90-01KO
Anti-Cavitation
Pressure Reducing Valve
• Virtually Cavitation Free Operation
• Sensitive and Accurate Pressure Control
• Easy Adjustment and Maintenance
• Optional Check Feature
• Fully Supported Frictionless Diaphragm
The Cla-Val Model 90-01KO Anti-Cavitation Hytrol Pressure Reducing
Valve automatically reduces a higher inlet pressure to a steady lower down-
stream pressure, regardless of changing flow rate and/or varying inlet pres-
sure. This valve is an accurate, pilot-operated regulator capable of holding
downstream pressure to a pre-determined limit. When downstream pres-
sure exceeds the pressure setting of the control pilot, the main valve and
Schematic Diagram pilot valve close drip-tight.
Item Description
1 100-01KO Hytrol Main Valve If a check feature is added, and a pressure reversal occurs, the down-
2 X58 Restriction Fitting stream pressure is admitted in the main valve cover chamber, closing the
3 CRD Pressure Reducing Control valve to prevent return flow.
Optional Features
Item Description
A X46A Flow Clean Strainer
B CK2 Isolation Valve
C CV Flow Control (Closing)*
D Check Valves with Isolation Valve
P X141 Pressure Gauge
S CV Speed Control (Opening)
V X101 Valve Position Indicator
Y X43 "Y" Strainer
H X43H Strainer For space savings, see
Cla-Val Model 90-48 or
90-99 with integral Low
*The closing speed control (optional) on this valve should Flow Bypass Pressure
always be open at least three (3) turns off its seat. Regulator.
Typical Applications
Typical applications include pressure reducing valve station using Cla-Val Model 90-01KO provides optimum downstream pressure
Model 90-01BYKO and Model 90-01ASKO in parallel to handle wide control while reducing noise and eliminating damage associated
range of flow rates. Larger valve meets requirements of peak loads. with cavitation. See Cavitation Guide to determine if the valve is a
The smaller valve handles low flows. A downstream pressure relief candidate for the KO Anti-Cavitation Trim. A downstream pressure
relief valve is recommended for this type of application.
valve is recommened for this type of application.
Upper Isolation
High Gauge Zone Valve
Pressure Gauge
X43H Strainer
CLA-VAL 90-01BYKO/ CLA-VAL Model
690-01BYKO 50-01/650-01
Pressure Relief/
Pressure Reducing Valve Pressure Sustaining Valve
X43H Strainer
100
PRESSURE DROP (psi)
20"
1 1/2" 36"
4" 8" 12" 18" 30"
24"
2" 2 1/2" 3" 6" 10" 14"16"
1 1/4"
10
1"
1
10 100 1000 10000 100000
FLOW RATE (gpm)
Notes: On Operating Differential
1. For atmospheric discharge, the maximum inlet pressure cannot exceed 150 psi.
2. For pressure differentials greater than 300 psi, the maximum flow velocity should not exceed 18 ft/sec.
3. Flow velocities greater than 25 ft/sec are not recommended.
4. Recommended minimum flow velocity is 1 ft/sec.
5. Consult factory for conditions exceeding these recommendations.
SELECTION GUIDELINE FOR KO ANTI-CAVITATION VALVES
400
350
Cavitation
Zone
300
INLET PRESSURE (psi)
250
200
150
100
50
B (Diameter)
J
100-01KO
Threaded &
Flanged K
X
H
C
(MAX)
Inlet Outlet
G E F
GG FF
GGG
Inlet D
DD
B (Diameter)
J
100-01KO
Grooved
K X
H CC
(MAX)
Y
Inlet Outlet
EE
GGGG Note:
Consult Factory on 10",12",
Z
Inlet DDDD 16" angle pattern
AAAA
Cla-Val Control Valves with KO ANTI-CAVITATION Trim operate with maximum efficiency when mounted in horizontal piping with the main valve cover Up. We recommend isolation valves
be installed on inlet and outlet for maintenance. Adequate space above and around the valve for service personnel should be considered essential. A regular maintenance program should
be established based on the specific application data. However, we recommend a thorough inspection be done at least once a year. Consult factory for specific recommendations.
90-01KO 100-01KO Pattern: Globe (G), Angle (A), End Connections: Threaded (T), Grooved (GR), Flanged (F) Indicate Available Sizes
Functional Data
Inches 1 11⁄4 11⁄2 2 21⁄2 3 4 6 8 10 12 14 16 18 20 24 30 36
Valve Size
mm. 25 32 40 50 65 80 100 150 200 250 300 350 400 450 500 600 750 900
Gal./Min. (gpm.) 14 14 14 25 37 52 90 218 362 660 810 1100 1200 1550 1950 3900 6100 9150
Globe
CV Pattern Litres/Sec. (l/s.) 3.4 3.4 3.4 6.0 8.9 12.5 21.6 52 87 159 194 264 288 360 469 938 1466 2199
Factor Gal./Min. (gpm.) — 15 15 26 39 55 95 232 388 479 790 1075 1175 — — — — —
Angle
Pattern Litres/Sec. (l/s.) — 3.6 3.6 6.2 9.4 13.2 22.8 56 93 115 190 258 282 — — — — —
Feet (ft.) 196 196 196 237 277 416 572 858 1315 2444 2118 1937 3022 3537 4199 4532 3897 3954
Equivalent Globe
Length of Pattern Meters (m.) 60 60 60 72 84 127 174 262 401 745 646 590 921 1078 1280 1381 1188 1205
Pipe Feet (ft.) — 171 171 219 250 372 514 757 1145 2133 2226 2021 3152 — — — — —
Angle
Pattern Meters (m.) — 52 52 67 76 113 157 231 349 650 678 616 961 — — — — —
Globe Pattern 30.6 30.6 30.6 26.1 24.3 29.3 29.0 25.5 27.7 41.0 27.7 22.8 31.4 30.2 29.5 28.9 17.6 15.1
K Factor
Angle Pattern — 26.7 26.7 24.1 21.8 26.2 26.0 22.5 24.1 35.8 29.1 23.8 32.8 — — — — —
Liquid Displaced from
U.S. Gal. 0.2 0.2 0.2 .03 .04 .08 .17 .53 1.26 2.5 4.0 6.5 9.6 11 12 29 65 90
Cover Chamber When
Valve Opens Litres 0.8 0.8 0.8 .12 .16 .30 .64 2.0 4.8 9.5 15.1 25.6 36.2 41.6 45.4 110 246 340
For assistance in selecting appropriate valve options or valves manufactured with special design requirements, please contact our Regional Sales Office or Factory.
C V Factor Where:
Formulas for computing CV Factor, Flow (Q) and Pressure Drop ( P): C V = U.S. (gpm) @ 1 psi differential at 60 F water
2 or
Q Q = (l/s) @ 1 bar (14.5 PSIG) differential
CV = Q = CV P P= C at 15 C water
P V
d = inside pipe diameter of Schedule 40 Steel Pipe (inches)
K Factor (Resistance Coefficient) 4
The Value of K is calculated from the formula: K = 894d f = friction factor for clean, new Schedule 40 pipe
(U.S. system units) Cv 2 (dimensionless) (from Cameron Hydraulic Data,