Low Voltage Alternator - 4 Pole: 410 To 660 kVA - 50 HZ / 510 To 825 kVA - 60 HZ Electrical and Mechanical Data
Low Voltage Alternator - 4 Pole: 410 To 660 kVA - 50 HZ / 510 To 825 kVA - 60 HZ Electrical and Mechanical Data
Low Voltage Alternator - 4 Pole: 410 To 660 kVA - 50 HZ / 510 To 825 kVA - 60 HZ Electrical and Mechanical Data
General characteristics
Insulation class H Excitation system 6-wire SHUNT AREP / PMG
Winding pitch 2/3 (wind.6S - 6-wire / wind.6 - 12-wire) AVR type R150 R180
Number of wires 6 (12 option) Excitation system 12-wire (option) SHUNT AREP / PMG
Protection IP 23 AVR type R150 R180
Altitude ≤ 1000 m Voltage regulation (**) ± 0.8 % ± 0.5 %
Overspeed 2250 R.P.M. Total Harmonic Distortion THD (***) in no-load < 1.5 %
Air flow 50 Hz 0.9 m3/s Total Harmonic Distortion THD (***) in linear load <5%
Air flow 60 Hz 1.1 m3/s Waveform: NEMA = TIF (***) < 50
AREP/PMG Short-circuit current = 2.7 In : 5 seconds (*) Waveform: I.E.C. = THF (***) < 2%
(*) D350: 10 seconds (**) Steady state (***) Total harmonic distortion between phases, no-load or on-load (non-distorting)
TAL 047 B kVA 430 455 455 430 390 415 415 390 455 480 480 455 475 500 500 475
kW 344 364 364 344 312 332 332 312 364 384 384 364 380 400 400 380
TAL 047 C kVA 475 500 500 460 430 455 455 420 505 530 530 490 525 550 550 505
kW 380 400 400 368 344 364 364 336 404 424 424 392 420 440 440 404
TAL 047 D kVA 525 550 550 535 480 500 500 485 555 585 585 565 580 600 600 590
kW 420 440 440 428 384 400 400 388 444 468 468 452 464 480 480 472
TAL 047 E kVA 585 600 600 570 530 545 545 520 620 635 635 605 645 660 660 625
kW 468 480 480 456 424 436 436 416 496 508 508 484 516 528 528 500
TAL 047 F (**) kVA 645 660 660 620 585 600 600 565 685 700 700 655 710 730 730 680
kW 516 528 528 496 468 480 480 452 548 560 560 524 568 584 584 544
(*) 12-wire option (**) 6-wire only
TAL 047 B kVA 475 510 530 570 430 465 480 520 505 540 560 605 525 560 585 625
kW 380 408 424 456 344 372 384 416 404 432 448 484 420 448 468 500
TAL 047 C kVA 520 555 590 625 475 505 535 570 550 590 625 665 570 610 650 690
kW 416 444 472 500 380 404 428 456 440 472 500 532 456 488 520 552
TAL 047 D kVA 560 610 630 690 510 555 575 630 595 645 670 730 615 670 695 750
kW 448 488 504 552 408 444 460 504 476 516 536 584 492 536 556 600
TAL 047 E kVA 600 660 685 750 545 600 625 685 635 700 725 795 660 725 755 825
kW 480 528 548 600 436 480 500 548 508 560 580 636 528 580 604 660
TAL 047 F (**) kVA 650 715 755 825 590 650 685 750 690 760 800 875 720 785 830 910
kW 520 572 604 660 472 520 548 600 552 608 640 700 576 628 664 728
(*) 12-wire option (**) 6-wire only
%
TAL 047 A % TAL 047 D
100.0 100.0
A BC D E F A BC D E F
30% 30%
25% 25%
20% 20%
Voltage drop
Voltage drop
15% 15%
10% 10%
5% 5%
0% 0%
0 200 400 600 800 1000 1200 1400 0 200 400 600 800 1000 1200 1400
Phase loading (SHUNT) - kVA at P.F. = 0.8 Phase loading (AREP/PMG) - kVA at P.F. = 0.8
A BC D E F A BC D E F
30% 30%
25% 25%
20% 20%
Voltage rise
Voltage rise
15% 15%
10% 10%
5% 5%
0% 0%
0 200 400 600 800 1000 1200 1400 0 200 400 600 800 1000 1200 1400
Load shedding (SHUNT) - kVA at P.F. = 0.8 Load shedding (AREP/PMG) - kVA at P.F. = 0.8
A BC DE F A BC DE F
30% 30%
25% 25%
20% 20%
Voltage drop
Voltage drop
15% 15%
10% 10%
5% 5%
0% 0%
0 200 400 600 800 1000 1200 1400 0 200 400 600 800 1000 1200 1400
1) For a starting P.F. other than 0.6, the starting kVA must be multiplied by K = Sine P.F. / 0.8
2) For voltages other than 400V (Y), 230V (Δ) at 50 Hz, then kVA must be multiplied by (400/U)2 or (230/U)2.
%
TAL 047 A % TAL 047 D
100.0 100.0
97.5 97.5
96.2 96.5 96.5 96.4
95.6 95.9 95.7 95.5
95.0 95.0
94.2 95.3 95.3
93.4 94.8 94.6
94.3 94.2
93.6 92.5 93.6
92.5 93.2
92.6
A BC D E F A BC D E F
30% 30%
25% 25%
20% 20%
Voltage drop
Voltage drop
15% 15%
10% 10%
5% 5%
0% 0%
0 200 400 600 800 1000 1200 1400 1600 1800 0 200 400 600 800 1000 1200 1400 1600 1800
Phase loading (SHUNT) - kVA at P.F. = 0.8 Phase loading (AREP/PMG) - kVA at P.F. = 0.8
A BC D E F A BC D E F
30% 30%
25% 25%
20% 20%
Voltage rise
Voltage rise
15% 15%
10% 10%
5% 5%
0% 0%
0 200 400 600 800 1000 1200 1400 1600 1800 0 200 400 600 800 1000 1200 1400 1600 1800
Load shedding (SHUNT) - kVA at P.F. = 0.8 Load shedding (AREP/PMG) - kVA at P.F. = 0.8
A BC DE F A BC DE F
30% 30%
25% 25%
20% 20%
Voltage drop
Voltage drop
15% 15%
10% 10%
5% 5%
0% 0%
0 200 400 600 800 1000 1200 1400 1600 1800 0 200 400 600 800 1000 1200 1400 1600 1800
1) For a starting P.F. other than 0.6, the starting kVA must be multiplied by K = Sine P.F. / 0.8
2) For voltages other than 480V (Y), 277V (Δ), 240V (YY) at 60 Hz, then kVA must be multiplied by (480/U)2 or (277/U)2 or (240/U)2.
10000
TAL 047 A
1000
AREP
Symmetrical -------- In In
Asymmetrical - - -
100
Current (A)
SHUNT
10
1
1 10 100 1000
Time (ms)
10000
TAL 047 B
AREP
1000
Symmetrical -------- In In
Asymmetrical - - -
100
Current (A)
SHUNT
10
1
1 10 100 1000
Time (ms)
10000
TAL 047 C
AREP
1000
In In
Symmetrical --------
Asymmetrical - - -
100
Current (A)
SHUNT
10
1
1 10 100 1000
Time (ms)
100000
TAL 047 D
10000
Symmetrical --------
Asymmetrical - - - AREP
1000
Current (A)
In In
100
SHUNT
10
1 10 100 1000
Time (ms)
100000
100000
TAL 047 E
10000
10000
Symmetrical --------
Asymmetrical - - - AREP
1000
1000
In
Current (A)
In In
100
100
SHUNT
1010
1 10 100 1000
1 10 100 1000
Time (ms)
100000
100
SHUNT
10
1
1 10 100 1000
Time (ms)
Single-bearing dimensions
L
568 (6-wire)
LB
740 (12-wire)
Xg 506 (6-wire) Access to regulator Optional cable
44.7 49
560 (12-wire) ß output
AH 330
Standard cable output
CF
512 (12-wire)
Y DIA, Qty X Eq. Sp.
456 (6-wire)
on Ø U P.C.D.
PMG optional
867 (12-wire)
811 (6-wire)
- 0.050
Ø BX - 0.100
Ø N - 0.127
Ø 616
Ø 235
ØP
0
355 - 1
0
Ø 206
12
89.3
62
AIR OUTLET AIR INLET
180 40 50 610
28
Ø 120
Ø 115
Ø 110
Ø 115
Ø 75
Ø 75
Lr
Centre of gravity: Xr (mm), Rotor length: Lr (mm), Weight: M (kg), Moment of inertia: J (kgm2): (4J = MD2)
Flex plate S.A.E. 14 S.A.E. 18
Type Xr Lr M J Xr Lr M J
TAL 047 A 418.3 1020 374.9 5.92 408.5 1020 376 6.18
TAL 047 B 456 1080 426.6 6.77 446 1080 427.7 7.03
TAL 047 C 456 1080 426.6 6.77 446 1080 427.7 7.03
TAL 047 D 496 1180 477 7.5 486 1180 478.1 7.76
TAL 047 E 507 1180 493.8 7.8 497 1180 494.9 8.06
TAL 047 F 528 1200 525.2 8.32 518 1200 526.3 8.58
NOTE : Dimensions are for information only and may be subject to modifications. The torsional analysis of the transmission is imperative. All values are available
upon request.
Linkedin.com/company/leroy-somer
Twitter.com/Leroy_Somer_en
Facebook.com/LeroySomer.Nidec.en
YouTube.com/LeroySomerOfficiel
© Nidec 2020. The information contained in this brochure is for guidance only and does not form part of
any contract. The accuracy cannot be guaranteed as Nidec have an ongoing process of development
and reserve the right to change the specification of their products without notice.