Index
1---Dimensions -----------------------------------------P-1
2---Panel&wiring instruction --------------------------P-2
3---Main parameters&Ordering code------------------P-4
4---Calibration parameters -----------------------------P-5
5---Parameter setting ------------------------------------P-6
5.1 General parameter setting ------------------------------ P-6
5.2 Control parameters setting ------------------------------- P-7
6---Control mode instruction-------------------------P-10
6.1 Control mode 0 ----------------------------------P-10
6.2 Control mode 1 ------------------------------------ P-11
6 . 3 C o n t r o l m o d e 2 - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - P - 11
6.4 Control mode 3 ----------------------------------P-12
6.4.1 Self-checking mode ------------------------------------- P-12
6.4.2 External control mode ----------------------------------- P-12
6.4.3 Relay mode ------------------------------------------------ P-12
7---Operating instructions--------------------------P-13
8---20mA current loop --------------------------------P-14
9---Data format of Continuous sending mode -----P-15
10---Data format of Command response mode ---P-15
11---Wiring instruction------------------------------P-17
12---Calibration instruction----------------------------P-18
13---Analog output setting---------------------P-20
14---Error alarm---------------------------------------P-21
P-1
2---Pannel&wiring instruction
Indicator FCT
Run Net
Zero
• Zero clearance under measuring state,only works when stable light is on.
• Change position during setting and calibration.
• Take the present value as 0 and net light turns on,only works when displayed value is not
Tare zero and stable light is on.Tare function is disabled under running state.
• Change the parameter value during setting and calibration.
• Confirm&save current parameter value under setting/calibration mode and enter into the
En next parameter setting.
P-2
1 2 3
GND N L
+12V I1 I2 I3 0V
110~230V, 50/60Hz O1 O2 O3
6 5 4
1---- Power
110~230V, 50/60Hz
6---- Calibration
For calibration,refer to P-5
P-3
3---Main parameters
ADC 24 bit Delta-Sigma
Power supply 110...230V AC,50/60Hz
Input range -19mV...+19mV
Display range - 999999...999999
Non-linearity ˂0.01% F.S.
Input sensitivity 1μV/d
Conversion rate 80Hz
Gain drifting <8PPM/°C
Working temp. -10...50°C
Relative humidity <90% RH
Net weight About 620g
Display 7 digit LED, height 0.55"
Up to 8pcs load cells(350Ω)
Input
3-way optoelectronic isolation switch input
RS232 or RS485
0-5V,0-10V or 4-20mA
Output 3 relays(NO),220V/0.5A
20mA current loop for remote display
5V DC,350mA(for load cell)
Ordering code
Communication Analog output
Part No. 3 Relays
RS485 RS232 0-5V 0-10V 4-20mA
FCTA √ √ √
FCTB √ √ √
FCTC √ √ √
FCTD √ √ √
FCTE √ √ √
FCTF √ √ √
P-4
4---Calibration parameters
In calibration state, button andTare
can be used to change the parameter value,button
Zero
En is
used to confirm the parameter value and enter into next step.
P-5
5---Parameter setting
Press F and at the same time, it will display “ SEt * ”,press
Zero
to change the parameter, Tare
P-6
Step Parameter Interpretation
9 F * Reserved function
0-No
14 Prt * Whether to print the set parameters
1-Yes
P-7
Step Parameter Interpretation
4 A****** Feeding value/Batch value
0- No auto tare
A-Tare state before feeding
1- Auto tare before feeding
0- No advance correction
B- Advance correction
1- With advance correction
3 C ABCD
0-Continue without treatment
C- Beyond tolerance treatment
1- Wait until within tolerance
0- Using gradual feed
D- Small gradual feed for shortage
1- Without gradual feed
4 A****** Feeding value/Batch value of material 1
P-8
Step Parameter Interpretation
P-9
6---Control mode instruction
6.1 Control mode 0
Case 1
A+d
A A+d
A-c
ed
fe gradual feed
ow
sl
A-b
feed
fast
fast feed
O1
slow feed
O2
discharge
O3
Case 2
A feed
slow
A-b
feed
fast
fast feed
O1
slow feed
O2
discharge
O3
P-10
6.2 Control mode 1(1 kind of material subtraction)
fas
t fe
ed
b slo
wf
ee
d
slow feed
O2
discharge
O3
A+P
A+P-d
A-b
L
• With gradual feed
material 1 feed
O1
material 2 feed
O2
discharge
O3
P-11
6.4 Control mode 3
6.4.1 Self-checking mode
Sorting weight C
Upper limit value
Sorting weight B
Lower limit value
Sorting weight A
Zero zone
Sorting B
O2
Sorting A
O1
Sorting C
O3
Trigger signal
Trigger signal
Trigger signal
Zero zone
Up limit>Weight>Low limit
O2
Weight<Lower limit
O1
Weight>Upper limit
O3
P-12
7---Operating instructions
7.1---Manual resetting
If the displayed value deviates from zero but within manual zero clearing range, manual zero
clearance can be done by press button when stable light is on.Refer to P-6 for detailed info
Zero
7.2---Tare
Under measure state,when displayed value is bigger than 0 and stable light is on,press button Tare
7.4---Run/stop
Two ways to exchange run/stop state:
Run
a. Press button Stop on the front panel
b. Input a pulse signal through I1 terminal on the back of the indicator
7.5---I/O
Input Output
Control
mode
I1 I2 I3 O1 O2 O3
L<Displayed
Mode 3 Run/Stop External control Discharge Displayed value≤L
value<H
Displayed value≥H
7.6---I/O test
Run
Press button F and at the same time to enter the internal code state,O1/O2/O3 will output
Stop
corresponding signal if level signal is given to I1/I2/I3, and corresponding indicate light will turn on.
P-13
8---20mA current loop
Each data consists of 3 data frames,each frame contains 11 bits.
Mode: Serial output in binary code
Sending period: 100ms
Baud rate: 600bps
Data bit
Low High
0
0 1 2 3 4 5 6 7 8 9 10
Start d0 d1 d2 d3 d4 d5 d6 d7 Mark Stop
bit bit bit
G16 G17
◘ d0/d1/d2: Decimal position(0~3)
◘ d3: Sign bit,1---Negative,2---Positive
◘ d4: Gross/net weight,1---Net weight,0---Gross weight
Second data frame
1
Data bit
Low High
0
0 1 2 3 4 5 6 7 8 9 10
Start d0 d1 d2 d3 d4 d5 d6 d7 Mark Stop
bit bit bit
G8 G9 G10 G11 G12 G13 G14 G15
Data bit
Low High
0
0 1 2 3 4 5 6 7 8 9 10
Start d0 d1 d2 d3 d4 d5 d6 d7 Mark Stop
bit bit bit
G0 G1 G2 G3 G4 G5 G6 G7
◘ G0~G17: Binary code for measured value.
P-14
9---Data format of Continuous sending mode
The transmitted data is the displayed value,each frame of data consists of 12 bytes.
th
X byte Contents Notes
1 02(XON) Start
2 + or - Sign bit
3 High bit
Weighing data
8 Low bit
9 Decimal 0~4
10 XOR Checking High bit
11 XOR Checking Low bit
12 03(X0FF) End
Please refer to the following sheet for the meaning of alpblet and corresponding
communication format:
P-15
Command Meaning Format Example
Send by PC Tare 02 AD 45 XH XL 03 02 41 45 30 34 03
E
Send by indicator Tare 02 AD 65 XH XL 03 02 41 65 32 34 03
Send by PC Running 02 AD 47 XH XL 03 02 41 47 30 36 03
G
Send by indicator Running 02 AD 67 XH XL 03 02 41 67 32 36 03
Send by PC Stop 02 AD 48 XH XL 03 02 41 48 30 39 03
H
Send by indicator Stop 02 AD 68 XH XL 03 02 41 68 32 39 03
P-16
11---Wiring instruction
11.1---4-wire load cell wiring
EXC+ EXC- SIG- SHL
SIG+
EX+
EX-
SEN+
SEN-
SIG+
SIG-
GND
EX+ and SEN+ needs to be short connected
EX- and SEN- needs to be short connected
EX-
SEN+
SEN-
SIG+
SIG-
GND
P-17
12---Calibration instruction
Before calibration,please make sure:
1---- The load cell is connected to the indicator correctly.
2---- The “CAL” switch is at position “ON”(Refer to P-3)
3---- The indicator is power on.
Measuring state
Press En and F at the same time
--CAL–
Press En
E ***
Set this parameter using Tare
,then press En
dC *
Set this parameter using Tare
,then press En
F******
Set this parameter using Zero
and Tare
,then press En
r*
Set this parameter using Tare
,then press En
noLoAd
Add no weight(or weight you want to take it as 0) to the load cell,
then press En after stable
******
Press En after stable
AdLoAd1
Add known weight(load1) to the load cell,
then press En after stable
******
Press En after stable
Set this parameter into the value of the added weight(load1)
******* using Zero and Tare ,then press En to finish calibration
AdLoAd2
Next page
P-18
AdLoAd2
Add known weight(load2 higher than load1)to the load cell,
then press En after stable.
******
Press En after stable
AdLoAd3
Add known weight(load3 higher than load2)to the load cell,
then press En after stable.
******
Press En after stable
AdLoAd4
Add known weight(load4 higher than load3)to the load cell,
then press En after stable.
******
Press En after stable
AdLoAd5
Add known weight(load5 higher than load4)to the load cell,
then press En after stable.
******
Press En after stable
2-Set “A******” into the total capacity of the load cells which is 100 in this case,it can also be
100.0, 100.00 ...depending on the decimal position.
3-Set “PL*****” into 0,the indicator will output 0~0.03V which is normal.
2-Set “A******” into the total capacity of the load cells which is 100 in this case,it can also be
100.0, 100.00 ...depending on the decimal position.
3-Set “PL*****” into 12520,if the indicator outputs less than 4mA,set this parameter a bit
higher,the output signal will change accordingly by adjusting this parameter,then press En
after you get 4mA output.
P-20
14---Error alarm
Err 01 — Doesn’t meet the requirements of tare
P-21