LSA 46.2
180 to 315 kVA - 50 Hz / 228 to 381 kVA - 60 Hz
Electrical and mechanical data
Low Voltage Alternators - 4 pole
LSA 46.2 - 180 to 315 kVA - 50 Hz / 228 to 381 kVA - 60 Hz
R250 Std - - - - - - √
R450 Option Std Std C.T. R726 R731 R734 √
D510C Option Option Option C.T. included included contact factory √
√ : possible mounting
Protection system suited to the environment
● The LSA 46.2 is IP 23.
● Standard winding protection for clean environments with relative humidity ≤ 95 %, including indoor marine environments.
Options : - Filters on air inlet : derating 5%.
- Filters on air inlet and air outlet (IP 44) : derating 10%.
- Winding protections for harsh environments and relative humidity greater than 95%.
- Space heaters.
- Thermal protection for winding and shields.
General characteristics
Insulation class H Excitation system SHUNT AREP or PMG
Winding pitch 2/3 (N° 6) AVR type R 250 R 450
Number of wires 12 Voltage regulation (*) ± 0.5 % ± 0.5 %
Protection IP 23 Short-circuit current - 300% (3 IN) : 10s
Altitude ≤ 1000 m Totale Harmonic distortion THD (**) no load < 2.5% - on load < 2.5%
Overspeed 2250 min-1 Waveform: NEMA = TIF (**) < 50
Air flow 0.43 m3/s (50Hz) / 0.51 (60Hz)
(*) Steady state. (**) Total harmonic distortion between phases, no-load or on-load (non-distorting)
88 88
20 40 60 80 100 120 140 160 180 200 220kVA 40 80 120 160 200 240 280 320kVA
88 88
20 40 60 80 100 120 140 160 180 200 220kVA 40 80 120 160 200 240 280 320 360kVA
LSA 46.2 L6
96% P.F. : 1
95
94.9 95.2 94.8
94
93.3 92.4 P.F. : 0.8
92.5 93.1
92
92
91.4
90
88
40 80 120 160 200 240 280kVA
% Voltage dip
L9
15 VL12 15
VL12
10 10
5 5
0 0
0 50 100 150 200 250 300 350 kVA 0 50 100 150 200 250 300 350 kVA
kVA at φ 0.8 power factor kVA at φ 0.8 power factor
20 20
L9 L9
% Voltage rise
% Voltage rise
15 VL12 15 VL12
10 10
5 5
0 0
0 50 100 150 200 250 300 350 kVA 0 50 100 150 200 250 300 350 kVA
kVA at φ 0.8 power factor kVA at φ 0.8 power factor
25 25
% Voltage dip
20 20
% Voltage dip
15 15
12%
10 10
5 5
0 0
0 100 200 300 400 500 600 700 800kVA 0 100 200 300 400 500 600 700 800 900kVA
229
kVA at φ 0.6 power factor locked rotor kVA at φ 0.6 power factor locked rotor
1) For a starting P.F. other than 0.6, the starting kVA must be multiplied by K = Sine P.F. / 0.8
Calculation example for a different P.F. other than 0.6: Starter motor kVA calculated at 0.4 P.F. = 200 kVA
➤ Sin P.F. 0.4 = 0.9165 ➤ K = 1.145 ➤ kVA corrected = 229 kVA ➤ Voltage dip corresponding to VL12 = 12%.
2) For voltages other than 400V (Y), 230V (D) at 50 Hz, then kVA must be multiplied by (400/U)2 or (230/U)2.
88 88
40 80 120 160 200 240 280kVA 60 100 140 180 220 260 300 340 380kVA
88 88
40 80 120 160 200 240 280kVA 60 100 140 180 220 260 300 340 380 420kVA
LSA 46.2 L6
96% P.F. : 1
95
95 94.9
94 94.3
92.8 P.F. : 0.8
93 93.2
92 92.5
91.1
90 90.2
88
60 100 140 180 220 260 300 340kVA
20 L6 20
L6
L9
% Voltage dip
% Voltage dip
L9
15 15
VL12
VL12
10 10
5 5
0 0
0 50 100 150 200 250 300 350 400 kVA 0 50 100 150 200 250 300 350 400 kVA
kVA at φ 0.8 power factor kVA at φ 0.8 power factor
L6 L6
20 20
% Voltage rise
% Voltage rise
L9 L9
15 15
VL12 VL12
10 10
5 5
0 0
0 50 100 150 200 250 300 350 400 kVA 0 50 100 150 200 250 300 350 400 kVA
kVA at φ 0.8 power factor kVA at φ 0.8 power factor
25 25
20 20
% Voltage dip
% Voltage dip
15 15
10 10
10%
5 5
0 0
0 100 200 300 400 500 600 700 800 900 kVA 0 100 200 300 400 500 600 700 800 900 10001100kVA
229 kVA at φ 0.6 power factor locked rotor kVA at φ 0.6 power factor locked rotor
1) For a starting P.F. other than 0.6, the starting kVA must be multiplied by K = Sine P.F. / 0.8
Calculation example for a different P.F. other than 0.6: Starter motor kVA calculated at 0.4 P.F. = 200 kVA
➤ Sin P.F. 0.4 = 0.9165 ➤ K = 1.145 ➤ kVA corrected = 229 kVA ➤ Voltage dip corresponding to VL12 = 10%.
2) For voltages other than 480V (Y), 277V (D), 240V (YY) at 60 Hz, then kVA must be multiplied by (480/U)2 or (277/U)2 or (240/U)2.
10000
Symmetrical
LSA 46.2 M3
Asymmetrical
1000
Current (A)
AREP or PMG
100
SHUNT
10
1 10 100 1000 10000 time (ms)
10000
1000
Current (A)
AREP or PMG
100
SHUNT
10
1 10 100 1000 10000 time (ms)
10000
Symmetrical
LSA 46.2 L6 Asymmetrical
1000
AREP or PMG
Current (A)
100
SHUNT
10
1 10 100 1000 10000 time (ms)
10000
100
SHUNT
10
1 10 100 1000 10000 time (ms)
10000
Symmetrical
LSA 46.2 VL12
Asymmetrical
AREP or PMG
1000
Current (A)
100
SHUNT
10
1 10 100 1000 10000 time (ms)
L
Access to terminals
LB
568 Optional cable
AH Xg 566 33 Access to regulator 15° output
CF
13 Standard cable
output
485
PMG optional
- 0,050
Ø BX - 0,100
Ø N - 0,127
765
0
Ø 235
ØP
S DIA. Qty 12 as
280 - 1
0
Ø 512 shown on Ø M Ø 206
77
17
AIR 80
AIR OUTLET 2 holes INLET 457
235
185 Ø 21 170 527
6 Access to rotating diodes
6 C Y DIA, Qty X Eq. Sp. on Ø U.
Ø 120
Ø 115
Ø 115
Ø 110
Ø 104(46.2 M)
Ø 75
Ø 75
Ø 106(46.2 L)
Lr
Centre of gravity: Xr (mm), Rotor length: Lr (mm), Weight: M (kg), Moment of inertia: J (kgm2): (4J = MD2)
Flange S.A.E. 11 1/2 Flange S.A.E. 14
Type Xr Lr M J Xr Lr M J
LSA 46.2 M3 422 935 229 1.78 407 935 229.4 1.909
LSA 46.2 M5 434 935 245 1.948 419 935 245.3 2.077
LSA 46.2 L6 466 1045 278 2.329 451 1045 278.8 2.458
LSA 46.2 L9 485 1045 304.3 2.605 474 1045 304.9 2.724
LSA 46.2 VL12 540 1145 357 3.1 529 1145 357.6 3.216
NOTE : Dimensions are for information only and may be subject to modifications. Contractuel 2D drawings can be downloaded from the Leroy-
Somer site, 3D drawing files are available upon request.
485
PMG optional
Ø 511,175 - 0,127
12
765
+ 0,030
Ø 75 + 0,011
0
Ø 235
ØP
280 - 1
0
20
Ø 512
79,5
77
17
B 80
AIR OUTLET AIR Access to 457
145 BB INLET rotating diodes 527
6 C 6 holes Ø 21 235
M10 DIA, Qty 12 Eq. as shown
on Ø 530,225
105
Ø 120
Ø 115
Ø 110
Ø 115
Ø 104(46.2 M)
Ø 75
Ø 80
Ø 75
Ø 92
Ø 106(46.2 L)
Lr
Centre of gravity: Xr (mm), Rotor length: Lr (mm), Weight: M (kg), Moment of inertia: J (kgm2): (4J = MD2)
Type Xr Lr M J
LSA 46.2 M3 395 955 199.9 1.57
LSA 46.2 M5 404 955 215.8 1.738
LSA 46.2 L6 436 1065 247.6 2.109
LSA 46.2 L9 453 1065 273.7 2.385
LSA 46.2 VL12 502 1165 323.8 2.845
NOTE : Dimensions are for information only and may be subject to modifications. Contractuel 2D drawings can be downloaded from the Leroy-
Somer site, 3D drawing files are available upon request.
© Emerson 2014. The information contained in this brochure is for guidance only and does not
form part of any contract. The accuracy cannot be guaranteed as Emerson have an ongoing
process of development and reserve the right to change the specification of their products
without notice.