Transmisor de Temperatura Omegaette TXDIN70

Download as pdf or txt
Download as pdf or txt
You are on page 1of 8

User’s Guide

Shop online at
omega.com
e-mail: info@omega.com
For latest product manuals:
www.omegamanual.info

TXDIN70 SERIES
Dual Transmitter
omega.com info@omega.com

Servicing North America:


U.S.A. Omega Engineering, Inc.
Headquarters: Toll-Free: 1-800-826-6342 (USA & Canada only)
Customer Service: 1-800-622-2378 (USA & Canada only)
Engineering Service: 1-800-872-9436 (USA & Canada only)
Tel: (203) 359-1660 Fax: (203) 359-7700
e-mail: info@omega.com

For Other Locations Visit omega.com/worldwide

The information contained in this document is believed to be correct, but OMEGA accepts no liability for any errors it contains, and
reserves the right to alter specifications without notice.
MODEL COVERED
TXDIN70 Description: Dual Transmitter
Supply Power: 100~240VAC,50/60Hz

TXDIN70-24V Description: Dual Transmitter


Supply Power: 24VDC

TXDIN70-DISPLAY Description: Transmitter Display


Supply Power: From TXDIN70 Transmitter

TECHNICAL SPECIFICATION
Input type: Thermocouple K(-50 °C ~1,300 °C), S(-50 °C ~1,700 °C), R(-50 °C ~1,600 °C),
E(0 °C ~1,000 °C), J(0 °C ~1,200 °C), N(-50 °C ~1,300 °C),
T(-200 °C ~350 °C), B(0 °C ~1,800 °C),
WRe5-WRe26(0 °C ~2,300 °C), WRe3-WRe25(°C 0~ 2,300 °C)
RTD Cu50(-50 °C ~+150 °C), Pt100(-200 °C ~+900 °C)
Linear Voltage 0~1V, 0.2~1V, 0~20mV, 0~60mV, 0~100mV
Retransmission accuracy: 0.3%FS ± 1 digit (including input and output error)
Output specification: Defined in the range of 0~22mA
with maximum output voltage ≥ 11V
Temperature drift: ≤0.015%FS / °C (including the temperature drift of input and output)
Electromagnetic compatibility (EMC):
±4KV/5KHz according to IEC61000-4-4 (EFT);
4KV according to IEC61000-4-5
Isolation withstanding voltage: Voltage between supply power and
signal input output terminals ≥300VDC;
Voltage between inputs or 2 outputs ≥200VDC
Power supply: 100~240VAC, -15%, +10% / 50~60Hz; or 24VDC
Power consumption: ≤ 3W
Operating Ambient : Temperature -10 °C~+60 °C; Humidity ≤90%RH
Remark: Type-B thermocouple operates in the range of 60 °C ~400 °C but the measurement accuracy
does not meet the stated accuracy. Accuracy is guranteed in the range of 400 °C~1,800 °C.

CONNECTION DIAGRAM
Terminal 1,2: Power supply of 100~240VAC (TXDIN70) or
24VDC (TXDIN70-24V)
Terminal 5,6 OP1: Positive and negative pole of channel 1
current retransmission output.
Terminal 7,8 OP2: Positive and negative pole of channel 2
current retransmission output.
Terminal 14,16 IN1: Channel 1 input.
Terminal 10,12 IN2: Channel 2 input.

OP1 and OP2 lights on when there is outputs in channel 1 and 2. The
luminosity change with the magnitude of output.
MODE light blinks when transmitter is communicatiing with upper device.
Blinking at 1.6 sec cycle: No active communication. Working normal without alarm
Blinking at 0.6 sec cycle: No active communication with alarm
Blinking at 0.3 sec cycle: No active communication with severe fault such as input
out of range.
Light off: No power or out of order.
Light kept on over 8 sec: Transmitter is powered on but it is out of order
DISPLAY/OPERATION
Parameters are set by an hot-plugged display TXDIN70-Display. Apart from nitial set-up, TXDIN70-
Display can be stay connected serving as an external display.
1 Upper Display: Displays PV of channel 1 or parameter
code, When the display keeps flashing or the reading is
abnormal, please check the input specification whether it is
correctly set.
2 Lower Display : Displays PV of channel 2 or parameter
value. When the display keeps flashing or the reading is
abnormal, please check the input specification whether it is
correctly set.
3 Set Key: Accessing parameter table and to confirm
parameter change.
4 Data Point Shift (to the left)
5 Data Decrease
6 Data Increase

Remark: The bundled IEEE-1394 cable is designed for


communication between TXDIN70-Display and TXDIN70. This
cable is not for other usages.
Entering Parameter Table
When the parameter lock “Loc” is not locked, press and hold for about 2 seconds to bring up the
Full Parameter Table. Press (without holding) to bring up the parameters one by one. Press
to modify a parameter value. Press to confirm and proceed to next one. Press and hold will
return to the preceding parameter. Press and then by holding two keys will escape from the
parameter table.
When the parameter lock “Loc” is locked, press to bring up Field Parameter Table which show field
parameters INP1,INP2, SCL1, SCL2, SCH1, SCH2. These field parameter value are not allowed to be
changed due to the lock.
The transmitter will automatically escape from the parameter table if there is no keys operation in 25
seconds. The change of the latest parameter will not be saved.

TROUBLESHOOTING
When there is a fault, the upper display blinks out an error message.

Error Message Description and Suggestion


orAL Incorrect input specification paramter. Pleaes check the INP1 and/or INP2
parameter.
Thermocouple, RTD or analog input wiring is disconnected. Probe of
thermocouple or RTD is broken. Please check the wiring.
Input wires are short-circuited. Please check the wiring.
EErr IC Software error. Factory repair is required.
8888 IC Software error. Factory repair is required.
PARAMETER TABLE
Code Parameter Description Range
INP1/ Input Define the input specification of channel 1~ 2. 0~32
INP2 Specification
InP Input spec. InP Input spec.
0 K 11~19 Spare
1 S 20 Cu50
2 R 21 Pt100
3 T 22~24 Spare
4 E 25 0~75mV voltage
input
5 J 26~27 Spare
6 B 28 0~20mV voltage
input
7 N 29 0~100mV voltage
input
8 WRe3-WRe25 30 0~60mV voltage
input
9 WRe5-WRe26 31 0~1 V
10 Extended input 32 0.2~1V
specification
SCL1/ Scale Low Limit SCL and SCH define the corresponding scale range of linear -999~
SCL2 output. For example, for channel 1, in order to retransmit +3000
0~600 °C to output channel 1, SCL1 should be set to 0, units
SCH1/ Scale High Limit and SCH1 should be set to 600. For channel 2, to transmit
SCH2 0~1000°C, then SCL2=0, SCH2=1000.
Scb1/ Input Offset Scb is used to shift input to compensate the error caused by -199~
Scb2 transducer, input signal, or auto cold junction compensation +999.0
of thermocouple. units/
PV_after_compensation=PV_before_compensation + Scb 0.1 °C
FIL1/FIL2 Digital Filter The value of FIL will determine the ability of filtering noise. 0~40
FIL=0, no filtering;
FIL=1, filtering with mean;
FIL=2~40, filtering with mean and integral.
When a large value is set, the measurement input is
stabilized but the response speed is slow. Generally, it can
be set to 1 to 3.
If great interference exists, then you can increase parameter
FIL gradually to make momentary fluctuation of measured
value less than 2 to 5.
When the instrument is being metrological verified, FIL can
be set to 0 or 1 to shorten the response time.
OPn Retransmission OPn=1, For 1 input 1 output or 2 inputs 2 outputs 0~2
Channel retransmission application,
Assignment OPn=2, For 1 input 2 outputs retransmission (Outputs from
input channel 2).
PARAMETER TABLE (cont.)
Code Parameter Description Range
OPL Low Limit Define the low limit and high limit of current retransmission 0~110
of Current of channel 1. The engineering unit is 0.1mA.
Retransmission For example, to retransmit 0~600°C in input channel 1
of Channel 1 to 4~20mA, then the parameter should be set as below:
OPH High Limit SCL1=0, SCH1=600, OPn=1, OPL=40, OPH=200. 0~220
of Current
Retransmission
of Channel 1
OPL2 Low Limit Define the low limit and high limit of current 0~100
of Current retransmission of channel 2. The engineering unit is
Retransmission 0.1mA.
of Channel 2 For example, to retransmit 0~1,000°C in input channel 2
OPH2 High Limit to 4~20mA, then the parameter should be set as below: 0~220
of Current SCL1=0, SCH1=1000, OPn=1, OPL=40, OPH=200.
Retransmission
of Channel 2
IVF1 OP1 Current For adjusting the current of OP1 output. The greater the 0~3000/
Correction value, the greater is the current output. Default
(Please record Note: This parameter is calibrated in factory. It is not ( )
the value in the recommended to alter by user.
first use)
IVF2 OP2 Current For adjusting the current of OP2 output. The greater the 0~3000/
Correction value, the greater is the current output. Default
(Please record Note: This parameter is calibrated in factory. It is not ( )
the value in the recommended to alter by user.
first use)
Loc Parameter Lock Loc=808: Allow to display and modify all parameters. 0~9999
Loc=any number: All parameters cannot be modified with
only INP1, INP2, SCL1, SCL2, SCH1 and SCH2 showing
Where Do I Find Everything I Need for
Process Measurement and Control?
OMEGA…Of Course!
Shop online at omega.com
TEMPERATURE
U Thermocouple, RTD & Thermistor Probes, Connectors, Panels & Assemblies
M
U Wire: Thermocouple, RTD & Thermistor
M
U Calibrators & Ice Point References
M
U Recorders, Controllers & Process Monitors
M
U Infrared Pyrometers
M

PRESSURE, STRAIN AND FORCE


U Transducers & Strain Gages
M
U Load Cells & Pressure Gages
M
U Displacement Transducers
M
U Instrumentation & Accessories
M

FLOW/LEVEL
U Rotameters, Gas Mass Flowmeters & Flow Computers
M
U Air Velocity Indicators
M
U Turbine/Paddlewheel Systems
M
U Totalizers & Batch Controllers
M

pH/CONDUCTIVITY
U pH Electrodes, Testers & Accessories
M
U Benchtop/Laboratory Meters
M
U Controllers, Calibrators, Simulators & Pumps
M
U Industrial pH & Conductivity Equipment
M

DATA ACQUISITION
U Communications-Based Acquisition Systems
M
U Data Logging Systems
M
U Wireless Sensors, Transmitters, & Receivers
M
U Signal Conditioners
M
U Data Acquisition Software
M

HEATERS
U Heating Cable
M
U Cartridge & Strip Heaters
M
U Immersion & Band Heaters
M
U Flexible Heaters
M
U Laboratory Heaters
M

ENVIRONMENTAL
MONITORING AND CONTROL
U Metering & Control Instrumentation
M
U Refractometers
M
U Pumps & Tubing
M
U Air, Soil & Water Monitors
M
U Industrial Water & Wastewater Treatment
M
U pH, Conductivity & Dissolved Oxygen Instruments
M

M4544/0617
WARRANTY/DISCLAIMER
OMEGA ENGINEERING, INC. warrants this unit to be free of defects in materials and workmanship
for a period of 13 months from date of purchase. OMEGA’s WARRANTY adds an additional one (1)
month grace period to the normal one (1) year product warranty to cover handling and shipping
time. This ensures that OMEGA’s customers receive maximum coverage on each product.
If the unit malfunctions, it must be returned to the factory for evaluation. OMEGA’s Customer Service
Department will issue an Authorized Return (AR) number immediately upon phone or written request.
Upon examination by OMEGA, if the unit is found to be defective, it will be repaired or replaced at no
charge. OMEGA’s WARRANTY does not apply to defects resulting from any action of the purchaser,
including but not limited to mishandling, improper interfacing, operation outside of design limits,
improper repair, or unauthorized modification. This WARRANTY is VOID if the unit shows evidence of
having been tampered with or shows evidence of having been damaged as a
result of excessive corrosion; or current, heat, moisture or vibration; improper
specification; misapplication; misuse or other operating conditions outside of
OMEGA’s control. Components in which wear is not warranted, include but are not
limited to contact points, fuses, and triacs.
OMEGA is pleased to offer suggestions on the use of its various products. However,
OMEGA neither assumes responsibility for any omissions or errors nor
assumes liability for any damages that result from the use of its products
in accordance with information provided by OMEGA, either verbal or
written. OMEGA warrants only that the parts manufactured by it will be as
specified and free of defects. OMEGA MAKES NO OTHER WARRANTIES OR
REPRESENTATIONS OF ANY KIND WHATSOEVER, EXPRESS OR IMPLIED, EXCEPT
THAT OF TITLE, AND ALL IMPLIED WARRANTIES INCLUDING ANY WARRANTY OF
MERCHANTABILITY AND FITNESS FOR A PARTICULAR PURPOSE ARE HEREBY
DISCLAIMED. LIMITATION OF LIABILITY: The remedies of purchaser set forth herein are
exclusive, and the total liability of OMEGA with respect to this order, whether
based on contract, warranty, negligence, indemnification, strict liability or otherwise,
shall not exceed the purchase price of the component upon which liability
is based. In no event shall OMEGA be liable for consequential, incidental or special damages.
CONDITIONS: Equipment sold by OMEGA is not intended to be used, nor shall it be used: (1) as a
“Basic Component” under 10 CFR 21 (NRC), used in or with any nuclear installation or activity; or (2)
in medical applications or used on humans. Should any Product(s) be used in or with any nuclear
installation or activity, medical application, used on humans, or misused in any way, OMEGA assumes
no responsibility as set forth in our basic WARRANTY / DISCLAIMER language, and, additionally,
purchaser will indemnify OMEGA and hold OMEGA harmless from any liability or damage whatsoever
arising out of the use of the Product(s) in such a manner.

RETURN REQUESTS/INQUIRIES
Direct all warranty and repair requests/inquiries to the OMEGA Customer Service Department.
BEFORE RETURNING ANY PRODUCT(S) TO OMEGA, PURCHASER MUST OBTAIN AN AUTHORIZED
RETURN (AR) NUMBER FROM OMEGA’S CUSTOMER SERVICE DEPARTMENT (IN ORDER TO AVOID
PROCESSING DELAYS). The assigned AR number should then be marked on the outside of the return
package and on any correspondence.
The purchaser is responsible for shipping charges, freight, insurance and proper packaging to prevent
breakage in transit.
FOR WARRANTY RETURNS, please have the FOR NON-WARRANTY REPAIRS, consult OMEGA
following information available BEFORE for current repair charges. Have the following
contacting OMEGA: information available BEFORE contacting OMEGA:
1. Purchase Order number under which the 1. Purchase Order number to cover the COST
product was PURCHASED, of the repair,
2. Model and serial number of the product under 2. Model and serial number of the product, and
warranty, and 3. Repair instructions and/or specific problems
3. Repair instructions and/or specific problems relative to the product.
relative to the product.
OMEGA’s policy is to make running changes, not model changes, whenever an improvement is possible. This affords
our customers the latest in technology and engineering.
OMEGA is a trademark of OMEGA ENGINEERING, INC.
© Copyright 2018 OMEGA ENGINEERING, INC. All rights reserved. This document may not be copied, photocopied,
reproduced, translated, or reduced to any electronic medium or machine-readable form, in whole or in part, without the
prior written consent of OMEGA ENGINEERING, INC.

M4544/0618