Float Valve: (Sizes 1/2"-6" / 15 - 150 MM)

Download as pdf or txt
Download as pdf or txt
You are on page 1of 4

MODEL 124-01

(Sizes 1/2"-6" / 15 - 150 mm)

Float Valve
• Accurate and Repeatable Level Control
• On-Off or Non-Modulating Action
• Fully Adjustable High and Low Level Settings
• Simple Design, Proven Reliable
• Easy Installation and Maintenance
The Cla-Val Model 124-01 Float Valve is a non-modulating valve that accurately
controls the liquid level in tanks. This valve is designed to open fully when the
liquid level reaches a pre-set low point and close drip-tight when the level
reaches a preset high point.
This is a hydraulically operated, diaphragm valve with the pilot control and float
mechanism mounted on the cover of the main valve. The float positions the pilot
control to close the valve when the float contacts the upper stop. The high and
low liquid levels are adjusted by positioning the stop collars on the float rod. The
difference between high and low levels can be adjusted to as little as 1" (25 mm),
or to as much as 18" (450 mm).
Level settings can be as much as eleven and one half feet below the valve. The
Schematic Diagram float mechanism may be located remotely from the main valve. See the technical
data sheet on Model CF1-C1 Float Control for additional information.
Item Description
1 100-01 Hytrol Main Valve
2 CF1-C1 Float Control

Optional Features
Item Description
A X46A Flow Clean Strainer
B CK2 Isolation Valve
C CV Flow Control (Closing)
F Independent Operating Pressure
P X141 Pressure Gauge
S CV Speed Control (Opening)
V X101 Valve Position Indicator
Y X43 "Y" Strainer

Typical Application Installation


The Model 124-01 Float Valve is A stilling well (8" / 300mm minimum diameter)
commonly mounted above the high must be provided around the float. When the
Float Valve water level in a tank. Globe pattern valve is mounted on top of the tank roof, a 2"
valves are supplied standard with the (50mm) clearance hole should be provided for
float control mounted on the cover as side movement of the float rod where the rod goes
illustrated, with a horizontal discharge. through the top of the tank.
Angle pattern valves are configured to
discharge downward. A clear independent source of air or water may be
used to operate the valve (option F). The pressure
from this independent source must at all times be
Notes: equal to or greater than pressure at the valve
Tank
1. We recommend protecting tubing inlet.If minimum flowing line pressure is less than
Supply
Stilling Well
and valve from freezing 10 psi, consult factory.
temperatures. If the float control is remotely mounted from the
2. Must be inspected periodically. main valve, the control may be installed at any
elevation above the valve, provided the flowing
line pressure in psi is greater than the vertical
distance in feet between the valve and the float
control. See the technical data sheet on Model
CF1-C1 for additional information.
Model 124-01 (Uses 100-01 Hytrol Main Valve)
B (Diameter)
J
Pressure Ratings (Recommended Maximum Pressure - psi)
100-01
Threaded &
Pressure Class Flanged K
X
Valve Body & Cover H
Flanged Grooved Threaded C
(MAX)

ANSI 150 300 300 End‡ Inlet Outlet


Grade Material
Standards* Class Class Class Details

ASTM A536 Ductile Iron B16.42 250 400 400 400 G E F


GG FF
ASTM A216-WCB Cast Steel B16.5 285 400 400 400 GGG

UNS 87850 Bronze B16.24 225 400 400 400


Inlet D
A DD
AA DDD
Note: * ANSI standards are for flange dimensions only. AAA
Flanged valves are available faced but not drilled.
‡ End Details machined to ANSI B2.1 specifications.
Valves for higher pressure are available; consult factory for details
Y

Materials
Component Standard Material Combinations Z
Body & Cover Ductile Iron Cast Steel Bronze
Available Sizes (inches) 1
⁄2" - 6" 1
⁄2" - 6" 1
⁄2" - 6"

Available Sizes (mm) 15 - 150 15 - 150 15 - 150 B (Diameter)


J
Disc Retainer & 100-01
Diaphragm Washer Cast Iron Cast Steel Bronze Grooved
K
Trim: Disc Guide, Bronze is Standard H
Seat & Cover Bearing CC
Stainless Steel is Optional (MAX)

Disc Buna-N Rubber®


Inlet Outlet
Diaphragm Nylon Reinforced Buna-N® Rubber
Stem, Nut & Spring Stainless Steel EE
For material options not listed, consult factory. GGGG
Cla-Val manufactures valves in more than 50 different alloys. Inlet DDDD
AAAA
Model 124-01 Dimensions (inches)
Valve Size (Inches) 1⁄ 2 * 3⁄ 4 * 1* 1 1 1⁄4 1 1⁄ 2 2 2 1⁄ 2 3 4 6
A Threaded 3.50 3.50 5.12 7.25 7.25 7.25 9.38 11.00 12.50 — —
AA 150 ANSI — — — — — 8.50 9.38 11.00 12.00 15.00 20.00
AAA 300 ANSI — — — — — 9.00 10.00 11.62 13.25 15.62 21.00
AAAA Grooved End — — — — — 8.50 9.00 11.00 12.50 15.00 20.00
B Diameter 3.12 3.12 4.38 5.62 5.62 5.62 6.62 8.00 9.12 11.50 15.75
C Maximum 5.88 5.88 6.25 5.50 5.50 5.50 6.50 7.56 8.19 10.62 13.38
CC Maximum Grooved End — — — — — 4.75 5.75 6.88 7.25 9.31 12.12
D Threaded — — — 3.25 3.25 3.25 4.75 5.50 6.25 — —
DD 150 ANSI — — — — — 4.00 4.75 5.50 6.00 7.50 10.00
DDD 300 ANSI — — — — — 4.25 5.00 5.88 6.38 7.88 10.50
DDDD Grooved End — — — — — — 4.75 — 6.00 7.50 —
E 0.88 0.88 1.63 1.12 1.12 1.12 1.50 1.69 2.06 3.19 4.31
EE Grooved End — — — — — 2.00 2.50 2.88 3.12 4.25 6.00
F 150 ANSI — — — — — 2.50 3.00 3.50 3.75 4.50 5.50
FF 300 ANSI — — — — — 3.06 3.25 3.75 4.13 5.00 6.25
G Threaded — — — 1.88 1.88 1.88 3.25 4.00 4.50 — —
GG 150 ANSI — — — — — 4.00 3.25 4.00 4.00 5.00 6.00
GGG 300 ANSI — — — — — 4.25 3.50 4.31 4.38 5.31 6.50
GGGG Grooved End — — — — — — 3.25 — 4.25 5.00 —
H NPT Body Tapping 0.125 0.125 0.25 0.375 0.375 0.375 0.375 0.50 0.50 0.75 0.75
J NPT Cover Center Plug 0.125 0.125 0.25 0.25 0.25 0.25 0.50 0.50 0.50 0.75 0.75
K NPT Cover Tapping 0.125 0.125 0.25 0.375 0.375 0.375 0.375 0.50 0.50 0.75 0.75
Stem Travel — — — 0.40 0.40 0.40 0.60 0.70 0.80 1.10 1.70
Approx. Ship Weight (lbs) 3 8 8 15 15 15 35 50 70 140 285
* Non Guided Stem
Installation Data
The float control is mounted above the high distance in feet between the valve and the
water level in the tank. The valve is installed float control. CF1-C1
in the line leading to the tank and is A clean independent source of air or water
connected to the float control pilot by tubing. may be used to operate the valve. The
(Min. 3⁄8" tubing) pressure from this independent source must
When line pressure is used to operate the constantly be equal to or greater than
valve, tubing connections are made from the pressure at the valve inlet. The independent
float control pilot to the valve cover, and also source is connected to the float control pilot
to the inlet side of the valve. An X46 Flow in place of the supply line connected to the Stilling
Clean Strainer must be installed in the inlet inlet side of the valve. If the Model 100-01 Well
side of the valve. The control may be under the control of the CF1-C1 is 8" or
installed at any elevation above the valve, larger, auxiliary Hytrol valves may be Flow
providing that the flowing line pressure in psi required. Consult factory for details. X43 or
X46
is equal to, or greater than, the vertical Strainer
Note: We recommend protecting Float Control tubing and valve from freezing temperatures.

Model 124-01 Metric Dimensions (Uses 100-01 Hytrol Main Valve)

B (Diameter) B (Diameter)
J J
100-01 100-01
Threaded & Grooved
Flanged K K
X
H H CC
C (MAX)
(MAX)

Inlet Outlet Inlet Outlet

G E F EE
GG FF GGGG
GGG
Inlet D Inlet DDDD
A DD
DDD Z Y AAAA
AA
AAA

Model 124-01 Dimensions (mm)


Valve Size (mm) 15 * 20 * 25 * 25 32 40 50 65 80 100 150
A Threaded 89 89 130 184 184 184 238 279 318 — —
AA 150 ANSI — — — — — 216 238 279 305 381 508
AAA 300 ANSI — — — — — 229 254 295 337 397 533
AAAA Grooved End — — — — — 216 228 279 318 381 508
B Diameter 80 80 111 143 143 143 168 203 232 292 400
C Maximum 149 149 159 140 140 140 165 192 208 270 340
CC Maximum Grooved End — — — — — 120 146 175 184 236 308
D Threaded — — — 83 83 83 121 140 159 — —
DD 150 ANSI — — — — — 102 121 140 152 191 254
DDD 300 ANSI — — — — — 108 127 149 162 200 267
DDDD Grooved End — — — — — — 121 — 152 191 —
E 23 23 42 29 29 29 38 43 52 81 110
EE Grooved End — — — — — 52 64 73 79 108 152
F 150 ANSI — — — — — 64 76 89 95 114 140
FF 300 ANSI — — — — — 78 83 95 105 127 159
G Threaded — — — 48 48 48 83 102 114 — —
GG 150 ANSI — — — — — 102 83 102 102 127 152
GGG 300 ANSI — — — — — 102 89 110 111 135 165
GGGG Grooved End — — — — — — 83 — 108 127 —
H NPT Body Tapping 0.125 0.125 0.25 0.375 0.375 0.375 0.375 0.50 0.50 0.75 0.75
J NPT Cover Center Plug 0.125 0.125 0.25 0.25 0.25 0.25 0.50 0.50 0.50 0.75 0.75
K NPT Cover Tapping 0.125 0.125 0.25 0.375 0.375 0.375 0.375 0.50 0.50 0.75 0.75
Stem Travel — — — 10 10 10 15 18 20 28 43
Approx. Ship Weight (kgs) 1.4 1.4 6 7 7 7 16 23 32 64 129
* Non Guided Stem
100-01 Pattern: Globe (G), Angle (A), End Connections: Threaded (T), Grooved (GR), Flanged (F) Indicate Available Sizes
124-01
Inches 1
⁄2 ⁄4
3
1 11⁄4 11⁄2 2 21⁄2 3 4 6 8 10 12 14 16 18 20 24
Valve
Selection mm 15 20 25 32 40 50 65 80 100 150 200 250 300 350 400 450 500 600

Pattern G G G, A G, A G, A G, A G, A G, A G, A G, A
Main Valve
100-01 T, F, T, F, T, F, T, F, F, F,
End Detail T T T T
Gr* Gr Gr* Gr Gr Gr*
Suggested Maximum 19 33 55 93 125 210 300 460 800 1800 See the 124-02/624-02 Technical Data Sheet
Flow for larger sizes.
Maximum
(gpm) Intermittent 24 42 68 120 160 260 370 580 990 2250
Suggested Maximum 1.2 2.1 3.5 6 8 13 19 29 50 113
Flow
Maximum
(Liters/Sec) Intermittent 1.5 2.6 4.3 7.6 10 16 23 37 62 142
100-01 Series is the full internal port Hytrol. *Globe Grooved Only

Pilot System Dimensions


124-01Float Valve (Globe)
1
⁄2"- ⁄4"
3
1" 11⁄4"-11⁄2" 2" 21⁄2" 3" 4" 6"
Size
(15 - 20mm) (25 mm) (32 - 40 mm) (50 mm) (65 mm) (80 mm) (100 mm) (150 mm)

2.50" 5.50" 6.00" 6.25" 6.75" 7.25" 8.00" 10.25"


X (140 mm) (150 mm) (160 mm) (170 mm) (180 mm) (200 mm) (260 mm)
(65 mm) Y x
4.25" 4.75" 6.75" 7.00" 7.75" 8.25" 9.50" 10.50"
Y (108 mm) (120 mm) (170 mm) (178 mm) (197 mm) (210 mm) (240) (265 mm)

29.75" 28.50" 28.25" 28.50" 28.75" 29.00" 29.25" 29.25" X


Z (MAX)* (756 mm) (724 mm) (718 mm) (724 mm) (730 mm) (737 mm) (743 mm) (743 mm) Y

124-01Float Valve (Angle)


Z
Z
1 ⁄2"
1
2" 21⁄2" 3" 4" 6"
Size (50 mm) (80 mm) (100 mm) (150 mm)
(40 mm) (65 mm)
6.00" 6.25" 6.75" 7.25" 8.25" 10.50"
X (150 mm) (160 mm) (170 mm) (180 mm) (210 mm) (265 mm) Globe Pattern Angle Pattern
1/2" to 6" 1 1/2" to 6"
6.75" 7.00" 7.75" 7.06" 9.00" 10.00"
Y (170 mm) (178 mm) (197 mm) (179 mm) (230 mm) (254 mm) Notes:
1) *Z (Max.) is with standard float rod.
28.25" 28.50" 28.75" 29.00" 29.25" 29.25"
Z (MAX)* (718 mm) (724 mm) (730 mm) (737 mm) (743 mm) (743 mm) 2) We recommend providing adequate space
around valve for maintenance work
3) Dimensions cover Threaded, Flanged and
Grooved connections.

Pilot System Specifications

Pressure Rating Float Rod


300 psi Max. Standard: Two 12" (300mm) sections PVC rod, When Ordering,
6" (150 mm) & smaller Please Specify
Temperature Rating 12" (300mm) extension increments at additional cost.
Larger counterweight required if float rod length
1. Catalog No. 124-01
Water: to 180°F (82°C) Maximum exceeds 5' (1524mm). 2. Valve Size
Optional: 24" (600mm) stainless steel rod, with 3. Pattern - Globe or Angle
Materials
24" (600mm) extension increments at additional cost. 4. Pressure Class
In contact with operating fluid: Larger counterweight required if float rod length
Nylon-reinforced Delrin,Stainless Steel, exceeds 2' (600mm). 5. Threaded or Flanged
Monel, with Buna-N® seals If maximum temperature exceeds 160°F (71°C) specify 6. Float Rod Material and Length
Float linkage and float rod: Brass and PVC stainless steel float rod.
Base plate: 316 Stainless Steel 7. Float Ball Material
Float: 304 Stainless Steel
Adjustment Range
8. Desired Options
Float Level Differential:
1" min. to 18" max.(25 - 450mm) with PVC rod. 9. When Vertically Installed
53/8" (180mm) diameter.
1" min to 40" max. (25 - 1016mm) with stainless steel rod.
Operating Fluids
Clean liquids or gases compatible with specified materials.

1701 Placentia Ave • Costa Mesa CA 92627 • Phone: 949-722-4800 • Fax: 949-548-5441 • E-mail: info@cla-val.com • www.cla-val.com
CLA-VAL © Copyright Cla-Val • Printed in USA • Specifications subject to change without notice. E-124-01 (R-04/2022)

You might also like