Low Voltage Alternator - 4 Pole: 410 To 660 kVA - 50 HZ / 510 To 825 kVA - 60 HZ Electrical and Mechanical Data
Low Voltage Alternator - 4 Pole: 410 To 660 kVA - 50 HZ / 510 To 825 kVA - 60 HZ Electrical and Mechanical Data
General characteristics
Insulation class H Excitation system 6-wire SHUNT AREP+ / PMG
Winding pitch 2/3 (wind.6S - 6-wire / wind.6 - 12-wire) AVR type R150 R180
Number of wires 6 (12 option) Excitation system 12-wire (option) SHUNT AREP+ / PMG
Protection IP 23 AVR type R150 R180
Altitude ≤ 1000 m Voltage regulation (**) ± 0.8 % ± 0.5 %
Overspeed 2250 R.P.M. Total Harmonic Distortion THD (***) in no-load < 1.5 %
Air flow 50 Hz 0.9 m3/s Total Harmonic Distortion THD (***) in linear load <5%
Air flow 60 Hz 1.1 m3/s Waveform: NEMA = TIF (***) < 50
AREP+/PMG Short-circuit current = 2.7 In : 5 seconds (*) Waveform: I.E.C. = THF (***) < 2%
(*) D350: 10 seconds (**) Steady state (***) Total harmonic distortion between phases, no-load or on-load (non-distorting)
98
98
96.0 95.9 96.5 96.5
96 95.4 95.2 96.2 96.1
94.8 96
95.1
94 94.8
94.0 94.1 95.4 95.1
93.2 94 94.4 94.4
92 92.8 94.1
90 kVA 92 kVA
0 100 200 300 400 500 0 100 200 300 400 500 600 700
98 98
96.3 96.3 96.2 96.5 96.5 96.4
95.8 96.0
96 96
90 kVA 90 kVA
0 100 200 300 400 500 600 0 100 200 300 400 500 600 700
98
98
96.0 96.3 96.2 96.1 96.8
96.5 96.6 96.5
96
96
93.8 94.9 94.9 94.8
94 95.6 95.5
94.4 94.2
95.0 94.8
93.1 94
92 94.2
90 kVA 92 kVA
0 100 200 300 400 500 600 0 200 400 600 800
A B C D E F A B C D E F
30% 30%
25% 25%
20% 20%
Voltage drop
Voltage drop
15% 15%
10% 10%
5% 5%
0% 0%
0 200 400 600 800 1000 1200 1400 1600 0 200 400 600 800 1000 1200 1400 1600 1800
Phase loading (SHUNT) - kVA at P.F. = 0.8 Phase loading (AREP+) - kVA at P.F. = 0.8
A A
B B
C D E F C D E F
30% 30%
25% 25%
20% 20%
Voltage rise
Voltage rise
15% 15%
10% 10%
5% 5%
0% 0%
0 200 400 600 800 1000 1200 1400 1600 0 200 400 600 800 1000 1200 1400 1600
Load shedding (SHUNT) - kVA at P.F. = 0.8 Load shedding (AREP+) - kVA at P.F. = 0.8
A BC D E F A B C D E F
30% 30%
25% 25%
20% 20%
Voltage drop
Voltage drop
15% 15%
10% 10%
5% 5%
0% 0%
0 200 400 600 800 1000 1200 1400 1600 0 200 400 600 800 1000 1200 1400 1600 1800
Motor starting (SHUNT) Motor starting (AREP+)
Locked rotor kVA at P.F. = 0.6 Locked rotor kVA at P.F. = 0.6
- For a starting P.F. other than 0.6, the starting kVA must be multiplied by K = Sine P.F. / 0.8
- For voltages other than 400V (Y), 230V (Δ) at 50 Hz, then kVA must be multiplied by (400/U)2 or (230/U)2.
- Transient performance of the PMG option, consult us.
98
98
95.7 95.8
96 95.4 95.3 96.1 96.4 96.2 96.1
93.9 96
94 94.5 94.3
94.2 95.2
93.5 95.1
93.2 93.1 94 94.6
92 94.3
93.7
90 kVA 92 kVA
0 100 200 300 400 500 600 0 200 400 600 800
98 98
96.2 96.1 96.3 96.4 96.4
96.0 95.7
96 95.3 96
98 98
96.6 96.5 96.5
96.1 96.1 96.1 96.2
96 95.5 96
94.1 95.4 95.4
94 94.8 95.1 94.9
92.9 94.6 94.5 94.4 94
93.6
92 92
92.3
90 kVA 90 kVA
0 200 400 600 800 0 200 400 600 800 1000
A B C D E F A B C D E F
30% 30%
25% 25%
20% 20%
Voltage drop
Voltage drop
15% 15%
10% 10%
5% 5%
0% 0%
0 200 400 600 800 1000 1200 1400 1600 1800 0 500 1000 1500 2000
Phase loading (SHUNT) - kVA at P.F. = 0.8 Phase loading (AREP+) - kVA at P.F. = 0.8
A A
BC D E F BC D E F
30% 30%
25% 25%
20% 20%
Voltage rise
Voltage rise
15% 15%
10% 10%
5% 5%
0% 0%
0 500 1000 1500 2000 0 500 1000 1500 2000
Load shedding (SHUNT) - kVA at P.F. = 0.8 Load shedding (AREP+) - kVA at P.F. = 0.8
A BC D E F A BC D E F
30% 30%
25% 25%
20% 20%
Voltage drop
Voltage drop
15% 15%
10% 10%
5% 5%
0% 0%
0 200 400 600 800 1000 1200 1400 1600 1800 0 500 1000 1500 2000
- For a starting P.F. other than 0.6, the starting kVA must be multiplied by K = Sine P.F. / 0.8
- For voltages other than 480V (Y), 277V (Δ), 240V (YY) at 60 Hz, then kVA must be multiplied by (480/U)2 or (277/U)2 or (240/U)2.
- Transient performance of the PMG option, consult us.
10000
AREP+
TAL 0473 A 1000
In
Symmetrical --------
Asymmetrical - - - 100
SHUNT
Current (A)
10
1
1 10 100 1000 5000
Time (ms)
10000
AREP+
1000
In
TAL 0473 B
100
Symmetrical -------- SHUNT
Asymmetrical - - -
Current (A)
10
1
1 10 100 1000 5000
Time (ms)
10000
AREP+
1000
In
TAL 0473 C
Asymmetrical - - - SHUNT
Current (A)
10
1
1 10 100 1000 5000
Time (ms)
10000
AREP+
TAL 0473 D 1000
In
Symmetrical --------
100
Asymmetrical - - -
SHUNT
Current (A)
10
1
1 10 100 1000 5000
Time (ms)
100000
10000
TAL 0473 E
AREP+
Symmetrical --------
1000 In
Asymmetrical - - -
100
SHUNT
Current (A)
10
1
1 10 100 1000 5000
Time (ms)
100000
10000
AREP+
TAL 0473 F 1000 In
Symmetrical --------
100
Asymmetrical - - - SHUNT
Current (A)
10
1
1 10 100 1000 5000
Time (ms)
Single-bearing dimensions
L
LB 568
Xg 43.3 Access to terminals Optional cable
506
ß output
AH 330 Standard cable
CF output
X holes Ø Y
Acces to regulator equidistant on Ø U
456
PMG optional
Ø N - 0.127
- 0.05
Ø BX - 0.15
811
Ø 616
0
Ø 235
ØP
Ø13
355 - 2
0
Ø 206
89.3
12
62
AIR OUTLET AIR INLET
180 40 50 610
28
Ø 125
Ø 130
Ø 115
Ø 110
Ø 75
Ø 88
Ø 75
Lr
Centre of gravity: Xr (mm), Rotor length: Lr (mm), Weight: M (kg), Moment of inertia: J (kgm2): (4J = MD2)
Flex plate S.A.E. 11 ½ S.A.E. 14 S.A.E. 18
Type Xr Lr M J Xr Lr M J Xr Lr M J
TAL 0473 A 436 1036 413 6.7 421 1023 414 6.77 411 1015 414 7.03
TAL 0473 B-C 473 1096 456 7.3 457 1083 456 7.41 447 1075 457 7.67
TAL 0473 D 502 1196 491 7.8 487 1183 492 7.88 477 1175 492 8.14
TAL 0473 E 533 1216 545 8.7 518 1203 546 8.83 508 1195 546 9.09
TAL 0473 F 544 1216 563 9.1 529 1203 564 9.18 519 1195 564 9.44
NOTE : Dimensions are for information only and may be subject to modifications. The torsional analysis of the transmission is imperative. All values are available
upon request.
Linkedin.com/company/leroy-somer
Twitter.com/Leroy_Somer_en
Facebook.com/LeroySomer.Nidec.en
YouTube.com/LeroySomerOfficiel
© Nidec 2020. The information contained in this brochure is for guidance only and does not form part of
any contract. The accuracy cannot be guaranteed as Nidec have an ongoing process of development
and reserve the right to change the specification of their products without notice.