LG is committed to the success of duct-free projects. We provide
75°F (DB) in heating if connected to standard Multi F Outdoor Units technical support during installation and commissioning. LG offers
or -13°F to 75°F (DB) in heating if connected to Multi F with LG a variety of classes designed for installers and servicers on Multi F
REDº Outdoor Units. installation. Classes are con-
• Quiet and comfortable environment ducted at LG’s training centers
• Reduced ductwork and in field locations at various
times throughout the year and on
special request.
MULTI F
Due to our policy of continuous product innovation, some specifications may change without notification.
4 | INTRODUCTION ©LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp.
MULTI F UNIT NOMENCLATURE
MULTI F MAX
Introduction
09 = 9,000 18 = 18,000 36 = 36,000 54 = 54,000
12 = 12,000 24 = 24,000 42 = 42,000 60 = 60,000
Generation
Features:
H = Heat Pump
V = Inverter
T = High Wall-Mounted Indoor Unit
P = Art Cool Gallery Indoor Unit
Family
Generation: 0, 1
Dry contact o o o o o o √7
Dry contact (temperature setting) o o o o o o o
Central control (LGAP) √ √ √ √ √ √ √
Connector for Water Sensor √ √ √
Function
Special
Wi-Fi8 √ o √ o o o o
1
Primary washable filters. 6
Requires wired zone controller √ = Standard feature
2
Secondary filter 7
For use with 3rd party thermostat o = Unit option
3
Branch location and static pressure requirements. Requires PTPKQ0 8
Embedded. Optional for HSD, LVNxxxHV4 4-way VAHU; LDN 9/12 MBH
Plasma kit. LSD are compatible as of June 2018 production. Not available for 2-way
4
Requires ventilation kit PTVK430 (Temperature, humidity, and volume LMVNxxxHV VAHU. LMANxxxHVP Art Cool Gallery compatible as of
limitations apply). January 2019 production.
5
Group control will affect available features
Due to our policy of continuous product innovation, some specifications may change without notification.
6 | INTRODUCTION ©LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp.
MULTI F FUNCTIONS, CONTROLS AND
MULTI F MAX OPTIONS OVERVIEW
Introduction
For Ceiling-Concealed Duct (High Static) Indoor Units
ZFBXM101A High Efficiency Filter Box for LHN248HV
ZFBXM201A High Efficiency Filter Box for LHN368HV
ZFBXD201A Dynamic V8 2VL Low Profile Air Cleaner
ZPLMV201A Dynamic 2VL Air Cleaner Low Profile Return Air Plenum
ZFBXD402A Dynamic V8 4VL Low Profile Air Cleaner
ZPLMV402A Dynamic 4VL Air Cleaner Low Profile Return Air Plenum
ZFLT1301A 4-Pack Dynamic V8 VL Air Cleaner Replacement Filter Pads
ZFLT1302A 24-Pack Dynamic V8 VL Air Cleaner Replacement Filter Pads
ZGRLRA01A Dynamic V8 Air Cleaner Louvered Return Air Grille (one per plenum )
ZGRLRA02A Dynamic V8 Air Cleaner Egg Crate Return Air Grille (one per plenum)
PRARH0 Aux Heat Relay Kit
PWFMDD200 Wi-Fi Module
Controls Accessories
PQWRHQ0FDB Wireless Handheld Remote (Duct/VAHU)
PREMTA000A Premium Controller
PREMTC00U Simple Controller (Wall/Cassette)
PREMTBVC0 MultiSITE CRC1 Base Controller
PREMTBVC1 MultiSITE CRC1 Plus Controller
ZVRCZ**** MultiSITE CRC1 Wireless Accessories
PDRYCB100 Dry Contact (Simple)
PDRYCB300 Dry Contact (3rd party controller)
PDRYCB400 Dry Contact (Setback)
ZRTBS01 Remote Temp Sensor (Cassette/Duct/VAHU)
PZCWRCG3 Group Control Cable Kit
PZCWRC1 Controller Extension Cable
Due to our policy of continuous product innovation, some specifications may change without notification.
©LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp. INTRODUCTION | 7
MULTI F
MULTI F MAX
Multi F and Multi F MAX Indoor Unit Engineering Manual
Due to our policy of continuous product innovation, some specifications may change without notification.
8 | INTRODUCTION ©LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp.
ART COOL MIRROR ™
ART COOL Mirror Wall-Mounted Figure 1: Multi F Art Cool Mirror Wall-Mounted Indoor Unit.
Indoor Units
General
All LG indoor units are factory assembled, wired, piped, and pro-
vided with a control circuit board, fan, and motor. ART COOL Mirror
Wall-Mounted indoor units have a sound rating no higher than 44
dB(A) as tested per KSA0701 ISO Standard 3745.
Coil
Multi F and Multi F MAX Indoor Unit Engineering Manual
1
Nominal capacity is rated 0 ft. above sea level with corresponding refrigerant piping length in 3
Acceptable operating voltage: 187V-253V.
accordance with standard length of each outdoor unit and a 0 ft. level difference between outdoor and 4
Sound pressure levels are tested in an anechoic chamber under ISO Standard 3745 and are the
indoor units. All capacities are net with a combination ratio between 95 – 105%. same in both cooling and heating mode. These values can increase due to ambient conditions during
Nominal cooling capacity rating obtained with air entering the indoor unit at 80ºF dry bulb (DB) and 67ºF operation.
wet bulb (WB) and outdoor ambient conditions of 95ºF dry bulb (DB) and 75ºF wet bulb (WB). 5
All power wiring / communications cable to the IDUs be minimum 14 AWG, 4-conductor, stranded,
Nominal heating capacity rating obtained with air entering the indoor unit at 70ºF dry bulb (DB) and 60ºF shielded or unshielded (if shielded, must be grounded to chassis at ODU only) and must comply with
wet bulb (WB) and outdoor ambient conditions of 47ºF dry bulb (DB) and 43ºF wet bulb (WB). applicable local and national codes.
2
This unit comes with a dry helium charge.
Due to our policy of continuous product innovation, some specifications may change without notification. ART COOL MIRROR | 11
©LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp.
MULTI F MAX
MULTI F
Left
©LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp.
Due to our policy of continuous product innovation, some specifications may change without notification.
Attaching the Installation Plate, Drilling Hole
32-15/16 (837) 7-9/16 (192) Unit Outline Place a Level on Raised Tab
ART COOL MIRROR INDOOR UNITS
Air Intake
C Type : 16.5 C Type : 16.5
Refrigerant,
Drain Pipe
Refrigerant, Drain Display & Remote and Cable
12-1/8 (308)
Pipe, and Cable Controller Signal Knock
Knock Out Hole Receiver Signal Out Hole Ø2-9/16" Ø2-9/16”
Ø2-9/16"
Installation Plate
2-7/32 (56)
2-7/32(56)
Air -7/32
11/32 (9)
2
C Type
2 (51) [28-5/32 (715)] Bottom Air Outlet 5/16 (8)
Air Outlet Hole
2 (51)
C Type : 3.9 C Type : 5.3
6 7.6
1-7/16 (33.5)
1-3/32 (50.2) 1-1/16 (26.2) 32-15/16 (837)
Terminal Block for
5-31/32 (152)
2-5/16
(59)
Refrigerant, Drain Approx. 8-19/32 (218) to liquid pipe
12-1/8 (308)
Figure 2: LAN090HSV5 and LAN120HSV5 Dimensions.
1-27/32(47)
1/4 (6) x 1/8 (3)
2-13/32 (61)
1-1/2 (38) 5-3/16 (132)
Unit Outline
Cooling Heating Connecting Gas/Liquid Pipe
1/8 (3) x 1/4 (6)
55° 55°
15°
15°
45°
12
Multi F and Multi F MAX Indoor Unit Engineering Manual
Art Cool Mirror™
13
Dimensions
ART COOL MIRROR INDOOR UNITS
|
ART COOL MIRROR
Unit : inch (mm)
[36-5/32 (918)]
Air Intake Hole
Rear Rear
©LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp.
Due to our policy of continuous product innovation, some specifications may change without notification.
Air Intake Hole
[6-11/16 (170)]
Left Right
8-11/32 (212)
39-9/32 (998) Attaching the Installation Plate, Drilling Hole
Air Intake Unit Outline Place a Level on Raised Tab
Refrigerant,
C Type: 19.4 C Type: 19.8
Drain Pipe
13-19/32 (345)
Refrigerant, Drain Display & Remote and Cable
Pipe, and Cable Controller Signal Knock
Knock Out Hole Receiver Signal Out Hole
t H 4)]
ole
utle (7
ir O /32
Ø2-9/16"
2-3/8 (60)
A [2-29
7/16(11)
2-3/8 (60) [34-11/32 (872)] Bottom
Air
Outlet
7/16 (11) Measuring Tape
Air Outlet Hole 2-3/8 (60)
3.3 3.3
1-7/16 (33.5) C Type: 5.3 Measuring Tape C Type: 5.9
1-3/32 (50.2) 1-1/16 (26.2) Hanger
Terminal Block for 39-9/32 (998)
5-31/32 (152)
2-7/32 (56)
Communication
Refrigerant, Drain
2-1/4 (57) Pipe and Cable In case of Left Side Piping
3-17/32 (90) Knock Out Hole
Decoration Cover
13-19/32 (345)
2-7/16 ( 61.5)
Approx. 9-7/16 (240) to gas pipe
1-1/4 (31)
Approx. 6-5/16 (160) to liquid pipe
1/4 (6) x 1/8 (3) * If airflow direction control is available,
Drain Hose Connection
2-13/32 (61)
Up & Down Left & Right
2-15/32 (63)
Cooling Heating
1/8 (3) x 1/4 (6)
1-15/32 (37) 6-15/32 (164)
50° 50° Unit Outline
Connecting Gas/Liquid Pipe
15°
20°
MULTI F MAX
45°
85°
MULTI F
ART COOL MIRROR INDOOR UNITS MULTI F
Cooling Capacity Table MULTI F MAX
Table 4: Multi F Art Cool Mirror Indoor Units Cooling Capacity Table.
Model No. / Indoor Air Temp. °F DB / °F WB
Nominal Capacity Outdoor Air
Temp. 68 / 57 73 / 61 77 / 64 80 / 67 86 / 72 90 / 75
of Indoor Unit (°F DB) TC SHC TC SHC TC SHC TC SHC TC SHC TC SHC
(Btu/h)
14 8.82 6.04 9.37 6.38 9.92 6.18 10.31 6.31 11.01 6.36 11.56 6.48
20 8.82 6.09 9.36 6.43 9.91 6.23 10.31 6.36 11.01 6.41 11.55 6.53
25 8.81 6.13 9.36 6.48 9.90 6.27 10.30 6.41 11.00 6.46 11.54 6.58
30 8.80 6.18 9.35 6.53 9.90 6.32 10.29 6.46 10.99 6.51 11.54 6.63
35 8.80 6.23 9.34 6.58 9.89 6.37 10.28 6.50 10.98 6.56 11.53 6.68
40 8.79 6.28 9.33 6.63 9.88 6.42 10.27 6.55 10.97 6.61 11.52 6.73
Multi F and Multi F MAX Indoor Unit Engineering Manual
45 8.78 6.32 9.33 6.68 9.87 6.47 10.27 6.60 10.96 6.66 11.51 6.78
50 8.78 6.37 9.32 6.73 9.87 6.51 10.26 6.65 10.96 6.71 11.50 6.83
55 8.77 6.42 9.31 6.78 9.86 6.56 10.25 6.70 10.95 6.76 11.49 6.88
60 8.76 6.46 9.31 6.83 9.85 6.61 10.24 6.75 10.94 6.81 11.48 6.93
65 8.76 6.51 9.30 6.88 9.84 6.66 10.24 6.80 10.93 6.85 11.47 6.98
LAN090HSV5 70 8.75 6.56 9.29 6.92 9.84 6.70 10.23 6.85 10.92 6.90 11.47 7.03
9,000 75 8.54 6.45 9.08 6.82 9.62 6.61 10.01 6.75 10.71 6.82 11.25 6.96
80 8.33 6.34 8.87 6.71 9.41 6.51 9.80 6.66 10.49 6.73 11.03 6.87
85 8.12 6.22 8.66 6.60 9.20 6.41 9.59 6.56 10.28 6.64 10.82 6.79
90 7.91 6.10 8.45 6.48 8.99 6.31 9.37 6.46 10.06 6.55 10.60 6.70
95 7.68 6.04 8.22 6.43 8.75 6.26 9.00 6.32 9.83 6.52 10.36 6.67
100 7.50 5.88 8.03 6.26 8.57 6.11 8.88 6.22 9.64 6.37 10.17 6.53
105 7.31 5.72 7.84 6.10 8.38 5.96 8.77 6.12 9.45 6.23 9.99 6.39
110 7.12 5.52 7.66 5.90 8.19 5.78 8.58 5.94 9.26 6.06 9.80 6.22
115 6.94 5.36 7.47 5.74 8.01 5.63 8.39 5.79 9.08 5.91 9.61 6.08
118 6.82 5.32 7.36 5.70 7.89 5.60 8.28 5.76 8.96 5.89 9.50 6.06
122 6.79 5.30 7.32 5.69 7.86 5.59 8.24 5.76 8.93 5.89 9.46 6.06
14 11.76 8.51 12.49 8.99 13.22 8.70 13.75 8.88 14.69 8.96 15.42 9.13
20 11.75 8.57 12.48 9.06 13.21 8.77 13.74 8.95 14.67 9.03 15.40 9.20
25 11.75 8.64 12.48 9.13 13.20 8.84 13.73 9.02 14.66 9.10 15.39 9.27
30 11.74 8.71 12.47 9.20 13.19 8.90 13.72 9.09 14.65 9.17 15.38 9.34
35 11.73 8.77 12.46 9.27 13.18 8.97 13.71 9.16 14.64 9.24 15.37 9.41
40 11.72 8.84 12.45 9.34 13.17 9.04 13.70 9.23 14.63 9.31 15.36 9.48
45 11.71 8.90 12.44 9.41 13.16 9.11 13.69 9.30 14.62 9.38 15.35 9.55
50 11.70 8.97 12.43 9.47 13.15 9.17 13.68 9.37 14.61 9.45 15.33 9.62
55 11.69 9.03 12.42 9.54 13.14 9.24 13.67 9.44 14.60 9.52 15.32 9.70
60 11.68 9.10 12.41 9.61 13.13 9.31 13.66 9.50 14.59 9.58 15.31 9.77
65 11.67 9.17 12.40 9.68 13.12 9.38 13.65 9.57 14.57 9.65 15.30 9.84
LAN120HSV5 70 11.66 9.23 12.39 9.75 13.11 9.44 13.64 9.64 14.56 9.72 15.29 9.91
12,000 75 11.38 9.08 12.11 9.60 12.83 9.31 13.35 9.51 14.27 9.60 15.00 9.79
80 11.10 8.92 11.82 9.45 12.55 9.17 13.07 9.38 13.99 9.48 14.71 9.68
85 10.83 8.76 11.54 9.29 12.26 9.03 12.78 9.24 13.70 9.36 14.42 9.56
90 10.55 8.60 11.26 9.13 11.98 8.88 12.50 9.10 13.42 9.22 14.13 9.43
95 10.25 8.51 10.96 9.05 11.67 8.82 12.00 8.90 13.10 9.18 13.81 9.39
100 10.00 8.28 10.71 8.82 11.42 8.61 11.84 8.76 12.85 8.98 13.56 9.20
105 9.75 8.05 10.46 8.59 11.17 8.40 11.69 8.62 12.60 8.78 13.31 9.01
110 9.50 7.77 10.21 8.31 10.92 8.14 11.44 8.37 12.35 8.53 13.07 8.76
115 9.25 7.54 9.96 8.08 10.67 7.92 11.19 8.15 12.10 8.33 12.82 8.56
118 9.10 7.49 9.81 8.03 10.52 7.88 11.04 8.12 11.95 8.30 12.67 8.54
122 9.05 7.47 9.76 8.01 10.48 7.87 10.99 8.11 11.90 8.29 12.62 8.53
TC = Total Capacity (kBtu/h).
SHC: Sensible Heat Capacity (kBtu/h).
Nominal capacity as rated 0 ft. above sea level and a 0 ft. level difference between outdoor and indoor units. Corresponding refrigerant piping length is accordance with standard length of each outdoor unit.
Nominal cooling capacity rating obtained with air entering the indoor unit at 80ºF dry bulb (DB) and 67ºF wet bulb (WB), and outdoor ambient conditions of 95ºF dry bulb (DB) and 75ºF wet bulb (WB).
The shaded table columns and rows indicate reference data. When operating at this temperature, these values can be different if the system is not running consistently.
14 | ART COOL MIRROR Due to our policy of continuous product innovation, some specifications may change without notification.
©LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp.
MULTI F ART COOL MIRROR INDOOR UNITS
MULTI F MAX Cooling Capacity Table
Table 5: Multi F Art Cool Mirror Indoor Units Cooling Capacity Table (continued).
Model No. / Indoor Air Temp. °F DB / °F WB
Nominal Capacity Outdoor Air
Temp. 68 / 57 73 / 61 77 / 64 80 / 67 86 / 72 90 / 75
of Indoor Unit (°F DB) TC SHC TC SHC TC SHC TC SHC TC SHC TC SHC
(Btu/h)
14 17.65 12.33 18.74 13.02 19.84 12.61 20.63 12.88 22.03 12.98 23.12 13.23
20 17.63 12.43 18.73 13.13 19.82 12.71 20.61 12.98 22.01 13.09 23.11 13.33
25 17.62 12.52 18.71 13.23 19.81 12.81 20.60 13.08 22.00 13.19 23.09 13.44
30 17.60 12.62 18.70 13.33 19.79 12.91 20.58 13.18 21.98 13.29 23.07 13.54
35 17.59 12.71 18.68 13.43 19.78 13.00 20.57 13.28 21.96 13.39 23.05 13.64
40 17.58 12.81 18.67 13.53 19.76 13.10 20.55 13.38 21.94 13.49 23.04 13.75
45 17.56 12.90 18.66 13.63 19.75 13.20 20.53 13.48 21.93 13.59 23.02 13.85
50 17.55 13.00 18.64 13.73 19.73 13.30 20.52 13.58 21.91 13.69 23.00 13.95
55 17.54 13.10 18.63 13.83 19.72 13.39 20.50 13.68 21.89 13.79 22.98 14.05
60 17.52 13.19 18.61 13.93 19.70 13.49 20.49 13.78 21.88 13.89 22.97 14.16
65 17.51 13.29 18.60 14.03 19.69 13.59 20.47 13.87 21.86 13.99 22.95 14.26
LAN180HSV5 70 17.50 13.38 18.58 14.13 19.67 13.69 20.46 13.97 21.84 14.09 22.93 14.36
18,000 75 17.08 13.16 18.16 13.92 19.24 13.49 20.03 13.79 21.41 13.92 22.50 14.20
80 16.66 12.93 17.74 13.70 18.82 13.30 19.60 13.60 20.98 13.75 22.06 14.03
85 16.24 12.70 17.32 13.47 18.40 13.09 19.17 13.40 20.55 13.56 21.63 13.85
90 15.82 12.46 16.90 13.23 17.97 12.88 18.75 13.19 20.12 13.37 21.20 13.67
95 15.37 12.33 16.44 13.12 17.51 12.78 18.00 12.90 19.65 13.30 20.72 13.61
100 14.99 12.00 16.06 12.78 17.13 12.47 17.77 12.70 19.28 13.01 20.35 13.33
105 14.62 11.67 15.69 12.45 16.76 12.17 17.53 12.50 18.90 12.73 19.97 13.05
Due to our policy of continuous product innovation, some specifications may change without notification. ART COOL MIRROR | 15
©LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp.
ART COOL MIRROR INDOOR UNITS MULTI F
Heating Capacity Table MULTI F MAX
Table 6: Multi F Art Cool Mirror Indoor Units Heating Capacity Table.
Model No. / Outdoor Air Temp. Indoor Air Temp. °F DB
Nominal Capacity of 61 64 68 70 72 75
Indoor Unit °F DB °F WB
(Btu/h) TC TC TC TC TC TC
0 -0.4 5.61 5.53 5.48 5.45 5.37 5.14
5 4.5 6.32 6.24 6.18 6.16 6.08 5.85
10 9 7.03 6.95 6.90 6.88 6.79 6.56
17 15 7.98 7.90 7.85 7.82 7.75 7.48
20 19 8.33 8.26 8.21 8.18 8.09 7.82
25 23 8.93 8.85 8.79 8.77 8.69 8.37
Multi F and Multi F MAX Indoor Unit Engineering Manual
16 | ART COOL MIRROR Due to our policy of continuous product innovation, some specifications may change without notification.
©LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp.
MULTI F ART COOL MIRROR INDOOR UNITS
MULTI F MAX Acoustic Data
Figure 4: Sound Pressure Level Measurement Location. • Measurement taken 2.6′ below the bottom of the unit and at a
distance of 3.3′ from face of unit.
• Measurements taken with no attenuation and units operating at full
load normal operating condition.
• Sound level will vary depending on a range of factors such as
construction (acoustic absorption coefficient) of particular area in
which the equipment is installed.
• Sound power levels are measured in dB(A).
• Tested in anechoic chamber per ISO Standard 3745.
3.3 ft.
Table 7:Sound Pressure Levels (dB[A]).
2.6 ft.
Sound Pressure Levels (dB[A]) (Cooling and Heating)
Model No. Medium Fan
High Fan Speed Low Fan Speed
Speed
LAN090HSV5 36 32 27
Microphone
Due to our policy of continuous product innovation, some specifications may change without notification. ART COOL MIRROR | 17
©LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp.
ART COOL MIRROR INDOOR UNITS MULTI F
Air Velocity and Temperature Distribution MULTI F MAX
Figure 6: LAN090HSV5 and LAN120HSV5 Air Velocity and Temperature Distribution Charts.
Cooling Heating
Multi F and Multi F MAX Indoor Unit Engineering Manual
18 | ART COOL MIRROR Due to our policy of continuous product innovation, some specifications may change without notification.
©LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp.
MULTI F ART COOL MIRROR INDOOR UNITS
MULTI F MAX Refrigerant Flow Diagram
Th3
Table 8: Art Cool Mirror Indoor Unit Refrigerant Pipe Sizes. Table 9: Art Cool Mirror Indoor Unit Refrigerant Pipe Connections
Indoor Unit Capacity Vapor Line Size Liquid Line Size Vapor Line Liquid Line
Indoor Unit Capacity Connection
(in., OD) (in., OD) (in., OD) Connection (in., OD)
9,000 Btu/h 9,000 Btu/h
Ø3/8 Ø3/8 Ø1/4
12,000 Btu/h Ø1/4 12,000 Btu/h
18,000 Btu/h Ø1/2 18,000 Btu/h Ø5/8 Ø3/8
Due to our policy of continuous product innovation, some specifications may change without notification. ART COOL MIRROR | 19
©LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp.
ART COOL MIRROR INDOOR UNITS MULTI F
Wiring Diagram MULTI F MAX
Figure 9: Multi F Art Cool Mirror LAN090HSV5, LAN120HSV5, and LAN180HSV5 Indoor Units Wiring Diagram.
Multi F and Multi F MAX Indoor Unit Engineering Manual
20 | ART COOL MIRROR Due to our policy of continuous product innovation, some specifications may change without notification.
©LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp.
MULTI F ART COOL MIRROR INDOOR UNITS
MULTI F MAX Factory Supplied Parts and Materials
7,000 ~ 15,000and
LAN090HSV5 Btu/h Indoor Units 18,000 and 24,000
LAN120HSV5 Btu/h Indoor Units
LAN180HSV5
WARNING
Installation work must be performed by trained personnel and in accordance with national wiring standards and all local or other applicable codes.
Improper installation can result in fire, electric shock, physical injury, or death.
Note:
Read all instructions before installing this product. Become familiar with the unit’s components and connections, and the order of installation. Incorrect
installation can degrade or prevent proper operation.
Due to our policy of continuous product innovation, some specifications may change without notification. ART COOL MIRROR | 21
©LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp.
ART COOL MIRROR INDOOR UNITS MULTI F
Installation and Best Layout Practices MULTI F MAX
DANGER
To avoid the possibility of fire, do not install the unit in an area where combustible gas will generate, flow, stagnate, or leak. Failure to do so will
cause serious bodily injury or death. Before beginning installation, read the safety summary at the beginning of this manual.
Select a location for installing the wall-mounted indoor unit (IDU) that meets the following conditions:
• Where there is enough structural strength to bear the weight of the unit
• Where air circulation will not be blocked
• Where noise prevention is taken into consideration
Multi F and Multi F MAX Indoor Unit Engineering Manual
• Indoor units (IDUs) must not be placed in an environment where the IDUs will be exposed to harmful volatile organic compounds (VOCs)
or in environments where there is improper air make up or supply or inadequate ventilation. If there are concerns about VOCs in the envi-
ronment where the IDUs are installed, proper air make up or supply and/or adequate ventilation must be provided. Additionally, in buildings
where IDUs will be exposed to VOCs, consider a third party factory-applied epoxy coating to the fan coils for each IDU where the entire coil
is dipped, not sprayed.
• If the unit is installed near a body of water, the installation parts are at risk of corroding. Appropriate anti-corrosion methods must be taken
for the unit and all installation parts.
Installing in an Area Exposed to Unconditioned Air Figure 10:Minimum Clearance Requirements.
In some installation applications, areas (floors, walls) in some rooms
will be exposed to unconditioned air (room will be above or next to
an unheated garage or storeroom). To countermeasure: >4 inches
• Verify that carpet is or will be installed (carpet will increase the
≥5 inches
temperature by three degrees).
• Add insulation between the floor joists.
• Install radiant heat or another type of heating system to the floor.
>4 inches
Required Clearances
Figure 10 shows required clearance distances around a typical
Recommended height
installed wall-mounted unit. >6-1/2 feet from floor
22 | ART COOL MIRROR Due to our policy of continuous product innovation, some specifications may change without notification.
©LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp.
MULTI F ART COOL MIRROR INDOOR UNITS
MULTI F MAX Installation and Best Layout Practices
Figure 11:Installation Plate for LAN090HSV5 and LAN120HSV5 Units. Figure 12:Installation Plate for LAN180HSV5 Units.
Place a level on raised tab
Unit Outline Place a level on raised tab
Unit Outline
(3/16"~5/16")
downward on the outdoor unit side). Bushing
2. Finish off the newly drilled hole as shown with bushing and sleeve covering. Sleeve and bush- Sleeve
ing prevents damage to the tubing/bundling of the piping.
Hanging the Indoor Unit Chassis Figure 13:Locking the Indoor Unit onto the Installation Plate.
1. Attach the three (3) hooks on the top of the indoor unit to the top edge of
the installation plate. Verify the hooks are properly attached to the instal-
lation plate by gently shaking the indoor unit from side to side.
2. Unlock the tubing clamp from the indoor unit frame. For easier access be-
tween the bottom of the indoor unit and the wall, prop the clamp between
the indoor unit frame and installation plate.
3. Remove the screw covers at the bottom of the indoor unit, unscrew the
two (2) screws, remove the frame cover, remove the piping connection Installation plate
cover, and position the piping for installation (down, back, left, or right).
Figure 14:Accessing the Back of the Indoor Unit. Figure 15:Removing the Frame Cover.
Frame Cover
Tubing Clamp
Figure 16:Exterior Back View of Indoor Unit. Figure 17:Piping Installed to the Left. Figure 18:Piping Installed to the Right.
Tubing Clamp
Tape
Connecting
Tape
pipe
Connecting
Right Left pipe
Back Drain hose
Down
Drain hose
Due to our policy of continuous product innovation, some specifications may change without notification. ART COOL MIRROR | 23
©LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp.
ART COOL MIRROR INDOOR UNITS MULTI F
Installation and Best Layout Practices MULTI F MAX
• Loose wiring will cause unit to malfunction, overheat, and catch fire, resulting in severe injury or death.
Note:
• Terminal screws will become loose during transport. Properly tighten the terminal connections during installation.
A voltage drop will cause the following problems:
• Magnetic switch vibration, fuse breaks, or disturbance to the normal function of an overload protection device.
• Compressor will not receive the proper starting current.
Connecting the Power Wiring and Communications Cable
1. Insert the power wiring/communications cable from the outdoor Figure 20:Connecting the Power Wiring / Communications Cable.
unit or branch distribution unit (Multi F MAX systems only)
through the bottom of the indoor unit.
3. Secure the power wiring/communications cable with the cable Terminal block
restraint.
Wired Remote Controller
Figure 21:Simplified View of Indoor Unit to Outdoor Unit / Branch Terminal (Optional)
Distribution Unit Terminal Connections—LAN090HSV5 and Power wiring /
LAN120HSV5 models.
communications cable
Outdoor Unit Terminal Block or Cable restraint
GND Branch Distribution Unit Terminal Block
Indoor Unit Terminal Block (Multi F MAX Systems Only)
3 or S
1(L1) 2(L2) 3
GRN / YLW
BR
GND
BL
RD
BR
GND
BL
RD
24 | ART COOL MIRROR Due to our policy of continuous product innovation, some specifications may change without notification.
©LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp.
MULTI F ART COOL MIRROR INDOOR UNITS
MULTI F MAX Installation and Best Layout Practices
Figure 23:AKB74955602 Wireless Controller. Table 12: AKB74955602 Wireless Controller Functions.
Screen Display
* *
RESET
Buttons
Due to our policy of continuous product innovation, some specifications may change without notification. ART COOL MIRROR | 25
©LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp.
ART COOL MIRROR INDOOR UNITS MULTI F
Installation and Best Layout Practices MULTI F MAX
GRN / YLW
GRN / YLW
BR
RD
BL
Multi F and Multi F MAX Indoor Unit Engineering Manual
BR
RD
BL
To Outdoor Unit or Branch Distribution Unit To Wired Controller To Outdoor Unit or Branch Distribution Unit To Wired Controller
(Multi F MAX Systems Only) (Multi F MAX Systems Only)
Wired Controller Placement Figure 26:Proper Location for the Wired Controller.
Wired controllers include a sensor to detect room temperature. To maintain comfort
levels in the conditioned space, the wired controller must be installed in a location
away from direct sunlight, high humidity, and where it could be directly exposed to
cold air. Controller must be installed four (4) to five (5) feet above the floor where its
LED display can be read easily, in an area with good air circulation, and where it can YES
detect an average room temperature.
TEMP
Remote Controlle r
NO
TEMP
Remote Controlle r
NO
• Concealed pipes and chimneys
• An area where temperatures are uncontrolled, such as an outside wall
26 | ART COOL MIRROR Due to our policy of continuous product innovation, some specifications may change without notification.
©LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp.
MULTI F ART COOL MIRROR INDOOR UNITS
MULTI F MAX Installation and Best Layout Practices
Hanging the Wired Controller Figure 27:Removing the Cable Guide Grooves.
Top
1. The controller wiring/cable can be installed in one of three direc- Top
tions: top, back, or on the right side. If top or right side installation
is desired, remove cable guide grooves on the controller, and
then position wiring/cable on applicable side. Back Right
Side
Right
Side
2. Choose and mark the area of installation, and then screw the wall
plate into place (using the provided parts). Install the controller
wall plate to fit the electrical box if one is present. Ensure that no
gaps exist between the wall plate and the wall itself.
Figure 28:Attaching the Wall Plate. Figure 29:Installing/Removing the
3. Arrange wiring/cables so as not to interfere with the controller Controller.
circuitry. Position the wired controller on the wall plate. Snap into
Installing the Controller
place by pressing the bottom part of the wired controller onto
the wall plate. Make sure that no gaps exist between the wired
controller and the wall plate on all sides. Wall Wall
Due to our policy of continuous product innovation, some specifications may change without notification. ART COOL MIRROR | 27
©LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp.
ART COOL GALLERY ™
ART COOL Gallery Indoor Units direction at the discharge, Figure 30: Multi F Art Cool Gallery
simulating a natural outdoor Indoor Unit.
General breeze.
All LG indoor units are factory assembled, wired, piped, and pro-
vided with a control circuit board, fan, and motor. Art Cool Gallery Air Filter
indoor units have a sound rating no higher than 42 dB(A) as tested Return air is filtered with a
per KSA0701 ISO Standard 3745. factory-supplied, removable,
washable pre-filter. Filter
Coil access is from the front of
Indoor unit coils are comprised of a minimum of two rows of the unit without the use of
aluminum fins mechanically bonded to copper tubing. The coils are tools.
pressure tested at the factory. Each unit is provided with a factory
installed condensate drain pan below the coil. Airflow Guide Vanes
Motorized oscillating guide
Refrigerant System vanes are factory installed,
System is designed for use with R410A refrigerant. The refrigeration and allows the ability to
circuit is pressure-tested at the factory and shipped with a holding control the direction of
charge of helium gas. Refrigerant pipe connections are 45° flare. airflow from side to side. A
All refrigerant lines from the outdoor unit to the indoor units must be motorized air sweep louver provides an automatic change in airflow
field insulated. by directing the air up and down to provide uniform air distribution.
Features
• Inverter (Variable speed fan) • Group control • 24-Hour on/off timer
• Chaos swing • Self-cleaning indoor coil • Wireless LCD remote control included;
• Jet cool • Auto operation / auto restart operation wired thermostat available (sold separately)
Due to our policy of continuous product innovation, some specifications may change without notification. ART COOL GALLERY™ | 29
©LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp.
ART COOL GALLERY INDOOR UNITS MULTI F
General Data / Specifications MULTI F MAX
Table 13: Multi F Art Cool Gallery Indoor Unit General Data.
Model Name LMAN097HVP LMAN127HVP
Nominal Cooling Capacity (Btu/h) 1
9,000 11,200
Nominal Heating Capacity (Btu/h) 1
10,400 13,300
Operating Range
Cooling (°F WB) 57-77 57-77
Heating (°F DB) 59-81 59-81
Multi F and Multi F MAX Indoor Unit Engineering Manual
Fan
Type Turbo Turbo
Motor Output (W) x Qty. 24 x 1 24 x 1
Motor/Drive Brushless Digitally Controlled / Direct Brushless Digitally Controlled / Direct
Airflow Rate CFM (H/M/L) 272 / 208 / 155 314 / 258 / 198
Unit Data
Refrigerant Type2 R410A R410A
Refrigerant Control EEV EEV
Power Supply V, Ø, Hz 3
208-230, 1, 60 208-230, 1, 60
Rated Amps (A) 0.2 0.2
Sound Pressure Level dB(A) (H/M/L) 4
39 / 35 / 31 42 / 38 / 34
Dimensions (W x H x D, in.) 23-5/8 x 23-5/8 x 5-25/32 23-5/8 x 23-5/8 x 5-25/32
Net Unit Weight (lbs.) 32 32
Shipping Weight (lbs.) 37 37
Power Wiring / Communications Cable 4 x 14 4 x 14
(No. x AWG)5
Heat Exchanger (2 x 20 x 21) x 1 (2 x 20 x 21) x 1
(Row x Column x Fin / inch) x Number
Piping
Liquid (in.) 1/4 1/4
Vapor (in.) 3/8 3/8
Drain O.D. / I.D. (in.) 27/32, 5/8 27/32, 5/8
1
Nominal capacity is rated 0 ft. above sea level with corresponding refrigerant piping length in 3
Acceptable operating voltage: 187V-253V.
accordance with standard length of each outdoor unit and a 0 ft. level difference between outdoor and 4
Sound pressure levels are tested in an anechoic chamber under ISO Standard 3745 and are the
indoor units. All capacities are net with a combination ratio between 95 – 105%. same in both cooling and heating mode. These values can increase due to ambient conditions during
Nominal cooling capacity rating obtained with air entering the indoor unit at 80ºF dry bulb (DB) and 67ºF operation.
wet bulb (WB) and outdoor ambient conditions of 95ºF dry bulb (DB) and 75ºF wet bulb (WB). 5
All power wiring / communications cable to the IDUs be minimum 14 AWG, 4-conductor, stranded,
Nominal heating capacity rating obtained with air entering the indoor unit at 70ºF dry bulb (DB) and 60ºF shielded or unshielded (if shielded, must be grounded to chassis at ODU only) and must comply with
wet bulb (WB) and outdoor ambient conditions of 47ºF dry bulb (DB) and 43ºF wet bulb (WB). applicable local and national codes.
2
This unit comes with a dry helium charge.
30 | ART COOL GALLERY™ Due to our policy of continuous product innovation, some specifications may change without notification.
©LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp.
MULTI F ART COOL GALLERY INDOOR UNITS
MULTI F MAX Dimensions
Supply
Air
Supply Air Vane
Supply Air
Air
Supply
Due to our policy of continuous product innovation, some specifications may change without notification. ART COOL GALLERY™ | 31
©LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp.
ART COOL GALLERY INDOOR UNITS MULTI F
Cooling Capacity Table MULTI F MAX
Table 14: Multi F Art Cool Gallery Indoor Units Cooling Capacity Table.
Model No. / Indoor Air Temp. °F DB / °F WB
Nominal Capacity Outdoor Air
Temp. 68 / 57 73 / 61 77 / 64 80 / 67 86 / 72 90 / 75
of Indoor Unit (°F DB) TC SHC TC SHC TC SHC TC SHC TC SHC TC SHC
(Btu/h)
14 8.82 5.68 9.37 6.00 9.92 5.81 10.31 5.93 11.01 5.98 11.56 6.09
20 8.82 5.72 9.36 6.04 9.91 5.85 10.31 5.98 11.01 6.03 11.55 6.14
25 8.81 5.77 9.36 6.09 9.90 5.90 10.30 6.02 11.00 6.07 11.54 6.19
30 8.80 5.81 9.35 6.14 9.90 5.94 10.29 6.07 10.99 6.12 11.54 6.23
35 8.80 5.85 9.34 6.18 9.89 5.99 10.28 6.11 10.98 6.17 11.53 6.28
40 8.79 5.90 9.33 6.23 9.88 6.03 10.27 6.16 10.97 6.21 11.52 6.33
Multi F and Multi F MAX Indoor Unit Engineering Manual
45 8.78 5.94 9.33 6.28 9.87 6.08 10.27 6.21 10.96 6.26 11.51 6.38
50 8.78 5.99 9.32 6.32 9.87 6.12 10.26 6.25 10.96 6.30 11.50 6.42
55 8.77 6.03 9.31 6.37 9.86 6.17 10.25 6.30 10.95 6.35 11.49 6.47
60 8.76 6.07 9.31 6.42 9.85 6.21 10.24 6.34 10.94 6.40 11.48 6.52
65 8.76 6.12 9.30 6.46 9.84 6.26 10.24 6.39 10.93 6.44 11.47 6.56
LMAN097HVP 70 8.75 6.16 9.29 6.51 9.84 6.30 10.23 6.43 10.92 6.49 11.47 6.61
9,000 75 8.54 6.06 9.08 6.41 9.62 6.21 10.01 6.35 10.71 6.41 11.25 6.54
80 8.33 5.96 8.87 6.31 9.41 6.12 9.80 6.26 10.49 6.33 11.03 6.46
85 8.12 5.85 8.66 6.20 9.20 6.03 9.59 6.17 10.28 6.24 10.82 6.38
90 7.91 5.74 8.45 6.09 8.99 5.93 9.37 6.07 10.06 6.16 10.60 6.30
95 7.68 5.68 8.22 6.04 8.75 5.88 9.00 5.94 9.83 6.12 10.36 6.27
100 7.50 5.52 8.03 5.89 8.57 5.74 8.88 5.85 9.64 5.99 10.17 6.14
105 7.31 5.37 7.84 5.73 8.38 5.60 8.77 5.76 9.45 5.86 9.99 6.01
110 7.12 5.19 7.66 5.55 8.19 5.43 8.58 5.58 9.26 5.69 9.80 5.85
115 6.94 5.03 7.47 5.39 8.01 5.29 8.39 5.44 9.08 5.56 9.61 5.71
118 6.82 5.00 7.36 5.36 7.89 5.26 8.28 5.42 8.96 5.54 9.50 5.70
122 6.79 4.98 7.32 5.35 7.86 5.25 8.24 5.41 8.93 5.53 9.46 5.69
14 10.98 7.06 11.66 7.46 12.34 7.22 12.84 7.38 13.71 7.44 14.39 7.58
20 10.97 7.12 11.65 7.52 12.33 7.28 12.83 7.43 13.70 7.50 14.38 7.64
25 10.96 7.17 11.64 7.58 12.32 7.34 12.82 7.49 13.69 7.55 14.37 7.70
30 10.95 7.23 11.63 7.64 12.31 7.39 12.81 7.55 13.68 7.61 14.36 7.76
35 10.95 7.28 11.63 7.69 12.31 7.45 12.80 7.61 13.66 7.67 14.34 7.82
40 10.94 7.34 11.62 7.75 12.30 7.51 12.79 7.66 13.65 7.73 14.33 7.87
45 10.93 7.39 11.61 7.81 12.29 7.56 12.78 7.72 13.64 7.79 14.32 7.93
50 10.92 7.45 11.60 7.87 12.28 7.62 12.77 7.78 13.63 7.84 14.31 7.99
55 10.91 7.50 11.59 7.92 12.27 7.67 12.76 7.83 13.62 7.90 14.30 8.05
60 10.90 7.56 11.58 7.98 12.26 7.73 12.75 7.89 13.61 7.96 14.29 8.11
65 10.90 7.61 11.57 8.04 12.25 7.78 12.74 7.95 13.60 8.02 14.28 8.17
LMAN127HVP 70 10.89 7.67 11.56 8.10 12.24 7.84 12.73 8.01 13.59 8.07 14.27 8.23
12,000 75 10.63 7.54 11.30 7.97 11.97 7.73 12.46 7.90 13.32 7.97 14.00 8.13
80 10.36 7.41 11.04 7.85 11.71 7.62 12.19 7.79 13.05 7.87 13.73 8.04
85 10.10 7.27 10.77 7.72 11.45 7.50 11.93 7.67 12.79 7.77 13.46 7.94
90 9.84 7.14 10.51 7.58 11.18 7.38 11.67 7.56 12.52 7.66 13.19 7.83
95 9.56 7.06 10.23 7.51 10.89 7.32 11.20 7.39 12.23 7.62 12.89 7.80
100 9.33 6.87 10.00 7.32 10.66 7.15 11.05 7.28 11.99 7.45 12.66 7.64
105 9.10 6.68 9.76 7.13 10.43 6.97 10.91 7.16 11.76 7.29 12.43 7.48
110 8.86 6.46 9.53 6.90 10.20 6.76 10.68 6.95 11.53 7.08 12.19 7.27
115 8.63 6.26 9.30 6.71 9.96 6.58 10.44 6.77 11.30 6.91 11.96 7.11
118 8.49 6.22 9.16 6.67 9.82 6.54 10.30 6.74 11.16 6.89 11.82 7.09
122 8.44 6.20 9.11 6.65 9.78 6.53 10.26 6.73 11.11 6.88 11.78 7.08
TC = Total Capacity (kBtu/h).
SHC: Sensible Heat Capacity (kBtu/h).
Nominal capacity as rated 0 ft. above sea level and a 0 ft. level difference between outdoor and indoor units. Corresponding refrigerant piping length is accordance with standard length of each outdoor unit.
Nominal cooling capacity rating obtained with air entering the indoor unit at 80ºF dry bulb (DB) and 67ºF wet bulb (WB), and outdoor ambient conditions of 95ºF dry bulb (DB) and 75ºF wet bulb (WB).
The shaded table columns and rows indicate reference data. When operating at this temperature, these values can be different if the system is not running consistently.
32 | ART COOL GALLERY™ Due to our policy of continuous product innovation, some specifications may change without notification.
©LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp.
MULTI F ART COOL GALLERY INDOOR UNITS
MULTI F MAX Heating Capacity Table
Table 15: Multi F Art Cool Gallery Indoor Units Heating Capacity Table.
Model No. / Outdoor Air Temp. Indoor Air Temp. °F DB
Nominal Capacity 61 64 68 70 72 75
of Indoor Unit °F DB °F WB
(Btu/h) TC TC TC TC TC TC
0 -0.4 5.35 5.28 5.23 5.20 5.12 4.90
5 4.5 6.03 5.95 5.90 5.88 5.80 5.58
10 9 6.71 6.63 6.58 6.56 6.48 6.26
17 15 7.61 7.54 7.49 7.46 7.39 7.14
20 19 7.95 7.88 7.83 7.80 7.72 7.46
25 23 8.52 8.44 8.39 8.37 8.29 7.99
30 28 9.01 8.93 8.88 8.86 8.78 8.52
Due to our policy of continuous product innovation, some specifications may change without notification. ART COOL GALLERY™ | 33
©LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp.
ART COOL GALLERY INDOOR UNITS MULTI F
Acoustic Data MULTI F MAX
Figure 32: Sound Pressure Level Measurement Location. • Measurement taken 2.6′ below the bottom of the unit and at a
distance of 3.3′ from face of unit.
• Measurements taken with no attenuation and units operating at full
load normal operating condition.
• Sound level will vary depending on a range of factors such as
construction (acoustic absorption coefficient) of particular area in
which the equipment is installed.
• Sound power levels are measured in dB(A).
• Tested in anechoic chamber per ISO Standard 3745.
Multi F and Multi F MAX Indoor Unit Engineering Manual
3.3ft
Table 16: Sound Pressure Levels (dB[A]).
2.6ft Sound Pressure Levels (dB[A]) (Cooling and Heating)
Model No. Medium Fan
High Fan Speed Low Fan Speed
Speed
Microphone LMAN097HVP 39 35 31
LMAN127HVP 42 38 34
70 70
NC-65 NC-65
Octave Band Sound Pressure Level (0dB = 20μPa)
60 60
NC-60 NC-60
NC-55 NC-55
50 50
NC-50 NC-50
NC-45 NC-45
40 40
NC-40 NC-40
NC-35 NC-35
30 30
NC-30 NC-30
NC-25 NC-25
20 20
Approximate Approximate
NC-20 NC-20
Hearing Hearing
Threshold Threshold
NC-15 NC-15
10 10
63 125 250 500 1000 2000 4000 8000 63 125 250 500 1000 2000 4000 8000
Octave Band Center Frequency (Hz) Octave Band Center Frequency (Hz)
s
34 | ART COOL GALLERY™ Due to our policy of continuous product innovation, some specifications may change without notification.
©LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp.
MULTI F ART COOL GALLERY INDOOR UNITS
MULTI F MAX Air Velocity and Temperature Distribution
7f t 7f t
6.6 6.6
3f t 3f t
4.6
4.9
52
109
55
3f t 3f t
106
59
63 102
66 91 95 99
0f t 0f t
16ft 13ft 10ft 7 ft 3f t 0f t 16ft 13ft 10ft 7 ft 3f t 0f t
7f t 7f t
8.2
6.6
6.6
3f t 3f t
4.9
4.9
1.6 3.3
1.6 3.3
0f t 0f t
16ft 13ft 10f t 7 ft 3f t 0f t 16ft 13ft 10f t 7 ft 3f t 0f t
7f t 7f t
52 11 3
55 109
59 3f t 3f t
106
66 63 99 102
91 95
0f t 0f t
16ft 13ft 10f t 7 ft 3f t 0f t 16ft 13ft 10f t 7 ft 3f t 0f t
Due to our policy of continuous product innovation, some specifications may change without notification. ART COOL GALLERY™ | 35
©LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp.
ART COOL GALLERY INDOOR UNITS MULTI F
Refrigerant Flow Diagram MULTI F MAX
Figure 36: Art Cool Gallery Indoor Unit Refrigerant Flow Diagram.
Outlet Temperature
M
Table 17: Art Cool Gallery Indoor Unit Refrigerant Pipe Connection Port Diameters.
Model No. Vapor (inch) Liquid (inch)
LMAN097HVP
Ø3/8 Ø1/4
LMAN127HVP
36 | ART COOL GALLERY™ Due to our policy of continuous product innovation, some specifications may change without notification.
©LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp.
MULTI F ART COOL GALLERY INDOOR UNITS
MULTI F MAX Wiring Diagram
Figure 37: Multi F Art Cool Gallery Indoor Units Wiring Diagram.
Due to our policy of continuous product innovation, some specifications may change without notification. ART COOL GALLERY™ | 37
©LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp.
ART COOL GALLERY INDOOR UNITS MULTI F
Factory Supplied Parts and Materials MULTI F MAX
Wireless Handheld
Controller with Holder One (1)
(AKB73635607)
WARNING
Installation work must be performed by trained personnel and in accordance with national wiring standards and all local or other applicable codes.
Improper installation can result in fire, electric shock, physical injury, or death.
Note:
Read all instructions before installing this product. Become familiar with the unit’s components and connections, and the order of installation. Incorrect
installation can degrade or prevent proper operation.
38 | ART COOL GALLERY™ Due to our policy of continuous product innovation, some specifications may change without notification.
©LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp.
MULTI F ART COOL GALLERY INDOOR UNITS
MULTI F MAX Installation and Best Layout Practices
3
Using the Installation Guide
1. Choose an appropriate location for the indoor unit. To hang the installation guide, verify that it is
level and plumb, and then tape it to the wall.
2. Drill four (4) 1/4-inch diameter holes with a depth of 1-3/16 to 1-3/8 inches for the mounting Plastic Anchor
screws. Drill one (1) two (2) inch-diameter hole for the field-installed refrigerant and drain piping.
Note:
If the unit is installed near a body of water, certain components are at risk of being corroded.
Appropriate anti-corrosion methods must be taken for the unit and all components.
Due to our policy of continuous product innovation, some specifications may change without notification. ART COOL GALLERY™ | 39
©LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp.
ART COOL GALLERY INDOOR UNITS MULTI F
Installation and Best Layout Practices MULTI F MAX
2. Remove the two (2) screws at the bottom (2A), then lift off the front
panel (2B).
2A 2B
Multi F and Multi F MAX Indoor Unit Engineering Manual
Panel Connector
Removing the Piping and Side Covers Figure 41:Removing the Piping and Side Covers.
1. Unscrew the center cover.
2. Remove the cover from the side of the indoor unit chosen for the piping connections,
and then knock out the piping access hole. If the refrigerant piping will be connected
through the back of the unit, the access hole does not need to be knocked out.
Access Hole
3. Remove any burrs that will have been made. for Piping
Side cover
2. Insert the drain hose into the handle of the drain pan.
Field-Installed
Drain Piping
Drain Rubber Stopper
Hose
40 | ART COOL GALLERY™ Due to our policy of continuous product innovation, some specifications may change without notification.
©LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp.
MULTI F ART COOL GALLERY INDOOR UNITS
MULTI F MAX Installation and Best Layout Practices
Preparing the Refrigerant and Drain Piping Connections Figure 43:Preparing the Refrigerant /
1. Depending on the installation requirements, route the indoor unit refrigerant piping and the Drain Connections.
drain hose to the left, right (see guidelines below), or rear of the frame. 1
2. Bundle the piping and drain hose with tape where they meet near the indoor unit frame. Po-
sition the drain hose at the bottom of the bundle (positioning the drain hose at the top of the
bundle will cause the drain pan to overflow inside the indoor unit).
Do not bend the piping/drain hose from side to side; it will damage the components.
Tape
Power wiring /
Communication
cable
Connecting
pipe Drain hose
Hanging the Indoor Unit Frame Figure 45:Hanging the Indoor Unit Frame.
1. Remove the installation guide and hang the indoor unit on the top two (2) screws. Verify Insta
llation
Guid
e
the indoor unit is hanging securely on the screws. 1
Holes for Hanging
2. Align the holes at the bottom of the indoor unit to the mounting holes. Tighten first the top (On back of
indoor unit)
screws, then tighten the bottom screws.
3. Verify that the indoor unit is completely secured to the wall by gently shaking it up and
down. 2
Plastic Anchors
Due to our policy of continuous product innovation, some specifications may change without notification. ART COOL GALLERY™ | 41
©LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp.
ART COOL GALLERY INDOOR UNITS MULTI F
Installation and Best Layout Practices MULTI F MAX
Figure 47:Extending the Drain Hose. Indoor unit piping Flare nut Field-installed
piping
Multi F and Multi F MAX Indoor Unit Engineering Manual
Drain extension
If the drain hose is routed in- Spanner
side a room, add insulation
Flare nut
to prevent condensation from Indoor unit
forming. drain hose Torque Field-installed
Narrow tape wrench piping
Adhesive
Drain hose must point 1. Pour water on the in- Figure 50:Checking the Drainage
down so water can flow door unit evaporator. System.
away easily. Wide tape
Figure 49:Drain Piping Slope. 2. Ensure the water Drain hose
flows through and out
Slope Down of the hose and away
from the indoor unit
without leaking.
Drain extension
s
Indoor Unit
42 | ART COOL GALLERY™ Due to our policy of continuous product innovation, some specifications may change without notification.
©LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp.
MULTI F ART COOL GALLERY INDOOR UNITS
MULTI F MAX Installation and Best Layout Practices
• Loose wiring will cause unit to malfunction, overheat, and catch fire, resulting in severe injury or death.
Note:
• Terminal screws will become loose during transport. Properly tighten the terminal connections during installation.
A voltage drop will cause the following problems:
• Magnetic switch vibration, fuse breaks, or disturbance to the normal function of an overload protection device.
BR
GND
BL
RD
Due to our policy of continuous product innovation, some specifications may change without notification. ART COOL GALLERY™ | 43
©LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp.
ART COOL GALLERY INDOOR UNITS MULTI F
Installation and Best Layout Practices MULTI F MAX
Controller Options
Art Cool Gallery wall-mounted indoor units include a handheld controller (AKB73635607), but optional LG-supplied wired controllers are
available.
Panel Description
Screen
Button
Air circulation button1: Circulates the room air without operating in cooling
or heating mode.
Display
Screen Sleep Mode Auto Button1: Sets the sleep mode auto operation.
Jet Cool / Jet Heat Button1: Warms up or cools down the indoor
temperature within a short period.
44 | ART COOL GALLERY™ Due to our policy of continuous product innovation, some specifications may change without notification.
©LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp.
MULTI F ART COOL GALLERY INDOOR UNITS
MULTI F MAX Installation and Best Layout Practices
BR
RD
BL
cold air. Controller must be installed four (4) to five (5) feet above the floor where its NO
TEMP
Remote Controlle r
LED display can be read easily, in an area with good air circulation, and where it can
roller
Cont
ot e
Rem
Due to our policy of continuous product innovation, some specifications may change without notification. ART COOL GALLERY™ | 45
©LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp.
ART COOL GALLERY INDOOR UNITS MULTI F
Installation and Best Layout Practices MULTI F MAX
2. Reconnect the panel connector found at the top of the indoor unit.
Front Panel
Connector
3. Attach the top part of the front panel, then position its tabs in the
grooves on the bottom part of the indoor unit frame.
46 | ART COOL GALLERY™ Due to our policy of continuous product innovation, some specifications may change without notification.
©LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp.
MULTI F
MULTI F MAX
Due to our policy of continuous product innovation, some specifications may change without notification. ART COOL GALLERY™ | 47
©LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp.
STANDARD
WALL-MOUNTED
INDOOR UNIT DATA
“Mechanical Specifications” on page 49
“General Data / Specifications” on page 50
“Dimensions” on page 51
“Cooling Capacity Table” on page 53
“Heating Capacity Table” on page 56
“Acoustic Data” on page 58
“Air Velocity and Temperature Distribution” on page 60
“Refrigerant Flow Diagram” on page 62
“Wiring Diagram” on page 63
“Factory Supplied Parts and Materials” on page 65
“Installation and Best Layout Practices” on page 66
MULTI F STANDARD WALL-MOUNTED INDOOR UNITS
MULTI F MAX Mechanical Specifications and Features
Standard Wall-Mounted Indoor Units Figure 60: Multi F Standard Wall-Mounted Indoor Unit.
General
All LG indoor units are factory assembled, wired, piped, and pro-
vided with a control circuit board, fan, and motor. Standard Wall-
Mounted units have a sound rating no higher than 46 dB(A) as tested
per KSA0701 ISO Standard 3745.
Coil
Indoor unit coils are comprised of a minimum of two rows of
aluminum fins mechanically bonded to copper tubing. The coils are
pressure tested at the factory. Each unit is provided with a factory Air Filter
installed condensate drain pan below the coil. The return air inlet has a factory-supplied primary removable, wash-
able filter. The unit is also equipped with a secondary 3M Micro Dust
Refrigerant System filter. Filters are accessed from the front of the unit without the use
The system is designed for use with R410A refrigerant. The refrig- of tools.
eration circuit is pressure-tested at the factory and shipped with a
holding charge of helium gas. Refrigerant pipe connections are 45° Airflow Guide Vanes
flare. All refrigerant lines from the outdoor unit to the indoor units A factory-installed motorized guide vane controls the direction of
Standard Wall-Mounted
must be field insulated. airflow from side to side. A motorized louver provides an automatic
change in airflow by directing the air up and down for uniform air
Electrical distribution.
The indoor units require 208–230Vac/60Hz/1Φ power with voltage
variance of no more than ±10%. Microprocessor Control
The indoor unit has an integrated control panel to communicate with
Casing the outdoor unit. All unit operation parameters are stored in non-vola-
The units mount on a vertical surface. They are shipped with a sepa- tile memory resident on the unit microprocessor. The microprocessor
rate back plate that secures the unit to the wall, protruding no more controls space temperature through using the value provided by the
than nine (9) inches. Refrigerant piping can be installed in one (1) of temperature sensor within the indoor unit. The microprocessor control
four (4) different directions. will activate indoor unit operation when the indoor room temperature
falls below or rises above a setpoint temperature, at which point, a
Finish signal is sent to the outdoor unit to begin the appropriate mode. The
The Standard Wall-Mounted unit has a curved architectural panel microprocessor also provides self-diagnostics and auto restart func-
with a pearl white finish. Unit casing has a pearl white or dark gray tions. A field-supplied four-wire power / communications cable must
finish and is manufactured of heavy-duty acrylonitrile butadiene be installed to connect the indoor unit(s) to the outdoor unit.
styrene (ABS) and high impact polystyrene (HIPS) plastic.
Controls
Fan Assembly and Control The indoor unit casing has a factory-standard, integral infrared sen-
The unit has a single, direct-drive, crossflow fan made of high strength sor to communicate with the supplied LG wireless handheld remote
ABS plastic. The fan motor is brushless digitally controlled (BLDC) controller. An optional LG supplied wired controller is available as
with permanently lubricated and sealed ball bearings. The fan / motor an additional accessory. Communication between the indoor units
assembly is mounted on vibration attenuating rubber grommets. Fan and the outdoor unit is accomplished through 14 AWG, four-core,
speed is controlled using a microprocessor-based direct digitally stranded and shielded power / communication cable. The indoor unit
controlled algorithm that provides pre-programmed, field-selectable has built-in wi-fi and can be controlled with LG’s SmartThinQ app on
fixed or auto fan speeds in the Heating and Cooling modes. For a smart device. A field-supplied wi-fi network and smart device are
Standard Wall-Mounted units, the indoor fan has Low, Med, High, Jet required. The SmartThinQ app is free and is available for Android
Cool, and Auto settings for Cooling mode; and has Low, Med, High, and iOS smart devices.
Jet Heat, and Auto settings for Heating mode. The Auto setting adjusts
the fan speed based on the difference between the controller setpoint Condensate
and space temperature. Also, the separate Chaos setting provides a The unit is designed for gravity draining of condensate and includes
simultaneous and random change in fan speed and flow direction at a flexible drain hose capable of installation in one of two directions.
the discharge, simulating a natural outdoor breeze. The unit also includes a connection that is compatible with the Aqua-
Guard® AG-9300-LG condensate sensor.
Features
• Inverter (Variable speed fan) • Group control • Built-in wi-fi
• Comfort Air • Self-cleaning indoor coil • Dehumidifying function
• 3M filter • Auto operation • Self-diagnostic function
• Jet cool/Jet Heat • Auto restart operation • Wireless LCD remote control included
Due to our policy of continuous product innovation, some specifications may change without notification. STD. WALL-MOUNTED | 49
©LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp.
STANDARD WALL-MOUNTED INDOOR UNITS MULTI F
General Data / Specifications MULTI F MAX
Fan
Type Cross Flow
Motor Output (W) x Qty. 30 x 1 60 x 1
Motor/Drive Brushless Digitally Controlled / Direct
Airflow Rate CFM (H/M/L) 254 / 204 / 148 268 / 218 / 169 282 / 233 / 177 314 / 268 / 184 558 / 438 / 353 597 / 452 / 367
Unit Data
Refrigerant Type2 R410A
Refrigerant Control EEV
Power Supply V, Ø, Hz 3
208-230, 1, 60
Rated Amps (A) 0.4
Sound Pressure Level dB(A) 35 / 31 / 26 36 / 32 / 27 38 / 34 / 29 42 / 38 / 32 44 / 38 / 34 46 / 41 / 36
(H/M/L)4
32-15/16 x 39-9/32 x
Dimensions (W x H x D, in.)
12-1/8 x 7-7/16 13-19/32 x 8-9/32
Net Unit Weight (lbs.) 18.3 25.6
Shipping Weight (lbs.) 23.4 32.2
Power Wiring / Communications 4 x 14
Cable (No. x AWG)5
Heat Exchanger (Row x Column x (2 x 23 x 22) x 1 (2 x 16 x 20) x 1
Fin / inch) x Number
Pipe Size
Liquid (in.) 1/4
Vapor (in.) 3/8 1/2
Connection Size
Liquid (in.) 1/4 3/8 1/4
Vapor (in.) 3/8 5/8 1/2
Drain O.D. / I.D. (in.) 27/32, 5/8
1
Nominal capacity is rated 0 ft. above sea level with corresponding refrigerant piping length in 3
Acceptable operating voltage: 187V-253V.
accordance with standard length of each outdoor unit and a 0 ft. level difference between outdoor and 4
Sound pressure levels are tested in an anechoic chamber under ISO Standard 3745 and are the
indoor units. All capacities are net with a combination ratio between 95 – 105%. same in both cooling and heating mode. These values can increase due to ambient conditions during
Nominal cooling capacity rating obtained with air entering the indoor unit at 80ºF dry bulb (DB) and 67ºF operation.
wet bulb (WB) and outdoor ambient conditions of 95ºF dry bulb (DB) and 75ºF wet bulb (WB). 5
All power wiring / communications cable to the IDUs be minimum 14 AWG, 4-conductor, stranded,
Nominal heating capacity rating obtained with air entering the indoor unit at 70ºF dry bulb (DB) and 60ºF shielded or unshielded (if shielded, must be grounded to chassis at ODU only) and must comply with
wet bulb (WB) and outdoor ambient conditions of 47ºF dry bulb (DB) and 43ºF wet bulb (WB). applicable local and national codes.
2
This unit comes with a dry helium charge.
50 | STD. WALL-MOUNTED Due to our policy of continuous product innovation, some specifications may change without notification.
©LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp.
Standard Wall-Mounted
51
Dimensions
STANDARD WALL-MOUNTED INDOOR UNITS
|
STD. WALL-MOUNTED
Unit : Inch (mm)
30-3/16 (767)
Air Intake Hole
Rear Rear
©LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp.
Due to our policy of continuous product innovation, some specifications may change without notification.
Right
[5-29/32 (150)]
Air Intake Hole
Left
32-15/16 (837) 7-7/16 (189) 32-15/16 (837)
2-15/32 (63)
3-21/32 (93) 12-1/16 (306) 3-11/16 (94)
2-15/32
Figure 61: LMN079HVT, LSN090HSV5, LSN120HSV5, and LMN159HVT Dimensions.
Air Intake
(63)
2-17/32 (64)
10-11/32 (263)
Refrigerant,
Drain Pipe
12-1/8 (308)
Display & Remote
12-1/8 (308)
Refrigerant,
and Cable
Drain Pipe 5-19/32 (142) 7-27/32 (199)
Routing Controller Signal and Cable
Knock Out
Hole Receiver Routing
Ø2-9/16 (65) Ø2-9/16 (65)
Knock Out
tlet 6)
le
Hole
Ou (5
29/32 (23)
29/32 (23)
Ho
2-7/32 (56)
2-7/32(56)
Air -7/32
Installation Plate
11/32 (9)
2
2-5/16
(59)
Refrigerant, Drain Approx. 8-19/32 (218) to liquid pipe
12-1/8 (308)
2-7/16 ( 61.5)
2-3/8 (60) Pipe and Cable
1-1/4 (31) 3-5/8 (92) Routing Knock Out Hole
Decoration Cover Drain Hose
1/4 (6) x 1/8 (3) Connection
* If airflow direction control is available,
1-27/32(47)
5/8 (15.3) 1-9/32 (32.7)
2-13/32 (61)
Up & Down Left & Right 1-1/2 (38) 5-3/16 (132)
1/8 (3) x 1/4 (6) Unit Outline
Cooling Heating Connecting Gas/Liquid Pipe
55° 55°
MULTI F MAX
15°
15°
45°
MULTI F
85°
MULTI F MAX
MULTI F
Rear
Air Intake Hole
[6-11/16 (170)]
Left Right
©LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp.
Due to our policy of continuous product innovation, some specifications may change without notification.
8-9/32 (210) 39-9/32 (998)
39-9/32 (998)
2-3/32 (53)
2-3/32 (53)
4-17/32 (115) 14-11/16 (373) 5-13/32 (137)
2-23/32 (69)
Air Intake
11-13/16 (300)
Refrigerant,
Refrigerant, Drain Pipe
13-19/32 (345)
Drain Pipe and Cable
13-19/32 (345)
and Cable Display & Remote Routing 7-13/32 (188)
Routing
Controller Signal Knock Out 5-29/32 (150)
Knock Out Hole
Ho )]
Ø2-9/16 (65)
tlet 74
Hole Receiver
le
Ø2-9/16 (65)
Ou 32 (
1-1/16 (27)
1-1/16 (27)
2-3/8 (60)
2-3/8 (60)
Air -29/
Installation Plate
[2
7/16(11)
Air 7/16 (11) 3-9/32 (83)
2-3/8 (60) [34-11/32 (872)] Bottom Outlet 3-9/32 (83)
2-3/8 (60) Unit Outline
Air Outlet Hole 5-9/32 (134) 5-29/32 (150)
Fixing the Installation Plate, Drilling Hole
1-7/16 (33.5)
1-3/32 (50.2) 1-1/16 (26.2)
39-9/32 (998)
5-31/32 (152)
2-7/32 (56)
Communication
2-7/16 ( 61.5)
Figure 62: LSN180HSV5 and LMN249HVT Dimensions.
13-19/32 (345)
1-1/4 (31) Refrigerant, Drain
Approx. 9-7/16 (240) to gas pipe
2-1/4 (57) Pipe and Cable
1/4 (6) x 1/8 (3) Routing Knock Out Approx. 6-5/16 (160) to liquid pipe
3-17/32 (90)
5/8 (15.3) 1-9/32 (32.7)
Decoration Cover Hole Drain Hose
2-13/32 (61)
Connection
2-15/32 (63)
1/8 (3) x 1/4 (6) * If airflow direction control is available,
Up & Down Left & Right 6-15/32 (164)
1-15/32 (37) Unit Outline
Cooling Heating
Connecting Gas/Liquid Pipe
50° 50°
15°
20°
| STD. WALL-MOUNTED
45°
85°
Dimensions
52
Multi F and Multi F MAX Indoor Unit Engineering Manual
MULTI F STANDARD WALL-MOUNTED INDOOR UNITS
MULTI F MAX Cooling Capacity Table
Table 22: Multi F Standard Wall-Mounted Indoor Units Cooling Capacity Table.
Model No. / Indoor Air Temp. °F DB / °F WB
Nominal Capacity Outdoor Air
Temp. 68 / 57 73 / 61 77 / 64 80 / 67 86 / 72 90 / 75
of Indoor Unit (°F DB) TC SHC TC SHC TC SHC TC SHC TC SHC TC SHC
(Btu/h)
14 6.86 4.68 7.29 4.95 7.71 4.79 8.02 4.89 8.57 4.93 8.99 5.03
20 6.86 4.72 7.28 4.99 7.71 4.83 8.02 4.93 8.56 4.97 8.99 5.06
25 6.85 4.76 7.28 5.02 7.70 4.86 8.01 4.97 8.55 5.01 8.98 5.10
30 6.85 4.79 7.27 5.06 7.70 4.90 8.00 5.01 8.55 5.05 8.97 5.14
35 6.84 4.83 7.27 5.10 7.69 4.94 8.00 5.04 8.54 5.09 8.97 5.18
40 6.84 4.87 7.26 5.14 7.68 4.98 7.99 5.08 8.53 5.12 8.96 5.22
45 6.83 4.90 7.25 5.18 7.68 5.01 7.99 5.12 8.53 5.16 8.95 5.26
50 6.83 4.94 7.25 5.22 7.67 5.05 7.98 5.16 8.52 5.20 8.94 5.30
55 6.82 4.97 7.24 5.25 7.67 5.09 7.97 5.19 8.51 5.24 8.94 5.34
60 6.81 5.01 7.24 5.29 7.66 5.12 7.97 5.23 8.51 5.28 8.93 5.38
65 6.81 5.05 7.23 5.33 7.66 5.16 7.96 5.27 8.50 5.31 8.92 5.42
LMN079HVT 70 6.80 5.08 7.23 5.37 7.65 5.20 7.95 5.31 8.49 5.35 8.92 5.45
7,000 75 6.64 5.00 7.06 5.29 7.48 5.13 7.79 5.24 8.33 5.29 8.75 5.39
80 6.48 4.91 6.90 5.20 7.32 5.05 7.62 5.16 8.16 5.22 8.58 5.33
85 6.31 4.82 6.73 5.12 7.15 4.97 7.46 5.09 7.99 5.15 8.41 5.26
90 6.15 4.73 6.57 5.03 6.99 4.89 7.29 5.01 7.83 5.08 8.24 5.19
Standard Wall-Mounted
95 5.98 4.68 6.39 4.98 6.81 4.85 7.00 4.90 7.64 5.05 8.06 5.17
100 5.83 4.56 6.25 4.86 6.66 4.74 6.91 4.82 7.50 4.94 7.91 5.06
105 5.69 4.43 6.10 4.73 6.52 4.62 6.82 4.75 7.35 4.83 7.77 4.96
110 5.54 4.28 5.96 4.58 6.37 4.48 6.67 4.61 7.21 4.70 7.62 4.82
115 5.39 4.15 5.81 4.45 6.23 4.36 6.53 4.49 7.06 4.58 7.48 4.71
118 5.31 4.12 5.72 4.42 6.14 4.34 6.44 4.47 6.97 4.57 7.39 4.70
122 5.28 4.11 5.69 4.41 6.11 4.33 6.41 4.46 6.94 4.56 7.36 4.70
14 8.82 6.04 9.37 6.38 9.92 6.18 10.31 6.31 11.01 6.36 11.56 6.48
20 8.82 6.09 9.36 6.43 9.91 6.23 10.31 6.36 11.01 6.41 11.55 6.53
25 8.81 6.13 9.36 6.48 9.90 6.27 10.30 6.41 11.00 6.46 11.54 6.58
30 8.80 6.18 9.35 6.53 9.90 6.32 10.29 6.46 10.99 6.51 11.54 6.63
35 8.80 6.23 9.34 6.58 9.89 6.37 10.28 6.50 10.98 6.56 11.53 6.68
40 8.79 6.28 9.33 6.63 9.88 6.42 10.27 6.55 10.97 6.61 11.52 6.73
45 8.78 6.32 9.33 6.68 9.87 6.47 10.27 6.60 10.96 6.66 11.51 6.78
50 8.78 6.37 9.32 6.73 9.87 6.51 10.26 6.65 10.96 6.71 11.50 6.83
55 8.77 6.42 9.31 6.78 9.86 6.56 10.25 6.70 10.95 6.76 11.49 6.88
60 8.76 6.46 9.31 6.83 9.85 6.61 10.24 6.75 10.94 6.81 11.48 6.93
65 8.76 6.51 9.30 6.88 9.84 6.66 10.24 6.80 10.93 6.85 11.47 6.98
LSN090HSV5 70 8.75 6.56 9.29 6.92 9.84 6.70 10.23 6.85 10.92 6.90 11.47 7.03
9,000 75 8.54 6.45 9.08 6.82 9.62 6.61 10.01 6.75 10.71 6.82 11.25 6.96
80 8.33 6.34 8.87 6.71 9.41 6.51 9.80 6.66 10.49 6.73 11.03 6.87
85 8.12 6.22 8.66 6.60 9.20 6.41 9.59 6.56 10.28 6.64 10.82 6.79
90 7.91 6.10 8.45 6.48 8.99 6.31 9.37 6.46 10.06 6.55 10.60 6.70
95 7.68 6.04 8.22 6.43 8.75 6.26 9.00 6.32 9.83 6.52 10.36 6.67
100 7.50 5.88 8.03 6.26 8.57 6.11 8.88 6.22 9.64 6.37 10.17 6.53
105 7.31 5.72 7.84 6.10 8.38 5.96 8.77 6.12 9.45 6.23 9.99 6.39
110 7.12 5.52 7.66 5.90 8.19 5.78 8.58 5.94 9.26 6.06 9.80 6.22
115 6.94 5.36 7.47 5.74 8.01 5.63 8.39 5.79 9.08 5.91 9.61 6.08
118 6.82 5.32 7.36 5.70 7.89 5.60 8.28 5.76 8.96 5.89 9.50 6.06
122 6.79 5.30 7.32 5.69 7.86 5.59 8.24 5.76 8.93 5.89 9.46 6.06
TC = Total Capacity (kBtu/h).
SHC: Sensible Heat Capacity (kBtu/h).
Nominal capacity as rated 0 ft. above sea level and a 0 ft. level difference between outdoor and indoor units. Corresponding refrigerant piping length is accordance with standard length of each outdoor unit.
Nominal cooling capacity rating obtained with air entering the indoor unit at 80ºF dry bulb (DB) and 67ºF wet bulb (WB), and outdoor ambient conditions of 95ºF dry bulb (DB) and 75ºF wet bulb (WB).
The shaded table columns and rows indicate reference data. When operating at this temperature, these values can be different if the system is not running consistently.
Due to our policy of continuous product innovation, some specifications may change without notification. STD. WALL-MOUNTED | 53
©LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp.
STANDARD WALL-MOUNTED INDOOR UNITS MULTI F
Cooling Capacity Table MULTI F MAX
Table 23: Multi F Standard Wall-Mounted Indoor Units Cooling Capacity Table (continued).
Model No. / Indoor Air Temp. °F DB / °F WB
Nominal Capacity Outdoor Air
Temp. 68 / 57 73 / 61 77 / 64 80 / 67 86 / 72 90 / 75
of Indoor Unit (°F DB) TC SHC TC SHC TC SHC TC SHC TC SHC TC SHC
(Btu/h)
14 11.76 8.51 12.49 8.99 13.22 8.70 13.75 8.88 14.69 8.96 15.42 9.13
20 11.75 8.57 12.48 9.06 13.21 8.77 13.74 8.95 14.67 9.03 15.40 9.20
25 11.75 8.64 12.48 9.13 13.20 8.84 13.73 9.02 14.66 9.10 15.39 9.27
30 11.74 8.71 12.47 9.20 13.19 8.90 13.72 9.09 14.65 9.17 15.38 9.34
35 11.73 8.77 12.46 9.27 13.18 8.97 13.71 9.16 14.64 9.24 15.37 9.41
40 11.72 8.84 12.45 9.34 13.17 9.04 13.70 9.23 14.63 9.31 15.36 9.48
Multi F and Multi F MAX Indoor Unit Engineering Manual
45 11.71 8.90 12.44 9.41 13.16 9.11 13.69 9.30 14.62 9.38 15.35 9.55
50 11.70 8.97 12.43 9.47 13.15 9.17 13.68 9.37 14.61 9.45 15.33 9.62
55 11.69 9.03 12.42 9.54 13.14 9.24 13.67 9.44 14.60 9.52 15.32 9.70
60 11.68 9.10 12.41 9.61 13.13 9.31 13.66 9.50 14.59 9.58 15.31 9.77
65 11.67 9.17 12.40 9.68 13.12 9.38 13.65 9.57 14.57 9.65 15.30 9.84
LSN120HSV5 70 11.66 9.23 12.39 9.75 13.11 9.44 13.64 9.64 14.56 9.72 15.29 9.91
12,000 75 11.38 9.08 12.11 9.60 12.83 9.31 13.35 9.51 14.27 9.60 15.00 9.79
80 11.10 8.92 11.82 9.45 12.55 9.17 13.07 9.38 13.99 9.48 14.71 9.68
85 10.83 8.76 11.54 9.29 12.26 9.03 12.78 9.24 13.70 9.36 14.42 9.56
90 10.55 8.60 11.26 9.13 11.98 8.88 12.50 9.10 13.42 9.22 14.13 9.43
95 10.25 8.51 10.96 9.05 11.67 8.82 12.00 8.90 13.10 9.18 13.81 9.39
100 10.00 8.28 10.71 8.82 11.42 8.61 11.84 8.76 12.85 8.98 13.56 9.20
105 9.75 8.05 10.46 8.59 11.17 8.40 11.69 8.62 12.60 8.78 13.31 9.01
110 9.50 7.77 10.21 8.31 10.92 8.14 11.44 8.37 12.35 8.53 13.07 8.76
115 9.25 7.54 9.96 8.08 10.67 7.92 11.19 8.15 12.10 8.33 12.82 8.56
118 9.10 7.49 9.81 8.03 10.52 7.88 11.04 8.12 11.95 8.30 12.67 8.54
122 9.05 7.47 9.76 8.01 10.48 7.87 10.99 8.11 11.90 8.29 12.62 8.53
14 14.02 10.23 14.89 10.80 15.76 10.46 16.39 10.68 17.50 10.77 18.37 10.97
20 14.01 10.31 14.88 10.89 15.75 10.54 16.38 10.76 17.49 10.85 18.36 11.06
25 14.00 10.39 14.87 10.97 15.74 10.62 16.36 10.85 17.47 10.94 18.34 11.15
30 13.99 10.47 14.85 11.06 15.72 10.70 16.35 10.93 17.46 11.02 18.33 11.23
35 13.98 10.55 14.84 11.14 15.71 10.79 16.34 11.01 17.45 11.11 18.32 11.32
40 13.96 10.62 14.83 11.22 15.70 10.87 16.33 11.10 17.43 11.19 18.30 11.40
45 13.95 10.70 14.82 11.31 15.69 10.95 16.31 11.18 17.42 11.27 18.29 11.49
50 13.94 10.78 14.81 11.39 15.68 11.03 16.30 11.26 17.41 11.36 18.27 11.57
55 13.93 10.86 14.80 11.47 15.66 11.11 16.29 11.34 17.39 11.44 18.26 11.66
60 13.92 10.94 14.79 11.56 15.65 11.19 16.28 11.43 17.38 11.52 18.25 11.74
65 13.91 11.02 14.78 11.64 15.64 11.27 16.26 11.51 17.37 11.61 18.23 11.83
LMN159HVT 70 13.90 11.10 14.76 11.72 15.63 11.35 16.25 11.59 17.35 11.69 18.22 11.91
14,300 75 13.57 10.92 14.43 11.55 15.29 11.19 15.91 11.44 17.01 11.55 17.87 11.78
80 13.23 10.73 14.09 11.36 14.95 11.03 15.57 11.28 16.67 11.40 17.53 11.64
85 12.90 10.53 13.76 11.17 14.61 10.86 15.23 11.11 16.33 11.25 17.18 11.49
90 12.57 10.33 13.42 10.98 14.28 10.68 14.90 10.94 15.99 11.09 16.84 11.34
95 12.21 10.23 13.06 10.88 13.91 10.60 14.30 10.70 15.61 11.03 16.46 11.29
100 11.91 9.95 12.76 10.60 13.61 10.35 14.11 10.53 15.31 10.79 16.16 11.06
105 11.61 9.68 12.46 10.33 13.32 10.09 13.93 10.37 15.02 10.56 15.87 10.83
110 11.32 9.35 12.17 10.00 13.02 9.78 13.63 10.06 14.72 10.26 15.57 10.53
115 11.02 9.07 11.87 9.71 12.72 9.52 13.33 9.80 14.42 10.01 15.27 10.29
118 10.84 9.00 11.69 9.66 12.54 9.48 13.16 9.76 14.24 9.98 15.09 10.26
122 10.78 8.98 11.63 9.64 12.48 9.46 13.10 9.74 14.18 9.97 15.03 10.25
TC = Total Capacity (kBtu/h).
SHC: Sensible Heat Capacity (kBtu/h).
Nominal capacity as rated 0 ft. above sea level and a 0 ft. level difference between outdoor and indoor units. Corresponding refrigerant piping length is accordance with standard length of each outdoor unit.
Nominal cooling capacity rating obtained with air entering the indoor unit at 80ºF dry bulb (DB) and 67ºF wet bulb (WB), and outdoor ambient conditions of 95ºF dry bulb (DB) and 75ºF wet bulb (WB).
The shaded table columns and rows indicate reference data. When operating at this temperature, these values can be different if the system is not running consistently.
54 | STD. WALL-MOUNTED Due to our policy of continuous product innovation, some specifications may change without notification.
©LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp.
MULTI F STANDARD WALL-MOUNTED INDOOR UNITS
MULTI F MAX Cooling Capacity Table
Table 24: Multi F Standard Wall-Mounted Indoor Units Cooling Capacity Table (continued).
Model No. / Indoor Air Temp. °F DB / °F WB
Nominal Capacity Outdoor Air
Temp. 68 / 57 73 / 61 77 / 64 80 / 67 86 / 72 90 / 75
of Indoor Unit (°F DB) TC SHC TC SHC TC SHC TC SHC TC SHC TC SHC
(Btu/h)
14 17.65 12.33 18.74 13.02 19.84 12.61 20.63 12.88 22.03 12.98 23.12 13.23
20 17.63 12.43 18.73 13.13 19.82 12.71 20.61 12.98 22.01 13.09 23.11 13.33
25 17.62 12.52 18.71 13.23 19.81 12.81 20.60 13.08 22.00 13.19 23.09 13.44
30 17.60 12.62 18.70 13.33 19.79 12.91 20.58 13.18 21.98 13.29 23.07 13.54
35 17.59 12.71 18.68 13.43 19.78 13.00 20.57 13.28 21.96 13.39 23.05 13.64
40 17.58 12.81 18.67 13.53 19.76 13.10 20.55 13.38 21.94 13.49 23.04 13.75
45 17.56 12.90 18.66 13.63 19.75 13.20 20.53 13.48 21.93 13.59 23.02 13.85
50 17.55 13.00 18.64 13.73 19.73 13.30 20.52 13.58 21.91 13.69 23.00 13.95
55 17.54 13.10 18.63 13.83 19.72 13.39 20.50 13.68 21.89 13.79 22.98 14.05
60 17.52 13.19 18.61 13.93 19.70 13.49 20.49 13.78 21.88 13.89 22.97 14.16
65 17.51 13.29 18.60 14.03 19.69 13.59 20.47 13.87 21.86 13.99 22.95 14.26
LSN180HSV5 70 17.50 13.38 18.58 14.13 19.67 13.69 20.46 13.97 21.84 14.09 22.93 14.36
18,000 75 17.08 13.16 18.16 13.92 19.24 13.49 20.03 13.79 21.41 13.92 22.50 14.20
80 16.66 12.93 17.74 13.70 18.82 13.30 19.60 13.60 20.98 13.75 22.06 14.03
85 16.24 12.70 17.32 13.47 18.40 13.09 19.17 13.40 20.55 13.56 21.63 13.85
90 15.82 12.46 16.90 13.23 17.97 12.88 18.75 13.19 20.12 13.37 21.20 13.67
Standard Wall-Mounted
95 15.37 12.33 16.44 13.12 17.51 12.78 18.00 12.90 19.65 13.30 20.72 13.61
100 14.99 12.00 16.06 12.78 17.13 12.47 17.77 12.70 19.28 13.01 20.35 13.33
105 14.62 11.67 15.69 12.45 16.76 12.17 17.53 12.50 18.90 12.73 19.97 13.05
110 14.24 11.27 15.32 12.05 16.39 11.79 17.16 12.13 18.53 12.36 19.60 12.70
115 13.87 10.93 14.94 11.71 16.01 11.48 16.79 11.82 18.15 12.07 19.22 12.41
118 13.65 10.85 14.72 11.64 15.79 11.42 16.56 11.77 17.93 12.03 19.00 12.37
122 13.57 10.83 14.64 11.62 15.71 11.40 16.49 11.75 17.85 12.01 18.92 12.36
14 23.53 16.82 24.99 17.77 26.45 17.21 27.50 17.57 29.37 17.72 30.83 18.05
20 23.51 16.95 24.97 17.91 26.43 17.34 27.48 17.70 29.35 17.85 30.81 18.19
25 23.49 17.08 24.95 18.05 26.41 17.47 27.46 17.84 29.33 17.99 30.79 18.33
30 23.47 17.21 24.93 18.19 26.39 17.61 27.44 17.98 29.30 18.13 30.76 18.47
35 23.46 17.35 24.91 18.32 26.37 17.74 27.42 18.12 29.28 18.27 30.74 18.61
40 23.44 17.48 24.89 18.46 26.35 17.88 27.40 18.25 29.26 18.41 30.72 18.75
45 23.42 17.61 24.87 18.60 26.33 18.01 27.38 18.39 29.24 18.54 30.69 18.89
50 23.40 17.74 24.85 18.74 26.31 18.14 27.36 18.52 29.21 18.68 30.67 19.03
55 23.38 17.87 24.84 18.87 26.29 18.27 27.34 18.66 29.19 18.82 30.64 19.17
60 23.37 18.00 24.82 19.01 26.27 18.41 27.32 18.79 29.17 18.95 30.62 19.31
65 23.35 18.13 24.80 19.15 26.25 18.54 27.29 18.93 29.15 19.09 30.60 19.45
LMN249HVT 70 23.33 18.26 24.78 19.28 26.23 18.67 27.27 19.07 29.13 19.23 30.57 19.59
24,000 75 22.77 17.95 24.21 18.99 25.66 18.41 26.70 18.81 28.55 18.99 29.99 19.37
80 22.21 17.65 23.65 18.69 25.09 18.14 26.13 18.55 27.97 18.75 29.42 19.14
85 21.65 17.33 23.09 18.38 24.53 17.86 25.57 18.28 27.40 18.50 28.84 18.90
90 21.09 17.00 22.53 18.06 23.96 17.57 25.00 18.00 26.83 18.24 28.27 18.65
95 20.49 16.82 21.92 17.89 23.35 17.44 24.00 17.60 26.20 18.14 27.63 18.57
100 19.99 16.37 21.42 17.44 22.85 17.02 23.69 17.33 25.70 17.75 27.13 18.19
105 19.49 15.92 20.92 16.99 22.35 16.60 23.38 17.06 25.20 17.36 26.63 17.81
110 18.99 15.38 20.42 16.44 21.85 16.09 22.88 16.55 24.70 16.87 26.13 17.32
115 18.49 14.91 19.92 15.98 21.35 15.66 22.38 16.12 24.20 16.47 25.63 16.93
118 18.19 14.81 19.62 15.88 21.05 15.59 22.08 16.05 23.90 16.41 25.33 16.88
122 18.10 14.77 19.52 15.85 20.95 15.56 21.98 16.03 23.81 16.39 25.23 16.86
TC = Total Capacity (kBtu/h).
SHC: Sensible Heat Capacity (kBtu/h).
Nominal capacity as rated 0 ft. above sea level and a 0 ft. level difference between outdoor and indoor units. Corresponding refrigerant piping length is accordance with standard length of each outdoor unit.
Nominal cooling capacity rating obtained with air entering the indoor unit at 80ºF dry bulb (DB) and 67ºF wet bulb (WB), and outdoor ambient conditions of 95ºF dry bulb (DB) and 75ºF wet bulb (WB).
The shaded table columns and rows indicate reference data. When operating at this temperature, these values can be different if the system is not running consistently.
Due to our policy of continuous product innovation, some specifications may change without notification. STD. WALL-MOUNTED | 55
©LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp.
STANDARD WALL-MOUNTED INDOOR UNITS MULTI F
Heating Capacity Table MULTI F MAX
Table 25: Multi F Standard Wall-Mounted Indoor Units Heating Capacity Table.
Model No. / Outdoor Air Temp. Indoor Air Temp. °F DB
Nominal Capacity of 61 64 68 70 72 75
Indoor Unit (Btu/h) °F DB °F WB
TC TC TC TC TC TC
0 -0.4 4.17 4.11 4.07 4.05 3.99 3.82
5 4.5 4.70 4.64 4.60 4.58 4.52 4.34
10 9 5.22 5.17 5.13 5.11 5.05 4.87
17 15 5.93 5.87 5.83 5.81 5.75 5.56
20 19 6.19 6.13 6.09 6.08 6.02 5.81
25 23 6.63 6.57 6.53 6.52 6.46 6.22
Multi F and Multi F MAX Indoor Unit Engineering Manual
56 | STD. WALL-MOUNTED Due to our policy of continuous product innovation, some specifications may change without notification.
©LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp.
MULTI F STANDARD WALL-MOUNTED INDOOR UNITS
MULTI F MAX Heating Capacity Table
Table 26: Multi F Standard Wall-Mounted Indoor Units Heating Capacity Table.
Model No. / Outdoor Air Temp. Indoor Air Temp. °F DB
Nominal Capacity of 61 64 68 70 72 75
Indoor Unit (Btu/h) °F DB °F WB
TC TC TC TC TC TC
0 -0.4 8.03 7.91 7.84 7.80 7.69 7.35
5 4.5 9.05 8.93 8.86 8.82 8.71 8.37
10 9 10.06 9.95 9.87 9.83 9.72 9.38
17 15 11.42 11.31 11.23 11.19 11.08 10.71
20 19 10.03 11.81 11.73 11.70 11.59 11.19
25 23 12.77 12.66 12.58 12.55 12.43 11.98
30 28 13.51 13.40 13.32 13.28 13.17 12.77
LMN159HVT 35 32 14.25 14.13 14.06 14.02 13.91 13.57
15,600 40 36 14.90 14.79 14.71 14.67 14.56 14.23
45 41 15.56 15.45 15.37 15.34 15.22 14.88
47 43 15.83 15.71 15.64 15.60 15.49 15.15
50 46 16.08 15.97 15.89 15.86 15.74 15.36
55 51 16.51 16.39 16.32 16.28 16.17 15.71
60 56 16.51 16.39 16.32 16.28 16.17 15.78
63 59 16.51 16.39 16.32 16.28 16.17 15.83
68 64 16.51 16.39 16.32 16.28 16.17 15.89
0 -0.4 11.11 10.96 10.85 10.80 10.64 10.18
5 4.5 12.52 12.37 12.26 12.21 12.06 11.58
Standard Wall-Mounted
10 9 13.93 13.77 13.67 13.61 13.46 12.99
17 15 15.81 15.65 15.55 15.49 15.34 14.84
20 19 16.51 16.36 16.25 16.20 16.04 15.49
25 23 17.69 17.53 17.43 17.37 17.22 16.59
30 28 18.70 18.55 18.44 18.39 18.24 17.69
LSN180HSV5 35 32 19.72 19.56 19.46 19.41 19.25 18.79
21,600 40 36 20.63 20.48 20.37 20.32 20.17 19.70
45 41 21.55 21.39 21.29 21.24 21.08 20.61
47 43 21.91 21.76 21.65 21.60 21.44 20.98
50 46 22.26 22.11 22.01 21.95 21.80 21.27
55 51 22.86 22.70 22.59 22.53 22.38 21.76
60 56 22.86 22.70 22.59 22.53 22.38 21.85
63 59 22.86 22.70 22.59 22.53 22.38 21.91
68 64 22.86 22.70 22.59 22.53 22.38 22.02
0 -0.4 13.17 12.99 12.87 12.80 12.61 12.06
5 4.5 14.84 14.66 14.54 14.47 14.29 13.73
10 9 16.51 16.33 16.20 16.14 15.96 15.40
17 15 18.74 18.56 18.42 18.37 18.18 17.59
20 19 19.57 19.39 19.27 19.20 19.01 18.37
25 23 20.96 20.77 20.65 20.59 20.40 19.66
30 28 22.17 21.98 21.85 21.80 21.61 20.96
LMN249HVT 35 32 23.37 23.19 23.07 23.00 22.82 22.26
25,600 40 36 24.45 24.27 24.15 24.08 23.90 23.34
45 41 25.53 25.35 25.23 25.16 24.98 24.42
47 43 25.97 25.79 25.67 25.60 25.41 24.86
50 46 26.39 26.21 26.08 26.02 25.83 25.20
55 51 27.09 26.90 26.78 26.71 26.53 25.79
60 56 27.09 26.90 26.78 26.71 26.53 25.90
63 59 27.09 26.90 26.78 26.71 26.53 25.97
68 64 27.09 26.90 26.78 26.71 26.53 26.08
TC = Total Capacity (kBtu/h).
Nominal capacity as rated 0 ft. above sea level and a 0 ft. level difference between outdoor and indoor units. Corresponding refrigerant piping length is accordance with standard length of each outdoor unit.
Nominal heating capacity rating obtained with air entering the indoor unit at 70ºF dry bulb (DB) and 60ºF wet bulb (WB), and outdoor ambient conditions of 47ºF dry bulb (DB) and 43ºF wet bulb (WB).
Due to our policy of continuous product innovation, some specifications may change without notification. STD. WALL-MOUNTED | 57
©LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp.
STANDARD WALL-MOUNTED INDOOR UNITS MULTI F
Acoustic Data MULTI F MAX
Figure 63: Sound Pressure Level Measurement Location. • Measurement taken 2.6′ below the bottom of the unit and at a
distance of 3.3′ from face of unit.
• Measurements taken with no attenuation and units operating at full
load normal operating condition.
• Sound level will vary depending on a range of factors such as
construction (acoustic absorption coefficient) of particular area in
which the equipment is installed.
• Sound power levels are measured in dB(A).
• Tested in anechoic chamber per ISO Standard 3745.
Multi F and Multi F MAX Indoor Unit Engineering Manual
Microphone
LMN159HVT 42 38 32
LSN180HSV5 44 38 34
LMN249HVT 46 41 36
58 | STD. WALL-MOUNTED Due to our policy of continuous product innovation, some specifications may change without notification.
©LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp.
MULTI F STANDARD WALL-MOUNTED INDOOR UNITS
MULTI F MAX Acoustic Data
Standard Wall-Mounted
Due to our policy of continuous product innovation, some specifications may change without notification. STD. WALL-MOUNTED | 59
©LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp.
STANDARD WALL-MOUNTED INDOOR UNITS MULTI F
Air Velocity and Temperature Distribution MULTI F MAX
Figure 66:LMN079HVT, LSN090HSV5, LSN120HSV5, LMN159HVT Air Velocity and Temperature Distribution Charts.
Multi F and Multi F MAX Indoor Unit Engineering Manual
60 | STD. WALL-MOUNTED Due to our policy of continuous product innovation, some specifications may change without notification.
©LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp.
MULTI F STANDARD WALL-MOUNTED INDOOR UNITS
MULTI F MAX Air Velocity and Temperature Distribution
Standard Wall-Mounted
Due to our policy of continuous product innovation, some specifications may change without notification. STD. WALL-MOUNTED | 61
©LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp.
STANDARD WALL-MOUNTED INDOOR UNITS MULTI F
Refrigerant Flow Diagram MULTI F MAX
Outlet Temperature
Thermistor for
Evaporator Inlet Temperature
Thermistor for
Table 28: Multi F Standard Wall-Mounted Indoor Unit Table 29: Multi F Standard Wall-Mounted Indoor Unit
Refrigerant Pipe Sizes. Refrigerant Pipe Connections.
Model No. Vapor (inch) Liquid (inch) Model No. Vapor (inch) Liquid (inch)
LMN079HVT LMN079HVT
LSN090HSV5 LSN090HSV5
Ø3/8 Ø3/8 Ø1/4
LSN120HSV5 LSN120HSV5
Ø1/4
LMN159HVT LMN159HVT
LSN180HSV5 LSN180HSV5 Ø5/8 Ø3/8
Ø1/2
LMN249HVT LMN249HVT Ø1/2 Ø1/4
Table 30: Multi F LSNxxxHSV5 Standard Wall-Mounted Indoor Unit Table 31: Multi F LMNxxxHVT Standard Wall-Mounted Indoor Unit
Thermistor Details. Thermistor Details.
Description (Based on Cooling Mode) PCB Connector Description (Based on Cooling Mode) PCB Connector
Indoor Air Temperature Thermistor Indoor Air Temperature Thermistor
CN-TH1 CN-TH1
Evaporator Inlet Temperature Thermistor Evaporator Inlet Temperature Thermistor
Evaporator Middle Temperature Thermistor Evaporator Outlet Temperature Thermistor CN-TH2
CN-TH2
Evaporator Outlet Temperature Thermistor Water Level Sensor (Optional) CN-TH3
Water Level Sensor (Optional) CN-TH3
62 | STD. WALL-MOUNTED Due to our policy of continuous product innovation, some specifications may change without notification.
©LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp.
MULTI F STANDARD WALL-MOUNTED INDOOR UNITS
MULTI F MAX Wiring Diagram
Figure 70:Multi F Standard Wall-Mounted LSN090HSV5, LSN120HSV5, LSN180HSV5 Indoor Units Wiring Diagram.
Standard Wall-Mounted
Due to our policy of continuous product innovation, some specifications may change without notification. STD. WALL-MOUNTED | 63
©LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp.
STANDARD WALL-MOUNTED INDOOR UNITS MULTI F
Wiring Diagram MULTI F MAX
Figure 71: Multi F Standard Wall-Mounted LMN079HVT, LMN159HVT, LMN249HVT Indoor Unit Wiring Diagram.
Multi F and Multi F MAX Indoor Unit Engineering Manual
64 | STD. WALL-MOUNTED Due to our policy of continuous product innovation, some specifications may change without notification.
©LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp.
MULTI F STANDARD WALL-MOUNTED INDOOR UNITS
MULTI F MAX Factory Supplied Parts and Materials
7,000 ~ 15,000 Btu/h Indoor Units 18,000 and 24,000 Btu/h Indoor Units
Standard Wall-Mounted
Type “B” Screws
Two (2)
(M4 x 12L)
Wireless
Controller with Holder One (1)
AKB74955602
WARNING
Installation work must be performed by trained personnel and in accordance with national wiring standards and all local or other applicable codes.
Improper installation can result in fire, electric shock, physical injury, or death.
Note:
Read all instructions before installing this product. Become familiar with the unit’s components and connections, and the order of installation. Incorrect
installation can degrade or prevent proper operation.
Due to our policy of continuous product innovation, some specifications may change without notification. STD. WALL-MOUNTED | 65
©LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp.
STANDARD WALL-MOUNTED INDOOR UNITS MULTI F
Installation and Best Layout Practices MULTI F MAX
• Indoor units (IDUs) must not be placed in an environment where the IDUs will be exposed to harmful volatile organic compounds (VOCs)
or in environments where there is improper air make up or supply or inadequate ventilation. If there are concerns about VOCs in the envi-
ronment where the IDUs are installed, proper air make up or supply and/or adequate ventilation must be provided. Additionally, in buildings
where IDUs will be exposed to VOCs, consider a third party factory-applied epoxy coating to the fan coils for each IDU where the entire coil
is dipped, not sprayed.
• If the unit is installed near a body of water, the installation parts are at risk of corroding. Appropriate anti-corrosion methods must be taken for
the unit and all installation parts.
Installing in an Area Exposed to Unconditioned Air Figure 73:Installation Plate—
In some installation applications, areas (floors, walls) in some rooms will be exposed to Side View.
unconditioned air (room will be above or next to an unheated garage or storeroom). To Installation Plate
countermeasure:
• Verify that carpet is or will be installed (carpet will increase the temperature by three degrees).
• Add insulation between the floor joists. Frame
Hooks
• Install radiant heat or another type of heating system to the floor.
Type "A" Screws
Mounting the Installation Plate
The mounting wall must be strong and solid enough to protect the unit from vibration.
• Mount the installation plate on the wall using the Type “A” screws. If mounting the unit on con-
crete, consider using anchor bolts.
• Always mount the installation plate horizontally. Measure the wall and mark the centerline using
thread and a level.
Figure 74:Installation Plate for LMN079HVT, LSN090HSV5,
LSN120HSV5, and LMN159HVT Units. Figure 75:Installation Plate for LSN180HSV5 and LMN249HVT Units.
Place a level on raised tab Place a level on raised tab
Unit Outline Unit Outline
Ø2-9/16
Ø2-9/16
Right rear piping
Ø2-3/4 inches
Left rear piping
Ø2-3/4 inches
Installation Plate
Left rear Measuring Tape Right rear
5 piping
piping
5-3/16 3-11/16
2-23/32 inches 2-7/32 inches
6-7/8 8-1/2
4-1/8 inches 8-5/32 inches
Measuring Tape Hanger
If the unit is installed near a body of water, certain components are at risk of being corroded. Appropriate anti-corrosion methods must be taken for the
unit and all components.
66 | STD. WALL-MOUNTED Due to our policy of continuous product innovation, some specifications may change without notification.
©LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp.
MULTI F STANDARD WALL-MOUNTED INDOOR UNITS
MULTI F MAX Installation and Best Layout Practices
Note:
Do not bend the piping / drain hose from side to side; it will damage the components.
Standard Wall-Mounted
remove the frame cover, remove the piping connection cover, and position the piping
for installation (down, back, left, or right).
Figure 77:Locking the Indoor Unit onto the Installation Plate. Figure 78:Accessing the Back of the Indoor Unit.
Installation plate
Tubing Clamp
Figure 79:Removing the Frame Cover. Figure 80:Exterior Back View of Indoor Unit.
Tubing Clamp
Right Left
Back
Frame Cover Down
Figure 81:Piping Installed to the Left. Figure 82:Piping Installed to the Right.
Tape
Connecting
pipe Tape
Connecting
pipe
Drain hose
Drain hose
Due to our policy of continuous product innovation, some specifications may change without notification. STD. WALL-MOUNTED | 67
©LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp.
STANDARD WALL-MOUNTED INDOOR UNITS MULTI F
Installation and Best Layout Practices MULTI F MAX
• Loose wiring will cause unit to malfunction, overheat, and catch Figure 83: Connecting Power Wiring / Communications Cable.
fire, resulting in severe injury or death.
Note:
• Terminal screws will become loose during transport. Properly
tighten the terminal connections during installation.
A voltage drop will cause the following problems:
• Magnetic switch vibration, fuse breaks, or disturbance to the
normal function of an overload protection device.
• Compressor will not receive the proper starting current.
Terminal block
Connect Power Wiring and Wired Remote Controller
Terminal (Optional)
Communications Cable Power wiring /
communications cable
1. Insert the power wiring / communications cable from the outdoor Cable restraint
unit or branch distribution unit (Multi F MAX systems only) through
the bottom of the indoor unit.
2. Connect each wire to its appropriate terminal on the indoor unit
control board. Verify that the color and terminal numbers from the
outdoor unit or branch distribution unit (Multi F MAX systems only)
wiring match the color and terminal numbers on the indoor unit.
3. Secure power wiring/communications cable with cable restraint.
Figure 84:Simplified View of Indoor Unit to Outdoor Unit / Branch Figure 85:Simplified View of Indoor Unit to Outdoor Unit / Branch
Distribution Unit Terminal Connections—LMN079HVT, LSN090HSV5, Distribution Unit Terminal Connections— LSN180HSV5 and
LSN120HSV5 and LMN159HVT. LMN249HVT.
Outdoor Unit Terminal Block or Outdoor Unit Terminal Block or
GND Branch Distribution Unit Terminal Block Branch Distribution Unit Terminal Block
Indoor Unit Terminal Block (Multi F MAX Systems Only) GND (Multi F MAX Systems Only)
Indoor Unit Terminal Block
3 or S 3 or S
1(L1) 2(L2) 3 1(L1 ) 2(L2) 3
GRN / YLW
GRN / YLW
BR
GND
BR
BL
GND
BL
RD
RD
68 | STD. WALL-MOUNTED Due to our policy of continuous product innovation, some specifications may change without notification.
©LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp.
MULTI F STANDARD WALL-MOUNTED INDOOR UNITS
MULTI F MAX Installation and Best Layout Practices
Controller Options
Standard wall-mounted indoor units include a wireless controller (AKB74955602), but optional LG-supplied wired controllers are available.
Wireless Controller
Figure 86:AKB74955602 Wireless Controller. Table 33: AKB74955602 Wireless Controller Functions.
Screen Display
Standard Wall-Mounted
* *
RESET
Buttons
Due to our policy of continuous product innovation, some specifications may change without notification. STD. WALL-MOUNTED | 69
©LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp.
STANDARD WALL-MOUNTED INDOOR UNITS MULTI F
Installation and Best Layout Practices MULTI F MAX
GRN / YLW
GRN / YLW
BR
BR
RD
RD
BL
BL
To Outdoor Unit or Branch Distribution Unit To Wired Controller To Outdoor Unit or Branch Distribution Unit To Wired Controller
(Multi F MAX Systems Only) (Multi F MAX Systems Only)
Wired Controller Placement Figure 89:Proper Location for the Wired Controller.
Wired controllers include a sensor to detect room temperature. To maintain comfort
levels in the conditioned space, the wired controller must be installed in a location away
from direct sunlight, high humidity, and where it could be directly exposed to cold air.
Controller must be installed four (4) to five (5) feet above the floor where its LED display
can be read easily, in an area with good air circulation, and where it can detect an aver- YES
age room temperature.
TEMP
Remote Controlle r
NO
TEMP
Remote Controlle r
roller
Cont
ot e
Rem
70 | STD. WALL-MOUNTED Due to our policy of continuous product innovation, some specifications may change without notification.
©LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp.
MULTI F STANDARD WALL-MOUNTED INDOOR UNITS
MULTI F MAX Installation and Best Layout Practices
Hanging the Wired Controller Figure 91:Removing the Cable Guide Grooves.
1. The controller wiring / cable can be installed in one of three direc- Top
Top
tions: top, back, or on the right side. If top or right side installation
is desired, remove cable guide grooves on the controller, and
then position wiring / cable on applicable side. Back Right
Side
Right
2. Choose and mark the area of installation. Use the provided parts Side
and screw the wall plate into place. Install the controller wall plate
to fit the electrical box if one is present. Ensure that no gaps exist
between the wall plate and the wall itself.
Standard Wall-Mounted
driver into the two holes at the bottom. Twist screwdriver to
release controller. Do not damage the controller components
when removing. Removing the Controller
Wall Wall
Finalizing Indoor Unit Installation Figure 90:Attach Bottom of Indoor Unit to Installation Plate.
1. Move the tubing clamp to its original position.
2. Ensure the three (3) hooks are properly attached to the installa-
tion plate by gently shaking the indoor unit from side to side.
3. Press the bottom left and right sides of the indoor unit against the
installation plate until the hooks click firmly into their slots. Type 'C' screws
4. Using two (2) Type “C” screws, secure the bottom of the indoor Figure 94:Removing the Filter Tabs.
unit to the installation plate.
Filter
Due to our policy of continuous product innovation, some specifications may change without notification. STD. WALL-MOUNTED | 71
©LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp.
CEILING-CONCEALED
DUCT (LOW STATIC)
INDOOR UNIT DATA
“Mechanical Specifications” on page 73
“General Data / Specifications” on page 74
“Dimensions” on page 75
“Cooling Capacity Table” on page 76
“Heating Capacity Table” on page 78
“External Static Pressure” on page 79
“Acoustic Data” on page 80
“Refrigerant Flow Diagrams” on page 81
“Wiring Diagram” on page 83
“Factory Supplied Parts and Materials” on page 85
“Installation and Best Layout Practices” on page 86
MULTI F DUCT (LOW STATIC) INDOOR UNITS
MULTI F MAX Mechanical Specifications and Features
Ceiling-Concealed Duct (Low Static) Figure 95: Ceiling-Concealed Duct (Low Static) Indoor Unit.
Indoor Unit
General
All LG indoor units are factory assembled, wired, piped, and pro-
vided with a control circuit board, fan, and motor. Ceiling-Concealed
Duct (Low Static) units have a sound rating no higher than 36 dB(A)
as tested per KSA0701 ISO Standard 3745, and are designed for
low-static pressure up to 0.20″WG.
Casing The indoor units are Wi-Fi compatible with the addition of an LG Wi-
The case has a low profile design with a maximum height of 7.5 Fi module accessory, and can be controlled by LG’s Smart ThinQ™
inches designed to mount fully concealed above a finished ceiling in app on a smart device. A field-supplied Wi-Fi network and smart
as little as 8 inches vertical space. Casing is manufactured of gal- device are required. The Smart ThinQ app is free, and is available
vanized steel plate, and provided with hanger brackets designed to for Android™ and iOS. (Android is a trademark of Google LLC.)
support the weight on four corners. Unit has a front horizontal supply
air discharge outlet, and one rear horizontal return air inlet; unit is Controls
also field-convertible for a rear bottom return. The indoor unit controller of choice must be ordered separately.
Communication between the indoor units and the outdoor unit is
Fan Assembly and Control accomplished through 14 AWG, four-core, stranded, shielded or
The units have at least two direct-drive, Sirocco fans made of unshielded power / communication cable.
high strength ABS HT-700 polymeric resin that are statically and
dynamically balanced. The fans are mounted on a common brush- Condensate Lift/Pump
less digitally controlled (BLDC) motor with permanently lubricated The indoor unit is provided with a factory installed and wired conden-
and sealed ball bearings. The fan / motor assembly is mounted on sate lift/pump capable of providing a minimum 27.5 inch lift from the
vibration-attenuating rubber grommets. Fan speed is controlled using bottom surface of the unit. Drain pump has a safety switch to shut off
a microprocessor-based direct digital control algorithm. The indoor the indoor unit if the condensate rises too high in the drain pan.
fan has Low, Med, High, and Auto settings for Cooling mode; and
has Low, Med, High, and Auto settings for Heating mode. Each of the
settings can be field-adjusted from the factory setting (RPM / ESP).
The Auto setting adjusts the fan speed based on the difference
between the controller set-point and space temperature.
Features
• Inverter (Variable speed fan) • Auto restart operation • Self-diagnostics function
• External mounted drain pump • Dehumidification function • Group control
• Control lock function • Two thermistor control • Wired controller ordered separately
• Auto operation • External static pressure control • Wi-Fi compatible
Due to our policy of continuous product innovation, some specifications may change without notification. DUCT (LOW STATIC) | 73
©LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp.
DUCT (LOW STATIC) INDOOR UNITS MULTI F
General Data / Specifications MULTI F MAX
Table 34: Multi F Ceiling-Concealed Low-Static Ducted Indoor Unit General Data.
Model Name LDN097HV4 LDN127HV4 LDN187HV4
Nominal Cooling Capacity (Btu/h) 1
9,000 12,000 18,000
Nominal Heating Capacity (Btu/h) 1
10,400 13,800 20,800
Operating Range
Cooling (°F WB) 57-77
Heating (°F DB) 59-81
Multi F and Multi F MAX Indoor Unit Engineering Manual
Fan
Type Sirocco
Motor Output (W) x Qty. 19 x 1 5 x 1, 19 x 1
Motor/Drive Brushless Digitally Controlled / Direct
Airflow Rate CFM (H/M/L) 318 / 247 / 194 353 / 300 / 247 530 / 441 / 353
Factory Set External Static Pressure (in. wg) 0.10
Max. External Static Pressure (in. wg) 0.20
Unit Data
Refrigerant Type2 R410A
Refrigerant Control EEV
Power Supply V, Ø, Hz 3
208-230, 1, 60
Rated Amps (A) 0.40 0.80
Sound Pressure Level dB(A) (H/M/L) 4
30 / 26 / 23 31 / 28 / 27 36 / 34 / 31
Dimensions (W x H x D, in.) 27-9/16 x 7-15/32 x 27-9/16 35-7/16 x 7-15/32 x 27-9/16
Net Unit Weight (lbs.) 39 51 48.5
Shipping Weight (lbs.) 46 60 57.3
Power Wiring / Communications Cable (No. x AWG) 5
4 x 14
Heat Exchanger (Row x Column x Fin / inch) x Number (2 x 11 x 14) x 1 (2 x 11 x 18) x 1
Pipe Size
Liquid Line (in.) 1/4
Vapor Line (in.) 3/8 1/2
Connection Size
Liquid Line (in.) 1/4
Vapor Line (in.) 3/8 1/2
Drain O.D. / I.D. (in.) 1-1/4, 1
1
Nominal capacity is rated 0 ft. above sea level with corresponding refrigerant piping length in 3
Acceptable operating voltage: 187V-253V.
accordance with standard length of each outdoor unit and a 0 ft. level difference between outdoor and 4
Sound pressure levels are tested in an anechoic chamber under ISO Standard 3745 and are the
indoor units. All capacities are net with a combination ratio between 95 – 105%. same in both cooling and heating mode. These values can increase due to ambient conditions during
Nominal cooling capacity rating obtained with air entering the indoor unit at 80ºF dry bulb (DB) and 67ºF operation.
wet bulb (WB) and outdoor ambient conditions of 95ºF dry bulb (DB) and 75ºF wet bulb (WB). 5
All power wiring / communications cable to the IDUs be minimum 14 AWG, 4-conductor, stranded,
Nominal heating capacity rating obtained with air entering the indoor unit at 70ºF dry bulb (DB) and 60ºF shielded or unshielded (if shielded, must be grounded to chassis at ODU only) and must comply with
wet bulb (WB) and outdoor ambient conditions of 47ºF dry bulb (DB) and 43ºF wet bulb (WB). applicable local and national codes.
2
This unit comes with a dry helium charge.
74 | DUCT (LOW STATIC) Due to our policy of continuous product innovation, some specifications may change without notification.
©LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp.
MULTI F DUCT (LOW STATIC) INDOOR UNITS
MULTI F MAX Dimensions
5-5/16 1-3/8
13/16
Due to our policy of continuous product innovation, some specifications may change without notification. DUCT (LOW STATIC) | 75
©LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp.
DUCT (LOW STATIC) INDOOR UNITS MULTI F
Cooling Capacity Table MULTI F MAX
Table 35: Multi F Ceiling-Concealed Duct (Low Static) Indoor Units Cooling Capacity Table.
Model No. / Indoor Air Temp. °F DB / °F WB
Nominal Capacity Outdoor Air
Temp. 68 / 57 73 / 61 77 / 64 80 / 67 86 / 72 90 / 75
of Indoor Unit (°F DB) TC SHC TC SHC TC SHC TC SHC TC SHC TC SHC
(Btu/h)
14 8.82 7.55 9.37 7.98 9.92 7.72 10.31 7.89 11.01 7.95 11.56 8.10
20 8.82 7.61 9.36 8.04 9.91 7.78 10.31 7.95 11.01 8.01 11.55 8.17
25 8.81 7.67 9.36 8.10 9.90 7.84 10.30 8.01 11.00 8.08 11.54 8.23
30 8.80 7.73 9.35 8.16 9.90 7.90 10.29 8.07 10.99 8.14 11.54 8.29
35 8.80 7.79 9.34 8.22 9.89 7.96 10.28 8.13 10.98 8.20 11.53 8.36
40 8.79 7.84 9.33 8.29 9.88 8.02 10.27 8.19 10.97 8.26 11.52 8.42
Multi F and Multi F MAX Indoor Unit Engineering Manual
45 8.78 7.90 9.33 8.35 9.87 8.08 10.27 8.25 10.96 8.32 11.51 8.48
50 8.78 7.96 9.32 8.41 9.87 8.14 10.26 8.31 10.96 8.38 11.50 8.54
55 8.77 8.02 9.31 8.47 9.86 8.20 10.25 8.38 10.95 8.45 11.49 8.61
60 8.76 8.08 9.31 8.53 9.85 8.26 10.24 8.44 10.94 8.51 11.48 8.67
65 8.76 8.14 9.30 8.59 9.84 8.32 10.24 8.50 10.93 8.57 11.47 8.73
LDN097HV4 70 8.75 8.19 9.29 8.66 9.84 8.38 10.23 8.56 10.92 8.63 11.47 8.79
9,000 75 8.54 8.06 9.08 8.52 9.62 8.26 10.01 8.44 10.71 8.53 11.25 8.69
80 8.33 7.92 8.87 8.39 9.41 8.14 9.80 8.33 10.49 8.42 11.03 8.59
85 8.12 7.78 8.66 8.25 9.20 8.02 9.59 8.20 10.28 8.30 10.82 8.48
90 7.91 7.63 8.45 8.10 8.99 7.89 9.37 8.08 10.06 8.19 10.60 8.37
95 7.68 7.55 8.22 8.03 8.75 7.83 9.00 7.90 9.83 8.14 10.36 8.34
100 7.50 7.35 8.03 7.83 8.57 7.64 8.88 7.78 9.64 7.97 10.17 8.16
105 7.31 7.15 7.84 7.63 8.38 7.45 8.77 7.66 9.45 7.79 9.99 7.99
110 7.12 6.90 7.66 7.38 8.19 7.22 8.58 7.43 9.26 7.57 9.80 7.77
115 6.94 6.69 7.47 7.17 8.01 7.03 8.39 7.24 9.08 7.39 9.61 7.60
118 6.82 6.65 7.36 7.13 7.89 7.00 8.28 7.21 8.96 7.37 9.50 7.58
122 6.79 6.63 7.32 7.11 7.86 6.98 8.24 7.19 8.93 7.36 9.46 7.57
14 11.76 9.94 12.49 10.50 13.22 10.17 13.75 10.38 14.69 10.47 15.42 10.67
20 11.75 10.02 12.48 10.58 13.21 10.25 13.74 10.46 14.67 10.55 15.40 10.75
25 11.75 10.09 12.48 10.66 13.20 10.33 13.73 10.54 14.66 10.63 15.39 10.83
30 11.74 10.17 12.47 10.75 13.19 10.40 13.72 10.62 14.65 10.71 15.38 10.92
35 11.73 10.25 12.46 10.83 13.18 10.48 13.71 10.70 14.64 10.79 15.37 11.00
40 11.72 10.33 12.45 10.91 13.17 10.56 13.70 10.79 14.63 10.88 15.36 11.08
45 11.71 10.40 12.44 10.99 13.16 10.64 13.69 10.87 14.62 10.96 15.35 11.16
50 11.70 10.48 12.43 11.07 13.15 10.72 13.68 10.95 14.61 11.04 15.33 11.25
55 11.69 10.56 12.42 11.15 13.14 10.80 13.67 11.03 14.60 11.12 15.32 11.33
60 11.68 10.63 12.41 11.23 13.13 10.88 13.66 11.11 14.59 11.20 15.31 11.41
65 11.67 10.71 12.40 11.31 13.12 10.96 13.65 11.19 14.57 11.28 15.30 11.49
LDN127HV4 70 11.66 10.79 12.39 11.40 13.11 11.03 13.64 11.27 14.56 11.36 15.29 11.58
12,000 75 11.38 10.61 12.11 11.22 12.83 10.88 13.35 11.12 14.27 11.22 15.00 11.45
80 11.10 10.43 11.82 11.05 12.55 10.72 13.07 10.96 13.99 11.08 14.71 11.31
85 10.83 10.24 11.54 10.86 12.26 10.55 12.78 10.80 13.70 10.93 14.42 11.17
90 10.55 10.04 11.26 10.67 11.98 10.38 12.50 10.63 13.42 10.78 14.13 11.02
95 10.25 9.94 10.96 10.57 11.67 10.30 12.00 10.40 13.10 10.72 13.81 10.97
100 10.00 9.67 10.71 10.31 11.42 10.06 11.84 10.24 12.85 10.49 13.56 10.75
105 9.75 9.41 10.46 10.04 11.17 9.81 11.69 10.08 12.60 10.26 13.31 10.52
110 9.50 9.09 10.21 9.72 10.92 9.51 11.44 9.78 12.35 9.97 13.07 10.24
115 9.25 8.81 9.96 9.44 10.67 9.26 11.19 9.53 12.10 9.73 12.82 10.00
118 9.10 8.75 9.81 9.39 10.52 9.21 11.04 9.49 11.95 9.70 12.67 9.98
122 9.05 8.73 9.76 9.37 10.48 9.19 10.99 9.47 11.90 9.69 12.62 9.97
TC = Total Capacity (kBtu/h).
SHC: Sensible Heat Capacity (kBtu/h).
Nominal capacity as rated 0 ft. above sea level and a 0 ft. level difference between outdoor and indoor units. Corresponding refrigerant piping length is accordance with standard length of each outdoor unit.
Nominal cooling capacity rating obtained with air entering the indoor unit at 80ºF dry bulb (DB) and 67ºF wet bulb (WB), and outdoor ambient conditions of 95ºF dry bulb (DB) and 75ºF wet bulb (WB).
The shaded table columns and rows indicate reference data. When operating at this temperature, these values can be different if the system is not running consistently.
76 | DUCT (LOW STATIC) Due to our policy of continuous product innovation, some specifications may change without notification.
©LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp.
MULTI F DUCT (LOW STATIC) INDOOR UNITS
MULTI F MAX Cooling Capacity Table
Table 36: Multi F Ceiling-Concealed Duct (Low Static) Indoor Units Cooling Capacity Table (continued).
Model No. / Indoor Air Temp. °F DB / °F WB
Nominal Capacity Outdoor Air
Temp. 68 / 57 73 / 61 77 / 64 80 / 67 86 / 72 90 / 75
of Indoor Unit (°F DB) TC SHC TC SHC TC SHC TC SHC TC SHC TC SHC
(Btu/h)
14 17.65 13.09 18.74 13.83 19.84 13.39 20.63 13.67 22.03 13.79 23.12 14.05
20 17.63 13.20 18.73 13.94 19.82 13.50 20.61 13.78 22.01 13.90 23.11 14.16
25 17.62 13.30 18.71 14.05 19.81 13.60 20.60 13.89 22.00 14.01 23.09 14.27
30 17.60 13.40 18.70 14.16 19.79 13.71 20.58 13.99 21.98 14.11 23.07 14.38
35 17.59 13.50 18.68 14.26 19.78 13.81 20.57 14.10 21.96 14.22 23.05 14.49
40 17.58 13.60 18.67 14.37 19.76 13.91 20.55 14.21 21.94 14.33 23.04 14.60
45 17.56 13.71 18.66 14.48 19.75 14.02 20.53 14.31 21.93 14.43 23.02 14.71
50 17.55 13.81 18.64 14.58 19.73 14.12 20.52 14.42 21.91 14.54 23.00 14.82
55 17.54 13.91 18.63 14.69 19.72 14.23 20.50 14.52 21.89 14.65 22.98 14.92
60 17.52 14.01 18.61 14.80 19.70 14.33 20.49 14.63 21.88 14.75 22.97 15.03
65 17.51 14.11 18.60 14.90 19.69 14.43 20.47 14.74 21.86 14.86 22.95 15.14
LDN187HV4
Due to our policy of continuous product innovation, some specifications may change without notification. DUCT (LOW STATIC) | 77
©LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp.
DUCT (LOW STATIC) INDOOR UNITS MULTI F
Heating Capacity Table MULTI F MAX
Table 37: Multi F Ceiling-Concealed Duct (Low Static) Indoor Units Heating Capacity Table.
Model No. / Outdoor Air Temp. Indoor Air Temp. °F DB
Nominal Capacity of 61 64 68 70 72 75
Indoor Unit °F DB °F WB
(Btu/h) TC TC TC TC TC TC
0 -0.4 5.35 5.28 5.23 5.20 5.12 4.90
5 4.5 6.03 5.95 5.90 5.88 5.80 5.58
10 9 6.71 6.63 6.58 6.56 6.48 6.26
17 15 7.61 7.54 7.49 7.46 7.39 7.14
20 19 7.95 7.88 7.83 7.80 7.72 7.46
25 23 8.52 8.44 8.39 8.37 8.29 7.99
Multi F and Multi F MAX Indoor Unit Engineering Manual
78 | DUCT (LOW STATIC) Due to our policy of continuous product innovation, some specifications may change without notification.
©LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp.
MULTI F DUCT (LOW STATIC) INDOOR UNITS
MULTI F MAX External Static Pressure
Table 38: Multi F Ceiling-Concealed Duct (Low Static) External Static Pressure Setting Values Table.
Static Pressure (in. wg) 0.0 0.04 0.08 0.12 0.16 0.20
Model No. / Nominal Capacity Airflow Rate / CFM Setting Value
of Indoor Unit (Btu/h)
High 318 98 103 108 116 123 130
LDN097HV4 Mid 247 82 88 94 102 110 118
9,000
Low 194 69 76 83 91 99 109
High 353 95 99 104 109 116 124
LDN127HV4 Mid 300 86 91 96 101 108 116
12,000
• To get the desired air flow and external static pressure combination, use the setting value from the table. Using a setting value other
than that listed in the table will not provide the desired combination.
• Table data is based at 230V. Air flow rate varies according to voltage fluctuation.
Due to our policy of continuous product innovation, some specifications may change without notification. DUCT (LOW STATIC) | 79
©LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp.
DUCT (LOW STATIC) INDOOR UNITS MULTI F
Acoustic Data MULTI F MAX
Figure 97:Sound Pressure Level Measurement Location. • Measurements taken with no attenuation and units operating at full
load normal operating condition.
• Sound level will vary depending on a range of factors such as
construction (acoustic absorption coefficient) of particular area in
which the equipment is installed.
• Sound power levels are measured in dB(A).
• Tested in anechoic chamber per ISO Standard 3745.
Ceiling
Multi F and Multi F MAX Indoor Unit Engineering Manual
4.9 ft.
70 70 70
Octave Band Sound Pressure Level (0dB = 20μPa)
60
NC-60 NC-60 NC-60
80 | DUCT (LOW STATIC) Due to our policy of continuous product innovation, some specifications may change without notification.
©LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp.
MULTI F DUCT (LOW STATIC) INDOOR UNITS
MULTI F MAX Refrigerant Flow Diagram
: Cooling
: Heating
Evaporator
Outlet
Temperature
Thermistor
Evaporator
Sirocco Fan Inlet
Indoor Unit
Indoor Air
Temperature
Thermistor
Table 40:Multi F Ceiling-Concealed Duct (Low Static) LDN097HV4 Indoor Unit Refrigerant Pipe Sizes.
Model No. Vapor (inch) Liquid (inch)
LDN097HV4 Ø3/8 Ø1/4
Table 41:Multi F Ceiling-Concealed Duct (Low Static) LDN097HV4 Refrigerant Pipe Connections.
Model No. Vapor (inch) Liquid (inch)
LDN097HV4 Ø3/8 Ø1/4
Table 42:Multi F Ceiling-Concealed Duct (Low Static) LDN097HV4 Indoor Unit Thermistor Details.
Description (Based on Cooling Mode) PCB Connector
Indoor Air Temperature Thermistor CN-ROOM
Evaporator Inlet Temperature Thermistor CN-PIPE/IN
Evaporator Outlet Temperature Thermistor CN-PIPE/OUT
Due to our policy of continuous product innovation, some specifications may change without notification. DUCT (LOW STATIC) | 81
©LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp.
DUCT (LOW STATIC) INDOOR UNITS MULTI F
Refrigerant Flow Diagrams MULTI F MAX
: Cooling
: Heating
Evaporator
Outlet
Temperature
Multi F and Multi F MAX Indoor Unit Engineering Manual
Thermistor
Evaporator
Inlet
Sirocco Fan Temperature
Thermistor
M M
Indoor Unit
Indoor Air
Temperature
Thermistor
Table 43: Multi F Ceiling-Concealed Duct (Low Static) LDN127HV4 and LDN187HV4 Indoor Unit Refrigerant
Pipe Sizes.
Model No. Vapor (inch) Liquid (inch)
LDN127HV4 Ø3/8
Ø1/4
LDN187HV4 Ø1/2
Table 44: Multi F Ceiling-Concealed Duct (Low Static) LDN127HV4 and LDN187HV4 Indoor Unit Refrigerant
Pipe Connections.
Model No. Vapor (inch) Liquid (inch)
LDN127HV4 Ø3/8
Ø1/4
LDN187HV4 Ø1/2
Table 45: Multi F Ceiling-Concealed Duct (Low Static) LDN127HV4 and LDN187HV4 Indoor Unit Thermistor
Details.
Description (Based on Cooling Mode) PCB Connector
Indoor Air Temperature Thermistor CN-ROOM
Evaporator Inlet Temperature Thermistor CN-PIPE/IN
Evaporator Outlet Temperature Thermistor CN-PIPE/OUT
82 | DUCT (LOW STATIC) Due to our policy of continuous product innovation, some specifications may change without notification.
©LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp.
MULTI F DUCT (LOW STATIC) INDOOR UNITS
MULTI F MAX Wiring Diagram
Figure 101:Multi F Ceiling-Concealed Duct (Low Static) LDN097HV4 Indoor Units Wiring Diagram.
Due to our policy of continuous product innovation, some specifications may change without notification. DUCT (LOW STATIC) | 83
©LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp.
DUCT (LOW STATIC) INDOOR UNITS MULTI F
Wiring Diagram MULTI F MAX
Figure 102:Multi F Ceiling-Concealed Duct (Low Static) LDN127HV4 and LDN187HV4 Indoor Units Wiring Diagram.
Multi F and Multi F MAX Indoor Unit Engineering Manual
MEZ62689324 11/18
84 | DUCT (LOW STATIC) Due to our policy of continuous product innovation, some specifications may change without notification.
©LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp.
MULTI F DUCT (LOW STATIC) INDOOR UNITS
MULTI F MAX Factory Supplied Parts and Materials
Washers for
Metal Clamp Two (2) Hanging Eight (8)
Insulation for
One (1) Set
Fittings
For Vapor Piping For Liquid Piping
WARNING
Installation work must be performed by trained personnel and in accordance with national wiring standards and all local or other applicable codes.
Improper installation can result in fire, electric shock, physical injury, or death.
Note:
Read all instructions before installing this product. Become familiar with the unit’s components and connections, and the order of installation. Incorrect
installation can degrade or prevent proper operation.
Due to our policy of continuous product innovation, some specifications may change without notification. DUCT (LOW STATIC) | 85
©LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp.
DUCT (LOW STATIC) INDOOR UNITS MULTI F
Installation and Best Layout Practices MULTI F MAX
23-5/8
Access Opening 23-5/8
( 23-5/8 x 23-5/8 )
Don’ts
• Do not install the unit near a heat or steam source, or where considerable Side view (Unit : Inch)
amounts of oil, iron powder, or flour are used.
• Do not install the unit where sulfuric acid and flammable or corrosive gases
are generated, vented into, or stored.
• Do not install the unit near high-frequency generators.
• Do not install the unit near a doorway.
H = ≤25/32
The unit will be damaged, will malfunction, and / or will not operate as
designed if installed in any of the conditions listed. • "H" dimension is necessary to ensure a slope is included for
condensate drainage.
86 | DUCT (LOW STATIC) Due to our policy of continuous product innovation, some specifications may change without notification.
©LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp.
MULTI F DUCT (LOW STATIC) INDOOR UNITS
MULTI F MAX Installation and Best Layout Practices
Duct (Low Static) Indoor Units can be installed in two ways: Table 49:Indoor Unit Bolt Locations.
Figure 105:Air inlet from the back of the indoor Figure 106:Air inlet from the bottom of the E
unit. indoor unit. G
Air Filter Back Panel
D C
Indoor Unit s
J
A
Air Outlet Air Outlet B
Back Panel Air Filter
Drainage hole
Table 48:Indoor Unit Bolt Location Dimensions.
Dimensions (in.)
Model / Capacity (Btu/h)
A B C D E F G H I J
LDN097HV4 / 9,000 28-27/32 30-13/32 25-31/32 27-9/16
LDN127HV4 / 12,000 24-23/32 27-9/16 1-13/32 7-15/32 25/32 6-3/32
36-23/32 38-9/32 33-27/32 35-7/16
LDN187HV4 / 18,000
Preparing the Installation Area and Hanging the Indoor Unit Frame
1. Select and mark the area for the suspension or console bolts 4. Add the plate washer, spring washer, and nut to secure the bolts
(use embedded inserts or anchor bolts in new buildings, and into the installation area.
hole-in-anchors in older buildings). 5. Position the indoor unit installation plates onto the bolts. Secure
2. Drill the holes. using nuts, plate washers, and spring washers. Adjust for level as
3. Add the set-anchor and the plate washer to the bolts (bolts must necessary.
be at least 13/32 inches in diameter), and then insert the bolts
into the installation area.
Figure 107:Preparing the Installation Area. Figure 108:Console Bolt Options. Figure 109:Hanging the Indoor Unit.
M10 Nut X4
(Field
M10 SP. washer X 4 supplied)
M10 washer X4
M10 washer X4
(Field
M10 SP. washer X 4 supplied)
M10 Nut X4
Install a canvas duct to the air outlet and air inlet so that vibration from the indoor unit does not carry
to the duct or ceiling. Also, add insulation to the interior of the duct, and apply anti-vibration to the
suspension bolts.
Due to our policy of continuous product innovation, some specifications may change without notification. DUCT (LOW STATIC) | 87
©LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp.
DUCT (LOW STATIC) INDOOR UNITS MULTI F
Installation and Best Layout Practices MULTI F MAX
fittings.
Ducted (low static) indoor units have two options for condensate drainage: Using the factory-installed drain pump, or using a gravity drain.
Using the Drain Pump Figure 111:Indoor Unit Using Drain Pump.
• Maximum drain lift is 27-9/16 inches, therefore, the drain piping must be placed below
the maximum lift height.
• Field-installed drain piping must have downward gradient of at least 1/50 to 1/100; to 1/50~1/100
prevent reverse flow, slope must not be straight up and down. Drain Pipe
≤27-9/16 inch
Drain Pump
Using the Gravity Drain Figure 112:Indoor Unit Using Gravity Drain.
Field-drain piping must have downward gradient of at least 1/50 to 1/100; to prevent Drain hose
reverse flow, slope must not be straight up and down. Angle ≥ 1/50~1/100
88 | DUCT (LOW STATIC) Due to our policy of continuous product innovation, some specifications may change without notification.
©LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp.
MULTI F DUCT (LOW STATIC) INDOOR UNITS
MULTI F MAX Installation and Best Layout Practices
Due to our policy of continuous product innovation, some specifications may change without notification. DUCT (LOW STATIC) | 89
©LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp.
DUCT (LOW STATIC) INDOOR UNITS MULTI F
Installation and Best Layout Practices MULTI F MAX
• Loose wiring will cause unit to malfunction, overheat, and catch fire, resulting in severe injury or death.
Note:
• Terminal screws will become loose during transport. Properly tighten the terminal connections during installation.
A voltage drop will cause the following problems:
• Magnetic switch vibration, fuse breaks, or disturbance to the normal function of an overload protection device.
• Compressor will not receive the proper starting current.
Connecting the Power Wiring and Communications Cable
1. Insert the power wiring / communications cable from the out- Figure 116:Indoor Unit to Outdoor Unit / Branch Distribution Unit
door unit or branch distribution unit (Multi F MAX systems only) (Multi F MAX systems only) Power Wiring / Communications Cable
through the side of the indoor unit. Pass the wiring through the Connections.
designated access holes to prevent damage. To prevent electro- Outdoor Unit Terminal Block or
magnetic interference and product malfunction, leave a space Branch Distribution Unit Terminal Block
between the power wiring and communications cable outside of Indoor Unit Terminal Block (Multi F MAX Systems Only)
the indoor unit. GND GND
1(L) 2(N) 3 3 or S
2. Connect each wire to its appropriate terminal on the indoor unit
BR
control board. Verify that the color and terminal numbers from
BL
only) wiring match the color and terminal numbers on the indoor
unit.
5. Fill in any gaps around the wiring access hole with sealant to prevent foreign particles from entering the indoor unit.
Using a Conduit Figure 117:Exterior View of Conduit Installation.
1. Remove the rubber stopper on the indoor unit. Pass the power
wiring / communications cable through the conduit, the conduit
mounting plate, and to the control panel of the indoor unit.
Lock nut
2. Connect the power wiring / communications cable to the indoor
unit terminal block.
Conduit Conduit
mounting
3. Screw the conduit mounting plate to the indoor unit. plate
90 | DUCT (LOW STATIC) Due to our policy of continuous product innovation, some specifications may change without notification.
©LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp.
MULTI F DUCT (LOW STATIC) INDOOR UNITS
MULTI F MAX Installation and Best Layout Practices
Controller Options
Ceiling-concealed duct (low static) indoor units can be used with many LG-supplied wired controllers (sold separately). The wireless hand-
held controller (Model No. PQWRHQ0FDB) is also an optional accessory with use wired controllers.
CN-REMO
OPER
Terminal
MODE
Extension cable
BL
RD
YL RD
Comm. 12V BK
(S) Power Ground
Connections on
Wired Controller
Due to our policy of continuous product innovation, some specifications may change without notification. DUCT (LOW STATIC) | 91
©LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp.
DUCT (LOW STATIC) INDOOR UNITS MULTI F
Installation and Best Layout Practices MULTI F MAX
Hanging the Wired Controller Figure 120:Removing the Cable Guide Grooves.
Top
1. The controller wiring / cable can be installed in one of three direc- Top
tions: top, back, or on the right side. If top or right side installation
is desired, remove cable guide grooves on the controller, and
then position wiring / cable on applicable side. Back Right
Side
Right
Side
2. Choose and mark the area of installation, and then screw the wall
plate into place (using the provided parts). Install the controller
wall plate to fit the electrical box if one is present. Ensure that no
Multi F and Multi F MAX Indoor Unit Engineering Manual
gaps exist between the wall plate and the wall itself.
Figure 121:Attaching the Wall Plate. Figure 122: Installing / Removing
3. Arrange wiring / cables so as not to interfere with the controller the Controller.
circuitry. Position the wired controller on the wall plate. Snap into Installing the Controller
place by pressing the bottom part of the wired controller onto
the wall plate. Make sure that no gaps exist between the wired
controller and the wall plate on all sides. Wall Wall
Wired Controller Placement Figure 123:Proper Location for the Wired Controller.
Wall indoor units can be used with various wired controllers (optional; sold sepa-
rately). Wired controllers include a sensor to detect room temperature. To maintain
comfort levels in the conditioned space, the wired controller must be installed in a
location away from direct sunlight, high humidity, and where it could be directly ex-
posed to cold air. Controller must be installed four (4) to five (5) feet above the floor TEMP
YES
where its display can be read easily, in an area with good air circulation, and where it
Remote Controlle r
Remote Controlle r
Do not install the remote controller where it can be impacted by the following: NO
• Drafts or dead spots behind doors and in corners TEMP
4 to 5 feet
above the floor
• Hot or cold air from ducts
roller
Cont
ot e
Rem
92 | DUCT (LOW STATIC) Due to our policy of continuous product innovation, some specifications may change without notification.
©LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp.
MULTI F DUCT (LOW STATIC) INDOOR UNITS
MULTI F MAX Installation and Best Layout Practices
Setting Values
01 : V-H Code
02 : F-H Set Value
04 : F-L TEM P
OPER
FAN
SPEED
MODE
3. Press the on / off button to save the established settings. TEM P
OPER
MODE
4. To deactivate system installer setting mode after the settings have been established, press and hold
the temperature increase and mode selection check buttons simultaneously for approximately three
(3) seconds. If a button is not pressed for more than 25 seconds, the system installer setting mode
will automatically deactivate.
• Select the position after verifying duct work and the external static pressure of the indoor unit.
• Factory set to pressure selection F-H.
Due to our policy of continuous product innovation, some specifications may change without notification. DUCT (LOW STATIC) | 93
©LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp.
DUCT (LOW STATIC) INDOOR UNITS MULTI F
Installation and Best Layout Practices MULTI F MAX
2. Use the fan speed button to select the desired fan speed. ( Lo→Med→Hi will display on the LED).
3. Use the temperature increase and decrease buttons to select the desired external static
Multi F and Multi F MAX Indoor Unit Engineering Manual
pressure setting value (thereby assigning the respective airflow). External static pressure value range:
0~255; the value will display near the lower right corner of the LED.
• A certified technician must set the external static pressure value(s). If the external static pressure is set incorrectly, the system will
malfunction.
• Do not alter the external static pressure value that corresponds to each air flow level.
• External static pressure value can vary depending on the indoor unit.
• If by pressing the fan speed button during external static pressure setup, the fan speed is raised to the next level, the air flow value of
the previous fan speed will be maintained (external static pressure setting value is saved).
94 | DUCT (LOW STATIC) Due to our policy of continuous product innovation, some specifications may change without notification.
©LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp.
CEILING-CONCEALED
DUCT (HIGH STATIC)
INDOOR UNIT DATA
“Mechanical Specifications” on page 96
“General Data / Specifications” on page 97
“Dimensions” on page 98
“Cooling Capacity Table” on page 99
“Heating Capacity Table” on page 100
“External Static Pressure” on page 101
“Acoustic Data” on page 100
“Refrigerant Flow Diagrams” on page 102
“Wiring Diagram” on page 103
“Factory Supplied Parts and Materials” on page 105
“Installation and Best Layout Practices” on page 106
DUCT (HIGH STATIC) INDOOR UNITS MULTI F
Mechanical Specifications and Features MULTI F MAX
Ceiling-Concealed Duct (High Static) Figure 127: Ceiling-Concealed Duct (High Static) Indoor Unit.
Indoor Unit
General
All LG indoor units are factory assembled, wired, piped, and provided
with a control circuit board, fan, and motor. Ceiling-Concealed Duct
(High Static) units are designed for high-speed air volume against an
external static pressure up to 0.78″WG for the 24,000 Btu/h model;
up to 0.55″WG for the 36,000 Btu/h model.
Multi F and Multi F MAX Indoor Unit Engineering Manual
Coil Auto settings for Cooling mode; and has Low, Med, High, and Auto
Indoor unit coils are factory built and are comprised of aluminum fins settings for Heating mode. Each of the settings can be field-adjusted
mechanically bonded to copper tubing. Each unit has two rows of from the factory setting (RPM / ESP). The Auto setting adjusts the
coils, which are pressure tested at the factory. Each unit is provided fan speed based on the difference between the controller setpoint
with a factory installed condensate drain pan below the coil. and space temperature.
Features
• Inverter (Variable speed fan) • Auto restart operation • Group control
• Internal drain pump • Dehumidifying function • Self-diagnostics function
• Control lock function • Two thermistor control • Wired controller ordered separately
• Auto operation • External static pressure control • Wi-Fi compatible
96 | DUCT (HIGH STATIC) Due to our policy of continuous product innovation, some specifications may change without notification.
©LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp.
MULTI F DUCT (HIGH STATIC) INDOOR UNITS
MULTI F MAX General Data / Specifications
Table 51: Multi F Ceiling-Concealed High-Static Ducted Indoor Unit General Data.
Model Name LHN248HV LHN368HV
Nominal Cooling Capacity (Btu/h) 1
24,000 36,000
Nominal Heating Capacity (Btu/h) 1
27,000 40,000
Operating Range
Cooling (°F WB) 57-77 57-77
Heating (°F DB) 59-81 59-81
Fan
Type Sirocco Sirocco
Motor Output (W) x Qty. 136.5 x 1 259 x 1
1
Nominal capacity is rated 0 ft. above sea level with corresponding refrigerant piping length in 3
Acceptable operating voltage: 187V-253V.
accordance with standard length of each outdoor unit and a 0 ft. level difference between outdoor and 4
Sound pressure levels are tested in an anechoic chamber under ISO Standard 3745 and are the
indoor units. All capacities are net with a combination ratio between 95 – 105%. same in both cooling and heating mode. These values can increase due to ambient conditions during
Nominal cooling capacity rating obtained with air entering the indoor unit at 80ºF dry bulb (DB) and 67ºF operation.
wet bulb (WB) and outdoor ambient conditions of 95ºF dry bulb (DB) and 75ºF wet bulb (WB). 5
All power wiring / communications cable to the IDUs be minimum 14 AWG, 4-conductor, stranded,
Nominal heating capacity rating obtained with air entering the indoor unit at 70ºF dry bulb (DB) and 60ºF shielded or unshielded (if shielded, must be grounded to chassis at ODU only) and must comply with
wet bulb (WB) and outdoor ambient conditions of 47ºF dry bulb (DB) and 43ºF wet bulb (WB). applicable local and national codes.
2
This unit comes with a dry helium charge.
Due to our policy of continuous product innovation, some specifications may change without notification. DUCT (HIGH STATIC) | 97
©LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp.
DUCT (HIGH STATIC) INDOOR UNITS MULTI F
Dimensions MULTI F MAX
98 | DUCT (HIGH STATIC) Due to our policy of continuous product innovation, some specifications may change without notification.
©LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp.
MULTI F
MULTI F MAX
Due to our policy of continuous product innovation, some specifications may change without notification. DUCT (HIGH STATIC) | 99
©LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp.
DUCT (HIGH STATIC) INDOOR UNITS MULTI F
Cooling Capacity Table MULTI F MAX
Table 52:Multi F Ceiling-Concealed Duct (High Static) Indoor Units Cooling Capacity Table.
Model No. / Indoor Air Temp. °F DB / °F WB
Nominal Capacity Outdoor Air
Temp. 68 / 57 73 / 61 77 / 64 80 / 67 86 / 72 90 / 75
of Indoor Unit (°F DB) TC SHC TC SHC TC SHC TC SHC TC SHC TC SHC
(Btu/h)
14 23.53 17.66 24.99 18.66 26.45 18.07 27.50 18.45 29.37 18.60 30.83 18.95
20 23.51 17.80 24.97 18.80 26.43 18.21 27.48 18.59 29.35 18.75 30.81 19.10
25 23.49 17.94 24.95 18.95 26.41 18.35 27.46 18.73 29.33 18.89 30.79 19.25
30 23.47 18.08 24.93 19.09 26.39 18.49 27.44 18.88 29.30 19.04 30.76 19.40
35 23.46 18.21 24.91 19.24 26.37 18.63 27.42 19.02 29.28 19.18 30.74 19.54
40 23.44 18.35 24.89 19.38 26.35 18.77 27.40 19.16 29.26 19.33 30.72 19.69
Multi F and Multi F MAX Indoor Unit Engineering Manual
45 23.42 18.49 24.87 19.53 26.33 18.91 27.38 19.31 29.24 19.47 30.69 19.84
50 23.40 18.62 24.85 19.67 26.31 19.05 27.36 19.45 29.21 19.61 30.67 19.99
55 23.38 18.76 24.84 19.82 26.29 19.19 27.34 19.59 29.19 19.76 30.64 20.13
60 23.37 18.90 24.82 19.96 26.27 19.33 27.32 19.73 29.17 19.90 30.62 20.28
65 23.35 19.03 24.80 20.10 26.25 19.47 27.29 19.88 29.15 20.04 30.60 20.42
LHN248HV 70 23.33 19.17 24.78 20.25 26.23 19.61 27.27 20.02 29.13 20.19 30.57 20.57
24,000 75 22.77 18.85 24.21 19.94 25.66 19.33 26.70 19.75 28.55 19.94 29.99 20.34
80 22.21 18.53 23.65 19.63 25.09 19.05 26.13 19.48 27.97 19.69 29.42 20.10
85 21.65 18.19 23.09 19.30 24.53 18.75 25.57 19.19 27.40 19.43 28.84 19.84
90 21.09 17.85 22.53 18.96 23.96 18.45 25.00 18.90 26.83 19.15 28.27 19.59
95 20.49 17.66 21.92 18.79 23.35 18.31 24.00 18.48 26.20 19.05 27.63 19.50
100 19.99 17.19 21.42 18.31 22.85 17.87 23.69 18.19 25.70 18.64 27.13 19.10
105 19.49 16.71 20.92 17.84 22.35 17.43 23.38 17.91 25.20 18.23 26.63 18.70
110 18.99 16.14 20.42 17.26 21.85 16.90 22.88 17.37 24.70 17.71 26.13 18.19
115 18.49 15.66 19.92 16.78 21.35 16.45 22.38 16.93 24.20 17.29 25.63 17.77
118 18.19 15.55 19.62 16.68 21.05 16.36 22.08 16.86 23.90 17.23 25.33 17.72
122 18.10 15.51 19.52 16.64 20.95 16.34 21.98 16.83 23.81 17.21 25.23 17.71
14 35.29 25.46 37.48 26.90 39.67 26.04 41.26 26.59 44.06 26.81 46.25 27.32
20 35.26 25.66 37.45 27.11 39.64 26.25 41.23 26.80 44.02 27.02 46.21 27.54
25 35.24 25.86 37.43 27.32 39.61 26.45 41.19 27.01 43.99 27.23 46.18 27.75
30 35.21 26.06 37.40 27.53 39.58 26.65 41.16 27.21 43.96 27.44 46.14 27.96
35 35.18 26.25 37.37 27.73 39.55 26.85 41.13 27.42 43.92 27.65 46.11 28.17
40 35.16 26.45 37.34 27.94 39.52 27.06 41.10 27.63 43.89 27.86 46.07 28.39
45 35.13 26.65 37.31 28.15 39.49 27.26 41.07 27.83 43.86 28.07 46.04 28.60
50 35.10 26.85 37.28 28.36 39.46 27.46 41.04 28.04 43.82 28.27 46.00 28.81
55 35.08 27.04 37.25 28.57 39.43 27.66 41.01 28.24 43.79 28.48 45.97 29.02
60 35.05 27.24 37.23 28.78 39.40 27.86 40.97 28.45 43.76 28.69 45.93 29.23
65 35.02 27.44 37.20 28.98 39.37 28.06 40.94 28.65 43.72 28.90 45.90 29.44
LHN368HV 70 34.99 27.63 37.17 29.19 39.34 28.26 40.91 28.86 43.69 29.10 45.86 29.65
36,000 75 34.15 27.18 36.32 28.75 38.49 27.87 40.05 28.47 42.82 28.75 44.99 29.32
80 33.31 26.71 35.47 28.29 37.64 27.46 39.20 28.08 41.96 28.39 44.12 28.97
85 32.48 26.23 34.63 27.82 36.79 27.03 38.35 27.66 41.10 28.00 43.26 28.61
90 31.64 25.73 33.79 27.33 35.94 26.59 37.50 27.24 40.25 27.61 42.40 28.23
95 30.74 25.46 32.88 27.09 35.02 26.39 36.00 26.64 39.30 27.46 41.44 28.11
100 29.99 24.78 32.13 26.40 34.27 25.76 35.53 26.23 38.55 26.87 40.69 27.53
105 29.24 24.10 31.38 25.72 33.52 25.13 35.07 25.82 37.80 26.28 39.94 26.96
110 28.49 23.27 30.63 24.89 32.77 24.36 34.32 25.04 37.05 25.54 39.20 26.22
115 27.74 22.58 29.88 24.19 32.02 23.71 33.57 24.41 36.31 24.93 38.45 25.62
118 27.29 22.41 29.43 24.04 31.57 23.59 33.12 24.30 35.86 24.84 38.00 25.55
122 27.14 22.36 29.28 23.99 31.43 23.55 32.97 24.26 35.71 24.81 37.85 25.53
TC = Total Capacity (kBtu/h).
SHC: Sensible Heat Capacity (kBtu/h).
Nominal capacity as rated 0 ft. above sea level and a 0 ft. level difference between outdoor and indoor units. Corresponding refrigerant piping length is accordance with standard length of each outdoor unit.
Nominal cooling capacity rating obtained with air entering the indoor unit at 80ºF dry bulb (DB) and 67ºF wet bulb (WB), and outdoor ambient conditions of 95ºF dry bulb (DB) and 75ºF wet bulb (WB).
The shaded table columns and rows indicate reference data. When operating at this temperature, these values can be different if the system is not running consistently.
100 | DUCT (HIGH STATIC) Due to our policy of continuous product innovation, some specifications may change without notification.
©LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp.
MULTI F DUCT (HIGH STATIC) INDOOR UNITS
MULTI F MAX Heating Capacity Table
Table 53:Multi F Ceiling-Concealed Duct (High Static) Indoor Units Heating Capacity Table.
Model No. / Outdoor Air Temp. Indoor Air Temp. °F DB
Nominal Capacity 61 64 68 70 72 75
of Indoor Unit °F DB °F WB
(Btu/h) TC TC TC TC TC TC
0 -0.4 13.89 13.70 13.57 13.50 13.30 12.72
5 4.5 15.65 15.46 15.33 15.26 15.07 14.48
10 9 17.41 17.22 17.09 17.02 16.83 16.24
17 15 19.76 19.57 19.43 19.37 19.17 18.55
20 19 20.64 20.45 20.32 20.25 20.05 19.37
25 23 22.11 21.91 21.78 21.72 21.52 20.74
30 28 23.38 23.18 23.05 22.99 22.79 22.11
Due to our policy of continuous product innovation, some specifications may change without notification. DUCT (HIGH STATIC) | 101
©LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp.
DUCT (HIGH STATIC) INDOOR UNITS MULTI F
External Static Pressure / Acoustic Data MULTI F MAX
Table 54:Multi F Ceiling-Concealed Duct (High Static) External Static Pressure Setting Values Table.
Static Pressure (in. wg) 0.1 0.16 0.2 0.24 0.28 0.31 0.35 0.39 0.43 0.47 0.51 0.59
Model No. / Nominal Capacity Airflow Rate / CFM Setting Value (in. wg)
of Indoor Unit (Btu/h)
High 777 110 117 121 124 127 130 133 136 137 - 138 140
LHN248HV Mid 706 102 110 114 118 120 125 127 130 133 - 134 136
24,000
Low 636 96 102 107 110 114 118 122 125 127 - 130 132
High 1,130 - 109 112 115 119 122 126 128 131 134 137 144
LHN368HV
Multi F and Multi F MAX Indoor Unit Engineering Manual
Mid 989 - 101 105 108 112 115 119 123 127 130 133 138
36,000
Low 848 - 92 97 101 105 109 113 117 121 124 127 134
• To get the desired air flow and external static pressure combination, use the setting value from the table. Using a setting value other
than that listed in the table will not provide the desired combination.
• Table data is based at 230V. Air flow rate varies according to voltage fluctuation.
Figure 130: Sound Pressure Level Measurement Location. • Measurements taken with no attenuation and units operating at full
load normal operating condition.
DISCHARGE SUCTION • Sound level will vary depending on a range of factors such as
construction (acoustic absorption coefficient) of particular area in
which the equipment is installed.
DUCT DUCT • Sound power levels are measured in dB(A).
• Tested in anechoic chamber per ISO Standard 3745.
6.6 ft.
Sound Pressure Levels (dB[A]) (Cooling and Heating)
Model No. Medium Fan
High Fan Speed Low Fan Speed
Speed
LHN248HV 37 35 34
LHN368HV 44 42 40
102 | DUCT (HIGH STATIC) Due to our policy of continuous product innovation, some specifications may change without notification.
©LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp.
MULTI F DUCT (HIGH STATIC) INDOOR UNITS
MULTI F MAX Refrigerant Flow Diagrams
Table 56: Multi F Ceiling-Concealed Duct (High Static) IDU Refrigerant Piping and Connection Sizes.
Table 57: Multi F Ceiling-Concealed Duct (High Static) Indoor Unit Thermistor Details.
Description (Based on Cooling Mode) PCB Connector
Indoor Air Temperature Thermistor CN-ROOM
Evaporator Inlet Temperature Thermistor CN-PIPE/IN
Evaporator Outlet Temperature Thermistor CN-PIPE/OUT
Due to our policy of continuous product innovation, some specifications may change without notification. DUCT (HIGH STATIC) | 103
©LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp.
DUCT (HIGH STATIC) INDOOR UNITS MULTI F
Wiring Diagrams MULTI F MAX
Figure 133: Multi F Ceiling-Concealed Duct (High Static) LHN248HV and LHN368HV Indoor Units Wiring Diagram.
Multi F and Multi F MAX Indoor Unit Engineering Manual
104 | DUCT (HIGH STATIC) Due to our policy of continuous product innovation, some specifications may change without notification.
©LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp.
MULTI F DUCT (HIGH STATIC) INDOOR UNITS
MULTI F MAX Factory Supplied Parts and Materials / Installation
Insulation for
Metal Clamp Two (2) One (1) Set
Fittings
For Vapor Piping For Liquid Piping
Don’ts
• Do not install the unit near a heat or steam source, or where considerable amounts of oil, iron powder, or flour are used.
• Do not install the unit where sulfuric acid and flammable or corrosive gases are generated, vented into, or stored.
• Do not install the unit near high-frequency generators.
• Do not install the unit near a doorway.
The unit will be damaged, will malfunction, and / or will not operate as designed if installed in any of the conditions listed.
Due to our policy of continuous product innovation, some specifications may change without notification. DUCT (HIGH STATIC) | 105
©LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp.
DUCT (HIGH STATIC) INDOOR UNITS MULTI F
Installation and Best Layout Practices MULTI F MAX
• Indoor units (IDUs) must not be placed in an environment where the IDUs will be exposed to harmful volatile organic compounds (VOCs)
or in environments where there is improper air make up or supply or inadequate ventilation. If there are concerns about VOCs in the envi-
ronment where the IDUs are installed, proper air make up or supply and/or adequate ventilation must be provided. Additionally, in buildings
where IDUs will be exposed to VOCs, consider a third party factory-applied epoxy coating to the fan coils for each IDU where the entire coil
is dipped, not sprayed.
• If the unit is installed near a body of water, the installation parts are at risk of corroding. Appropriate anti-corrosion methods must be taken for
the unit and all installation parts.
Multi F and Multi F MAX Indoor Unit Engineering Manual
Figure 134: Access Panel and General Service Space Required Figure 135: Indoor Unit Bolt Locations.
Dimensions.
E
23-5/8 inches x 23-5/8 inches
G
D C
23-5/8 23-5/8
inches inches
inches
39-3/8
J
A
B
F
I
H = ≥25/32 inches H
Drainage hole
Table 59:Indoor Unit Bolt Location Dimensions.
Model / Capacity Dimensions (inches)
(Btu/h) A B C D E F G H I J
LHN248HV / 24,000 36-3/4 38-1/4 24-3/8 27-9/16 1-3/16 10-5/8 19/32 33-25/32 7-15/16 35-7/16
LHN368HV / 36,000 50-17/32 52-1/32 24-3/8 27-9/16 1-3/16 10-5/8 19/32 47-9/16 7-15/16 49-7/32
106 | DUCT (HIGH STATIC) Due to our policy of continuous product innovation, some specifications may change without notification.
©LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp.
MULTI F DUCT (HIGH STATIC) INDOOR UNITS
MULTI F MAX Installation and Best Layout Practices
Preparing the Installation Area and Hanging the Indoor Unit Frame
1. Select and mark the area for the suspension or console bolts (use 4. Add the plate washer, spring washer, and nut to secure the bolts
embedded inserts or anchor bolts in new buildings, and hole-in- into the installation area.
anchors in older buildings).
5. Position the indoor unit installation plates onto the bolts. Secure
2. Drill the holes. using nuts, plate washers, and spring washers. Adjust for level as
necessary.
3. Add the set-anchor and the plate washer to the bolts (bolts must
be at least 13/32 inches in diameter), and then insert the bolts
into the installation area.
Figure 136: Preparing the Installation Area. Figure 137: Suspension Bolt Options. Figure 138: Hanging the Indoor Unit.
M10 Nut X4
(Field-
M10 washer X4
(Field-
M10 SP. washer X4 supplied)
M10 Nut X4
Install a canvas duct to the air outlet and air inlet so that vibration from the indoor unit does not
carry to the duct or ceiling. Also, add insulation to the interior of the duct, and apply anti-vibration
to the suspension bolts.
• Unit must be installed correctly. Tighten the nuts and bolts to prevent the unit from falling and
causing severe injury or death.
Drain Port
Figure 140:Drain Piping Installation Dimensions. Maintenance
clamp
Maximum
Maximum
Flexible drain hose 27-9/16 inches
Insulation
Due to our policy of continuous product innovation, some specifications may change without notification. DUCT (HIGH STATIC) | 107
©LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp.
DUCT (HIGH STATIC) INDOOR UNITS MULTI F
Installation and Best Layout Practices MULTI F MAX
• After the test is complete, connect the flexible drain hose to the indoor unit drain port.
Drain Pan
Ensure all piping is insulated. Exposed piping can cause burns if touched.
Refrigerant Piping Insulation
Field-installed vapor and liquid refrigerant piping lines must be Figure 143: Insulating the Piping.
properly and completely covered in insulation (up to the indoor unit
piping connections). Any exposed piping will generate condensate or
will cause burns if touched. Insulation for this field-installed refriger- Liquid Piping
ant piping must have a minimum heat resistance of 248°F. Connection
Insulation for Refrigerant Piping
Drain Piping Insulation (Field-Supplied)
Drain piping must have insulation a minimum of 7/32 inches thick.
Clamp for Insulation
(Field-Supplied)
Insulation
(Field-Supplied)
Vapor Piping Connection
108 | DUCT (HIGH STATIC) Due to our policy of continuous product innovation, some specifications may change without notification.
©LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp.
MULTI F DUCT (HIGH STATIC) INDOOR UNITS
MULTI F MAX Installation and Best Layout Practices
• Loose wiring will cause unit to malfunction, overheat, and catch fire, resulting in severe injury or death.
3. Connect each wire to its appropriate terminal on the indoor unit control board.
Verify that the color and terminal numbers from the outdoor unit or branch Control Box Cover
distribution unit (Multi F MAX systems only) wiring match the color and terminal
numbers on the indoor unit. Lock nut
Figure 145:Indoor Unit to Outdoor Unit / Branch Distribution Unit (Multi F
Conduit
4. Secure the power wiring / communications cable with the cable MAX systems only) Power Wiring / Communications Cable Conduit
restraint. Connections. mounting
plate
Outdoor Unit Terminal Block or
5. Screw the steel clamp to the inside of the control panel. Branch Distribution Unit Terminal Block
Indoor Unit Terminal Block (Multi F MAX Systems Only)
• Place the wiring / cables in the clamp and tighten the plastic GND
clamp to an open surface of the control panel. 1(L1 ) 2 (L2) 3 3 or S3
1(L1) 2(L2)
tions. GND
BL
GRN /
YLW
electric box cover, and ensure the cover firmly closes. Power Wiring Connections
6. Fill in any gaps around the wiring access holes with sealant to
prevent foreign particles from entering the indoor unit.
Due to our policy of continuous product innovation, some specifications may change without notification. DUCT (HIGH STATIC) | 109
©LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp.
DUCT (HIGH STATIC) INDOOR UNITS MULTI F
Installation and Best Layout Practices MULTI F MAX
If the distance between the outdoor unit and indoor unit is greater than 131 feet, connect
the power wiring and communications cable separately (i.e., a conduit cannot be used). Remote controller cable and
transmission cable between
the indoor unit and the
outdoor unit
Indoor power cable
Power Supply
High Voltage
(208/230 V)
GN/YL
Wired Remote
Controller
Conduit Hole
Controller Options
Ceiling-concealed duct (high static) indoor units can be used with many LG-supplied wired controllers (sold separately). The wireless hand-
held controller (Model No. PQWRHQ0FDB) is also an optional accessory with use of the wired controller.
CN-REMO
OPER
Terminal
MODE
Extension cable
2. Field-supplied controller cable that connects to the indoor unit
terminal block (must be at least UL2547 or UL1007, 22 AWG,
two-core, one-shield core, at least FT-6 rated if local electric and Figure 148:Wired Controller Connections on the Indoor Unit Terminal
building codes require plenum cable usage). Block.
BL
RD
GRN /
YLW
110 | DUCT (HIGH STATIC) Due to our policy of continuous product innovation, some specifications may change without notification.
©LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp.
MULTI F DUCT (HIGH STATIC) INDOOR UNITS
MULTI F MAX Installation and Best Layout Practices
Wired Controller Placement Figure 149:Proper Location for the Wired Controller.
Wired controllers include a sensor to detect room temperature. To maintain comfort
levels in the conditioned space, the wired controller must be installed in a location
away from direct sunlight, high humidity, and where it could be directly exposed to
cold air. Controller must be installed four (4) to five (5) feet above the floor where its
LED display can be read easily, in an area with good air circulation, and where it can YES
detect an average room temperature.
TEMP
Remote Controlle r
NO
TEMP
Remote Controlle r
Hanging the Wired Controller Figure 150:Removing the Cable Guide Grooves.
Top
1. The controller wiring / cable can be installed in one of three direc- Top
tions: top, back, or on the right side. If top or right side installation
is desired, remove cable guide grooves on the controller, and
then position wiring / cable on applicable side. Back Right
Side
Right
Side
2. Choose and mark the area of installation, and then screw the wall
plate into place (using the provided parts). Install the controller
wall plate to fit the electrical box if one is present. Ensure that no
gaps exist between the wall plate and the wall itself.
Figure 151:Attaching the Wall Plate. Figure 152:Installing / Removing
3. Arrange wiring / cables so as not to interfere with the controller the Controller.
circuitry. Position the wired controller on the wall plate. Snap into
Installing the Controller
place by pressing the bottom part of the wired controller onto
the wall plate. Make sure that no gaps exist between the wired
controller and the wall plate on all sides. Wall Wall
Due to our policy of continuous product innovation, some specifications may change without notification. DUCT (HIGH STATIC) | 111
©LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp.
DUCT (HIGH STATIC) INDOOR UNITS MULTI F
Installation and Best Layout Practices MULTI F MAX
2. Use the temperature increase and decrease buttons to select the Figure 153:Select Code and
Multi F and Multi F MAX Indoor Unit Engineering Manual
Setting Values
01 : V-H Code
FAN
02 : F-H Set Value SPEED
03 : V-L TEM P
OPER
04 : F-L MODE
4. To deactivate system installer setting mode after the settings have been established, press and hold
the temperature increase and mode selection check buttons simultaneously for approximately three
(3) seconds. If a button is not pressed for more than 25 seconds, the system installer setting mode
will automatically deactivate.
• Select the position after verifying duct work and the external static pressure of the indoor unit.
• Factory set to pressure selection F-H.
112 | DUCT (HIGH STATIC) Due to our policy of continuous product innovation, some specifications may change without notification.
©LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp.
MULTI F DUCT (HIGH STATIC) INDOOR UNITS
MULTI F MAX Installation and Best Layout Practices
2. Use the fan speed button to select the desired fan speed. ( Lo→Med→Hi will display on the LED).
3. Use the temperature increase and decrease buttons to select the desired external static pressure set-
ting value (thereby assigning the respective airflow). External static pressure value range: 0~255; the
value will display near the lower right corner of the LED.
FAN
4. Press the on / off button to save the established settings.
5. To deactivate system installer setting mode after the settings have been established, press and hold OPER
MODE
the temperature increase and mode selection check buttons simultaneously for approximately three
(3) seconds. If a button is not pressed for more than 25 seconds, the system installer setting mode
will automatically deactivate.
• A certified technician must set the external static pressure value(s). If the external static pressure is set incorrectly, the system will
malfunction.
• Do not alter the external static pressure value that corresponds to each air flow level.
• External static pressure value can vary depending on the indoor unit.
• If by pressing the fan speed button during external static pressure setup, the fan speed is raised to the next level, the air flow value of
the previous fan speed will be maintained (external static pressure setting value is saved).
Due to our policy of continuous product innovation, some specifications may change without notification. DUCT (HIGH STATIC) | 113
©LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp.
FOUR-WAY
CEILING-CASSETTE
INDOOR UNIT DATA
“Mechanical Specifications” on page 115
“General Data / Specifications” on page 116
“Dimensions” on page 117
“Cooling Capacity Table” on page 119
“Heating Capacity Table” on page 121
“Acoustic Data” on page 123
“Air Velocity and Temperature Distribution” on page 125
“Refrigerant Flow Diagram” on page 127
“Wiring Diagram” on page 128
“Factory Supplied Parts and Materials” on page 129
“Installation and Best Layout Practices” on page 130
MULTI F FOUR-WAY CEILING CASSETTE INDOOR UNITS
MULTI F MAX Mechanical Specifications and Features
Four-Way Ceiling-Cassette
and all refrigerant lines from the outdoor unit to the indoor units must
uniform / random air distribution.
be field insulated.
Electrical Microprocessor Control
The indoor unit is provided with an integrated control panel to com-
Each indoor unit is designed to operate using 208–230/60/1 power
with voltage variances of ±10%. municate with the outdoor unit. All unit operation parameters are
stored in non-volatile memory residing on the unit microprocessor.
Casing The microprocessor controls space temperature through using the
The case is constructed of a galvanized steel plate designed to recess value provided by the temperature sensor within the indoor unit.
in the ceiling, and has a surface mounted concentric grille on the bot- The microprocessor control will activate indoor unit operation when
tom of the unit. Unit has four supply air outlets and one return air inlet. the indoor room temperature falls below or rises above a setpoint
temperature, at which point, a signal is sent to the outdoor unit to
Ventilation Air begin the appropriate mode. The microprocessor will also provide
The case has a factory designated knockouts to connect a field- self-diagnostics and auto restart functions. A field-supplied four-
supplied, pressurized, and filtered outside air duct. wire power / communications cable must be installed to connect the
indoor unit(s) to the outdoor unit.
Fan Assembly and Control
The indoor units are Wi-Fi compatible with the addition of an LG Wi-
All indoor units have a single, direct-drive turbo fan. Fans are manu-
Fi module accessory, and can be controlled by LG’s Smart ThinQ™
factured of high-strength ABS HT-700 polymeric resin that is statically
app on a smart device. A field-supplied Wi-Fi network and smart
and dynamically balanced. The fan motor is brushless digitally con-
device are required. The Smart ThinQ app is free, and is available
trolled (BLDC) with permanently lubricated and sealed ball bearings.
for Android™ and iOS. (Android is a trademark of Google LLC.)
The fan / motor assembly is mounted on vibration-attenuating rubber
grommets. Fan speed is controlled using a microprocessor-based di- Controls
rect digital control algorithm that provides pre-programmed, field-se- The indoor unit casing has a factory-standard, integral infrared
lectable fixed or auto fan speeds in the Heating and Cooling modes. sensor designed to communicate with the supplied LG wireless
The indoor fan has Low, Med, High, Power Cool and Auto settings handheld remote controller. An optional wired controller is available
for Cooling mode; and has Low, Med, High, and Auto settings for as an additional accessory. Communication between the indoor units
Heating mode. Auto setting adjusts the fan speed based on the dif- and the outdoor unit is accomplished through 14 AWG, four-core,
ference between the controller setpoint and space temperature. stranded and shielded power / communication cable.
Air Filter Condensate Lift/Pump
Return air is filtered with a factory-supplied, 14" x 14" x 1", remov- The indoor unit is provided with a factory installed and wired internal
able, washable filter accessible from the bottom of the unit. condensate lift/pump capable of providing a minimum 27.5 inch lift
from the bottom surface of the unit. Drain pump has a safety switch to
Features shut off the indoor unit if the condensate rises too high in the drain pan.
• Inverter (Variable speed fan) • Auto restart operation • Group Control
• Internal drain pump • 24-Hour on/off timer • Wireless LCD remote control included;
• Jet cool • Two thermistor control wired thermostat available (sold separately)
• Control lock function • Required accessory grille (PT-QCHW0) • Wi-Fi compatible
• Auto operation sold separately
Due to our policy of continuous product innovation, some specifications may change without notification. CEILING-CASSET TE | 115
©LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp.
FOUR-WAY CEILING-CASSETTE INDOOR UNITS MULTI F
General Data / Specifications MULTI F MAX
1
Nominal capacity is rated 0 ft. above sea level with a 0 ft. level difference between outdoor and indoor 3
Acceptable operating voltage: 187V-253V.
units. All capacities are net with a combination ratio between 95 – 105%. 4
Sound pressure levels are tested in an anechoic chamber under ISO Standard 3745 and are the
Nominal cooling capacity rating obtained with air entering the indoor unit at 80ºF dry bulb (DB) and 67ºF same in both cooling and heating mode. These values can increase due to ambient conditions during
wet bulb (WB) and outdoor ambient conditions of 95ºF dry bulb (DB) and 75ºF wet bulb (WB). operation.
Nominal heating capacity rating obtained with air entering the indoor unit at 70ºF dry bulb (DB) and 60ºF 5
All power wiring / communications cable to the IDUs be minimum 14 AWG, 4-conductor, stranded,
wet bulb (WB) and outdoor ambient conditions of 47ºF dry bulb (DB) and 43ºF wet bulb (WB). shielded or unshielded (if shielded, must be grounded to chassis at ODU only) and must comply with
2
This unit comes with a dry helium charge. applicable local and national codes.
116 | CEILING-CASSET TE Due to our policy of continuous product innovation, some specifications may change without notification.
©LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp.
MULTI F FOUR-WAY CEILING-CASSETTE INDOOR UNITS
MULTI F MAX Dimensions
4-17/32 2-51/64
(115) (71)
7-61/64
(202)
2-51/64 4-17/32
(71)
5-29/32
(150)
(115)
5-29/32
(150)
2-3/4
(70)
7/64
(3)
Four-Way Ceiling-Cassette
Max. Condensate Lift: 27-916
(700) or less
10-13/64 (259)
63/64
(25)
14-29/32 (379) (Air Outlet Hole)
22-7/16 (570)
7-13/64
(183)
5-19/32
(142)
63/64
(25)
1-31/32
1-3/16
14-29/32 (379)
(50)
(30)
6-1/16
(154)
24-13/32 (620)
PT-QCHW0
11
132
24-13/32 (620)
22-7/16 (570)
Due to our policy of continuous product innovation, some specifications may change without notification. CEILING-CASSET TE | 117
©LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp.
FOUR-WAY CEILING-CASSETTE INDOOR UNITS MULTI F
Dimensions MULTI F MAX
6-3/16 2-51/64
(157) (71)
Multi F and Multi F MAX Indoor Unit Engineering Manual
7-61/64
(202)
5-29/32
(150)
7-9/16
(192)
7/64
(3)
2-3/4
(70)
Max. Condensate Lift: 27-916
(700) or less 23-5/8 (600) (Ceiling Opening)
20-23/64 (517) (Hanging Bolt)
10-13/64 (259)
63/64
(25)
14-29/32 (379) (Air Outlet Hole)
22-7/16 (570)
7-13/64
(183)
5-19/32
1-31/32(142)
63/64
1-3/16
(25)
(50)
(30)
11
132
24-13/32 (620)
22-7/16 (570)
118 | CEILING-CASSET TE Due to our policy of continuous product innovation, some specifications may change without notification.
©LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp.
MULTI F FOUR-WAY CEILING CASSETTE INDOOR UNITS
MULTI F MAX Cooling Capacity Table
Four-Way Ceiling-Cassette
90 6.15 4.93 6.57 5.23 6.99 5.09 7.29 5.21 7.83 5.29 8.24 5.40
95 5.98 4.87 6.39 5.19 6.81 5.05 7.00 5.10 7.64 5.26 8.06 5.38
100 5.83 4.74 6.25 5.05 6.66 4.93 6.91 5.02 7.50 5.14 7.91 5.27
105 5.69 4.61 6.10 4.92 6.52 4.81 6.82 4.94 7.35 5.03 7.77 5.16
110 5.54 4.46 5.96 4.76 6.37 4.66 6.67 4.79 7.21 4.89 7.62 5.02
115 5.39 4.32 5.81 4.63 6.23 4.54 6.53 4.67 7.06 4.77 7.48 4.90
118 5.31 4.29 5.72 4.60 6.14 4.52 6.44 4.65 6.97 4.76 7.39 4.89
122 5.28 4.28 5.69 4.59 6.11 4.51 6.41 4.64 6.94 4.75 7.36 4.89
14 8.82 6.31 9.37 6.66 9.92 6.45 10.31 6.59 11.01 6.64 11.56 6.77
20 8.82 6.36 9.36 6.72 9.91 6.50 10.31 6.64 11.01 6.70 11.55 6.82
25 8.81 6.41 9.36 6.77 9.90 6.55 10.30 6.69 11.00 6.75 11.54 6.87
30 8.80 6.46 9.35 6.82 9.90 6.60 10.29 6.74 10.99 6.80 11.54 6.93
35 8.80 6.50 9.34 6.87 9.89 6.65 10.28 6.79 10.98 6.85 11.53 6.98
40 8.79 6.55 9.33 6.92 9.88 6.70 10.27 6.84 10.97 6.90 11.52 7.03
45 8.78 6.60 9.33 6.97 9.87 6.75 10.27 6.90 10.96 6.95 11.51 7.09
50 8.78 6.65 9.32 7.03 9.87 6.80 10.26 6.95 10.96 7.00 11.50 7.14
55 8.77 6.70 9.31 7.08 9.86 6.85 10.25 7.00 10.95 7.06 11.49 7.19
60 8.76 6.75 9.31 7.13 9.85 6.90 10.24 7.05 10.94 7.11 11.48 7.24
65 8.76 6.80 9.30 7.18 9.84 6.95 10.24 7.10 10.93 7.16 11.47 7.29
LCN098HV4 70 8.75 6.85 9.29 7.23 9.84 7.00 10.23 7.15 10.92 7.21 11.47 7.35
9,000 75 8.54 6.73 9.08 7.12 9.62 6.90 10.01 7.05 10.71 7.12 11.25 7.26
80 8.33 6.62 8.87 7.01 9.41 6.80 9.80 6.96 10.49 7.03 11.03 7.18
85 8.12 6.50 8.66 6.89 9.20 6.70 9.59 6.85 10.28 6.94 10.82 7.09
90 7.91 6.37 8.45 6.77 8.99 6.59 9.37 6.75 10.06 6.84 10.60 6.99
95 7.68 6.31 8.22 6.71 8.75 6.54 9.00 6.60 9.83 6.80 10.36 6.96
100 7.50 6.14 8.03 6.54 8.57 6.38 8.88 6.50 9.64 6.66 10.17 6.82
105 7.31 5.97 7.84 6.37 8.38 6.23 8.77 6.40 9.45 6.51 9.99 6.68
110 7.12 5.77 7.66 6.17 8.19 6.03 8.58 6.20 9.26 6.33 9.80 6.50
115 6.94 5.59 7.47 5.99 8.01 5.87 8.39 6.05 9.08 6.18 9.61 6.35
118 6.82 5.55 7.36 5.96 7.89 5.84 8.28 6.02 8.96 6.15 9.50 6.33
122 6.79 5.54 7.32 5.94 7.86 5.83 8.24 6.01 8.93 6.15 9.46 6.32
TC = Total Capacity (kBtu/h).
SHC: Sensible Heat Capacity (kBtu/h).
Nominal capacity as rated 0 ft. above sea level and a 0 ft. level difference between outdoor and indoor units. Corresponding refrigerant piping length is accordance with standard length of each outdoor unit.
Nominal cooling capacity rating obtained with air entering the indoor unit at 80ºF dry bulb (DB) and 67ºF wet bulb (WB), and outdoor ambient conditions of 95ºF dry bulb (DB) and 75ºF wet bulb (WB).
The shaded table columns and rows indicate reference data. When operating at this temperature, these values can be different if the system is not running consistently.
Due to our policy of continuous product innovation, some specifications may change without notification. CEILING-CASSET TE | 119
©LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp.
FOUR-WAY CEILING CASSETTE INDOOR UNITS MULTI F
Cooling Capacity Table MULTI F MAX
45 11.71 8.90 12.44 9.41 13.16 9.11 13.69 9.30 14.62 9.38 15.35 9.55
50 11.70 8.97 12.43 9.47 13.15 9.17 13.68 9.37 14.61 9.45 15.33 9.62
55 11.69 9.03 12.42 9.54 13.14 9.24 13.67 9.44 14.60 9.52 15.32 9.70
60 11.68 9.10 12.41 9.61 13.13 9.31 13.66 9.50 14.59 9.58 15.31 9.77
65 11.67 9.17 12.40 9.68 13.12 9.38 13.65 9.57 14.57 9.65 15.30 9.84
LCN128HV4 70 11.66 9.23 12.39 9.75 13.11 9.44 13.64 9.64 14.56 9.72 15.29 9.91
12,000 75 11.38 9.08 12.11 9.60 12.83 9.31 13.35 9.51 14.27 9.60 15.00 9.79
80 11.10 8.92 11.82 9.45 12.55 9.17 13.07 9.38 13.99 9.48 14.71 9.68
85 10.83 8.76 11.54 9.29 12.26 9.03 12.78 9.24 13.70 9.36 14.42 9.56
90 10.55 8.60 11.26 9.13 11.98 8.88 12.50 9.10 13.42 9.22 14.13 9.43
95 10.25 8.51 10.96 9.05 11.67 8.82 12.00 8.90 13.10 9.18 13.81 9.39
100 10.00 8.28 10.71 8.82 11.42 8.61 11.84 8.76 12.85 8.98 13.56 9.20
105 9.75 8.05 10.46 8.59 11.17 8.40 11.69 8.62 12.60 8.78 13.31 9.01
110 9.50 7.77 10.21 8.31 10.92 8.14 11.44 8.37 12.35 8.53 13.07 8.76
115 9.25 7.54 9.96 8.08 10.67 7.92 11.19 8.15 12.10 8.33 12.82 8.56
118 9.10 7.49 9.81 8.03 10.52 7.88 11.04 8.12 11.95 8.30 12.67 8.54
122 9.05 7.47 9.76 8.01 10.48 7.87 10.99 8.11 11.90 8.29 12.62 8.53
14 17.65 12.33 18.74 13.02 19.84 12.61 20.63 12.88 22.03 12.98 23.12 13.23
20 17.63 12.43 18.73 13.13 19.82 12.71 20.61 12.98 22.01 13.09 23.11 13.33
25 17.62 12.52 18.71 13.23 19.81 12.81 20.60 13.08 22.00 13.19 23.09 13.44
30 17.60 12.62 18.70 13.33 19.79 12.91 20.58 13.18 21.98 13.29 23.07 13.54
35 17.59 12.71 18.68 13.43 19.78 13.00 20.57 13.28 21.96 13.39 23.05 13.64
40 17.58 12.81 18.67 13.53 19.76 13.10 20.55 13.38 21.94 13.49 23.04 13.75
45 17.56 12.90 18.66 13.63 19.75 13.20 20.53 13.48 21.93 13.59 23.02 13.85
50 17.55 13.00 18.64 13.73 19.73 13.30 20.52 13.58 21.91 13.69 23.00 13.95
55 17.54 13.10 18.63 13.83 19.72 13.39 20.50 13.68 21.89 13.79 22.98 14.05
60 17.52 13.19 18.61 13.93 19.70 13.49 20.49 13.78 21.88 13.89 22.97 14.16
65 17.51 13.29 18.60 14.03 19.69 13.59 20.47 13.87 21.86 13.99 22.95 14.26
LCN188HV4 70 17.50 13.38 18.58 14.13 19.67 13.69 20.46 13.97 21.84 14.09 22.93 14.36
18,000 75 17.08 13.16 18.16 13.92 19.24 13.49 20.03 13.79 21.41 13.92 22.50 14.20
80 16.66 12.93 17.74 13.70 18.82 13.30 19.60 13.60 20.98 13.75 22.06 14.03
85 16.24 12.70 17.32 13.47 18.40 13.09 19.17 13.40 20.55 13.56 21.63 13.85
90 15.82 12.46 16.90 13.23 17.97 12.88 18.75 13.19 20.12 13.37 21.20 13.67
95 15.37 12.33 16.44 13.12 17.51 12.78 18.00 12.90 19.65 13.30 20.72 13.61
100 14.99 12.00 16.06 12.78 17.13 12.47 17.77 12.70 19.28 13.01 20.35 13.33
105 14.62 11.67 15.69 12.45 16.76 12.17 17.53 12.50 18.90 12.73 19.97 13.05
110 14.24 11.27 15.32 12.05 16.39 11.79 17.16 12.13 18.53 12.36 19.60 12.70
115 13.87 10.93 14.94 11.71 16.01 11.48 16.79 11.82 18.15 12.07 19.22 12.41
118 13.65 10.85 14.72 11.64 15.79 11.42 16.56 11.77 17.93 12.03 19.00 12.37
122 13.57 10.83 14.64 11.62 15.71 11.40 16.49 11.75 17.85 12.01 18.92 12.36
TC = Total Capacity (kBtu/h).
SHC: Sensible Heat Capacity (kBtu/h).
Nominal capacity as rated 0 ft. above sea level and a 0 ft. level difference between outdoor and indoor units. Corresponding refrigerant piping length is accordance with standard length of each outdoor unit.
Nominal cooling capacity rating obtained with air entering the indoor unit at 80ºF dry bulb (DB) and 67ºF wet bulb (WB), and outdoor ambient conditions of 95ºF dry bulb (DB) and 75ºF wet bulb (WB).
The shaded table columns and rows indicate reference data. When operating at this temperature, these values can be different if the system is not running consistently.
120 | CEILING-CASSET TE Due to our policy of continuous product innovation, some specifications may change without notification.
©LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp.
MULTI F FOUR-WAY CEILING-CASSETTE INDOOR UNITS
MULTI F MAX Heating Capacity Table
Four-Way Ceiling-Cassette
47 43 8.22 8.16 8.12 8.10 8.04 7.87
50 46 8.35 8.29 8.25 8.23 8.17 7.98
55 51 8.57 8.51 8.47 8.45 8.39 8.16
60 56 8.57 8.51 8.47 8.45 8.39 8.20
63 59 8.57 8.51 8.47 8.45 8.39 8.22
68 64 8.57 8.51 8.47 8.45 8.39 8.25
0 -0.4 5.35 5.28 5.23 5.20 5.12 4.90
5 4.5 6.03 5.95 5.90 5.88 5.80 5.58
10 9 6.71 6.63 6.58 6.56 6.48 6.26
17 15 7.61 7.54 7.49 7.46 7.39 7.14
20 19 7.95 7.88 7.83 7.80 7.72 7.46
25 23 8.52 8.44 8.39 8.37 8.29 7.99
30 28 9.01 8.93 8.88 8.86 8.78 8.52
Due to our policy of continuous product innovation, some specifications may change without notification. CEILING-CASSET TE | 121
©LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp.
FOUR-WAY CEILING-CASSETTE INDOOR UNITS MULTI F
Heating Capacity Table MULTI F MAX
122 | CEILING-CASSET TE Due to our policy of continuous product innovation, some specifications may change without notification.
©LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp.
MULTI F FOUR-WAY CEILING-CASSETTE INDOOR UNITS
MULTI F MAX Acoustic Data
Figure 159:Sound Pressure Level Measurement Location. • Measurement taken 4.9′ away from the unit.
• Measurements taken with no attenuation and units operating at full
load normal operating condition.
• Sound level will vary depending on a range of factors such as
construction (acoustic absorption coefficient) of particular area in
which the equipment is installed.
• Sound power levels are measured in dB(A).
• Tested in anechoic chamber per ISO Standard 3745.
Ceiling Table 72:Sound Pressure Levels (dB[A]).
Sound Pressure Levels (dB[A]) (Cooling and Heating)
Model No.
4.9 ft. High Fan Speed Medium Fan
Speed Low Fan Speed
LMCN078HV 31 27 24
Microphone LCN098HV4 36 33 30
Four-Way Ceiling-Cassette
LCN128HV4 38 35 32
LCN188HV4 41 39 36
LMCN078HV LCN098HV4
80
90
70 80
Sound Pressure Level (dB re 20uPa)
Octave Band Sound Pressure Level (dB re 20Pa)
NC-65 70
60 NC-70
NC-60
NC-65
60
NC-55
50 NC-60
NC-50 NC-55
50
NC-50
NC-45
40
NC-45
NC-40 40
NC-40
NC-35
30 NC-35
30
NC-30 NC-30
NC-25
NC-25
20 20
NC-20
Approximate
NC-20
Hearing
Threshold NC-15
10
NC-15
10
63 125 250 500 1000 2000 4000 8000
63 125 250 500 1000 2000 4000 8000
Octave Band Center Frequency (Hz) Octave Band Center Frequency (Hz)
Due to our policy of continuous product innovation, some specifications may change without notification. CEILING-CASSET TE | 123
©LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp.
FOUR-WAY CEILING CASSETTE INDOOR UNITS MULTI F
Acoustic Data MULTI F MAX
LCN128HV4 LCN188HV4
80
70
Sound pressure level (0 dB = 20 µPa)
NC-65
Multi F and Multi F MAX Indoor Unit Engineering Manual
60
NC-60
NC-55
50
NC-50
NC-45
40
NC-40
NC-35
30
NC-30
20 NC-25
Approximate
NC-20
Hearing
Threshold NC-15
10
63 125 250 500 1000 2000 4000 8000
124 | CEILING-CASSET TE Due to our policy of continuous product innovation, some specifications may change without notification.
©LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp.
MULTI F FOUR-WAY CEILING-CASSETTE INDOOR UNITS
MULTI F MAX Air Velocity and Temperature Distribution
9f t 9f t
6.6 6.6 6.6 6.6
0f t 0f t
8f t 5f t 0f t 5 ft 8 ft 8f t 5f t 0f t 5 ft 8 ft
Four-Way Ceiling-Cassette
Temperature [°F] Temperature [°F]
9f t 9f t
91 91
7f t 70 70 7f t
54 54
68 68 81 81
64 64
3f t 75 75 3f t
72 72
75 75
0f t 0f t
8f t 5f t 0f t 5 ft 8 ft 8f t 5f t 0f t 5 ft 8 ft
9ft 9ft
6.6 6.6
6.6 6.6
4.9 4.9
7ft 7ft
4.9 4.9
3.3 3.3
3.3 3.3
3ft 1.6 1.6 3ft
1.6 1.6
0ft 0ft
8ft 5ft 0ft 5ft 8ft 8ft 5ft 0ft 5ft 8ft
9ft 9ft
64 64 91 91
7ft 86 86 7ft
68 68
81 81
75 75
72 72 70 70
3ft 3ft
75 75
0ft 0ft
8ft 5ft 0ft 5ft 8ft 8ft 5ft 0ft 5ft 8ft
Due to our policy of continuous product innovation, some specifications may change without notification. CEILING-CASSET TE | 125
©LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp.
FOUR-WAY CEILING CASSETTE INDOOR UNITS MULTI F
Air Velocity and Temperature Distribution MULTI F MAX
9ft 9ft
6.6 6.6
6.6 6.6
7ft 7ft
4.6 4.6 4.6
Multi F and Multi F MAX Indoor Unit Engineering Manual
4.6
9ft 9ft
64 64 91 91
68 68 7ft 7ft
72 72 75
75
3ft 3ft
81 81
75 75
0ft 0ft
8ft 5ft 0ft 5ft 8ft 8ft 5ft 0ft 5ft 8ft
0ft 0ft
13ft 10ft 7ft 3ft 0ft 3ft 7ft 10ft 13ft 13ft 10ft 7ft 3ft 0ft 3ft 7ft 10ft 13ft
75 75
0ft 0ft
13ft 10ft 7ft 3ft 0ft 3ft 7ft 10ft 13ft 13ft 10ft 7ft 3ft 0ft 3ft 7ft 10ft 13ft
126 | CEILING-CASSET TE Due to our policy of continuous product innovation, some specifications may change without notification.
©LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp.
MULTI F FOUR-WAY CEILING-CASSETTE INDOOR UNITS
MULTI F MAX Refrigerant Flow Diagram
Indoor Air
Four-Way Ceiling-Cassette
Temperature Thermistor
Evaporator Inlet
Temperature Thermistor
Liquid pipe connection port
(flare connection)
Table 73:Multi F Four-Way Ceiling-Cassette Indoor Unit Refrigerant Pipe Table 74:Multi F Four-Way Ceiling-Cassette Indoor Unit Refrigerant Pipe
Sizes. Connections.
Model No. Vapor (inch) Liquid (inch) Model No. Vapor (inch) Liquid (inch)
LMCN078HV LMCN078HV
LCN098HV4 Ø3/8 LCN098HV4 Ø3/8
Ø1/4 Ø1/4
LCN128HV4 LCN128HV4
LCN188HV4 Ø1/2 LCN188HV4 Ø1/2
Due to our policy of continuous product innovation, some specifications may change without notification. CEILING-CASSET TE | 127
©LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp.
FOUR-WAY CEILING CASSETTE INDOOR UNITS MULTI F
Wiring Diagram MULTI F MAX
128 | CEILING-CASSET TE Due to our policy of continuous product innovation, some specifications may change without notification.
©LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp.
MULTI F FOUR-WAY CEILING-CASSETTE INDOOR UNITS
MULTI F MAX Factory Supplied Parts and Materials
Metal Conduit
Two (2) One (1)
Clamp Bracket
Four-Way Ceiling-Cassette
Insulation One (1)
M4 Screws Two (2)
for Fittings Set
For Vapor Piping For Liquid Piping
Wireless Handheld
Washer for
Controller with
Hanging Eight (8) One (1)
Holder
Bracket
(AKB73757604) 1
1
Wireless Handheld Controller for the four-way ceiling cassette indoor units is also referenced by Model No. PQWRHQ0FDB.
Grille Kit
One (1)
(PT-QCHW0)
Read all instructions before installing this product. Become familiar with the unit’s components and connections, and the order of installation. Incorrect
installation can degrade or prevent proper operation.
Due to our policy of continuous product innovation, some specifications may change without notification. CEILING-CASSET TE | 129
©LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp.
FOUR-WAY CEILING CASSETTE INDOOR UNITS MULTI F
Installation and Best Layout Practices MULTI F MAX
inches
≥13/32
• Ensure there is sufficient maintenance space. Ceiling
≥11-13/16 inches
Ceiling Tile
• Locate the indoor unit in a location that is level, and where it can Ceiling Tile
be easily connected to the outdoor unit / branch distribution unit.
Multi F and Multi F MAX Indoor Unit Engineering Manual
≤11-13/16 inches
Don’ts
≥39-3/8 inches
• Do not install the unit near a heat or steam source, or where ≥19-11/16 ≥19-11/16
H = 6 feet to 12 feet
inches inches
considerable amounts of oil, iron powder, or flour are used.
• Do not install the unit where sulfuric acid and flammable or cor-
rosive gases are generated, vented into, or stored.
• Do not install the unit near high-frequency generators.
• Do not install the unit near a doorway.
The unit will be damaged, will malfunction, and/or will not Floor
operate as designed if installed in any of the conditions listed.
• Indoor units (IDUs) must not be placed in an environment where the IDUs will be exposed to harmful volatile organic compounds (VOCs)
or in environments where there is improper air make up or supply or inadequate ventilation. If there are concerns about VOCs in the envi-
ronment where the IDUs are installed, proper air make up or supply and/or adequate ventilation must be provided. Additionally, in buildings
where IDUs will be exposed to VOCs, consider a third party factory-applied epoxy coating to the fan coils for each IDU where the entire coil
is dipped, not sprayed.
• If the unit is installed near a body of water, the installation parts are at risk of corroding. Appropriate anti-corrosion methods must be taken
for the unit and all installation parts.
Installing in a High or Dropped Ceiling Table 78:Indoor Unit High Ceiling Mode Selection Options.
High or dropped ceilings, often found in commercial buildings and Ceiling Height Mode Selection
offices, will cause a wide temperature differentiation. To counter-
measure: ≤7-1/2 feet Low Ceiling
• Change the indoor unit mode selection to allow for higher ceilings 7-1/2 feet to 8-7/8 feet Standard
(see table). 8-7/8 feet to 10-3/16 feet High Ceiling
• Install an air circulator. 10-3/16 feet to 11-13/16 feet Very High Ceiling
• Set the air discharge outlet so that heated air flows in a downward
direction.
• Use a dual door system to protect the building gate or exit.
Installing in an Area Exposed to Unconditioned Air
In some installation applications, areas (floors, walls) in some rooms will be exposed to unconditioned air (room will be above or next to an
unheated garage or storeroom). To countermeasure:
• Verify that carpet is or will be installed (carpet will increase the temperature by three (3) degrees).
• Add insulation between the floor joists.
• Install radiant heat or another type of heating system to the floor. Figure 169:Installing in a Highly Humid Location.
130 | CEILING-CASSET TE Due to our policy of continuous product innovation, some specifications may change without notification.
©LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp.
MULTI F FOUR-WAY CEILING-CASSETTE INDOOR UNITS
MULTI F MAX Installation and Best Layout Practices
Installing Multiple Indoor Units in One Area Figure 170:Installing Multiple Indoor Units.
Ensure there is enough space between indoor units, lighting fixtures, Indoor unit Indoor unit
and ventilation fans / systems. Ventilator
Lighting
>59-1/16 inches
>78-25/32 inches
>118-5/32 inches
Preparing the Installation Area and Hanging the Indoor Unit Frame
Preparing the Installation Area Figure 171:Ceiling Opening Dimensions and Bolt Locations.
1. Installation guide (template) depicts the exact dimensions 23-1/16 inches ~ 26 inches (Ceiling Opening)
necessary for the ceiling opening.
Four-Way Ceiling-Cassette
20-3/8 inches
2. Choose the location for the indoor unit, and then mark where the
bolts, refrigerant piping, and drain hose must be. Suspension bolt
angle must account for drain direction.
20-3/8 inches
20-19/32 inches
Unit Size
22-15/32 inches
Unit Size
Figure 172:Installing the Hanging Bolt in the Ceiling. Figure 173:Installation Diagram.
Ceiling
Ceiling
7-3/32 inches
Due to our policy of continuous product innovation, some specifications may change without notification. CEILING-CASSET TE | 131
©LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp.
FOUR-WAY CEILING CASSETTE INDOOR UNITS MULTI F
Installation and Best Layout Practices MULTI F MAX
4. Align the installation guide (template) with the label attached to the unit (affixing the Flat washer for M10
template to the unit if desired) to properly place the unit. (field supplied)
Nut
5. Remove the temporary washer plate and position the indoor unit hanger brackets
(W3/8 or M10)
on the bolts. Secure with nuts and washers on the top and bottom of the hanger
brackets.
6. Ceiling-cassette indoor units are equipped with a built-in drain pump and float switch, therefore, the unit must be installed horizontally or
condensate will drip out and cause product malfunction. Measure the unit at each corner to verify that it is level.
7. Remove the installation guide (template).
• After the test is complete, connect the flexible drain hose to the indoor unit drain port.
Drain Pan
132 | CEILING-CASSET TE Due to our policy of continuous product innovation, some specifications may change without notification.
©LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp.
Liquid Piping
Connection
MULTI F FOUR-WAY CEILING-CASSETTE INDOOR
Insulation for Refrigerant Piping
(Field-Supplied)UNITS
MULTI F MAX Installation and Best Layout Practices Clamp for Insulation
(Field-Supplied)
Insulation
(Field-Supplied)
Insulating the Refrigerant and Drain Piping Vapor Piping Connection
Figure 177:Insulating the Piping.
Insulation for Refrigerant Piping
Ensure all piping is insulated. Exposed piping can cause burns if touched.
(Field-Supplied) Insulation for Field-Installed Piping
Refrigerant Piping Insulation (Field-Supplied)
Field-installed vapor and liquid refrigerant piping lines must be
properly and completely covered in insulation (up to the indoor unit
piping connections). Any exposed piping will generate condensate or
will cause burns if touched. Insulation for this field-installed refriger-
ant piping must have a minimum heat resistance of 248°F. Overlap the Insulation at the
Connection
Drain Piping Insulation
Drain piping must have insulation a minimum of 7/32 inches thick. Ensure no gaps are present.
Four-Way Ceiling-Cassette
1. Overlap the insulation at the connection of the field-installed piping and the indoor unit piping. Tape together so that no gaps exist.
2. Secure insulation to the rear piping housing section with vinyl tape.
3. Bundle the piping and drain hose with tape where they meet at the back of the indoor unit frame. Position the drain hose at the bottom of
the bundle (positioning the drain hose at the top of the bundle will cause the drain pan to overflow inside the indoor unit).
Loose wiring will cause unit to malfunction, overheat, and catch fire, resulting in severe injury or death.
• Terminal screws will become loose during transport. Properly tighten the terminal connections during installation.
A voltage drop will cause the following problems:
• Magnetic switch vibration, fuse breaks, or disturbance to the normal function of an overload protection device.
• Compressor will not receive the proper starting current.
Due to our policy of continuous product innovation, some specifications may change without notification. CEILING-CASSET TE | 133
©LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp.
FOUR-WAY CEILING CASSETTE INDOOR UNITS MULTI F
Installation and Best Layout Practices MULTI F MAX
Connecting the Power Wiring and Figure 178:Power Wiring and Communications
Cable Connection Access.
Communications Cable
1. To access the terminal block, open the control box cover.
2. Insert the power wiring / communications cable from the outdoor unit or branch
distribution unit (Multi F MAX systems only) through the sides of the indoor unit and Power Wiring
control box. Pass the wiring through the designated access holes to prevent dam-
age. To prevent electromagnetic interference and product malfunction, leave a space
Multi F and Multi F MAX Indoor Unit Engineering Manual
between the power wiring and communications cable outside of the indoor unit. Wired
Controller
Cable
3. Connect each wire to its appropriate terminal on the indoor unit control board. Verify
that the color and terminal numbers from the outdoor unit or branch distribution unit Control Box Cover Control Box
(Multi F MAX systems only) wiring match the color and terminal numbers on the Cover Screws
indoor unit.
4. Neatly arrange power wiring / communications cable and secure with the appropriate
cable restraint. When clamping, do not apply force to the wiring connec-
tions.
5. Firmly reattach the control box cover. Do not catch the wiring in the electric box
cover and make sure the cover firmly closes.
6. Fill in any gaps around the wiring access holes with sealant to prevent foreign Wiring / Cable Connections
particles from entering the indoor unit.
BR
GND
BL
RD
3. Connect the power wiring / communications cable to the indoor unit terminal block. Conduit Bracket Cable
If the distance between the outdoor unit and indoor unit is greater than 131 feet, connect the power Ceiling cassette 4-way _ 19
134 | CEILING-CASSET TE Due to our policy of continuous product innovation, some specifications may change without notification.
©LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp.
MULTI F FOUR-WAY CEILING-CASSETTE INDOOR UNITS
MULTI F MAX Installation and Best Layout Practices
Controller Options
Four-way ceiling-concealed indoor units include a wireless handheld controller (AKB73757604)1, but optional LG-supplied wired controllers
are available.
Wireless Handheld Controller
Figure 181:AKB73757604 Wireless Handheld Controller. Table 79:AKB737576041 Wireless Handheld Controller Functions.2
Button Description
Label
1 Vane Angle Button: Sets the angle to each vane.
Function Setting Button: Sets or clears auto clean, smart clean,
2
electric heater, or individual vane angle control functions.
3 On / Off Button: Turns the power on/off.
Jet Cool: Sets the unit to super high fan speed when in cooling
4
mode.
1
Left / Right Air Flow Button (optional): Sets the desired left / right
5
2 10 (horizontal) air flow direction.
11 Up / Down Air flow Button: Stops or starts louver movement, and
6
Four-Way Ceiling-Cassette
3 12 sets the desired air flow direction to up or down.
7 On Time Button: Sets the time when the operation begins.
13
Operation Mode Sequence 8 Sleep Timer Button: Sets the sleep mode operation.
4
Cooling Mode Set / Clear Button: Sets or cancels the timer, also sets the current
5 9
↓ time.
6 14 10 Plasma Button: Starts or stops plasma-purification functions.
Auto Mode/Changeover
7 Room Temperature Setting Button: Raises or lowers temperature
15 ↓ 11
8 setpoint in cooling and heating operation.
16 Dehumidification Mode 12 Operation mode selection button: Selects the operation mode.
↓ Indoor Fan Speed Button: Changes the fan speed to one of four
9 17 13
Heating Mode choices: low, medium, high, and chaos.
↓ Room Temperature Check Button: Displays / checks the room
14
Fan Mode temperature.
15 Off Timer button: Sets the time when the operation ends.
Time Setting (Up / Down) / Light Button: Sets the timer and
16
adjusts the brightness of the LED.
17 Reset Button: Resets the remote controller.
1
Wireless Handheld Controller for the four-way ceiling cassette indoor units is also referenced by Model
No. PQWRHQ0FDB.
2
Depending on the indoor unit model, some functions will not be supported or displayed.
Terminal
MODE
Extension cable
2. Field-supplied controller cable that connects to the indoor unit Outdoor Unit Termin
terminal block (must be at least UL2547 or UL1007, 22 AWG, Figure 183:Wired Controller Connections on theBlock
Indoor Unit Terminal Indoor Unit Terminal
BranchBlock.
Distribution Unit
two-core, one-shield core, at least FT-6 rated if local electric CN-REMO (Multi F MAX Syste
and building codes require plenum cable usage). GND 3 or
1(L) 2(N) 3
To Wired Controller
BR
BL
RD
Due to our policy of continuous product innovation, some specifications may change without notification. CEILING-CASSET TE | 135
©LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp.
FOUR-WAY CEILING CASSETTE INDOOR UNITS MULTI F
Installation and Best Layout Practices MULTI F MAX
Wired Controller Placement Figure 184:Proper Location for the Wired Controller.
Wall indoor units can be used with various wired controllers (optional; sold separately).
Wired controllers include a sensor to detect room temperature. To maintain comfort
levels in the conditioned space, the wired controller must be installed in a location
away from direct sunlight, high humidity, and where it could be directly exposed to cold
air. Controller must be installed four (4) to five (5) feet above the floor where its display TEMP
YES
can be read easily, in an area with good air circulation, and where it can detect an
Remote Controlle r
Remote Controlle r
Multi F and Multi F MAX Indoor Unit Engineering Manual
Do not install the remote controller where it can be impacted by the following: NO
4 to 5 feet
• Drafts or dead spots behind doors and in corners Rem
ot e
Cont
roller
TEMP
Hanging the Wired Controller Figure 185:Removing the Cable Guide Grooves.
Top
1. The controller wiring / cable can be installed in one of three direc- Top
tions: top, back, or on the right side. If top or right side installation
is desired, remove cable guide grooves on the controller, and
then position wiring / cable on applicable side. Back Right
Side
Right
Side
2. Choose and mark the area of installation, and then screw the wall
plate into place (using the provided parts). Install the controller
wall plate to fit the electrical box if one is present. Ensure that no
gaps exist between the wall plate and the wall itself.
Figure 186:Attaching the Wall Figure 187:Installing / Removing
3. Arrange wiring / cables so as not to interfere with the controller Plate. the Controller.
circuitry. Position the wired controller on the wall plate. Snap into
Installing the Controller
place by pressing the bottom part of the wired controller onto
the wall plate. Make sure that no gaps exist between the wired
controller and the wall plate on all sides. Wall Wall
136 | CEILING-CASSET TE Due to our policy of continuous product innovation, some specifications may change without notification.
©LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp.
MULTI F FOUR-WAY CEILING-CASSETTE INDOOR UNITS
MULTI F MAX Installation and Best Layout Practices
Decoration panel must be installed properly; cool air will leak from any gaps found between the indoor unit frame and the decoration panel,
which will cause condensation to generate.
1. Remove the packaging, take out air inlet grille from the front Figure 188:Installing the Decoration Panel.
panel (1A), and then remove the corner covers of the panel (1B).
1A 1B
2. Attach the panel to the indoor frame by inserting the hooks as
shown (2). Grille
Corner
3. Attach two screws on diagonal corners of each panel, but Cover
do not tighten completely (3). Screws to attach the panel to
the indoor unit frame are factory-provided and can be found in
the shipping box.
Four-Way Ceiling-Cassette
2 3
4. Verify the panel is aligned with the ceiling. Adjust the height by
Hook clip
using the hanging bolts as shown (4).
Hook
5. Attach the corner covers (5).
8. Close the control box cover. Attach the link on the front panel as
shown (8). The link is supplied in the front panel shipping package.
9. Attach the other side of the link on the filter guide of the air inlet
grille, then install the filter and the air inlet grille on the front panel
(9). 6 7
Indoor Unit
CN VANE 1,2 CN DISP
8 9
Ceiling Link
Tile
Link
Decoration panel Filter
Insulation should fit tightly so that guide
cool air does not leak
Due to our policy of continuous product innovation, some specifications may change without notification. CEILING-CASSET TE | 137
©LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp.
TWO-WAY
VERTICAL-HORIZONTAL
AIR HANDLING
INDOOR UNIT DATA
“Mechanical Specifications” on page 139
“General Data / Specifications” on page 140
“Dimensions” on page 141
“Cooling Capacity Table” on page 142
“Heating Capacity Table” on page 143
“External Static Pressure” on page 144
“Acoustic Data” on page 145
“Refrigerant Flow Diagram” on page 146
“Wiring Diagram” on page 147
“Factory Supplied Parts and Materials” on page 149
“Installation and Best Layout Practices” on page 150
MULTI F TWO-WAY VAHU INDOOR UNITS
MULTI F MAX Mechanical Specifications and Features
Two-way Vertical-Horizontal Air steel housing and a forward Figure 190: Multi F Vertical-Horizontal
curve fan wheel. The fan Air Handling Indoor Unit.
Handing Indoor Unit motor is a brushless digitally
General controlled (BLDC) motor with
All LG indoor units are factory assembled, wired, piped, and pro- permanently lubricated and
vided with a control circuit board, fan, and motor. Vertical-Horizontal sealed ball bearings. The fan
Air Handling units are designed for high-speed air volume against an / motor assembly is mounted
external static pressure up to 1.00″WG. Supply air opening is flanged on vibration-attenuating rub-
to accept field-installed ductwork that cannot exceed the external ber grommets. Fan speed is
static pressure limit of the unit. controlled using a micropro-
cessor-based direct digital
Coil control algorithm. The indoor
fan has Low, Med, High, and
Indoor unit coils are factory built and are comprised of aluminum fins
Auto settings for Cooling
mechanically bonded to copper tubing. Each unit has a minimum of
mode; and has Low, Med,
two rows of coils, which are pressure tested at the factory. Each unit is
High, and Auto settings for
Features
• Inverter (Variable speed fan) • Dehumidifying function • External static pressure control
• Control lock function • Two thermistor control • Self-diagnostics function
• Auto operation • Group control • Wired controller ordered separately
Due to our policy of continuous product innovation, some specifications may change without notification. VERTICAL-HORIZONTAL | 139
©LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp.
TWO-WAY VAHU INDOOR UNITS MULTI F
General Data / Specifications MULTI F MAX
Table 80: Multi F Vertical-Horizontal Air Handling Indoor Unit General Data.
Model Name LMVN240HV LMVN360HV
Nominal Cooling Capacity (Btu/h) 1
24,000 36,000
Nominal Heating Capacity (Btu/h) 1
27,000 40,000
Operating Range
Cooling (°F WB) 57-77 57-77
Heating (°F DB) 59-81 59-81
Multi F and Multi F MAX Indoor Unit Engineering Manual
Fan
Type Sirocco Sirocco
Motor Output (W) x Qty. 96 x 1 182 x 1
Motor/Drive Brushless Digitally Controlled / Direct Brushless Digitally Controlled / Direct
Airflow Rate CFM (H/M/L) at 0.5"WG ESP 710 / 640 / 480 990 / 880 / 800
Maximum External Static Pressure (in. WG) 1.00 1.00
Unit Data
Refrigerant Type2 R410A R410A
Refrigerant Control EEV EEV
Power Supply V, Ø, Hz 3
208-230, 1, 60 208-230, 1, 60
Rated Amps (A) 0.59 1.12
Sound Pressure Level dB(A) (H/M/L)4 at 0.3"WG ESP 43 / 42 / 41 45 / 44 / 43
Dimensions (W x H x D, in.) 18 x 48-21/32 x 21-1/4 18 x 48-21/32 x 21-1/4
Net Weight (lbs.) 117 121
Shipping Weight (lbs.) 130 135
Power Wiring / Communications Cable (No. x AWG) 5
4 x 14 4 x 14
Heat Exchanger (2 x 24 x 18) x 2 (3 x 24 x 18) x 2
(Row x Column x Fin / inch) x Number
Piping
Liquid (in.) 1/4 3/8
Vapor (in.) 1/2 5/8
Primary Drain I.D. (in.) 3/4 FPT 3/4 FPT
Secondary Drain I.D. (in.) 3/4 FPT 3/4 FPT
1
Nominal capacity is rated 0 ft. above sea level with corresponding refrigerant piping length in 3
Acceptable operating voltage: 187V-253V.
accordance with standard length of each outdoor unit and a 0 ft. level difference between outdoor and 4
Sound pressure levels are tested in an anechoic chamber under ISO Standard 3745 and are the
indoor units. All capacities are net with a combination ratio between 95 – 105%. same in both cooling and heating mode. These values can increase due to ambient conditions during
Nominal cooling capacity rating obtained with air entering the indoor unit at 80ºF dry bulb (DB) and 67ºF operation.
wet bulb (WB) and outdoor ambient conditions of 95ºF dry bulb (DB) and 75ºF wet bulb (WB). 5
All power wiring / communications cable to the IDUs must be minimum 14 AWG, 4-conductor, stranded,
Nominal heating capacity rating obtained with air entering the indoor unit at 70ºF dry bulb (DB) and 60ºF shielded or unshielded (if shielded, must be grounded to chassis at ODU only) and must comply with
wet bulb (WB) and outdoor ambient conditions of 47ºF dry bulb (DB) and 43ºF wet bulb (WB). applicable local and national codes.
2
This unit comes with a dry helium charge.
140 | VERTICAL-HORIZONTAL Due to our policy of continuous product innovation, some specifications may change without notification.
©LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp.
MULTI F TWO-WAY VAHU INDOOR UNITS
MULTI F MAX Dimensions
17
12-1/8
D
21-1/4
W
1-9/16
1-15/16
H
1-15/16
2-1/8 2-1/16
2-9/16
1-1/2
14-5/16
4-11/16
1-9/16
9-15/16
13
LMVN360HV
LMVN240HV
Model
18
W
48-21/32 21-1/4
H
Unit: Inch
D
Due to our policy of continuous product innovation, some specifications may change without notification. VERTICAL-HORIZONTAL | 141
©LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp.
TWO-WAY VAHU INDOOR UNITS MULTI F
Cooling Capacity Table MULTI F MAX
Table 81: Multi F Vertical-Horizontal Air Handling Indoor Units Cooling Capacity Table.
Model No. / Indoor Air Temp. °F DB / °F WB
Nominal Capacity Outdoor Air
Temp. 68 / 57 73 / 61 77 / 64 80 / 67 86 / 72 90 / 75
of Indoor Unit (°F DB) TC SHC TC SHC TC SHC TC SHC TC SHC TC SHC
(Btu/h)
14 23.53 17.89 24.99 18.90 26.45 18.30 27.50 18.69 29.37 18.84 30.83 19.20
20 23.51 18.03 24.97 19.05 26.43 18.44 27.48 18.83 29.35 18.99 30.81 19.35
25 23.49 18.17 24.95 19.20 26.41 18.59 27.46 18.98 29.33 19.14 30.79 19.50
30 23.47 18.31 24.93 19.34 26.39 18.73 27.44 19.12 29.30 19.28 30.76 19.65
35 23.46 18.45 24.91 19.49 26.37 18.87 27.42 19.27 29.28 19.43 30.74 19.80
40 23.44 18.59 24.89 19.64 26.35 19.01 27.40 19.41 29.26 19.58 30.72 19.95
Multi F and Multi F MAX Indoor Unit Engineering Manual
45 23.42 18.73 24.87 19.78 26.33 19.15 27.38 19.56 29.24 19.72 30.69 20.10
50 23.40 18.87 24.85 19.93 26.31 19.30 27.36 19.70 29.21 19.87 30.67 20.24
55 23.38 19.00 24.84 20.07 26.29 19.44 27.34 19.85 29.19 20.01 30.64 20.39
60 23.37 19.14 24.82 20.22 26.27 19.58 27.32 19.99 29.17 20.16 30.62 20.54
65 23.35 19.28 24.80 20.37 26.25 19.72 27.29 20.13 29.15 20.30 30.60 20.69
LMVN240HV 70 23.33 19.42 24.78 20.51 26.23 19.86 27.27 20.28 29.13 20.45 30.57 20.84
24,000 75 22.77 19.10 24.21 20.20 25.66 19.58 26.70 20.01 28.55 20.20 29.99 20.60
80 22.21 18.77 23.65 19.88 25.09 19.30 26.13 19.73 27.97 19.95 29.42 20.36
85 21.65 18.43 23.09 19.55 24.53 18.99 25.57 19.44 27.40 19.68 28.84 20.10
90 21.09 18.08 22.53 19.21 23.96 18.69 25.00 19.14 26.83 19.40 28.27 19.84
95 20.49 17.89 21.92 19.03 23.35 18.55 24.00 18.72 26.20 19.30 27.63 19.75
100 19.99 17.41 21.42 18.55 22.85 18.10 23.69 18.43 25.70 18.88 27.13 19.35
105 19.49 16.93 20.92 18.07 22.35 17.66 23.38 18.14 25.20 18.47 26.63 18.94
110 18.99 16.35 20.42 17.49 21.85 17.12 22.88 17.60 24.70 17.94 26.13 18.42
115 18.49 15.86 19.92 17.00 21.35 16.66 22.38 17.15 24.20 17.51 25.63 18.00
118 18.19 15.75 19.62 16.89 21.05 16.58 22.08 17.07 23.90 17.46 25.33 17.96
122 18.10 15.71 19.52 16.86 20.95 16.55 21.98 17.05 23.81 17.44 25.23 17.94
14 35.29 26.84 37.48 28.35 39.67 27.45 41.26 28.03 44.06 28.26 46.25 28.80
20 35.26 27.05 37.45 28.57 39.64 27.66 41.23 28.25 44.02 28.49 46.21 29.02
25 35.24 27.26 37.43 28.79 39.61 27.88 41.19 28.47 43.99 28.71 46.18 29.25
30 35.21 27.47 37.40 29.01 39.58 28.09 41.16 28.68 43.96 28.93 46.14 29.47
35 35.18 27.67 37.37 29.23 39.55 28.31 41.13 28.90 43.92 29.15 46.11 29.70
40 35.16 27.88 37.34 29.45 39.52 28.52 41.10 29.12 43.89 29.37 46.07 29.92
45 35.13 28.09 37.31 29.67 39.49 28.73 41.07 29.34 43.86 29.58 46.04 30.14
50 35.10 28.30 37.28 29.89 39.46 28.94 41.04 29.55 43.82 29.80 46.00 30.37
55 35.08 28.51 37.25 30.11 39.43 29.16 41.01 29.77 43.79 30.02 45.97 30.59
60 35.05 28.71 37.23 30.33 39.40 29.37 40.97 29.99 43.76 30.24 45.93 30.81
65 35.02 28.92 37.20 30.55 39.37 29.58 40.94 30.20 43.72 30.46 45.90 31.03
LMVN360HV 70 34.99 29.13 37.17 30.77 39.34 29.79 40.91 30.42 43.69 30.67 45.86 31.26
36,000 75 34.15 28.65 36.32 30.30 38.49 29.37 40.05 30.01 42.82 30.30 44.99 30.90
80 33.31 28.16 35.47 29.82 37.64 28.94 39.20 29.60 41.96 29.92 44.12 30.54
85 32.48 27.64 34.63 29.32 36.79 28.49 38.35 29.16 41.10 29.52 43.26 30.15
90 31.64 27.12 33.79 28.81 35.94 28.03 37.50 28.71 40.25 29.10 42.40 29.76
95 30.74 26.84 32.88 28.55 35.02 27.82 36.00 28.08 39.30 28.95 41.44 29.63
100 29.99 26.12 32.13 27.83 34.27 27.15 35.53 27.65 38.55 28.32 40.69 29.02
105 29.24 25.40 31.38 27.11 33.52 26.49 35.07 27.21 37.80 27.70 39.94 28.41
110 28.49 24.53 30.63 26.23 32.77 25.67 34.32 26.40 37.05 26.92 39.20 27.64
115 27.74 23.80 29.88 25.49 32.02 24.99 33.57 25.72 36.31 26.27 38.45 27.01
118 27.29 23.62 29.43 25.34 31.57 24.87 33.12 25.61 35.86 26.18 38.00 26.93
122 27.14 23.56 29.28 25.29 31.43 24.82 32.97 25.57 35.71 26.15 37.85 26.91
TC = Total Capacity (kBtu/h).
SHC: Sensible Heat Capacity (kBtu/h).
Nominal capacity as rated 0 ft. above sea level and a 0 ft. level difference between outdoor and indoor units. Corresponding refrigerant piping length is accordance with standard length of each outdoor unit.
Nominal cooling capacity rating obtained with air entering the indoor unit at 80ºF dry bulb (DB) and 67ºF wet bulb (WB), and outdoor ambient conditions of 95ºF dry bulb (DB) and 75ºF wet bulb (WB).
The shaded table columns and rows indicate reference data. When operating at this temperature, these values can be different if the system is not running consistently.
142 | VERTICAL-HORIZONTAL Due to our policy of continuous product innovation, some specifications may change without notification.
©LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp.
MULTI F TWO-WAY VAHU INDOOR UNITS
MULTI F MAX Heating Capacity Table
Table 82: Multi F Vertical-Horizontal Air Handling Indoor Units Heating Capacity Table.
Model No. / Outdoor Air Temp. Indoor Air Temp. °F DB
Nominal Capacity 61 64 68 70 72 75
of Indoor Unit °F DB °F WB
(Btu/h) TC TC TC TC TC TC
0 -0.4 13.89 13.70 13.57 13.50 13.30 12.72
5 4.5 15.65 15.46 15.33 15.26 15.07 14.48
10 9 17.41 17.22 17.09 17.02 16.83 16.24
17 15 19.76 19.57 19.43 19.37 19.17 18.55
20 19 20.64 20.45 20.32 20.25 20.05 19.37
25 23 22.11 21.91 21.78 21.72 21.52 20.74
30 28 23.38 23.18 23.05 22.99 22.79 22.11
Due to our policy of continuous product innovation, some specifications may change without notification. VERTICAL-HORIZONTAL | 143
©LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp.
TWO-WAY VAHU INDOOR UNITS MULTI F
External Static Pressure MULTI F MAX
Table 83: Multi F Vertical-Horizontal Air Handling Unit External Static Pressure Setting Values Table.
Static Pressure (in. wg) 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1.0
Model No. / Nominal Capacity Airflow Rate / CFM Setting Value at (in. wg)1
of Indoor Unit (Btu/h)
High 710 56 67 74 78 87 94 98 982 982 982
LMVN240HV Mid 640 53 65 70 75 85 91 96 962 962 962
24,000
Low 480 53 55 64 70 79 84 92 922 922 922
High 990 80 85 90 95 100 103 1032 1032 1032 1032
LMVN360HV
Multi F and Multi F MAX Indoor Unit Engineering Manual
Do not operate the air conditioning system using less than the minimum airflow. There is risk of fire and severe injury or death.
Note:
Do not operate the air conditioning system using less than the minimum airflow. There is risk of product damage.
Table 85: Electric Heater Static Pressure Drop.
Heater Capacity (kW) Static Pressure Drop (in. wg)
0 0
5 -0.01
10 -0.02
Note:
• The external static pressure value must be reset if an electric heater is installed. For each 0.01 in. wg. increase in static pressure, the
external static pressure must increase by 1.
• If the external static pressure is not set properly, the provided safety device will turn off the heater (according to airflow).
Table 86: Field-Supplied Air Filter Static Pressure Drop Factors.
Model No. / Nominal Capacity of Indoor Unit (Btu/h) Airflow Rate / CFM Static Pressure Drop (in. wg)
High 710 -0.04
LMVN240HV (24,000) Mid 640 -0.03
Low 480 -0.03
High 990 -0.07
LMVN360HV (36,000) Mid 880 -0.05
Low 800 -0.05
Note:
• The external static pressure value must be reset if an air filter is installed. For each 0.01 in. wg. increase in static pressure, the
external static pressure must increase by 1.
• Factory tested with MERV 4 filter media. Fan speed set value when the unit is used with field-supplied filter media.
144 | VERTICAL-HORIZONTAL Due to our policy of continuous product innovation, some specifications may change without notification.
©LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp.
MULTI F TWO-WAY VAHU INDOOR UNITS
MULTI F MAX Acoustic Data
Figure 192: Sound Pressure Level Measurement Location. • Measurement taken 3.3′ away from the unit.
• Measurements taken with no attenuation and units operating at full load normal
With Case Microphone operating condition.
• Sound level will vary depending on a range of factors such as construction
(acoustic absorption coefficient) of particular area in which the equipment is
installed.
3.3 ft.
70 70
NC-65
60 60
Octave Band Sound Pressure Level (dB = 20μPa)
Octave Band Sound Pressure Level (dB = 20μPa)
NC-60
NC-55
50 50
NC-50
NC-45
40 40
NC-40
NC-35
30 30
NC-30
NC-25 20
20
Approximate NC-20
Hearing
Threshold NC-15
10 10 63 125 250 500 1000 2000 4000 8000
63 125 250 500 1000 2000 4000 8000
Octave Band Center Frequency (Hz)
Octave Band Center Frequency (Hz)
Due to our policy of continuous product innovation, some specifications may change without notification. VERTICAL-HORIZONTAL | 145
©LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp.
TWO-WAY VAHU INDOOR UNITS MULTI F
Refrigerant Flow Diagram MULTI F MAX
Figure 194: Multi F Vertical-Horizontal Air Handling Indoor Unit Refrigerant Flow Diagram.
Outlet Temperature
Thermistor for
Evaporator Inlet Temperature
Thermistor for
Table 88: Multi F Vertical-Horizontal Air Handling Indoor Unit Refrigerant Pipe Connection Port Diameters.
Model No. Vapor (inch) Liquid (inch)
LMVN240HV 1/2 1/4
LMVN360HV 5/8 3/8
146 | VERTICAL-HORIZONTAL Due to our policy of continuous product innovation, some specifications may change without notification.
©LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp.
MULTI F TWO-WAY VAHU INDOOR UNITS
MULTI F MAX Wiring Diagram
Due to our policy of continuous product innovation, some specifications may change without notification. VERTICAL-HORIZONTAL | 147
©LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp.
TWO-WAY VAHU INDOOR UNITS MULTI F
Wiring Diagram MULTI F MAX
2. Indoor unit with electric heater, DIP switches 5 and 6 must be set to ON.
• SW 5 ON: Fan operates continuously. (Can have uninterrupted heating during defrost or oil return modes using continuous heater and
fan operation.)
• SW5 OFF: Fan discontinuous operation. (There would be reduction in heating capacity while defrosting or oil return operation.)
• SW6 ON: Automatic heater operation. (Heater operates automatically using the heater algorithm.)
• SW6 OFF: Manual heater operation. (On / off operation is set manually. Heater operation follows the heater algorithm.)
148 | VERTICAL-HORIZONTAL Due to our policy of continuous product innovation, some specifications may change without notification.
©LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp.
MULTI F TWO-WAY VAHU INDOOR UNITS
MULTI F MAX Factory Supplied Parts and Materials
WARNING
Installation work must be performed by trained personnel and in accordance with national wiring standards and all local or other applicable codes.
Improper installation can result in fire, electric shock, physical injury, or death.
Note:
Read all instructions before installing this product. Become familiar with the unit’s components and connections, and the order of installation. Incorrect
• Indoor units (IDUs) must not be placed in an environment where the IDUs will be exposed to harmful volatile organic compounds
(VOCs) or in environments where there is improper air make up or supply or inadequate ventilation. If there are concerns about VOCs in
the environment where the IDUs are installed, proper air make up or supply and/or adequate ventilation must be provided. Additionally, in
buildings where IDUs will be exposed to VOCs, consider a third party factory-applied epoxy coating to the fan coils for each IDU where the
entire coil is dipped, not sprayed.
• If the unit is installed near a body of water, the installation parts are at risk of corroding. Appropriate anti-corrosion methods must be taken
for the unit and all installation parts.
Due to our policy of continuous product innovation, some specifications may change without notification. VERTICAL-HORIZONTAL | 149
©LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp.
TWO-WAY VAHU INDOOR UNITS MULTI F
Installation and Best Layout Practices MULTI F MAX
Access Holes
for Conduit
Multi F and Multi F MAX Indoor Unit Engineering Manual
Refrigerant Piping
>23-5/8
Connections
Clearance from
Access Panels
for Service
0 (zero) 0 (zero) Drain Connections
inches inches for Horizontal Install
>13-25/32 inches
Filter Access Drain Connections
for Vertical Install
Top
Right Side
Refrigerant Piping
Connections Drain
Connections
for Vertical Install
Drain Connections
for Horizontal Install
150 | VERTICAL-HORIZONTAL Due to our policy of continuous product innovation, some specifications may change without notification.
©LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp.
MULTI F TWO-WAY VAHU INDOOR UNITS
MULTI F MAX Installation and Best Layout Practices
Vertical-Horizontal Air Handling Units can be installed in a choice of vertical (upflow) or horizontal (left side) configurations.
• Plenum must be strong and secure enough to support the installation of adapter collars to accommo-
date duct work.
• Air handler platform must be sturdy enough to support the frame, plus any accessories (e.g., filter box). Field Supplied
Return Air Duct /
Plenum
• To prevent air leaks, seal all duct work according to local codes, but make sure that filter access is still
• Vibration isolators (field supplied) must be installed between the unit frame and the platform. If neces-
sary, provide the installing contractor with an illustration of where the vibration isolator must be added
and how it must be positioned.
>1 inch
Do not install the screws on the front and back of the unit, doing so will block filter installation.
• If the unit will not be suspended, still use angled steel support Table 93:Bracket / Bolt Position Dimensions.
brackets, but also add vibration isolators (field supplied) to avoid Capacity Dimensions (inches)
sound transmission. If necessary, provide the installing contractor (Btu/h) A B C
with an illustration of where the vibration isolator must be added
and how it must be positioned. 24,000
4 23 41-11/32
36,000
• Unit must be positioned properly for plenum / duct installation.
To ensure proper drainage for horizontal installations, unit must be installed within ±1/8 inches level of the unit’s length and width.
Due to our policy of continuous product innovation, some specifications may change without notification. VERTICAL-HORIZONTAL | 151
©LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp.
TWO-WAY VAHU INDOOR UNITS MULTI F
Installation and Best Layout Practices MULTI F MAX
152 | VERTICAL-HORIZONTAL Due to our policy of continuous product innovation, some specifications may change without notification.
©LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp.
MULTI F TWO-WAY VAHU INDOOR UNITS
MULTI F MAX Installation and Best Layout Practices
Figure 208:Close Up of Refrigerant Piping Connection Insulation. Connection for Liquid Piping
Refrigerant Piping Insulation (Field Supplied)
Refrigerant Piping Insulation
(Field Supplied) Refrigerant Piping
Insulation (Field Supplied)
Due to our policy of continuous product innovation, some specifications may change without notification. VERTICAL-HORIZONTAL | 153
©LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp.
TWO-WAY VAHU INDOOR UNITS MULTI F
Installation and Best Layout Practices MULTI F MAX
• Loose wiring will cause unit to malfunction, overheat, and catch fire, resulting in severe injury or death.
Note:
• Terminal screws will become loose during transport. Properly tighten the terminal connections during installation.
A voltage drop will cause the following problems:
• Magnetic switch vibration, fuse breaks, or disturbance to the normal function of an overload protection device.
• Compressor will not receive the proper starting current.
Connecting the Power Wiring and Communications Cable
1. To access the terminal block, first unscrew the top front panel, Figure 210:Connecting the Power Wiring and Communications Cable.
and then unscrew the cover from the control box.
Control
2. Knockout the access holes for the wiring. Insert the power wiring/ Top Front Box Cover
Panel
communications cable from the outdoor unit or branch distribution
unit (Multi F MAX systems only) through the conduits, pass the Access Holes
for Wiring
conduits through the designated access holes, and then insert
the conduits into the control box. To prevent electromagnetic
interference and product malfunction, leave a space between the
power wiring and communications cable outside of the indoor
unit.
Communications Cable
Figure 211:Indoor Unit to Outdoor Unit / Branch Distribution Unit (Multi F MAX
systems only) Power Wiring / Communications Cable Connections.
Outdoor Unit Terminal Block or
Branch Distribution Unit Terminal Block
Indoor Unit Terminal Block (Multi F MAX Systems Only)
GND
1(L1 ) 2 (L2) 3 3 or S
BR
GND
BL
RD
GRN /
YLW
154 | VERTICAL-HORIZONTAL Due to our policy of continuous product innovation, some specifications may change without notification.
©LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp.
MULTI F TWO-WAY VAHU INDOOR UNITS
MULTI F MAX Installation and Best Layout Practices
Controller Options
Vertical-Horizontal Air Handling indoor units can be used with many LG-supplied wired controllers (sold separately). The wireless handheld
controller (Model No. PQWRHQ0FDB) is also an optional accessory with use of the wired controller.
2. Field-supplied controller cable that connects to the indoor unit terminal block (must be at least UL2547 or UL1007, 22 AWG, two-core,
one-shield core, at least FT-6 rated if local electric and building codes require plenum cable usage).
Terminal
MODE
Extension cable
CN-REMO Outdoor Unit Terminal Block or controller cable, make sure to connect
When using field-supplied
Indoor Unit Terminal Block Branch Distribution UnittoTerminal
the yellow Block
yellow (communications wire), red to red (12V power
(Multi F MAX
wire),Systems
and black Only)
to black (ground wire) terminals from the remote
YL RD BK GND controller to the indoor unit terminal blocks.
12V 1(L1 ) 2 (L2) 3 3 or S
Comm. Power Ground
BR
GND
BL
RD
GRN /
YLW
Due to our policy of continuous product innovation, some specifications may change without notification. VERTICAL-HORIZONTAL | 155
©LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp.
TWO-WAY VAHU INDOOR UNITS MULTI F
Installation and Best Layout Practices MULTI F MAX
Wired Controller Placement Figure 214:Proper Location for the Wired Controller.
Wired controllers include a sensor to detect room temperature. To maintain
comfort levels in the conditioned space, the wired controller must be installed in
a location away from direct sunlight, high humidity, and where it could be directly
exposed to cold air. Controller must be installed four (4) to five (5) feet above the
floor where its LED display can be read easily, in an area with good air circula- TEMP
YES
tion, and where it can detect an average room temperature.
Remote Controlle r
NO
TEMP
Remote Controlle r
NO
4 to 5 feet
• Hot or cold air from ducts above the floor
TEMP
roller
Cont
ot e
Rem
Hanging the Wired Controller Figure 215:Removing the Cable Guide Grooves.
1. The controller wiring / cable can be installed in one of three directions: top, Top
Top
back, or on the right side. If top or right side installation is desired, remove
cable guide grooves on the controller, and then position wiring / cable on ap- Back Right
plicable side. Side
Right
Side
2. Choose and mark the area of installation, and then screw the wall plate into
place (using the provided parts). Install the controller wall plate to fit the elec-
trical box if one is present. Ensure that no gaps exist between the wall plate
and the wall itself. Figure 217:Installing /
Removing the Controller.
3. Arrange wiring / cables so as not to interfere with the controller circuitry. Figure 216:Attaching the Installing the Controller
Position the wired controller on the wall plate. Snap into place by pressing the Wall Plate.
bottom part of the wired controller onto the wall plate. Make sure that no gaps
exist between the wired controller and the wall plate on all sides. Wall Wall
4. To remove wired controller from the wall plate, insert a screwdriver into the
two holes at the bottom. Twist screwdriver to release controller. Do not Removing the Controller
156 | VERTICAL-HORIZONTAL Due to our policy of continuous product innovation, some specifications may change without notification.
©LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp.
MULTI F
MULTI F MAX
Due to our policy of continuous product innovation, some specifications may change without notification. VERTICAL-HORIZONTAL | 157
©LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp.
FOUR-WAY
VERTICAL-HORIZONTAL
AIR HANDLING
INDOOR UNIT DATA
“Mechanical Specifications” on page 159
“General Data / Specifications” on page 160
“Dimensions” on page 161
“Cooling Capacity Table” on page 162
“Heating Capacity Table” on page 164
“External Static Pressure” on page 166
“Heater Capacities” on page 168
“Acoustic Data” on page 169
“Refrigerant Flow Diagram” on page 171
“Wiring Diagram” on page 172
“Factory Supplied Parts and Materials” on page 174
“Installation and Best Layout Practices” on page 175
MULTI F FOUR-WAY VAHU INDOOR UNITS
MULTI F MAX Mechanical Specifications and Features
Four-way Vertical-Horizontal Air Fan Assembly and Figure 218: Multi F Vertical-Horizontal
Handing Indoor Unit Control Air Handling Indoor Unit.
The units have an integral
General fan assembly consisting of
All LG indoor units are factory assembled, wired, piped, and provided galvanized steel housing and a
with a control circuit board, and constant CFM ECM fan. Vertical- forward curve fan wheel. The ECM
Horizontal Air Handling units are designed for high-speed air volume (electronically commutated motor)
against an external static pressure up to 0.7″WG. Supply air opening fan is programmed to deliver con-
is flanged to accept field-installed ductwork that cannot exceed the stant CFM regardless of permitted
external static pressure limit of the unit. ESP (external static pressure),
and has permanently lubricated
Coil and sealed ball bearings. The
Indoor unit coils are factory built and are comprised of aluminum fins fan / motor assembly is mounted
mechanically bonded to copper tubing. Each unit has a minimum of on vibration-attenuating rubber
Condensate
Features The unit is designed for gravity draining of condensate.
• Inverter (Variable speed fan) • Two thermistor control • Built-in dry contact for third party
• Control lock function • Group control thermostat
• Auto operation • Optional accessory electric heater • Wired controller ordered separately
• Dehumidifying function • Self-diagnostics function • Constant CFM ECM fan
Due to our policy of continuous product innovation, some specifications may change without notification. VERTICAL-HORIZONTAL | 159
©LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp.
FOUR-WAY VAHU INDOOR UNITS MULTI F
General Data / Specifications MULTI F MAX
Table 94: Multi F Vertical-Horizontal Air Handling Indoor Unit General Data.
Model Name LVN181HV4 LVN241HV4 LVN361HV4
Nominal Cooling Capacity (Btu/h) 1
18,000 24,000 36,000
Nominal Heating Capacity (Btu/h) 1
20,000 27,000 40,000
Operating Range
Cooling (°F WB) 57-77 57-77 57-77
Heating (°F DB) 59-81 59-81 59-81
Multi F and Multi F MAX Indoor Unit Engineering Manual
Fan
Type Sirocco Sirocco Sirocco
Motor Output (W) x Qty. 250 x 1 250 x 1 250 x 1
ECM (Electronically ECM (Electronically ECM (Electronically
Motor/Drive
Commutated Motor) / Direct Commutated Motor) / Direct Commutated Motor) / Direct
Airflow Rate CFM (H/M/L) 640 / 580 / 480 710 / 640 / 480 990 / 880 / 800
Maximum External Static Pressure (in. WG) 0.7 0.7 0.7
Unit Data
Refrigerant Type2 R410A R410A R410A
Refrigerant Control EEV EEV EEV
Power Supply V, Ø, Hz 3
208-230, 1, 60 208-230, 1, 60 208-230, 1, 60
Rated Amps (A) 1.1 1.1 1.1
Sound Pressure Level dB(A) (H/M/L) at 0.3"WG ESP 4
35 / 33 / 30 36 / 34 / 30 44 / 41 / 39
Dimensions (W x H x D, in.) 18 x 48-11/16 x 21-1/4 18 x 48-11/16 x 21-1/4 18 x 48-11/16 x 21-1/4
Net Weight (lbs.) 123.5 123.5 129
Shipping Weight (lbs.) 135.1 135.1 140
Power Wiring / Communications Cable (No. x AWG) 5
4 x 14 4 x 14 4 x 14
Heat Exchanger (2x24x18)x2 (2x24x18)x2 (3x24x18)x2
(Row x Column x Fin / inch) x Number
Pipe Size
Liquid (in.) 1/4 1/4 3/8
Vapor (in.) 1/2 1/2 5/8
Connection Size
Liquid (in.) 3/8 3/8 3/8
Vapor (in.) 5/8 5/8 5/8
Primary Drain I.D. (in.) 3/4 FPT 3/4 FPT 3/4 FPT
Secondary Drain I.D. (in.) 3/4 FPT 3/4 FPT 3/4 FPT
1
Nominal capacity is rated 0 ft. above sea level with corresponding refrigerant piping length in 3
Acceptable operating voltage: 187V-253V.
accordance with standard length of each outdoor unit and a 0 ft. level difference between outdoor and 4
Sound pressure levels are tested in an anechoic chamber under ISO Standard 3745 and are the
indoor units. All capacities are net with a combination ratio between 95 – 105%. same in both cooling and heating mode. These values can increase due to ambient conditions during
Nominal cooling capacity rating obtained with air entering the indoor unit at 80ºF dry bulb (DB) and 67ºF operation.
wet bulb (WB) and outdoor ambient conditions of 95ºF dry bulb (DB) and 75ºF wet bulb (WB). 5
All power wiring / communications cable to the IDUs must be minimum 14 AWG, 4-conductor, stranded,
Nominal heating capacity rating obtained with air entering the indoor unit at 70ºF dry bulb (DB) and 60ºF shielded or unshielded (if shielded, must be grounded to chassis at ODU only) and must comply with
wet bulb (WB) and outdoor ambient conditions of 47ºF dry bulb (DB) and 43ºF wet bulb (WB). applicable local and national codes.
2
This unit comes with a dry helium charge.
160 | VERTICAL-HORIZONTAL Due to our policy of continuous product innovation, some specifications may change without notification.
©LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp.
MULTI F FOUR-WAY VAHU INDOOR UNITS
MULTI F MAX Dimensions
I J
Top
J
A
Drain connections
connections
for horizontal right
application
Drain connections
for horizontal left
application Drain
connections
D
B for upflow
C
Air filter cover application
Front Side-right
F
E
Bottom
Unit: inch
Dimensions Wiring
Knock out Refrigerant Refrigerant
Capacity Pipe size Pipe
ODU A B C I J Connections
(kBtu/h) D E F G H
Comm-
Height Width Depth Power unication Liquid Gas Liquid Gas
18 48-11/16 18 21-1/4 1-9/16 17-1/2 20 17 12-1/8 1-11/16 7/8 1/4 1/2 3/8 5/8
Multi 24
Zone
36 48-11/16 18 21-1/4 1-9/16 17-1/2 20 17 12-1/8 1-11/16 7/8 3/8 5/8 3/8 5/8
Due to our policy of continuous product innovation, some specifications may change without notification. VERTICAL-HORIZONTAL | 161
©LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp.
FOUR-WAY VAHU INDOOR UNITS MULTI F
Cooling Capacity Table MULTI F MAX
Table 95: Multi F Vertical-Horizontal Air Handling Indoor Units Cooling Capacity Table.
Model No. / Indoor Air Temp. °F DB / °F WB
Nominal Capacity Outdoor Air
Temp. 68 / 57 73 / 61 77 / 64 80 / 67 86 / 72 90 / 75
of Indoor Unit (°F DB) TC SHC TC SHC TC SHC TC SHC TC SHC TC SHC
(Btu/h)
14 17.65 13.25 18.74 13.99 19.84 13.55 20.63 13.83 22.03 13.95 23.12 14.22
20 17.63 13.35 18.73 14.10 19.82 13.65 20.61 13.94 22.01 14.06 23.11 14.33
25 17.62 13.45 18.71 14.21 19.81 13.76 20.60 14.05 22.00 14.17 23.09 14.44
30 17.60 13.56 18.70 14.32 19.79 13.87 20.58 14.16 21.98 14.28 23.07 14.55
35 17.59 13.66 18.68 14.43 19.78 13.97 20.57 14.27 21.96 14.39 23.05 14.66
40 17.58 13.76 18.67 14.54 19.76 14.08 20.55 14.37 21.94 14.49 23.04 14.77
Multi F and Multi F MAX Indoor Unit Engineering Manual
45 17.56 13.87 18.66 14.65 19.75 14.18 20.53 14.48 21.93 14.60 23.02 14.88
50 17.55 13.97 18.64 14.75 19.73 14.29 20.52 14.59 21.91 14.71 23.00 14.99
55 17.54 14.07 18.63 14.86 19.72 14.39 20.50 14.69 21.89 14.82 22.98 15.10
60 17.52 14.17 18.61 14.97 19.70 14.50 20.49 14.80 21.88 14.93 22.97 15.21
65 17.51 14.27 18.60 15.08 19.69 14.60 20.47 14.91 21.86 15.03 22.95 15.32
LVN181HV4 70 17.50 14.38 18.58 15.19 19.67 14.70 20.46 15.01 21.84 15.14 22.93 15.43
18,000 75 17.08 14.14 18.16 14.96 19.24 14.50 20.03 14.81 21.41 14.96 22.50 15.25
80 16.66 13.90 17.74 14.72 18.82 14.29 19.60 14.61 20.98 14.77 22.06 15.07
85 16.24 13.64 17.32 14.47 18.40 14.06 19.17 14.39 20.55 14.57 21.63 14.88
90 15.82 13.39 16.90 14.22 17.97 13.84 18.75 14.17 20.12 14.36 21.20 14.69
95 15.37 13.25 16.44 14.09 17.51 13.73 18.00 13.86 19.65 14.29 20.72 14.62
100 14.99 12.89 16.06 13.74 17.13 13.40 17.77 13.65 19.28 13.98 20.35 14.32
105 14.62 12.54 15.69 13.38 16.76 13.08 17.53 13.43 18.90 13.67 19.97 14.02
110 14.24 12.11 15.32 12.95 16.39 12.67 17.16 13.03 18.53 13.29 19.60 13.64
115 13.87 11.75 14.94 12.58 16.01 12.34 16.79 12.70 18.15 12.97 19.22 13.33
118 13.65 11.66 14.72 12.51 15.79 12.27 16.56 12.64 17.93 12.92 19.00 13.29
122 13.57 11.63 14.64 12.48 15.71 12.25 16.49 12.62 17.85 12.91 18.92 13.28
14 23.53 17.89 24.99 18.90 26.45 18.30 27.50 18.69 29.37 18.84 30.83 19.20
20 23.51 18.03 24.97 19.05 26.43 18.44 27.48 18.83 29.35 18.99 30.81 19.35
25 23.49 18.17 24.95 19.20 26.41 18.59 27.46 18.98 29.33 19.14 30.79 19.50
30 23.47 18.31 24.93 19.34 26.39 18.73 27.44 19.12 29.30 19.28 30.76 19.65
35 23.46 18.45 24.91 19.49 26.37 18.87 27.42 19.27 29.28 19.43 30.74 19.80
40 23.44 18.59 24.89 19.64 26.35 19.01 27.40 19.41 29.26 19.58 30.72 19.95
45 23.42 18.73 24.87 19.78 26.33 19.15 27.38 19.56 29.24 19.72 30.69 20.10
50 23.40 18.87 24.85 19.93 26.31 19.30 27.36 19.70 29.21 19.87 30.67 20.24
55 23.38 19.00 24.84 20.07 26.29 19.44 27.34 19.85 29.19 20.01 30.64 20.39
60 23.37 19.14 24.82 20.22 26.27 19.58 27.32 19.99 29.17 20.16 30.62 20.54
65 23.35 19.28 24.80 20.37 26.25 19.72 27.29 20.13 29.15 20.30 30.60 20.69
LVN241HV4 70 23.33 19.42 24.78 20.51 26.23 19.86 27.27 20.28 29.13 20.45 30.57 20.84
24,000 75 22.77 19.10 24.21 20.20 25.66 19.58 26.70 20.01 28.55 20.20 29.99 20.60
80 22.21 18.77 23.65 19.88 25.09 19.30 26.13 19.73 27.97 19.95 29.42 20.36
85 21.65 18.43 23.09 19.55 24.53 18.99 25.57 19.44 27.40 19.68 28.84 20.10
90 21.09 18.08 22.53 19.21 23.96 18.69 25.00 19.14 26.83 19.40 28.27 19.84
95 20.49 17.89 21.92 19.03 23.35 18.55 24.00 18.72 26.20 19.30 27.63 19.75
100 19.99 17.41 21.42 18.55 22.85 18.10 23.69 18.43 25.70 18.88 27.13 19.35
105 19.49 16.93 20.92 18.07 22.35 17.66 23.38 18.14 25.20 18.47 26.63 18.94
110 18.99 16.35 20.42 17.49 21.85 17.12 22.88 17.60 24.70 17.94 26.13 18.42
115 18.49 15.86 19.92 17.00 21.35 16.66 22.38 17.15 24.20 17.51 25.63 18.00
118 18.19 15.75 19.62 16.89 21.05 16.58 22.08 17.07 23.90 17.46 25.33 17.96
122 18.10 15.71 19.52 16.86 20.95 16.55 21.98 17.05 23.81 17.44 25.23 17.94
TC = Total Capacity (kBtu/h).
SHC: Sensible Heat Capacity (kBtu/h).
Nominal capacity as rated 0 ft. above sea level and a 0 ft. level difference between outdoor and indoor units. Corresponding refrigerant piping length is accordance with standard length of each outdoor unit.
Nominal cooling capacity rating obtained with air entering the indoor unit at 80ºF dry bulb (DB) and 67ºF wet bulb (WB), and outdoor ambient conditions of 95ºF dry bulb (DB) and 75ºF wet bulb (WB).
The shaded table columns and rows indicate reference data. When operating at this temperature, these values can be different if the system is not running consistently.
162 | VERTICAL-HORIZONTAL Due to our policy of continuous product innovation, some specifications may change without notification.
©LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp.
MULTI F FOUR-WAY VAHU INDOOR UNITS
MULTI F MAX Cooling Capacity Table
Table 95: Multi F Vertical-Horizontal Air Handling Indoor Units Cooling Capacity Table - continued
Model No. / Indoor Air Temp. °F DB / °F WB
Nominal Capacity Outdoor Air
Temp. 68 / 57 73 / 61 77 / 64 80 / 67 86 / 72 90 / 75
of Indoor Unit (°F DB) TC SHC TC SHC TC SHC TC SHC TC SHC TC SHC
(Btu/h)
14 35.29 27.18 37.48 28.71 39.67 27.80 41.26 28.39 44.06 28.63 46.25 29.17
20 35.26 27.39 37.45 28.94 39.64 28.02 41.23 28.61 44.02 28.85 46.21 29.40
25 35.24 27.61 37.43 29.16 39.61 28.24 41.19 28.83 43.99 29.07 46.18 29.62
30 35.21 27.82 37.40 29.39 39.58 28.45 41.16 29.05 43.96 29.30 46.14 29.85
35 35.18 28.03 37.37 29.61 39.55 28.67 41.13 29.27 43.92 29.52 46.11 30.08
40 35.16 28.24 37.34 29.83 39.52 28.88 41.10 29.49 43.89 29.74 46.07 30.30
45 35.13 28.45 37.31 30.05 39.49 29.10 41.07 29.71 43.86 29.96 46.04 30.53
50 35.10 28.66 37.28 30.28 39.46 29.32 41.04 29.93 43.82 30.19 46.00 30.76
55 35.08 28.87 37.25 30.50 39.43 29.53 41.01 30.15 43.79 30.41 45.97 30.98
60 35.05 29.08 37.23 30.72 39.40 29.74 40.97 30.37 43.76 30.63 45.93 31.21
65 35.02 29.29 37.20 30.94 39.37 29.96 40.94 30.59 43.72 30.85 45.90 31.43
LVN361HV4
Due to our policy of continuous product innovation, some specifications may change without notification. VERTICAL-HORIZONTAL | 163
©LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp.
FOUR-WAY VAHU INDOOR UNITS MULTI F
Heating Capacity Table MULTI F MAX
Table 96: Multi F Vertical-Horizontal Air Handling Indoor Units Heating Capacity Table.
Model No. / Outdoor Air Temp. Indoor Air Temp. °F DB
Nominal Capacity 61 64 68 70 72 75
of Indoor Unit °F DB °F WB
(Btu/h) TC TC TC TC TC TC
0 -0.4 10.29 10.14 10.05 10.00 9.86 9.42
5 4.5 11.59 11.45 11.35 11.30 11.16 10.72
10 9 12.90 12.75 12.66 12.61 12.46 12.03
17 15 14.64 14.49 14.40 14.35 14.20 13.74
Multi F and Multi F MAX Indoor Unit Engineering Manual
164 | VERTICAL-HORIZONTAL Due to our policy of continuous product innovation, some specifications may change without notification.
©LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp.
MULTI F FOUR-WAY VAHU INDOOR UNITS
MULTI F MAX Heating Capacity Table
Table 96: Multi F Vertical-Horizontal Air Handling Indoor Units Heating Capacity Table - continued
Model No. / Outdoor Air Temp. Indoor Air Temp. °F DB
Nominal Capacity 61 64 68 70 72 75
of Indoor Unit °F DB °F WB
(Btu/h) TC TC TC TC TC TC
0 -0.4 20.58 20.29 20.10 20.00 19.71 18.84
5 4.5 23.19 22.90 22.71 22.61 22.32 21.45
10 9 25.80 25.51 25.31 25.22 24.93 24.06
17 15 29.28 28.99 28.79 28.70 28.41 27.48
20 19 30.58 30.29 30.10 30.00 29.71 28.70
25 23 32.75 32.46 32.27 32.17 31.88 30.72
30 28 34.64 34.35 34.15 34.06 33.77 32.75
Due to our policy of continuous product innovation, some specifications may change without notification. VERTICAL-HORIZONTAL | 165
©LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp.
FOUR-WAY VAHU INDOOR UNITS MULTI F
External Static Pressure MULTI F MAX
Note:
Do not operate with less than the minimum airflow. If an airflow Do not operate with less than the minimum airflow. If an airflow is
is used below the minimum, there is a risk of fire, which will used below the minimum, there is a risk of damage to the product.
lead to physical injury or death
These VAHUs are constant air volume (CAV) units and do not require any
field adjustment to change ESP settings.
166 | VERTICAL-HORIZONTAL Due to our policy of continuous product innovation, some specifications may change without notification.
©LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp.
MULTI F FOUR-WAY VAHU INDOOR UNITS
MULTI F MAX External Static Pressure
Table 101: Down Flow Air Filter Static Pressure Drop Factors
Capacity (kBtu/h [tons]) Flow Rate (CFM) Static Pressure Drop (in wg)
High (640) -0.04
18 (1.5) Middle(580) -0.04
Low (480) -0.04
High (710) -0.04
24 (2.0) Middle(640) -0.04
Low (480) -0.04
High (990) -0.04
36 (3.0) Middle(880) -0.04
Low (800) -0.04
Table 102: Down Flow Internal Electric Heater Static Pressure Drop.
Heater Capacity (kW) Static Pressure Drop (in. wg)
0 0
3, 5 -0.01
8, 10 -0.01
Due to our policy of continuous product innovation, some specifications may change without notification. VERTICAL-HORIZONTAL | 167
©LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp.
FOUR-WAY VAHU INDOOR UNITS MULTI F
Heater Capacities MULTI F MAX
Figure 220: Typical Vertical Air Handling Unit Optional Electric Heater Accessory.
Example: 5kW Capacity Heater
Bracket
Bi metal
Heater Coil
Terminal Block
Relay
LVN241HV4 (24) √ √ √ √ X X
LVN361HV4 (36) √ √ √ √ X X
√ = Compatible X = Not Compatible
168 | VERTICAL-HORIZONTAL Due to our policy of continuous product innovation, some specifications may change without notification.
©LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp.
MULTI F FOUR-WAY VAHU INDOOR UNITS
MULTI F MAX Acoustic Data
Standard 3745.
• Operating Conditions:
Power source: 220V/60 Hz.
3.3 ft. • Sound level will vary depending on a range of factors including the con-
struction (acoustic absorption coefficient) of a particular room in which
the unit was installed.
Due to our policy of continuous product innovation, some specifications may change without notification. VERTICAL-HORIZONTAL | 169
©LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp.
FOUR-WAY VAHU INDOOR UNITS MULTI F
Acoustic Data MULTI F MAX
Table 106: Vertical Air Handling Unit Sound Power Levels (dB[A]).
Sound Power Levels (dB[A]) • Data is valid under diffuse field conditions.
Model No. • Data is valid under nominal operating conditions.
High Fan Speed
LVN181HV4 54 • Sound power level is measured using rated conditions, and tested
LVN241HV4 55
in a reverberation room per ISO 3741 standards.
LVN361HV4 63 • Sound level will vary depending on a range of factors such as
construction (acoustic absorption coefficient) of particular area in
which the equipment is installed.
• Reference acoustic intensity: 0dB = 10E-6μW/m2
Multi F and Multi F MAX Indoor Unit Engineering Manual
170 | VERTICAL-HORIZONTAL Due to our policy of continuous product innovation, some specifications may change without notification.
©LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp.
MULTI F FOUR-WAY VAHU INDOOR UNITS
MULTI F MAX Refrigerant Flow Diagram
Figure 224: Four-way Vertical-Horizontal Air Handling Indoor Unit Refrigerant Flow Diagram.
Scirocco Fan
M
Vapor Pipe Connection Port
Heat Exchanger
(Flare Connection)
Heating
Table 107: Four-way Vertical-Horizontal Air Handling Indoor Unit Refrigerant Pipe Sizes and Connection Sizes.
Due to our policy of continuous product innovation, some specifications may change without notification. VERTICAL-HORIZONTAL | 171
©LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp.
FOUR-WAY VAHU INDOOR UNITS MULTI F
Wiring Diagram MULTI F MAX
172 | VERTICAL-HORIZONTAL Due to our policy of continuous product innovation, some specifications may change without notification.
©LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp.
MULTI F FOUR-WAY VAHU INDOOR UNITS
MULTI F MAX Wiring Diagram
WARNING
Multi F and Multi F MAX Indoor Unit Engineering Manual
Installation work must be performed by trained personnel and in accordance with national wiring standards and all local or other applicable codes.
Improper installation can result in fire, electric shock, physical injury, or death.
Note:
Read all instructions before installing this product. Become familiar with the unit’s components and connections, and the order of installation. Incorrect
installation can degrade or prevent proper operation.
Selecting the Best Location
Do’s Don’ts
• Place the unit where air circulation through the ducts will not be • Do not install the unit near a heat or steam source, or where
blocked. considerable amounts of oil, iron powder, or flour are used.
• Place the unit where drainage can be obtained easily. • Do not install the unit where sulfuric acid and flammable or cor-
• Place the unit where noise prevention is taken into consideration. rosive gases are generated, vented into, or stored.
• Ensure there is sufficient strength to bear the load of the indoor • Do not install the unit near high-frequency generators.
unit. • Do not install the unit near a doorway.
• Ensure there is sufficient maintenance space. The unit will be damaged, will malfunction, and/or will not op-
• Locate the indoor unit in a location that is level, and where it can erate as designed if installed in any of the conditions listed.
be easily connected to the outdoor unit / branch distribution unit.
• Indoor units (IDUs) must not be placed in an environment where the IDUs will be exposed to harmful volatile organic compounds
(VOCs) or in environments where there is improper air make up or supply or inadequate ventilation. If there are concerns about VOCs in
the environment where the IDUs are installed, proper air make up or supply and/or adequate ventilation must be provided. Additionally, in
buildings where IDUs will be exposed to VOCs, consider a third party factory-applied epoxy coating to the fan coils for each IDU where the
entire coil is dipped, not sprayed.
• If the unit is installed near a body of water, the installation parts are at risk of corroding. Appropriate anti-corrosion methods must be taken
for the unit and all installation parts.
174 | VERTICAL-HORIZONTAL Due to our policy of continuous product innovation, some specifications may change without notification.
©LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp.
MULTI F FOUR-WAY VAHU INDOOR UNITS
MULTI F MAX Installation and Best Layout Practices
Access Holes
for Conduit
Refrigerant Piping
Connections
More than 23-5/8
clearance from 0 (zero) 0 (zero)
access panels
for Service Drain Connections
More than
Unit : inch 13-25/32
G
H
I J
Top
J
Refrigerant
A
Drain connections
connections
for horizontal right
application
Drain connections
for horizontal left
application Drain
connections
D
B for upflow
C
Air filter cover application
Front Side-right
F
Unit: inch
E
Bottom
Dimensions Wiring
Knock out Refrigerant
Refrigerant Pipe
ODU VAHU A B C I J Pipe size Connections
Capacity D E F G H
(kBtu/h) Comm-
Height Width Depth Power unication Liquid Gas Liquid Gas
18
Multi 24 48-11/16 18 21-1/4 1-9/16 17-1/2 20 17 12-1/8 1-11/16 7/8 1/4 1/2 3/8 5/8
Zone
36 48-11/16 18 21-1/4 1-9/16 17-1/2 20 17 12-1/8 1-11/16 7/8 3/8 5/8 3/8 5/8
Due to our policy of continuous product innovation, some specifications may change without notification. VERTICAL-HORIZONTAL | 175
©LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp.
FOUR-WAY VAHU INDOOR UNITS MULTI F
Installation and Best Layout Practices MULTI F MAX
Vertical-Horizontal Air Handling Units can be installed in a choice of vertical upflow, vertical downflow (with optional downflow kit), or horizontal (left
or right side) configurations.
Figure 229:Vertical Installation /
Vertical (Upflow) Installation Attaching the Bottom Duct.
• Unit must be positioned properly for plenum / duct installation.
• To maintain proper air flow, minimum height clearance is 14 inches. Field Supplied
Supply Air Duct
• Plenum must be strong and secure enough to support the installation of adapter collars to accommo-
Multi F and Multi F MAX Indoor Unit Engineering Manual
sary, provide the installing contractor with an illustration of where the vibration isolator must be added
and how it must be positioned.
Do not install the screws on the front and back of the unit; doing so will block filter installation.
>1 inch
Refrigerant
connections
Drain
connections
for downflow
application
176 | VERTICAL-HORIZONTAL Due to our policy of continuous product innovation, some specifications may change without notification.
©LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp.
MULTI F FOUR-WAY VAHU INDOOR UNITS
MULTI F MAX Installation and Best Layout Practices
Horizontal Installation
• Units will be installed in horizontal left or horizontal right con- Figure 231: Typical Horizontal Left Installation.
figuration. Horizontal left is the factory default configuration. For Field Supplied
Field-Supplied >3/8 inch Threaded Rod
horizontal right, the unit must be field converted. The horizontal Supply Air Duct
Return Air Duct / Plenum
right conversion requires removing the internal drain pan from the
left side of the unit and reinstalling on the right side. No conver-
sion kit is required. Refer to the installation manual for details.
• Units must be installed so that the access panels face to the side,
not facing up or down.
• Installation must be in accordance with all relevant building
codes, which will necessitate the installation of an external con-
densate pan (position the unit in or above the external conden- >1-1/2 inch x 1-1/2 inch Angle A
sate pan). Recommended length >26 inches
B
Table 111: Bracket / Bolt Position Dimensions for Horizontal Left and
Horizontal Right Installation.
Capacity Dimensions (inches)
(Btu/h) A B C
18,000 4 23 41-11/32
24,000 4 23 41-11/32
36,000 4 23 41-11/32
Due to our policy of continuous product innovation, some specifications may change without notification. VERTICAL-HORIZONTAL | 177
©LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp.
FOUR-WAY VAHU INDOOR UNITS MULTI F
Installation and Best Layout Practices MULTI F MAX
Figure 240:Close Up of Refrigerant Piping Connection Insulation. Connection for Liquid Piping
Refrigerant Piping Insulation (Field Supplied)
Refrigerant Piping Insulation
(Field Supplied) Refrigerant Piping
Insulation (Field Supplied)
Due to our policy of continuous product innovation, some specifications may change without notification. VERTICAL-HORIZONTAL | 179
©LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp.
FOUR-WAY VAHU INDOOR UNITS MULTI F
Installation and Best Layout Practices MULTI F MAX
• Loose wiring will cause unit to malfunction, overheat, and catch fire, resulting in severe injury or death.
Note:
• Terminal screws will become loose during transport. Properly tighten the terminal connections during installation.
A voltage drop will cause the following problems:
• Magnetic switch vibration, fuse breaks, or disturbance to the normal function of an overload protection device.
• Compressor will not receive the proper starting current.
Connecting the Power Wiring and Communications Cable
1. To access the terminal block, first unscrew the top front panel, Figure 242:Connecting the Power Wiring and Communications Cable.
and then unscrew the cover from the control box.
Control
2. Knockout the access holes for the wiring. Insert the power wiring/ Top Front Box Cover
Panel
communications cable from the outdoor unit or branch distribution
unit (Multi F MAX systems only) through the conduits, pass the Access Holes
for Wiring
conduits through the designated access holes, and then insert
the conduits into the control box. To prevent electromagnetic
interference and product malfunction, leave a space between the
power wiring and communications cable outside of the indoor
unit.
Communications Cable
Figure 243:Indoor Unit to Outdoor Unit / Branch Distribution Unit (Multi F MAX
systems only) Power Wiring / Communications Cable Connections.
Outdoor Unit Terminal Block or
Branch Distribution Unit Terminal Block
Indoor Unit Terminal Block (Multi F MAX Systems Only)
GND
1(L1 ) 2 (L2) 3 3 or S
BR
GND
BL
RD
GRN /
YLW
180 | VERTICAL-HORIZONTAL Due to our policy of continuous product innovation, some specifications may change without notification.
©LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp.
MULTI F FOUR-WAY VAHU INDOOR UNITS
MULTI F MAX Installation and Best Layout Practices
Controller Options
Vertical-Horizontal Air Handling indoor units can be used with many LG-supplied wired controllers (sold separately). The wireless handheld
controller (Model No. PQWRHQ0FDB) is also an optional accessory with use of the wired controller.
2. Field-supplied controller cable that connects to the indoor unit terminal block (must be at least UL2547 or UL1007, 22 AWG, two-core,
one-shield core, at least FT-6 rated if local electric and building codes require plenum cable usage).
Terminal
MODE
Extension cable
CN-REMO Outdoor Unit Terminal Block or controller cable, make sure to connect
When using field-supplied
Indoor Unit Terminal Block Branch Distribution UnittoTerminal
the yellow Block
yellow (communications wire), red to red (12V power
(Multi F MAX
wire),Systems
and black Only)
to black (ground wire) terminals from the remote
YL RD BK GND controller to the indoor unit terminal blocks.
12V 1(L1 ) 2 (L2) 3 3 or S
Comm. Power Ground
BR
GND
BL
RD
GRN /
YLW
Due to our policy of continuous product innovation, some specifications may change without notification. VERTICAL-HORIZONTAL | 181
©LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp.
FOUR-WAY VAHU INDOOR UNITS MULTI F
Installation and Best Layout Practices MULTI F MAX
Wired Controller Placement Figure 246:Proper Location for the Wired Controller.
Wired controllers include a sensor to detect room temperature. To maintain
comfort levels in the conditioned space, the wired controller must be installed in
a location away from direct sunlight, high humidity, and where it could be directly
exposed to cold air. Controller must be installed four (4) to five (5) feet above the
floor where its LED display can be read easily, in an area with good air circula- TEMP
YES
tion, and where it can detect an average room temperature.
Remote Controlle r
NO
TEMP
Remote Controlle r
NO
4 to 5 feet
• Hot or cold air from ducts above the floor
TEMP
roller
Cont
ot e
Rem
Hanging the Wired Controller Figure 247:Removing the Cable Guide Grooves.
1. These steps are typical. Refer to the installation instructions with your control- Top
Top
ler. The controller wiring / cable can be installed in one of three directions: top,
back, or on the right side. If top or right side installation is desired, remove Back Right
cable guide grooves on the controller, and then position wiring / cable on ap- Side
Right
plicable side. Side
2. Choose and mark the area of installation, and then screw the wall plate into
place (using the provided parts). Install the controller wall plate to fit the elec-
trical box if one is present. Ensure that no gaps exist between the wall plate Figure 249:Installing /
and the wall itself. Removing the Controller.
Figure 248:Attaching the Installing the Controller
3. Arrange wiring / cables so as not to interfere with the controller circuitry. Wall Plate.
Position the wired controller on the wall plate. Snap into place by pressing the
bottom part of the wired controller onto the wall plate. Make sure that no gaps Wall Wall
exist between the wired controller and the wall plate on all sides.
4. To remove wired controller from the wall plate, insert a screwdriver into the Removing the Controller
182 | VERTICAL-HORIZONTAL Due to our policy of continuous product innovation, some specifications may change without notification.
©LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp.
MULTI F
MULTI F MAX
Due to our policy of continuous product innovation, some specifications may change without notification. VERTICAL-HORIZONTAL | 183
©LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp.
APPLICATION
GUIDELINES
“Equipment Selection Procedure” on page 185
“Placement Considerations” on page 192
MULTI F EQUIPMENT SELECTION PROCEDURE
MULTI F MAX
To choose the multi-zone system that is the most appropriate for the space, as with traditional air-conditioning systems, follow similar
protocols outlined in Manual J from the Air Conditioning Contractors of America (ACCA; see www.acca.org).
1. Obtain the design conditions, and calculate the maximum cool and heat loads for the structure.
2. Select the equipment (choosing the appropriate indoor units and outdoor unit):
• Determine number of zones.
• Determine total number of indoor units (refer to zone load calculations when choosing indoor units).
• Determine number of indoor units allocated to each outdoor unit, considering allowable indoor unit connections, both indoor unit and
outdoor unit capacities, and system piping capabilities.
3. Determine the corrected capacity for the indoor units and outdoor unit using LATS HVAC software (preferred method) or:
• System Combination Tables.
• Capacity Tables (it will be necessary to interpolate).
• Capacity Coefficient Factors (such as refrigerant line length derates, design condition derates, defrost operation derate [heating mode],
altitude derate [if applicable]).
4. Compare corrected capacities to load calculations.
5. Reselect equipment if necessary.
Application Guidelines
Obtain the winter outdoor / indoor temperature and summer and winter outdoor / indoor temperature design parameters for the location in
which the system is installed. Determine if summer or winter design gains, relative humidity, and building features like skylights, orientation,
number of occupants, etc., would change the total heat loss / gain and sensible / latent heat gain, and then calculate the maximum cool and
heat loads for the space (using Manual J or energy modeling programs).
2. Total connected indoor unit nominal capacity must be a minimum 40% and a maximum of 133% of outdoor unit nominal capacity.
3. To calculate the connected total indoor unit nominal capacity, simply sum up the nominal capacities of all indoor units.
• For high static duct and vertical-horizontal air handling indoor units, a 1.3 multiplier must first be applied before adding to the sum of
other indoor units (when connected to an ODU other than the LMU600HV).
• When high static duct and / or vertical-horizontal air handling indoor units are the only connected indoor units, the multiplier is 1.2.
For allocated capacity information, see the combination tables in the "Multi F / Multi F MAX Combination Data Manual" on www.lghvac.com.
For performance data, see "Multi F / Multi F MAX Performance Data Manual" on www.lghvac.com. Also refer to the appropriate manuals on
www.lghvac.com for combination and capacity data for Multi F with LG RED / Multi F MAX with LG RED units.
Due to our policy of continuous product innovation, some specifications may change without notification.
©LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp. APPLICATION GUIDELINES | 185
EQUIPMENT SELECTION PROCEDURE MULTI F
MULTI F MAX
Multiplier Examples
Example 1 Branch Distribution Unit (PMBD3641) Example 2 Branch Distribution Unit (PMBD3620)
Multi F and Multi F MAX Indoor Unit Engineering Manual
Table 112: Allowable Indoor Unit to Multi F / Multi F MAX with LGRED Outdoor Unit Connections.
Indoor units Outdoor units
LMU18CHV LMU24CHV LMU30CHV LMU36CHV LMU480HV LMU540HV LMU600HV
Indoor Unit Nominal
Model Type Maximum No. of Connectable Indoor Units
Capacity (Btu/h)
2 3 4 4 8 8 8
9,000 O O O O O O O
ART COOL Mirror 12,000 O O O O O O O
18,000 - O O O O O O
9,000 O O O O O O O
ART COOL Gallery
12,000 O O O O O O O
7,000 O O O O O O O
9,000 O O O O O O O
12,000 O O O O O O O
Standard Wall Mounted
15,000 O O O O O O O
18,000 - O O O O O O
24,000 - O O O O O O
9,000 O O O O O O O
Ceiling Concealed Duct-
12,000 O O O O O O O
Low Static
18,000 - O O O O O O
Ceiling Concealed Duct- 24,000 - - O O O O O
High Static 36,000 - - - - O O O
7,000 O O O O O O O
9,000 O O O O O O O
Four-Way Ceiling Cassette
12,000 O O O O O O O
18,000 - O O O O O O
18,000 - O O O O O O
Vertical-Horizontal Air Handler 24,000 - - O O O O O
36,000 - - - - O O O
Due to our policy of continuous product innovation, some specifications may change without notification.
186 | APPLICATION GUIDELINES ©LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp.
MULTI F EQUIPMENT SELECTION PROCEDURE
MULTI F MAX
Table 114: Allowable Indoor Unit to Multi F / Multi F MAX with LGRED Outdoor Unit Connections.
Indoor units Outdoor units
LMU180HHV LMU240HHV LMU300HHV LMU360HHV LMU420HHV
Indoor Unit Nominal
Model Type Maximum No. of Connectable Indoor Units
Capacity (Btu/h)
2 3 4 5 6
9,000 O O O O O
ART COOL Mirror 12,000 O O O O O
18,000 - O O O O
9,000 O O O O O
ART COOL Gallery
12,000 O O O O O
7,000 O O O O O
9,000 O O O O O
12,000 O O O O O
Standard Wall Mounted
15,000 O O O O O
18,000 - O O O O
24,000 - O O O O
9,000 O O O O O
Ceiling Concealed Duct-
12,000 O O O O O
Low Static
18,000 - O O O O
Application Guidelines
Ceiling Concealed Duct- 24,000 - - O O O
High Static 36,000 - - - - O
7,000 O O O O O
9,000 O O O O O
Four-Way Ceiling Cassette
12,000 O O O O O
18,000 - O O O O
18,000 - O O O O
Vertical-Horizontal Air Handler 24,000 - - O O O
36,000 - - - - O
Due to our policy of continuous product innovation, some specifications may change without notification.
©LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp. APPLICATION GUIDELINES | 187
EQUIPMENT SELECTION PROCEDURE MULTI F
MULTI F MAX
Table 115: Multi F / Multi F MAX with LGRED Rated Outdoor Unit Capacity.
Outdoor Units
LMU180HHV LMU240HHV LMU300HHV LMU360HHV LMU420HHV
Rated Capacity Cooling 18,000 24,000 28,400 36,000 42,000
(Btu/h)* Heating 22,000 26,000 28,600 41,000 45,000
Connectable Minimum No. of Connectable IDUs 2 2 2 2 2
Indoor Maximum No. of Connectable IDUs 2 3 4 5 6
Units Maximum Capacity Index 24,000 33,000 40,000 48,000 56,000
Multi F and Multi F MAX Indoor Unit Engineering Manual
• The formula can be used to find individual indoor unit capacity for Multi F MAX / Multi F MAX with LGRED systems.
• A more accurate method to determine expected capacity would be to apply the outdoor unit’s corrected capacity instead of rated capacity.
Due to our policy of continuous product innovation, some specifications may change without notification.
188 | APPLICATION GUIDELINES ©LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp.
MULTI F EQUIPMENT SELECTION PROCEDURE
MULTI F MAX
A more accurate method to determine expected capacity would be to apply the outdoor unit’s corrected capacity instead of rated capacity.
Application Guidelines
Table 116: Multi F / Multi F with LGRED Outdoor Unit (Multiple Piping) to Indoor Unit Refrigerant Line Length Derates.
Piping Length (feet) Cooling Capacity (%) Heating Capacity (%)
7,000 Btu/h Indoor Unit Models
25.0 100.0 100.0
32.8 98.4 99.2
49.2 95.8 97.8
65.6 93.2 96.4
82.0 90.6 95.0
9,000 Btu/h Indoor Unit Models
25.0 100.0 100.0
32.8 98.0 99.0
49.2 94.8 97.4
65.6 91.6 95.8
82.0 88.4 94.2
12,000 Btu/h Indoor Unit Models
25.0 100.0 100.0
32.8 97.6 98.6
49.2 93.8 96.4
65.6 89.9 94.1
82.0 86.1 91.9
15,000 Btu/h Indoor Unit Models
25.0 100.0 100.0
32.8 97.2 98.2
49.2 93.0 95.4
65.6 88.8 92.6
82.0 84.6 89.8
18,000 Btu/h Indoor Unit Models
25.0 100.0 100.0
32.8 98.6 99.6
49.2 96.4 99.0
65.6 94.1 98.3
82.0 91.9 97.7
24,000 Btu/h Indoor Unit Models
25.0 100.0 100.0
32.8 98.2 99.2
49.2 95.4 98.0
65.6 92.4 96.6
82.0 89.6 95.4
Due to our policy of continuous product innovation, some specifications may change without notification.
©LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp. APPLICATION GUIDELINES | 189
EQUIPMENT SELECTION PROCEDURE MULTI F
MULTI F MAX
Table 117: Multi F MAX / Multi F MAX with LGRED Outdoor Unit to Branch Distribution Unit Refrigerant Line Length Derates.
Main Piping Length (feet) 16.4 32.8 49.2 65.6 82.0 98.4 114.8 131.2 147.6 164.0 180.4
Cooling Capacity (%) 100.0 98.8 97.3 95.8 94.3 92.8 91.3 89.8 88.3 86.8 85.3
Heating Capacity (%) 100.0 99.6 99.2 98.7 98.3 97.8 97.4 96.9 96.5 96.0 95.6
Figure 250: Multi F MAX / Multi F MAX with LGRED Outdoor Unit to Branch Distribution Unit Refrigerant Line Length Derate Chart.
100.0
Multi F and Multi F MAX Indoor Unit Engineering Manual
95.0 Heating
capacity
90.0
Capacity (%)
85.0 Cooling
capacity
80.0
75.0
70.0
0 32.8 65.6 98.4 131.2 164.0 180.4
Main piping length (ft.)
Table 118: Multi F MAX and Multi F MAX with LGRED Branch Distribution Unit to Indoor Unit Refrigerant Line Length Derates.
Piping Length (feet) Cooling Capacity (%) Heating Capacity (%)
7,000 Btu/h Indoor Unit Models
16.4 100.0 100.0
32.8 98.0 99.5
49.2 96.0 98.9
9,000 Btu/h Indoor Unit Models
16.4 100.0 100.0
32.8 97.5 98.8
49.2 95.0 97.5
12,000 Btu/h Indoor Unit Models
16.4 100.0 100.0
32.8 97.0 98.3
49.2 94.0 96.5
15,000 Btu/h Indoor Unit Models
16.4 100.0 100.0
32.8 97.2 98.2
49.2 93.0 95.4
18,000 Btu/h Indoor Unit Models
16.4 100.0 100.0
32.8 98.3 99.5
49.2 96.5 99.0
24,000 Btu/h Indoor Unit Models
16.4 100.0 100.0
32.8 97.8 99.2
49.2 95.5 98.4
36,000 Btu/h Indoor Unit Models
16.4 100.0 100.0
32.8 97.9 98.8
49.2 95.7 97.6
Due to our policy of continuous product innovation, some specifications may change without notification.
190 | APPLICATION GUIDELINES ©LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp.
MULTI F EQUIPMENT SELECTION PROCEDURE
MULTI F MAX
A=BxC Entering DB (ºF) 19.4 23.0 26.6 32.0 37.4 41.0 44.6
Derate factor 0.98 0.95 0.93 0.86 0.93 0.96 1.0
Where: 1
At 85% outdoor air relative humidity.
A = Integrated Heating Capacity. The frost accumulation factor does not account for effects of snow accumulation restricting airflow
B = Value found in the Capacity Table.
Application Guidelines
through the outdoor unit coil.
C = Correction Factor for Frost Accumulation Factor (from Table 101).
There will be temporary reduction in capacity when frost / ice accumulates on the outside surface of the outdoor unit heat exchanger. The level
of capacity reduction depends on a number of factors, for example, outdoor temperature (°F DB), relative humidity (RH), and the amount of frost
present.
Selecting the Best Location for the Branch Distribution (BD) Unit
Note:
Branch Distribution (BD) units are used only with Multi F MAX / Multi F MAX with LGRED systems to distribute the refrigerant from the out-
door unit to up to eight indoor units. Select location indoors that will meet the following conditions:
• Within allowable parameters for proper connection to the Multi F MAX / Multi F MAX with LGRED outdoor unit and indoor unit(s); refrigerant
piping and wire lengths must not exceed amounts specified by LG Electronics, U.S.A., Inc.
• Condensate drain piping is not required.
• Ensure there is enough space in the installation area for service purposes; install the refrigerant piping and electrical wiring system in an
easily accessible location.
• Level where there is enough strength to bear the weight of the BD unit.
• Do not install the BD unit in a location where it would be subjected to strong radiation heat from heat sources.
• Avoid an installation environment where the BD unit would be exposed to heat, water, steam, oil splattering or spray.
• Install the unit in a location where any sound it generates will not disturb occupants in the surrounding rooms.
• No obstacles to air circulation around the unit; keep proper distances from ceilings, doorways, floor, walls, etc.
• Where high-frequency electrical noise / electromagnetic waves will not affect operation. Maintain proper distances between the BD unit(s)
and electric wires, audio and visual appliances, breaker / circuit panels, etc.
Selecting the Best Location for the Outdoor Unit
DANGER
To avoid the possibility of fire, do not install the unit in an area where combustible gas will generate, flow, stagnate, or leak. Failure to
do so will cause serious bodily injury or death.
WARNING
Do not install the unit in a location where acidic solution and spray (sulfur) are often used as this will cause serious bodily injury or
death. Do not use the unit in environments where oil, steam, or sulfuric gas are present as this will cause serious bodily injury or death.
CAUTION
When deciding on a location to place the outdoor unit, be sure to choose an area where run-off from defrost will not accumulate and freeze
on sidewalks or driveways which will create unsafe conditions.
Select a location for installing the outdoor unit that will meet the following general conditions:
• A location strong enough to bear the weight of the outdoor unit.
• A location that allows for optimum air flow and is easily accessible for inspection, maintenance, and service.
Due to our policy of continuous product innovation, some specifications may change without notification.
192 | APPLICATION GUIDELINES ©LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp.
MULTI F PLACEMENT CONSIDERATIONS
MULTI F MAX
• Where it will not be subjected to direct thermal radiation from other heat sources, nor an area that would not expose the outdoor unit to
heat or steam like discharge from boiler stacks, chimneys, steam relief ports, other air conditioning units, kitchen vents, plumbing vents,
and other sources of extreme temperatures.
• Where high-frequency electrical noise / electromagnetic waves will not affect operation.
• Where operating sound from the unit will not disturb inhabitants of surrounding buildings.
• Where the unit will not be exposed to direct, strong winds.
Rooftop Installations
Application Guidelines
If the outdoor unit is installed on a roof structure, be sure to level the unit. Ensure the roof structure and anchoring method are adequate for
the unit location. Consult local codes regarding rooftop mounting.
Due to our policy of continuous product innovation, some specifications may change without notification.
©LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp. APPLICATION GUIDELINES | 193
PLACEMENT CONSIDERATIONS MULTI F
MULTI F MAX
Minimum
Minimum 4 3-15/16
Minimum
3-15/16)
parts gravel.
2-3/4~4 23/32
• The surface of the foundation must be finished with mortar with rounded edges,
and weatherproofed. Unit: Inch
Due to our policy of continuous product innovation, some specifications may change without notification.
194 | APPLICATION GUIDELINES ©LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp.
MULTI F PLACEMENT CONSIDERATIONS
MULTI F MAX
• The strength of the roof must be checked before installing the Protection Angle (25˚~55˚)
outdoor units.
• If the installation site is prone to high winds or earthquakes, when 51.5m
feet
installing on the wall or roof, securely anchor the mounting base
using a field-provided tie-down configuration approved by a local
professional engineer.
• The overall tie-down configuration must be approved by a local
professional engineer. Always refer to local code when using a
wind restraint system.
Lightening Protection
• To protect the outdoor unit from lightning, it must be placed within
the specified lightning safety zone.
Application Guidelines
Building Height (feet) 66 98 148 197
Protection Angle (˚) 55 45 35 25 Safe zone
• Power cable and communication cable must be installed five (5) Ground
feet away from lightning rod.
• A high-resistance ground system must be included to protect
against induced lightning or indirect strike. If the building does not include lightning protection, the outdoor unit
will be damaged from a lightening strike. Inform the customer of this
possibility in advance.
Outdoor Unit Service Access and Allowable Clearances
Appropriate airflow through the outdoor unit coil is critical for proper unit operation.
• Include enough space for airflow and for service access. If installing multiple outdoor units, avoid placing the units where the discharge
of one unit will blow into the inlet side of an adjacent unit.
• If an awning is built over the unit to prevent direct sunlight or rain exposure, make sure that the discharge air of the outdoor unit isn’t restricted.
• No obstacles to air circulation around the unit; keep proper distances from ceilings, fences, floor, walls, etc. (Install a fence to prevent pests
from damaging the unit or unauthorized individuals from accessing it.)
When installing the outdoor unit, consider service, inlet, and outlet, and minimum allowable space requirements as illustrated in the following
diagrams.
Minimum 11-13/16 Sun
roo Strong
f wind
Minimum 11-13/16
Minimum 11-13/16
Strong
wind
Fe
obsnce or Blown
tacl air
es Minimum 11-13/16
Minimum 19-1/16
Air inlet grille
Minimum 23-5/8 Unit: Inch
Ensure that the space at the back of the outdoor unit is a minimum of 11-13/16 inches, and If the outdoor unit discharge side faces a wall, include a minimum of 19-11/16 inches
include a minimum of 23-5/8 inches at the right side of the unit for service. between the outdoor unit and the wall. Install the outdoor unit so that the discharge port is
set at a right angle to the wind direction.
Due to our policy of continuous product innovation, some specifications may change without notification.
©LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp. APPLICATION GUIDELINES | 195
PLACEMENT CONSIDERATIONS MULTI F
MULTI F MAX
Min
" imu
/16 m1
11-13 1-1
3/16
u m "
inim 6"
M
1- 13/1
Min m1
imu imu
m2
3-1 Min
9/32
"
Obstacles above and on the air intake side. Obstacles above, on the air intake side,
and on both left and right sides
6"
11/1
Minimum 39-3/8"
m 19-
imu
Max
Minimum 39-3/8"
1/16"
9-1
m1
imu
Min
Min
imu
m1
1-1
3/16
1 3 /16" " 3/16
"
11- 1-1
um Min
imu u m1
Minim m2 Minim
3-1
9/32
"
6"
9- 11/1
m1
imu
Min
"
1/16
19-1
imum
Min
Due to our policy of continuous product innovation, some specifications may change without notification.
196 | APPLICATION GUIDELINES ©LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp.
MULTI F PLACEMENT CONSIDERATIONS
MULTI F MAX
Clearance Requirements when Different Obstacles are Present, continued. (Unit: Inch)
Where there
Where are are
there obstacles
obstacleson on
both suction
both suction Where
Wherethere
there are
are obstacles above,and
obstacles above, andononboth
both
and and discharge
discharge sides
sides (discharge
(discharge side
side obstacle
obstacle suctionand
suction and discharge
discharge sides
sides(discharge
(dischargeside
sideobstacle
obstacle
is higher
is higher thanthan
the the outdoor
outdoor unit).
unit). isishigher
higher than
than the
the outdoor
outdoor unit).
unit).
6"
11/1 16"
19- -11/ Table 122: Ratio among H, A, and L.
i m umm 19
ax mu
M axi
M L A
Minimum 39-3/8"
0 < L ≤ 1/2 H 29-1/32 inches
Minimum 39-3/8"
L≤H
1/2 H < L 39-3/8 inches
H<L Set Stand as: L ≤ H
If a stand is necessary, it must be contained (not open
frame) to prevent the discharge air from short cycling.
3/1 6"
1-1 "
m 1 /16 L
imu -13
Minm 11
imu L13/16"
Min 11-
/16" H um 6"
19-
11 inim 13/1
um /16" H M m 11-
inim -11
M 19 imu
m A Min
imu
Application Guidelines
Min
A
Where there are obstacles on both suction Where there are obstacles above, and on both
and discharge sides (discharge side obstacle suction and discharge sides (discharge side obstacle
is lower than the outdoor unit). is lower than the outdoor unit).
6"
11/1
m 19-
Minimum 39-3/8"
imu
Max
“L” must be lower
than “H”. If a stand is
necessary, it must be
H contained (not open
/16" frame) to prevent the
13 "
11- 3/16 discharge air from
im um 1 1-1
Min i mum short cycling.
6" Min
9-11/1
m1
imu /8"
Min L 9-3
u m3
Minim
Series installation
Side-by-side series installation.
6"
1-13/1
m1
imu
Min
/4" Minimum 24"
8-3
u m7
Minim
Minimum 24" 12"
Minimum 23-19/32" um
M inim
Minimum 39-3/8"
Due to our policy of continuous product innovation, some specifications may change without notification.
©LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp. APPLICATION GUIDELINES | 197
REFRIGERANT PIPING
DESIGN & LAYOUT
BEST PRACTICES
“Design Guideline Summary” on page 199
“Creating a Balanced System” on page 203
“Condensate Drain Piping” on page 204
MULTI F REFRIGERANT PIPING DESIGN
MULTI F MAX Design Guideline Summary
The following are examples of manual pipe size calculations. Designers are highly encouraged to use LATS for Multi F systems.
One of the most critical elements of multi-zone systems is the refrigerant piping. The following pages list pipe length limits that must be
followed in the design of Multi F and Multi F MAX refrigerant pipe systems:
Multi F System
Example: LMU36CHV outdoor unit with four (4)
indoor units connected.
ODU: Outdoor Unit.
IDU: Indoor Unit.
A, B, C, D: Pipes from Outdoor Unit to Indoor Unit.
A
B
Max. 49.2 feet Max. 24.6 feet
Due to our policy of continuous product innovation, some specifications may change without notification.
©LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp. DESIGN & PRACTICES | 199
REFRIGERANT PIPING DESIGN MULTI F
Design Guideline Summary MULTI F MAX
The following are examples of manual pipe size calculations. Designers are highly encouraged to use LATS for Multi F systems.
IDU
h3 ≤ 32.8 feet
ΣA: Main Pipe. B IDU
ΣB: Branch Pipe (Branch Distribution Unit[s] to IDU
Indoor Unit[s]). h4 ≤ 49.2 feet
B
IDU
h2 ≤ 49.2 feet
A
BDU B
IDU
B
IDU
h1 ≤ 98.4 feet
B
IDU
Table 125: Multi F MAX Outdoor Unit Refrigerant Piping System Limitations. Table 126: Multi F MAX Piping Sizes.
Piping Main
Total piping length (ΣA + ΣB) ≤475.7 feet Pipe A Branch Pipe B
Main pipe (Outdoor Unit to Minimum 10 feet (inch)
Pipe Length Branch Distribution Units: ΣA) Maximum ≤180.4 feet Liquid Ø3/8 Depends on the size
(ELF = Equivalent
Length of pipe in Feet) Total branch piping length (ΣB) ≤295.3 feet Gas Ø3/4 of the indoor unit piping
Branch pipe (Branch Distribu- Minimum 10 feet
tion Units to Indoor Units: B) Maximum ≤49.2 feet
Elevation Differential If outdoor unit is above or below indoor unit (h1) ≤98.4 feet
(All Elevation Between the farthest two indoor units (h2) ≤49.2 feet
Limitations are Between branch distribution unit and farthest
Measured in Actual ≤32.8 feet
connected indoor unit(s) (h3)
Feet) Between branch distribution units (h4) ≤49.2 feet
Due to our policy of continuous product innovation, some specifications may change without notification.
200 | DESIGN & PRACTICES ©LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp.
MULTI F REFRIGERANT PIPING DESIGN
MULTI F MAX Design Guideline Summary
The following are examples of manual pipe size calculations. Designers are highly encouraged to use LATS for Multi F systems.
Table 127:Multi F with LGRED Outdoor Unit Refrigerant Piping System Limitations.
Minimum Length Maximum Piping Length to Maximum Total Piping Maximum Height Difference Maximum Height Difference
Outdoor Unit for Each Pipe Each Indoor Unit (ft.) Length for Each System (Max. [ft.]) (Max. [ft.])
(ft.) A B C D (ft.) Outdoor Unit ~ Indoor Unit Indoor Unit ~ Indoor Unit
LMU180HHV 10 82 82 - - 164 49.2 24.6
LMU240HHV 10 82 82 82 - 246.1 49.2 24.6
LMU300HHV 10 82 82 82 82 246.1 49.2 24.6
Multi F MAX with LGRED System with One Branch Distribution Unit
IDU
Due to our policy of continuous product innovation, some specifications may change without notification.
©LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp. DESIGN & PRACTICES | 201
REFRIGERANT PIPING DESIGN MULTI F
Design Guideline Summary MULTI F MAX
The following are examples of manual pipe size calculations. Designers are highly encouraged to use LATS for Multi F systems.
Multi F MAX with LGRED System with Two Branch Distribution Units
A
ΣA: Main Pipe.
h3 ≤ 32.8 feet
B IDU
ΣB: Branch Pipe (Branch Distribution Unit[s] to
IDU
Indoor Unit[s]). h4 ≤ 49.2 feet
B
BDU IDU
h2 ≤ 49.2 feet
A
B
IDU
B
h1 ≤ 98.4 feet
IDU
Table 128: Multi F MAX with LGRED Outdoor Unit Refrigerant Piping System Limitations. Table 129: Multi F MAX with LGRED Piping Sizes.
Piping Main
Total piping length (ΣA + ΣB) ≤475.7 feet Pipe A Branch Pipe B
Main pipe (Outdoor Unit to Minimum 10 feet (inch)
Pipe Length Branch Distribution Units: ΣA) Maximum ≤180.4 feet Liquid Ø3/8 Depends on the size
(ELF = Equivalent
Length of pipe in Feet) Total branch piping length (ΣB) ≤295.3 feet Gas Ø3/4 of the indoor unit piping
Branch pipe (Branch Distribu- Minimum 10 feet
tion Units to Indoor Units: B) Maximum ≤49.2 feet
Elevation Differential If outdoor unit is above or below indoor unit (h1) ≤98.4 feet
(All Elevation Between the farthest two indoor units (h2) ≤49.2 feet
Limitations are Between branch distribution unit and farthest
Measured in Actual ≤32.8 feet
connected indoor unit(s) (h3)
Feet) Between branch distribution units (h4) ≤49.2 feet
Due to our policy of continuous product innovation, some specifications may change without notification.
202 | DESIGN & PRACTICES ©LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp.
MULTI F REFRIGERANT PIPING DESIGN
MULTI F MAX Creating a Balanced System / Manual Layout Procedure
The designer must avoid creating excessive pressure drop. When liquid refrigerant is subjected to excessive pressure drop, liquid re-
Any field changes, such as re-routing, shortening or lengthening a pipe segment, adding or eliminating elbows and/or fittings, re-sizing, adding,
or eliminating indoor units, changing the mounting height or moving the location of a device or fitting during installation must be done with cau-
tion and ALWAYS VERIFIED in LATS HVAC SOFTWARE before supplies are purchased or installed. Doing so ensures profitable installation,
eliminates rework, and ensures easier system commissioning.
Due to our policy of continuous product innovation, some specifications may change without notification.
©LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp. DESIGN & PRACTICES | 203
INSTALLATION & LAYOUT BEST PRACTICES MULTI F
Condensate Drain Piping MULTI F MAX
Figure 255:Diagram of an Indoor Unit with a Gravity Drain. Figure 256:Diagram of an Indoor Unit with a Drain Pump.
Metal clamp
≤Max. 31-1/2 in. (18MBh Cassette)
≤11-13/16 in.
Flexible drain hose
≤Max. 27-1/2 in. (Ducted and
Insulation
PVC elbow
PVC
9/12MBh Cassette)
1/50~1/100 slope
PVC
Drain pan Insulation Flexible hose
Drain pump
Due to our policy of continuous product innovation, some specifications may change without notification.
204 | DESIGN & PRACTICES ©LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp.
ELECTRICAL
CONNECTIONS
“General Information” on page 206
“Power Wiring (208-230V) and Communications Cable
Details” on page 209
“Remote Controller Connections” on page 219
“Indoor Unit Group Control” on page 220
ELECTRICAL CONNECTIONS MULTI F
General Information MULTI F MAX
• All power (line voltage) wiring and communication cable installation must be performed by trained service providers working in accordance
with all local, state, and National Electrical Code (NEC) / UL / ETL federal regulations related to electrical equipment and wiring, and following
the manufacturer product diagrams, requirements, and instructions in this manual. Electric shock can cause physical injury or death.
• Be sure that main power to the unit is completely off before proceeding. Follow all safety and warning information outlined at the beginning of
this manual. Failure to do so will cause electric shock and bodily injury.
• Install a main shutoff switch or circuit breaker that interrupts all power sources simultaneously (circuit breaker must be resistant to electro-
magnetic currents). Be sure that the circuit breaker or some other emergency power cutoff device is in place before any power wiring is done
to the system. Failure to do so will cause bodily injury or death.
Multi F and Multi F MAX Indoor Unit Engineering Manual
• Never touch any power lines or live cables before all power is cutoff to the system. To do so will cause bodily injury or death.
• Power wiring and communication cable sizes must comply with all applicable federal, state, and local codes. Undersized wiring will lead to
unacceptable voltage at the unit and will cause a fire, which will cause bodily injury or death.
• Properly ground the outdoor unit, indoor units, and branch distribution units. Ground wiring must always be installed by a trained technician.
Ground wiring is required to prevent accidental electrical shock during current leakage, which will cause bodily injury or death.
• Verify that the branch switch and circuit breaker are set to OFF before installing the wiring system. Electric shock can cause physical injury
or death.
• Install appropriately sized breakers / fuses / overcurrent protection switches and wiring in accordance with local, state, and NEC regulations
related to electrical equipment and wiring, and following the instructions in this manual. Generated overcurrent will include some amount of
direct current. Using an oversized breaker or fuse will result in electric shock, physical injury or death.
• Do not connect ground wire to refrigerant, gas, sewage, or water piping; to lightning rods; to telephone ground wiring; or to the building
plumbing system. Failure to properly provide a NEC-approved earth ground can result in electric shock, fire, physical injury or death.
• Consider ambient conditions (temperature, direct sunlight, inclement weather, etc.) when selecting, installing, and connecting the power wiring.
• Properly ground the outdoor unit, indoor units, and branch distribution units. Ground wiring must always be installed by a trained technician.
Improperly grounded wire can cause communication problems from electrical noise, and motor current leakage.
• Install appropriately sized breakers / fuses / overcurrent protection switches and wiring in accordance with local, state, and NEC regulations
related to electrical equipment and wiring, and following the instructions in this manual. Generated overcurrent will include some amount of
direct current. Using an oversized breaker or fuse will result in equipment malfunction and property damage.
• Do not connect ground wire to refrigerant, gas, or water piping; to lightning rods; to telephone ground wiring; or to the building plumbing
system. Failure to properly provide a NEC-approved earth ground can result in property damage and equipment malfunction.
• Do not operate the air conditioning system until the refrigerant piping installation is complete. Operating the system before refrigerant
piping is finalized will damage the compressor.
Wiring Connections
distribution unit(s) must be a minimum of 14 AWG, four (4) conductor, stranded,
shielded or unshielded (if shielded, it must be grounded to the chassis of the outdoor Wiring Lengths GREATER THAN 130 Feet. 1/8"
6" ±
unit only), and must comply with applicable local and national codes. 7/1
• Communication / connection (power) cable from the branch distribution unit(s) to 1(L1)
Two-Conductor
the indoor units for lengths up to 130 feet must use a minimum of 14 AWG, four (4) Power Cable
2(L2)
conductor, stranded, shielded or unshielded (if shielded, it must be grounded to the
chassis of the outdoor unit only), and must comply with applicable local and national 13/
16"
codes. Separate At Least
Two (2) Inches "
• When the communication / connection (power) wires between the branch distribution 1/8
/ 1 6" ±
unit and indoor unit is GREATER THAN 130 feet, use: 7
• A two (2) conductor wire for power (for each indoor unit). Two-Conductor 3
• A two (2) conductor wire for communication / ground (for each indoor unit). Communication / GN/YL
• Separate the power AT LEAST two (2) inches away from the communication / Ground Cable
13/
ground wire (for each indoor unit). GN/YL = (Ground, Yellow)
16"
• All wiring is still minimum 14 gauge, stranded, shielded, or unshielded as cited
above (for each indoor unit).
• Insulation material as required by local code.
• Rated for continuous exposure of temperatures up to 140°F.
• Firmly attach the cable; provide slack but secure in a way to prevent external forces from being imparted on the terminal block.
• Wiring must be completed without splices.
• Use a conduit for the communications / connection (power) cable from the outdoor unit to the indoor units and branch distribution unit(s).
Electrical interference my cause product malfunction.
• Never ground the shield of the communications cable to the indoor unit frame or other grounded entities of the building. Ground the com-
munications cable shield only at the outdoor unit. Improperly grounding this cable can cause communications errors.
• The communications / connection (power) cable from the outdoor unit to the indoor units / branch distribution unit(s) must be separated and
isolated from power wiring to the outdoor unit, computers, radio and television broadcasting facilities, as well as medical imaging equipment.
Electrical interference my cause product malfunction.
Due to our policy of continuous product innovation, some specifications may change without notification.
©LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp. WIRING CONNECTIONS | 207
ELECTRICAL CONNECTIONS MULTI F
General Information MULTI F MAX
Figure 260:Typical Multi F System General Power / Communications Figure 261:Typical Multi F MAX System General Power / Communica-
System Schematic When Wiring is Less Than 130 Feet. tions System Schematic When Wiring is Less Than 130 Feet.
Indoor Units
Indoor Unit
Power Supply
Power Supply
Multi F and Multi F MAX Indoor Unit Engineering Manual
Ground Wiring
Outdoor Unit
Figure 262:Schematic of a Multi F System When the Wiring is GREATER THAN 130 Feet.
Power Flow: L → N
Communication Flow: Comm → N 3 (Communications)
1(L1) (Power, L)
2(L2) (Neutral, N) Power
G (Ground)
Supply At Least Two (2) Inches
Figure 263:Schematic of a Multi F MAX with LGRED System When the Wiring is GREATER THAN 130 Feet.
1(L1) (Power, L)
2(L2) (Neutral, N)
Power
At Least Two (2) Inches
G (Ground) Supply
3 (Communications)
Diagram is an example of communication and
power cables when the wiring is GREATER THAN GREATER THAN 130 feet: Must Separate Communications and Ground (G) Cable
130 feet. Terminals may be labeled differently depending on the model. from the Power (1[L1]) and Neutral (2[L2]) Cable at Least Two (2) Inches for Each
Outdoor and Indoor Unit appearances may vary depending on the model. Indoor Unit.
• Secure the separate wires in the control box panel using zip ties.
• Secure wiring with accessory clamps so that it does not touch piping.
• Use a conduit for the cable.
• Outside the unit, make sure the communications cable / power wiring are separately shielded, otherwise, the outdoor unit operation will be
affected by electrical noise and will malfunction or fail.
• For details on the Multi F with LG RED and Multi F MAX with LG RED units, refer to the engineering manuals on www.lghvac.com.
Due to our policy of continuous product innovation, some specifications may change without notification.
208 | WIRING CONNECTIONS ©LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp.
MULTI F ELECTRICAL CONNECTIONS
MULTI F MAX Power Wiring (208-230V) and Communications Cable Details
Figure 264: Multi F LMU18CHV System Power Wiring and Communications Cable.
L1 L2
Power Supply
Main Switch
G Outdoor Unit
L1 L2
Circuit Breaker G Outdoor Unit Terminal Block
Wiring Connections
POWER WIRING 1(L1) 2(L2) 3 1(L1) 2(L2) 3
COMMUNICATION CABLE Indoor Unit Terminal Block Indoor Unit Terminal Block
Unit A Unit B
• All field-supplied wiring, components, and materials must follow national, state, and local codes and requirements. Electric shock can cause physical
injury or death.
• Use only stranded, shielded or unshielded copper communications / power wiring from the outdoor unit to the indoor units. If shielded, wiring must be
grounded to the chassis at the outdoor unit only. Improper wiring will result in fire, electric shock, physical injury or death.
• Ground wiring is required to prevent accidental electrical shock during current leakage, communication problems from electrical noise, and motor cur-
rent leakage. Do not connect the ground line to the pipes. Improper wiring will result in fire, electric shock, physical injury or death.
• Install a main shutoff switch or circuit breaker that interrupts all power sources simultaneously. Electric shock can cause physical injury or death.
• Wiring cable size must comply with applicable national, state, and local codes. Improper wiring will result in fire, electric shock, physical injury or death.
• For Multi F with LGRED, refer to Multi F & Multi F MAX with LGRED ODU engineering manual.
• Ground wiring is required to prevent communication problems from electrical noise, and motor current leakage. Failure to provide proper ground wiring
can result in property damage and equipment malfunction.
• All field-supplied wiring, components, and materials must follow national, state, and local codes and requirements. Failure to install proper electrical
components can result in property damage and equipment malfunction.
• Use only stranded, shielded or unshielded copper communications / power wiring from the outdoor unit to the indoor units. If shielded, wiring must be
grounded to the chassis at the outdoor unit only. Failure to install proper wiring can result in property damage and equipment malfunction.
• Install a main shutoff switch or circuit breaker that interrupts all power sources simultaneously. Failure to install proper electric components can result in
property damage and equipment malfunction.
• Wiring cable size must comply with applicable national, state, and local codes. Improper wiring can result in property damage and equipment malfunction.
Due to our policy of continuous product innovation, some specifications may change without notification.
©LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp. WIRING CONNECTIONS | 209
ELECTRICAL CONNECTIONS MULTI F
Power Wiring (208-230V) and Communications Cable Details MULTI F MAX
G
Outdoor Unit
Multi F and Multi F MAX Indoor Unit Engineering Manual
L1 L2
Circuit Breaker G Outdoor Unit Terminal Block
POWER WIRING
COMMUNICATIONS CABLE
• All field-supplied wiring, components, and materials must follow national, state, and local codes and requirements. Electric shock can cause physical
injury or death.
• Use only stranded, shielded or unshielded copper communications / power wiring from the outdoor unit to the indoor units. If shielded, wiring must be
grounded to the chassis at the outdoor unit only. Improper wiring will result in fire, electric shock, physical injury or death.
• Ground wiring is required to prevent accidental electrical shock during current leakage, communication problems from electrical noise, and motor cur-
rent leakage. Do not connect the ground line to the pipes. Improper wiring will result in fire, electric shock, physical injury or death.
• Install a main shutoff switch or circuit breaker that interrupts all power sources simultaneously. Electric shock can cause physical injury or death.
• Wiring cable size must comply with applicable national, state, and local codes. Improper wiring will result in fire, electric shock, physical injury or death.
• For Multi F with LGRED, refer to Multi F & Multi F MAX with LGRED ODU engineering manual.
• Ground wiring is required to prevent communication problems from electrical noise, and motor current leakage. Failure to provide proper ground wiring
can result in property damage and equipment malfunction.
• All field-supplied wiring, components, and materials must follow national, state, and local codes and requirements. Failure to install proper electrical
components can result in property damage and equipment malfunction.
• Use only stranded, shielded or unshielded copper communications / power wiring from the outdoor unit to the indoor units. If shielded, wiring must be
grounded to the chassis at the outdoor unit only. Failure to install proper wiring can result in property damage and equipment malfunction.
• Install a main shutoff switch or circuit breaker that interrupts all power sources simultaneously. Failure to install proper electric components can result in
property damage and equipment malfunction.
• Wiring cable size must comply with applicable national, state, and local codes. Improper wiring can result in property damage and equipment malfunction.
Due to our policy of continuous product innovation, some specifications may change without notification.
210 | WIRING CONNECTIONS ©LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp.
MULTI F ELECTRICAL CONNECTIONS
MULTI F MAX Power Wiring (208-230V) and Communications Cable Details
Figure 266:Multi F LMU30CHV and LMU36CHV System Power Wiring and Communications Cable.
L1 L2
Power Supply
Main Switch
G
Outdoor Unit
Wiring Connections
1(L1) 2(L2) 3 1(L1) 2(L2) 3 1(L1) 2(L2) 3 1(L1) 2(L2) 3
Indoor Unit Terminal Block Indoor Unit Terminal Block Indoor Unit Terminal Block Indoor Unit Terminal Block
POWER WIRING
COMMUNICATIONS CABLE
• All field-supplied wiring, components, and materials must follow national, state, and local codes and requirements. Electric shock can cause physical
injury or death.
• Use only stranded, shielded or unshielded copper communications / power wiring from the outdoor unit to the indoor units. If shielded, wiring must be
grounded to the chassis at the outdoor unit only. Improper wiring will result in fire, electric shock, physical injury or death.
• Ground wiring is required to prevent accidental electrical shock during current leakage, communication problems from electrical noise, and motor cur-
rent leakage. Do not connect the ground line to the pipes. Improper wiring will result in fire, electric shock, physical injury or death.
• Install a main shutoff switch or circuit breaker that interrupts all power sources simultaneously. Electric shock can cause physical injury or death.
• Wiring cable size must comply with applicable national, state, and local codes. Improper wiring will result in fire, electric shock, physical injury or death.
• For Multi F with LGRED, refer to Multi F & Multi F MAX with LGRED ODU engineering manual.
• Ground wiring is required to prevent communication problems from electrical noise, and motor current leakage. Failure to provide proper ground wiring
can result in property damage and equipment malfunction.
• All field-supplied wiring, components, and materials must follow national, state, and local codes and requirements. Failure to install proper electrical
components can result in property damage and equipment malfunction.
• Use only stranded, shielded or unshielded copper communications / power wiring from the outdoor unit to the indoor units. If shielded, wiring must be
grounded to the chassis at the outdoor unit only. Failure to install proper wiring can result in property damage and equipment malfunction.
• Install a main shutoff switch or circuit breaker that interrupts all power sources simultaneously. Failure to install proper electric components can result in
property damage and equipment malfunction.
• Wiring cable size must comply with applicable national, state, and local codes. Improper wiring can result in property damage and equipment malfunction.
Due to our policy of continuous product innovation, some specifications may change without notification.
©LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp. WIRING CONNECTIONS | 211
ELECTRICAL CONNECTIONS MULTI F
Power Wiring (208-230V) and Communications Cable Details MULTI F MAX
Figure 267:Multi F MAX LMU480HV and LMU540HV System Power Wiring and Communications Cable.
L N
Power Supply
Main Switch
Outdoor unit
(Including Ground)
POWER WIRING
COMMUNICATIONS CABLE
• All field-supplied wiring, components, and materials must follow national, state, and local codes and requirements. Electric shock can cause physical
injury or death.
• Use only stranded, shielded or unshielded copper communications / power wiring from the outdoor unit to the indoor units. If shielded, wiring must be
grounded to the chassis at the outdoor unit only. Improper wiring will result in fire, electric shock, physical injury or death.
• Ground wiring is required to prevent accidental electrical shock during current leakage, communication problems from electrical noise, and motor cur-
rent leakage. Do not connect the ground line to the pipes. Improper wiring will result in fire, electric shock, physical injury or death.
• Install a main shutoff switch or circuit breaker that interrupts all power sources simultaneously. Electric shock can cause physical injury or death.
• Wiring cable size must comply with applicable national, state, and local codes. Improper wiring will result in fire, electric shock, physical injury or death.
• For Multi F MAX with LGRED, refer to Multi F & Multi F MAX with LGRED ODU engineering manual.
• Ground wiring is required to prevent communication problems from electrical noise, and motor current leakage. Failure to provide proper ground wiring
can result in property damage and equipment malfunction.
• All field-supplied wiring, components, and materials must follow national, state, and local codes and requirements. Failure to install proper electrical
components can result in property damage and equipment malfunction.
• Use only stranded, shielded or unshielded copper communications / power wiring from the outdoor unit to the indoor units. If shielded, wiring must be
grounded to the chassis at the outdoor unit only. Failure to install proper wiring can result in property damage and equipment malfunction.
• Install a main shutoff switch or circuit breaker that interrupts all power sources simultaneously. Failure to install proper electric components can result in
property damage and equipment malfunction.
• Wiring cable size must comply with applicable national, state, and local codes. Improper wiring can result in property damage and equipment malfunction.
Due to our policy of continuous product innovation, some specifications may change without notification.
212 | WIRING CONNECTIONS ©LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp.
MULTI F ELECTRICAL CONNECTIONS
MULTI F MAX Power Wiring (208-230V) and Communications Cable Details
Figure 268:Multi F MAX LMU600HV System Power Wiring and Communications Cable.
L N
Power Supply
Main Switch
Outdoor unit
L N
Circuit Breaker G
L1 L2 1( L1 ) 2 (L2 ) 3 (A ) 3 (B)
Three-wire Power Wiring Fuse
(Including Ground)
Wiring Connections
Branch Distribution Unit (A) Branch Distribution Unit (B)
POWER WIRING
COMMUNICATIONS CABLE
• All field-supplied wiring, components, and materials must follow national, state, and local codes and requirements. Electric shock can cause physical
injury or death.
• Use only stranded, shielded or unshielded copper communications / power wiring from the outdoor unit to the indoor units. If shielded, wiring must be
grounded to the chassis at the outdoor unit only. Improper wiring will result in fire, electric shock, physical injury or death.
• Ground wiring is required to prevent accidental electrical shock during current leakage, communication problems from electrical noise, and motor cur-
rent leakage. Do not connect the ground line to the pipes. Improper wiring will result in fire, electric shock, physical injury or death.
• Install a main shutoff switch or circuit breaker that interrupts all power sources simultaneously. Electric shock can cause physical injury or death.
• Wiring cable size must comply with applicable national, state, and local codes. Improper wiring will result in fire, electric shock, physical injury or death.
• For Multi F MAX with LGRED, refer to Multi F & Multi F MAX with LGRED ODU engineering manual.
• Ground wiring is required to prevent communication problems from electrical noise, and motor current leakage. Failure to provide proper ground wiring
can result in property damage and equipment malfunction.
• All field-supplied wiring, components, and materials must follow national, state, and local codes and requirements. Failure to install proper electrical
components can result in property damage and equipment malfunction.
• Use only stranded, shielded or unshielded copper communications / power wiring from the outdoor unit to the indoor units. If shielded, wiring must be
grounded to the chassis at the outdoor unit only. Failure to install proper wiring can result in property damage and equipment malfunction.
• Install a main shutoff switch or circuit breaker that interrupts all power sources simultaneously. Failure to install proper electric components can result in
property damage and equipment malfunction.
• Wiring cable size must comply with applicable national, state, and local codes. Improper wiring can result in property damage and equipment malfunction.
Due to our policy of continuous product innovation, some specifications may change without notification.
©LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp. WIRING CONNECTIONS | 213
ELECTRICAL CONNECTIONS MULTI F
Power Wiring (208-230V) and Communications Cable Details MULTI F MAX
Figure 269:Multi F with LGRED System General Power / Communications System Schematic.
Indoor Units
Power Supply
Multi F and Multi F MAX Indoor Unit Engineering Manual
Circuit Breaker
Ground Wiring
Outdoor Unit
Figure 270:Multi F MAX with LGRED System General Power / Communications System Schematic. Indoor Unit
Power Supply
Circuit Breaker
Ground Wiring
Outdoor Unit
• Secure the separate wires in the control box panel using zip ties.
• Secure wiring with accessory clamps so that it does not touch the piping.
• Use a conduit for the communications cable / power wiring from the outdoor unit to the indoor / branch distribution units.
• Make sure the communications cable / power wiring from the outdoor units to the indoor / branch distribution units, and the power wiring to the
outdoor unit are separate, otherwise, the outdoor unit operation will be affected by electrical noise and will malfunction or fail.
Due to our policy of continuous product innovation, some specifications may change without notification.
214 | WIRING CONNECTIONS ©LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp.
MULTI F ELECTRICAL CONNECTIONS
MULTI F MAX Power Wiring (208-230V) and Communications Cable Details
Figure 271:Multi F with LGRED LMU180HHV System Power Wiring and Communications Cable Connections.
L1 L2
Power Supply
Main Switch
G Outdoor Unit
Wiring Connections
(Including Ground)
COMMUNICATION CABLE Indoor Unit Terminal Block Indoor Unit Terminal Block
Unit A Unit B
• All field-supplied wiring, components, sizes, and materials must comply with all applicable national, state, and local codes and requirements.
Improper wiring will result in fire, electric shock, physical injury or death.
• Ground wiring is required to prevent accidental electrical shock during current leakage, communication problems from electrical noise, and
motor current leakage. Do not connect the ground line to the pipes. There is a risk of fire, electric shock, explosion, physical injury or
death.
• Install a main shutoff switch or circuit breaker that interrupts all power sources simultaneously. There is a risk of fire, electric shock, explosion,
physical injury or death.
• All field-supplied wiring, components, sizes, and materials must comply with all applicable national, state, and local codes and requirements.
Failure to install proper electrical components can result in property damage and equipment malfunction.
• Ground wiring is required to prevent communication problems from electrical noise, and motor current leakage. Failure to provide proper
ground wiring can result in property damage and equipment malfunction.
• Install a main shutoff switch or circuit breaker that interrupts all power sources simultaneously. Failure to install proper electric components
will result in property damage and equipment malfunction.
• Maintain polarity throughout the communication network. The system will malfunction if not properly wired.
Due to our policy of continuous product innovation, some specifications may change without notification.
©LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp. WIRING CONNECTIONS | 215
ELECTRICAL CONNECTIONS MULTI F
Power Wiring (208-230V) and Communications Cable Details MULTI F MAX
Figure 272:Multi F with LGRED LMU240HHV System Power Wiring and Communications Cable Connections.
L1 L2
Power Supply
Main Switch
G Outdoor Unit
Multi F and Multi F MAX Indoor Unit Engineering Manual
• All field-supplied wiring, components, sizes, and materials must comply with all applicable national, state, and local codes and requirements.
Improper wiring will result in fire, electric shock, physical injury or death.
• Ground wiring is required to prevent accidental electrical shock during current leakage, communication problems from electrical noise, and
motor current leakage. Do not connect the ground line to the pipes. There is a risk of fire, electric shock, explosion, physical injury or
death.
• Install a main shutoff switch or circuit breaker that interrupts all power sources simultaneously. There is a risk of fire, electric shock, explosion,
physical injury or death.
• All field-supplied wiring, components, sizes, and materials must comply with all applicable national, state, and local codes and requirements.
Failure to install proper electrical components can result in property damage and equipment malfunction.
• Ground wiring is required to prevent communication problems from electrical noise, and motor current leakage. Failure to provide proper
ground wiring can result in property damage and equipment malfunction.
• Install a main shutoff switch or circuit breaker that interrupts all power sources simultaneously. Failure to install proper electric components
will result in property damage and equipment malfunction.
• Maintain polarity throughout the communication network. The system will malfunction if not properly wired.
Due to our policy of continuous product innovation, some specifications may change without notification.
216 | WIRING CONNECTIONS ©LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp.
MULTI F ELECTRICAL CONNECTIONS
MULTI F MAX Power Wiring (208-230V) and Communications Cable Details
Figure 273:Multi F with LGRED LMU300HHV System Power Wiring and Communications Cable Connections.
L1 L2
Power Supply
Main Switch
G Outdoor Unit
Wiring Connections
POWER WIRING 1(L1) 2(L2) 3 1(L1) 2(L2) 3 1(L1) 2(L2) 3 1(L1) 2(L2) 3
COMMUNICATION CABLE Indoor Unit Terminal Block Indoor Unit Terminal Block Indoor Unit Terminal Block Indoor Unit Terminal Block
• All field-supplied wiring, components, sizes, and materials must comply with all applicable national, state, and local codes and requirements.
Improper wiring will result in fire, electric shock, physical injury or death.
• Ground wiring is required to prevent accidental electrical shock during current leakage, communication problems from electrical noise, and
motor current leakage. Do not connect the ground line to the pipes. There is a risk of fire, electric shock, explosion, physical injury or
death.
• Install a main shutoff switch or circuit breaker that interrupts all power sources simultaneously. There is a risk of fire, electric shock, explosion,
physical injury or death.
• All field-supplied wiring, components, sizes, and materials must comply with all applicable national, state, and local codes and requirements.
Failure to install proper electrical components can result in property damage and equipment malfunction.
• Ground wiring is required to prevent communication problems from electrical noise, and motor current leakage. Failure to provide proper
ground wiring can result in property damage and equipment malfunction.
• Install a main shutoff switch or circuit breaker that interrupts all power sources simultaneously. Failure to install proper electric components
will result in property damage and equipment malfunction.
• Maintain polarity throughout the communication network. The system will malfunction if not properly wired.
Due to our policy of continuous product innovation, some specifications may change without notification.
©LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp. WIRING CONNECTIONS | 217
ELECTRICAL CONNECTIONS MULTI F
Power Wiring (208-230V) and Communications Cable Details MULTI F MAX
Figure 274:Multi F MAX with LGRED LMU360HHV and LMU420HHV System Power Wiring and Communications Cable Connections.
L N
Power Supply
Main Switch
Outdoor Unit
L N
Multi F and Multi F MAX Indoor Unit Engineering Manual
Circuit Breaker G
L1 L2 1(L1) 2(L2) 3(A) 3(B)
Three-wire Power Wiring Fuse
(Including Ground)
POWER WIRING
COMMUNICATIONS CABLE
• All field-supplied wiring, components, sizes, and materials must comply with all applicable national, state, and local codes and requirements.
Improper wiring will result in fire, electric shock, physical injury or death.
• Ground wiring is required to prevent accidental electrical shock during current leakage, communication problems from electrical noise, and
motor current leakage. Do not connect the ground line to the pipes. There is a risk of fire, electric shock, explosion, physical injury or
death.
• Install a main shutoff switch or circuit breaker that interrupts all power sources simultaneously. There is a risk of fire, electric shock, explosion,
physical injury or death.
• All field-supplied wiring, components, sizes, and materials must comply with all applicable national, state, and local codes and requirements.
Failure to install proper electrical components can result in property damage and equipment malfunction.
• Ground wiring is required to prevent communication problems from electrical noise, and motor current leakage. Failure to provide proper
ground wiring can result in property damage and equipment malfunction.
• Install a main shutoff switch or circuit breaker that interrupts all power sources simultaneously. Failure to install proper electric components
will result in property damage and equipment malfunction.
• Maintain polarity throughout the communication network. The system will malfunction if not properly wired.
Due to our policy of continuous product innovation, some specifications may change without notification.
218 | WIRING CONNECTIONS ©LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp.
MULTI F ELECTRICAL CONNECTIONS
MULTI F MAX Remote Controller Connections
Figure 275:One Example of Indoor Unit to Zone Controller Connection. Figure 276:Another Example of Indoor Unit to Zone Controller
Connection.
YL
Signal
12VDC
Common
RD
Wiring Connections
BK
4 5 6
Indoor Unit
CN-REMO CN-REMO
BK RD YL
13 14 15
BACnet Common
BACnet+
Not used
Not used
Not used
YL RDBK
Front Back
Due to our policy of continuous product innovation, some specifications may change without notification.
©LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp. WIRING CONNECTIONS | 219
ELECTRICAL CONNECTIONS MULTI F
Indoor Unit Group Control MULTI F MAX
Between Multiple Indoor Units Operating as a Figure 277:Example of Indoor Unit Group to Zone
Controller Connections (Sig-12V-GND [Comm.]
Group (Group Control) Terminal).
If any indoor units were specified to operate in unison:
• Before running the field provided or LG provided cable, decide which indoor unit will be
the “Master.” The other indoor units in that group will be designated as “Slave(s).” The
zone controller will be connected to the “Master.” Master Indoor Unit Indoor Unit Indoor Unit
• Set the pertinent DIP switch at each indoor unit to identify the Master and Slave(s).
On wall mounted indoor unit models, set the assignment using the handheld remote Signal 12VDC Comm. Signal 12VDC Comm. Signal 12VDC Comm.
Multi F and Multi F MAX Indoor Unit Engineering Manual
controller.
• Use a daisy chain configuration and connect all of the group’s indoor units together
starting at the “Master” unit.
• NEVER splice, cut, or extend LG provided cable with field provided cable. Always 4 5 6
Signal 12VDC Comm.
include enough cable to cover distance between all components.
For indoor units with hardwired connections SIG - 12V - GND (Comm.)
terminals:
• From the controller to the master indoor unit, use field provided or LG provided 22 Figure 278:Example of Indoor Unit Group to Zone
AWG, 3-conductor, twisted, stranded, unshielded. All wiring must comply with all ap- Controller Connections (CN-REMO).
plicable local / national codes.
• From the master indoor unit to the slave indoor unit(s), daisy chain using field provided
or LG provided 22 AWG, 3-conductor, twisted, stranded, unshielded. All wiring must
comply with all applicable local / national codes. On All Indoor Unit Styles On All Indoor Unit Styles
CN-REMO CN-REMO
On All Indoor Unit Styles
CN-REMO
• Do not attach wire to 12VDC terminal to the slave indoor units. All wiring must
comply with all applicable local and national codes. LG
Supplied
• NEVER splice, cut, or extend LG provided cable with field provided cable. Always
include enough cable to cover distance between all components.
LG Supplied Group Control Kit (PZCWRCG3)
Wiring Connections
CR Combination Ratio ODU Outdoor Unit
DB Dry Bulb OUCF Outdoor Unit Correction Factor
dB(A) Decibels with “A” frequency weighting PDI Power Distribution Indicator
DDOAS Decoupled Dedicated Outdoor Air PI Power Input
DFS Duct-Free Split PTAC Packaged Terminal Air Conditioner
DI Digital Input PVE Polyvinyl Ether
DO Digital Output RAT Return Air Temperature
ECM Electronically Commutated Motor RCL Refrigerant Concentration Limit
EEV Electronic Expansion Valve SC Sensible Capacity
ELF Equivalent Length in Feet TC Total Capacity
EPDM Ethylene Propylene Diene M-Class Rubber VAV Variable Air Volume
ESP External Static Pressure VRF Variable Refrigerant Flow
ETL Electronic Testing Laboratories VRP Ventilation Rate Procedure
HACR Heating, Air Conditioning, and Refrigeration
H/M/L High / Medium / Low
Due to our policy of continuous product innovation, some specifications may change without notification.
©LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp. WIRING CONNECTIONS | 221
20001747 ISO 9001: 2008
LG ELECTRONICS INC.