DSP Lab 4
DSP Lab 4
DSP Lab 4
EXPERIMENT NO: 4
EXPERIMENT TITLE: Definite Time Lag (DTL) over-current and earth fault
relays
Warning: Do not switch on the power supply to any equipment before and during the
connection of the circuit.
Switch off the supply before you disconnect the circuit.
Objective: To study the operation of Definite Time Lag 1)Over current Relay (OCR) and
2) Earth Fault Relay
A. C. Ammeter
A.C. ammeter (0 – 20 A)
(0-50A) CT
A A R1
L S1
Contacts
OCR
Injection
Test Set N S2
R2
Use 3 turns for primary
Fig. 1
2. Ensure that the relay current setting is 2 A and the relay time setting is
0.5 second. (This step has been done for you. Do not adjust the relay.)
3. Switch ON the current injection test set and adjust the current output
until the LED on the OCR lights up. Record the primary and
secondary currents. (This current is known as the “pick up” current of
the relay).
5. Switch OFF the test set without changing the position of the variac.
7. Switch on the current injection test set and press the ON-TIME
button.
8. Record the operating time of the relay. Repeat the experiment with
the same current setting and take the average tripping time.
9. Set the primary current to 16A and repeat Steps 4 to 8. Record both
current and time.
10. Repeat the experiment for primary currents of 20A and 24A.
11. Switch OFF the test set and disconnect the circuit.
A. C. Ammeter
(0 – 20 A)
A Y1
Contacts
L
OCR
Injection
Test Set N
Y2
Fig. 2
2. Do not adjust the current setting and the time setting of the relay.
3. Switch ON the current injection test set and adjust the current
output until the LED lights up. Record the current. (This current
is known as the “pick up” current.)
7. Switch on the S.I. test set and press the ON-TIME button.
11. Switch OFF the test set and disconnect the circuit.
A. C. Ammeter
A.C. ammeter (0 – 5 A)
(0-50A) CT
A A 2
L S1
Contacts
EFR
Injection
Test Set N S2
7
Use 1 turn for primary
Fig. 3
2. Do not adjust the current and time settings on the earth fault relay.
(Note: the current setting is approximately 1.0A)
3. Switch ON the current injection test set and adjust the current
output until the plunger on the relay pops up. Record the primary
and secondary currents. (This current is known as the “pick up”
current.)
5. Switch OFF the test set without changing the position of the
variac.
Current Setting = 2 A
Time Setting = 0.5 sec
Current Setting = 1 A
Time Setting = 0.5 sec
EXPERIMENT NO.: 4
EXPERIMENT TITLE: Time Lag (DTL) over-current and earth fault relays
3 x 12 A =
3 x 16 A =
3 x 20 A =
3 x 24 A =
Time (seconds)
Current
1st 2nd Average
* NA NA NA
4A
6A
8A
9A
2. What are the differences between a primary injection test and a secondary injection
test? (Bigger current in primary test is not an answer).
3. You are given a 3 phase DTL over-current relay, a DTL earth fault relay and 4
current transformers. Draw the wiring diagram showing the connections of the
over-current and earth fault relays to the current transformers in a 3-phase LV
switchboard and from the relay to the shunt trip coil of the circuit breaker. The
supply is 400V, 3-phase, 50 Hz, 4-wire and the shunt trip coil operates at 230 V.
Label all terminals.
R Y B N