Piping Cleat Loads
Piping Cleat Loads
Piping Cleat Loads
7" gap
2"
3"
7"
3"
1.5"
1" gap
Insulation Thickness t=
Gap between Insulation and Bracket g=
Location of Bolt Center for ISMC-250 from Equipment shell Cl. Bolt =
Table below shows platform cleat load for a maximum arc length of 6 ft for ISMC250 & C
1 PS-U710-060 F08
2 PS-U710-121 F09
PS-U710-058 AB BEAM
PS-U710-058 AB V. BRACE
PS-U710-056 V. BRACE
5 PS-U710-050 A09
6 PS-U710-052 A10
PS-U710-048 AB V. BRACE
8 PS-U710-045 K02
9 PS-U710-044 K03
11
12 PS-U710-064 C09
3"
2"
2.
= 75
= "
13/16" dia - 4 nos of bolt
holes.
Bracing Angle with
Vertical- "α".
3"
Lc 1.5"
7.75
2.50 in
1.00 in
5.00 in
45.00 degrees
7.75 in
F
x
Fy
1.127 m = 3.70
Cut-Tee UB
- - 3.18 3.18 - - - 203x133x30
Cut-Tee UB
- - 1.03 0.78 - - - 203x133x30
Cut-Tee UB
- - 0.37 0.32 - - - 203x133x30
Cut-Tee UB
- - 2.55 2.49 - - - 203x133x30
UC152x152x30
UC152x152x30
UB 203x133x30
Cut-Tee UB
203x133x30
Cut-Tee UB
203x133x30
UC152x152x30
UC152x152x30
Cut-Tee UB
203x133x30
UC152x152x30
UC152x152x30
ISMC 200 X 75
Cut-Tee UB
203x133x30
UC152x152x30
PS-U710-048 AB
Horizontal Vertical Horizontal Moment
Node L/C Fx kip Fy kip Fz kip Mx kip-ft My kip-ft Mz kip-ft
1 1 DL OF STRUCTUR -0.103 0.042 0 0 0 0
2 SUSTAIN -2.128 0.277 0 0 0 0
3 WNC (EMPTY) -2.128 0.277 0 0 0 0
4 HYDROTEST -2.97 0.387 0 0 0 0
5 THERMAL -7.35 0.735 -0.035 0 0 0
6 SEISMIC -0.485 0.049 -0.015 0 0 0
7 WIND -0.788 0.044 -0.089 0 0 0
4 1 DL OF STRUCTUR -0.103 0.042 0 0 0 0
2 SUSTAIN -2.138 0.279 0 0 0 0
3 WNC (EMPTY) -2.138 0.279 0 0 0 0
4 HYDROTEST -2.981 0.388 0 0 0 0
5 THERMAL -6.993 0.727 -0.034 0 0 0
6 SEISMIC -0.324 0.044 -0.015 0 0 0
7 WIND -0.151 0.049 -0.089 0 0 0
PS-U710-041-115