Parallel Operation of Two Single Phase Transformers: Experiment No: 05
Parallel Operation of Two Single Phase Transformers: Experiment No: 05
Parallel Operation of Two Single Phase Transformers: Experiment No: 05
EXPERIMENT NO: 05
PARALLEL OPERATION OF TWO SINGLE PHASE TRANSFORMERS
AIM: Parallel operation of two dissimilar (2 KVA, 3 KVA) single phase transformers and
determination of load sharing and analytical verification given the short circuit test details.
EQUIPMENTS REQUIRED:
PROCEDURE :
a) Make connections as per circuit diagram; keep the Load switch (DPST) and SPST(S1) switch
open.
b) First, Perform polarity test on each of the units and note down terminals with the same
polarity.
c) Switch ON the main supply, see the voltmeter reading of V connected across SPST switch, if
this reading double the secondary voltage of both the transformers then switch OFF main
supply and interchange the connections of secondary of any transformers.
d) If it reads zero which confirms that two transformers are connected correctly and parallel
then switch SPST(S1)can be closed, this way the polarity can be checked.(since wrong
polarity will short circuit the transformer if operated in parallel).
e) Also, confirm that no load voltages of both the transformers match in magnitude.
(It is important to perform both these tests before attempting the parallel operation).
f) As we are not applied load on the Transformers, the ammeters shows zero readings.
g) Start applying the load on transformers, then T/F-1 and T/F-2 starts drawing the
corresponding currents as per their ratings.
h) Note down the corresponding current readings I1 , I2 & IL .
i) As we increase the load the corresponding values of currents I1 , I2 & IL increases.
j) Repeat the procedure for 4 to 6 readings by applying load stepwise.
k) Once the readings are noted down switch off the loads gradually, open SPST switch and
switch OFF the main supply.
l)
a) Connections are made as shown in the circuit diagram for SC test for each Transformer.
b) Keeping the auto transformer at zero output position close the supply switch.
c) Vary the auto transformer till the ammeter reads the rated full-load current of the
Transformer under test.
d) Note down the ammeter, voltmeter and wattmeter readings.
e) Bring the auto transformer to zero output position and open the supply switch.
f) Tabulate the readings, disconnect the windings.
(Note : Impedance calculating should be in (a+jb) rectangular form and load sharing shall be
reported in the tabular column in a+jb form.)
𝑍2 𝑍1
I1 = I L X (Amp) ; I2 = I L X (Amp)
𝑍1 +𝑍2 𝑍1 +𝑍2
S.No Vsc (Volts) Isc (amp) Wsc (watts) COS ⍉sc R01 (Ω) X01 (Ω)
T/F-1
T/F-2
𝑊𝑠𝑐
1. R01 = 2 (Ω)
𝐼𝑠𝑐
𝑉𝑠𝑐
2. Z01 = (Ω)
𝐼𝑠𝑐
3. X01 = √𝑍01
2 2
− 𝑅01 (Ω)
CONCLUSION : The load sharing between the two transformers connected in parallel is studied
theoretically and verified practically.
EXPERIMENT NO: 03
SUMPNER’S TEST (or) BACK TO BACK TEST
AIM : To conduct Back to Back test on two identical transformers and to determine the efficiency
and regulation of Transformer.
APPARATUS :
THEORY :
1. In OC test we find :
a) Core loss (Wo)
b) Core Parameter (Ro & Xo)
2. In SC test we find :
a) Copper loss (Wcu)
b) Winding Parameters (R01 & X01)
3. From Sumpner’s test we find :
a) all the four parameters can be find (i.e. Ro, Xo, Ro1 & Xo1)
b) In addition to above we can also find temperature rise of transformers.
PROCEDURE :
TABULATION :
OC TEST :
2*Io 2* Wo
Vo (Volts) Ro (Ω) Xo (Ω) Zo (Ω)
(Amp) (Watts)
SC TEST :
2*Vsc (Volts)
Isc (Amp) (Across auto 2*Wsc Req (Ω) Xeq (Ω) Zeq (Ω)
transformer output)
𝑊𝑂
1. COS ⍉O = 𝑉𝑂∗ 𝐼𝑂
𝑉𝑂 𝑉𝑂
2. Zo=√𝑅𝑜2 + 𝑋𝑂2 3) Ro = 𝐼 Ω 4) Xo = 𝐼 Ω
𝑂 𝑋 𝐶𝑂𝑆⍉𝑂 𝑂 𝑋 𝑆𝑖𝑛 ⍉𝑂
Wsc Vsc
5. Req = Ω 6) Zeq = Ω 7) Xeq=√𝑍𝑒𝑞
2 − 𝑅2
𝑒𝑞
(Isc)2 Isc
RESULT: The characteristic curve of efficiency at different loads and % Regulation at full-load at
different power factors are drawn.
EXPERIMENT NO: 04
SCOTT CONNECTION (or) T-CONNECTION ON TRANSFORMERS
AIM : To obtain two single phase (1-∅) supplies from a three phase (3-∅) supply by scott
connecting the two transformers and further study the loading on the three phase side
due to loading on the two single phase & determination of efficiency of the combined set
(2 x 1.2 KVA).
APPARATUS :
THEORY :
Here we are using two transformers (T/F-1 & T/F-2 )
a) Transformer-1 called as -------- Main Transformer
b) Transformer-2 called as -------- Teaser Transformer
c) Transformer-1 in which used 86.6 % of secondary tappings, whereas
d) Transformer-2 in which used 50 % of secondary tapping.
PROCEDURE :
TABULAR COLUMN :
CALUCULATION :
𝑂𝑈𝑇 𝑃𝑈𝑇
3. %ɳ = X 100
𝐼𝑁𝑃𝑈𝑇
EXPERIMENT NO: 08
REGULATION OF ALTERNATOR BY USING SYCHRONOUS IMPEDANCE METHOD
AIM : To find the regulation of a 3-⌀ alternator by using synchronous impedance method.
APPARATUS REQUIRED :
CIRCUIT DIAGRAM:
PROCEDURE :
OBSERVATIONS :
OC TEST S.C.TEST
S.N S.N
Field Current (Amp) OC Voltage/phase (Vo) Field Current If (Amp) SC Current Isc (Amp)
OBSERVATIONS :
𝑽
S.No Armature Current (amp) Armature Voltage (volts) Rdc = (Ω)
𝑰
MODEL CALCULATIONS:
𝑉𝑜𝑐
𝑍𝑠 = for the same If and speed : 𝑋𝑠 = √𝑍𝑆2 − 𝑅𝑎2 [Ra Rdc ]
𝐼𝑠𝑐
𝐸𝑜− 𝑉
% Reg = X 100
𝑉
MODEL GRAPH :
Draw the graph between If (vs) Eo per phase and If (vs) Isc
PRECAUTIONS :
RESULT :
EXPERIMENT NO: 07
DIRECT LOAD TEST ON ALTERNATOR
AIM : To conduct direct load test on Alternator and obtain voltage regulation.
APPARATUS REQUIRED :
CIRCUIT DIAGRAM :
PROCEDURE:
1. Make the connection as per the circuit diagram.
2. Before starting the experiment, the potential divider network in the alternator field circuit
and field regulator rheostat of motor circuit is set minimum resistance position.
3. Switch ON the supply and close the DPST switch. The DC motor is started by moving starter
handle.
4. Adjust the field rheostat of DC motor to attain rated speed (equal to synchronous speed of
alternator)
5. Increase excitation current of alternator gradually until we get rated terminal voltage by
decreasing the field resistance.
6. Note the readings of line current, and its corresponding armature voltage under no load
condition in a tabular column.
7. Now close TPST switch to apply load on alternator.
8. Apply load on alternator step wise and note the readings of line current, armature voltage for
corresponding load values in a tabular column.
9. Increase load up to rated current and take the values of terminal voltage, line current and
calculate regulation of alternator at different load conditions.
10. Remove load gradually from the alternator and switch off the power supply.
OBSERVATIONS :
1
2
3
4
5