SIL 2 Temperature Signal Converter,

D1072 Duplicator, Adder/Subtractor DIN-Rail


Models D1072S, D1072D

Characteristics: Technical Data:


General Description: Supply: 12-24 Vdc nom (10 to 30 Vdc) reverse polarity protected,
ripple within voltage limits ≤ 5 Vpp.
The single and dual channel DIN Rail Temperature Signal Converter D1072S and Current consumption @ 24 V: 70 mA for 2 channels D1072D,
D1072D accepts a low level dc signal from millivolt, thermocouple or RTD temperature 45 mA for 1 channel D1072S with 20 mA output typical.
sensor, located in Hazardous Area, and converts, with isolation, the signal to drive a Current consumption @ 12 V: 140 mA for 2 channels D1072D,
Safe Area load. Output signal can be direct or reverse. 80 mA for 1 channel D1072S with 20 mA output typical.
Duplicator function provides two independent outputs for the single input. Power dissipation: 1.5 W for 2 channels D1072D, 1.0 W for 1 channel D1072S
Adder, subtractor, low/high selector functions provides two independent outputs with 24 V supply voltage and 20 mA output typical.
representing input A, input B, input A plus input B, input A minus input B, Max. power consumption: at 30 V supply voltage, overload condition and
low/high selector. PPC1090 connected, 2.1 W for 2 channels D1072D, 1.4 W for 1 channel D1072S.
Function: Isolation (Test Voltage): I.S. In/Out 1.5 KV; I.S. In/Supply 1.5 KV; I.S. In/I.S. In 500 V;
Out/Supply 500 V; Out/Out 500 V.
1 or 2 channel I.S. input from mV, thermocouples, 3-4 wires resistance thermometers, Input: millivolt or thermocouple type A1, A2, A3, B, E, J, K, L, Lr, N, R, S, S1, T, U or
transmitting potentiometers, provides 3 port isolation (input/output/supply) and 3-4 wires RTD Pt100, Pt200, Pt300 to DIN43760, Pt100 (0.3916), Ni100, Ni120 or
current (source mode) or voltage output signal. Pt500, Pt100, Pt50, Cu100, Cu53, Cu50, Cu46 (russian standard) or
Duplicator, adder, subtractor, low/high selector function provided. 3 wires transmitting potentiometer (50 Ω to 20 KΩ).
The programmable RTD line resistance compensation allows the use of 2 wires RTDs Integration time: 500 ms.
or error compensation for 3-4 wires RTDs. Reference junction compensation can be Resolution: 5 µV on mV or thermocouple, 1 µV thermocouple type B, R, S, S1,
automatic, with option 91, or fixed by software setting. 2 µV thermocouple A1, A2, A3, 20 mΩ on RTD, 0.05 % on transmitting potentiometer.
Signalling LEDs: Visualization: 0.1 °C on temperature, 10 µV on mV, 0.1 % on potentiometer.
Input range: within rated limits of sensor (-10 to + 80 mV).
Power supply indication (green), burnout (red). Measuring RTD current: ≤ 0.5 mA.
Configurability: RTD line resistance compensation: ≤ 10 Ω.
Totally software configurable, no jumpers or switches, input sensor, connection mode, RTD line resistance error compensation: - 5 to + 20 Ω, programmable.
burnout operation, mA or V output signal, by GM Pocket Portable Configurator Thermocouple Reference Junction Compensation: automatic, by external
PPC1090, powered by the unit or configured by PC via RS-232 serial line with sensor OPT1091 separately ordered, or fixed programmable from - 60 to + 100 °C.
PPC1092 Adapter and SWC1090 Configurator software. Thermocouple burnout current: ≤ 30 nA.
A 16 characters tag can be inserted using SWC1090 Configurator software. Burnout: enabled or disabled. Analog output can be programmed to detect burnout
To operate PPC1090 or PPC1092 refer to instruction manual. condition with downscale or highscale forcing.
EMC: Burnout condition signalled by red front panel LED.
Output: 0/4 to 20 mA, on max. 600 Ω load source mode, current limited at 22 mA or
Fully compliant with CE marking applicable requirements. 0/1 to 5 V or 0/2 to 10 V signal, limited at 11 V.
Front Panel and Features: Resolution: 2 µA current output or 1 mV voltage output.
Transfer characteristic: linear or reverse on mV or transmitting potentiometer,
SIL 2 according to IEC 61508:2010 (Route 2H) temperature linear or reverse on temperature sensors.
1 2 3 4 for analog current source output of each channel Response time: ≤ 50 ms (10 to 90 % step change).
D1072S:Tproof = 3/10 yrs (≤10% / >10 % of total SIF) Output ripple: ≤ 20 mVrms on 250 Ω load.
D1072D:Tproof = 3/10 yrs (≤10% / >10 % of total SIF) Performance: Ref. Conditions 24 V supply, 250 Ω load, 23 ± 1 °C ambient temperature.
5 6 7 8 SC2 : Systematic Capability SIL2. Input: Calibration and linearity accuracy: ≤ ± 40 µV on mV or thermocouple,
Input from Zone 0 (Zone 20), Division 1, 200 mΩ on RTD, 0.2 % on potentiometer or ± 0.05 % of input value.
installation in Zone 2, Division 2. Temperature influence: ≤ ± 2 µV, 20 mΩ, 0.02 % or ± 0.01 % of input value
mV, thermocouples, RTD or for a 1 °C change.
transmitting potentiometers Input Signal. Ref. Junction Compensation influence: ≤ ± 1 °C (thermocouple sensor).
Programmable RTD line resistance compensation. Analog Output: Calibration accuracy: ≤ ± 0.1 % of full scale.
Reference Junction Compensation automatic or Linearity error: ≤ ± 0.05 % of full scale.
fixed (programmable value). Supply voltage influence: ≤ ± 0.05 % of full scale for a min to max supply change.
Load influence: ≤ ± 0.05 % of full scale for a 0 to 100 % load resistance change.
C 0/4-20 mA, 0/1-5 V, 0/2-10 V Temperature influence: ≤ ± 0.01 % on zero and span for a 1 °C change.
O Output Signal temperature linear or reverse. Compatibility:
N Duplicated output for single channel input. CE mark compliant, conforms to Directive:
F Adder, Subtractor, low/high Selector. 2014/34/EU ATEX, 2014/30/EU EMC, 2014/35/EU LVD, 2011/65/EU RoHS.
PWR BURN 16 characters tag for each channel. Environmental conditions: Operating: temperature limits -20 to + 60 °C,
Common burnout detection available when relative humidity max 90 % non condensing, up to 35 °C.
using Power Bus enclosure. Storage: temperature limits – 45 to + 80 °C.
High Accuracy, µP controlled A/D converter. Safety Description:
Three port isolation, Input/Output/Supply.
EMC Compatibility to EN61000-6-2, EN61000-6-4. ATEX: II (1) G [Ex ia Ga] IIC, II (1) D [Ex ia Da] IIIC, I (M1) [Ex ia Ma] I, II 3G Ex nA IIC T4 Gc
Fully programmable operating parameters. IECEx / INMETRO: [Ex ia Ga] IIC, [Ex ia Da] IIIC, [Ex ia Ma] I, Ex nA IIC T4 Gc
ATEX, IECEx, UL & C-UL, FM & FM-C, INMETRO, associated electrical apparatus.
D1072 EAC-EX, UKR TR n. 898, TÜV Certifications. Uo/Voc = 10.8 V, Io/Isc = 9 mA, Po/Po = 24 mW at terminals 13-14-15-16, 9-10-11-12.
TÜV Functional Safety Certification. Ui/Vmax = 18 V, Ci = 6 nF, Li = 0 nH at terminals 13-14-15-16, 9-10-11-12.
Type Approval Certificate DNV and KR for Um = 250 Vrms, -20 °C ≤ Ta ≤ 60°C.
9 10 11 12 maritime applications. Approvals:
High Reliability, SMD components. DMT 01 ATEX E 042 X conforms to EN60079-0, EN60079-11, EN60079-26.
High Density, two channels per unit. IECEx BVS 07.0027X conforms to IEC60079-0, IEC60079-11, IEC60079-26.
IMQ 09 ATEX 013 X conforms to EN60079-0, EN60079-15.
13 14 15 16 Simplified installation using standard IECEx IMQ 13.0011X conforms to IEC60079-0, IEC60079-15.
DIN Rail and plug-in terminal blocks. UL & C-UL E222308 conforms to UL913, UL 60079-0, UL60079-11, UL60079-15,
250 Vrms (Um) max. voltage allowed to the ANSI/ISA 12.12.01 for UL and CSA-C22.2 No.157-92, CSA-E60079-0, CSA-E60079-11,
instruments associated with the barrier. CSA-C22.2 No. 213 and CSA-E60079-15 for C-UL.
Ordering Information: FM & FM-C No. 3024643, 3029921C, conforms to Class 3600, 3610, 3611, 3810,
ANSI/ISA 12.12.02, ANSI/ISA 60079-0, ANSI/ISA 60079-11, C22.2 No.142,
C22.2 No.157, C22.2 No.213, E60079-0, E60079-11, E60079-15.
Model: D1072 Power Bus and C-IT.MH04.B.00306 conforms to GOST R IEC 60079-0,GOST R IEC 60079-11,
DIN-Rail accessories: GOST R IEC 60079-15.
1 channel S DIN rail anchor MCHP065 CЦ 16.0034 X conforms to ДСТУ 7113, ГОСТ 22782.5-78, ДСТУ IЕС 60079-15.
2 channels D DIN rail stopper MOR016 TÜV Declaration of Compliance No. C-IS-722238330, SIL 2 according to
Terminal block male MOR017 IEC 61508:2010 Ed.2.
Power Bus enclosure /B Terminal block female MOR022 TÜV Certificate No. C-IS-236198-09, SIL 3 Functional Safety certificate conforms to
IEC61508:2010 Ed.2, for Management of Functional Safety.
Ref. Junction Compensator (TC input) OPT1091 DNV No.A-13778 and KR No.MIL20769-EL001 Certificates for maritime applications.
Mounting: T35 DIN Rail according to EN50022.
Operating parameters are programmable by the GM Pocket Portable Configurator Weight: about 170 g D1072D, 140 g D1072S.
PPC1090 or via RS-232 serial line with PPC1092 Adapter and SWC1090 Configurator Connection: by polarized plug-in disconnect screw terminal blocks to accomodate
software. If the parameters are provided with the purchasing order the unit will be terminations up to 2.5 mm2.
configured accordingly, otherwise the unit will be supplied with default parameters. Location: Safe Area/Non Hazardous Locations or Zone 2, Group IIC T4,
NOTE: for thermocouple sensor input, the Reference Junction Compensator is required Class I, Division 2, Groups A, B, C, D Temperature Code T4 and
for automatic ambient temperature compensation. It has to be ordered as OPT1091, Class I, Zone 2, Group IIC, IIB, IIA T4 installation.
it will be supplied separately and it has to be connected to the input terminal blocks as Protection class: IP 20.
indicated in the function diagram. Dimensions: Width 22.5 mm, Depth 99 mm, Height 114.5 mm.

G.M. International DTS0025-25 Page 1/6 www.gminternational.com


Parameters Table: Image:
Safety Description Maximum External Parameters
Group Co/Ca Lo/La Lo/Ro
Cenelec (µF) (mH) (µH/Ω)
Terminals
13-14-15-16, 9-10-11-12
Uo/Voc = 10.8 V IIC 2.134 468 1510
Io/Isc = 9 mA IIB 14.994 1874 6050
Po/Po = 24 mW IIA 65.994 3749 12100
I 58 6100 19850
IIIC 14.994 1874 6050
NOTE for USA and Canada:
IIC equal to Gas Groups A, B, C, D, E, F and G
IIB equal to Gas Groups C, D, E, F and G
IIA equal to Gas Groups D, E, F and G

Function Diagram:
HAZARDOUS AREA ZONE 0 (ZONE 20) GROUP IIC,
SAFE AREA, ZONE 2 GROUP IIC T4,
HAZARDOUS LOCATIONS CLASS I, DIVISION 1, GROUPS A, B, C, D,
NON HAZARDOUS LOCATIONS, CLASS I, DIVISION 2,
CLASS II, DIVISION 1, GROUPS E, F, G, CLASS III, DIVISION 1,
GROUPS A, B, C, D T-Code T4, CLASS I, ZONE 2, GROUP IIC T4
CLASS I, ZONE 0, GROUP IIC

MODEL D1072D

Reference Junction 3+
=
=
Compensator 4 - Supply 12-24 Vdc
Option 91 =
In 1 13
= Source I Source V
14 1 + +
TC TC
+ + 15 2 mA RL Out 1
V
= - -
16
- -
Reference Junction =
Compensator =
Option 91 =
In 2 9
= Source I Source V
10 5 + +
TC TC
+ + 11 6 mA RL Out 2
V
= - -
12
- -

MODEL D1072D
3+
In 1 =
=
4 - Supply 12-24 Vdc
Pot. 4 wire RTD 3 wire RTD =
13
= Source I Source V
14 1 + +
15 2 mA RL Out 1
V
= - -
16

=
=
Pot. 4 wire RTD 3 wire RTD =
9
= Source I Source V
10 5 + +
11 6 mA RL Out 2
V
= - -
12

In 2

G.M. International DTS0025-25 Page 2/6


Function Diagram:
HAZARDOUS AREA ZONE 0 (ZONE 20) GROUP IIC,
SAFE AREA, ZONE 2 GROUP IIC T4,
HAZARDOUS LOCATIONS CLASS I, DIVISION 1, GROUPS A, B, C, D,
NON HAZARDOUS LOCATIONS, CLASS I, DIVISION 2,
CLASS II, DIVISION 1, GROUPS E, F, G, CLASS III, DIVISION 1,
GROUPS A, B, C, D T-Code T4, CLASS I, ZONE 2, GROUP IIC T4
CLASS I, ZONE 0, GROUP IIC

MODEL D1072D (Duplicator)

Reference Junction 3+
=
=
Compensator 4 - Supply 12-24 Vdc
Option 91 =
In 1 13
= Source I Source V
14 1 + +
TC TC
+ + 15 2 mA RL Out 1-A
V
= - -
16
- -
=
=
Source I Source V
5 + +
6 mA RL Out 1-B
V
- -

MODEL D1072D (Duplicator)

3+
In 1 =
=
4 - Supply 12-24 Vdc
Pot. 4 wire RTD 3 wire RTD =
13
= Source I Source V
14 1 + +
15 2 mA RL Out 1-A
V
= - -
16

=
=
Source I Source V
5 + +
6 mA RL Out 1-B
V
- -

G.M. International DTS0025-25 Page 3/6


Function Diagram:
HAZARDOUS AREA ZONE 0 (ZONE 20) GROUP IIC,
SAFE AREA, ZONE 2 GROUP IIC T4,
HAZARDOUS LOCATIONS CLASS I, DIVISION 1, GROUPS A, B, C, D,
NON HAZARDOUS LOCATIONS, CLASS I, DIVISION 2,
CLASS II, DIVISION 1, GROUPS E, F, G, CLASS III, DIVISION 1,
GROUPS A, B, C, D T-Code T4, CLASS I, ZONE 2, GROUP IIC T4
CLASS I, ZONE 0, GROUP IIC

MODEL D1072D Adder, Subtractor, Low/High Selector


Output repeats input A, B, (A+B)/2 or A-B
Reference Junction 3+
=
=
Compensator 4 - Supply 12-24 Vdc
Option 91 =
In A 13
= Source I Source V
14 1 + +
TC TC
+ + 15 2 mA RL Out 1
V
= - -
16
- -
Reference Junction =
Compensator =
Option 91 =
In B 9
= Source I Source V
10 5 + +
TC TC
+ + 11 6 mA RL Out 2
V
= - -
12
- -

MODEL D1072D Adder, Subtractor, Low/High Selector


Output repeats input A, B, (A+B)/2 or A-B
3+
In A =
=
4 - Supply 12-24 Vdc
Pot. 4 wire RTD 3 wire RTD =
13
= Source I Source V
14 1 + +
15 2 mA RL Out 1
V
= - -
16

=
=
Pot. 4 wire RTD 3 wire RTD =
9
= Source I Source V
10 5 + +
11 6 mA RL Out 2
V
= - -
12

In B

G.M. International DTS0025-25 Page 4/6


Function Diagram:
HAZARDOUS AREA ZONE 0 (ZONE 20) GROUP IIC,
SAFE AREA, ZONE 2 GROUP IIC T4,
HAZARDOUS LOCATIONS CLASS I, DIVISION 1, GROUPS A, B, C, D,
NON HAZARDOUS LOCATIONS, CLASS I, DIVISION 2,
CLASS II, DIVISION 1, GROUPS E, F, G, CLASS III, DIVISION 1,
GROUPS A, B, C, D T-Code T4, CLASS I, ZONE 2, GROUP IIC T4
CLASS I, ZONE 0, GROUP IIC

MODEL D1072S

Reference Junction 3+
=
=
Compensator 4 - Supply 12-24 Vdc
Option 91 =
In 1 13
= Source I Source V
14 1 + +
TC TC
+ + 15 2 mA RL Out 1
V
= - -
16
- -

MODEL D1072S

3+
In 1 =
=
4 - Supply 12-24 Vdc
Pot. 4 wire RTD 3 wire RTD =
13
= Source I Source V
14 1 + +
15 2 mA RL Out 1
V
= - -
16

G.M. International DTS0025-25 Page 5/6


Friendly Configuration with SWC1090 Software and PPC1092 Adapter or Pocket Portable Configurator PPC1090:

Configuration Parameters:
INPUT SECTION: OUTPUT SECTION:
Sensor: input sensor type Output: analog output type
 TC A1 thermocouple to STI90, GOST R8.585 2001  4-20 mA current output range from 4 to 20 mA (for SIL applications)
range from –10 to +2500 °C  0-20 mA current output range from 0 to 20 mA
 TC A2 thermocouple to STI90, GOST R8.585 2001  1-5 V voltage output range from 1 to 5 V
range from –10 to +1800 °C  0-5 V voltage output range from 0 to 5 V
 TC A3 thermocouple to STI90, GOST R8.585 2001  2-10 V voltage output range from 2 to 10 V
range from –10 to +1800 °C  0-10 V voltage output range from 0 to 10 V
 TC B thermocouple to STI90, NBS125, GOST R8.585 2001 Burnout: analog output burnout state
range from +50 to +1800 °C  None burnout function is disabled;
 TC E thermocouple to STI90, NBS125, GOST R8.585 2001 analog output represents the input measure as configured
range from –250 to +1000 °C  Downscale analog output is forced at mA Burnout or V Burnout lower value
 TC J thermocouple to STI90, NBS125, GOST R8.585 2001  Upscale analog output is forced at mA Burnout or V Burnout higher value
range from –200 to +750 °C Function: analog output function
 TC K thermocouple to STI90, NBS125, GOST R8.585 2001  Ch. A analog output represents input of first channel
range from –250 to +1350 °C  Ch. B analog output represents input of second channel
 TC L thermocouple to SIPT68, DIN43710 range from –200 to +800 °C  Add analog output represents the sum of the two input channels: (A+B)/2
 TC Lr thermocouple to STI90, GOST R8.585 2001  Sub analog output represents the difference of the two input channels: A-B
range from –200 to +800 °C  High Ch analog output represents the higher of the two input channels
 TC N thermocouple to STI90, NBS121, GOST R8.585 2001  Low Ch analog output represents the lower of the two input channels
range from –250 to +1300 °C Output Limits: current or voltage analog output normal working range limits or
 TC R thermocouple to STI90, NBS125, GOST R8.585 2001 burnout detection range limits:
range from –50 to +1750 °C mA working: current analog output range in normal working condition.
 TC S thermocouple to STI90, NBS125, GOST R8.585 2001 mA Burnout: current analog output lower and higher value for burnout signalation.
range from –50 to +1750 °C V working: voltage analog output range in normal working condition.
 TC S1 thermocouple type S1 to SIPT68, russian range from –50 to +1600 °C V Burnout: voltage analog output lower and higher value for burnout signalation.
 TC T thermocouple to STI90, NBS125, GOST R8.585 2001
range from –250 to +400 °C Each channel has independent configurations.
 TC U thermocouple to SIPT68, DIN43710 range from –200 to +400 °C
 Pt 100 thermoresistance =385 to SIPT68, IEC751 range from –200 to +850 °C
 Pt 200 thermoresistance =385 to SIPT68, IEC751 range from –150 to +400 °C
 Pt 300 thermoresistance =385 to SIPT68, IEC751 range from –150 to +250 °C
 Pp 100 thermoresistance =392 to SIPT68, ANSI range from –200 to +625 °C
 Pi 500 thermoresistance =391 to SIPT68, russian range from –200 to +75 °C
 Pi 100 thermoresistance =391 to SIPT68, russian range from –200 to +650 °C
 Pi 50 thermoresistance =391 to SIPT68, russian range from –200 to +650 °C
 Ni 100 thermoresistance to SIPT68, DIN43760 range from –50 to +180 °C
 Ni 120 thermoresistance =672 to SIPT68, russian range from –75 to +300 °C
 Cu 100 thermoresistance to SIPT68, russian range from –50 to +200 °C
 Cu 53 thermoresistance to SIPT68, russian range from –50 to +180 °C
 Cu 50 thermoresistance to SIPT68, russian range from –50 to +200 °C
 Cu 46 thermoresistance to SIPT68, russian range from –200 to +650 °C
 Pot 3 wires transmitting potentiometer, 50 Ω to 20 KΩ, range from 0 to 100 %
 E DC millivolt signal range from –20 to +85 mV
Lead: input sensor connection type (thermoresistance only)
 3 wire 3 wires connection type
 4 wire 4 wires connection type
Downscale: input value of measuring range corresponding to defined low output value.
Upscale: input value of measuring range corresponding to defined high output value.
Cold Junction: reference junction compensation type (thermocouple only)
 Automatic ambient temperature compensation automatic by OPT1091 sensor
 Fixed programmable temperature compensation at fixed temperature
CJ Reference: temperature compensation value (Cold Junction type Fixed only),
range from –60 to +100 °C.
RTD line resist: line resistance error compensation value (thermoresistance only),
range from –5 to +20 Ω.
INPUT TAG SECTION:
1: first channel tag
2: second channel tag

Each channel has independent configurations.

G.M. International DTS0025-25 Page 6/6