MODEL

129-01
Modulating Float Valve
• Accurate and Repeatable Level Control
• Proportional Flow
• Reliable Hydraulic Operation
• Completely Automatic Operation
The Cla-Val Model 129-01 Float Valve maintains a relatively constant
level in storage tanks and reservoirs by admitting flow into the tank in
direct proportion to the flow out of the tank. It is a hydraulically
operated, pilot controlled, diaphragm valve. The rotary disc type float
operated pilot control is installed at the high liquid level in the reservoir
and is connected via tubing or pipe to the main valve. As the liquid
level changes, the float control proportionally opens or closes the
main valve, keeping the liquid level nearly constant. If the check
feature option "D" is added and a pressure reversal occurs, the
downstream pressure is admitted into the main valve cover chamber
and the valve closes to prevent return flow.

Schematic Diagram
Item Description
1 100-01 Hytrol Main Valve
2 X47A Ejector
3 Bell Reducer
4 CFM2 Float Control

Optional Features
Item Description
A X46A Flow Cleaner Strainer
B CK2 Isolation Valve
C CV Flow Control (Closing)
D Check Valves With Isolation Valve
SUD

F Independent Operating Pressure see page 3 for


P X141 Pressure Gauge approvals
S CV Speed Control (Opening)
V X101 Valve Position Indicator
Y X43 “Y” Strainer

Typical Applications Float Control

Control Piping
(Not Furnished)
CLA-VAL
129-01/629-01 TANK

Isolation

Piping and Tank Sizing Filter Liquid Level Control


Valves

Install valve and control as shown in the diagram above. The Maintains constant level in rapid sand filter.
float control should be located in a still liquid surface. If it is Usually requires the use of an independent
necessary to obtain this condition, a stilling well should be operating pressure as shown.
constructed. Mount the float control on the connecting piping
with the outlet port at the desired high water level. When a DO NOT USE FOR ON-OFF SERVICE.
separate source of supply pressure (Option F) is used by the pilot
control system, that pressure must at all times be constant and Note: We recommend protecting tubing and
equal to or greater than the pressure at the valve inlet. valve from freezing temperatures.
Model 129-01 (Uses the 100-01 Hytrol Main Valve)
Pressure Ratings (Recommended Maximum Pressure - psi)
Pressure Class
Valve Body & Cover
B (Diameter)
Flanged Grooved Threaded J
100-01
ANSI 150 300 300 End‡
Grade Material
Standards* Class Class Class Details
Threaded &
Flanged K
X
ASTM A536 Ductile Iron B16.42 250 400 400 400 H
C
ASTM A216-WCB Cast Steel B16.5 285 400 400 400
(MAX)

UNS 87850 Bronze B16.24 225 400 400 400


Inlet Outlet

Note: * ANSI standards are for flange dimensions only. G E F


Flanged valves are available faced but not drilled. GG
‡ End Details machined to ANSI B2.1 specifications.
FF
Valves for higher pressure are available; consult factory for details
GGG
Inlet D
Materials
A DD
AA DDD
Component Standard Material Combinations
AAA
Body & Cover Ductile Iron Cast Steel Bronze
Available Sizes (inches) 1" - 36" 1" - 16" 1" - 16"
Available Sizes (mm) 25 - 900 mm 25 - 400 mm 25 - 400 mm
Disc Retainer &
Cast Iron Cast Steel Bronze
Y
Diaphragm Washer
Trim: Disc Guide, Bronze is Standard
Seat & Cover Bearing Stainless Steel is Optional
Disc Buna-N® Rubber
Diaphragm Nylon Reinforced Buna-N® Rubber Z
Stem, Nut & Spring Stainless Steel
For material options not listed, consult factory.
Cla-Val manufactures valves in more than 50 different alloys.

Model 129-01 Dimensions (Inches) Important Notice: Do Not Oversize


Note: The top two flange holes on valve
size 36 are threaded to 1 1/2"-6 UNC.

Valve Size (Inches) 1 1 1⁄ 4 1 1⁄ 2 2 2 1⁄ 2 3 4 6 8 10 12 14 16 18 20 24 30 36


A Threaded 7.25 7.25 7.25 9.38 11.00 12.50 — — — — — — — — — — — —
AA 150 ANSI — — 8.50 9.38 11.00 12.00 15.00 20.00 25.38 29.75 34.00 39.00 41.38 46.00 52.00 61.50 63.00 72.75
AAA 300 ANSI — — 9.00 10.00 11.62 13.25 15.62 21.00 26.38 31.12 35.50 40.50 43.50 47.64 53.62 63.24 64.50 74.75
AAAA Grooved End — — 8.50 9.00 11.00 12.50 15.00 20.00 25.38 — — — — — — — — —
B Diameter 5.62 5.62 5.62 6.62 8.00 9.12 11.50 15.75 20.00 23.62 28.00 32.75 35.50 41.50 45.00 53.16 56.00 66.00
C Maximum 5.50 5.50 5.50 6.50 7.56 8.19 10.62 13.38 16.00 17.12 20.88 24.19 25.00 39.06 41.90 43.93 54.60 59.00
CC Maximum Grooved End — — 4.75 5.75 6.88 7.25 9.31 12.12 14.62 — — — — — — — — —
D Threaded 3.25 3.25 3.25 4.75 5.50 6.25 — — — — — — — — — — — —
DD 150 ANSI — — 4.00 4.75 5.50 6.00 7.50 10.00 12.69 14.88 17.00 19.50 20.81 — — 30.75 — —
DDD 300 ANSI — — 4.25 5.00 5.88 6.38 7.88 10.50 13.25 15.56 17.75 20.25 21.62 — — 31.62 — —
DDDD Grooved End — — — 4.75 — 6.00 7.50 — — — — — — — — — — —
E 1.12 1.12 1.12 1.50 1.69 2.06 3.19 4.31 5.31 9.25 10.75 12.62 15.50 12.95 15.00 17.75 21.31 24.56
EE Grooved End — — 2.00 2.50 2.88 3.12 4.25 6.00 7.56 — — — — — — — — —
F 150 ANSI — — 2.50 3.00 3.50 3.75 4.50 5.50 6.75 8.00 9.50 10.50 11.75 15.00 16.50 19.25 22.50 28.50
FF 300 ANSI — — 3.06 3.25 3.75 4.13 5.00 6.25 7.50 8.75 10.25 11.50 12.75 15.00 16.50 19.25 24.00 30.00
G Threaded 1.88 1.88 1.88 3.25 4.00 4.50 — — — — — — — — — — — —
GG 150 ANSI — — 4.00 3.25 4.00 4.00 5.00 6.00 8.00 8.62 13.75 14.88 15.69 — — 22.06 — —
GGG 300 ANSI — — 4.25 3.50 4.31 4.38 5.31 6.50 8.50 9.31 14.50 15.62 16.50 — — 22.90 — —
GGGG Grooved End — — — 3.25 — 4.25 5.00 — — — — — — — — — — —
H NPT Body Tapping 0.375 0.375 0.375 0.375 0.50 0.50 0.75 0.75 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 2.00 2.00
J NPT Cover Center Plug 0.25 0.25 0.25 0.50 0.50 0.50 0.75 0.75 1.00 1.00 1.25 1.50 2.00 1.00 1.00 1.00 2.00 2.00
K NPT Cover Tapping 0.375 0.375 0.375 0.375 0.50 0.50 0.75 0.75 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 2.00 2.00
Stem Travel 0.40 0.40 0.40 0.60 0.70 0.80 1.10 1.70 2.30 2.80 3.40 4.00 4.50 5.10 5.63 6.75 7.50 8.50
Approx. Ship Weight (lbs) 15 15 15 35 50 70 140 285 500 780 1165 1600 2265 2982 3900 6200 7703 11720
Approx. X Pilot System 11 11 11 13 14 15 17 29 31 33 36 40 40 43 47 68 79 85
Approx. Y Pilot System 9 9 9 9 10 11 12 20 22 24 26 29 30 32 34 39 40 45
Approx. Z Pilot System 9 9 9 9 10 11 12 20 22 24 26 29 30 32 34 39 42 47
Model 129-01 Metric Dimensions (Uses the 100-01 Hytrol Main Valve)

B (Diameter) Valve & Pilot Approvals


NSF/ANSI 372: National Lead Free
J
100-01
Threaded & Mandate “Reduction of Lead in
Drinking Water Act”
Flanged K
X
H
NSF International recognizes Cla-Val
C
as complying with NSF/ANSI 61 and
(MAX)

all applicable requirements.


Inlet Outlet

G E F
GG Cla-Val fulfills the requirements
described in the American Water
FF

Works Association’s (AWWA)


GGG

Standard for Pilot-Operated Control


Inlet D
Valves: C530:12
A DD
AA DDD
AAA

SUD

Model 129-01 Dimensions (mm)


Note: The top two flange holes on valve
Important Notice: Do Not Oversize size 36 are threaded to 1 1/2"-6 UNC.

Valve Size (mm) 25 32 40 50 65 80 100 150 200 250 300 350 400 450 500 600 750 900
A Threaded 184 184 184 238 279 318 — — — — — — — — — — — —
AA 150 ANSI — — 216 238 279 305 381 508 645 756 864 991 1051 1168 1321 1562 1600 1848
AAA 300 ANSI — — 229 254 295 337 397 533 670 790 902 1029 1105 1210 1326 1606 1638 1899
AAAA Grooved End — — 216 228 279 318 381 508 645 — — — — — — — — —
B Diameter 143 143 143 168 203 232 292 400 508 600 711 832 902 1054 1143 1350 1422 1676
C Maximum 140 140 140 165 192 208 270 340 406 435 530 614 635 992 1064 1116 1387 1499
CC Maximum Grooved End — — 120 146 175 184 236 308 371 — — — — — — — — —
D Threaded 83 83 83 121 140 159 — — — — — — — — — — — —
DD 150 ANSI — — 102 121 140 152 191 254 322 378 432 495 528 — — 781 — —
DDD 300 ANSI — — 108 127 149 162 200 267 337 395 451 514 549 — — 803 — —
DDDD Grooved End — — — 121 — 152 191 — — — — — — — — — — —
E 29 29 29 38 43 52 81 110 135 235 273 321 394 329 381 451 541 624
EE Grooved End — — 52 64 73 79 108 152 192 — — — — — — — — —
F 150 ANSI — — 64 76 89 95 114 140 171 203 241 267 298 381 419 489 572 724
FF 300 ANSI — — 78 83 95 105 127 159 191 222 260 292 324 381 419 489 610 762
G Threaded 48 48 48 83 102 114 — — — — — — — — — — — —
GG 150 ANSI — — 102 83 102 102 127 152 203 219 349 378 399 — — 560 — —
GGG 300 ANSI — — 102 89 110 111 135 165 216 236 368 397 419 — — 582 — —
GGGG Grooved End — — — 83 — 108 127 — — — — — — — — — — —
H NPT Body Tapping 0.375 0.375 0.375 0.375 0.50 0.50 0.75 0.75 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 2.00 2.00
J NPT Cover Center Plug 0.25 0.25 0.25 0.50 0.50 0.50 0.75 0.75 1.00 1.00 1.25 1.50 2.00 1.00 1.00 1.00 2.00 2.00
K NPT Cover Tapping 0.375 0.375 0.375 0.375 0.50 0.50 0.75 0.75 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 2.00 2.00
Stem Travel 10 10 10 15 18 20 28 43 58 71 86 102 114 130 143 171 190 216
Approx. Ship Weight (kgs) 7 7 7 16 23 32 64 129 227 354 528 726 1027 1353 1769 2812 3494 5316
Approx. X Pilot System 280 280 280 331 356 381 432 737 788 839 915 1016 1016 1093 1194 1728 2007 2159
Approx. Y Pilot System 229 229 229 229 254 280 305 508 559 610 661 737 762 813 864 991 1016 1143
Approx. Z Pilot System 229 229 229 229 254 280 305 508 559 610 661 737 762 813 864 991 1067 1194
100-01 Pattern: Globe (G), Angle (A), End Connections: Threaded (T), Grooved (GR), Flanged (F) Indicate Available Sizes

129-01 Inches 1 11⁄4 11⁄2 2 21⁄2 3 4 6 8 10 12 14 16 18 20 24 30 36


Valve
Selection
mm 25 32 40 50 65 80 100 150 200 250 300 350 400 450 500 600 750 900

Pattern G, A G, A G, A G, A G, A G, A G, A G, A G, A G, A G, A G, A G, A G G G, A G G
Main Valve
100-01 T, F, T, F, T, F, T, F, F, F, F,
End Detail T T F F F F F F F F F
Gr* Gr Gr* Gr Gr Gr* Gr*

Suggested
Flow Maximum 55 93 125 210 300 460 800 1800 3100 4900 7000 8400 11000 14000 17000 25000 42000 50000
(gpm)

Suggested
Flow Maximum 3.5 6 8 13 19 29 50 113 195 309 442 530 694 883 1073 1577 2650 3150
(Liters/Sec)

100-01 Series is the full internal port Hytrol. *Globe Grooved Only

Pilot System Specifications


Pressure Rating Optional Materials
Maximum: 300 psi Aluminum, Bronze and Stainless Steel

Temperature Range
Water: to 180°F/82°C Control Piping (customer supplied)
Use either copper tubing or brass pipe
between CFM2 Float Control and the main
Materials valve pilot system.
Pilot Control System: 1/2" dia. for distances less than 25 feet;
Low Lead Materials with 3/4" dia. for greater distances.
303 Stainless Steel Trim, Bronze
fittings and copper tubing.

CFM2 FLOAT CONTROL


30º Max. Ball Travel Up
Inlet (Closed)
Supply
1/2" NPT
From Valve
Pilot Systems

1.50
4" DIA.

When Ordering,
Please Specify
.94

8.00 –
+ .06

1. Catalog No. 129-01


Standard

2. Valve Size
30º Max. Ball Travel Down

3. Pattern - Globe or Angle


(Open)

4. Pressure Class
5. Threaded or Flanged
6. Materials Desired
7. Desired Options
8. When Vertically Installed

CLA-VAL 1701 Placentia Ave • Costa Mesa CA 92627 • Phone: 949-722-4800 • Fax: 949-548-5441 • E-mail: info@cla-val.com • www.cla-val.com